Ansul CheckFire-210 Detection and Actuation System
Ansul CheckFire-210 Detection and Actuation System
CHECKFIRE 210
Detection and
Actuation System
Features
n Supervised power, detection, release, and communication
circuits
n Display module with LED system status indicators
n Compact size
Branch terminator
(On end of detector)
Checkfire 210
Spot thermal Electric manual DISPLAY module
detectors (Install actuator and bracket
with heat shield and bracket
and bracket)
Detection
circuit
cable
EOL and tees
DEVICE
Display
Visual Cable
Seal
Interface
control
module
Release circuit
drop cable
Electric- Relay Circuit
Release circuit
pneumatic Cable
cable and tees
actuator
Relay
Cable-LEADS
Expellant
gas
cartridge
AGENT
TANK
009269
Typical System Connections Display Module
The CHECKFIRE 210 Display Module communicates with the The CHECKFIRE 210 Display Module communicates with the
CHECKFIRE 210 Interface Control Module (ICM) through the Interface Control Module (ICM) to indicate system status.
display cable using threaded circular connectors. Color-coded Installation within reach of the operator provides easy access
receptacles in the ICM are the central connection point for all to operator controls.
system cables.
Guard
System Cabling: Enables communication and control of Door
components.
n IP67 connectors
n Linear detectors
Delay/Reset/ Push to activate/
n Spot thermal detectors Silence button alarm when lit
button and LED
n Pressure switch (detection circuit #2 only)
Release Circuit: Connects to a maximum of 10 electric- n Dust and water tight (IP67 rated)
pneumatic actuators installed on agent tank expellant gas
cartridges using release circuit cable(s), tee(s), and release n Durable high-strength glass-filled nylon material
circuit drop cable(s). n Surface or bracket mounted
External Power Circuit: Provides a direct connection to the n Two index pins on back for secure mounting
vehicle power source using power circuit cable(s) and a single n Ambient temperature range: -40 °F to 185 °F
fused power circuit cable, when external power is required. (-40 °C to 85 °C)
Auxiliary Output Circuit: Connects to external notification n LED indicators provide notification of system status
devices. (internal sounder matches LED pulse rate)
Display Circuit: Connects display module with ICM. n PUSH To Activate / Alarm When Lit manual-activation
button and LED
Relay Circuit: Provides connection for two independent inter-
nal relay contacts for connection by others. – Provides manual actuation (immediate release)
– Indicates alarm condition
n Guard door with visual seal to protect manual-activation
Detection button
A Linear Detector with an activation temperature rating of n DELAY/Reset/Silence Button
356 °F (180 °C) provides fire detection in the protected area.
–R
estarts Time Delay #1 (TD1) before TD1 sequence
Two twisted spring steel conductors separated by a heat-
expires
sensitive insulator are limited to a minimum bend radius of 2
1/2 in. (64 mm). For easy installation, red color-coded connec- – Resets system (during non-alarm status)
tors match the red connectors of the entire detection circuit. –S
ilences internal sounder during fault conditions and
isolate mode
Spot Thermal Detectors have the temperature rating stamped
on the detector and are color-coded blue for 250 °F (121
°C) and red for 350 °F (177 °C) operating temperatures. The
included retaining nut securely holds the detector in the
required bracket and heat shield.
Interface Control Module (ICM)
The CHECKFIRE 210 Interface Control Module (ICM) is the
central connection point for input/output circuits. Through
communication with the display module, operators receive
continuous system status updates, and operator input
commands go directly to the ICM. Color-coded receptacles
match with color-coded cable connectors providing quick
visual confirmation of proper circuit connections.
Battery
compartment
Isolate
009267
switch
Battery Module
A supervised 3.6 VDC lithium CHECKFIRE 210 Battery
Module provides internal power for the CHECKFIRE 210
System. A connector pigtail extending from the top of the
Color-coded battery connects to the ICM battery cable.
receptaCles
(7 places) 009271
Electric-Pneumatic Actuator
With a focus on ease of installation and safety, the Electric-
The protective battery compartment cover is held in place Pneumatic Actuator reduces system complexity. The
with 4 captive screws. Besides the internal power supply, Protracting Actuation Device (PAD) directly actuates the
the battery compartment includes the battery cable, a electric-pneumatic actuator pin eliminating the need for
mini USB connection port, and the programming inter- pneumatic actuation.
face (button and LEDs). The system programming may be
accomplished with the manual programming button and The re-designed PAD with plug-in spade connectors is
indicator LEDs or by using a computer with the ANSUL easy to install and replace without tools. After plugging the
CHECKFIRE 210 Programmer software communicating PAD into the release circuit drop cable, the cable is hand-
through the mini USB port. tighted to the top of the electric-pneumatic actuator.
Approvals
FM Approved and CE Marked
009268
Ordering Information
Part No. Description
Part No. Description
Display Cables
System Components
439452 Cable, Display, 2 ft (0.61 m)
439560 Display Module, CHECKFIRE 210
439454 Cable, Display, 5 ft (1.53 m)
439564 Mounting Bracket, CHECKFIRE 110/210
439456 Cable, Display, 10 ft (3.05 m)
439561 Interface Control Module, CHECKFIRE 210
439458 Cable, Display, 20 ft (6.10 m)
439569 Electric-Pneumatic Actuator
(normally supplied with agent tanks) 439460 Cable, Display, 30 ft (9.15 m)
439400 Electric Manual Actuator (EMA) 439462 Cable, Display, 50 ft (15.24 m)
440537 Electric Manual Actuator Bracket 439449 Connector, Bulkhead, Display Cable