LIM650
LIM650
Disclaimer
The information contained in this document is subject to change without
notice. Precision Digital makes no representations or warranties with respect
to the contents hereof, and specifically disclaims any implied warranties of
merchantability or fitness for a particular purpose.
2
Model PD650 Large Display Process Meter Instruction Manual
Table of Contents
INTRODUCTION ----------------------------------------------------------------------- 7
Features ----------------------------------------------------------------------------------------- 7
Typical Applications ------------------------------------------------------------------------- 8
Ordering Information ------------------------------------------------------------------------ 8
Safety Notice ----------------------------------------------------------------------------------- 9
Specifications-------------------------------------------------------------------------------- 10
Basic Process Meter --------------------------------------------------------------------- 10
Rate/Totalizer/Batch Controller Features ------------------------------------------- 11
Options -------------------------------------------------------------------------------------- 12
Display Functions and Messages ----------------------------------------------------- 15
SETUP AND PROGRAMMING -------------------------------------------------- 17
Overview --------------------------------------------------------------------------------------- 17
Disassembling the Meter----------------------------------------------------------------- 18
Reassembling the Meter ----------------------------------------------------------------- 18
Jumper Configuration--------------------------------------------------------------------- 19
Overview ------------------------------------------------------------------------------------ 19
Jumper Arrays Function and Location ---------------------------------------------- 19
Power Selection ----------------------------------------------------------------------------- 20
Overview ------------------------------------------------------------------------------------ 20
Changing from 115 to 230 VAC Power --------------------------------------------- 20
Labeling Meter for 115 VAC, 230 VAC, or 24 VDC ------------------------------ 20
Connections ---------------------------------------------------------------------------------- 21
Overview ------------------------------------------------------------------------------------ 21
Wiring Instructions ------------------------------------------------------------------------ 22
Terminals Designation -------------------------------------------------------------------- 22
Power Connections ---------------------------------------------------------------------- 23
Signal Connections ---------------------------------------------------------------------- 24
Enter, Acknowledgement, and Reset Total Connections ----------------------- 26
Optional Relays & 4-20 mA Output Terminals ------------------------------------ 26
Isolated 4-20 mA Output Option Connections ------------------------------------- 27
Programming -------------------------------------------------------------------------------- 28
Overview ------------------------------------------------------------------------------------ 28
General Programming Description --------------------------------------------------- 28
ENTER and ACK Functionality ---------------------------------------------------- 28
Five Basic Digit/Display Setting Instructions ----------------------------------- 30
Basic Meter Programming -------------------------------------------------------------- 32
Overview -------------------------------------------------------------------------------- 32
Select Input Signal -------------------------------------------------------------------- 32
Select Calibration Method ---------------------------------------------------------- 33
Initial Calibration With External Source (if Needed) -------------------------- 33
Scale or Calibrate the Meter ------------------------------------------------------- 34
Scale Using Internal Calibration (I-CAL) ------------------------------------ 34
Minimum Input Span (Error Message) ------------------------------------- 35
Calibrate Using External Calibration (E-CAL)------------------------------- 38
Calibrate Using External Calibration (E-CAL)------------------------------- 38
Round Horizontal Tank Calibration Points ---------------------------------- 40
Calibration Error (error) -------------------------------------------------------- 40
Rate Meter Programming --------------------------------------------------------------- 41
3
Model PD650 Large Display Process Meter Instruction Manual
Overview -------------------------------------------------------------------------------- 41
Set Display to Rate (dSPy r) ------------------------------------------------------ 41
Low-Flow Cutoff Programming (Cutoff) --------------------------------------- 42
Totalizer Programming ------------------------------------------------------------------ 43
Overview -------------------------------------------------------------------------------- 43
Set Display for Total (dSPy t) ----------------------------------------------------- 43
Set Rate Time Base (t baSE) ----------------------------------------------------- 44
Set Totalizer Conversion Factor (tot CF) -------------------------------------- 44
Set Totalizer Decimal Point (tot dp) -------------------------------------------- 45
Set Alternating Total/Rate Display ------------------------------------------------ 46
Parameter Combinations Resulting in Error Message (error1 ) --------- 46
Set Point Setup and Programming --------------------------------------------------- 47
Overview -------------------------------------------------------------------------------- 47
Set Relays for Manual or Automatic Reset ------------------------------------- 48
Set Relays for Fail-Safe Operation ----------------------------------------------- 48
Assigning Set Points to Process/Rate or Total (setup) --------------------- 49
Rate or Total, Latching or Non-Latching Relays--------------------------- 50
Programming Internal Total Reset and Delay (DELAy) ------------------- 52
Setting Relays for Pump Alternation (ALtERn) ------------------------------------ 53
Programming Alarm Points and Presets (SEtPtS) --------------------------- 54
Overview----------------------------------------------------------------------------- 54
Set and Reset Points for Process/Rate Alarms---------------------------- 54
Preset Values for Total Set Points -------------------------------------------- 54
Preset Offset Values for Total Set Points (OFFSET)----------------------- 54
Programming Alarm and Preset Values (SEtPtS) ------------------------ 55
4-20 mA Isolated Output Option Programming (output)----------------------- 59
4-20 mA Output Programming Confirmation ------------------------------- 59
Lockout and Display Selection Programming ------------------------------------- 60
Overview -------------------------------------------------------------------------------- 60
Lockout ---------------------------------------------------------------------------------- 60
Display Selection (dSPLAy) --------------------------------------------------------- 61
Alternating Display ---------------------------------------------------------------- 62
Include or Exclude Menu Titles From Menu Scroll------------------------ 63
OPERATION -------------------------------------------------------------------------- 64
Overview --------------------------------------------------------------------------------------- 64
Two Types of Display: Process/Rate and Total ---------------------------------- 65
Basic Meter Operation -------------------------------------------------------------------- 66
Overview ------------------------------------------------------------------------------------ 66
ENTER and ACK Button Operation -------------------------------------------------- 66
Display Peak & Reset Peak Operation (dSPY P & rSEt P) ------------------- 67
Rate Meter Operation---------------------------------------------------------------------- 68
Overview -------------------------------------------------------------------------------- 68
Display Rate (dSPy r) --------------------------------------------------------------- 68
Low-Flow Cutoff (CutoFF) ---------------------------------------------------------- 68
Totalizer Operation------------------------------------------------------------------------- 69
Overview ------------------------------------------------------------------------------------ 69
Display Total (dSPy t) --------------------------------------------------------------- 69
Total Conversion Factor (tot CF) & Time Base (t bASE) ----------------- 69
Applications Using Total Conversion Factor and Time Base -------------- 70
Totalizer Reset------------------------------------------------------------------------- 71
Resetting Total Using the ENTER Button ----------------------------------- 71
Resetting Total via External Contact Closure ------------------------------ 71
4
Model PD650 Large Display Process Meter Instruction Manual
Resetting Total Automatically via User Selectable Preset -------------- 71
Relays Operation --------------------------------------------------------------------------- 72
Overview ------------------------------------------------------------------------------------ 72
Relays Auto Initialization ---------------------------------------------------------------- 72
Fail-Safe Operation ---------------------------------------------------------------------- 72
Front Panel LEDs ------------------------------------------------------------------------- 73
Acknowledging Relays ------------------------------------------------------------------ 75
Simple On/Off Control with 100% Deadband Operation ------------------------ 76
Manual Batch Control Operation ----------------------------------------------------- 78
Automatic Batch Control Operation -------------------------------------------------- 79
Delay on Release (delay) ------------------------------------------------------ 80
Priority Batch Programming or Quick Presets ------------------------------------- 80
Batch Control with Varying Batch Sizes -------------------------------------------- 80
Pump Alternation Control --------------------------------------------------------------- 81
Pump Alternation Typical Application -------------------------------------------- 81
Switching Inductive Loads -------------------------------------------------------------- 82
AC and DC Loads--------------------------------------------------------------------- 82
Low Voltage DC Loads -------------------------------------------------------------- 82
4-20 mA Output Operation--------------------------------------------------------------- 83
Overview ------------------------------------------------------------------------------------ 83
Lockout and Display Selection Operation ----------------------------------------- 83
Overview ------------------------------------------------------------------------------------ 83
Low Voltage Detector --------------------------------------------------------------------- 83
INSTALLATION ---------------------------------------------------------------------- 84
Wall Mounting Dimensions-------------------------------------------------------------- 84
Panel Mounting Instructions------------------------------------------------------------ 85
OPTION CARD REMOVAL & INSTALLATION ------------------------------ 87
PROGRAMMED PARAMETER SETTINGS ---------------------------------- 89
Diagnostic Feature (dIA9) --------------------------------------------------------------- 93
Overview ------------------------------------------------------------------------------------ 93
Operation ----------------------------------------------------------------------------------- 93
OTHER PRECISION DIGITAL PRODUCTS ---------------------------------- 94
5
Model PD650 Large Display Process Meter Instruction Manual
List of Figures
6
Model PD650 Large Display Process Meter Instruction Manual
INTRODUCTION
This instrument is an analog input process meter with flow rate, totalizer, and
batch control capabilities housed in a rugged, die-cast aluminum NEMA 4X
enclosure. It accepts the common process signals such as 4-20 mA, 0-5 VDC,
1-5 VDC, and 0-10 VDC. It displays these signals in engineering units on a 2.3"
high 4½ digit LED display. The meter also provides two isolated 24 VDC power
supplies to drive both the input and output loops. Options include up to 4 relays
for alarms or batch controlling as well as an isolated 4-20 mA transmitter output.
Features
This model contains several features of interest:
• Rate Display in Units per Day, in Addition to Second, Minute, and Hour
7
Model PD650 Large Display Process Meter Instruction Manual
Typical Applications
Level:
Sump Pump Control
Water Tank Level
Round Horizontal Tank Volume Measurement
Well Draw-Down
Lift Station Control
Flow:
Square Root Extraction from Differential Pressure Transmitter
Programmable Exponent for Weirs and Flumes
Rate, Total, and Batch Control
Pressure:
Compound Pressure
High Pressure Alarms
Temperature:
Heat Exchanger Display and Alarm
Boiler Temperature Monitoring
Gas Turbine Combustor Alarm
Condenser Temperature Indicator
Ordering Information
115/230 VAC 24 VDC Options Installed
Model Model
PD650-N PD650-2-N No Options
PD650-34 PD650-2-34 2 Relays
PD650-35 PD650-2-35 4-20 mA Output
PD650-36 PD650-2-36 2 Relays + 4-20 mA Output
PD650-37 PD650-2-37 4 Relays
PD650-38 PD650-2-38 4 Relays + 4-20 mA Output
Accessories
PDA6504 Panel Mounting Kit**
8
Model PD650 Large Display Process Meter Instruction Manual
Safety Notice
!
CAUTION: Read complete WARNING: Risk of electric shock.
instructions prior to installation and
operation of the unit.
WARNING
Hazardous voltages exist within enclosure. Installation and service should
be performed only by trained service personnel.
AVERTISSEMENT
Les pièces à l'intérieur du boîtier portent des tensions dangereuses. Seules
des personnes qualifiées et bien entrainées devraient entreprondre
l'ótalonnage et la maintenance.
9
Model PD650 Large Display Process Meter Instruction Manual
Specifications
Except where noted all specifications apply to operation at +25°C.
10
Model PD650 Large Display Process Meter Instruction Manual
PEAK HOLD Captures the maximum or peak process/rate and displays it via
MAX (DISPLAY PEAK) the front panel ENTER button (Dspy p)
PEAK HOLD OR Front panel flashing “R” LED
MAX INDICATION
LOCKOUT Jumper JP1 labeled “LOCK” restricts modification of
programmed settings.
NON-VOLATILE All programming values are stored in non-volatile memory for a
MEMORY minimum of ten years if power is lost.
POWER OPTIONS AC power: 115 or 230 VAC (field select) ±10%, 50/60 Hz, 12 VA
DC power: 22-28 VDC; 12 watts maximum
NORMAL MODE 64 dB at 50/60 Hz
REJECTION
ENCLOSURE Die-cast aluminum, NEMA 4X, modified specifically for PDC;
four holes for ½" conduit provided at base, 3 plugs provided.
ENVIRONMENTAL Operating temperature range: -20 to 65°C
Storage temperature range: -40 to 85°C
Relative humidity: 0 to 90% non-condensing
CONNECTIONS Removable screw terminal blocks, accept 22 to 12 AWG wire
MOUNTING Enclosure contains four ¼" holes for wall mounting. Panel
mounting kit available
OVERALL 4.9" x 14.3" x 3.2" (125 mm x 362 mm x 81 mm)
DIMENSIONS
WEIGHT 7.0 lbs (3.2 kg)
WARRANTY 2 years parts & labor
EXTENDED 1 or 2 years, refer to the Price List for details.
WARRANTY
LOW-FLOW Any input below the low-flow cutoff value will result in a display
CUTOFF of zero. May be set from 1 count to 100% FS, user selectable.
To disable low-flow cutoff, program cutoff value to zero.
Totalizer is based on rate display. So, inputs below the low-
flow cutoff value will not affect the totalizer.
ALTERNATING Display may be programmed to alternate between rate and
DISPLAY total every 10 seconds.
11
Model PD650 Large Display Process Meter Instruction Manual
TOTALIZER Up to four, user selectable under setup menu Setup. Any set
PRESETS point can be assigned to total and may be programmed
anywhere in the range of the meter.
PRESET OFFSET Relays assigned to total can be programmed to trip at any
point below the next relay’s preset value.
PROGRAMMABLE If the meter is programmed to reset total to zero automatically
DELAY ON when the highest preset is reached, then a delay will occur
RELEASE before the total relays reset. This delay can be programmed
anywhere from 1 to 999 seconds.
PRIORITY BATCH This feature allows the user to quickly change preset values
PROGRAMMING without going into the main menu by holding the ENTER
button for more than 3 seconds.
TOTAL RESET Via front panel ENTER button, external contact closure, or
automatically via user selectable preset value.
TOTAL RESET Meter may be programmed so total cannot be reset from front
LOCKOUT panel.
Options
Relays
RATING 2 or 4 SPDT (Form C); rated 2 A @ 30 VDC or 2 A @
1
250 VAC resistive load; /14 HP @ 125/250 VAC for inductive
loads. Built-in suppression.
ASSIGN TO Any relay may be assigned to process/rate or total.
PROCESS/RATE
OR TOTAL
BUILT-IN A built-in suppressor (snubber) to prolong the life of the relays
SUPPRESSION protects each relay contact. The suppressor provides a degree
of protection against electrical noise caused by inductive
loads. Suppressor value: .01 µF/470 Ω, 250 VAC.
DEADBAND 0-100% of full scale, user selectable
HIGH OR LOW User may program any alarm for a high or low trip point.
ALARM
RELAY Latching or non-latching
OPERATION
12
Model PD650 Large Display Process Meter Instruction Manual
13
Model PD650 Large Display Process Meter Instruction Manual
14
Model PD650 Large Display Process Meter Instruction Manual
-19999 Underrange Indicates the input signal is below the negative range of
the meter.
29999 Overrange Indicates the input signal exceeds the full-scale range of
the meter.
ALtErn Alternate Sets any relay pair for pump alternation control.
CutoFF Low-flow cutoff Sets meter to display zero below programmed cutoff
point.
Day Day Sets time base to display rate in units per day.
Delay Delay Sets delay on release from 1 to 999 seconds for internal
total reset.
DspLAy Display Sets menu title scroll, selections are activated with
lockout jumper installed.
E rSt External total reset Indicates total reset was set to externally reset total to
zero via the ENTER button or an external switch closure.
E-CAL External calibration Sets meter to calibrate using a calibrated signal source.
Hour Hour Sets time base to display rate in units per hour.
I or e Internal or external Sets highest preset for internal or external total reset.
I rSt Internal total reset Indicates highest preset was set to internally reset total to
zero when preset value is reached.
I-CAL Internal calibration Sets meter for internal calibration to scale meter without
applying an input signal.
15
Model PD650 Large Display Process Meter Instruction Manual
Display Parameter Description/Comments
LInear Linear input Indicates linear input was selected.
min Minute Sets time base to display rate in units per minute.
OFFSET Preset offset Sets preset offset value (Relay n trips at a point below
Relay n+1 preset value).
Pro9 r Programmable root Sets exponent for special root extraction used for weirs
and flumes.
Rset P Reset peak Erases peak value from memory and captures a new
peak reading.
SCALE Scale Scales meter using internal calibration for desired display
(Signal source not required).
SeC Second Sets time base to display rate in units per second.
SetPtS Set points Sets alarm set /reset points and total presets (relays are
optional).
t bASE Time base Sets meter with correct time unit factor (second, minute,
hour, or day).
Tot CF Totalizer conversion Sets multiplier factor to display total in any engineering
factor unit.
Tot dp Total decimal point Sets the decimal position for the totalizer.
16
Model PD650 Large Display Process Meter Instruction Manual
17
Model PD650 Large Display Process Meter Instruction Manual
18
Model PD650 Large Display Process Meter Instruction Manual
Jumper Configuration
Overview
Before programming the meter, it is necessary to configure three jumper arrays.
The jumper arrays are used for setting the type of input signal (4-20 mA, 0-5 V,
or 0-10 V); locking out the programmed settings, enable relay acknowledgement
(ACK), and setting relay fail-safe operation.
19
Model PD650 Large Display Process Meter Instruction Manual
Power Selection
Overview
Power Selection involves the following:
1. Changing to 230 VAC power if needed. Factory default is 115 VAC.
2. Labeling the meter as to how it will be powered: 115 VAC, 230 VAC, or
24 VDC. Meters powered from 24 VDC are labeled as such at the factory.
Note: Meters ordered to operate from 24 VDC do not require any special setup,
this option is not field selectable.
All AC powered meters are shipped from the factory set for
! 115 VAC power. Do not apply 230 VAC without first setting up the
meter to accept this voltage.
Disconnect power prior to performing the following procedures.
! The meter is field selectable for either 115 VAC or 230 VAC power.
Changing the voltage selection involves the removal of the front
cover and the Display Board, then selecting 115V or 230V on
switch S1 located on the Main Board.
Observe polarity for DC powered meters. Applying voltage with
! reverse polarity may damage the meter.
20
Model PD650 Large Display Process Meter Instruction Manual
Connections
Overview
The following connections are made to removable screw terminal connectors
supplied with each meter:
Power Connections
Signal Connections
Enter, Acknowledgement, and Reset Total Connections
Relays Connections
4-20 mA Output Connections
21
Model PD650 Large Display Process Meter Instruction Manual
Terminals Designation
Terminal Description Terminal Description
L1, L2, Gnd AC input power CM Common (return) for
AK, EN, & R
V+, V- DC input power S+, S- Input signal
22
Model PD650 Large Display Process Meter Instruction Manual
Power Connections
!
Refer to Changing from 115 to 230 VAC Power, page 20, to make sure meter
is set up to accept proper voltage before applying power.
!
Disconnect power to the meter before making any connections.
!
Do not connect Power or Earth Ground to any unused or CM terminals.
Connecting 230 VAC with 115 VAC selected will result in damage to the
instrument as well as endanger personnel. Connecting AC power when meter is
set up for DC power will result in damage to the instrument as well as endanger
personnel.
Connect power to terminals L2(V-) and L1(V+). Connect Earth Ground to screw
terminal marked with Ground symbol on the enclosure’s base (see Figure 3).
23
Model PD650 Large Display Process Meter Instruction Manual
Signal Connections
Signal connections are made to a 10-position connector J1 on the Main Board.
This connector also includes connections for Enter, Acknowledgement, Reset
Total, and Common. Refer to Figure 3 for location of J1.
24
Model PD650 Large Display Process Meter Instruction Manual
3-Wire
Transducer
25
Model PD650 Large Display Process Meter Instruction Manual
ACK switch
ENTER switch
J1 PD375
PD376
J3 PD374
PD378
PD377
J4
Figure 13. Input Loop Powered by Meter, Output Loop Powered from
External Supply
If the output loop is powered by an external supply, the loop power
! supply must be turned on before the meter is turned on. Otherwise,
the output loop signal may be incorrect.
27
Model PD650 Large Display Process Meter Instruction Manual
Programming
Overview
The meter is programmed using the ENTER button and three jumper arrays. The
ENTER button is used to calibrate the meter, program various totalizer functions,
and set alarm trip and reset points. The jumper arrays are used for programming
the input signal, lockout, relays acknowledge enable, and relays fail-safe
operation. This section of the manual deals with programming the following
aspects of the meter:
• Basic Meter
• Process/Rate Meter
• Totalizer
• Batch Controller
• Relays
• 4-20 mA Output
• Lockout and Display Selection
28
Model PD650 Large Display Process Meter Instruction Manual
ENTER Button
The ENTER button is used to program the meter for various functions and is
located behind the front panel on the Display Board, It is labeled SW2 in Figure
14 above. The ENTER button can also be accessed by wiring a normally open
pushbutton switch across terminals EN and CM on connector J1 located on the
Main Board (see Figure 3, page 21).
Jumper Arrays Function and Location
Jumper Array Function Label Location Diagram
Input signal and Lockout JP1 Main Board Figure 3
Relay ACK enable JP5 Display Board Figure 14
Fail-safe J5 Options Board Figure 4
29
Model PD650 Large Display Process Meter Instruction Manual
Five Basic Digit/Display Setting Instructions
1. If the flashing display is OK, to accept it, press ENTER before it stops
flashing.
2. If the flashing display is not OK, (or if ENTER was not pressed in time to
accept it), wait for the first digit to flash.
3. If a flashing digit is OK, to accept it, press ENTER before it starts to scroll.
4. If a flashing digit is not OK, (or if ENTER was not pressed in time to accept
it) wait for that digit to scroll, and press ENTER when OK.
5. Digits will scroll until ENTER is pressed. When a digit is accepted by
pressing ENTER, the next digit flashes.
The display will scroll through the following functions in the order shown:
Display Type of Function
Dspy r or
Displays process/rate or display total.
Dspy t
Rset t Resets total to zero.
Dspy p Displays and hold peak reading.
CALIb or Calibrates meter after setting it for external or internal
SCale calibration.
30
Model PD650 Large Display Process Meter Instruction Manual
Press
ENTER
Select
LInear
29999 appears;
select dec point
then no. PtS
Inpt1 flashes;
Apply input 1 signal
(e.g. 4 mA)
Inpt 2 flashes;
Press ENTER Apply input 2 signal
(e.g. 20 mA)
Is YES
flashing display Press ENTER
OK?
NO
NO
Wait for digit Has Input 2
to flash been calibrated
yet?
NO YES
Is
Wait for digit
flashing
to scroll
digit OK?
YES
Calibration
Complete!
Press ENTER
Press ENTER
when OK
Is NO
entire display
flashing?
YES
31
Model PD650 Large Display Process Meter Instruction Manual
32
Model PD650 Large Display Process Meter Instruction Manual
33
Model PD650 Large Display Process Meter Instruction Manual
Scale or Calibrate the Meter
The meter may be scaled without applying an external signal source or calibrated
by applying an external signal source.
Scale Using Internal Calibration (I-CAL)
Note To simplify programming, write down the desired programming
values prior to attempting to program the meter. The Programmed
Parameter Settings form located at the back of this manual provides
a convenient method to record the user settings; it also provides the
factory setting for most of the programmable parameters.
Press ENTER, then press it again when the scale SCale
(SCale) function appears.
29.999
Select the number of calibration points
No. pts
If ENTER is not pressed when no. pts is displayed, the
number of points will default to whatever was selected then
previously. To program the number of calibration points, 2
press ENTER while no. pts is flashing. The current setting
for the number of points will flash. If this is the desired value, then
press ENTER to accept it. If not, wait and the number will
increase. When the desired number of points is displayed,
3
press ENTER to accept it. ….
11
34
Model PD650 Large Display Process Meter Instruction Manual
Set the first calibration point
Inpt 1
Input 1 (INPT 1) flashes indicating that the meter
is ready to be programmed for the input for the
first calibration point. Press ENTER.
Set the input for the first calibration point
04.000
The entire display will flash for three seconds. For
then
instructions see Five Basic Digit/Display Setting
Instructions, page 30. 04.001
final input 1
04.003
Set the display for the first calibration point
Dspy 1
Display 1 (Dspy 1) flashes indicating that the
meter is ready to be programmed for the display
for the first calibration point. Press ENTER.
Program the display for display 1 (Dspy 1) as described 00.000
above when the input for the first calibration point was
programmed. final display 1
02.500
To quit main menu, calibration, or scaling press ACK while displaying main menu
item or while display is flashing input n (InPt n) or display n (dspy n), where n is
the input or display number.
Minimum Input Span (Error Message)
The calibration input signals must be within the range of the meter and input 2
must be greater than input 1. However, the display for input 2 does not have to
be greater than the desired display for input 1.
If input 1 and input 2 signals are too close together an Error message will
appear and the display will return to the current input to be calibrated. To
terminate calibration process, press ACK button.
Input Range Minimum Difference Between Input 1 & Input 2
0-5 V 0.16 V
0-10 V 0.32 V
4-20 mA 1.60 mA
35
Model PD650 Large Display Process Meter Instruction Manual
05.000
Set the display for the remaining calibration points
Inpt 3
If other calibration points were selected, they will be
displayed and can be set according to the procedure for the
first two points.
When the display for the last calibration point is accepted by
pressing ENTER, the meter will display total or process/rate.
36
Model PD650 Large Display Process Meter Instruction Manual
29.999
Select the number of calibration points
No. pts
If ENTER is not pressed when no. pts is displayed, the
number of points will default to whatever was selected then
previously. To program the number of calibration points, 2
press ENTER while no. pts is flashing. The current setting
for the number of points will flash. If this is the desired value, then
press ENTER to accept it. If not, wait and the number will
increase. When the desired number of points is displayed,
3
press ENTER to accept it. ….
11
38
Model PD650 Large Display Process Meter Instruction Manual
Apply the signal for the first calibration point
Inpt 1
Input 1 (INPT 1) flashes indicating that the meter
is ready to accept a signal for the first calibration
point. Apply the desired signal, typically 4 mA, and
press ENTER.
Set the display for the first calibration point
-0.000
The entire display will flash for three seconds. For
instructions see Five Basic Digit/Display Setting then
Instructions, page 30. 01.000
then
02.000
final
03.000
12.000
Set the display for the remaining calibration points
Inpt 3
If other calibration points were selected, they will be
displayed and can be set according to the procedure for the
first two points.
When the display for the last calibration point is accepted by
pressing ENTER, the meter will display total or process/rate.
39
Model PD650 Large Display Process Meter Instruction Manual
40
Model PD650 Large Display Process Meter Instruction Manual
41
Model PD650 Large Display Process Meter Instruction Manual
The totalizer in the meter accumulates based on the rate display. This means
that when the rate display is zero, even as a result of the low-flow cutoff, the
totalizer will not accumulate.
01.500
final
01.520
42
Model PD650 Large Display Process Meter Instruction Manual
Totalizer Programming
Overview
The meter can also be used to display total flow. There are five functions to be
programmed to allow the meter to act as a flow totalizer:
1. Set Display to Total
2. Set Rate Time Base
3. Set Totalizer Conversion Factor
4. Set Totalizer Decimal Point
5. Set Alternating Display (if Needed)
43
Model PD650 Large Display Process Meter Instruction Manual
The different units of time will scroll: minute, hour, day, and min
second. Press ENTER when the required unit is displayed.
or
Hour
or
Day
or
seC
44
Model PD650 Large Display Process Meter Instruction Manual
9.99999
Set the total conversion factor value
The entire display will flash for three seconds. For
instructions see Five Basic Digit/Display Setting 0.01000
Instructions, page 30. then
0.02000
then
0.02380
final
0.02381
9999.99
45
Model PD650 Large Display Process Meter Instruction Manual
46
Model PD650 Large Display Process Meter Instruction Manual
4. Programming set, reset, preset, offset, and delay values using the SEtPtS
menu:
a. Set and reset points for alarms (set points) assigned to process/rate
(thus determining high or low alarm status and deadband).
b. Preset values for set points assigned to total.
c. Preset offset values for set points assigned to total with offset selected.
47
Model PD650 Large Display Process Meter Instruction Manual
48
Model PD650 Large Display Process Meter Instruction Manual
49
Model PD650 Large Display Process Meter Instruction Manual
Rate or Total, Latching or Non-Latching Relays
Note To simplify programming, write down the desired programming
values prior to attempting to program the meter. The Programmed
Parameter Settings form located at the back of this manual provides
a convenient method to record the user settings; it also provides the
factory setting for most of the programmable parameters.
Press ENTER, then press ENTER again when the
Setup
setup (Setup) function appears
SEt 3
then
SEt 4
then
I or E
If ENTER is pressed while set point 1 (SEt 1) is
SEt 1
shown, the display will then show rate or total
(r or t) flashing alternately. then
Select the desired one by pressing ENTER when
R or t
it is flashing.
Select process/rate
R or t
After selecting r for process/rate, the display will show latch
(LatCH). Press ENTER to program this function. If ENTER is then
not pressed within 3 seconds, this function will remain
LatCk
programmed as it was before, and the next set point will be
displayed. then
SEt 2
If ENTER is pressed while the display reads
R or t
LatCH, yes or no (Y or N) will flash alternately. To
program this set point for Latching relay, press then
ENTER when Y is flashing. To program this set
point for non-latching relay, press ENTER when n LAtCH
is flashing. After making the selection, setup of set then
point 1 is complete and the next set point will be
displayed. Press ENTER to set up that set point, if y or n
not, wait until desired set point is displayed or wait then
for the meter to exit the Setup menu completely.
SEt 2
50
Model PD650 Large Display Process Meter Instruction Manual
Select total
R or t
After selecting t for total, the display will show set point 2
(Set 2), press ENTER to set up set point 2 or wait and the then
display will move to the next set point.
SET 2
SEt 3
If ENTER is pressed while the display reads
R or t
LAtCH, yes or no (Y or N) will flash alternately. To
program this set point for latching relay, press then
ENTER when Y is flashing. To program this set
point for Non-latching relay, press ENTER when n LatCk
is flashing. After making the selection, setup of set then
point 1 is complete and the next set point will be
displayed. Press ENTER to program that set point, Y or n
if not, wait until desired set point is displayed or then
wait for the meter to exit the Setup menu
completely. SEt 3
Select total when the first set point was assigned to rate
R or t
After selecting t for total, the display will show set point 3
(Set 3), press ENTER to set up set point 3 or wait and the then
display will move to the next set point.
Set 3
51
Model PD650 Large Display Process Meter Instruction Manual
Select total when the first set point was assigned to
R or t
total
After selecting t for total for second set point, the display will then
show preset offset (OFFSEt) press ENTER to set up this
OFFSET
function. If ENTER is not pressed within 3 seconds, this
function will remain programmed as it was before, and the then
next set point will be displayed.
SEt 3
000010
final delay
000600
The display moves to setting the relays for pump alternation control.
52
Model PD650 Large Display Process Meter Instruction Manual
53
Model PD650 Large Display Process Meter Instruction Manual
Overview
The SEtPtS menu is used to program the following functions:
1. Set and reset points for alarms assigned to process/rate (thus determining
high or low alarm status and deadband).
2. Preset values for set points assigned to total
3. Preset offset values for set points assigned to total with OFFSET selected
54
Model PD650 Large Display Process Meter Instruction Manual
The 4 discrete LEDs to the left of the display indicate which set point is being
programmed.
For set points assigned to process/rate, there are also two LEDs on the right side
of the display, labeled S and R, that indicate whether a set or reset point is being
programmed.
Figure 18. Display Showing Location of Set, Reset and Rate LEDs
When programming set points assigned to total, only one of the 4 discrete LEDs
on the left side of the display will be illuminated at a time. A flashing LED
indicates that a preset offset value is being programmed, a steady-on LED
indicates that a preset value is being programmed.
55
Model PD650 Large Display Process Meter Instruction Manual
SEt 4
then
outPut
If ENTER is pressed while set point 1 (SEt 1) is
SEt 1
shown, the display will then show a flashing
number. Follow instructions below to program set then
points assigned to process/rate and set points
(presets) assigned to total. 070.00
Set points assigned to process/rate
For set points that have been assigned to
process/rate during the Setup function, the
alarm # (1,2,3, or 4) and the S (set point) LED
will be illuminated. This indicates that the set
point for alarm # (1, 2, 3, or 4) is being Meter displaying alarm # 1 set
point
programmed.
56
Model PD650 Large Display Process Meter Instruction Manual
120.00
final
125.00
Set the display for alarm # (1,2,3, or 4)
reset point
As soon as the set point for alarm # (1,2,3 or
4) has been programmed, the meter displays
the reset point for alarm # (1,2,3, or 4). This is
indicated by the alarm # (1, 2, 3, or 4) LED Meter displaying alarm # 1 reset
and R (reset point) LED being illuminated. point
The reset point is programmed in the same
fashion as the set point above.
120.00
final
125.00
57
Model PD650 Large Display Process Meter Instruction Manual
120.00
final
125.00
58
Model PD650 Large Display Process Meter Instruction Manual
The green “4” LED illuminates indicating the meter is displaying the value at
which it will produce a 4 mA output. Confirm that this is the desired value. Press
ENTER (within 3 seconds) before the entire display stops flashing and the green
“20” LED illuminates indicating the meter is displaying the value at which it will
produce a 20 mA output. Confirm that this is the desired value. Press ENTER
(within 3 seconds), before the entire display stops flashing and the meter returns
to indication mode.
59
Model PD650 Large Display Process Meter Instruction Manual
60
Model PD650 Large Display Process Meter Instruction Manual
61
Model PD650 Large Display Process Meter Instruction Manual
Notes:
1. User may program which of these routine titles are active during operation
and which ones are not. See below for instructions.
2. Note: Selections made through the display menu (dSPLAY) can be made
with or without the lockout jumper installed, but only become active when the
lockout jumper is installed.
3. With the lockout jumper in place, the SEtPtS menu still appears.
4. Selecting y for SEtPtS will allow an operator to view and change set/reset
points and presets even with the lockout jumper in place.
5. Selecting n for SEtPtS will still allow an operator to view set/reset points and
presets, but not to make changes.
6. Select n for both dSPy r and dSPy t to program display to toggle between
rate and total every 10 seconds.
7. Total can be reset with an external push-button even if rSEt t is set to n.
Alternating Display
The display may be programmed to toggle between rate and total every 10
seconds. The alternating display feature is programmed, by selecting n for both
dSPy r and dSPy t, under Display Selection menu (dSPLAy).
Note: Selections made through the display menu (dSPLAY) can be made with or
without the lockout jumper installed, but only become active when the lockout
jumper is installed.
62
Model PD650 Large Display Process Meter Instruction Manual
63
Model PD650 Large Display Process Meter Instruction Manual
OPERATION
Overview
This instrument is an analog input process meter with flow rate, totalizer, and
batch control capabilities. It accepts the common process signals such as
4-20 mA, 0-5 VDC, 1-5 VDC, and 0-10 VDC. It displays these signals in any
engineering unit on a 2.3" high, 4½ digit LED display for process/rate and six full
digits for total. The meter also provides two isolated 24 VDC power supplies to
drive both the input and output loops. Options include up to 4 relays for alarms or
batch control applications as well as an isolated 4-20 mA transmitter output.
64
Model PD650 Large Display Process Meter Instruction Manual
The four alarm status LEDs indicate alarm condition only and do not represent
relay status when set points are set up for non-latching relay mode. For instance,
if alarm 1 is programmed for a high alarm at 500 with manual reset of the relays
and the operator resets the relays when the display reads 650, the #1 LED will
stay on until the display falls below 500.
Set points setup for latching relay mode will reflect the status of the LEDs,
regardless of the status of the alarm condition. For instance, when a latching
relay is acknowledged the corresponding status LED will extinguish.
65
Model PD650 Large Display Process Meter Instruction Manual
Overview
In its most basic form, the meter provides a digital display in engineering units of
any process variable from a transmitter, such as temperature, pressure, level,
flow, etc. The meter is calibrated for the appropriate range, the output of the
transmitter is connected to the meter and the meter displays the process. As a
standard feature, the meter can also provide the power to drive the input
transmitter and the 4-20 mA output option while maintaining isolation between
the input and the output signals.
The ENTER button performs the following operations with lockout jumper
installed:
66
Model PD650 Large Display Process Meter Instruction Manual
Note:
While in the display peak (DSPy P) mode, the meter continues capturing new
peaks; but it does not respond to signals below the last peak value captured;
it remains “locked” on the peak display reading. For instance, if while the
meter is displaying a peak of 100, the input increases to 150, the new peak
of 150 will be displayed. If the input falls down to 125 before the peak display
is reset, the meter will continue displaying 150 as the peak reading.
67
Model PD650 Large Display Process Meter Instruction Manual
The totalizer in the meter accumulates based on the rate display. This means
that when the rate display is zero, even as a result of the low-flow cutoff, the
totalizer will not accumulate.
68
Model PD650 Large Display Process Meter Instruction Manual
Totalizer Operation
Overview
The meter provides a display of accumulated flow total by integrating the flow
rate input to the meter and multiplying this value by a user-defined totalizer
conversion factor. The total is displayed on a six-digit display that is capable of
reading to 999,999. When the total exceeds 999,999, the display “rolls” over and
begins counting from zero again without loosing counts. The total can be reset at
any time via the front panel, via an external switch closure, or when the meter
reaches the highest preset value.
Display Total (dSPy t)
The user may toggle between a display of process/rate or total at any time. When
displaying process/rate, the process/rate LED indicator will be illuminated.
69
Model PD650 Large Display Process Meter Instruction Manual
Applications Using Total Conversion Factor and Time Base
The following tables illustrate the effect various total conversion factors and time
bases have on the operation of the meter:
Application #1
Application #2
In the above application, 5 gallon paint cans are being filled and the user wants
to keep track of the number of cans that have been filled, not the total gallons of
paint that has been dispensed.
Application #3
70
Model PD650 Large Display Process Meter Instruction Manual
Totalizer Reset
The totalizer may be reset in any of three ways:
RSEt t
then
0.0
Note: It is possible to exclude the reset total (rset t) function from the menu
scroll. See Display Selection (dSPLAy), page 61 for details.
71
Model PD650 Large Display Process Meter Instruction Manual
Relays Operation
Overview
The relay capabilities of the meter expand its usefulness beyond simple
indication to provide users with alarming and controlling functions. These
capabilities include front panel alarm status LEDs as well as either 2 or 4 optional
relays. Typical applications include high or low temperature, level, pressure or
flow alarms, simple control applications like sump-pump or tank-filling and
automatic or manual batch controlling. There are four basic ways the relays can
be used:
1. High or Low Alarms
2. Simple On/Off Control with 100% aAdjustable Ddeadband
3. Automatic Batch Control
4. Manual Batch Control
Fail-Safe Operation
The following table indicates how the relays behave based on Jumper J5 being
installed or not installed:
72
Model PD650 Large Display Process Meter Instruction Manual
The meter is supplied with four alarm points that include front panel LEDs to
indicate alarm conditions. This standard feature is particularly useful for alarm
applications that require visual-only indication. The front panel LEDs are
controlled by the set and reset points programmed by the user. When the display
passes a set point for a particular alarm, that alarm’s LED will light up. When the
meter passes back through that alarm’s reset point the LED will go off. The front
panel LEDs respond differently for latching and non-latching relays.
For non-latching relays, the LED is always off during normal condition and
always on during alarm condition, regardless of the state of the relay.
For latching relays, the alarm LEDs reflect the status of the relays, regardless of
the alarm condition. The following tables illustrate how the alarm LEDs function in
relation to the relays and the acknowledge button:
73
Model PD650 Large Display Process Meter Instruction Manual
Relay key legend for following tables
Key Relay condition
On Tripped
Off Reset
Ack Acknowledged
The On and Off keys do not refer to the status of the relay’s coil, which depends
on the fail-safe mode selected.
Non-Latching Relay
Automatic reset only JP5(1-4 off)
Condition LED Relay
Normal Off Off
Alarm On On
Ack (No effect) On On
Normal Off Off
In this application, the meter is set up for automatic reset and non-latching relay.
Acknowledging the alarm while it is still present has no effect on either the LED
or the relay. When the alarm finally goes away, the relay automatically resets and
the LED also goes Off.
Non-Latching Relay
Automatic + manual reset at any time JP5(1-4 on)
Condition LED Relay
Normal Off Off
Alarm On On
Normal Off Off
In this application, the meter is set up for automatic + manual reset at any time
and non-latching relay. The LED and the relay automatically reset when the
meter returned to the normal condition.
74
Model PD650 Large Display Process Meter Instruction Manual
Latching Relay
Manual reset only after signal passes reset point JP5(1-4 off)
Condition LED Relay
Normal Off Off
Alarm On On
Ack (No effect) On On
Normal On On
Ack Off Off
In this application, the meter is set up for manual reset only after the signal
passes the reset point of the latching relay. Acknowledging the alarm while it is
still present has no effect on either the LED or the relay. When the alarm is
acknowledged after it returns to the normal state, the LED and the relay go Off.
Notice that the LED remained On, even after the meter returned to the normal
condition. This is because, for latching relays, the alarm LEDs reflect the status
of the relays, regardless of the alarm condition.
Manual reset only after signal passes reset point JP5(1-4 off)
Condition LED Relay
Normal Off Off
Alarm On On
Normal On On
Ack Off Off
In this application, the meter is set up for manual reset only after the signal
passes the reset point of the latching relay. When the alarm is acknowledged
after it returns to the normal state, the LED and the relay go Off.
Latching Relay
Manual reset any time JP5(1-4 on)
Condition LED Relay
Normal Off Off
Alarm On On
Ack Off Off
In this application, the meter is set up for manual reset at any time.
Acknowledging the alarm even if the alarm condition is still present resets the
relay and turns off the LED.
Acknowledging Relays
There are two ways to acknowledge relays programmed for manual reset: via the
front panel ACK button and remotely via a switch wired across AK and CM
terminals on the Main Board. When the ACK button or a switch wired across the
AK and CM terminals is closed, all relays programmed for manual reset will
reset.
The “total” display is not affected by this action and therefore pressing the ACK
button or closing the ACK switch will not reset the total.
75
Model PD650 Large Display Process Meter Instruction Manual
76
Model PD650 Large Display Process Meter Instruction Manual
77
Model PD650 Large Display Process Meter Instruction Manual
78
Model PD650 Large Display Process Meter Instruction Manual
79
Model PD650 Large Display Process Meter Instruction Manual
9823.69
Relay 2 Relay 1
COM
Output 1
NO or NC SW1-A
Stop/Ready
Switch
COM
Output 2
NO or NC SW1-B
80
Model PD650 Large Display Process Meter Instruction Manual
81
Model PD650 Large Display Process Meter Instruction Manual
AC and DC Loads
Notes:
1. Use capacitors rated for 240 VAC.
2. Snubbers may affect load release time of solenoid loads, check to confirm
proper operation.
3. Install the RC network at the meter's relay screw terminals. An RC network
may also be installed across the load. Experiment for best results.
Use a diode with a reverse breakdown voltage two to three times the circuit
voltage and forward current at least as large as the load current.
82
Model PD650 Large Display Process Meter Instruction Manual
Overview
The meter can be equipped with an isolated 4-20 mA output option that can be
programmed to produce a 4-20 mA signal for virtually any process/rate display
with at least a 501 count span.
Overview
The meter provides the user with the ability to restrict modification of
programming values and to exclude menu titles from appearing during the menu
scroll. Restricting modification of the programming values is accomplished by
installing the lockout jumper (JP1). Excluding menu titles from the menu scroll is
performed with the display menu.
Note: Selections made through the display menu (dSPLAY) can be made with or
without the lockout jumper installed, but only become active when the lockout
jumper is installed.
83
Model PD650 Large Display Process Meter Instruction Manual
INSTALLATION
The meter overall dimensions are as shown:
13.49" (342.6)
13.54" (344.0)
3.2" (82)
Procedure:
1. Drill holes into the wall to accommodate suitable fasteners.
2. Remove the front bezel from the housing by removing the four mounting
screws.
3. Align the enclosure mounting holes with the holes in the wall and insert the
fasteners. Tighten the fasteners.
84
Model PD650 Large Display Process Meter Instruction Manual
BRACKET
METER BASE
DECORATIVE BEZEL
14.30" (363)
Ø0.250"
(6.4)
15.32" (389)
85
Model PD650 Large Display Process Meter Instruction Manual
Notes:
1. Allowable panel thickness: 0.06" – 0.25" (1.5 mm x 6.4 mm). Longer
bracket screws may be used for panel thickness up to 0.5" (12.7 mm).
2. Mounting space required: 7" x 17.5" x 4" (178 mm x 445 mm x102 mm)
(HxWxD). Meter cover extends 0.8" (20.3 mm) - X from the surface of the
panel, where X equals the thickness of the panel.
3. See Figure 31 above for panel cutout dimensions. Tolerance for all
dimensions: ±0.01" (0.25 mm).
4. This panel mounting kit is not intended to provide waterproof protection to
the panel.
86
Model PD650 Large Display Process Meter Instruction Manual
87
Model PD650 Large Display Process Meter Instruction Manual
88
Model PD650 Large Display Process Meter Instruction Manual
Process/rate
decimal point 299.99
Number of
points 2 PtS 2 points
Set point
setup Set 1 Total
Set 2 Total
Set 3 Rate
Latching relay latCH Non-latching
Set 4 Rate
Latching relay latCH Non-latching
89
Model PD650 Large Display Process Meter Instruction Manual
Parameter Display Factory User Setting
Setting
Total reset External
mode e rst total reset
Set point
values Set 1 1000
Set 2 4000
Set 3 70.00
(Reset 3) 60.00
Set 4 90.00
(Reset 4) 80.00
4-20 mA
output (4 mA) 000.00
dSPy t Yes
rSEt t Yes
dspy p Yes
setpts No
90
Model PD650 Large Display Process Meter Instruction Manual
91
Model PD650 Large Display Process Meter Instruction Manual
Delay on
release delay
92
Model PD650 Large Display Process Meter Instruction Manual
Overview
The Diagnostic menu in the meter provides an easy way to view and write down
the parameter settings. The information gathered through the diagnostic menu
will be helpful to determine if a wrong setting is causing the operation of the
meter to be undesirable.
Operation
When the diagnostic menu is entered, the function and programmed parameter
settings will be displayed one at a time. Press ENTER to step through the
functions and settings. If ENTER is not pressed within 10 seconds, the display
will move to the next function or setting. To exit the diagnostic menu press the
ACK button at any time.
93
Model PD650 Large Display Process Meter Instruction Manual
Model Description
PD118 MINIMUX® 8 Point Scanner
PD154 Vigilante® II 4-Point Annunciator (UL Listed)
PD158 Vigilante® II 8-Point Annunciator (UL Listed)
PD202 General Purpose Digital Pressure Gauge
PD213-224 Industrial Digital Pressure Gauges (FM & CSA)
PD233-253 Precision Digital Test Pressure Gauges (FM & CSA)
PD603 Sabre P Low-Cost Process Meter (UL Listed)
PD644 Javelin D High-Voltage DC Panel Meter (UL Listed)
PD655 1.0" LED NEMA 4X Large Display Process Meter
PD656 0.8" LED Exp-Proof Large Display Process Meter
PD660 Low-Cost NEMA 4X Loop-Powered Meter
PD661 Low-Cost Exp-Proof Loop-Powered Meter (FM & CSA)
PD683 Loop-Powered Meter
PD684 Loop-Powered Rate/Totalizer
PD685 3½ Digit Loop Powered NEMA 4X Meter (General Purpose)
PD686 3½ Digit Loop Powered NEMA 4X Meter (FM & CSA)
PD687 3½ Digit Loop Powered Exp-Proof Meter (FM & CSA)
PD688 Loop-Powered Meter (FM & CSA)
PD689 Loop-Powered Rate/Totalizer (FM & CSA)
PD690 1/8 DIN Analog Input Process Meter (UL Listed)
PD691 1/8 DIN Strain Gauge & mV Input Meter (UL Listed)
PD692 1/8 DIN Analog Input Flow Rate/Totalizer (UL Listed)
PD693 1/8 DIN Freq/Pulse Input Flow Totalizer (UL Listed)
PD743 Sabre T Low-Cost Temperature Meter (UL Listed)
PD750 TC & RTD Temperature Meter (UL Listed)
PD751 10 Ω Cu RTD Temperature Meters (UL Listed)
PD752 120 Ω Ni RTD Temperature Meters (UL Listed)
PD765 Trident Process & Temperature Meter (UL Listed)
PD865 Snooper Modbus Serial Input Meter (UL Listed)
PD940 & 941 ConsoliDator® 4 Multi-Channel Controllers (UL Listed)
PD980 & 981 ConsoliDator® 8 Multi-Channel Controllers (UL Listed)
PD6000 ProVu Process Meter (UL Listed)
PD6200 ProVu Analog Rate/Totalizer (UL Listed)
PD6300 ProVu Pulse Rate/Totalizer (UL Listed)
94
Model PD650 Large Display Process Meter Instruction Manual
NOTES
95
Model PD650 Large Display Process Meter Instruction Manual
LIM650_G.doc
SFT003 Ver 1.300 & up
11/08