En Catalog Innofloor 2020 Com

Download as pdf or txt
Download as pdf or txt
You are on page 1of 16

www.innofloor.

eu Radiant underfloor heating system


Underfloor heating system

Why INNOFLOOR 02

Radiant heating explained 04


System advantages 06
System description 08

Our underfloor heating collection 11


PE-Xa EVOH pipe 12

Tacker roll system 13

Castellated board system 14

Innotack & Innostud accesories 16

Manifold cabinets 17

Manifolds 18

Mixing groups 20

Thermal actuators 21

Wiring centers 22

Electric thermostats 24

Sizing, estimates and technical support services 26


Why
INNOFLOOR
underfloor heating?
INNOFLOOR is committed to developing energy efficient heating solutions.
Bringing together the best and latest technologies, we provide design-led solutions
underpinned with unrivalled technical support.

With you every step of the way


We give you all the help and support you need - before, during and after
installation. Whether your project is small, big or complex, we offer a free
estimation and technical support service. With our experience, you can be
assured that our experts will design the most energy efficient solution.

Save time and money with easy fit systems


By combining our INNOPEX PE-Xa pipe, INNOTACK/INNOSTUD pipe fixing systems and
INNOFLOW manifolds, we offer a comprehensive range of underfloor heating
solutions that are quick and easy to install.

Guaranteed to perform
All of our components are manufactured under the ISO9001 Quality Management
System. Our quality assurance team stringently test them at every stage of
production. Thus we can provide a 15 years warranty for a COMPLETE INNOFLOOR
SYSTEM (except the electronic/electric components).

02 03
Underfloor heating explained

INNOFLOOR system advantages


System description

04 05
Reasons to install
Innofloor underfloor heating
At INNOFLOOR we make underfloor heating simple, offering high quality solutions underpinned by
unrivalled technical support. Not only does INNOFLOOR underfloor heating create a better use of space, it is
more efficient and kinder to the environment too.
Radiant surface heating systems require a much lower flow temperature than radiant heating systems, so
there are a number of advantages in terms of thermal comfort and energy savings with a true heating
Reduced heating Durability
system with low temperatures. Due to lower flow temperatures than conventional heating systems, $ bills Much longer service life than
underfloor heating systems can be easily used in conjunction with alternative heat sources, for example conventional heating systems.
Due to the radiant heat of a underfloor
with heat pumps, solar collectors, etc. heating system, there is a much lower
heat exchange between the radiant Healty & Safe
Greater More comfort surface and the walls of the room
living
compared with radiator heating
heating control Like The Sun, Innofloor uses radiant
systems. Thus the room temperature Less moisture and lower air movement
heat to warm objects and the fabric of
Create the perfect comfort zone with can be kept about 2-3°C lower, without may help reduce dust allergens. Plus
the building to create a cosy,
individual or multi room temperature affecting the thermal comfort. This with no hot radiators and sharp edges it
comfortable environment.
control - simple, standard and smart results in a considerable reduction in creates a safer space.
solutions. heating bills by up to 40%. Due to the low movements of the air,
the amount of dust in the inhaled air is
Renewable much smaller and this represents an
More living space heat source improvement in the quality of life,
By removing bulky and unsightly Compatible with conventional and especially for allergic people.
radiators it will free up wall space and renewable heat sources that reduce Less noise In the case of heating with radiators,
give freedom for interior design. environmental impact and cut fuel C r e a t e a r e l a x i n g a n d t ra n q u i l due to the flow of air caused by
All surfaces in the room are freely bills, including air and ground source ambience with no more creaking pipes convection, dust particles are moved
accessible, can be freely arranged and heat pumps and solar panels. or water flow noise. Virtually silent to throughout the room, thus increasing
are suitable for children. run the amount of inhaled dust.

06 07
System description The INNOFLOOR system monitors the individual room temperatures by using thermostats to send signals to the
INNOLINK wiring centers. They control the actuators on each heating circuit and switch off the INNOMIX mixing group
and/or boiler pump, as appropriate. INNOMIX mixes water to maintain a constant floor temperature, which means
that any heat source can be used, including conventional boilers (solid or gaseous fuel), condensing boilers or heat
The INNOFLOOR underfloor heating system mainly uses radiant heat, the most comfortable form of heating, pumps.
providing a uniform distribution of heat throughout the room. By contrast, radiators transfer energy by convection,
heating the air above and around the radiator to a much higher temperature, causing an upward movement of hot air,
so the floor becomes the coldest surface in the room and the ceiling accumulates a large mass of useless hot air.
Underfloor heating, on the other hand, solves this problem by distributing heat evenly exactly where it is needed.
A conventional radiator can also reach temperatures of 75°C, while a underfloor heating system has a much lower Air vent valve

and safer surface temperature between 27-29°C.


Delivery from Boiler
80ºC

Outlet

Wiring center

19 °C
Performs switching of
24 ° zone actuators. switches boiler
C and mixing group on/off
Return to Boiler
60ºC

19 °C

20 °C
20 °C
Inlet
30 °C

Thermostat
(stand-by mode)

Mixing group and

24 °C
24 °C
manifold
16°
C Wiring center
16° Thermostat
C (calling for heat)

Radiators transfer heat to a room largely by convection Underfloor heating systems are simple to install, low
from a hot metal surface. Because the surface area of the maintenance and low operating costs. The room is heated
radiator is small, compared to the volume of the room, a mostly by radiation - the most natural and comfortable
high temperature of the heating medium is required and form of heating, creating a uniform environment without Boiler
Thermostat
the heat is not evenly distributed. hot or cold currents. (calling for heat)
Convection currents also move allergens, dust particles, With a underfloor heating system, the heat is
smoke and germs, which are then distributed around the concentrated at the floor level where it is most needed.
room, contributing to an unhealthy atmosphere.

INNOFLOOR underfloor heating is done by a wet fixing system in which the pipes are laid directly in the screed. The
minimum thickness of the screed must be 45 mm above the top of the pipe. In this system the heat transfer is very
good, however, it is necessary to add screed additive (INNOSET), which reduces the level of air inclusions (thus
increasing thermal conductivity) and makes the screed more elastic to withstand repeated expansions and
contractions.
INNOFLOOR proposes INNOTACK Tacker plates as well as INNOSTUD castellated plates as load-bearing systems.

Wet floor mounting (bottom to top)


Pipe circuit
• Raw floor construction, such as raw concrete, screed, sand filler, or other similar materials. In the case of fillings, a one or more circuits
per zone
protective film must be applied.
• If necessary, an insulating layer with a thickness of 20-30 mm for the raw floor. INNOSET screed
additive
• Insulating layer for damping noises caused by footsteps, etc.
Floor Mixing group and Wiring
• Vapor barrier (polyethylene foil)
• Tacker polystyrene mounting plates, castellated plates manifold Thermostats center Pipe circuit
• Underfloor heating pipes: INNOPEX Pe-Xa pipes with oxygen barrier The hot water is pumped from Individual room thermostats Performs central switching of When heat is switched on the
• Screed the heat source to the manifold control when heating is zone actuators, mixing group entire floor area is warmed to
INNOEDGE and mixed by the mixing group required in each room, as well and boiler as signalled by the between 27ºC - 29ºC, providing
• Floor Edge strip at about 35-40°C(temperature as the temperature required in thermostats. even distribution of heat at
INNOTACK controlled by the thermostatic each room slightly higher than room
Tacker plate
INNOPIN staples
valve). temperature.
Raw floor
INNOPEX
PE-Xa pipe

08 09
Underfloor heating collection
All INNOFLOOR underfloor heating systems are supplied to specifications
and are made of high quality and reliable components.
INNOFLOOR underfloor heating is available for all types of applications:
commercial, industrial, public and residential.
The elements of the system - floor insulation, perimeter insulation,
moisture barrier, fixing system and pipes - are installed and then covered
with the appropriate screed and the final finishes of the floor (marble,
granite, ceramic tiles, parquet, etc.).

Education

Leisuire Churches, Cathedrals


& Retail Museum & Cultural buildings

Healthcare
Government and public buildings

Warehouses
Residential
& industrial buildings

10 11
Underfloor heating system components Underfloor heating system components
Oxygen barrier PE-Xa floor heating pipes Specification
Description Art. code Dimension Type PN Coil lenght Characteristics Value Type Class
022729-018 16 x 2 PE-Xa PN6 100 Liniar dilatation 1,4x10¯⁴ K¯¹ 16x2 C 4/10 bar; 5/8 bar
022729-019 16 x 2 PE-Xa PN6 240 Max. work temperature 95°C 17x2 C 4/6 bar; 5/6 bar
022729-020 16 x 2 PE-Xa PN6 500 Peak temperature (Tmal) 110°C 20x2 C 4/8 bar; 5/6 bar
022729-022 17 x 2 PE-Xa PN6 240 Max. pressure 10 bar 25x2.3 A 4/6 bar; 5/6 bar
022729-023 17 x 2 PE-Xa PN6 500 Roughness 0,007 mm 32x2.9 A 4/6 bar; 5/6 bar
022729-024 20 x 2 PE-Xa PN6 100 Density 0,945 gr/cm²
022729-025 20 x 2 PE-Xa PN6 240 Thermal conductivity 0,38 W/mK
022729-026 25 x 2.3 PE-Xa PN6 50 Min. bending radius 5xd
022729-027 32 x 2.9 PE-Xa PN6 50
Working conditions in constant heating mode
Reticulated PE-Xa (peroxide) pipe, with oxygen barrier, produced according to the European standard EN The maximum parameters of a constant heating system are:
1264-4. - maximum working pressure - 6 bar
The EVOH oxygen barrier is a thin layer of ethyl-vinyl-alcohol copolymer that avoids the permeability of the - sizing temperature - 70 ° C
pipe to oxygen diffusion, eliminating the problem of adding oxygen to the water flow and corrosion of the - service life - 50 years
metal fittings of the installation, thus extending the heating system life. If the application is dimensioned for a service life of less than 50 years, higher temperature/pressure
combinations may be used as follows:
Innopex PE-Xa is a high quality underfloor heating pipe with an EVOH oxygen barrier. Oxygen barrier PE-Xa - maximum working pressure - 6 bar
(peroxide) pipes provide greater flexibility than cross-linked PEX pipes with other cross-linked - design temperature - 90 ° C
polyethylene systems. When using PE-Xa pipes with EVOH in the underfloor heating system, due to the low - service life - 10 years
temperatures of the thermal agent on which the system operates, the EVOH oxygen barrier prevents the
Working conditions in variable heating mode
formation of bacteria and microorganisms that clog circuits and block valves.
Advantages of Pe-Xa pipes: Summer/winter operating mode, variable temperature curves during heating periods - service life 50
• Easy installation. No welding or machining operations are required. years in the case of a high temperature radiator application:
• Flexibility. PE-Xa pipes have greater flexibility than PEX pipes produced by other methods. They can be Operating temperature (°C) Pressure (bar) Service life
bent at low and/or negative temperatures without special tools, saving connections and installation time. 20 6 14 years
• Resistance to high temperatures. INNOPEX pipes are suitable for use at normal operating temperatures 40 6 +25 years
up to 95 ° C and are able to withstand accidental temperatures up to 110 ° C. 60 6 +10 years
80 6 +1 year INNOSET screed additive
• Frost resistance. INNOPEX pipes do not break when water freezes inside. The pipe, due to its flexibility, will Total 50 years
expand. Floor
• High pressure resistance. INNOPEX pipes, due to the manufacturing process, are more resistant to high Tacker system
pressure, exceeding by more than 35% those manufactured using other cross-linking methods. Description
• Corrosion resistance. INNOPEX pipes cannot be attacked by most chemicals (acids, bases, antifreeze, etc.)
and are resistant to any kind of corrosion. INNOTACK thermal insulation Tacker plate with 25
• Higher flow. Due to the smooth inner surface, INNOPEX pipes have a lower pressure drop, thus obtaining a mm thickness, packed in a roll, used for underfloor Edge
heating is made of quality-monitored EPS in strip
higher flow with the same inner diameter. INNOEDGE
• Absence of limestone and other deposits. Also, thanks to its extremely smooth surfaces, such frequent accordance with SR EN13163 and a tear-resistant,
Tacker plate
limescale deposits are avoided. INNOPEX pipes guarantee that the initial flow will be maintained woven, crimped fabric on the top, as a moisture INNOTACK
throughout the use. barrier against screed water. INNOPIN staples
Raw floor
• There is no electrical conductivity. INNOPEX pipes do not generate any galvanic corrosion. The thermal insulation roll is an efficient support for Pe-Xa Pipe
INNOPEX
• No noise. Due to the flexibility a low transmission of sound waves is achieved at even high speeds of water the pipes used in the underfloor heating system, which are fixed with INNOPIN staples.
flow (up to 2.5 m/s). Due to the reinforced material, the exit of INNOPIN staples from the plate is no longer possible. The foil has
• Thermal memory effect. INNOPEX pipes regain their original shape when hot air is applied, which allows a printed grid with a pitch of 5 cm, which makes it possible to easily cut the roll, as well as a simple and
the correction of installation errors and easier repairs on construction sites. quick installation of pipes. The Tacker board has a self-adhesive overlap of about 3 cm on one side.
• Narrow bending radius. The largest bending radius is 10 x the outer diameter of the pipe by manual INNOTACK board is used in underfloor heating systems for thermal insulation, the heat being directed
bending and 5 x the outer diameter of the pipe using the bending guide. towards the interior of the room.
Caution: Hot bending of INNOPEX pipes can damage the EVOH layer. Bend INNOPEX pipes only when cold.
The use of pipe guides is recommended. Art. code Description
023271-035 Innotack Tacker plate 25 - 10 sqm roll
041204-201 Innofoil aluminum insert grid printed foil - 50 m roll

12 13
Underfloor heating system components Underfloor heating system components
Specification
2. castellated boards
Innotack 25 characteristics Value - the special mushroom-shaped shape of the nut
Roll size 1x10 m ensures that the pipes are kept in the mounting
Effective area 10 mp
position
Thermal conductivity 0,038 W/mK
Nominal insulation thickness 25 mm - waste-free laying thanks to the “nub on nub”
Thermal resistence 0,65 m²K/W principle
Fire behaviour E/81 - special design for easy and precise installation
Compressive stress CS(10)80≥80 kPa of pipes
Water absorbtion WL(T) 3 %
- the secure, tight fit of the castellated floor
Dimensional stability DS(N) 2 %
boards makes them suitable for liquid screed
- quick one-person assembly
Castellated boards system - applied film thickness - 0.6 mm
Screed
Description additive INNOSET Specification 023271-036 023271-037 023271-038
Expanded polystyrene insulation panel provided Characteristics INNOSTUD PLUS 11 INNOSTUD PLUS 20 INNOSTUD PLUS 30
with grooves for the installation of INNOPEX Pe-Xa Floor Effective board size 1400x800 mm 1400x800 mm 1400x800 mm
Nominal insulation thickness 11 mm 20 mm 30 mm
pipes with laying pitch from 50mm, 100mm, 150mm, Total thickness 30 mm 39 mm 50 mm
200mm.The advantage of grooved boards for Pipe diameter 14-17 14-17 14-17
underfloor heating is the much easier and safer Laying grid (pipe spacing) 50 mm 50 mm 50 mm
installation of Pe-Xa pipes. The sides of the plates Thermal conductivity 0,034 W/mK 0,034 W/mK 0,034 W/mK
have a special profile through which their assembly Thermal resistance 0,32 m² K/W 0,59 m² K/W 0,88 m² K/W
Edge Fire behaviour per EN13501-1 E E E
is easy and fast, so the screed cannot drain under the strip Packing 13 boards = 14,56 sqm 10 boards = 11,2 sqm 8 boards = 8,96 sqm
plate avoiding the formation of thermal bridges. The INNOEDGE
panel is resistant to compression and high Castellated board Double density INNOSTUD PLUS 30-2 SILENT guarantees
INNOSTUD Pe-Xa pipe
temperatures due to the laminated or applied plastic INNOPEX
optimum impact resistance and ideal noise and sound
high density
film over the polystyrene board. Raw floor insulation ( 28 dB noise reduction)
low density

1. EPS laminated boards


- laminated with 0.34 mm thick PE film which 3. Solotop castellated boards
increases the surface strength; - without EPS insulation
- special nut-feder design for easy and precise - ideal for renovations - low installation heights
installation of pipes - the special mushroom-shaped shape of the nut ensures
- the way of inter-plate connection allows the use of that the pipes are kept in the mounting position
liquid screed - waste-free laying thanks to the “nub on nub” principle
- quick assembly - special design for easy and precise installation of pipes
- INNOSTUD 35 has soundproofing properties - - the secure, tight fit of the castellated floor boards makes
it reduces noise by 26 dB them suitable for liquid screed
- laminated film thickness - 0.34 mm - quick one-person assembly
- film thickness - 1mm
Specification
Characteristics 023271-034 INNOSTUD 20 023271-033 INNOSTUD 35
Board dimension 1030x530 mm 1030x530 mm Specification
023271-028 SOLOTOP
Nominal insulation thickness 20 mm 35 mm Characteristics INNOSTUD PLUS 1 mm
Total thickness 39 mm 57 mm Board dimensions 1450x850 mm
Effective board area (0,5 m²) 1000x500 mm 1000x500 mm Effective board size 1400x800 mm
Laying grid (pipe spacing) 50 mm 50 mm Effective board area 1,12m²
Thermal conductivity 0,035 W/mK 0,040 W/mK Pipe diameter 14-17
Thermal resistance 0,57 m² K/W 0,87 m² K/W Laying grid (pipe spacing) 50 mm
Fire behaviour per EN13501-1 E E Total thickness 20 mm
Packing 15 boards = 7,5 sqm 12 boards = 6 sqm Packing 12 boards = 13,44 sqm

14 15
Underfloor heating system components Underfloor heating system components
Innotack & Innostud accesories 5. Expansion joint profile
1. Tacker staples - article code 010502-022 It is used for surfaces larger than 40 sqm or with a side greater than 8 m for the
INNOPIN Tacker staples allows quick and easy assembly of pipes in underfloor heating realization of joints with permanent elasticity in the heating screed as well as the
systems on Tacker plates with a thickness of at least 25 mm with any configuration of delimitation of screed fields (eg - in the case of doors).
heating pipes (spiral or meander). With a height of 40 mm, they allow the fixing of pipes Characteristics 041204-200
with diameters of 14-16-17-20 mm. Dimensions 80x30x2000 mm
Staples can be installed with the INNOCLIP quick stapler(see page 25). Density 30 kg/m³
6. Tape / connecting element
2. Edge strips Thermoformed film tape for joining INNOSTUD PLUS boards with and without
The edge strips allows the screed toexpand to all sides and must be applied to all external and internal insulation.
walls. This is necessary as screeds with underfloor heating have an increased heat expansion in Characteristics 023271-021
comparison to non-heated screeds. The edge insulation creates an expansion joint between the wall and Dimensions 1400x100 mm
Packing 28 pcs/box
floor to provide the necessary expansion and to avoid the formation of thermal bridges
At the joints, the strips will be overlapped at least 5 cm. 7. Compensating element
Element for door openings and distributor area.
LDPE perimeter tape with self-adhesive tape and LDPE perimeter tape with 100 x 5 mm Characteristics 023271-022
protective foil 150 x 8 mm protective foil Dimensions 1400x200 mm
Packing 14 pcs/box
8. Pipe mount
Allows the pipes to be fixed at 45 degrees.
Characteristics 023270-040 INNOEDGE PLUS 023271-020 INNOEDGE PROJEKT
Characteristics 023271-023
Dimension 150x8 mm 100x5 mm Dimensions 565x70 mm
Roll lenght 25 ml 25 ml Packing 40 pcs/box
Density 20 kg/m³ 20 kg/m³
Thermal conductivity 0,05 W/mK 0,05 W/mK 9. Nub bridge
Thermal resistance 0,5 m²K/W 0,5 m²K/W Allows the pipes fixing in difficult areas or mounting at 45 degrees.
Fire behaviour E E
Acoustic absorption coefficient Characteristics 010502-027
≤ 0,5 ≤ 0,5
Working temperature range -40 ... +80°C -40 ... +80°C Dimensions 90x28 mm
Packing 100 pcs/box
3. Bend formers 90° Art. code Description/Dimensiune țeavă Manifolds cabinets
Bend formers are used to stiffen pipes at the place 010502-030 Bend former INNOBEND 14-18
of the bend at an angle of 90°. It provides optimal 010502-031 Bend former INNOBEND 20-22 Description
change in direction of the pipe without creating 010502-032 Bend former INNOBEND 25 Metal boxes used for wall mounting of manifolds, wiring centers and
010502-033 Bend former INNOBEND 32-34 mixing groups.
folds. Bend formers allow safe and secure outlet of
the pipe from the floor (underfloor heating) to the Made entirely of galvanized steel sheet with 0.8 mm thickness and
manifold cabinet or from vertical surface (wall heating) to the horizontal without the risk of excessive electrostatically painted with white paint.
stress at the bend of the pipe, which could lead to damage. Bend formers are also used to change the INNOBOX boxes are available in two constructive variants:
direction of the pipe at an angle of 90˚ directly on the insulation layer of the surface heating. - fixed
4. Screed additive- article code 060301-097 - adjustable in depth and height.
Professional water-reducing plasticizer, specially produced for screeds that cover underfloor heating
installations. Used in a mixture with cement, the additive gives the screed a higher elasticity, increasing its
malleability and mechanical resistance to vibration through the action of quickly removing the existing air Specification
in the concrete. The mixture ensures better contact with the underfloor heating circuits, optimizing heat
transfer. The screed additive is completely soluble in water, does not contain chlorides and does not fixed adjustable in depth and height
corrode metal structures or equipment. The product bears the CE mark and is manufactured according to Art. code Description Width Height Depth Art. code Description Width Height Depth
023260-058 INNF-0 335 023260-051 INNA-0 335
SR EN 934-2 T2 being compatible with all varieties of cement recommended for the realization of 023260-059 INNF-1 435 023260-052 INNA-1 435
underfloor heating installations. 023260-060 INNF-2 565 023260-053 INNA-2 565
023260-061 INNF-3 715 450 110 023260-054 INNA-3 715 575-665 110-170
The required additive quantity is calculated as follows: 023260-062 INNF-4 795 023260-055 INNA-4 795
- if the final thickness of the screed is known: 0,035 x area [sqm] x screed height[cm] = additive quantity [kg] 023260-063 INNF-5 965 023260-056 INNA-5 965
- if the final thickness of the screed is not known: 0,5 - 1 kg additive per 100 kg of cement 023260-064 INNF-6 1140 023260-057 INNA-6 1140
All dimensions in mm.

16 17
Underfloor heating system components Underfloor heating system components
Stainless steel manifold Specification
Thermal with flowmeters and thermostatic
Mixing group actuator valves - AISI304 stainless steel distributor
- Available from 2 to 13 circuits
- 3/4 ”connection size
- Distributor body connection diameter: 1" FE
- Flow meters with PPA technopolymer housing
- Flow distributor equipped with flow meters with a scale from 0 - 5 l / min, and flow control valves
- Return manifold with thermostatic valves equipped with ABS caps for manual adjustment
(closed / open), suitable for mounting electrothermal actuators with pivot nut connection INNOAKT
M30x1.5
- Maximum operating pressure 6 bar
- Operating temperature 0 ÷ 60 ° C
- Maximum test pressure 10 bar
- Maximum percentage of glycol 30%
- KV factors in wide opening conditions - Supply manifold KV=1.2 / Return manifold KV=2.8
- Supply + return KV = 0.84
The manifolds are installed in cabinets
with mounting brackets - inter-axial
distance = 210 mm provided with rubber
shock absorbers for vibration remittance
and noise elimination.

Wiring center Adjustable manifold cabinet Art. code Description


010502-129 Mounting brackets interaxial=210 mm-2 pcs

Pipe connection to the manifold is done


Stainless steel manifolds with flow meters and thermostatic valves with EUROCON threaded connectors
Description INNOCON.
INNOFLOW distributors / collectors are designed for heating agent
flow distribution and regulation.
Made of stainless steel, in one piece - without welding points or other
Art. code Description
welds, they are ideal for underfloor heating systems.
041204-303 EUROCON conector INNOCON 16x2x3/4"
The particular design of the distributor has a high flow section, with 041204-304 EUROCON conector INNOCON 17x2x3/4"
low pressure drops and therefore low energy consumption in 023273-202 EUROCON conector 20X2x3/4"
circulating pumps. Their large flow section allows the water to reduce
its speed so will not produce noise.

The manifolds are equipped with 3/4 "Eurocon connections with an Art. code Description A B C D E L
interaxial distance of 50 mm and are composed of a flow distributor 030910-321 Innoflow 2 way 1” 3/4” 50 115 90 130
030910-322 Innoflow 3 way 1” 3/4” 50 115 90 180
with flow regulators (flow meters with 0 - 5 l / min adjustment) and 030910-323 Innoflow 4 way 1” 3/4” 50 115 90 230
return collector with thermostatic valves on which thermal actuators 030910-324 Innoflow 5 way 1” 3/4” 50 115 90 280
can be mounted. Distributors / collectors are packed in a cardboard 030910-325 Innoflow 6 way 1” 3/4” 50 115 90 330
box with labels included to identify the connected circuits. 030910-326 Innoflow 7 way 1” 3/4” 50 115 90 380
030910-327 Innoflow 8 way 1” 3/4” 50 115 90 430
030910-328 Innoflow 9 way 1” 3/4” 50 115 90 480
030910-329 Innoflow 10 way 1” 3/4” 50 115 90 530
030910-330 Innoflow 11 way 1” 3/4” 50 115 90 580
030910-331 Innoflow 12 way 1” 3/4” 50 115 90 630
030910-332 Innoflow 13 way 1” 3/4” 50 115 90 680

18 19
Underfloor heating system components Underfloor heating system components
Pumping and control systems Max. working pressure 10 bar
Min. working pressure 0.1 bar
1. Mixing group Max. working temperature 90 °C

The mixing group is an essential component of the INNOFLOOR Safety thermostat


Default set 65°C
system and has a dual function: Contact Normally closed
Protection IP67
a) adjusts the working temperature of the heating agent. Max. temperature 150°C

b) pumps the thermal agent to the collector-distributor and then to


Immersion
the heating circuits. Thermostat head sensor thermometer
Inlet
Factory pre-assembled, the groups are delivered with 2 eccentrics
to allow installation on any type of distributor. Circulator model Wilo Para 25/7 SC
Power supply 230V +10%/-15%, 50/60Hz
Innomix groups are equipped with air vent and drain valve. Center distance 130 mm
Threaded connections G1"1/2
They can be used with both conventional and condensing boilers Temperature range 0-95°C
for underfloor heating. Max. working pressure PN10
Hydronic
valve

Regulation thermostatic head


Max. static working pressure 10 bar
Max. working temperature 120°C
Regulation thermostatic head
Max. differential pressure 1 bar
Max. static working pressure 10 bar Outlet
Regulating range 20-65°C
Max. working temperature 120°C Capillary lenght 2m
Max. differential pressure 1 bar
Regulating range 20-65°C
Delivery from boiler 80°C Return to boiler 60°C
Capillary lenght 2m

3. Thermal actuators
Max. working pressur e 10 bar 40 30 20

Min. working pressu re 0.1 bar Air vent valve


Max. working temperature 90 °C Description
20
30
40


50

60
The thermal actuator is operating the thermostatic valves installed on
Safety thermostat
Default set: 65°C
10

0 80
70

distributors in the heating and / or cooling circuits. The main field of


Contact: Normally closed
Immersion
application is energetic efficiency by temperature control.
Protection: IP67 Delivery from
thermometer
Max. temperature: 150°C boiler - 80°C
Outlet

Thermostat head sensor Specification


- Compact size, small dimensions
Circulator model Wilo Para 25/7 SC - Snap-on installation
Power supply 230V +10%/-15%, 50/60Hz
Center distance 130 mm - 360° installation position
Connections G1"1/2
Temperature range 0-95°C Return to - Patented 100% protection against leaky valves
Max. working pressure PN10 boiler - 60°C
Drain valve
Inlet
- Valve adapter concept
- All around function indicator
Art. code Description
- Maintenance-free, noiseless
023273-022 Mixing group INNOMIX 250KE-Y8763, circulating pump WILO Yonos Para 25/7 - delivered in first open function
- Low power consumption
- High functional safety and long expected service life
2. COMPACT mixing group
- High over-voltage protection
Control unit with connections at the bottom of the Wilo primary circulation pump, - Supply 230 V - 50 Hz
65°C safety thermostat, flow valve, thermostatic valve and hydraulic control valve.
Supply voltage 230V - 50Hz. Characteristics 041204-189 INNOAKT - INN244A 041204-302 INNOAKT KOMFORT
Factory pre-assembled, the groups are delivered with 2 eccentrics to allow Type Normally closed Normally closed
installation on any type of distributor. Voltage 230 V AC, 50/60 Hz DC 12, 24V AC 110,230V 50/60Hz
Operating power 2W 2W
Actuator travel 4 mm 4.0 ± 0.5mm
Closing and opening time aprox. 3 min. 3 - 5 min
Actuating force 100 N ±5% 110 N
Class of protection IP54 IP54
Art. code Description Working temperature 0... +60°C -5... +60°C
Mixing group INNOMIX COMPACT 249KE-065-873, Connection size M30x1,5 mm M30x1,5 mm
023273-301 Conecting cable lenght 1000 mm 800 mm
circulating pump WILO Yonos Para 25/7

20 21
Underfloor heating system components Underfloor heating system components
4. Electronic wiring center Characteristics Innolink Base Innolink Innolink Plus Innolink Komfort
Operating voltage 230 V / ±10% / 50 Hz
Description Voltage supply external voltage source
The INNOLINK wiring center is the central unit for connecting the thermostats in the multi-zone floor Max. power consumption (without consumers) 50 W < 80 W
heating and cooling control systems. Fuse T4AH 5-10 A
Max. thermostats number 6 8
With a minimal investment, the INNOLINK wiring center ensures the connection to all system components
Max. actuators number 15 16
such as. thermostats and thermal actuators. The system components are supplied directly with voltage Pump circuit Closing contact (monopolar switching)/Direct connection via L/N Active (potential)
from the wiring center. All switching commands from the thermostats are transmitted directly to the Boiler circuit Closing contact (monopolar switching) Potential free contact
actuators through the INNOLINK. Pump Switching power 2A, 200 VA inductive
The high quality wiring center from the INNOLINK series are available in 6 and 8 zone versions. For a more control and Switching element Relay
boiler Turn-on delay 2 min
precise adaptation to the specifics of the installation, four versions are available: INNOLINK Basic,
control Follow-up time 2 min, additionally 0-15 min. adjustable with DIP switch 2 min
INNOLINK, INNOLINK Plus and INNOLINK Komfort. Fully equipped, INNOLINK wiring centers include
Control direction NC NC with connected pump NC/NO adjustable with DIP switch NC
extensive functions for energy-efficient operation and increased comfort. Admissible ambient temperature 0...+50°C
INNOLINK gives you the possibility to offer customers an easy installation and maximum comfort by Admissible storage temperature -20...+70°C
adjusting the temperature of the heated surfaces and the environment. Admissible ambient humidity 80%, non-condensing
Connection terminals screw less terminals for 0,2 to 1,5 mm², vertical cable entry
Connection massive NYM-J/NYM-0 (max 5 x1,5 mm²)
Innolink Plus line flexible H03V2V2H2-F / H05V2V2H2-F
Cable strain relief integrated
Standards EN 60730-1, EN 60730-2-9
Protection class II
Protection type IP20
Material ABS
Innolink Komfort - INTCC Weight 380g 394g 410g 510g
Dimensions (HxLxD 90x326,5x52 mm 90x324x52 mm
Electrical connections
For the connection of the voltage supply, the cable sections must be a minimum of 0.75 mm² for 24 V or 1.5
mm² for 230 V. Depending on the voltage version of the base, it is possible to take L1 or L and L2 or N, as well
as the protective conductor, from the base. If no temperature limiter is connected, the connection TB/%H
Art. code Description Zones Pump/boiler control Max. actuators must be bridged (provided for at the factory). The bridge must be removed as soon as a temperature limiter
041204-188 Innolink Base - INN5032-6B 6 -/- 15
is connected. The temperature limiter must be a normally closed contact.
041204-080 Innolink - NN2142-6 6 x/- 15
041204-115 Innolink Plus - INN2052-6 6 x/x 15
041204-301 Innolink Komfort - INTCC 8 x/x 16 The wiring of the thermostats depends on type. For
wiring purposes, please observe the instructions of
the thermostat or of the respective component.
Specification
- Available in 4 versions: Innolink Basic, Innolink, - Clearly structured connection terminals Innolink Komfort 1 - Pump control
Innolink Plus, Innolink Comfort - Pump and boiler control, depending on the model 2 - Boiler control
- Design with 6 and 8 zones - Adjustable follow-up time for pump and boiler 3 - Voltage supply/
- Power supply directly from the mains - 230V control through clump
- Heating and / or cooling equipment - Connection for a temperature limiter or dew point
4 - Fuse
- Simple and intuitive installation and operation sensor
- Signaling the operation status with LEDs - Selectable control direction NC or NO via 5 - Connection for
(Plus and Komfort version) micro-switches (NC: normally closed / NO: thermostat
- Proven cable guide and standard-complying normally open), depending on the model 6 - Status signaling
strain relief, wear resistant - High functional security by leds
- Quick connection clamps, without screws - Maintenance free 7 - Connection for
actuators
The quality of INNOLINK components ensures a simple and intuitive installation, operation and 8 - Cable guide and
maintenance of the entire system. strain relief

22 23
Underfloor heating system components NEW
5. Room thermostats
Description
Electronic room thermostats that use PWM control technology (pulse width modulation) performing a
proportional control with INNOAKT thermal actuators.
Tacker staple gun
Models with analog adjustment or illuminated display, with or without programming clock, without
batteries.
Models for heating-cooling mode with inlet for temperature limiter or dew point sensor. Innoclip Tacker staple gun is made of high quality material
The thermostats can work in conjunction with the wiring centers but can also be connected directly to the guaranteed for long operation and durability. It’s light functional ERGONOMIC HANDLE
thermal actuators. design manufactured from metal/plastic alloy is meant to save time matched to an upright
The quality of Innotroll products ensures easy and intuitive installation, as well as easy use and and effort when fixing pipe onto insulation. Simply load the magazine working position
maintenance of the entire system. of clips onto the tacker gun arm and begin fixing. This product will
Art. code Description
Denumire help reduce the time it takes to lay underfloor heating pipe
041526-321 Analog electronic thermostat INNOTROLL STANDARD without LCD - R20203-10 dramatically.
041526-322 Digital electronic thermostat INNOTROLL STANDARD with LCD - RD20203-10N5 Enhanced by an effective support system (metal foot), large capacity
041526-323 Programmable digital electronic thermostat INNOTROLL CONTROL with LCD - RD25203-60N5
of the guide (up to 4 packages) and an inspection flap enabling easy
041526-325 Programmable digital electronic thermostat INNOTROLL with LCD - HT 3m temperature limiter
041526-326 Programmable digital electronic thermostat SMART INNOTROLL with LCD - HT WiFi 3m temperature limiter removal of a stuck clip.

Programmable digital electronic thermostat INNOTROLL CONTROL with LCD - RD25203-60N5 optionals
Art. code Description MORE CLIPS ON THE GUIDE
041204-082 Temperature limiter - 3m - ES 1000 GREATER EFFICIENCY.
041526-324 Dew point sensor KG-A/1
Extended guide enabling
Analog electronic thermostat Digital electronic thermostat Programmable digital electronic Programmable digital electronic
INNOTROLL STANDARD without LCD INNOTROLL STANDARD with LCD thermostat INNOTROLL CONTROL thermostat INNOTROLL with LCD loading of up to 100 clips.
R20203-10 R20203-10N5 with LCD RD25203-60N5 HT SMART HT WiFi flush
wall mount wall mount wall mount mounted
Art. code Description A(mm) B(mm) C(mm)
010502-025 Tacker staple gun Innoclip Aluminum 942 348 80
010502-026 Tacker staple gun Innoclip Plastic 938 276 82

Specification
- Control algorithm to match heating system - Adjustable temperature reduction HIGH GUIDE
- Smart Start/Smart Stop function - Set point limiter allows you

A
- Intuitive user navigation and operation - Control direction NC/NO selectable to work longer,
- Heating and cooling program settings exact - Frost and valve protection function enables loading
to the day - Heating/cooling (change over) of up to 100
Plastic Aluminum clips
- Target temperature adjustable - High quality modern design
Characteristics R20203-10 R20203-10N5 RD25203-60N5 HT WiFi
Power supply 230 V / ±10% / 50 Hz
Voltage supply via base / mains connection INSPECTION FLAP
Target temperature setting range 10°C -28°C 5°C-30°C 5°C -35°C enabling easy removal
Controlling precision ±0,5°C of stuck clips
Switching power 2A 1A 3A LEG
Included temperature limiter NO NO OPTIONAL YES
OPEN WINDOW function NO
allowing the tacker
YES
Admissible ambient temperature 0°C-50°C C B staple gun to be
Admissible ambient humidity 80% non condensing 85% set in a vertical position

24 25
Sizing, estimates and technical support services

We offer all the help and support you need - before, during and after installation. With the help of a Manifold: Distributor

customized software we offer you free services of sizing and estimating the necessary materials. With our Type:
Manifold set:
Manifold with flowmeters
With ball valve straight valve
experience, you can be sure that our experts will present you the most energy efficient solution. The Secondary side temp. (heating): 44.7 / 32.7°
Manifold cabinet: Concealed manifold cabinet 500x750x160
software goes through all the stages of sizing the works, starting from the installation diagrams, through Feed mass flow: 299.1 kg/h
hydraulic and thermal calculations and ends with prints. The calculation of underfloor heating systems is Min. required differential
pressure: 4.41 kPa
done according to the SR EN 1264 standard , Available differential pressure: 4.41 kPa
Nr. Type To terminal Room label L Effect. Pipe Obtained m ∆p Valve
unit area spc. heating preset (S)
output

m m² mm W kg/h kPa l/min


0.9
1 H/C Fl Bedroom-1-2 Bedroom 86.5 4.4 100/50 288 25.9 0.40
3.4 0.0
1.5
2 H/C Fl Bedroom-1-1 Bedroom 88.6 9.1 100 548 44.5 0.60
2.7 0.1
0.4
3 H/C Fl Bathroom-1-1 Bathroom 50.5 2.3 50 221 23.4 0.20
3.8 0.0
Living 1.8
4 H/C Fl Living room 98.2 8.8 100 532 49.2 0.80
room -1-1 2.3 0.2
Living 1.8
5 H/C Fl Living room 95.9 8.2 100 492 48.4 0.80
room-1-3 2.4 0.2
Living 1.1
6 H/C Fl Living room 94.2 4.2 100/50 273 32.0 0.40
room-1-2 3.1 0.1
3.6
7 H/C Fl Kitchen-1-1 Kitchen 64.0 6.3 100 494 75.8 1.20
0.3 0.4

26 27
Note Note

You might also like