FMDS0135
FMDS0135
FMDS0135
Table of Contents
Page
©2020-2023 Factory Mutual Insurance Company. All rights reserved. No part of this document may be reproduced,
stored in a retrieval system, or transmitted, in whole or in part, in any form or by any means, electronic, mechanical,
photocopying, recording, or otherwise, without written permission of Factory Mutual Insurance Company.
1-35 Vegetative Roof Systems, Occupied Roof Areas and Decks
Page 2 FM Global Property Loss Prevention Data Sheets
List of Figures
Fig. 2.2.5.1-1. Example of non-vegetated border zone detail at parapet wall .............................................. 8
Fig. 2.2.16-1. Recommended roof expansion joint detail ............................................................................ 13
Fig. C.2.1-1. Modular trays being installed ................................................................................................... 25
Fig. C.2.1-2. Sample extensive vegetative roof assembly ........................................................................... 26
Fig. C.2.2-1. Sample intensive vegetative roof assembly ........................................................................... 26
Fig. C.2.2-2. Extensive vegetated roof with small hill and no concealed space ........................................ 27
Fig. C.2.2-3. Extensive vegetated roof with combustible concealed spaces .............................................. 27
Fig. C.2.2-4. Tree truck and roof ball secured with concrete deadman weights ........................................ 28
Fig. C.2.2-5. Wood deck on plastic pedestals on extruded polystyrene (covered by landscaping fabric)
forming a combustible concealed space ................................................................................ 29
Fig C.2.2-6. Rooftop concrete pavers elevated ½ in. (13 mm) above extruded polystyrene
(covered with landscape fabric) using plastic pedestals ......................................................... 29
Fig. E-1. Extensive vegetative roof, Chicago City Hall, Chicago, Illinois, USA (C 2005, Roofscapes, Inc.,
used by permission; all rights reserved) ....................................................................................... 31
Fig. E-2. Extensive vegetative roof with sedums (courtesy of Genzyme Corp.) ........................................ 31
Fig. E-3. Extensive vegetative roof Life Expression Wellness Center, Sugar Load, Pennsylvania, USA
(C 2005, Roofscapes, Inc., used by permission; all rights reserved) .......................................... 32
Fig. E-4. Extensive vegetative roof at time of installation; Montgomery Park Business Center,
Baltimore, Maryland, USA (Courtesy of Katrin Scholz-Barth). ..................................................... 32
Fig. E-5. Extensive vegetative roof 10 months after installation; Montgomery Park Business Center,
Baltimore, Maryland, USA (Courtesy of Katrin Scholz-Barth and Kai-Henrik Barth) ................... 33
Fig. E-6. Extensive vegetative roof 2 years after installation; Montgomery Park Business Center,
Baltimore, Maryland, USA (Courtesy of Katrin Scholz-Barth) ...................................................... 33
Fig. F.1-1. Ratings Calculator ...................................................................................................................... 34
Fig. F.2.2-1. Assembly Search view ............................................................................................................ 34
Fig. F.2.2-2. Specifications view .................................................................................................................. 35
Fig. F.2.2-3. Coating/Surfacing Details view ................................................................................................ 35
Fig. F.2.2-4. Coating/Surfacing Details saved ............................................................................................. 36
Fig. F.2.2-5. Search Results ........................................................................................................................ 36
Fig. F.3.1-1. Product Search view ............................................................................................................... 37
Fig. F.3.1-2. RoofNav’s Search Results ...................................................................................................... 37
Fig. F.3.1-3. Product Detail Report .............................................................................................................. 38
Fig. F.4.1-1. Coating Surfacing Details ........................................................................................................ 38
Fig. F.4.1-2. Saved Specifications view ....................................................................................................... 39
Fig. F.4.1-3. Search results view ................................................................................................................. 39
Fig. G.2-1. Final test assembly with plastic pedestals ................................................................................ 40
Fig. G.2-2. Test assembly at approximately 9:24 into the test .................................................................... 41
Fig. G.2-3. Aftermath of the fire test, prior to disassembly ......................................................................... 41
Fig. G.2-4. First row of wood deck tiles removed ....................................................................................... 42
Fig. G.3-1. Final test assembly with steel pedestals ................................................................................... 42
Fig. G.3-2. Close-up of final test assembly showing 15/16 in. (24 mm) layer of latex modified
cement on extruded polystyrene ............................................................................................... 43
Fig. G.3-3. Test assembly at approximately 9:24 into the test .................................................................... 43
Fig. G.3-4. Ipe wood deck tiles prior to disassembly ................................................................................... 44
Fig. G.3-5. Leading edge of test assembly showing intact joint ................................................................. 44
Fig. G.3-6. Modified latex cement surface (Ipe wood tiles and pedestals removed) ................................. 45
List of Tables
Table 2.2.10-1. Reasonable Minimum Design Loads by Type of Vegetation .............................................. 10
1.0 SCOPE
This data sheet provides guidance for selecting and installing vegetative roof systems, occupied roof areas
and decks. These structures may also be known as landscaped roofs, roof-top gardens, roof-top parks, roof
terraces, plazas and lounge areas. They are installed on or above the roof or waterproofing membrane
assembly.
This data sheet does not address structures such as penthouses or roof mounted solar photovoltaic panels.
Follow applicable FM Global Data sheets for guidance on roof-top structures and penthouses and FM Global
Property Loss Prevention Data Sheet 1-15, Roof Mounted Solar Photovoltaic Panels.
Vegetated roofs, combustible decks and other combustibles should only be installed in areas not susceptible
to wildland fire per Data Sheet 9-19, Wildland Fire.
1.1 Hazards
1.1.1 Collapse
Additional loads from vegetative roofing, roof-top decks and other roof-top installations to convert a roof to
an occupied space can be significant and must be considered to determine possible reinforcement needs for
existing roofs and proper design for new roofs. Failure to do so could result in collapse due to overload or
excessive deflection that could also result in excessive ponding.
In addition to strength, structural stiffness is also critical. Stiffness governs the amount of deflection the roof
structure will experience when loaded. A roof structure that has sufficient strength may not necessarily
possess sufficient stiffness. If stiffness is insufficient, a progressive deflection scenario can develop from
ponding water (from rain, melting snow, or un-checked irrigation) resulting in collapse. Ponding water is a
concern with all roof systems, but of particular concern with vegetative roof systems because of the large
amount of water that can be retained in the system.
Existing steel-framed buildings with steel roof decks will likely need structural strengthening and stiffening
to properly support a new vegetative roof system.
Proper drainage is also critical to ensure overloading does not occur, especially considering the large amount
of water that can be retained in the system.
1.1.4 Fire
A wide range of fire hazards can be associated with vegetative roofs, roof decks and occupied roof spaces.
For instance, a vegetative roof introduces large continuous plant cover that could spread fire. In addition,
these systems can utilize layers of combustible materials within the assembly, such as plastic mats, barriers,
insulation, protective boards and pre-cultivated vegetative mats that use synthetic or natural fiber fabrics.
Roofs that are designed or converted to an occupiable space may include elevated decks and contouring
(landscaping) that create large, continuous, combustible concealed spaces where fire could spread. Detection
and control of such a fire could be very difficult given the concealed and inaccessible nature of the space
as well as the concerns for the safety of emergency responders.
Additional fire hazards could be present from amenity installations including furniture, rooftop bars and
restaurants, pergolas and temporary installations for special events.
1.1.5 Earthquake
Vegetative roof systems and other rooftop installations associated with making a roof an occupiable space
can add significant mass to the roof of a structure. For existing construction, the original structural design
would not have accounted for this increased mass, nor the associated increased lateral loads induced during
a seismic event.
1.1.6 Hail
The growth media layer normally provides substantial protection to waterproofing membranes from hail
impact. However, areas of membrane without growth media or hardscape surfacing (e.g., vertical surfaces
at curbs or parapets) as well as other rooftop installations will be exposed to hail impact just as with a
conventional roofing system.
In addition, hail can be expected to damage some of the roof vegetation, wood decks and furniture.
1.2 Changes
January 2023. Interim revision. The following changes were made for this revision:
A. The title of this Data Sheet was changed to Vegetative Roof Systems, Occupied Roof Areas and Decks
from Vegetative Roof Systems.
B. The restriction on vegetative roof systems to areas where the wind speed is less than 100 mph
(63 m/s) has been removed and guidance added for growth media when the windspeed is greater than
or equal to 100 mph (63 m/s).
C. Added guidance for intensive vegetative roof systems including decks and when areas are elevated
above the roof assembly.
2.1 Introduction
2.1.1 Use FM Approved equipment, materials, and services whenever they are applicable and available.
For a list of products and services that are FM Approved, see the Approval Guide and RoofNav, online
resources of FM Approvals.
2.1.2 Install the roof deck, above-deck waterproofing components, and stone or concrete paver ballast in
accordance with Data Sheet 1-29.
2.1.3 Use FM Approved flashing or coping selected and installed in accordance with Data Sheet 1-49,
Perimeter Flashing.
2.1.4 For best performance from wind in all geographic areas, select non-vegetative surfaced FM Approved
roofs using RoofNav and following Data Sheets 1-28, 1-29 or 1-31. Vegetative roof systems approved to
FM Approval Standard 4477 have not had the portion of the roof above the waterproofing membrane tested
for wind uplift or wind scouring. All vegetative surfacing, bushes and trees will experience wind scouring.
A. 1/2 in. (12.5 mm) diameter growing medium (100% passing ½-inch (12.5 mm) sieve), with a saturated
particle density ≤ 1.4 g/ml (0.051 lb./in.3)
B. 3/8 in. (9.5 mm) growing medium 100% passing 3/8-inch (10 mm) sieve) with a saturated particle density
> 1.4 g/ml and ≤ 1.7 g/ml.
Density thresholds noted here are for the saturated aggregate particle - not bulk density or unit weight that
account for the voids and degree of compaction for a layer of aggregate.
Do not use pea gravel.
2.2.2.3 Extensive (shallow) Vegetative Roof Assemblies with Concealed Air Space(s)
2.2.2.3.1 Use only non-combustible materials in the concealed air space. This includes the support system
such that there are no exposed combustible materials within the air space including pedestals, framing,
structural decking, trays or drainage mats etc.
2.2.2.3.2 Use RoofNav to select an FM Approved assembly with vegetation surfacing with a class A rating
for exterior fire exposure. See Appendix F Using RoofNav to Select Vegetative Roof Assemblies.
The vegetation surfacing (FM Approved vegetation and drainage mats, etc.) will be supported, typically by
grates and pedestals, creating a concealed air space.
2.2.2.3.3 Use RoofNav to select one of the following roof assemblies for installation on the roof deck:
(The support structure for the vegetative assembly, commonly grates and pedestals, will be on this roof
assembly creating a concealed air space between this assembly and the underside of the vegetative
assembly.)
1. An FM Approved assembly with concrete paver surfacing. See Appendix F, Using RoofNav to Select
Vegetative Roof Assemblies.
These protected membrane roof assemblies have extruded polystyrene (XPS) insulation boards adhered
with hot asphalt to the built-up roofing plies and topped with loose laid concrete pavers. All have a 1-90 roof
rating but can be used for any recommended wind rating when the XPS boards and multi-ply roofs are fully
adhered to concrete decks.
Concrete pavers and the polystyrene boards in the FM Approved assembly can be replaced with extruded
polystyrene (XPS) insulation boards with a factory laminated, latex modified cement topping having a
minimum thickness of 15/16 in. (24 mm). These boards are still adhered to the built-up roofing plies with hot
asphalt.
2. An FM Approved roof assembly for low slope roofs topped with loose laid concrete pavers with a slip
sheet between the concrete pavers and the roof cover. The combination of slip sheet and paver should be
acceptable to the roof manufacturer.
Use minimum 2 in. (51 mm) thick concrete pavers meeting ASTM International, ASTM C1491-18, Standard
Specification for Concrete Roof Pavers, 2018.
2.2.2.4.2 Use RoofNav to select an FM Approved roof assembly compatible with the vegetative surfacing.
2.2.2.5 Intensive or Semi-Intensive Roofs including Hardscapes and Decks with Concealed Air Spaces
2.2.2.5.1 Follow recommendations 2.2.2.3.1 and 2.2.2.3.3.
2.2.2.5.2 Use roof-top vegetation and hardscaped areas from a designer experienced in this construction,
and follow guidance in Section 2.2.15 Vegetation Roof Components and Section 3.0, Support for
Recommendations.
Determine minimum design roof live load requirements in accordance with Data Sheet 1-54, Roof Loads
for New Construction, with the following restrictions:
A. For extensive vegetative roofs (see Appendix A for definition), use a minimum roof live load of no less
than 12 psf. (0.58 kPa), even when considering live load reduction.
B. For intensive and simple intensive vegetative roofs (see Appendix A for definitions), use a minimum
roof live load of no less than 20 psf. (0.96 kPa), even when considering live load reduction.
C. For systems where people are expected or encouraged to congregate, such as in such assembly areas
(similar to balconies, terraces, etc.), design the supporting roof structure to support a minimum roof live
load of 100 psf. (4.8 kPa).
3. Environmental Loads
Design snow and rain loads in accordance with Data Sheet 1-54, Roof Loads for New Construction. Consider
transient water to be part of the total rain load.
2.2.12.3 Include the weight of rainwater (based on the depth required to achieve the secondary drainage
design capacity) in the roof design load. Consider potential ponding resulting from roof deflections.
2.2.12.4 Provide drainage systems designed to conform to the more stringent of the following conditions:
A. The vegetative roof system as proposed
B. The roof with a traditional roof cover (i.e., without the above-membrane vegetative roof assembly)
2.2.12.5 Provide drains and outlets that have inspection chambers with removable covers, allowing for easily
accessible inspections to ensure plants, growth media, and gravel do not restrict or reduce flow.
2.2.12.6 Ensure the drainage design accounts for vertical sheet flow from large facades due to wind-driven
rains in addition to that from horizontal roof surfaces.
2.2.12.7 Use steel roof drains with steel drain lines on the top floor when expanded or extruded polystyrene
is not isolated with a fire barrier or part of an FM Approved assembly.
2.2.12.8 Refer to Data Sheet 1-54, Roof Loads for New Construction, for additional information regarding
design rainfall intensity and duration.
2.2.15.1 Vegetation
2.2.15.1.1 Use plants generally accepted as appropriate for vegetative roof applications, the local climate,
and the rooftop microclimate. Vegetation on high-rise buildings dry out faster than those on lower roofs due
to the more consistent air flow and winds.
2.2.15.1.2 Avoid the use of grass and moss, which can dry out and create a potential fire hazard.
2.2.15.1.3 For extensive roofs, growth media should be fully covered with vegetation with at least 60% of
vegetation from the Sedum family for groundcover plantings where they are appropriate. (Sedums may not
be appropriate in warmer climates such as in Florida, USA.) Use at least three different species of Sedums,
in more or less equal quantities.
2.2.15.1.4 For groundcover plantings, sow seeds at a rate of not less than 3,000 seeds per 100 ft2
(325 per 1 m2), distribute cuttings at not less than 2.5 lb per 100 ft2 (12 kg per 100 m2), or install pre-grown
plugs at the rate of not less than 100 plugs per 100 ft2 (11 plugs per 1 m2).
2.2.15.1.5 For intensive and semi-intensive roofs, select shrubs and trees that will not readily ignite and burn
fiercely, such as those with a high water or salt content, or low amounts of volatile oils. Deciduous trees are
preferred over evergreen trees as they require lower maintenance with all the leaves dropping together in
autumn instead of continuously throughout the year.
2.2.15.6.2 When the seams of waterproofing membranes are not designed to be heat-welded (e.g., EPDM
membranes), provide continuous heat-welded root barrier seams.
2.2.15.6.3 Lap all root barrier seams to be sealed at least 6 in. (150 mm). Use welded seams not less than
1.5 in. (38 mm) wide in order to create a watertight seal. Test welded seams for integrity by either air lance
or hand scribe techniques.
2.2.15.9 Mulch
2.2.15.9.1 Use non-combustible mulch. When non-combustible mulch is not available, use mulches that are
less combustible, with lower flame height and spread such as wood or bark chips. Do not use shredded,
rubber, pine needle or straw mulches.
Combustible mulches vary in their flame height, rate of fire spread and combustion temperature; and are
also affected by the rooftop temperature and humidity.
See The Combustibility of Landscape Mulches https://naes.agnt.unr.edu/PMS/Pubs/1510_2011_95.pdf for
additional information.
• Compressible mineral
wool insulation
• NC insulation or cover
board below cover
2.3 Protection
2.3.1 Provide automatic sprinklers with a 0.20 gpm/ft2 over 2000 ft2 (8.1 mm/min over 190 m2) density in
the following areas:
A. Under wood or plastic decks, regardless of their fire rating.
B. In concealed areas with any of the following:
1. Exposed combustibles including the support structure, fiberglass grates, plastic pedestals or plastic
trays.
2. Combustible foam plastic boards (e.g., extruded or expanded polystyrene) where the surface that
is exposed to the concealed space is not covered by minimum 2 in. (51 mm) thick concrete pavers or
minimum 15/16 in. (24 mm) latex modified concrete.
When no other combustibles such as plastic grates or pedestals are present, the latex modified concrete
covering can be reduced to a minimum thickness of 3/8 in. (10 mm)
3. Single-ply or multi-ply membranes without a topping of minimum 2 in. (51 mm) thick concrete pavers.
Sprinklers are not needed in the following situations:
1. When the only combustible is a landscaping fabric.
2. When concrete pavers are elevated less than or equal to 2 in. (51 mm) above the roof assembly. The
2 in. (51 mm) maximum elevation applies throughout the entire area since the elevation varies with roof slope.
Concrete pavers must not be on plastic trays. See Fig. C.2.2-6 for this construction.
Install dry-pipe sprinkler systems where outdoor temperatures can drop below 40°F (4°C). Follow Data Sheet
2-0, Installation Guidelines for Automatic Sprinklers.
Provide sprinkler systems only where they can be accessed for maintenance and dry-pipe systems can be
properly drained.
2.3.2 Provide FM Approved linear heat detection where automatic sprinklers cannot be installed. Install in
accordance with Data Sheet 5-48, Automatic Fire Detection.
Linear heat detection need not be installed when concrete pavers are elevated less than or equal to 2 in.
(51 mm) above the roof assembly. The 2 in. (51 mm) maximum elevation applies throughout the entire area
since the elevation varies with roof slope. Concrete pavers must not be on plastic trays. See Fig. C.2.2-6
for this construction.
2.3.3 Provide non-combustible fire partitions spaced a maximum of 2000 ft2 (186 m2) in combustible
concealed spaces where automatic sprinklers cannot be installed.
2.3.4 Provide video surveillance in a constantly attended location of roof-top areas with vegetative roofs,
roof-top decks with combustible construction or furnishings, and combustible concealed spaces.
2.3.5 Provide exposure protection on adjacent buildings following Data Sheet 1-20 where there are insufficient
fire breaks and/or sufficient combustibles for a fire to damage adjacent buildings.
2.3.6 Provide a standpipe system in the stairwell with hose connections at the roof level or roof fire hydrant
near a roof access hatch. Follow Data Sheet 4-4N, Standpipe and Hose Systems, for standpipes and Data
Sheet 3-10, Installation and Maintenance of Private Fire Service Mains and Their Appurtenances, for roof
fire hydrants.
2.4.1 Irrigation
2.4.1.1 Provide rooftop hose bibs for vegetative roof systems designed to be self-sustaining without regularly
scheduled irrigation (i.e., most Extensive systems). This allows for irrigation during initial stages of plant
propagation and during occasional drought conditions.
2.4.1.2 Provide a permanent irrigation system for vegetative roof systems that require regular irrigation (i.e.,
Intensive and Simple Intensive systems)
2.4.4 Warranty
2.4.4.1 Ensure the manufacturer’s warranty includes the initial vegetation viability if the entire system
(waterproofing assembly as well as vegetative roof cover, including vegetation and growth media) is provided
by a single source. In addition to the standard waterproofing warranty, ensure the warranty states that the
proposed vegetative roof cover is completely compatible with the waterproofing assembly. Also, ensure the
warranty for the vegetative roof cover states that the proposed waterproofing system is compatible with the
vegetative system (including plant climate zone, roof slope, and irrigation and maintenance requirements).
If the waterproofing and vegetative roof cover are not provided by a single source, ensure the waterproofing
assembly will be warranted separately, independent of any warranty for the vegetative roof cover.
3.10 Vegetation
This section contains information to supplement the manufacturer’s instructions for vegetative roof systems.
3.10.1 Climate
In the United States, vegetation can be selected based partly on the USDA Plant Hardiness Zone Map;
however, the effects of solar radiation, wind, and frost can create a microclimate that will be more challenging
for vegetation on a roof than for the same plants at grade level. The existence of a distinct microclimate is
one of the reasons native vegetation frequently does not thrive on a vegetative roof.
3.13 Irrigation
Extensive vegetative roofs are designed to be viable without supplemental irrigation. However, during the
first one or two growing seasons, and at times of extreme drought, access to irrigation (such as rooftop hose
bibs) will be necessary.
Intensive vegetative roofs are not expected to be viable without regular irrigation and maintenance.
4.0 REFERENCES
4.1 FM Global
Data Sheet 1-2, Earthquakes
Data Sheet 1-28, Wind Design
Data Sheet 1-28R/1-29R, Roof Systems
Data Sheet 1-29, Roof Securement and Above-Deck Roof Components
Data Sheet 1-34, Hail Damage
Data Sheet 1-42, MFL limiting Factors
Data Sheet 1-54, Roof Loads for New Construction
Data Sheet 2-0, Installation Guidelines for Automatic Sprinklers
Data Sheet 2-81, Fire Protection System Inspection, Testing and Maintenance
Data Sheet 4-4N, Standpipe and Hose Systems
Data Sheet 9-19, Wildland Fire
FM Approval Standard 4477, Vegetative Roof Systems
4.2 Other
ASTM International. E2397-05 Standard Practice for Determination Dead Loads and Live Loads associated
with Green Roof Systems.
ASTM International, ASTM C1491-18, Standard Specification for Concrete Roof Pavers, 2018.
ASTM International. E2399-05 Standard Test Method for Maximum Media Density for Dead Load Analysis
of Green Roof Systems.
ASTM International. Hot Dip Galvanized Coils and Sheet Quality Norms.
American Concrete Institute (ACI). Building Code Requirements for Structural Concrete and Commentary.
ACI 318.
Forchungsgesellschaft Landschaftsentwicklung Landschaftsbau e.V. (FLL). Guidelines for the Planning,
Execution, and Upkeep of Green-Roof Sites.
National Roofing Contractors Association. The NRCA Vegetative Roof Systems Manual. Third edition. 2017.
National Roofing Contractors Association. “Testing Vegetative Roof Systems.” (accessed July 2022).
Single-Ply Roofing Industry (SPRI). ANSI/SPRI RP-14 2016, Wind Design Standard for Vegetative Roofing
Systems.
University of Nevada Cooperative Extension. “The Combustibility of Landscape Mulches.” Available online
at https://naes.agnt.unr.edu/PMS/Pubs/1510_2011_95.pdf (accessed July 2022).
from the growth media. Some drainage panels are supplied with an integral filter fabric. In lieu of a drainage
panel, systems can consist of a layer of granular material (expanded slate and clay, pumice, crushed brick)
to perform the same functions. The granular media used for the drainage layer is typically required to meet
specific requirements for gradation, porosity, hydraulic conductivity, and alkalinity.
EFVM: Electric Field Vector Mapping. A method of leak detection based on the electrical conductivity of a
moist cover material (growth media) and the electrical insulating properties of the waterproofing membrane.
Environmental load: Variable loads due to earthquake, flood, wind, snow, rain, and ice. These loads are
not typically subject to reduction in the same manner as live loads.
EPDM: Ethylene propylene diene monomer (or ethylene propylene diene terpolymer). A thermoset elastic
monomer commonly used for single-ply roofing membranes.
Extensive vegetative roof: Classification of a vegetative roof system where vegetation typically consists
of low-growing ground cover such as mosses, herbaceous plants, and hardy alpine succulent plants from the
Sedum family. Extensive vegetative roof systems are intended to be self-propagating and require little or
no maintenance once established. Growth media for Extensive systems is less than 6 in. (150 mm) in depth.
Growth media (mixed media, media, or engineered soil): The material used to support the growth of
vegetation
Hardscape: Materials and features, such as stone ballast (roof gravel), concrete pavers, gravel stops, curbs,
and grating used for bordering or enclosing vegetative roof areas and intended to support foot traffic
HDPE: High-density polyethylene. A thermoplastic material typically used for root barriers, and sometimes
for drainage panels.
Heat welded: A process of bonding two layers of thermoplastic material together, typically using hot air or
heated platens, to form a watertight seam.
Intensive vegetative roof: Classification of a vegetative roof system where vegetation can consist of a large
range of plants types, including ground cover, herbaceous plants, grasses, woody shrubs, and small trees.
Intensive vegetative roof systems are intended to simulate landscaped park facilities and typically require
continuous maintenance, including irrigation and fertilization. Growth media for Intensive systems is greater
than 8 in. (200 mm) in depth.
LEED: Leadership in Energy and Environmental Design. A green building rating system sponsored by the
U.S. Green Building Council (USGBC).
Live load: Variable loads produced by the use and occupancy during the life of the structure. Live loads
on a roof include those loads produced by people, moveable maintenance materials and equipment, and other
moveable object such as planters. Occupancy loads (produced by people) are typically subject to live load
reduction based on the size of the contributing (tributary) area. The reduced occupancy live load can be as low
as 40% of the full live load. However, governing building codes, model codes, and FM Global Data Sheets
place several exemptions and restrictions on the level of live load reduction based on the structural
properties and use of the building, and on the magnitude of the code-required minimum live load.
Maximum media density: The density of growth media after it has been subjected to a specific amount of
compaction and hydrated by immersion to simulate prolonged exposure to both foot traffic and rainfall
Maximum media water retention: The quantity of water held in growth media at the maximum media density
Media: See growth media.
Permeability: The coefficient which, when multiplied by the hydraulic gradient, will yield the apparent velocity
with which water (at 68|SNF or 20|SNC) will move through a cross-section of growth media.
PVC: Polyvinyl chloride. A thermoplastic polymer commonly used for single-ply waterproofing membranes
and root barriers.
Retained water: The quantity of water that is retained, typically for several hours to several days, once new
water additions by rainfall or irrigation have ceased, and that will eventually diminish primarily by gravity
run-off. Retained water is that quantity of water that remains on the roof after the passage of transient water,
minus the quantity of captured water. Retained water contributes to the dead load of the system.
Saturation point: The moisture content at which the tension in a growth media is zero, but a free water
surface has not developed.
Simple Intensive (semi-intensive) vegetative roof: A vegetative roof system where vegetation typically
consists of low-growing ground cover, herbaceous plants, grasses, and small shrubs. Simple Intensive
systems require maintenance programs similar to those required for Intensive systems. Growth media for
Simple Intensive systems is generally from 6 to 8 in. (150 to 200 mm) in depth.
TPO: Thermoplastic polyolefin (or flexible polyolefin). A thermoplastic polymer-based material commonly
used for single-ply waterproofing membranes.
Transient water: The quantity of water required to completely fill the drainage layer, minus the quantity of
captured water, when new water additions by rainfall or irrigation are actively occurring. Transient water can
be held for only a period of minutes and begins to drain once the saturation point of the growth media has
been reached and the drainage layer has reached its captured-water capacity. Transient water contributes to
the rain load of the system.
USDA: United States Department of Agriculture.
• Extensive
• Intensive
• Simple Intensive
Each type is defined primarily by the depth of the growth media layer, but also by the kind of vegetation.
Fig. C.2.2-2. Extensive vegetated roof with small hill and no concealed space
Guy wires (1 of 3)
Tree anchor
webbing
Concrete deadman
anchors (1 of 3)
Fig. C.2.2-4. Tree truck and roof ball secured with concrete deadman weights
B. Roofing base assembly. These components include the waterproofing roof membrane, protection board,
rigid insulation, thermal barrier, and the supporting structural roof deck. The components can be fully
adhered, mechanically attached.
The waterproofing membrane may be directly attached to the roof deck with the insulation above. These
are known as IRMA (Inverted Roofing Membrane Assembly or Protected Membrane Roof Assemblies). See
figures in Data Sheet 1-29.
Fig. C.2.2-5. Wood deck on plastic pedestals on extruded polystyrene (covered by landscaping fabric) forming a
combustible concealed space
Fig C.2.2-6. Rooftop concrete pavers elevated ½ in. (13 mm) above extruded polystyrene (covered with landscape fabric)
using plastic pedestals
APPENDIX D BIBLIOGRAPHY
Bass, Brad, and Bas Baskaran. Evaluating Rooftop and Vertical Gardens as an Adaptation Strategy for Urban
Areas. NRCC-46737. Project no. A020. CCAF Report B1046. National Research Council of Canada, 2003.
Available online at http://nrc-publications.canada.ca (accessed August 2022).
Dennis, F. C. ‘‘Fire Wise Plant Materials.’’ Colorado State University Cooperative Extension Service.
Publication 6.305. Available online at https://extension.colostate.edu/ (accessed August 2022)..
‘‘Federal Technology Alert: Green Roofs.’’ DOE / EE-0298. U.S. Dept. of Energy, Office of Energy Efficiency
and Renewable Energy (EERE). Federal Energy Management Program, 2004. Available online at https://
www.nps.gov/tps/sustainability/greendocs/fta_green_roofs-sm.pdf (accessed August 2022)..
Liu, K., and Bas Baskaran. Thermal Performance of Green Roofs through Field Evaluation. NRCC-46412.
Institute for Research in Construction, National Research Council of Canada, 2003. Available online at
http://researchgate.net (accessed August 2022).
Peck, Steven, and Monica Kuhn. Design Guidelines for Green Roofs. Canada Mortgage and Housing
Corporation and the Ontario Association of Architects, 2003.
Scholz-Barth, Katrin. ‘‘Green Roofs: Stormwater Management from the Top Down.’’ Environmental Design
& Construction (January/February 2001).
United States General Services Administration “The Benefits and Challenges of Green Roofs on Public and
Commercial Buildings”. Available online at https://www.gsa.gov (accessed May 2019).
Wark, Christopher G., and Wendy W. Wark. “Green Roof Specifications and Standards.” Construction
Specifier (August 2003). Available online at https://www.researchgate.net/publication/
284388900_Green_roof_specifications_and_standards (accessed August 2022).
Fig. E-1. Extensive vegetative roof, Chicago City Hall, Chicago, Illinois, USA (C 2005, Roofscapes, Inc., used by permission;
all rights reserved)
Fig. E-2. Extensive vegetative roof with sedums (courtesy of Genzyme Corp.)
Fig. E-3. Extensive vegetative roof Life Expression Wellness Center, Sugar Load, Pennsylvania, USA
(C 2005, Roofscapes, Inc., used by permission; all rights reserved)
Fig. E-4. Extensive vegetative roof at time of installation; Montgomery Park Business Center, Baltimore, Maryland, USA
(Courtesy of Katrin Scholz-Barth).
Fig. E-5. Extensive vegetative roof 10 months after installation; Montgomery Park Business Center, Baltimore, Maryland,
USA (Courtesy of Katrin Scholz-Barth and Kai-Henrik Barth)
Fig. E-6. Extensive vegetative roof 2 years after installation; Montgomery Park Business Center, Baltimore, Maryland,
USA (Courtesy of Katrin Scholz-Barth)
F.1 Use Ratings Calculator to determine the recommended wind, fire and hail ratings.
See Figure F.1-1.
F.4 Using RoofNav to Select FM Approved roof assemblies with concrete paver surfacing
F.4.1. Select FM Approved roof assemblies with concrete paver surfacing as follows:
1. Follow Figures F.2.1 and F.2.2.
2. Follow Figure F.3.1-1 selecting “stone/masonry” in the Material drop down.
3. Select search results as shown in fig. F.3.1-2.
4. Select a roof assembly from the search result on Figure F.3.1-3.
4. The combination of the fuel from the plastic pedestals, the joint in the polystyrene panels and the narrow
flue space resulted in melting and loss of structural integrity in the topping layer of latex modified cement.
5. Once the topping layer fractured and collapsed, it allowed direct fire exposure to the extruded
polystyrene insulation layers.
6. As the polystyrene upstream of the flame became involved, it resulted in collapse of successive portions
of the concrete topping and additional polystyrene fire exposure.
The second fire test used steel pedestals and a 15/16 in. (24 mm) layer oflatex modified cement on
polystyrene boards resulting in minimal damage to the polystyrene and its coating.
Fire Test Criteria
The test samples and fire tests conducted by FM Global were constructed and tested in accordance with
ASTM E108, Standard Test Method for Fire Tests of Roof Coverings. The Spread of Flame test was conducted
to determine if the roof assemblies would meet the requirements for a Class A exterior fire rating. This test
involves exposing the sample for a period of 10 minutes to a flame temperature of 1400°F ± 50°F in
conjunction with a one-minute timed average wind velocity of 1056 ± 44 ft/min measured from three locations
across the front of the sample.
G.2 Fire Test with wood deck on plastic pedestals and 3/8 in. (10 mm) thickness of latex-modified concrete
on extruded polystyrene boards Test assembly details listed from the bottom up, based on the image in Figure
G.2-1.
• 3 in. (76 mm) thick tongue and groove extruded polystyrene insulation boards, 2 ft (0.6 m) x 4 ft
(1.2 m), with a factory-applied topping of 3/8 in. (9.5 mm) latex-modified concrete. This deck was sloped
1/8 in. per ft.
• Landscaping fabric was placed over the top of the with a longitudinal joint in the center of the sample.
The fabric was overlapped 6 in. (150 mm) at that joint.
• Adjustable plastic pedestals spaced 2.0 ft (0.6 m) by 2 ft (0.6 m).
• 2 ft x 2 ft (0.6 m x 0.6 m) Ipe wood tiles were installed on top of the plastic, and the pedestals were
adjusted such that the wood tiles were level.
G.3 Fire Test with wood deck on steel pedestals on 15/16 in. (24 mm) thickness of latex-modified concrete
on extruded polystyrene boards
This test assembly is similar to that in section G.3 with steel pedestals replacing plastic pedestals and
15/16 in. (24 mm) thickness of latex-modified concrete on extruded polystyrene boards replacing a 3/8 in.
(10 mm) layer.
Fig. G.3-2. Close-up of final test assembly showing 15/16 in. (24 mm) layer of latex modified cement on extruded
polystyrene
Fig. G.3-6. Modified latex cement surface (Ipe wood tiles and pedestals removed)