CT Calculation - Fltcal
CT Calculation - Fltcal
CT Calculation - Fltcal
Zone of fault
Calculation of Stabilising Resistor-Rs
Current setting of the relay (in %) 10
in Amperes 0.1
DIFFERENTIAL PROTECTION CALCULATION
ALSTOM Document No : PGIE: CALCN-2 Project :7. 5MW TG Rev:-
Vk/2
Rs
Rr
Primary current at which the relay operates =(Relay current +Exctn current at Vk/2)CT ratio
108.3 Amperes
Time setting from the relay characteristic assuming a time multiplier of 1.0for a plug setting of 2pu
18sec
Document No : PGIE: CALCN-2 Project :7. 5MW TG Rev:-
Rev Sno Project:TATA SPONG IRON LTD
A Generator Data Sheet