DIN Rail Energy Meter for Single and Three Phase Electrical Systems
USER MANUAL
2016 V4.7
HEFFTRON HFEM-3400CTCOM-MT
Introduction
This document provides operating, maintenance and installation instructions. The unit measures
and displays the characteristics of single phase two wires (1p2w), three phase three wires(3p3w,)
and three phase four wires(3p4w) supplies, including voltage, frequency, current, power ,active and
reactive energy, imported or exported. Energy is measured in terms of kWh, kVArh. Maximum
demand current can be measured over preset periods of up to 60minutes. In order to measure
energy, the unit requires voltage and current inputs in addition to the supply required to power the
product. The requisite current input(s) are obtained via current transformers(CT).
This meter can be configured to work with a wide range of CTs, giving the unit a wide range of
operation. Built-in interfaces provides pulse and RS485 Modbus RTU outputs. Configuration is
password protected.
This unit can be powered from a separate auxiliary (AC or DC) supply. Alternatively it can be
powered from the monitored supply, where appropriate.
Unit Characteristics
The Unit can measure and display:
Line voltage and THD% (total harmonic distortion) of all phases
Line Frequency
Currents, Current demands and current THD% of all phases
Power, maximum power demand and power factor
Active energy imported and exported
Reactive energy imported and exported
Two pulse output indicates real-time energy measurement. An RS485 output allows remote
monitoring from another display or a computer.
-1-
HEFFTRON HFEM-3400CTCOM-MT
Pulse output
This provides two pulse outputs that clock up measured active and reactive energy. The constant
for active energy is 3200imp/kWh(Terminals 11&12). The pulse width for pulse 1(Terminals 9&10)
can be set from the set-up menu.
Start Up Screens
*After a short delay, the screen will display active energy measurements.
Measurements
The buttons operate as follows:
1 Selects the Voltage and Current display screens
In Set-up Mode, this is the “Left” or “Back”
button.
2 Select the Frequency and Power factor display
screens
In Set-up Mode, this is the “Up” button
3 Select the Power display screens
In Set-up Mode, this is the “Down” button
-3-
HEFFTRON HFEM-3400CTCOM-MT
-4-
HEFFTRON HFEM-3400CTCOM-MT
Power
Energy Measurements
-5-
HEFFTRON HFEM-3400CTCOM-MT
Setting Up
To enter set-up mode, pressing the button for 3 seconds, until the password screen
appears.
-6-
HEFFTRON HFEM-3400CTCOM-MT
Setting up is password-protected so you must enter the correct password (default ‘1000’) before
processing.
If an incorrect password is entered, the display will show: PASS Err
To exit setting-up mode, press repeatedly until the measurement screen is restored.
1) Use the and buttons to select the required item from the menu. Selection
does not roll over between bottom and top of list
3) If an item flashes, then it can be adjusted by the and buttons. If not, there
maybe a further layer.
4) Having selected an option from the current layer, press to confirm your selection.
The SET indicator will appear.
5) Having completed a parameter setting, press to return to a higher menu level. The
SET indicator will be removed and you will be able to use the and buttons for
further menu selection.
-7-
HEFFTRON HFEM-3400CTCOM-MT
1) The current digit to be set flashes and is set using the and buttons
2) Press to confirm each digit setting. The SET indicator appears after the last digit has
been set.
3) After setting the last digit, press to exit the number setting routine. The SET indicator
will be removed.
Change password
1
Use the and to
choose the change password option
2-1
Press the to enter the change
password routine. The new password
screen will appear with the first digit
flashing
2-2
Use and to set the
-8-
HEFFTRON HFEM-3400CTCOM-MT
Press to exit the number setting routine and return to the Set-up menu. SET will be
removed
2-1
Press to enter the selection
routine. The current time interval will
flash
2-2
Use and buttons to
select the time required.
2-3
Press to confirm the selection.
SET indicator will appear.
-9-
HEFFTRON HFEM-3400CTCOM-MT
Press to exit the DIT selection routine and return to the menu.
Backlit set-up
The meter provides a function to set the blue backlit lasting time.
1 The backlit lasting time is settable
Default lasting time is 60minutes
For example, if it’s set as 5, the backlit
will be off in 5minutes from the last time
operation on the meter.
Notes: If it’s set as 0, the backlit will
always be on.
2
Press to enter the selection
routine. The current time interval will
flash
The options can be:
0/5/10/30/60/120minutes
Use and buttons to select the time required. Then press to confirm
the set-up,
Supply System
Use this section to set the type of power supply being monitored.
1
From the Set-up menu, use and
2
Press to enter the selection
routine. The current selection will flash
- 10 -
HEFFTRON HFEM-3400CTCOM-MT
3-1
Use and buttons to
select the required system option:
1P2(W),3P3(W) ,3P4(W)
3-2
Press to confirm the selection.
SET indicator will appear.
Press to exit the system selection routine and return to the menu. SET will disappear
and you will be returned to the main Set-up Menu
CT
The CT option sets the secondary current (CT2 1A or 5A) of the current transformer (CT) that
wires to the meter.
1
From the Set-up menu, use and
2 Secondary CT setting
Example: If set the ratio to be 100,it means the primary current equals secondary currentx100
- 11 -
HEFFTRON HFEM-3400CTCOM-MT
PT
The PT option sets the secondary voltage (PT2 100 to 500V) of the Voltage transformer (PT) that
wires to the meter.
1
From the Set-up menu, use and
For example, if set the ratio to be 100,it means the primary voltage equals secondary
voltagex100
Pulse output
This option allows you to configure the pulse output. The output can be set to provide a pulse for
a defined amount of energy active or reactive.
Use this section to set up the pulse output 1—Units: Total kWh, Total kVArh
1
From the Set-up menu, use and
- 12 -
HEFFTRON HFEM-3400CTCOM-MT
2
Press to enter the selection
routine. The unit symbol will flash.
3
Use and buttons to
choose kWh or kVArh.
On completion of the entry procedure, press to confirm the setting and press
Pulse rate
Use this to set the energy represented by each pulse. Rate can be set to 1 pulse per
0.01kWh/0.1kWh/1kWh/10kWh/100/1000kWh.
2
Press to enter the selection
routine. The current setting will flash.
0.01/0.1/1/10/100/1000kWh/kVArh per
pulse
- 13 -
HEFFTRON HFEM-3400CTCOM-MT
procedure, press to confirm the setting and press to return to the main set
up menu.
Pulse Duration
The energy monitored can be active or reactive and the pulse width can be 200, 100 or 60ms.
1-2
Press to enter the selection
routine. The current setting will flash.
On completion of the entry procedure, press to confirm the setting and press
Communication
There is a RS485 port can be used for communication using Modbus RTU protocol. For Modbus
RTU, parameters are selected from Front panel.
- 14 -
HEFFTRON HFEM-3400CTCOM-MT
RS485 Address
2-1
Press button to enter the
selection routine. The current setting
will be flashing.
2-2
Use and buttons to
choose Modbus Address(001 to 247)
On completion of the entry procedure, press button to confirm the setting and press
Baud Rate
1
From the Set-up menu, use
- 15 -
HEFFTRON HFEM-3400CTCOM-MT
2-1
Press to enter the selection
routine. The current setting will flash.
2-2
Use and buttons to
choose Baud rate 2.4k. 4.8k, 9.6k, 19.2k,
38.4k
On completion of the entry procedure, press to confirm the setting and press
Parity
1
From the Set-up menu, use
2-1
Press to enter the selection
routine. The current setting will flash.
2-2
Use and buttons to
choose Parity (EVEN / ODD/ NONE)
Default is NONE.
- 16 -
HEFFTRON HFEM-3400CTCOM-MT
On completion of the entry procedure, press to confirm the setting and press
Stop bits
1
From the Set-up menu, use and
2-1
Press to enter the selection
routine. The current setting will flash.
2-2
Use and buttons to
choose Stop Bit (2 or 1)
On completion of the entry procedure, press to confirm the setting and press
CLR
The meter provides a function to reset the maximum demand value of current and power.
1
From the Set-up menu, use and
buttons to select the reset
option.
- 17 -
HEFFTRON HFEM-3400CTCOM-MT
2
Press to enter the selection
routine. The MD will flash.
Press to confirm the setting and press to return to the main set up menu.
1
use and buttons to
select page “SET sys cont”
2-1
Press to enter Phase A , the
default is Frd (forward)
2-2
use and buttons to
Phase B or C setting pages
- 18 -
HEFFTRON HFEM-3400CTCOM-MT
2
Press to enter the selection
routine. The Frd will flash.
Press to confirm the setting and press to return to the main set up menu.
Specifications
Measured Parameters
The unit can monitor and display the following parameters of a single phase two wire(1p2w),
three phase three wire(3p3w) or four phase four wire(3p4w) supply.
Energy Measurements
Imported/Exported active energy 0 to 9999999.9 kWh
- 19 -
HEFFTRON HFEM-3400CTCOM-MT
Measured Inputs
Voltage inputs through 4-way fixed connector with 2.5mm² stranded wire capacity. single phase
two wire(1p2w), three phase three wire(3p3w) or four phase four wire(3p4w) unbalanced. Line
frequency measured from L1 voltage or L3 voltage.
Three current inputs (six physical terminals) with 2.5mm² stranded wire capacity for connection
of external CTs. Nominal rated input current 5A or 1A a.c. Rms.
Accuracy
Voltage 0·5% of range maximum
Current 0·5% of nominal
Frequency 0·2% of mid-frequency
Power factor 1% of unity (0.01)
Active power (W) ±1% of range maximum
Reactive power (VAr) ±1% of range maximum
Apparent power (VA) ±1% of range maximum
Active energy (Wh) Class 1 IEC 62053-21
Reactive energy (VARh) ±1% of range maximum
Total harmonic distortion 1% up to 31st harmonic
Response time to step input 1s, typical, to >99% of final reading, at 50 Hz.
*Auxiliary Supply
Two-way fixed connector with 2·5mm2 stranded wire capacity.
85 to 275V a.c. 50/60Hz ±10% or 120V to 380V d.c. ±20%. Consumption < 10W.
Pulse Output
The unit provides two pulse outputs. Both pulse outputs are passive type.
Pulse output 1 is configurable. The pulse output can be set to generate pulses to represent total
kWh or kVarh.
The pulse constant can be set to generate 1 pulse per:
0.01 = 10 Wh/VArh
0.1 = 100 Wh/VArh
1 = 1 kWh/kVArh
- 20 -
HEFFTRON HFEM-3400CTCOM-MT
10 = 10 kWh/kVArh
100 = 100 kWh/kVArh
1000=1000 kWh/kVArh
Pulse width: 200/100(default)/60ms
Pulse output 2 is non-configurable. It is fixed up with total kWh. The constant is 3200imp/kWh.
Environment
Operating temperature -25°C to +55°C*
Storage temperature -40°C to +70°C*
Relative humidity 0 to 90%, non-condensing
Altitude Up to 2000m
Warm up time 1 minute
Vibration 10Hz to 50Hz, IEC 60068-2-6, 2g
Shock 30g in 3 planes