Titan ESC User Manual r0
Titan ESC User Manual r0
The Titan Controller with Diffusions Energy Saving software strategy is designed to be a cost effective
multi-purpose digital control unit fulfilling the requirements for either Electric or Hot Water door
curtain and heating unit types.
The control system consists of a Titan FCU-402 controller mounted within the heating unit, and a room
/ wall mounted RDU-4 user interface / display module; connected to the controller via an RJ11 cable.
Features:
Three fan speed settings, plus off, with silent fan speed switching.
BMS controllable of fan speeds.
On/off input for occupancy sensed control; with adjustable run on time, default 15 minutes.
On / Off and Fan speed function are manually selected via the RDU-4 user interface / display module.
Time clock switching or BMS connection can control these functions remotely.
Summer / Winter operating modes are manually switched selected via the RDU-4 user interface /
display module.
Outside temperature sensor or BMS connection can control this function remotely.
Off coil and Return Air sensors are used to control the temperature of the air leaving the supply grill to
maintain the Off Coil set-point value; for Summer or Winter mode.
However when the Return Air temperature reaches that set-point this turns the heating off; unless the
Set-back temperature has been adjusted, when this feature reduces the Off Coil temperature by the
Set-back value rather than turn the heating off completely.
Controller 04-ELEC-6494
Slave Unit:
Controller Address: 3.0
Device ID: 3.2
MAC Address: 3.3
Group Number: 3.4
Slave Unit Input Settings Adjustments: 4.0
Summer / Winter Off Coil Temperature Adjustments: 5.0
Off Coil Return Air Temp Controlled Set-back: 6.0
Summer / Winter Return Air Temp Set-points: 7.0
Reinstating Slave unit Return Air Temp Sensor 8.0
PIR Sensor Configuration: 9.0
PIR Off Time Delay: 10.0
Time Clock Input NO/NC Polarity Change: 11.0
Interface Setting For Fan Speed Control via BMS: 12.0
Summer / Winter Auto Changeover via VO Temp Sensor 13.0
Adjusting Summer / Winter changeover temp Set-points: 14.0
1.0 In order to enter engineering mode press all four buttons on the RDU for 3 seconds.
The RDU screen turns to a green (Maintenance Screen).
Left buttons, , navigate through the menus.
Right buttons, , select the options.
1.1 Adjustment of any kind to control parameters not covered in this document should not be made
without written instruction from Diffusion.
1.2 Adjustment of the factory set Safety run-on times should not be made under any circumstances.
NOTE: Highlighted text identifies the RDU-4 screen colour and specific on screen wording
during each stage of the configuration process.
Each Slave controller Device ID and MAC address needs to be uniquely configured.
The RDU remote control plate will need to be plug into each slave controller for programming.
Following on from section 3.0 each Slave controller requires three Inputs adjusting to Out of Service to
enable referencing of the Master controller.
Note
Stand alone, Master and subsequent Master units on the same network will need to be setup on
separate groups.
Unit ID’s can only be repeated on the same network if they are within a separate group.
Normal energy saving operation is achieved with the standard factory settings for Off Coil temperature
control; Summer temperature set-point is 18.0°C, and Winter temperature set-point is 40.0°C.
These set-points are user adjustable, but should not exceed the limits detailed below:
Normal energy saving operation is achieved with the standard factory setting of 0°C
By adding a set-back temperature this offsets / reduces the Off Coil Temperature by this value when the
Return Air Temperature is reached; maintaining this as minimum Off Coil Temperature.
These set-points are user adjustable, but should not exceed the limits detailed below:
Normal energy saving operation is achieved with the standard factory settings for Return Air
temperature control; Summer temperature set-point is 16.0°C, and Winter temperature set-point is
25.0°C.
It should not be necessary to adjust these set-points; however they are user adjustable, but should not
exceed the limits detailed below:
As standard the Slave unit is fitted with its own return air sensor which is disabled as standard to suit
close coupled operation; should the units be mounted above separate doors the Slave return air
temperature sensor can be reinstated.
The RDU remote control plate will need to be plugged into each slave controller for programming.
The Titan Controller strategy is pre-configured to operate with a PIR sensor using the NO contacts to
enable the unit; shutting the unit off when the contacts are closed.
(This can be modified if required by following the sequence below).
With the PIR fitted this enables the timed delay off function; this is factory set to 15 minutes, and is fully
adjustable to suit installation requirements.
The Titan Controller strategy is pre-configured to operate with a VFC time clock switch; Open contact
shuts the unit OFF and Closed contact turns the unit ON.
(This function can be reversed if required by following the sequence below).
The Titan Controller strategy is pre-configured to adjust fan speed using the Select buttons.
Sequence: Off – Low – Medium – High.
(This can be amended to operate from a 0-10Vdc signal following the sequence below).
(Fan Off = 0V, Low Speed = 3V, Medium Speed = 5V & High Speed = 7V).
The Titan Controller settings require adjustment to allow the Winter / Summer auto changeover
operation, via a 0-10Vdc signal from the VOTS.
Normal energy saving operation is achieved with the standard factory settings for outside temperatures;
OT Summer temperature set-point is 20.0°C, and OT Winter temperature set-point is 15.0°C.
It should not be necessary to adjust these set-points; however they are user adjustable, but should not
exceed the limits detailed below:
PWM 24V
24V TPC - Close High Temperature Cut Out (can be
allocated to any input)
24V TPC - Open
Remote ON/OFF
PWM 0-10V
Volt Free PIR Input
Heat 0-10V
0V
Allocated input on controller
24V Supply
- All Low voltage cables must be segregated from any mains carrying inductors and they should not be run in the
same containment system
- All low voltage cables must not run in close proximately to any mains AC inductive loads such as florescent
fittings and electric motors
Based on the standards for RS485 networks a BACnet MS/TP network layer allows for only a daisy-
chained network configuration, consisting of a single cable routed between controllers. Star and
Ring network topologies are not supported.
The network electrically supports a maximum of 127 nodes, however BUS network size capability is
determined by factors such as network traffic and BMS capabilities and we recommend maximum
network size of 32 or 64 devices.
To comply with the EIA-485 standard, the maximum number of nodes per segment shall be 32 and
any additional nodes will require the use of repeaters. If only Titan controllers are on the MS/TP
network, the number of controllers may be increased but this will depend on the network traffic,
the baud rate being used and the length/route of the cable.
A termination resistor of 120 ohms should be connected at each of the end devices, when a
network is connected to a Router or BMS this becomes one of the end devices. Please check with
the Router/BMS manufacturer if the 120 ohms end of line resistor is fitted internally.
50.1
The above diagram shows a typical 3-wire daisy chain configuration. For all BACnet standard wiring variants please consult ASHRAE wiring standards .
MS/TP allows for only a daisy-chained network configuration, consisting of a single cable routed between controllers.
Star and Ring network topologies are not supported.
The network supports a maximum of 254 nodes; addresses 0 to 127 are valid for both master and slave nodes and
addresses 128 to 254 are valid only for slave nodes.
To comply with the EIA-485 standard, the maximum number of nodes per segment shall be 32 and any additional nodes
will require the use of repeaters. If only Titan controllers are on the MS/TP network, the number of controllers may be
increased to 127 dependent on wiring length as specified below.
A termination resistance of 120 ohms shall be connected at each of the two ends of the segment medium.
The cable used in an MS/TP EIA-485 network should conform to the following specifications:
The cable shield must be connected to Earth ground at the network router end only.
The BACnet commissioning settings can be accessed on the graphical RDU or programming tool by simultaneously
pressing all four buttons. The left buttons can be used to scroll through the menu selections and the right buttons to
change settings. To navigate and access the engineers settings please see supporting documentation.
The following settings need to be commissioned before connection to the MS/TP network:
60.3 - BACnet Device Object Identifier: This setting allows the entry of a unique internet work wide BACnet Device
Object Identifier. With a default setting of 0000000, the device will operate on the local MS/TP network but will not
dynamically bind and initiate I_Am messages. A valid Device Object ID in the range 1 to 4194302 can be entered and
this will set the Device Object Name to “FCU4 DevObjectID”.
60.4 - MAC Address: This setting corresponds to a unique MAC address on the local MS/TP network and can be in the
range 1 to 127.
60.5 - Baud Rate: This setting corresponds to the MS/TP network Baud Rate and should match all other devices on the
same local network. Options are 9600, 19200, 38400 and 76800.
The tables below indicate the Objects supported and the functions they perform.
Outputs
BO1 DO1 Triac1 output (Default TPC Open)
BO2 DO2 Triac2 output (Default TPC Close)
BO3 DO3 Triac3 output (Default PWM)
BO4 DO4 Triac4 output (Default PWM)
BO5 Aux Relay Relay output
AO1 AO1 Analogue output (Default 0-10V valve actuator)
AO2 AO2 Analogue output (Default 0-10V PWM)
MSO1 3-Stage Relay Fan relay
Control Settings
AV400 RAT Summer SP Return air summer set point
0-50DegC
AV401 RAT Winter SP Return air winter set point
0-50DegC
AV402 OT Summer SP Outside air summer set point
-10-40DegC
AV403 OT Winter SP Outside air winter set point
-10-40DegC
AV404 Setback Value Setback temperature for OCT set point
0-50DegC
BV405 RAT Ctrl Option for fan off / setback SP when RAT is at set point
0 – Setback
1- Fan Off
AV406 Max OCT SP Maximum OCT setpoint
0 – 70DegC
AV407 Min OCT SP Minimum OCT setpoint
0 – 70DegC
AV408 Pb Heating proportional band
0 – 25DegC
AV409 It Heating integral time
0 – 20min
AV410 Slew Heating slew rate
0 – 300sec
User Settings
BV500 Mode Mode: 0 – Winter, 1 - Summer
AV501 OCT Summer SP Off coil summer set point
10-70DegC
AV502 OCT Winter SP Off coil winter set point
10-70DegC
User Interface
BV600 Occ Occupancy: 0 – Unoccupied, 1 - Occupied
AV601 Maint Passcode Maintenance passcode (0000)
AV602 Setup Passcode Setup passcode (0000)
BV603 Fan Display Fan display: 0 – Number, 1 - Text
AV604 Backlight Time RDU backlight time after key press
0 – 500sec
BV605 Display DegC RDU displays DegC: 0 – No, 1 - Yes
AV606 SP Adjust OCT setpoint adjust: +/- 100DegC
Misc
BV0 Flash store Set True to store current values to flash memory so that they are
not lost following a reboot
BV1 Build Fail Is set to True if the primary configuration file fails to build. Unit
will run on the secondary configuration until the unit is updated
Triac 1
AV220 TPC time Period (0-360s)
AV222 TPC Accuracy Accuracy (0-10%)
AV223 Heat % Current % position
Triac 2
AV230 PWM time Period (0-360s)
AV233 Heat % Current % position
Control Group
BV1200 Transmit All Set to True to copy the master’s set up to all slave units under
group control
AV1200 Update Period The time between group updates
MSV1200 Group Number The group number (1-64)
MSV1201 Group Type The group type of this device: 1- None, 2 – Slave, 3 - Master
Segmentation Capability:
File Object_Identifier
Object_Name
Object_Type
Description
File_Type
File_Size 0
Modification_Date
Archive
Read_Only
File_Access_Method
1
Present_Value only writable when Out_Of_Service True
2
Dynamic Device Binding when BACnetRecipient ::= CHOICE { device [0] BACnetObjectIdentifier }
Is static device binding supported? (This is currently necessary for two-way communication with MS/TP slaves and
certain other devices.) Yes No
Networking Options:
Router, Clause 6 - List all routing configurations, e.g., ARCNET-Ethernet, Ethernet-MS/TP, etc.
Annex H, BACnet Tunneling Router over IP
BACnet/IP Broadcast Management Device (BBMD)
Does the BBMD support registrations by Foreign Devices? Yes No
Indicating support for multiple character sets does not imply that they can all be supported simultaneously.
www.diffusion-group.co.uk