Research On Distributed Generation
Research On Distributed Generation
P resently, central power generation, long distance power energy efficiency and reduce costs, it often uses Combined
transmission and power grid interconnection are main Cooling, Heat and Power, (CCHP). This generation
modes of the electrical energy production, transmission and technology is a very promising technology for power
distribution, supplying for more than 90% power loads of the generation from the point of view of energy use, energy saving
world. However, the requires to energy, power supply and environmental [2].
reliability, quality and safety are increasing nowadays. B. The types and technical characteristics of DG
Meanwhile, the world-wide energy crisis, electricity crisis and
In different areas, classification of DG is different.
large scale power outages also exposed the deficiencies of
Generally, there are three classification methods: 1) According
central power generation to a certain extent [1]. For the merits
to the type of technology, DG can be divided into wind power,
of small investment, clean and environment protection, power
solar photovoltaic, small hydropower, fuel cells, micro-
supply reliability and flexible power generation methods,
turbines, and so on; 2) based on the use of primary energy, DG
Distributed Generation (DG) is becoming a hot research
can be divided into renewable energy and Non-renewable
increasingly. Distributed generation combined with
energy; 3) in accordance with the interface to power system,
centralized power generation methods will be the development
DG can be divided into directly associated (electromechanical)
of power systems.
and through the inverter connected system. The technical
characteristics of DG are shown in Table I.
F.H. Guan is M.S. student in power system and its automation at North
China Electric Power University, 102206,Beijing,China (email:
[email protected])
D.M. Zhao is a professor of the School of Electrical Engineering, NCEPU,
102206,Beijing,China (email: [email protected])
X. Zhang is a teacher a Ph.D. in power system and its automation at North
China Electric Power University, 102206,Beijing,China (email:
[email protected])
B.T Shan and Z. Liu are M.S. students in power system and its automation
at North China Electric Power University, 102206,Beijing,China(email:
[email protected] and [email protected])
2
1) All load quantity at the load nodes are greater than the 2) The support effect of DC on voltage in the same node
amount of the DG nodes output, the direction of power flow is should be less than that in a number of nodes, whose
invariable , all the lines losses reduce; penetration Level is the same.
2) At least one load capacity of the nodes is less than the 3) In steady-state case, the transmission power in the feeder
amount of DG output, but the total load quantity of system is reduces and the output of reactive power support, the load
greater than that of the DG, there may be reflux ,and the losses nodes voltages along the feeder are driven up.
of some lines increase ,but the overall line losses may reduce;
E. The impact on Power Quality
3) At least one load capacity of the nodes is less than the
amount of DG output, and the total load quantity of system is DG is built on the basis of power electronics technology. A
greater than that of the DG, if the total quantity of all DG is large number of power electronic converters increase the
less than twice the total load, the impact is the same to the number of non-linear loads, which will cause the waveform
situation. distortion of current, voltage, harmonic pollution of the power
4)Otherwise, the line loss of distribution network will grid. DG affects Power Quality in the two main ways:
increase. 1) voltage flicker. The factors caused voltage flicker by DG
include: a large-scale distributed units start-up, the drastic
C. The impact on power short-circuits current and relay change of the distributed unit output, as well as adverse effects
Although, there are power relays installed in the distribution brought by the interplay of the DC unit output and voltage
network side in many cases, when the distribution network feedback control equipment in system.
operates normally, there isn’t inject grid power, but when 2) The introduction of a large number of harmonics. A large
failure, there will be transient DC current injecting power grid, number of power electronic devices used in DG will inevitably
which increase short-circuit current level of the distribution bring a large number of harmonics to the system; the
network switches and may exceed standard. As a result, when magnitude and order of harmonics are affected by the way, as
high power DC inject power grid, it is important to compute well as power converters work mode.
and analysis advance beforehand in order to determine the Although the introduction of DG can cause voltage flicker
impact level of DC on the short-circuit current of distribution and the introduction of a large number of harmonics, DG also
network. has the potential to improve power quality. When the load
80% of the faults are transient in distribution network, and paralleled power grid is large, DG can be quickly put into use,
the relay protection devices has already existed early ,whose as far as possible to reduce the system failures and improve
design is based on the structure of single power radial the the stability of the entire power grid, thus ensure power
network [4],[8]-[9]. After DC is injected, the structure will quality.
change, so that the size, direction and duration of short-circuit
F. The impact on power market
current will change. Thus, DG produces a greater influence on
the original relay in the distribution network [10]: The deregulation of power industry and the rise of the power
1) the run-time of DC may lead to failure of the relay. market make all kinds of DG ways fair exchange on the
2) The relay may misoperation. The feeder may trip, which is unified and open market transactions to supply the users a
adjacent to the feeder fault and operating normally. variety of choices [13]:
3) It change the fault levels the of distribution network. The 1) Different electricity suppliers;
raise or decrease of the level depends on the amount and types 2) Different periods of electricity;
of operating DC, the raise request to upgrade the switching 3) Different quality of power;
equipment; the decrease could cause problems to over-current 4) Different measurement methods;
protection. Thereby , if the capacity of DC is very large, which 5) Different rate structure;
causes great fault current changes; it must improve its capacity 6) Different payment forms;
and upgrade the circuit protection device. 7) Different management plans in the user side;
8) Own power generation or storage. The open distribution
D. The impact on voltage network introduced the electric power retail market [14]. The
The access of DC causes the structure change, and then competitions brought about business opportunities to company
causes the steady-state voltage change [11]. The original self-install power plants and the DC installed by the users in
voltage regulating scheme may not meet the requests of the retail electricity market. The users are facing with three
distribution network after DC access. Therefore, it must assess options:
the impact of DC on power system voltage, so as to ensure 1) Supply from the electric power grid;
that the applications of DC will not have adverse 2) Own generation, self-sufficiency;
consequences for users in a growing number of cases. The 3) Own generation and sell to grid. According to the
impacts of DG on distribution network voltage are as follows: information from generation competitive market and the
1) DC access will have a significant impact on the feeder’s demand of retail power market, the users can live with their
voltage in distribution networks, related to the size of the DC and let it play a bigger role, resulting in greater efficiency
capacity and the location of distributed power [12]. and supply for themselves or in the vicinity of users heating
and supply service. The establishment of retail electricity
market will radiate the power retail mechanisms. Any form
4
power generation can provide power products to the retail information, which is going to implement. All these are
electricity market as electricity supplier fair exchange in the required re-validation according to DC grid connected
retail market. regulations, and finalize an agreement through the specific DC
grid connected protocol.
G. The impact on traditional control devices
Every traditional control device of distribution network is K. The Ferro-resonance problem.
designed for one-way flow. When DG is accessed to the When the DC connects with distribution network through
system, the direction of each flow relates with the concrete transformers, cable lines, switches and so on, once the
position and capacity of DG. As a result, how to choose a distribution network failures (such as single-phase short-
reasonable DG to adapt the original line, in other words, how circuit) and the switch in system side off, the switch in DC
to transform the existing control devices to adapt to the DG side will be disconnected also, supposing that the DC
will be the real problems we have to face. With further Transformer did not take the load at this time, the reactor of
practical of DG technology, new types of control and interface transformer and the large cable capacitance possibly cause
devices will emerge. The problem how to coordinate different Ferro-resonance and result in over-voltage, may cause large
devices and with the control and setting devices in traditional electromagnetic force, so that the transformer sends out noise
power grid has to be solved. or damage the transformer.
H. Reliability problem. L. Others problem.
Sometimes DC has a negative impact on the reliability, but In addition to the above-mentioned impacts, DC access still
sometimes has a beneficial role; it depends on the Specific exist some other problems to be further studied. For example,
situation and can not be generalized. with the rise of DG, it is necessary to establish appropriate
1) Adverse circumstances: when the big system power laws and regulations and industry Specification[15];
failure, the fuel of some DC will be suspended or auxiliary meanwhile, in order to achieve coordination between the DG
power supply to DC losses, DC outage will still be unable to systems as well as between the DG system and the distribution
upgrade the reliability of power supply at the same time. DC network and the dispatching of DC, it needs to research
can’t cooperate with the relay of distribution network well, so communication technology, GPS technology, DSP technology
that the relay may malfunction, lower reliability. Improper involved as well as the application of the dynamic
installation location, capacity and connection way will measurement and online detection of the power system in DG
deteriorate reliability of the distribution network. , and so on.
2) Favorable situations: DC may partly eliminate the
overload and plug of distribution network; increase the margin IV. THE FUTURE RESEARCH DIRECTIONS OF DG
of transmission distribution network. Under the appropriate Distributed generation, as a cutting-edge research field of
DC disposal and voltage regulator way, DC will help to ease power system, focused on how DG impact on power system.
voltage dip and improve the system voltage regulation In view of this, this paper expatiated on the future research
performance. Specially designed DC make itself keep running direction of DG from the following aspects:
when the big electricity transmission and distribution systems 1) The improvement of existing distribution generation
fail. These are conducive to improve the reliability level of the technologies and research and development of new
system. technology, such as the development of new electrolyte
materials and catalysts and the improvement of the
I. Power-effectiveness problem.
performance of fuel cells, service life, cost performance and so
DC Access may make some equipment idle or back-up. Such on.
as: when the DC runs, distribution transformers and cable 2) For the planning and operation of DG, the installation site,
lines connected with the power distribution system often light capacity and permeation limit of different types of DG in
load because of the small load, some of the equipments in the distribution network should be determined in order to ensure
power distribution system become back-up for DC, so that the the optimization of economy and security; Researching the
cost of distribution network increases and the effectiveness of probabilistic power flow model and algorithm of the DG
the supply bureau decline. Otherwise, the load forecasting of power system and voltage and reactive power control strategy
distribution system may also more difficult. of DG power network, as well as improving and enhancing the
J. The real-time monitoring, control and adjustment problems system's ability to bear the random power; researching
in distribution system coordination control method of the randomized generation
The real-time monitoring, control and adjustment problems power and conventional generation power, and the system’s
in original distribution system were unified complete by best operating point should be found.
power supply department. As the original source of the power 3) The modeling method of high permeability containing DG
grid is a radial network, information collection, the switch would be researched for a variety of ways and features
operation, the corresponding energy scheduling is relatively provided by DG of the power; researching on the change law
simple. The DC Access make it complicated, which needs to of solar and wind energy with the weather conditions;
increase information, such as monitor information or control establishing the models of random energy forecast, generated
5