The document provides design data for lighting transformers according to IS 2026. It lists technical parameters such as ratings of 5KVA, 10KVA and 40KVA, voltage ratios, cooling type, insulation class, temperature rise limits, terminal arrangements and other specifications. Key requirements include efficiencies above 97.5%, impedance below 4%, temperature rise below 70°C and taps to provide voltage regulation of +/-2.5%, 5% and 7.5%. Tests are to be witnessed by the client's representative to verify compliance with standards.

Uploaded by

ramkumar meil
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
214 views6 pages

Lighting Transformer

The document provides design data for lighting transformers according to IS 2026. It lists technical parameters such as ratings of 5KVA, 10KVA and 40KVA, voltage ratios, cooling type, insulation class, temperature rise limits, terminal arrangements and other specifications. Key requirements include efficiencies above 97.5%, impedance below 4%, temperature rise below 70°C and taps to provide voltage regulation of +/-2.5%, 5% and 7.5%. Tests are to be witnessed by the client's representative to verify compliance with standards.

Uploaded by

ramkumar meil
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 6

LIGHTING TRANSFORMER DESIGN DATA AS PER IS 2026

TYPICAL LIGHTING TRANSFORMER DESIGN DATA


Sr.No. TECHNICAL PERTICULERS DETAILS
1 EQUIPMENT REFENRECE LIGHTING TRANSFORMER
2 QUANTITY 1
3 RATING 4OKVA
4 PHASES 3
5 TYPE WITH ENCLOUSER
6 NO LOAD VOLTAGE RATIO 415/415v
7 HIGHEST SYSTEM VOLTAGE 1.1KV
8 FREQUENCY 50HZ +/-5%
9 IMPEDENCE <4%
10 VECTOR GROUP D/yn11
11 POLARITY
12 PRIMARY SUPPLY 415V+/- 7.5%
13 SECONDARY SUPPLY 415v+/- 7.5%
14 REF. INDIAN STANDARD IS 2026
15 DESIGN AMBIENT TEMP. 60 degree cent.
16 ALTITUDE ABOVE MSL
17 RELATIVE HUMIDITY 90%
18 ANNUAL RAINFALL
19 ATMOSPHERE To be specified
20 INSTALLATION INDOOR
21 TYPE OF COOLING FORCED COOLING
22 INSULATION LEVEL CLASS F
IMPULSE TEST - HV/LV ---
POWER FREQUENCY HV /LV 3KV
23 TEMPERATURE RISE OF WINDINGS 70 Degree cent above amb.
24 RADIATORS N.A
THRU' TERMINAL BOX (CABLE BOX) /
25 TERMINAL ARRANGEMENT ON PRIMARY OPEN TYPE: BRASS NUT BOLRT ON
TERMINAL PLATE
THRU' TERMINAL BOX (CABLE BOX) /
TERMINAL ARRANGEMENT
26 OPEN TYPE: BRASS NUT BOLRT ON
ON SECONDARY
TERMINAL PLATE
27 EXTRA OUTDOOR N.A
NEUTRAL BUSHING FOR EARTHING To be provided

RATED CURRENT OF BUSHINGS


28 As per design data sheet
ON PRIMARY
RATED CURRENT OF BUSHINGS
29 As per design data sheet
ON SECONDARY
CREEPAGE DISTANCE OF
30 As per design data sheet
INSULATORS AND BUSHINGS
31 ON Load circuit with AUTO VOLTAGE
TAP CHANGER
Regulator

TAPS/STEPS ON PRIMARY TO GET


32 +/-2.5%, +/- 5% & +/- 7.5%
CONSTANT VOLTAGE ON
SECONDARY

33 CABLE/CONDUCTOR SIZE ON PRIMARY As per design data sheet

CABLE/CONDUCTOR SIZE ON
34 As per design data sheet
SECONDARY
35 TYPE OF PAINTING RAL7032
36 SHADE OF PAINT Siemens Grey
37 INSPECTION At our works
38 TESTS TO BE WITNESSED By client’s Rep.
DRAWINGS, DATA &
39
TEST CERTIFICATES
40 RATED kVA 40KVA
41 NO LOAD VOLTAGE RATIO 415/415
42 VECTOR GROUP REFERENCE D/Yn11
43 NO LOAD LOSSES AT RATED VOLTAGE. <1%
44 LOAD LOSSES AT RATED
CURRENT AT 75 DEG.C <1.5%
45 IMPEDANCE VOLTAGE AT RATED kVA,
75 DEG.C AND 50 Hz. <4%
EFFICIENCY (AT 75 DEG.C) AT
45 97.5%
FULL LOAD
46 a) 1.0 P.F.
47 b) 0.8 P.F. (LAG)
48 TOTAL W EIGHT WITH ACCESSORIES.
APPROXIMATE OVERALL DIM. (L x W x
49
H)
LIGHTING TRANSFORMER DESIGN DATA AS PER IS 2026

TYPICAL LIGHTING TRANSFORMER DESIGN DATA


Sr.No. TECHNICAL PERTICULERS DETAILS
1 EQUIPMENT REFENRECE LIGHTING TRANSFORMER
2 QUANTITY 1
3 RATING 10 KVA
4 PHASES 3
5 TYPE WITH ENCLOUSER
6 NO LOAD VOLTAGE RATIO 415/415v
7 HIGHEST SYSTEM VOLTAGE 1.1KV
8 FREQUENCY 50HZ +/-5%
9 IMPEDENCE <4%
10 VECTOR GROUP D/yn11
11 POLARITY
12 PRIMARY SUPPLY 415V+/- 7.5%
13 SECONDARY SUPPLY 415v+/- 7.5%
14 REF. INDIAN STANDARD IS 2026
15 DESIGN AMBIENT TEMP. 60 degree cent.
16 ALTITUDE ABOVE MSL
17 RELATIVE HUMIDITY 90%
18 ANNUAL RAINFALL
19 ATMOSPHERE To be specified
20 INSTALLATION INDOOR
21 TYPE OF COOLING FORCED COOLING
22 INSULATION LEVEL CLASS F
IMPULSE TEST - HV/LV ---
POWER FREQUENCY HV /LV 3KV
23 TEMPERATURE RISE OF WINDINGS 70 Degree cent above amb.
24 RADIATORS N.A
THRU' TERMINAL BOX (CABLE BOX) /
25 TERMINAL ARRANGEMENT ON PRIMARY OPEN TYPE: BRASS NUT BOLRT ON
TERMINAL PLATE
THRU' TERMINAL BOX (CABLE BOX) /
TERMINAL ARRANGEMENT
26 OPEN TYPE: BRASS NUT BOLRT ON
ON SECONDARY
TERMINAL PLATE
27 EXTRA OUTDOOR N.A
NEUTRAL BUSHING FOR EARTHING To be provided

RATED CURRENT OF BUSHINGS


28 As per design data sheet
ON PRIMARY
RATED CURRENT OF BUSHINGS
29 As per design data sheet
ON SECONDARY
CREEPAGE DISTANCE OF
30 As per design data sheet
INSULATORS AND BUSHINGS
31 ON Load circuit with AUTO VOLTAGE
TAP CHANGER
Regulator

TAPS/STEPS ON PRIMARY TO GET


32 +/-2.5%, +/- 5% & +/- 7.5%
CONSTANT VOLTAGE ON
SECONDARY

33 CABLE/CONDUCTOR SIZE ON PRIMARY As per design data sheet

CABLE/CONDUCTOR SIZE ON
34 As per design data sheet
SECONDARY
35 TYPE OF PAINTING RAL7032
36 SHADE OF PAINT Siemens Grey
37 INSPECTION At our works
38 TESTS TO BE WITNESSED By client’s Rep.
DRAWINGS, DATA &
39
TEST CERTIFICATES
40 RATED kVA 10KVA
41 NO LOAD VOLTAGE RATIO 415/415
42 VECTOR GROUP REFERENCE D/Yn11
43 NO LOAD LOSSES AT RATED VOLTAGE. <1%
44 LOAD LOSSES AT RATED
CURRENT AT 75 DEG.C <1.5%
45 IMPEDANCE VOLTAGE AT RATED kVA,
75 DEG.C AND 50 Hz. <4%
EFFICIENCY (AT 75 DEG.C) AT
45 97.5%
FULL LOAD
46 a) 1.0 P.F.
47 b) 0.8 P.F. (LAG)
48 TOTAL W EIGHT WITH ACCESSORIES.
APPROXIMATE OVERALL DIM. (L x W x
49
H)
LIGHTING TRANSFORMER DESIGN DATA AS PER IS 2026

TYPICAL LIGHTING TRANSFORMER DESIGN DATA


Sr.No. TECHNICAL PERTICULERS DETAILS
1 EQUIPMENT REFENRECE LIGHTING TRANSFORMER
2 QUANTITY 1
3 RATING 5KVA
4 PHASES 3
5 TYPE WITH ENCLOUSER
6 NO LOAD VOLTAGE RATIO 415/415v
7 HIGHEST SYSTEM VOLTAGE 1.1KV
8 FREQUENCY 50HZ +/-5%
9 IMPEDENCE <4%
10 VECTOR GROUP D/yn11
11 POLARITY
12 PRIMARY SUPPLY 415V+/- 7.5%
13 SECONDARY SUPPLY 415v+/- 7.5%
14 REF. INDIAN STANDARD IS 2026
15 DESIGN AMBIENT TEMP. 60 degree cent.
16 ALTITUDE ABOVE MSL
17 RELATIVE HUMIDITY 90%
18 ANNUAL RAINFALL
19 ATMOSPHERE To be specified
20 INSTALLATION INDOOR
21 TYPE OF COOLING FORCED COOLING
22 INSULATION LEVEL CLASS F
IMPULSE TEST - HV/LV ---
POWER FREQUENCY HV /LV 3KV
23 TEMPERATURE RISE OF WINDINGS 70 Degree cent above amb.
24 RADIATORS N.A
THRU' TERMINAL BOX (CABLE BOX) /
25 TERMINAL ARRANGEMENT ON PRIMARY OPEN TYPE: BRASS NUT BOLRT ON
TERMINAL PLATE
THRU' TERMINAL BOX (CABLE BOX) /
TERMINAL ARRANGEMENT
26 OPEN TYPE: BRASS NUT BOLRT ON
ON SECONDARY
TERMINAL PLATE
27 EXTRA OUTDOOR N.A
NEUTRAL BUSHING FOR EARTHING To be provided

RATED CURRENT OF BUSHINGS


28 As per design data sheet
ON PRIMARY
RATED CURRENT OF BUSHINGS
29 As per design data sheet
ON SECONDARY
CREEPAGE DISTANCE OF
30 As per design data sheet
INSULATORS AND BUSHINGS
31 ON Load circuit with AUTO VOLTAGE
TAP CHANGER
Regulator

TAPS/STEPS ON PRIMARY TO GET


32 +/-2.5%, +/- 5% & +/- 7.5%
CONSTANT VOLTAGE ON
SECONDARY

33 CABLE/CONDUCTOR SIZE ON PRIMARY As per design data sheet

CABLE/CONDUCTOR SIZE ON
34 As per design data sheet
SECONDARY
35 TYPE OF PAINTING RAL7032
36 SHADE OF PAINT Siemens Grey
37 INSPECTION At our works
38 TESTS TO BE WITNESSED By client’s Rep.
DRAWINGS, DATA &
39
TEST CERTIFICATES
40 RATED kVA 5KVA
41 NO LOAD VOLTAGE RATIO 415/415
42 VECTOR GROUP REFERENCE D/Yn11
43 NO LOAD LOSSES AT RATED VOLTAGE. <1%
44 LOAD LOSSES AT RATED
CURRENT AT 75 DEG.C <1.5%
45 IMPEDANCE VOLTAGE AT RATED kVA,
75 DEG.C AND 50 Hz. <4%
EFFICIENCY (AT 75 DEG.C) AT
45 97.5%
FULL LOAD
46 a) 1.0 P.F.
47 b) 0.8 P.F. (LAG)
48 TOTAL W EIGHT WITH ACCESSORIES.
APPROXIMATE OVERALL DIM. (L x W x
49
H)