Sr. No. DESCRIPTION QTY

Tower-3

B HYDRANT SYSTEM
Installation, Testing and Commissioning of above ground MS ERW
Pipes ( for suction side of pumps) confirming to IS 3589 Gr 330 heavy
grade (200 NB & above) and IS 1239 Pt - I, Heavy grade (150NB &
below), with painting, suitable type of supports, anchor fasteners, bolts
nuts (Galvanised), clamps, "U" bolte, malleable specials such as
Reducers,Tees, elbows (25mm to 50mm forged socket weld type-
3000psi, 65mm and above ERW butt welded fitting), flanges. Including
cutting, Welding, fixing in / on walls, ceiling by using suitable supports
etc, as per drawings. The pipes shall be painted with 2coats of etching
primer & 2 coats of approved paint (Red), MS supports at standard
spacing, anchor fasteners, G.I. bolts and nuts, clamps, rails "U" &
threaded bolt, Including cutting, Welding, fixing in / on walls, ceiling by
using the HI tech / MS supports etc, as per drawings. The quoted rate
shall also include for chasing / chipping walls, making bore holes in walls
1
/ floor and making them good with filler material and finished in cement
morter etc. complete in the opening for pipes passing through walls,
masonry walls as instructed by site engineer. However in case of sealing
the fire walls, application of fire sealant shall be separately paid.

The supports like fabricated structural steel support ,wire steel thread, U
Clamps threaded rods and concrete pedestal shall be included in the
cost. The supports will be hot dip galvanized.

Quoted price shall be inclusive of Supporting arrangement at all levels


& for the metal deck slab shall be with Wedge/ Gripple / Lindapter /
fischer fixing arrangement for TR 60 / TR 80 metal decks.

Paints must have VOC value less than 250 g/l.


a 150mm nominal dia 715
b 100mm nominal dia 120
c 80mm nominal dia 34
d 25mm nominal dia 54.4
Installation, Testing and Commissioning of Landing Hydrants
5
comprising of the following in the Fire duct;
Single headed hydrant valve type -A as per IS 5290, made of stainless
I steel with 63 mm dia instantaneous outlet of 80mm dia fanged 46
inlet ,Blank caps , chain and hand wheels etc complete.
15 M long, 63mm dia RRL hose with instataneuos couplings and Hoses
ii 46
shall be stored inside the hose cabinet.(2 No`s)
iii 1 no. stainless steel short branch pipe with nozzle. 46
Hose reel drum of swinging type with 19mm dia Rubber braided hose of
iv 40M. length with Gate valve (upstream) and Shut off nozzle,25mm Ball 46
valve complete set.
Fire duct Shutter fabricated out of M.S.sheet of 16 swg., and frame,
door shall be 900mm x 1200mm x 150mm min. & fixed with 4 mm thick
Glass, suitable Rubber beedibg and Locking arrangement. Quoted rate
v 46
shall be includes all fasteners etc, and complete shutter shall be powder
coated of approved colour both inside and out side, with locking key &
emergency breaking glass

C FIRE EXTINGUISHERS

Installation, Testing and Commissioning Portable Fire extinguishers of


1
following type & capacity.

ABC powder type fire extinguisher of 2Kgs. Capacity, with initial filling in
brand new cylinder with powder coated finish, fitted with Gun metal
a 20
union,stored pressure type, discharge hose, wall mounting bracket etc.
complete, confirming to IS:15683. (inside lifts, pantry)

Carbon-di-oxide type fire extinguisher of 4.5Kgs. Capacity, with initial


filling in brand new cylinder with powder coated finish, fitted with Gun
b 164
metal union, stored pressure type, discharge hose, wall mounting
bracket etc. complete, (for electrical & utility rooms)

ABC powder type fire extinguisher of 6Kgs. Capacity, with initial filling in
brand new cylinder with powder coated finish, fitted with Gun metal
c union, stored pressure type, discharge hose, wall mounting bracket etc. 216
complete, confirming to IS:15683. (for car parks, lift lobby & refuge
areas)
Water mist type fire extinguisher of 4lts. Capacity, with initial filling in
brand new cylinder with powder coated finish, fitted with Gun metal
d 78
union, stored pressure type, discharge hose, wall mounting bracket etc.
complete, (near every staircase)

Foam type fire extinguisher of 9lts. Capacity, with initial filling in brand
new cylinder with powder coated finish, fitted with Gun metal union,
e 6
stored pressure type, discharge hose, wall mounting bracket etc.
complete, (near D.G room, trafo yard)

Fire buckets round bottom type enamel painted, white inside & Red out
f side and Letter "FIRE" in black with 9 liters cap,out side and handle with 350
mounting bracket.

g Fire bucket stand fabricated by MS angles to install 2 Nos. of buckets. 175

Supply of floor mounting stand for to keep Extinguishers. Stand shall be


h 38
MS powder coated.

C TOTAL FOR PART - C

D SIGNAGES
Providing and installing in position the following type of sign boards
made out of 3mm thick "Opaque" PVC foam board with computer cut,
1
PVC non-reflective self adhesive vinyle painted foam board, complete
with mirror fasteners.

Signage with printed "IN CASE OF FIRE, USE STAIRS UNLESS


INSTRUCTED OTHERWISE" of 1.5cm height letters in red with white
a. 79
back ground.The size of the board shall be 25cm x 30 cm and shall be
fixed at the height of 2 mts. from finished floor near Manual call points.

Floor indentification signage ( ie, GROUND FLOOR …etc.) at each stair


enclosure on every floor, indicating the floor number in words, lettering
b. 79
size shall be 7.5 cm with contrasting colour from back ground.Size shall
be 30cm x 20cm.
Providing and fixing in position the signages " FIRE ORDER" it should
contain the following matter on 3mm thick "Opaque" PVC foam board of
2
computerised cut, PVC non-reflective self adhesive vinyle painted foam
board of 3' x 4'.
A) ALERT THE SECURITY AT SECURITY ROOM BY ACTUATING MANUAL
a 1
CALL POINT LOCATED AT STRATEGIC LOCATIONS.

B) EVACUATE THE OCCUPANTS BY USING FIRE EXITS AND


EMERGENCY EXITS ONLY AND ASSEMBLE AT VARIOUS ASSEMBLY
POITS.

C) IF POSSIBLE TRY TO EXTINGUISH THE FIRE BY USING NEAREST /


SUITABLE PORTABLE EXTINGUISHER OR WATER FROM NEAREST WET
RISER.

D) BE CALM AND DO NOT GIVE ANY ROOM FROM PANIC, WALK, DO


NOT RUN.

E) IF YOU ENCOUNTER SERIOUS DIFFICULTY IN EVACUATION, FLAT


AND TRY TO ATTRACT ATTENTION OF RESCUE TEAM.

ACTION BY SECURITY/RECEPTION UPON RECEIPT OF INFORMATION


b THROUGH FIRE ALARM ORFIRE DETECTORS OR BY USING PUBLIC RO
ADDRESS SYSTEM.

A) ALERT THE OCCUPANTS BY USING PUBLIC ADDRESS SYSTEM.

B) INFORM FIRE CONTROL THROUGH ANY ONE OF THE FOLLOWING


PHONE NUMBERS: 101 / 2251780 / 2251781 / 2251782.

C) REFER EVACUATION PLAN FROM EVACUATING STANDARD PEOPLE.

D) GUIDE THE FIRE FORCE, ON THEIR ARRIVAL TO THE SEAT OF FIRE.

E) IN CASE OF THE CASUALTIES, CALL AMBULANCE BY DIALLING


NUMBER……..

FIRE FIGHTING AGNECY -------------------------------

PHONE : -----------------------
FAX : ----------------------------
Providing and fixing in position the signages indicating each lift bank by
an "alphabetical " letter. The sign indicating the letter of identification
3 shall be posted and maintained at each lift landing & on the side of the 223
stairway door from which egress is made. The numerals & signs shall be
at least 12.5mm high & bold.

D TOTAL FOR PART - D

F AUTOMATIC SPRINKLER SYSTEM


Installation, Testing and Commissioning of M.S. pipes confirming to IS
1239 Pt - I Heavy grade with painting, suitable type of supports, anchor
fasteners, bolts nuts (Galvanised), clamps, "U" bolte, malleable specials
such as Reducers,Tees, elbows (25mm to 50mm forged socket weld
type-3000psi, 65mm and above ERW butt welded fitting), flanges.
Including cutting, Welding, fixing in / on walls, ceiling by using suitable
supports etc, as per drawings. The pipes shall be painted with one coat
of primer & 2 coats of enamel paint using approved type, MS supports
at standard spacing, anchor fasteners, G.I. bolts and nuts, clamps, rails
"U" & threaded bolt, Including cutting, Welding, fixing in / on walls,
ceiling by using the HI tech / MS supports etc, as per drawings. The
quoted rate shall also include for chasing / chipping walls, making bore
holes in walls / floor and making them good with filler material and
1 finished in cement morter etc. complete in the opening for pipes
passing through walls, masonry walls as instructed by site engineer.
However in case of sealing the fire walls, application of fire sealant shall
be separately paid.

The supports like fabricated structural steel support ,wire steel thread, U
Clamps threaded rods and concrete pedestal shall be included in the
cost. The supports will be hot dip galvanized.

Quoted price shall be inclusive of Supporting arrangement at all levels &


for the metal deck slab shall be with Wedge/ Gripple / Lindapter /
fischer fixing arrangement for TR 60 / TR 80 metal decks.

Paints must have VOC value less than 250 g/l.


a 150mm nominal dia 18
b 100mm nominal dia 62
c 80mm nominal dia 137
d 65mm nominal dia 85
e 50mm nominal dia 98
f 40mm nominal dia 98
g 32mm nominal dia 63
h 25mm nominal dia 646

Installation, Testing and Commissioning of M.S 'C' class pipes


confirming to IS:1239 malleable specials extruded type, such as
Reducers, elbows, Fittings(25mm to 50mm socket weld type, 65mm and
above butt welded fitting) flanges. necessary puddle flanges for tank
connection, The pipes shall be anti corrosive wrapping treated.
2
Wrapping material shall consist of three layers of high molecular high
density polyethylene, three layers of polymerized bitumen and one layer
of polyesters (total seven layers).Wrapping is applied over two coats of
anti corrosive rubber modified bituminous primer. (under groung
piping )
a 150mm nominal dia 90

Installation, Testing and Commissioning of PN 25 rated full bore forged


3 brass finished Ball valves with fittings of screwed end type. (for
sprinkler drain pipe at every floor level)
a 50 mm dia 34
b 25mm dia RO

Installation, Testing and Commissioning S.G Iron body butterfly valves


as per BS 2789 (PN-20) slim seal standared lever operated type upto
150mm. Above 150mm it shall be gear operated, with required flanges,
4
nuts, bolts etc. complete. with tamper switch arrangement (for high
level riser). The valves shall be fitted with Lock and Key facility for
monitoring.
a 150mm dia 0
b 100mm dia RO

Installation, Testing and Commissioning CI butterfly valves as per BS


5155 (PN-16) slim seal standared lever operated type upto 150mm.
Above 150mm it shall be gear operated, with required flanges, nuts,
5
bolts etc. complete. with tamper switch arrangement (for low level
riser). The valves shall be fitted with Lock and Key facility for
monitoring.
a 150mm dia 34
b 100mm dia RO
Installation, Testing and Commissioning CI butterfly valves as per BS
5155 (PN-16) slim seal standared lever operated type upto 150mm.
Above 150mm it shall be gear operated, with required flanges, nuts,
5.1
bolts etc. complete. with tamper switch arrangement. The valves shall
be fitted with Lock and Key facility for monitoring. (tapping provision for
bfc sprinklers)
a 150mm dia 36

Installation, Testing and Commissioning conventional Standard


response Sprinkler quartzoid bulb type with 15mm screwed end
connection of 68 deg. C. temperature rating, K-factor of 80 and orifice
6
shall not be less than 6mm. Sprinklers shall be UL Listed / FM approved
with Chrome finished. Color/finish of the cover plate shall be as
approved by the clients / architects.
a Pendent sprinkler for office, basement car park areas 500

Installation, Testing and Commissioning of flow switch on sprinkler


8 distribution header on each floor and shall be connected to fire alarm 34
panel through cable. Flow switch shall be "UL" Listed and FM approved.

Stainless steel corrugated flexible pipe(braided hose) for dropping


sprinklers below false ceiling, pipe shall be 16 bar pressure rating and
9 120
1500 mm long 25 mm dia with union / reducer collar, clamps etc. as
required. It shall be FM approved.

Installation, Testing and Commissioning of Sight glass unit for sprinkler


drain, drain valves, ball valves, check valves, Union etc. complete.Set
10 34
shall be UL Listed. ( 25mm dia. Sight glass , 25 mm dia. Test valve &
50 mm dia. Drain valve with accessories)

Supply and installation of Pressure gauges of suitable range for Sprinkler


11 headers with siphon, Fittings like unions / colors / reducers etc. The dial 34
size shall be 150mm.

F TOTAL FOR PART - F

Total
-3 PROJECT - FPS WORKS
Labour cost
UNIT Rate Amount
Remarks

Rmt
Rmt
Rmt
Rmt
Nos

Nos
Nos

Nos

Nos

Nos

Nos

Nos
Nos

Nos

Nos

Nos

Nos

Nos

Nos
Nos

Nos
Nos

Rmt
Rmt
Rmt
Rmt
Rmt
Rmt
Rmt
Rmt

Rmt

Nos
Nos

Nos
Nos

Nos
Nos
Nos

Nos

Nos

Nos

Nos

Set
Sr. No. Description Blue Star Scope

1 Electric Pump Supply Only

2 Diesel driven pump Supply Only

3 Exhaust Pipe Supply Only

4 MS piping Supply Only

5 MS Fittings Supply Only

Butterfly Valves / stariner / NRV / Ball


6 Supply Only
Valve / Flowmeter / Control Valve

7 Sprinkler/ Curtain Nozzles Supply Only

8 SS Flexible Connection Supply Only

9 Pressure Guage / Pressure Switch Supply Only

10 Fire Extinguishers Supply Only

11 Scaffoldings Supply Only

12 ESIC / PF -

Safety items pertains to works & PPE's &


13 -
Tools & tackels.

14 Labour Compliances i.e PF/ ESI -

15 Contractor Store & Office Area will be allocated

16 Wedge anchor fastners -

Bullet anchor fastners Approved Make :


17
HILTI / FISCHER -

18 Welding rod approved make : ESAB


-
Vendor Scope

Receiving, Lifting & Shifting, Installation & providing foundation bolt, Anti vibration damper and associated GI nut
as per approved drawing / specification
Receiving, Lifting & Shifting, Installation & providing foundation bolt, Anti vibration pad and associated GI nut, bo
exhaust piping as per approved drawing / specification
Receiving, Installation, Testing & Commissioning including providing necessary support system including flange / f
drawing / Specification & Insulation with AL Cladding
Receiving, Installation, hydrotest, Testing & Commissioning including providing necessary support system and appl
(RUST O CAP GREY - ASIAN) and enamel paint (PO Red) as per drawing / Specification.
Receiving, Installation, hydrotest, Testing & Commissioning including providing necessary support system and appl
(RUST O CAP GREY - ASIAN) and enamel paint (PO Red) as per drawing / Specification.
Receiving, Installation, Testing & Commissioning inclusing providing flanges as per ANSI B16.5 C150 and associat
washer, nipple and Rubber gaskets as per drawing / Specification

Receiving, Installation, Testing & Commissioning inclusing providing teflon tape as per drawing / Specification

Receiving, Installation, Testing & Commissioning including providing necessary support system including necessary
washers and fittings as per drawing / Specification
Receiving, Installation, Testing & Commissioning inclusing providing associated nut, bolt & washer nipple and redu
drawing / Specification

Receiving, Installation including providing necessary mounting arrangements as per drawing / Specification

To be returned after works completion

Vendor Scope

Vendor Scope

Vendor Scope

Fabrication and arrangement of store with all necessary equipment & material.

Vendor Scope

Vendor Scope

Vendor Scope
BSL Scope
1.Supply of pumps & accessories
2. Supply of all valves
3. Supply of pipe/fittings.
4. MS C Class pipe
5. MS fittings
6. Scaffolding
7. Constrution Power at location
8. Drinking water.
9. Valves
10. If it is wedge anchor fastners, Supply will be in BSL Scope.
11.Supply of sprinklers/felxibles/ball valves/drain valve etc.

Contractor scope
1. Consumables i.e fastners (HILTI/FISCHER),Hi tech threaded rod,U bolts,U clamps,tesflon tape. If it is wedge anchor fastners
2. Epoxy primer (RUST O CAP GREY - ASIAN) - 1 Coat
3.Enamel Paint (PO Red) - 2 coat (ASIAN)
4.All PPE,Tool & tackels.
5.ESI PF - rate inclusive of ESI PF.
6.ANSI B16.5 Class 150 Flanges/GI Nut bolts/Rubber gasket
7.Installation of pumps/valves/piping.

You might also like