GloEn Patrol Manual (QS38000 1 2) (IMO)
GloEn Patrol Manual (QS38000 1 2) (IMO)
GloEn Patrol Manual (QS38000 1 2) (IMO)
2N
INSTRUCTION
MANUAL(IMO)
PROJECT : QS38000-1/2
1 |Page
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
2 |Page
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
Table of Contents
I. PRINCIPLES OF GLOEN-PATROL™ BALLAST WATER MANAGEMENT SYSTEM ............................................ 6
A. GENERAL DESCRIPTION OF THE MATERIALS USED FOR CONSTRUCTION AND INSTALLATION OF GLOEN-PATROL™ .............. 19
B. GENERAL ARRANGEMENT(S) FOR GLOEN-PATROL™........................................................................................................... 28
C. INTENDED USAGE FOR GLOEN-PATROL™ ......................................................................................................................... 28
D. MAXIMUM AND MINIMUM FLOW AND VOLUME CAPACITIES OF GLOEN-PATROL™ ................................................... 28
IV. HEALTH AND SAFETY RISKS TO THE PERSONNEL ASSOCIATED WITH THE INSTALLATION, OPERATION
AND MAINTENANCE OF GLOEN-PATROL™ ..................................................................................................... 65
A. INSTRUCTION FOR ANY HEALTH AND SAFETY CERTIFICATION/TRAINING REQUIREMENTS OF PERSONNEL OPERATING THE
GLOEN-PATROL™ SYSTEM............................................................................................................................................................ 65
B. MATERIAL SAFETY DATA SHEETS FOR HAZARDOUS OR RELEVANT CHEMICALS USED, STORED, OR GENERATED BY OR FOR THE
SYSTEM. ........................................................................................................................................................................................ 69
3 |Page
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
A. USE OF TOOLS AND TEST EQUIPMENT IN ACCORDANCE WITH THE MAINTENANCE PROCEDURES ......................................... 99
B. ILLUSTRATED LIST OF SPARE PARTS .................................................................................................................................... 140
THIS SPARE PART LIST IS STANDARD. FOR THE INFORMATION ON QUANTITY OF EACH SPARE PART, SEE THE FINAL DRAWING. ...... 140
4 |Page
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
5 |Page
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
1. Ballast Mode
2. De-Ballast Mode
3. Bypass Mode
4. Eductor (Stripping) Mode
1. Filtration unit: for removal of equal to or larger than 50 micron size organisms and particles
(> 50μm)
2. UV unit: for disinfection to destroy DNA of organisms and pathogens smaller than 50 micron
size (<50μm)
3. Control Panel
4. UV Power Supply Panel
The primary treatment takes place during ballasting and a secondary treatment during de-
ballasting. During ballasting, organisms and sediment larger than fifty microns (50μm) are
separated by the filter and returned to local waters. Smaller organisms passing through
the filter flow into the UV chamber where the UV disinfection takes place.
During de-ballasting, any surviving organisms during intake are treated again in the UV
chamber to ensure compliance of the applicable rules. The filter is bypassed during de-
ballasting.
6 |Page
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
• FILTER is located downstream of the ballast pump(s) and removes particles and marine
organisms larger than fifty microns (50μm) and returns them to the local waters. When
particles and organisms clog the filter screen and the unit senses differential pressure build
up, back flushing takes place automatically.
• CONTROL PANEL is a programmable logic controller (PLC) based unit with proportional-
integral-derivative (PID) controller and touchscreen operator interface that controls all
devices and functions of the BWMS and performs real-time monitoring of operating
conditions, data collection and recording.
• UV POWER SUPPLY PANEL houses all devices and parts required to provide power to the UV
unit. It contains necessary devices to automatically adjust the power level to maintain the
required UV dosage level, to protect the UV lamps and to provide safety of the power
supply system.
7 |Page
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
Local water in the seachest is pumped in and passes through a filter with a fifty micron (50μm)
screen. Back-flushing takes place automatically when differential pressure reaches 0.45 kg/cm2.
Suction scanners rotate and move vertically in a spiral manner, to cover the entire screen in
approximately 40-45 seconds. Extracted organisms and sediment are discharged overboard
into the local waters. Water passed through the filter goes though the UV chamber and then
to the ballast tank.
Treated ballast water is re-treated through the UV unit before being discharged overboard
without going through the filter.
8 |Page
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
(3) Warming Up
9 |Page
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
BYPASS MODE is selected and operates for the exception conditions outlined below in the IMO
(International Maritime Organization) Regulations or during malfunction of the treatment
system.
(Exceptions)
IMO 2004 BWMS Convention does not allow treatment system bypass except under the
following conditions:
(i) the uptake or discharge of Ballast Water and Sediments necessary for the purpose of
ensuring the safety of a ship in emergency situations or saving life at sea; or
(ii) the accidental discharge or ingress of Ballast Water and Sediments resulting from
damage to a ship or its equipment:
- provided that all reasonable precautions have been taken before and after the
occurrence of the damage or discovery of the damage or discharge for the purpose
of preventing or minimizing the discharge; and
- unless the owner, company or officer in charge willfully or recklessly caused damage;
or
(iii) the uptake and discharge of Ballast Water and Sediments when being used for the
purpose of avoiding or minimizing pollution incidents from the ship; or
(iv) the uptake and subsequent discharge on the high seas of the same Ballast Water
and Sediments; or
the discharge of Ballast Water and Sediments from a ship at the same location where the whole
of that Ballast Water and those Sediments originated and provided that no mixing with
unmanaged Ballast Water and Sediments from other areas has occurred. If mixing has occurred,
the Ballast Water taken from other areas is subject to Ballast Water Management in accordance
with this Annex.
10 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
• Bypass Operation
During BYPASS MODE, ballast water and sediment from the seachest is discharged overboard.
Bypass operation can take place if abnormal condition occurs during BALLAST or DE-BALLAST
MODE. Abnormal condition will close ballast valves automatically but other main line valves
such as seachest, bypass and overboard valves are controlled by the Valve Remote Control (VRC)
system operator as shown in Figure 1.6 and Figure 1.7 below. All external valve(s) can be
controlled by the operator and valve status will be recorded.
11 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
12 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
To remove the remaining water in the tank, a stripping eductor is used. After completing the
warming up process, an operator will need to open the eductor suction valve. After EDUCTOR
MODE, close the eductor suction valve then turn off the UV unit. The unit will have a cooling
time and the default cooling time is 5 minutes. Once the cooling time is completed, system will
automatically switch to BYPASS MODE.
Figure 1.8 Process flow diagram of EDUCTOR MODE during DE-BALLAST MODE
13 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
C. Limitations of GloEn-Patrol™
There will be no limitation or adverse effects to the vessel’s ballast water, ballast water tanks
and ballast water piping and pumping systems except for the removal of particles and marine
organisms larger than 50 microns (50μm) and the destruction of reproduction cells of living
organisms in the remaining water.
The system does not use or have a byproduct of any substances, relevant chemicals, and
pesticides generated or stored onboard the vessel.
14 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
Two (2) types of UV units are available depending on the area classification:
• PU### model is used in non-hazardous area(s);
• PU###-Ex (explosion-proof) model is IEC-Ex certified and used for hazardous area (Zone 1).
Maximum
Model Name Application # of Lamps
Capacity (TRC)
PU50 2 50 m3/hr
6 150 m3/hr
PU250 8 250 m3/hr
Standard model
12 350 m3/hr
UV Unit 18 500 m3/hr
PU500
24 700 m3/hr
PU1000 22 1,000 m3/hr
PU1250 High Capacity model 26 1,250 m3/hr
PU1500 32 1,500 m3/hr
NOTE:
For application in hazardous area, all electrical devises are explosion proof type.
Explosion proof type (Optional):
a. IEC-Ex : Ex pxb IIC T4 Gb (-20C ≤ Ta ≤ 60C)
b. ATEX : II 2 G Ex pxb IIC T4 (-20C ≤ Ta ≤ 60C)
Table 1.2 UV unit models
PF50 50 m3/hr
PF250 250 m3/hr
Standard model
PF500 500 m3/hr
PF750 750 m3/hr
PF900 900 m3/hr
Filter
PF1200 1,200 m3/hr
PF1500 1,500 m3/hr
High Capacity model
PF2000 2,000 m3/hr
PF2500 2,500 m3/hr
PF3000 3,000 m3/hr
NOTE:
For application in hazardous area, all electrical devises are explosion proof type.
Table 1.3 Filter models
Standard filter models handle capacity between 50m3/hr and 750m3/hr inclusive. High
capacity filter models handle capacity between 900 and 3,000 m3/hr inclusive. Capacity in the
range of 750 ~ 6,000 m3/hr can be handled by combining single or multiple capacity UV unit(s)
and filter(s) in parallel (Refer to Table 1.4 below).
15 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
16 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
The system can be skid mounted and located in the engine room, pump room or on deck,
depending on available space and ship owner’s preference.
GloEn-PatrolTM is supplied with a machine case (enclosed area) which is a part of vessel when it
is installed on deck. The BWMS is not installed independently for deck application.
Standard installation position of UV unit is vertical type installation, and horizontal type
installation is applied to resolve insufficient space for installation. UV lamps shall be positioned
horizontally under any circumstances even though UV unit itself can have horizontal & vertical
position consistent with pipe position
For existing vessels where available space, in general is limited, the four (4) major components
of the system (filter unit, UV unit, UV power supply panel and control panel) are supplied and
installed separately. If necessary, filter unit and UV unit can be separated. UV Power supply
panel and control panel can be located remotely from the filter and UV units. Existing or new
ballast pump characteristics need to be considered for flow and pressure requirement of the
BWMS.
The system is designed to operate in all conditions of salinity, temperature and UV transmittance
with the understanding that a minimum UV intensity and exposure time (flow rate) will be
required for optimal effectiveness.
If a vessel with more than two sets of ballast pumps it is recommended to use applicable GloEn-
Patrol™ system for treatment so vessel must have a suitable system depending on the capacity
of ballast pump. Figure 1.9 shows general arrangement of BWM system.
Parallel installation of filter and UV units in the treatment system is designed to ensure an even
flow distribution for each UV unit. It is fully controlled with individual flow meter and flow
control valve unless even flow is justified due to unusual vessel condition.
17 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
NOTE: If GloEn-Patrol BWMS is intended to be installed on deck of a ship, we recommend inlet piping
line shall be vent piping to avoid that the water flows rapidly down when the BWMS is shut down.
18 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
A. General description of the materials used for construction and installation of GloEn-
Patrol™
(1) Filter
Filter is installed prior to UV unit. It must operate during ballasting, while it is bypassed during
de-ballasting. Filter element (screen) is of 50 microns (50μm) size, and clogged organisms and
particles equal to or larger than 50 microns are removed and returned to local water by filter
cleaning (back-flushing) is automatic. Several cleaning (scanner) heads scan over the filter
screen surface with a “corkscrew-like” rotational & vertical motion by an electric motor and suck
clogged materials. There are several size filter chambers and each chamber can accommodate
a few different size of filter element and also some chambers have multiple numbers of filter
elements (Refer to Figure 2.1). The filter consists of a filter elements, sensors and back-
flushing parts.
Pressure Transmitter
Filter Element
• Filter element:
- Installed inside filter chamber 50 microns mesh screen (normally made of Hastelloy) in a
stainless steel frame.
- PF 250/ 500/ 750 have one filter element and PF 900/ 1200/ 1500/ 2000/ 2500/ 3000
have several filter elements in one chamber.
19 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
• Sensor part:
- Pressure Transmitters: Two (2) transmitters, one (1) for inlet and one (1) for outlet
pressure of the filter. Differential pressure between two transmitters activates back-
flushing.
- Limit switches: Switches to limit axial movement of the cleaning head (suction scanner)
assembly and located on two different points of the threaded shaft of the cleaning
assembly.
• Back-flushing part:
- There are several suction scanners inside the filter element. They move axially and
rotate over the screen surface. High differential pressure across the screen activates
back-flushing automatically and opens the back-flushing valve. When the valve opens,
suction takes place and removes and clogged materials. Construction of the filter for
high-capacity application is shown in the Figure 2.2.
• Features:
20 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
21 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
The system uses high intensity UV light to destroy living organisms present in the ballast water
being treated so that it prevents to preclude invaders from colonizing.
UV lamps emitting rays perpendicular to the fluid flow are well designed to reach the maximum
to destroy the organisms. This design has several unique advantages to manufacture in
compact design, including the ability to treat effectively with a very poor transmittance, or
extremely high flow rates without bypass. As flow rates increase, chamber size and lamp
power output can be increased to the current maximum single chamber capacity. For larger
flows, multiple chambers are used. All the necessary monitoring equipment is integral and the
separate power/ control modules can be installed either remotely or in proximity to the UV
treatment chamber. Reliable disinfection requires that a constant UV dosage is applied to the
water.
Fluctuations in the power supply are common in some installations, but GloEn-Patrol™ UV
system is designed to handle such fluctuations and to deliver constant power to the UV unit.
Major components and features of the UV unit are as follows (Refer to Figure 2.3 and Figure 2.4).
UV Lamp
• Sensor Part:
- Broad-spectrum, high intensity medium pressure UV lamps with the entire germicidal
output range.
- Multiple lamp configurations.
- High-purity quartz for maximum transmission.
22 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
• Chamber:
• Features:
23 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
The lifetime of UV lamp is approximately 4,000 operating hours but regular check is required.
The UV lamps generate large amount of heat during operation. Generated heat causes high
temperature and it affects to the UV system. This is the main reason why it requires both
warming up and cooling down process for protection. Even it indirectly exposed into the
running water, this cooling effect is quite limited and it is not always safe for continuous working
with proper flow that must be secured under normal operation. High temperature would
become a potential problem in the long term, and it is able to affect to be shut down during
ballasting and de-ballasting.
In order to prevent forced termination of BWM system due to high temperature, both
temperature transmitter and switch are installed for monitoring the temperature in/outside of
the chamber for Non proof model. Mechanically, most heated air transferred out through the
vent hole, but these temperature sensors are equipped for secondary safety. The temperature
transmitter is installed as the first layer of safety. If the temperature inside of chamber exceeds
the normal set point, a warning signal appears and shut down process are given in regular logic
sequence. In addition, the temperature switch is installed as the second layer of safety. So if
temperature of UV surface exceeds the normal set point, shut down function can be performed
by mechanical type which is independent of the PLC or software type which is controlled by PLC
control. For protection of human body from touching, surface temperature of the chamber
must be maintained by a temperature switch sensor.
In the case of Ex proof models, temperature transmitter and two (2) flow switches are fitted for
checking the loss of water flow through BWMS during any stage of ballasting including warming
up and cooling down stages. If the temperature inside of the UV chamber could reach high
temperature due to potential damage or problem, it would cause serious problem. So In order
to prevent this situation, the UV chamber must be filled with water during operation. As the
same method with temperature switch, flow switch is second layer of safety. If flow switch
become a trip condition, shut down function can be performed by mechanical type which is
independent of the PLC or software type which is controlled by PLC control.
24 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
25 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
Control panel is a programmable logic controller (PLC) based unit with proportional-integral-
derivative (PID) controller and touchscreen operator interface that controls all devices and
functions of the BWMS and performs real-time monitoring of operating conditions, data
collection and recording. The electromagnetic ballasts, which are installed in UV power supply
panel, are controlled by PLC which controls each lamp with a maximum input power 3.5 kW.
Three (3) stage power levels are available in each system and adjust automatically based on the
UV intensity sensor.
An operator with the help of a touchscreen takes charge of the operation and commands each
task. The control panel also performs real-time monitoring while storing the operating
conditions of each unit and the data detected by the main sensor(s) at the same time.
26 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
The major function of UV power supply panel is to operate the medium pressure lamps inside
the UV chamber. It controls the strength of the UV lamp with the capacitors mounted in the
panel. Also it detects whether the UV lamps are functioning properly or not. The
temperature sensor is mounted inside to monitor in order to give an alarm to an operator and
shut down the system in case of emergency. The UV power supply panel enables the UV lamp
to be powered and controlled in a safe manner with the backup of monitoring and safety
functions. A control of three (3) stage power levels takes place automatically to maintain the
required minimum UV dosage in changing UV transmittance and flow conditions.
27 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
The system can be arranged skid mounted or in a dedicated enclosure and located in the engine
room, pump room or on deck, depending on available space and ship owner’s preference.
FILTER (Standard and High Capacity Models) can be arranged in a vertical or horizontal
arrangement. Those models requiring multiple units can be arranged in a series in vertical or
horizontal arrangements. These arrangements are dependent of the available space
UV UNIT (Standard and High Capacity Models) can be arranged in a vertical or horizontal
arrangement, but UV lamps must be installed in a horizontal. Those models requiring multiple
units can be arranged in a series in vertical or horizontal arrangements.
The system can be used with all vessel types, services and locations. While the salinity and
temperature of local waters having little or no effect, the system does require a minimum UV
intensity to kill or inactivate organisms. The UV transmittance and radiation angle and
distance from the UV source will affect UV intensity. The exposure duration (Flow Rate) is very
important for system effectiveness.
28 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
Connection
Unit Model Name Application Weight (kg)
Flange
PU50 80A 120
PU250 Standard model 350A 180
PU500 350A 230
UV Unit
PU1000 350A 300
High Capacity
PU1250 400A 500
model
PU1500 400A 700
Table 2.8 UV unit Models
Connection
Unit Model Name Application Weight (kg)
Flange
PF50 80A 450
PF250 200A 500
Standard model
PF500 300A 750
PF750 350A 1,100
PF900 350A 2,300
Filter
PF1200 350A 2,500
PF1500 High Capacity 400A 3,000
PF2000 model 500A 3,400
PF2500 500A 4,000
PF3000 500A 4,400
NOTE:
Connection Flange could be changed by shipyard piping size.
Table 2.9 Filter models
29 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
30 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
PU###-Ex (explosion-proof) models are certified by DNV-GL for compliance of IEC-Ex and ATEX.
The model complies with USCG (United States Coast Guard) and IMO (International Maritime
Organization) specifications for hazardous area (Zone 1). Ex models use all explosion proof
type components with proper label or certification by UL (Underwriters Laboratories), CE
(Conformite Europeene) mark or other globally recognized safety agencies. UV chamber is a
purge/pressurization type built and certified.
Previously, Table 1.4 shows the names and maximum capacity of models and specific
components can be found on Figure 2.9.
31 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
Figure 2.10 Purge control unit and relief vent for Explosion proof model
General specifications
Power requirement 20 to 30 VDC / 0.6A
Operating temperature −20C ~ 60C
Protected enclosure contact output × 2 8A @ 240VAC/24VDC
Auxiliary contact output × 2 2A @ 240VAC/24VDC
LED indication
Safe pressure BLUE – when safe pressure is achieved
Enclosure power GREEN - power on / RED - power off
Rapid exchange BLUE - when purging is running
System bypass YELLOW - when bypass is activated
RED (flicking) - any alarm
Alarm fault
/ RED (not flicking) - system fault
Table 2.10 Specifications of the purge system
General parameters
Pressure requirement 0.3 MPa ~ 0.7 MPa
Degree of protection IP66
Minimum purging flow rate 141 ℓ /min
Minimum purging duration 10 minutes
Type of protective gas Air
Minimum over pressure 63 Pa
Maximum over pressure 999 Pa
Minimum flow rate (pressurization) 0.3 ℓ /min
Maximum leakage rate 3.0 ℓ /min
Low Pressure alarm 100 Pa
UV lamp : 960V, ~ 8A, 60Hz
Wiper Motor : 100V,110V ~ 1.0A or
Electrical rating
220V ~ 0.36A 60Hz
Purge/Pressurization system : 24Vd.c. 0.6A
Type of lamp Medium pressure UV lamp
Type of protection (IEX-Ex) Ex pxb IIC T4 Gb (-20C ≤ Ta ≤ 60C)
Type of protection (ATEX) II 2 G Ex pxb IIC T4 (-20C ≤ Ta ≤ 60C)
Table 2.11 Common specifications of UV unit
32 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
Specific parameters
Model PU250(x)-Ex PU500(x)-Ex PU1000-Ex PU1250-Ex PU1500-Ex
3 3 3 3
Enclosure volume 0.05 m 0.08 m 0.08 m 0.11 m 0.13 m3
Water flow rate ~ 350 m3/hr ~ 700 m3/hr ~ 1,000 m3/hr ~ 1,250 m3/hr ~ 1,500 m3/hr
Max. of Lamp 6 / 8 / 12 ea 18 / 24 ea 22 ea 26 ea 32 ea
Wiper motor 1 ea 1 ea 1 ea 2 ea 2 ea
“(x)” indicates numbers of UV lamps
Table 2.12 Specific characteristics of UV unit
33 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
After all conditions meet requirements, then BWMS can be operated as Chapter III. STANDARD
OPERATION PROCEDURE in this document.
It is especially important to achieve suitable water flow rate for normal operation. The flow
switches, temperature transmitter and flow transmitter are safety barriers for explosion proof
modes, so If UV unit does not operate properly, check out with trouble shooting.
GloEn-Patrol 2460
Product Name : UV Unit
Model : PU□□□□-EX
II 2 G Ex pxb IIC T4 Gb
-20°C≤Ta≤60°C
SN : -UV- EX
IECEx PRE □□.□□□□X
DATE : 20 . Presafe □□ ATEX □□□□X
www.worldpanasia.com
55 MIEUMSANDAN 3-RO, GANGSEO-GU, BUSAN, KOREA (Zipcode : 618-220)
Rep.Phone : +82-51-831-1010, Fax : +82-51-831-1399
www.worldpanasia.com, E-mail : [email protected]
Description
Model PU250(x)-Ex PU500(x)-Ex PU1000-Ex PU1250-Ex PU1500-Ex
IECEx PRE IECEx PRE IECEx PRE IECEx PRE IECEx PRE
IECEx No.
16.0049X 16.0050X 19.0075X 19.0076X 19.0077X
Presafe 16 Presafe 16 Presafe 19 Presafe 19 Presafe 19
ATEX No.
ATEX 8136 ATEX 8137 ATEX 20303 ATEX 20304 ATEX 20305
Enclosure
0.05 0.08 0.08 0.11 0.13
Volume(m3)
UV-Lamp
6 / 8 / 12 ea 18 / 24 ea 22 ea 26 ea 32 ea
number
“(x)” indicates numbers of UV lamps
ATEX marking
II 2 G Ex pxb IIC T4 -20C ≤Ta≤60C
① ② ③ ④ ⑤ ⑥ ⑦ ⑧ ⑨
IEC-Ex marking
Ex Pxb IIC T4 -20C ≤Ta≤60C Gb
⑤ ⑥ ⑦ ⑧ ⑨ ⑩
34 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
35 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
Figure 3.1 shows the initial HOME screen that operator can see when BWMS is on. Operator
can check parameters or operation status from this screen. This home screen displays the
following:
36 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
• Warm Up
The warm up process, while not a separate mode, is required for the valves to be arranged in
order for water to flow through the ballast line and to ensure the sufficient approximately five (5)
minutes time takes the system to reach full power:
Normal warming up process when operator selects BALLAST MODE or DE-BALLAST MODE
button(s) can be shown here in Figure 3.2.
37 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
• Ballast Mode
After warming up completely and when BALLAST MODE button ( ) is selected, valves will
arrange for water to enter ballast tank. Water will flow from the seachest, through the pipeline
and into the ballast tank:
38 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
• De-Ballast Mode
When DE-BALLAST MODE ( ) button is selected, valves will arrange for discharging water
overboard. Ballast water will flow from ballast tank through the pipeline overboard:
39 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
• Bypass Mode
When BYPASS MODE ( ) button is selected, valves will arrange for discharging water
overboard. Ballast water will flow from seachest through the pipeline overboard:
BYPASS MODE is designed to pass the system and to discharge directly overboard and is
activated in the following situations:
Bypass normally occurs due to a trip or an error and it is used to reset the system. While
suction and ballast valves are closed, seachest and overboard valves will be opened during this
mode. On the other hand, bypass also available if the position of switch control indicates
BYPASS. All external valve(s) can be controlled by the operator and valve status will be
recorded (Refer to Figure 3.22 Status log files). This mode can be used without the system
operation while the ballast pump is activating, and it is also able to transfer water between tanks.
40 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
When EDUCTOR MODE ( ) button is selected, valves will arrange for discharging water
overboard. Ballast water will flow from ballast tank through the pipeline overboard:
Normal stripping process can be shown here in Figure 3.6, and de-ballast, outlet valves activate
automatically in EDUCTOR (STRIPPING) MODE.
The VRC (Valve Remote Control) system contributes to organize relevant valves for the warming
up process.
41 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
When an alarm occurs during system operation, the ALARM HISTORY button ( ) located on
the right side of the HOME screen will flash, and at that time, operator should select the now
red colored button marked ALARM HISTORY ( ). The flashing red alarm and the audible
alarm will stop when the ACK button ( ) is selected. This will acknowledge the alarm
and reset the ALARM HISTORY indicating color back to white. The audible alarm will stop and
reset when the BUZZER STOP button ( ) is selected.
To scroll the list up and down to check the alarm history use the UP ( ) and DOWN ( )
arrow keys.
When the ( ) button is selected, the cursor will move right onto the next page.
When the ( ) button is pressed, the cursor will move left onto the previous page.
The OPERATING LOG button ( ) will advance the screen onto the OPERATING LOG page.
42 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
• Operating Log
When an operator selects the OPERATING LOG button ( ) located on the right upper
side of the screen, all the system operational information will appear (as shown below in Figure
3.8). All operational information of the filter unit, UV unit and valves are recording in the
system’s memory for as long as twenty-four (24) months.
The log and the real-time readings can be sorted by year, month, day and time. In order to set
up or change values in the OPERATING LOG, you must first login with a created password. To
save any records in the OPERATING LOG, the password will again be required.
To scroll the list up and down to check the operation log use the UP ( ) and DOWN ( )
arrow keys.
When the ( ) button is selected, the cursor will move right onto the next page.
When the ( ) button is pressed, the cursor will move left onto the previous page.
43 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
When an operator selects the SYSTEM STATUS button ( ), the status list of all control positions
will show on-screen. If an operation is on, the indicator lamp will be orange. If an operation
is off, the indicator lamp will be gray.
Parameter Explanation
POWER ON Filter unit is on
MANUAL MODE FLUSHING Back-flushing is manually operated
Automatically initiates back-flushing (by using differential
DP MODE FLUSHING
pressure) when it is higher than set value
MOTOR FORWARD Back-flushing motor rotates forward
MOTOR REVERSE Back-flushing motor rotates in reverse
FLUSHING VALVE OPEN Back-flushing valve is open
AIR INLET VALVE OPEN Air inlet valve is open
DRAIN VALVE OPEN Drain valve is open
44 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
Parameter Explanation
POWER ON UV unit is on
MANUAL MODE CLEANING Wiper is manually operated
Automatically initiates wiper when intensity of UV lamps is less
INTENSITY MODE CLEANING
than set value
TIMER MODE CLEANING Automatically initiates wiper set time
MOTOR FORWARD Wiper motor rotates forward
MOTOR REVERSE Wiper motor rotates in reverse
AIR INLET VALVE OPEN Air inlet valve is open
DRAIN VALVE OPEN Drain valve is open
UV LAMP ON UV Lamp(s) are activating
Required warming up period for UV lamps (approximately 5
WARMING-UP
minutes) before UV lamps reach necessary intensity level
WARMING-UP TIME Displays remaining time before completed UV lamp warming-up
Required Cooling period for UV lamps (Default 5 minutes) after
COOLING (LAMP)
UV lamps are turned off
COOLING (LAMP) TIME Displays remaining time before complete Lamp Cooling
When an operator selects the UV LAMP RUN TIME button ( ), bellow information
will be pop up to check how long times relevant UV lamps are operated.
45 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
(4) Setting
When selecting the SETTING button ( ), the operator must first enter a security password.
It is required to set the control values for each parameter in order to use the GloEn-Patrol™
system safely.
The password is required for adjusting system pre-set settings (i.e. emergency situation, trip
condition). In case of power loss however, the system will automatically restore and resume
operation without needing to enter any passwords.
The display will indicate currently set values. A keypad will pop up when the indicated
value/number on the display is touched. The operator can change the value by entering a new
value and saving new value by selecting the enter ENT button ( ). The system will save
and update the newly set value once the operator selects the ENT button ( ). If
operator selects the CANCEL button ( ), the entered value will be canceled, defaulting to
the previous set value.
Setting a value not within the system’s preset range and selecting the ENT button ( ), the
value will not change reverting back to the default value.
46 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
The bottom portions of the SETTING screen shown in Figure 3.10 are for an operator to set the
WIPER ACTIVATION MODE in the following options:
Flushing
Mode Button Explanation
When selected, Mode will change to option of Back-flushing
DP Mode
will automatically activate when DP is higher than the set value
When selected, Mode will change to option of Back-flushing
Manual Mode will activate and will revert back to the previous mode (DP
MODE or TIMER MODE)
Cleaning
Mode Button Explanation
When selected, Mode will change to option of Wiper cleaning
Intensity Mode will activates when the intensity of the UV is lower than the set
value
When selected, Mode will change to option of Wiper cleaning
Timer Mode
will activate and operate at the set time duration
When selected, Mode will change to option of Wiper will
Manual Mode activate and will revert back to the previous mode (INTENSITY
MODE or TIMER MODE)
47 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
• Ballast Mode
After warming up completely and when BALLAST MODE button ( ) is selected, valves will
arrange for water to enter ballast tank. Water will flow from the seachest, through the pipeline
and into the ballast tank:
NOTE: Open the appropriate valves are located inline as below sequences by VRC.
NOTE: If above step(s) are not done properly, operator can NOT proceed.
48 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
e. Select the UV UNIT icon ( ) when flow rate reaches required level.
g. Required warming up period for UV lamps is approximately five (5) minutes before UV lamps
reach necessary intensity level. View the display for the remaining time before completed
lamp warming up is finished.
h. WARMING UP indicating lamp turns on until warming up process is completed then, it will
be flicker up.
i. Open the ballast valve, and then close the overboard valve in order.
a. Open the overboard valve, and then close the ballast valve from VRC system.
d. The UV lamp(s) will be turned off and UV cooling down process will be activated.
h. Draining will commence from the filter and UV unit after operating.8-
i. Water must be drained from the system by opening the drain and air inlet valves of the filter
and UV unit after operating in order to prevent the unit elements from corrosion.
NOTE: One (1) ~ Nine hundreds (900) minutes after BWMS operation is completed draining
process starts automatically. The drain time can be adjustable from one (1) minute to Nine
hundreds (900) minutes.
49 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
• De-Ballast Mode
When DE-BALLAST MODE ( ) button is selected, valves will arrange for discharging water
overboard. Ballast water will flow from ballast tank through the pipeline overboard:
NOTE: If above step(s) are not done properly, operator can NOT proceed.
50 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
e. Select the UV UNIT icon ( ) when flow rate reaches required level.
h. WARMING UP indicating lamp turns on until warming up process is completed then, it will
be flicker up.
i. Open the suction valve, and then close the sea chest valve from the VRC system.
j. The de-ballasting valve will open, and then the inlet and intermediate valves will close in
order.
a. Open the sea chest valve, and then close the suction valve from VRC system.
c. The UV lamp(s) will be turned off and UV cooling down process will be
activated.
d. During the UV cooling process, all valves will be reorganized as WARMING UP and then
automatically converted to BY-PASS MODE when UV cooling process is completed.
h. Water must be drained from the system by opening the drain and air inlet valves of the filter
and UV unit after operating in order to prevent the unit elements from corrosion.
NOTE: One (1) ~ Nine hundreds (900) minutes after BWMS operation is completed draining
process starts automatically. The drain time can be adjustable from one (1) minute to Nine
hundreds (900) minutes.
51 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
When EDUCTOR MODE ( ) button is selected, valves will arrange for discharging water
overboard. Ballast water will flow from ballast tank through the pipeline overboard:
Normal stripping process can be shown here in Figure 3.13, and de-ballast, outlet valves activate
automatically in EDUCTOR MODE.
From the VRC (Valve Remote Control) system contributes for the warming up process.
Once it completes, the ballast pump is able to operate.
NOTE: If above step(s) are not done properly, operator can NOT proceed.
52 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
a. Arrange valves for water to flow from driving (G/S, Fire) line through eductor and by-pass
valve to overboard.
d. Select the UV UNIT icon ( ) when flow rate reaches required level.
f. Required warming up period for UV lamps is approximately five (5) minutes before UV lamps
reach necessary intensity level. View the display for the remaining time before lamp
warming up is completed.
c. The UV lamp(s) will be turned off and UV cooling down process will be activated.
h. Water must be drained from the system by opening the drain and air inlet valves of the filter
and UV unit after operating in order to prevent the unit elements from corrosion.
NOTE: One (1) ~ Nine hundreds (900) minutes after BWMS operation is completed draining
process starts automatically. The drain time can be adjustable from one (1) minute to Nine
53 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
GloEn-Patrol™ BWMS requires for operators to completely drain the system by either
confirming open positions of all individual equipment drain valves during the draining
stage, by using the manual drain point(s) throughout the system after a predetermined
CAUTION number of ballasting operation, or after a set time interval.
• UV Alarm list
54 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
55 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
• UV Trip list
56 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
• Check Mode
Figure 3.14 shows that the screen appears if the select switch is turned to CHECK position on the
control panel.
4
Figure 3.14 Check Mode screen
PLC individual output can be controlled on this screen by selecting either ON/OFF icons ( /
). Selecting either ON/OFF icon(s) ( / ), each individual item can be checked
whether each item (i.e. motors, lamps) is properly operating.
The CHECK MODE screen changes to VALVE CHECK PAGE when selecting the VALVE CHECK button
( ) at the bottom of the CHECK MODE screen.
It is also available to change the screen to FILTER CLOGGING SOLUTION when selecting the
CLOGGING button ( ) at the bottom of the CHECK MODE screen.
NOTE: Do NOT change the select switch to CHECK while system is operating in either BALLAST /
DE-BALLAST MODE.
57 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
• Valve Check
The VALVE CHECK screen appears if the select switch is turned to CHECK position on the control
panel and selecting the VALVE CHECK button ( ) at the bottom of the CHECK
MODE screen.
4
Figure 3.15 Valve Check screen
When selecting the OPEN button ( ) on any of the valves on-screen, the valve should open.
When selecting the CLOSE button ( ), on any of the valves on-screen, the valve should close.
If the valve is opened, yellow ‘OPENED’ is indicated on STATUS window(s) and when valve is
closed, blue ‘CLOSED’ is indicated on STATUS.
If any valves do not work, the system has a problem and must be checked.
58 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
When system shuts down due to FILTER DP HIGH HIGH (Refer to Alarm and trip conditions)
situation, the filter clogging problem can be resolved by using this operation.
The FILTER CLOGGING SOLUTION screen appears if the select switch is turned to CHECK position
on the control panel, and then selecting the CLOGGING button ( ) at the bottom
of the CHECK MODE screen.
Step-by-step trouble shooting actions will pop-up on left side of screen for operator to review.
After solving the filter clogging problem, select the STOP button ( ) and change the
select switch to NORMAL.
59 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
To download data to user PC, installing the software on the PC is needed. At the time of
commissioning, the software will be set up on the user PC based on customer needs.
After the software is installed, data logs can be downloaded when the LAN cable is connected to
HUB’s RJ45 socket in the BWMS control panel and the PC.
Put the CD into the PC and run the installation file in the CD ROM drive.
60 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
Click the next button to continue. Click the install button to continue.
61 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
After connecting LAN cable to HUB’s RJ45 and the PC, run the Transfer Tool icon on the Window
screen. Figure 3.18 shows the Transfer Tool screen.
After selecting the Transfer Tool window, select Transfer Settings button. The Transfer Settings
window will popup. Select LAN and Transfer CF/SD card data as shown in Figure 3.19, and then
select OK button.
Next, select the CF/SD Card Connection ( ) button in Transfer Tool window.
In the CF/SD Card Connection window, select the Connect Online button and select the OK
button otherwise the system will shut down when selecting the Connect Offline shown below in
Figure 3.20.
62 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
Figure 3.21 shows the CF/SD Card Explorer window. Double click the Alarm folder and the folder
contents will popup as shown below in Figure 3.21(a).
(a) (b)
(c)
Figure 3.21 Contents of CF/SD Card
Select and drag files to desired folder in the Explorer window (Figure 3.21(b)).
After saving all files, you must close all windows and check the following saved files:
63 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
Figure 3.22 Alarm file (top) and Status log file (bottom)
➢ Alarm & status data’s names are referenced by the first and second digits
are the month, third and fourth the year, and the fifth digit is the number
of file.
NOTICE ➢ Analog sampling data’s names are referenced by the first and second digits
are day, third and fourth are month, and the fifth digit is year.
64 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
IV. HEALTH AND SAFETY RISKS TO THE PERSONNEL ASSOCIATED WITH THE
INSTALLATION, OPERATION AND MAINTENANCE OF GloEn-Patrol™
The GloEn-Patrol™ Ballast Water Management System is designed for simple and easy operation.
Although the BWMS will not generate any active substances, the system must be operated by
properly trained staff. Please follow all the instructions in this document for personnel safety.
In addition, an operator must be familiar with these instructions during operation and
maintenance.
Operations and maintenance personnel should read and fully understand prior to working on
the system in accordance with applicable safety rules. Following the instructions in this manual
will describe for general safety during installation, operation and maintenance of GloEn-Patrol™
so that it prevents personnel injury or fatality or damage to equipment.
The filter is a mechanical device, causing little to no danger, but the following instruction must
be taken for safety.
• General instruction
✓ Prior to installation and/or operation, review the installation and operation instructions
thoroughly;
✓ While operating the filter, all conventional safety instructions should be observed in
order to avoid harm to operators property and others in the vicinity;
• Installation
✓ Install the filter according to the installation instructions detailed in this manual (Refer
to Figure 7.1 through 7.8);
✓ Make sure to leave ample clearance for easy and safe access for installation, operation
and maintenance;
✓ Avoid water contact on the electrical components or on the control panel while
installing the filter.
65 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
✓ Removing bolts should be done only after the pressure in the filter has been released;
✓ Avoid moisture build-up (i.e. splashing and/or water leaks) minimize slipping or
electrical dangers;
• Filter Sludge
The GloEn-Patrol™ does not discharge nor creates byproducts due to the UV technology.
However, a pre-treatment filter is installed prior to the UV unit to eliminate sludge and sea
creatures larger than 50 microns. The filter accumulates large particles and organisms inside of
the filter screen. Over time, the large particles must be removed to maintain the filter
efficiency. A back-flushing cleaning system has been installed to return large particles to the
local water, so BWMS will not pollute to the marine environment at all.
Prior to installation or handling of the UV unit, read the operating and maintenance manual and
follow caution signs carefully.
• Grounding
Ensure that all the equipment, especially the UV chamber, be grounded by using an adequate
cross section of the conductor, and it complies with local electrical wiring regulations.
• Ultraviolet light
While in use, the UV lamps emit high intensity Ultraviolet (UV) radiation, which may damage to
the eyes and any exposed skin.
➢ Do NOT operate the UV lamp without wearing personal protections for test!
➢ Do NOT look at the UV light, when the UV lamp is switched on!
CAUTION
66 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
• High Voltages
• High Temperature
The UV lamp temperatures will reach up to 600C ~ 800C during normal operation, and the
ceramic supports of the UV lamps retains heat for a while after they have been powered off.
• Mercury
The UV lamp contains a small amount of Mercury. Great care should be taken to avoid any
breakage of the lamp. Dispose of UV lamp(s) safely, complying with local environmental rules
and regulations. UV lamp(s) must be stored in their original packing until required for use.
The UV unit with purge/ pressurization system is specially installed for operating in hazardous
area and is a pressurized enclosure.
The enclosure shall not be opened unless the area is known to be free of flammable materials or
unless all devices have been de-energized. Power shall not be restored after enclosure has
been opened until enclosure has been purged in accordance with the purge system start up
instructions.
67 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
Service Engineer
Water - Local inlet/outlet valves with isolation
Operator
(Pressure) WARNING tags (operator responsibility)
Installer
68 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
B. Material safety data sheets for hazardous or relevant chemicals used, stored, or
generated by or for the system.
69 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
70 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
71 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
72 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
73 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
74 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
The GloEn-Patrol™ system is designed and built for easy, simple and efficient operation.
Operators nevertheless, must take proper steps to assuring the personal and vessel’s safety by
reading and thoroughly understanding this manual and subsequent training. In addition to this
instruction manual, general applicable safety rules and regulations must be observed at all times.
• Keep your work area clean and tidy; make sure it is properly illuminated.
• Keep the control panel closed during normal use.
• Carry out proper maintenance on a regular basis.
75 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
• Design recommendations
For multi-filter applications, if flow increases and pressure drops drastically, it is recommended
that a pressure-sustaining valve be installed upstream of the filters in order to ensure a
controlled fill-up to the line flow and pressure stability.
• Installation instructions
✓ Install the filter in a way which will allow sufficient space to dismantle and separate the
Filter for maintenance purposes;
✓ Confirm the flow direction according to the inlet and outlet marked on the filter
housing;
✓ Connect pipe to the back-flushing valve. The back-flushing pipe should be designed
so that it creates minimal resistance to flow;
✓ Operator should arrange for suitable lighting in the area of the filter to enable good
visibility and safe maintenance;
✓ Operator should arrange for suitable platforms and safety barriers to enable easy and
safe access to the filter.
Filter body must be supported by the lugs to floor. Maintenance space (“A”) is needed above
the filter to lift the unit by device hooks as below Figure 5.2 and Figure 5.3: If needed, install an
access floor for maintenance to replace the filter element.
76 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
77 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
78 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
• Installation recommendations
79 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
Figure 5.5 Installation support for the UV unit (Vertical Type: Bottom support)
80 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
Figure 5.6 Installation support for the UV unit (Vertical Type: Wall mount)
81 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
Figure 5.7 Installation support for the UV unit (Horizontal Type: Bottom support)
82 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
To remove any accidental finger marks on the UV lamps, use isopropyl alcohol and a cloth.
➢ Never touch a UV lamp with bare fingers. Use a tissue or cotton gloves
when handling UV lamp(s).
CAUTION
NOTE: When UV lamps are cold, Mercury may condense in patches on the inner surfaces and
appear as finger marks. This is normal and will NOT affect lamp efficiency.
The quartz sleeve forms a water-tight barrier between UV lamps and the treated water. It is
essential that the sleeves are kept clean, or possible reduction of UV intensity will reduce the
effectiveness of treatment.
The quartz sleeves should be handled with care. Iron and/or carbonate deposits from hard water
may develop. If so, clean sleeves with a 5% citric acid, wash off with water and dry carefully.
Replacement of sleeves will be necessary if the deposits cannot be removed.
The UV intensity sensor should be cleaned periodically with isopropyl alcohol, ideally whenever
the quartz sleeves are also being cleaned.
If the system is set in Dose control, no adjustment is necessary. As the wiper passes the
monitor, UV intensity will drop for a few seconds, which is normal occurrence.
83 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
The UV unit is controlled by the PLC, enclosed in the control panel, but UV lamps and wiper
motor are connected to UV power supply panel. Temperature transmitter, UV intensity
transmitter, two level switches and two reed switches and purge/pressurization system (for Ex
proof model) are also connected to control panel.
Refer to each drawing for detail connection. The technical section (schematic diagram of the
monitoring system, electrical wiring diagrams enabling faultfinding and other additional
drawings) is to be kept in a maintenance record, separately supplied to ship owner and shipyard.
➢ The drawings for the above descriptions can be found in Wiring Diagram that provided by
manufacturer.
84 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
➢ Intrinsically safe cable must be applied to the line between the Purge
Control Unit and Relief Vent, and between the Temperature Transmitter and
the Control Panel through the safety barrier.
➢ Intrinsically safe cable must be separated away at least 50mm from the
common cable(s).
CAUTION ➢ For replacement of safety barrier, see the following electric data of the
temperature transmitter.
- Signal output / supply, terminal 1 to 2:
- Ui: 30 VDC, Ii: 120 mADC, Pi: 0.84 W, Li: 10 μH, Ci: 1.0 nF.
Installation of a sampling valve in the GloEn-Patrol™ system complies with USCG ETV and IMO
G2 regulation. A sampling valve is installed at the nearest practical discharge point.
Furthermore, sampling valves can be installed at the inlet and/or outlet points per the
shipowner’s request keeping the following considerations:
The install location must be accessible by operator(s) and door clear to mount the control panel
and UV power supply panel(s). Except specific purpose of using, it should be installed dry area
against water ingress.
85 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
✓ The highest point or in the draining-off side of a pipeline which could increase the risk
of air accumulating;
✓ Directly upstream from a free pipe outlet in a vertical pipeline.
<Incorrect> <Correct>
If possible, install the sensor well clear of assemblies such as valves, manifolds, fittings etc. in
front of the meter tube. Note the following inlet and outlet runs to comply with measuring
accuracy specifications;
86 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
The following list of troubleshooting situations will identify the cause and action(s) needed to be
taken onboard during operation. It must be executed by authorized and/or certified persons
who have been trained properly to operate the GloEn-Patrol™ system. Troubleshooting
situations are designated by Alarm and Trip conditions.
Alarm indicates that differential pressure is over 0.6 kg/cm2 for longer than 60 seconds.
Alarm indicates that inlet pressure is lower than set value (Default = 1 kg/cm2).
87 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
Alarm indicates that the back-flushing motor has exceeded maximum set point.
88 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
Trip indicates that filter back flushing motor does not work properly
89 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
Alarm indicates that the wiper motor has experienced a mechanical overload.
Alarm indicates that the UV dosage is below than 250mJ/cm2 for longer than 50 seconds.
90 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
91 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
Trip indicates that the UV dosage is lower than 230mJ/cm2 for longer than 60 seconds.
92 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
93 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
94 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
Alarm indicates that the flow meter does not work properly
95 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
Alarm indicates that ballast valve and/or suction valve are opened during by-pass operation.
Alarm indicates that operator intended to turn UV lamp on while it is not available.
96 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
Alarm indicates that there is a loss of communication between PLC to GPS module.
Trip indicates that main power is not supplied and/or circuit breaker(s) is damaged.
Trip indicates that the ballast pump is shut down while UV lamp is operating.
97 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
Trip indicates that suction valve is opened before warming up of UV lamp completed.
Trip indicates that suction valve is opened before warming up of UV lamp completed.
98 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
A. Use of tools and test equipment in accordance with the maintenance procedures
• Weekly maintenance
Check that sufficient grease is applied on the drive shaft and drive bushing. If necessary add
additional grease.
Take care of any leaks from the scanner shaft. If necessary, tighten the gland packing or replace
the sealing materials.
If the BWMS will not operate for more than a month, complete the following steps;
✓ Manual back-flushing of the filter for cleaning (if possible, cleaning with fresh water).
✓ Disconnect the power of the control panel and UV power supply panel.
✓ Drain the inside of the filter.
✓ Grease the drive shaft and drive bushing.
Prior to dismantling the filter elements, it is recommended that manual back-flushing operation
should be completed prior to disassembly.
✓ Close the Filter inlet and outlet valves and release the pressure;
✓ Press the MANUAL BACK-FLUSHING button on the control panel;
✓ Disconnect the power when the scanner is in the middle of its track.
99 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
B
Remove the B/F Drum (B) after unscrewing
bolts (A).
4.
Unscrew the bolts from the flange of filter A C
body (C).
100 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
101 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
• Suction scanner
When the differential pressure inside the filter reaches the set value, filter cleaning (back-
flushing) is automatically activated and ballasting is uninterrupted during cleaning. Several
cleaning (scanner) heads scan over the filter screen surface with a “corkscrew-like” rotational
and an up & down, vertical motion by an electric motor and un-clog trapped materials. Back-
flushing pump (optional) runs simultaneously with the scanner to discharge the flushing water
from the filter overboard so that differential pressure will be decreased.
102 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
NOTE: This drawing is an example for the shape of filter unit. Please refer to each project’s final
drawing for each code/part No. and size.
Element of Filter 1 1 1 1
103 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
104 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
105 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
106 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
107 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
Element of Filter 3 4 5 7 9 11
108 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
109 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
110 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
111 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
The quartz sleeve(s) must be cleaned regularly. The frequency of cleaning will depend on
water quality. When the measured UV intensity is below than set value (290mJ/cm2)
automatic wiper-cleaning will activate.
If the quartz sleeves are still not cleaned by auto-wiping, it should be manually cleaned with
alcohol. Cleaning must be accomplished as follows:
The UV intensity sensor measures the efficiency of the UV lamps in combination with the level
of UV transmittance of the water. A quartz window on the inside of the disinfection chamber
covers the measuring surface of the sensor.
Build up may occur on this window and has a negative effect on the UV measurement. If the
system does not have a built-in cleaning mechanism the quartz window should be cleaned
chemically as described below.
➢ Turn OFF the main switch and the circuit breakers in the control panel.
➢ Turn OFF the flow and drain the liquid in the disinfection chamber.
➢ Remember that the lamps can be HOT.
WARNING
Procedure describes the actions required to replace lamp(s) and to clean and/or replace quartz
sleeves.
➢ Turn OFF the main switch and the circuit breakers in the control panel.
➢ Turn OFF the flow and drain the liquid in the disinfection chamber.
WARNING ➢ Remember that the lamps can be HOT.
➢ Wear clean gloves free of talcum powder and grease to avoid damaging the
lamp(s).
➢ Regarding the handling Mercury (Hg) vapor within the lamps must be cared
CAUTION in accordance with Material Safety Data Sheet (MSDS) in this document.
112 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
113 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
B
Take the spring (A) and anti-vibration stopper (B)
5. A
out of the quartz sleeve.
B
On both ends use tool (A) to unscrew the A
7. isolating T/B body (B) from the chamber end
plate.
A
114 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
12. Wear clean gloves and hold the lamp at the ends. O
115 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
NOTE: When inserting the lamp, don’t arrange joint connection of exhaust on the lamp and UV
intensity sensor in a straight line. If they are in a straight line, UV intensity is measured lower.
116 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
It is difficult to check the faulty UV lamp(s) if the UV lamp(s) have been already installed in the
UV chamber. In order to reduce inconveniences, a UV lamp test kit comes with the BWM
system. As this test kit is applicable to check the UV lamp(s) on a vessel without dismantling
many parts, it contributes to decrease maintenance costs and working hours.
Material ABS
Input Voltage AC 110V/220V
Weight 0.6kg
Figure 7.14 UV Lamp Test Kit
➢ Do NOT test during BWMS operation (it MUST be power off before using
the test kit).
➢ Do NOT touch the clamps while the POWER OUTPUT LED lamp turns on due
to a high risk of electric shock.
➢ Do NOT supply exceeding 220VAC for the TEST KIT.
➢ NEVER touch a UV Lamp with bare fingers. Use a tissue or cotton gloves
when handling UV Lamp(s)
CAUTION ➢ UV Lamp contains a small amount of Mercury. UV Lamp(s) must be stored
in the original packing until required for use.
➢ Used UV Lamp(s) must be returned to PANASIA CO., LTD.
➢ Do NOT dispose old UV Lamp(s) as unsorted municipal waste.
➢ Waste must be disposed of in accordance with federal, state and local
environmental control regulation.
117 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
It is designed to use as free voltage so it includes common plug for 110VAC. The one set of test
kit will be supplied with 5 spare fuses. Description on each part is shown in figure 7.10. See the
table 7.4 for test procedure.
118 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
119 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
See below the detailed table of maintenance of the automatic cleaning mechanism.
➢ Turn OFF the main switch and the circuit breakers in the control panel.
➢ Turn OFF the flow and drain the liquid in the disinfection chamber.
WARNING ➢ Remember that the lamps can be HOT.
➢ Wear clean gloves free of talcum powder and/or grease to avoid damaging
UV lamp.
CAUTION
A
B
On wiper motor side use flat spanner (A) to
2. unscrew the screw plug adopter (B) from the
chamber end plate.
120 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
121 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
B
A
7. Take wiper (B) out of the wiper holder (A).
122 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
UV Lamp 2 6 8 12 18 24
Wiper Motor 1 1 1 1 1 1
123 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
124 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
125 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
126 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
Figure 7.24 Purge/Pressurization system & Purge Vent Unit (Explosion proof type)
127 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
UV Lamp 22 26 32
Wiper Motor 1 2 2
128 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
129 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
8 MOTOR 85 CONDENSOR:2UF
36 SUPPORT BAR 86 R/BOLT
36-1 MOTOR SUPPORT BAR NUT 87 H/BOLT(N, P/W, S/W)
37 COUPLING 91 TERMINAL BLOCK
72 MOTOR SUPPORT 92 R/BOLT(B,S/W)
Figure 7.27 Disassembly of UV Unit Element (Reducer Motor)
130 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
131 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
132 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
133 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
134 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
Figure 7.33 Purge/Pressurization system & Purge Vent Unit (Explosion proof type)
135 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
Check the Earth Leakage Circuit Breaker (ELCB) monthly by pressing the test button to make
sure it is working properly. The system will shut-down immediately.
1) CBN001: Main circuit breaker for the entire BWMS monitoring system.
136 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
9) NF1: Noise filters to stabilize power which is supplied to the power supply of PLC.
10) PLC: Controller for the entire monitoring system, from left to right: Power Supply, CPU, Digital
Input (DI), Digital Output (DO), Analog Input (AI) and Analog Output (AO) modules.
13) TB: Common terminal block for power line of PLC system.
14) PO: 220VAC power supply outlet for auxiliary equipment (i.e. laptop).
16) MONITORING UNIT: Graphic panel with touch screen functions for control and monitoring.
19) BZ: Alarm device when there is any abnormality in the monitoring system.
137 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
23) ELCB S101~S102: Device to stop the UV system under any abnormal condition by detecting a
leakage current, which could be generated in operating an UV lamp, and each ELCB connected to
two (2) electromagnetic ballast.
24) CBS121~125: Circuit breaker for the UV lamps, and installed two (2) breakers depending on
number of electromagnetic ballast installed.
25) CBS101, CBS141: Circuit breaker for the back flushing motor and wiper motor.
26) CBS100: Circuit breaker for control circuit (i.e. cooling fan, etc.).
27) CPS11: Surge protector, protecting control and driving circuits from switching surges, generated
at times of controlling the main circuit breaker.
28) EBS101~S104: Electromagnetic ballasts for discharging lamps to operate UV lamps. Each
controls two (2) UV Lamps
29) SC101~128: UV lamps capacitors connected to the secondary of electromagnetic ballast. Each
electromagnetic ballast has three (3) capacitors independently.
30) SC151~154: Capacitors for power control of UV Lamps (Step 1; 88% of maximum power)
138 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
31) SC171~174: Capacitors for power control of UV Lamps (Step 2; 72% of maximum power)
32) MCS1FF: Forward-turn electronic switch of three-phase motor used for filter flushing.
MCS1FR: Reverse-turn electronic switch of three-phase motor used for filter flushing.
MCS101~105: Electronic switches for UV lamps operation control. Each controls two (2) UV
lamps.
34) EUCRS101~104: Device to stop the UV System under any abnormal conditions by detecting an
undercurrent, generated by operating an UV lamp. Each controls two (2) UV lamps.
37) FAN S101~106: Cooling fans (side) that discharge the internal air outside the panel.
38) FAN S107: Cooling fans that (top) discharge the internal air outside the panel.
139 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
This spare part list is standard. For the information on quantity of each spare part, see the final
drawing.
Spec. Weight
No. Name Illustration Model Remark
(Mat’l) (kg)
SPARE
1 Spare Box SS400 18 -
BOX-STD
140 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
141 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
Spec. Weight
No. Name Illustration Model Remark
(Mat’l) (kg)
142 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
143 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
Spec. Weight
No. Name Illustration Model Remark
(Mat’l) (kg)
144 | P a g e
Ballast Water Management System GloEn-PatrolTM_Ver.6.2N
145 | P a g e