Usman 2012
Usman 2012
Abstract—The load variation on a power system being unpredictable decoupled; the frequency is dependent on the active power
causes drifts in frequency and voltage from their nominal values while the voltage is highly dependent on the reactive power.
resulting in loss of generation due to tripping of lines and even Thus the control issue in power systems can be decoupled into
blackouts. Frequency and voltage drifts can be minimized and kept
within tolerable limits by automatic generation control. Automatic
two independent problems; one is about the active power and
generation control of a system consists of two parts; load frequency frequency control while the other is about the reactive power
control (LFC) and automatic voltage regulator (AVR). In this paper, and voltage control. As the load on a system is not constant
a simulation study is carried out to understand the operation of load there is a need for Automatic Frequency and Voltage
frequency controller by developing models in SIMULINK. The regulators at the generating stations.
simulation study helps students to understand the principle and As said above any mismatch between generation and
challenges behind load frequency controller. demand causes the system frequency to deviate from
scheduled value. Thus high frequency deviation may lead to
Index Terms –Automatic generation and control (AGC), Tie-line system collapse. This necessitates an accurate and fast acting
power, automatic load frequency control (ALFC), frequency bias
controller to maintain constant nominal frequency. The
tie-line control.
limitations of the conventional controls viz., Integral, PI, and
I. INTRODUCTION PID are slow and lack of efficiency in handling system non
linearities. Much research is ongoing to develop Artificial
The schematic diagram of AGC is shown below. It consists of s Pos T s (3)
speed valve controller, turbine, generator and governor. Any
change in load is reflected on the frequency. The change in For the case with no frequency-sensitive load (D=0),
frequency is compared with a reference speed setting. A steam
valve controller is used to regulate the steam valve thereby ss Po R (4)
increasing the power output from the generators resulting in
matching of generation and demand. As a result the frequency
is restored to the original value. The generators are grouped Where ∆ω is the frequency drift for the step change in load
together to form a coherent network. Based on this the ∆PL. The above equation gives the steady state value of the
network can be classified as single area or two area systems as frequency drift following a load disturbance and it can be
discussed below. inferred that the system’s new operating frequency will be less
than the nominal value due to the load disturbance. However
from the stability point of view, the frequency drift should be
brought down to zero or to a level acceptable for stable
operation and this is done with the help of a secondary loop
shown below.
The ALFC loop shown in Fig. 2(a) achieves the primary goal
of real power balance by adjusting the turbine output ΔPm to
match the change in load demand ΔPo. But a change in load
Fig. 2 (a) Model of a Single Area without secondary Loop [ 2 ] results in a steady state frequency deviation . The
215
restoration of the frequency to the nominal value requires an A typical control area consists of number of generators
additional control loop called the supplementary loop. This coupled together and operating in unison. The combination of
objective is met by using an integral controller which makes turbine-generators with AFC can be grouped under a system
the frequency deviation zero. The ALFC with the referred to as a Control Area. The two areas are connected by
supplementary loop is generally called the AGC. The block means of a tie line with a reactance X12.Then the power
diagram of an AGC is shown figure 2(b). delivered out of area 1 to area 2 will be given as P12. This
power is known as tie line power and is given in (6)
The main requirement in the frequency control is to make-
Δω=0. So the speed changer setting is changed in response to E1 E2
Δω(s) through an integrator. For this purpose the signal from P12 sin 12 (6)
X 12
Δω(s) is fed back through an integrator block (1/s) to adjust
ΔPref so as to bring the frequency to the steady state value. Where X12 X1 X tie X 2 and 12 1 2 Equation
Because of the secondary loop the steady state value of
can be linearized
Δω(s)=0. Thus the integral action results in automatic
adjustment of ΔPref so as to make Δω=0. This action is rightly
dP12
called Automatic Generation Control. P12 12 Ps 12 (7)
d12
120
The transfer function with the integral group is given below
[2], The tie-line power derivation
P12 Ps 1 2
1
1
P ref Po
D
R (5) Consider a change in load PO1 in area1. The steady state
frequency deviation is the same for both the areas. That
B. Two Area system and tie line flow
is 1 2 . Thus, for area1, we have [2]
1) With primary loop
Pm1 P12 Po1 D1 (8)
where, P12 is the tie line power flow from Area1to Area 2;
and for Area 2
Pm1 (10)
R1
Pm2 (11)
R2
1
Fig. 2 (c). Two Area System (without secondary Loop) [ 2 ] D1 P12 PD1 (12)
R
1
The model is similar to the Single Area System but with the 1 D P (13)
R 1 12
1
additional input of P12 . Suppose there is a change in load
( Po ) in area1, the frequencies of the two area systems
settle to a steady state value. Solving for , we get
1 2
216
PO1 PO1 (14) 3) Two Area system (with secondary loop)
1 D 1 D 1 2
R 1 2
1 R2
P011
P12 (15)
1 2
where, 1 and 2 are the composite frequency response
characteristic of Area1 and Area 2 respectively [2]. An
increase of load in area1 by PO1 results in a frequency
reduction in both areas and a tie-line flow of P12 . A
positive P12 is indicative of flow from Area1 to Area 2
while a negative P12 means flow from Area 2 to Area1.
Similarly, for a change in Area 2 load by PO 2 , we have
as
PO 2
(16)
1 2
PO 2 1
and P12 P21 (17) Fig. 2(d).Two Area System (with secondary Loop) [ 2 ]
1 2
ACEs are used as actuating signals to activate changes in the
2) Frequency bias tie line control reference power set points, and when steady-state is reached,
The tie line deviation reflects the contribution of regulation P12 and will be zero. The integrator gain constant
characteristic of one area to another. The basic objective of must be chosen small enough so as not to cause the area to go
supplementary control is to restore balance between each area into a change mode. The block diagram of a simple AGC for a
load generation. This objective is met when the control action two-area system is shown in fig 2(d). Conventional LFC is
maintains frequency at the scheduled value. The
based upon tie-line bias control, where each area tends to
supplementary control should ideally correct only for changes
in that area. In other words, if there is a load change in Area1, reduce the area control error (ACE) to zero. The control error
there should be supplementary control only in Area1 and not for each area tends to consists of linear combination of
in Area 2. For this purpose the area control error (ACE) is frequency and tie-line error [2].
used [2]. The ACE of the two areas are given by
For area 1: ACE1 = P12 1 ACEi nj Pij Ki (20)
For area 2: ACE2 = P21 2
In an interconnected (multi area) system, there will be one
ALFC loop for each control area (located at the ECC of that
area). They are combined as shown in Fig 2(d). for the
interconnected system operation. For a total change in load of
PD the steady state deviation in frequency in the two areas
is given by [2]
PL1 PL1
(18)
1 1 1 2
D1 D2
R1 R2
Where
1 1
1 D1 (15) and 2 D2 (19)
R1 R2
217
III. SIMULATION RESULTS
del PL
10s+0.8
gen +load del ws 1
1 1
-30
0.5s+1 0.2s+1
turbine governor 1/R
Pref
Fig.3 (a) Single area system without secondary loop
Fig.3 (d) Simulation results of single area system with secondary loop
B 1=(D1 + 1/R1)
20
1/R
Fig.3 (b) Simulation results of single area system without secondary loop
del PL
1 1 1
brings about the change in speed which causes the variation in del P12 2
1
s del ws
del Pm2
the graph. From the above plot students will be able to ACE
0.3
Gain 3
1
s
Integrator 2
1 1 1 del w2
understand that the frequency drift will settle down to a finite 0.3s+1 del Pv 0.6s+1 del Pm2 8s+0.9 del w2
value and that the new operating frequency will be lower than 16
B 2= (D2+1/R2)
1 1 1
0.2s+1 del Pv 0.5s+1 del Pm 10s+0.8 del w
2
del PL
del PL Scope
1
del PL
20
1/R
1
7 del w
s
Ki Integrator
Pm1
del Pref
Fig.3 (f) Simulation results of two area system without secondary loop
218
Fig.3 (e) shows the schematic of LFC of 2-area system As seen from the figures the secondary loop causes the return
without the secondary loop while fig.3 (f) shows the of frequency drifts to zero. Students will be able to play with
simulation results. As the two systems are interconnected, the the gain of the secondary loop and observe the change in the
frequency drifts of the two will settle down to equal value dynamic response of the system.
after some oscillations. The mechanical inputs of the two vary
to reduce the mismatch power between the electrical load in Observations: From the above simulation plots it can be
area 1 and the mechanical inputs. It can also be observed that observed that the system experiences frequency drift
area 2 will generate excess power to share the load change in following a load disturbance and it is mainly due to the
area 1. Students can observe the tie-line power flow following mismatch between the electrical load and the mechanical input
a load disturbance in area 1. Compared to the same result with to the turbine. The system oscillation is serious in single area
single area system, students will appreciate the stability system compared to two area system because all the load
improvement with interconnection. change in load is to be met by only one area. Also, using the
secondary loop in both the single area as well as the two area
C. Two area system[with secondary loop] system the change in frequency is brought to zero.
1/R
0.3
1
governor turbine gen +load
loops are very well depicted through simulation models. The
s
del Pm1
Gain 2 Integrator 1 del w1 advantage of interconnection is best understood by comparing
del P12 2
1
s del ws the results of single and two area systems. It can be seen that
Ki Integrator
del Pm2 the oscillations due to change in load in any area is damped
ACE 1
down quickly because of tie line power flow. It can also be
0.3
s
Gain 3 Integrator 2
1
0.3s+1 del Pv
1
0.6s+1 del Pm2
1
8s+0.9 del w2
del w2
observed that the dynamic response is mainly governed by the
governor 2 turbine 2 gen +load 2
secondary loop and hence design criteria of which is
16
extremely vital for efficient implementation.
1/R1
16 .9
B2= (D2+1/R2)
It is envisaged that through these simulations the
Fig.3 (g) Two area system with secondary loop topic of automatic generation and control can be made very
interesting to students thus fulfilling the basic purpose of this
paper.
ACKNOWLEDGEMENT
[2] I. J Nagrath and D. P Kothari Modern power system analysis- TMH 1993.
Pm 2
P12 [3] Sandeep Bhongade, H.O. Gupta, Dr. Barjeev Tyagi ,“Genetic Algorithm
based PID controller for Frequency Regulation Ancillary services”,
International Journal of Engineering Science and Technology
Vol. 2(12), 2010, 6902-6908.
219