Micom P40 Agile P94V: Technical Manual
Micom P40 Agile P94V: Technical Manual
Micom P40 Agile P94V: Technical Manual
Technical Manual
Feeder Management IED
Hardware Version: A
Software Version: 55
Publication Reference: P94V-TM-EN-5
© ALSTOM 2015. All rights reserved. Information contained in this document is indicative only. No representation or warranty is
given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical
and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or
disclosure to third parties, without express written authority, is strictly prohibited.
Contents
Chapter 1 Introduction 1
1 Chapter Overview 3
2 Foreword 4
2.1 Target Audience 4
2.2 Typographical Conventions 4
2.3 Nomenclature 5
2.4 Compliance 5
3 Product Scope 6
3.1 Ordering Options 6
4 Features and Functions 7
4.1 Protection Functions 7
4.2 Control Functions 7
4.3 Measurement Functions 8
4.4 Communication Functions 8
5 Logic Diagrams 9
6 Functional Overview 11
Chapter 4 Configuration 55
1 Chapter Overview 57
2 Settings Application Software 58
3 Using the HMI Panel 59
3.1 Navigating the HMI Panel 60
3.2 Getting Started 60
3.3 Default Display 61
3.4 Default Display Navigation 62
3.5 Password Entry 63
3.6 Processing Alarms and Records 64
3.7 Menu Structure 64
3.8 Changing the Settings 65
3.9 Direct Access (The Hotkey menu) 66
3.9.1 Setting Group Selection 66
3.9.2 Control Inputs 67
3.9.3 Circuit Breaker Control 67
3.10 Function Keys 68
4 Date and Time Configuration 69
4.1 Time Zone Compensation 69
4.2 Daylight Saving Time Compensation 69
5 Settings Group Selection 70
ii P94V-TM-EN-5
P94V Contents
P94V-TM-EN-5 iii
Contents P94V
iv P94V-TM-EN-5
P94V Contents
P94V-TM-EN-5 v
Contents P94V
vi P94V-TM-EN-5
P94V Contents
P94V-TM-EN-5 vii
Contents P94V
viii P94V-TM-EN-5
P94V Contents
P94V-TM-EN-5 ix
Contents P94V
x P94V-TM-EN-5
P94V Contents
P94V-TM-EN-5 xi
Contents P94V
xii P94V-TM-EN-5
Table of Figures
Figure 1: Key to logic diagrams 10
Figure 2: Functional Overview 11
Figure 3: Hardware design overview 30
Figure 4: Exploded view of IED 32
Figure 5: 20TE rear panel 33
Figure 6: 30TE Three-MIDOS block rear panel 34
Figure 7: 30TE Two-MIDOS block + communications rear panel 34
Figure 8: 30TE Two-MIDOS block + blanking plate 35
Figure 9: P94V in 20TE case with I/O option A 36
Figure 10: P94V in 30TE case with I/O option A + Ethernet communications 38
Figure 11: P94V in 30TE case with I/O option B 39
Figure 12: P94V in 30TE case with I/O option C 41
Figure 13: P94V in 30TE case with I/O option D 43
Figure 14: P94V in 20TE case with I/O option E 45
Figure 15: P94V in 30TE case with I/O option E + Ethernet communications 46
Figure 16: P94V in 30TE case with I/O option F 48
Figure 17: Front panel (20TE) 50
Figure 18: Front panel (30TE) 51
Figure 19: Navigating the HMI 60
Figure 20: Default display navigation 62
Figure 21: Undervoltage - single and three phase tripping mode (single stage) 75
Figure 22: Overvoltage - single and three phase tripping mode (single stage) 78
Figure 23: Rate of Change of Voltage protection logic 81
Figure 24: Residual Overvoltage logic 83
Figure 25: Residual voltage for a solidly earthed system 84
Figure 26: Residual voltage for an impedance earthed system 85
Figure 27: Negative Sequence Overvoltage logic 86
Figure 28: Moving Average undervoltage logic 89
Figure 29: Moving Average overvoltage logic 90
Figure 30: Moving Average zero sequence voltage logic 90
Figure 31: Moving Average positive sequence voltage logic 90
Figure 32: Moving Average negative sequence voltage logic 91
Figure 33: Underfrequency logic (single stage) 97
Figure 34: Overfrequency logic (single stage) 99
Figure 35: Power system segregation based upon frequency measurements 100
Figure 36: Independent rate of change of frequency logic (single stage) 102
Figure 37: Frequency-supervised rate of change of frequency logic (single stage) 105
Figure 38: Frequency supervised rate of change of frequency protection 106
Table of Figures P94V
xiv P94V-TM-EN-5
P94V Table of Figures
P94V-TM-EN-5 xv
Table of Figures P94V
Figure 113: P94V Voltage and Frequency IED with 3 inputs, 4 outputs and Check 356
Synchronisation Input (Model P)
Figure 114: P94VP Voltage and Frequency IED with 6 inputs, 8 outputs and Check 357
Synchronisation Input (Model P)
xvi P94V-TM-EN-5
INTRODUCTION
CHAPTER 1
Chapter 1 - Introduction P94V
2 P94V-TM-EN-5
P94V Chapter 1 - Introduction
1 CHAPTER OVERVIEW
This chapter provides some general information about the technical manual and an introduction to the
device(s) described in this technical manual.
P94V-TM-EN-5 3
Chapter 1 - Introduction P94V
2 FOREWORD
This technical manual provides a functional and technical description of Alstom Grid's P94V, as well as a
comprehensive set of instructions for using the device. The level at which this manual is written assumes
that you are already familiar with protection engineering and have experience in this discipline. The
description of principles and theory is limited to that which is necessary to understand the product. For
further details on general protection engineering theory, we refer you to Alstom's publication NPAG, which is
available online or from our contact centre.
We have attempted to make this manual as accurate, comprehensive and user-friendly as possible. However
we cannot guarantee that it is free from errors. Nor can we state that it cannot be improved. We would
therefore be very pleased to hear from you if you discover any errors, or have any suggestions for
improvement. Our policy is to provide the information necessary to help you safely specify, engineer, install,
commission, maintain, and eventually dispose of this product. We consider that this manual provides the
necessary information, but if you consider that more details are needed, please contact us.
All feedback should be sent to our contact centre via the following URL:
http://www.alstom.com/grid/contactcentre/
4 P94V-TM-EN-5
P94V Chapter 1 - Introduction
2.3 NOMENCLATURE
Due to the technical nature of this manual, many special terms, abbreviations and acronyms are used
throughout the manual. Some of these terms are well-known industry-specific terms while others may be
special product-specific terms used by Alstom Grid. The first instance of any acronym or term used in a
particular chapter is explained. In addition, a separate glossary is available on the Alstom Grid website, or
from the Alstom Grid contact centre.
We would like to highlight the following changes of nomenclature however:
● The word 'relay' is no longer used to describe the device itself. Instead, the device is referred to as the
'IED' (Intelligent Electronic Device), the 'device', or the 'product'. The word 'relay' is used purely to
describe the electromechanical components within the device, i.e. the output relays.
● British English is used throughout this manual.
● The British term 'Earth' is used in favour of the American term 'Ground'.
2.4 COMPLIANCE
The device has undergone a range of extensive testing and certification processes to ensure and prove
compatibility with all target markets. A detailed description of these criteria can be found in the Technical
Specifications chapter.
P94V-TM-EN-5 5
Chapter 1 - Introduction P94V
3 PRODUCT SCOPE
The P94V Voltage and Frequency IED has been designed for the protection of a wide range of overhead
lines and underground cables for distribution voltage level. The P94V provides integral overvoltage/
undervoltage and overfrequency/underfrequency detection.
In addition to the protection features, the devices include a comprehensive range of non-protection features
to aid with power system diagnosis and fault analysis.
The P94V can be used in various applications, depending on the chosen firmware. There are two different
models according to which firmware is installed: P94VB, P94VP
● The P94VB is the base device for general application
● The P94VP is for check synchronising applications
● The P94VR provides all the features of the P94VP but also provides Autoreclose functionality
All models are available with a range of Input/Output options, which are described in the hardware design
chapter and summarised in the ordering options.
A major advantage of the P40 Agile platform is its backward compatibility with the K-series products. The
P40 Agile products have been designed such that the case, back panel terminal layout and pin-outs are
identical to their K-series predecessors and can be retrofitted without the usual overhead associated with
replacing and rewiring devices. This allows easy upgrade of the protection system with minimum impact and
minimum shutdown time of the feeder.
6 P94V-TM-EN-5
P94V Chapter 1 - Introduction
P94V-TM-EN-5 7
Chapter 1 - Introduction P94V
Fault Records 10
Maintenance Records 10
Event Records / Event logging 2048
Time Stamping of Opto-inputs Yes
8 P94V-TM-EN-5
P94V Chapter 1 - Introduction
5 LOGIC DIAGRAMS
This technical manual contains many logic diagrams, which should help to explain the functionality of the
device. Although this manual has been designed to be as specific as possible to the chosen product, it may
contain diagrams, which have elements applicable to other products. If this is the case, a qualifying note will
accompany the relevant part.
The logic diagrams follow a convention for the elements used, using defined colours and shapes. A key to
this convention is provided below. We recommend viewing the logic diagrams in colour rather than in black
and white. The electronic version of the technical manual is in colour, but the printed version may not be. If
you need coloured diagrams, they can be provided on request by calling the contact centre and quoting the
diagram number.
P94V-TM-EN-5 9
Chapter 1 - Introduction P94V
Key:
Energising Quantity AND gate &
Hardcoded setting
Pulse / Latch
Measurement Cell S
SR Latch Q
R
Internal Calculation
S
SR Latch Q
Derived setting Reset Dominant RD
Switch Multiplier X
Bandpass filter
Comparator for detecting
undervalues
10 P94V-TM-EN-5
P94V Chapter 1 - Introduction
6 FUNCTIONAL OVERVIEW
81O
81RF
86 dV/dT 25 27 47 51V 59 67 81U 81RAV
59N 67N 81R
81df/dt
81V
V00003
P94V-TM-EN-5 11
Chapter 1 - Introduction P94V
12 P94V-TM-EN-5
SAFETY INFORMATION
CHAPTER 2
Chapter 2 - Safety Information P94V
14 P94V-TM-EN-5
P94V Chapter 2 - Safety Information
1 CHAPTER OVERVIEW
This chapter provides information about the safe handling of the equipment. The equipment must be properly
installed and handled in order to maintain it in a safe condition and to keep personnel safe at all times. You
must be familiar with information contained in this chapter before unpacking, installing, commissioning, or
servicing the equipment.
P94V-TM-EN-5 15
Chapter 2 - Safety Information P94V
The documentation provides instructions for installing, commissioning and operating the equipment. It
cannot, however cover all conceivable circumstances. In the event of questions or problems, do not take any
action without proper authorisation. Please contact your local sales office and request the necessary
information.
16 P94V-TM-EN-5
P94V Chapter 2 - Safety Information
3 SYMBOLS
Throughout this manual you will come across the following symbols. You will also see these symbols on
parts of the equipment.
Caution:
Refer to equipment documentation. Failure to do so could result in damage to
the equipment
Warning:
Risk of electric shock
Earth terminal. Note: This symbol may also be used for a protective conductor (earth) terminal if that
terminal is part of a terminal block or sub-assembly.
Note:
The term 'Earth' used in this manual is the direct equivalent of the North American term 'Ground'.
P94V-TM-EN-5 17
Chapter 2 - Safety Information P94V
Plan carefully, identify any possible hazards and determine how best to move the product. Look at other
ways of moving the load to avoid manual handling. Use the correct lifting techniques and Personal Protective
Equipment (PPE) to reduce the risk of injury.
Caution:
All personnel involved in installing, commissioning, or servicing this equipment
must be familiar with the correct working procedures.
Caution:
Consult the equipment documentation before installing, commissioning, or
servicing the equipment.
Caution:
Always use the equipment as specified. Failure to do so will jeopardise the
protection provided by the equipment.
Warning:
Removal of equipment panels or covers may expose hazardous live parts. Do
not touch until the electrical power is removed. Take care when there is
unlocked access to the rear of the equipment.
Warning:
Isolate the equipment before working on the terminal strips.
Warning:
Use a suitable protective barrier for areas with restricted space, where there is a
risk of electric shock due to exposed terminals.
Caution:
Disconnect power before disassembling. Disassembly of the equipment may
expose sensitive electronic circuitry. Take suitable precautions against
electrostatic voltage discharge (ESD) to avoid damage to the equipment.
18 P94V-TM-EN-5
P94V Chapter 2 - Safety Information
Caution:
NEVER look into optical fibres or optical output connections. Always use optical
power meters to determine operation or signal level.
Caution:
Testing may leave capacitors charged to dangerous voltage levels. Discharge
capacitors by rediucing test voltages to zero before disconnecting test leads.
Caution:
Operate the equipment within the specified electrical and environmental limits.
Caution:
Before cleaning the equipment, ensure that no connections are energised. Use a
lint free cloth dampened with clean water.
Note:
Contact fingers of test plugs are normally protected by petroleum jelly, which should not be removed.
Caution:
Equipment intended for rack or panel mounting is for use on a flat surface of a
Type 1 enclosure, as defined by Underwriters Laboratories (UL).
Caution:
To maintain compliance with UL and CSA/CUL, install the equipment using UL/
CSA-recognised parts for: cables, protective fuses, fuse holders and circuit
breakers, insulation crimp terminals, and replacement internal batteries.
Caution:
Where UL/CSA listing of the equipment is required for external fuse protection, a
UL or CSA Listed fuse must be used for the auxiliary supply. The listed
protective fuse type is: Class J time delay fuse, with a maximum current rating
of 15 A and a minimum DC rating of 250 V dc (for example type AJT15).
P94V-TM-EN-5 19
Chapter 2 - Safety Information P94V
Caution:
Where UL/CSA listing of the equipment is not required, a high rupture capacity
(HRC) fuse type with a maximum current rating of 16 Amps and a minimum dc
rating of 250 V dc may be used for the auxiliary supply (for example Red Spot
type NIT or TIA).
For P50 models, use a 1A maximum T-type fuse.
For P60 models, use a 4A maximum T-type fuse.
Caution:
Digital input circuits should be protected by a high rupture capacity NIT or TIA
fuse with maximum rating of 16 A. for safety reasons, current transformer
circuits must never be fused. Other circuits should be appropriately fused to
protect the wire used.
Caution:
CTs must NOT be fused since open circuiting them may produce lethal
hazardous voltages
Warning:
Terminals exposed during installation, commissioning and maintenance may
present a hazardous voltage unless the equipment is electrically isolated.
Caution:
Tighten M4 clamping screws of heavy duty terminal block connectors to a
nominal torque of 1.3 Nm.
Tighten captive screws of terminal blocks to 0.5 Nm minimum and 0.6 Nm
maximum.
Caution:
Always use insulated crimp terminations for voltage and current connections.
Caution:
Always use the correct crimp terminal and tool according to the wire size.
Caution:
Watchdog (self-monitoring) contacts are provided to indicate the health of the
device on some products. We strongly recommend that you hard wire these
contacts into the substation's automation system, for alarm purposes.
20 P94V-TM-EN-5
P94V Chapter 2 - Safety Information
Caution:
Earth the equipment with the supplied PCT (Protective Conductor Terminal).
Caution:
Do not remove the PCT.
Caution:
The PCT is sometimes used to terminate cable screens. Always check the PCT’s
integrity after adding or removing such earth connections.
Caution:
Use a locknut or similar mechanism to ensure the integrity of stud-connected
PCTs.
Caution:
The recommended minimum PCT wire size is 2.5 mm² for countries whose
mains supply is 230 V (e.g. Europe) and 3.3 mm² for countries whose mains
supply is 110 V (e.g. North America). This may be superseded by local or
country wiring regulations.
For P60 products, the recommended minimum PCT wire size is 6 mm². See
product documentation for details.
Caution:
The PCT connection must have low-inductance and be as short as possible.
Caution:
All connections to the equipment must have a defined potential. Connections
that are pre-wired, but not used, should be earthed, or connected to a common
grouped potential.
Caution:
Check voltage rating/polarity (rating label/equipment documentation).
Caution:
Check CT circuit rating (rating label) and integrity of connections.
Caution:
Check protective fuse or miniature circuit breaker (MCB) rating.
P94V-TM-EN-5 21
Chapter 2 - Safety Information P94V
Caution:
Check integrity of the PCT connection.
Caution:
Check voltage and current rating of external wiring, ensuring it is appropriate for
the application.
Warning:
Do not open the secondary circuit of a live CT since the high voltage produced
may be lethal to personnel and could damage insulation. Short the secondary of
the line CT before opening any connections to it.
Note:
For most Alstom equipment with ring-terminal connections, the threaded terminal block for current transformer
termination is automatically shorted if the module is removed. Therefore external shorting of the CTs may not be
required. Check the equipment documentation and wiring diagrams first to see if this applies.
Caution:
Where external components such as resistors or voltage dependent resistors
(VDRs) are used, these may present a risk of electric shock or burns if touched.
Warning:
Take extreme care when using external test blocks and test plugs such as the
MMLG, MMLB and P990, as hazardous voltages may be exposed. Ensure that CT
shorting links are in place before removing test plugs, to avoid potentially lethal
voltages.
4.9 UPGRADING/SERVICING
Warning:
Do not insert or withdraw modules, PCBs or expansion boards from the
equipment while energised, as this may result in damage to the equipment.
Hazardous live voltages would also be exposed, endangering personnel.
Caution:
Internal modules and assemblies can be heavy and may have sharp edges. Take
care when inserting or removing modules into or out of the IED.
22 P94V-TM-EN-5
P94V Chapter 2 - Safety Information
Caution:
Before decommissioning, completely isolate the equipment power supplies
(both poles of any dc supply). The auxiliary supply input may have capacitors in
parallel, which may still be charged. To avoid electric shock, discharge the
capacitors using the external terminals before decommissioning.
Caution:
Avoid incineration or disposal to water courses. Dispose of the equipment in a
safe, responsible and environmentally friendly manner, and if applicable, in
accordance with country-specific regulations.
P94V-TM-EN-5 23
Chapter 2 - Safety Information P94V
6 STANDARDS COMPLIANCE
Compliance with the European Commission Directive on EMC and LVD is demonstrated by self certification
against international standards.
Protective Class
IEC 60255-27: 2005 Class 1 (unless otherwise specified in equipment documentation). This equipment
requires a protective conductor (earth) to ensure user safety.
Installation category
IEC 60255-27: 2005 Overvoltage Category 3. Equipment in this category is qualification tested at 5kV peak,
1.2/50 mS, 500 Ohms, 0.5 J, between all supply circuits and earth and also between independent circuits.
Environment
IEC 60255-27: 2005, IEC 60255-26:2009. The equipment is intended for indoor use only. If it is required for
use in an outdoor environment, it must be mounted in a cabinet with the appropriate degree of ingress
protection.
24 P94V-TM-EN-5
P94V Chapter 2 - Safety Information
Equipment with this marking is not itself suitable for operation within a potentially explosive
atmosphere.
P94V-TM-EN-5 25
Chapter 2 - Safety Information P94V
26 P94V-TM-EN-5
HARDWARE DESIGN
CHAPTER 3
Chapter 3 - Hardware Design P94V
28 P94V-TM-EN-5
P94V Chapter 3 - Hardware Design
1 CHAPTER OVERVIEW
This chapter provides information about the product's hardware design.
This chapter contains the following sections:
Chapter Overview 29
Hardware Architecture 30
Mechanical Implementation 32
Terminal Connections 36
Front Panel 50
P94V-TM-EN-5 29
Chapter 3 - Hardware Design P94V
2 HARDWARE ARCHITECTURE
The main components comprising devices based on the P40Agile platform are as follows:
● The housing, consisting of a front panel and connections at the rear
● The Main processor module consisting of the main CPU (Central Processing Unit), memory and an
interface to the front panel HMI (Human Machine Interface)
● An I/O board consisting of output relay contacts and digital opto-inputs
● Communication modules
● Power supply
All modules are connected by a parallel data and address bus, which allows the processor module to send
and receive information to and from the other modules as required. There is also a separate serial data bus
for conveying sampled data from the input module to the CPU. These parallel and serial databuses are
shown as a single interconnection module in the following figure, which shows typical modules and the flow
of data between them.
Keypad
Output relay module Output relay contacts
Processor module
Front panel HMI
LCD
Opto-input module Digital inputs
LEDs
I/O
Front port
CTs Power system currents *
Memory
Interconnection
V00200
30 P94V-TM-EN-5
P94V Chapter 3 - Hardware Design
P94V-TM-EN-5 31
Chapter 3 - Hardware Design P94V
3 MECHANICAL IMPLEMENTATION
All products based on the P40Agile platform have common hardware architecture. The hardware comprises
two main parts; the cradle and the housing.
The cradle consists of the front panel which is attached to a carrier board into which all of the hardware
boards and modules are connected. The products have been designed such that all the boards and modules
comprising the product are fixed into the cradle and are not intended to be removed or inserted after the
product has left the factory.
The housing comprises the housing metalwork and connectors at the rear into which the boards in the cradle
plug into.
The products are available in panel-mount or standalone versions. All products are nominally 4U high. This
equates to 177.8 mm or 7 inches.
The cases are pre-finished steel with a conductive covering of aluminium and zinc. This provides good
grounding at all joints, providing a low resistance path to earth that is essential for performance in the
presence of external noise.
The case width depends on the product type and its hardware options. There are two different case widths
for the described range of products: 20TE and 30TE. The products in the P40Agile range can be used as a
32 P94V-TM-EN-5
P94V Chapter 3 - Hardware Design
K-series refit and the cases, cradle, and pin-outs are completely inter-compatible. The case dimensions and
compatibility criteria are as follows:
Case width (TE) Case width (mm) Equivalent K series Products
20TE 102.4 mm (4 inches) KCGG140/142 P14N
30TE 154.2 mm (6 inches) KCEG140/142 P14N (with extra I/O), P14D
P94V-TM-EN-5 33
Chapter 3 - Hardware Design P94V
34 P94V-TM-EN-5
P94V Chapter 3 - Hardware Design
P94V-TM-EN-5 35
Chapter 3 - Hardware Design P94V
4 TERMINAL CONNECTIONS
Component I/O option A I/O option B I/O option C I/O option D I/O option E I/O option F
8 11 11 13 6
3
Digital inputs (1 group of 3 and (2 groups of 3 and (1 group of 3, 1 group (1 group of 3 and (1 group of 3 and
(1 group of 3)
1 group of 5) 1 group of 5) of 5 and 3 individual) 2 groups of 5) 3 individual)
8 12 12 12 4 8
Output relays
(NO) (NO) (11 NO, 1 NC) (NO) (NO) (5 NO, 1 NC)
Note:
I/O options C and F are suitable for Trip Circuit Supervision (TCS) applications.
1 29 30
3 4 31 RL5 RL1 32
5 WatchDog 6 33 34
7 8 35 RL6 RL2 36
9 10 37 38
11 12 39 RL7 RL3 40
13 14 41 42
PSU
15 16 43 RL8 RL4 44
17 Vcs 18 45 46
19 Va Vb 20 L4 L1
47 48
21 Vc 22 L5 L2
49 50
23 24 L6 L3
51 52
25 26 L7
53 54
27 28 L8
55 56
SCN
E00212
Terminal Description
1 Earth
2 Not used
3+5 Watchdog, normally closed
4+6 Watchdog, normally open
7 to 12 Not used
13 + 14 Power Supply Unit
36 P94V-TM-EN-5
P94V Chapter 3 - Hardware Design
Terminal Description
15 + 16 Voltage Transformer Vcs
17+18 Voltage Transformer Va and Vb
19 + 20 Voltage Transformer Vc
21 to 28 Not used
Terminal Description
30 + 32 Relay 1, normally open
34 + 36 Relay 2, normally open
38 + 40 Relay 3, normally open
42 + 44 Relay 4, normally open
29 + 31 Relay 5, normally open
33 + 35 Relay 6, normally open
37 + 39 Relay 7, normally open
41 + 43 Relay 8, normally open
46 + 52 Opto-input L1 (group 1)
48 + 52 Opto-input L2 (group 1)
50 + 52 Opto-input L3 (group 1)
45 + 55 Opto-input L4 (group 2)
47 + 55 Opto-input L5 (group 2)
49 + 55 Opto-input L6 (group 2)
51 + 55 Opto-input L7 (group 2)
53 + 55 Opto-input L8 (group 2)
54 + 56 EIA(RS)485 or Demodulated IRIG-B
P94V-TM-EN-5 37
Chapter 3 - Hardware Design P94V
1 29 30
3 4 31 RL5 RL1 32
5 WatchDog 6 33 34
7 8 Ethernet 35 RL6 RL2 36
9 10 Communications 37 38
Board
11 12 39 RL7 RL3 40
13 14 41 42
PSU Single Channel
15 16 43 RL8 RL4 44
17 Vcs 18 45 46
Va Vb 10/100Base-TX L4 L1
19 20 47 48
21 Vc 22
or L5 L2
49 50
23 24 100Base-FX L6 L3
51 52
25 26 L7
53 54
27 28 L8
55 56
SCN
E00216
Figure 10: P94V in 30TE case with I/O option A + Ethernet communications
Terminal Description
1 Earth
2 Not used
3+5 Watchdog, normally closed
4+6 Watchdog, normally open
7 to 12 Not used
13 + 14 Power Supply Unit
15 + 16 Voltage Transformer Vcs
17+18 Voltage Transformer Va and Vb
19 + 20 Voltage Transformer Vc
21 to 28 Not used
Terminal Description
30 + 32 Relay 1, normally open
34 + 36 Relay 2, normally open
38 + 40 Relay 3, normally open
42 + 44 Relay 4, normally open
29 + 31 Relay 5, normally open
33 + 35 Relay 6, normally open
38 P94V-TM-EN-5
P94V Chapter 3 - Hardware Design
Terminal Description
37 + 39 Relay 7, normally open
41 + 43 Relay 8, normally open
46 + 52 Opto-input L1 (group 1)
48 + 52 Opto-input L2 (group 1)
50 + 52 Opto-input L3 (group 1)
45 + 55 Opto-input L4 (group 2)
47 + 55 Opto-input L5 (group 2)
49 + 55 Opto-input L6 (group 2)
51 + 55 Opto-input L7 (group 2)
53 + 55 Opto-input L8 (group 2)
54 + 56 EIA(RS)485 or Demodulated IRIG-B
1 57 58 29 30
3 4 59 RL9 60 31 RL5 RL1 32
5 WatchDog 6 61 62 33 34
7 8 63 RL10 64 35 RL6 RL2 36
9 10 65 66 37 38
11 12 67 RL11 68 39 RL7 RL3 40
13 14 69 70 41 42
PSU
15 16 71 RL12 72 43 RL8 RL4 44
17 Vcs 18 73 74 45 46
19 Va Vb 20 L9 L4 L1
75 76 47 48
21 Vc 22 L10 L5 L2
77 78 49 50
23 24 L11 L6 L3
79 80 51 52
25 26 L7
81 82 53 54
27 28 L8
83 84 55 56
SCN SCN
E00214
Terminal Description
1 Earth
2 Not used
3+5 Watchdog, normally closed
4+6 Watchdog, normally open
7 to 12 Not used
13 + 14 Power Supply Unit
15 + 16 Voltage Transformer Vcs
P94V-TM-EN-5 39
Chapter 3 - Hardware Design P94V
Terminal Description
17+18 Voltage Transformer Va and Vb
19 + 20 Voltage Transformer Vc
21 to 28 Not used
Terminal Description
30 + 32 Relay 1, normally open
34 + 36 Relay 2, normally open
38 + 40 Relay 3, normally open
42 + 44 Relay 4, normally open
29 + 31 Relay 5, normally open
33 + 35 Relay 6, normally open
37 + 39 Relay 7, normally open
41 + 43 Relay 8, normally open
46 + 52 Opto-input L1 (group 1)
48 + 52 Opto-input L2 (group 1)
50 + 52 Opto-input L3 (group 1)
45 + 55 Opto-input L4 (group 2)
47 + 55 Opto-input L5 (group 2)
49 + 55 Opto-input L6 (group 2)
51 + 55 Opto-input L7 (group 2)
53 + 55 Opto-input L8 (group 2)
54 + 56 EIA(RS)485 or Demodulated IRIG-B
Terminal Description
58 + 60 Relay 9, normally open
62 + 64 Relay 10, normally open
66 + 68 Relay 11, normally open
70 + 72 Relay 12, normally open
74 + 80 Opto-input L9 (group 3)
76 + 80 Opto-input L10 (group 3)
78 + 80 Opto-input L11 (group 3)
82 + 84 EIA(RS)485 or Demodulated IRIG-B
The rest Not used
40 P94V-TM-EN-5
P94V Chapter 3 - Hardware Design
1 57 58 29 30
3 4 59 RL9 60 31 RL5 RL1 32
5 WatchDog 6 61 62 33 34
7 8 63 RL10 64 35 RL6 RL2 36
9 10 65 66 37 38
11 12 67 RL11 68 39 RL7 RL3 40
13 14 69 70 41 42
PSU
15 16 71 RL12 72 43 RL8 RL4 44
17 Vcs 18 73 74 45 46
19 Va Vb 20 L9 L4 L1
75 76 47 48
21 Vc 22 L5 L2
77 78 49 50
23 24 L10 L6 L3
79 80 51 52
25 26 L7
81 82 53 54
27 28 L11 L8
83 84 55 56
SCN
E00215
Terminal Description
1 Earth
2 Not used
3+5 Watchdog, normally closed
4+6 Watchdog, normally open
7 to 12 Not used
13 + 14 Power Supply Unit
15 + 16 Voltage Transformer Vcs
17+18 Voltage Transformer Va and Vb
19 + 20 Voltage Transformer Vc
21 to 28 Not used
Terminal Description
30 + 32 Relay 1, normally open
34 + 36 Relay 2, normally open
38 + 40 Relay 3, normally open
42 + 44 Relay 4, normally open
29 + 31 Relay 5, normally open
33 + 35 Relay 6, normally open
P94V-TM-EN-5 41
Chapter 3 - Hardware Design P94V
Terminal Description
37 + 39 Relay 7, normally open
41 + 43 Relay 8, normally open
46 + 52 Opto-input L1 (group 1)
48 + 52 Opto-input L2 (group 1)
50 + 52 Opto-input L3 (group 1)
45 + 55 Opto-input L4 (group 2)
47 + 55 Opto-input L5 (group 2)
49 + 55 Opto-input L6 (group 2)
51 + 55 Opto-input L7 (group 2)
53 + 55 Opto-input L8 (group 2)
54 + 56 EIA(RS)485 or Demodulated IRIG-B
Terminal Description
58 + 60 Relay 9, normally open
62 + 64 Relay 10, normally open
66 + 68 Relay 11, normally open
70 + 72 Relay 12, normally closed
74 + 76 Opto-input L9
78 + 80 Opto-input L10
82 + 84 Opto-input L11
The rest Not used
42 P94V-TM-EN-5
P94V Chapter 3 - Hardware Design
1 57 58 29 30
3 4 59 RL9 60 31 RL5 RL1 32
5 WatchDog 6 61 62 33 34
7 8 63 RL10 64 35 RL6 RL2 36
9 10 65 66 37 38
11 12 67 RL11 68 39 RL7 RL3 40
13 14 69 70 41 42
PSU
15 16 71 RL12 72 43 RL8 RL4 44
17 Vcs 18 73 74 45 46
19 Va Vb 20 L9 L4 L1
75 76 47 48
21 Vc 22 L10 L5 L2
77 78 49 50
23 24 L11 L6 L3
79 80 51 52
25 26 L12 L7
81 82 53 54
27 28 L13 L8
83 84 55 56
SCN
E00213
Terminal Description
1 Earth
2 Not used
3+5 Watchdog, normally closed
4+6 Watchdog, normally open
7 to 12 Not used
13 + 14 Power Supply Unit
15 + 16 Voltage Transformer Vcs
17+18 Voltage Transformer Va and Vb
19 + 20 Voltage Transformer Vc
21 to 28 Not used
Terminal Description
30 + 32 Relay 1, normally open
34 + 36 Relay 2, normally open
38 + 40 Relay 3, normally open
42 + 44 Relay 4, normally open
29 + 31 Relay 5, normally open
33 + 35 Relay 6, normally open
P94V-TM-EN-5 43
Chapter 3 - Hardware Design P94V
Terminal Description
37 + 39 Relay 7, normally open
41 + 43 Relay 8, normally open
46 + 52 Opto-input L1 (group 1)
48 + 52 Opto-input L2 (group 1)
50 + 52 Opto-input L3 (group 1)
45 + 55 Opto-input L4 (group 2)
47 + 55 Opto-input L5 (group 2)
49 + 55 Opto-input L6 (group 2)
51 + 55 Opto-input L7 (group 2)
53 + 55 Opto-input L8 (group 2)
54 + 56 EIA(RS)485 or Demodulated IRIG-B
Terminal Description
58 + 60 Relay 9, normally open
62 + 64 Relay 10, normally open
66 + 68 Relay 11, normally open
70 + 72 Relay 12, normally open
74 + 84 Opto-input L9 (group 5)
76 + 84 Opto-input L10 (group 5)
78 + 84 Opto-input L11 (group 5)
80 + 84 Opto-input L12 (group 5)
82 + 84 Opto-input L13 (group 5)
The rest Not used
44 P94V-TM-EN-5
P94V Chapter 3 - Hardware Design
1 29 30
3 4 31 RL1 32
5 WatchDog 6 33 34
7 8 35 RL2 36
9 10 37 38
11 12 39 RL3 40
13 14 41 42
PSU
15 16 43 RL4 44
17 Vcs 18 45 46
19 Va Vb 20 L1
47 48
21 Vc 22 L2
49 50
23 24 L3
51 52
25 26 53 54
27 28 55 56
SCN
E00268
Terminal Description
1 Earth
2 Not used
3+5 Watchdog, normally closed
4+6 Watchdog, normally open
7 to 12 Not used
13 + 14 Power Supply Unit
15 + 16 Voltage Transformer Vcs
17+18 Voltage Transformer Va and Vb
19 + 20 Voltage Transformer Vc
21 to 28 Not used
Terminal Description
30 + 32 Relay 1, normally open
34 + 36 Relay 2, normally open
38 + 40 Relay 3, normally open
42 + 44 Relay 4, normally open
29 + 31 Not used
33 + 35 Not used
37 + 39 Not used
P94V-TM-EN-5 45
Chapter 3 - Hardware Design P94V
Terminal Description
41 + 43 Not used
46 + 52 Opto-input L1 (group 1)
48 + 52 Opto-input L2 (group 1)
50 + 52 Opto-input L3 (group 1)
45 + 55 Not used
47 + 55 Not used
49 + 55 Not used
51 + 55 Not used
53 + 55 Not used
54 + 56 EIA(RS)485 or Demodulated IRIG-B
1 29 30
3 4 31 RL1 32
5 WatchDog 6 33 34
7 8 Ethernet 35 RL2 36
9 10 Communications
37 38
Board
11 12 39 RL3 40
13 14 41 42
PSU Single Channel
15 16 43 RL4 44
17 Vcs 18 45 46
Va Vb 10/100Base-TX L1
19 20 47 48
21 Vc 22
or L2
49 50
23 24 100Base-FX L3
51 52
25 26 53 54
27 28 55 56
SCN
E00274
Figure 15: P94V in 30TE case with I/O option E + Ethernet communications
Terminal Description
1 Earth
2 Not used
3+5 Watchdog, normally closed
4+6 Watchdog, normally open
7 to 12 Not used
13 + 14 Power Supply Unit
15 + 16 Voltage Transformer Vcs
17+18 Voltage Transformer Va and Vb
46 P94V-TM-EN-5
P94V Chapter 3 - Hardware Design
Terminal Description
19 + 20 Voltage Transformer Vc
21 to 28 Not used
Terminal Description
30 + 32 Relay 1, normally open
34 + 36 Relay 2, normally open
38 + 40 Relay 3, normally open
42 + 44 Relay 4, normally open
29 + 31 Not used
33 + 35 Not used
37 + 39 Not used
41 + 43 Not used
46 + 52 Opto-input L1 (group 1)
48 + 52 Opto-input L2 (group 1)
50 + 52 Opto-input L3 (group 1)
45 + 55 Not used
47 + 55 Not used
49 + 55 Not used
51 + 55 Not used
53 + 55 Not used
54 + 56 EIA(RS)485 or Demodulated IRIG-B
P94V-TM-EN-5 47
Chapter 3 - Hardware Design P94V
1 57 58 29 30
3 4 59 RL5 60 31 RL1 32
5 WatchDog 6 61 62 33 34
7 8 63 RL6 64 35 RL2 36
9 10 65 66 37 38
11 12 67 RL7 68 39 RL3 40
13 14 69 70 41 42
PSU
15 16 71 RL8 72 43 RL4 44
17 Vcs 18 73 74 45 46
19 Va Vb 20 L4 L1
75 76 47 48
21 Vc 22 L2
77 78 49 50
23 24 L5 L3
79 80 51 52
25 26 81 82 53 54
27 28 L6
83 84 55 56
SCN
EN00269
Terminal Description
1 Earth
2 Not used
3+5 Watchdog, normally closed
4+6 Watchdog, normally open
7 to 12 Not used
13 + 14 Power Supply Unit
15 + 16 Voltage Transformer Vcs
17+18 Voltage Transformer Va and Vb
19 + 20 Voltage Transformer Vc
21 to 28 Not used
Terminal Description
30 + 32 Relay 1, normally open
34 + 36 Relay 2, normally open
38 + 40 Relay 3, normally open
42 + 44 Relay 4, normally open
29 + 31 Not used
33 + 35 Not used
48 P94V-TM-EN-5
P94V Chapter 3 - Hardware Design
Terminal Description
37 + 39 Not used
41 + 43 Not used
46 + 52 Opto-input L1 (group 1)
48 + 52 Opto-input L2 (group 1)
50 + 52 Opto-input L3 (group 1)
45 + 55 Not used
47 + 55 Not used
49 + 55 Not used
51 + 55 Not used
53 + 55 Not used
54 + 56 EIA(RS)485 or Demodulated IRIG-B
Terminal Description
58 + 60 Relay 5, normally open
62 + 64 Relay 6, normally open
66 + 68 Relay 7, normally open
70 + 72 Relay 8, normally closed
74 + 76 Opto-input L4
78 + 80 Opto-input L5
82 + 84 Opto-input L6
The rest Not used
P94V-TM-EN-5 49
Chapter 3 - Hardware Design P94V
5 FRONT PANEL
50 P94V-TM-EN-5
P94V Chapter 3 - Hardware Design
5.3 KEYPAD
The keypad consists of the following keys:
P94V-TM-EN-5 51
Chapter 3 - Hardware Design P94V
A read key for viewing larger blocks of text (arrow keys now used
for scrolling)
2 hot keys for scrolling through the default display and for control
of setting groups. These are situated directly below the LCD
display.
The port is intended for temporary connection during testing, installation and commissioning. It is not
intended to be used for permanent SCADA communications. This port supports the Courier communication
protocol only. Courier is a proprietary communication protocol to allow communication with a range of
protection equipment, and between the device and the Windows-based support software package.
You can connect the unit to a PC with a USB cable up to 5 m in length.
The inactivity timer for the front port is set to 15 minutes. This controls how long the unit maintains its level of
password access on the front port. If no messages are received on the front port for 15 minutes, any
password access level that has been enabled is cancelled.
Note:
The front USB port does not support automatic extraction of event and disturbance records, although this data can be
accessed manually.
Caution:
When not in use, always close the cover of the USB port to prevent
contamination.
52 P94V-TM-EN-5
P94V Chapter 3 - Hardware Design
P94V-TM-EN-5 53
Chapter 3 - Hardware Design P94V
54 P94V-TM-EN-5
CONFIGURATION
CHAPTER 4
Chapter 4 - Configuration P94V
56 P94V-TM-EN-5
P94V Chapter 4 - Configuration
1 CHAPTER OVERVIEW
Each product has different configuration parameters according to the functions it has been designed to
perform. There is, however, a common methodology used across the entire product series to set these
parameters.
Some of the communications setup can only be carried out using the HMI, and cannot be carried out using
settings applications software. This chapter includes concise instructions of how to configure the device,
particularly with respect to the communications setup, as well as a description of the common methodology
used to configure the device in general.
P94V-TM-EN-5 57
Chapter 4 - Configuration P94V
58 P94V-TM-EN-5
P94V Chapter 4 - Configuration
The keypad provides full access to the device functionality using a range of menu options. The information is
displayed on the LCD.
Keys Description Function
Function keys (not all models) For executing user programmable functions
P94V-TM-EN-5 59
Chapter 4 - Configuration P94V
Note:
As the LCD display has a resolution of 16 characters by 3 lines, some of the information is in a condensed mnemonic
form.
Alarm message
V00400
60 P94V-TM-EN-5
P94V Chapter 4 - Configuration
If there are alarms present, the yellow Alarms LED will be flashing and the menu display will read as follows:
Alarms / Faults
Present
HOTKEY
Even though the device itself should be in full working order when you first start it, an alarm could still be
present, for example, if there is no network connection for a device fitted with a network card. If this is the
case, you can read the alarm by pressing the 'Read' key.
ALARMS
NIC Link Fail
If the device is fitted with an Ethernet card, you will first need to connect the device to an active Ethernet
network to clear the alarm and get the default display.
If there are other alarms present, these must also be cleared before you can get into the default display
menu options.
11:09:15
23 Nov 2011
HOTKEY
Description (user-defined)
For example:
Description
MiCOM P14NB
HOTKEY
P94V-TM-EN-5 61
Chapter 4 - Configuration P94V
Plant Reference
MiCOM
HOTKEY
Access Level
For example:
Access Level
3
HOTKEY
In addition to the above, there are also displays for the system voltages, currents, power and frequency etc.,
depending on the device model.
NERC compliant
banner
System Current
Access Level
Measurements
System Voltage
System Frequency
Measurements
System Power
Plant Reference
Measurements
V00403
62 P94V-TM-EN-5
P94V Chapter 4 - Configuration
If the device is cyber-secure but is not yet configured for NERC compliance (see Cyber-security chapter), a
warning will appear when moving from the "NERC compliant" banner. The warning message is as follows:
You will have to confirm with the Enter button before you can go any further.
Note:
Whenever the IED has an uncleared alarm the default display is replaced by the text Alarms/ Faults present. You
cannot override this default display. However, you can enter the menu structure from the default display, even if the
display shows the Alarms/Faults present message.
Enter Password
1. A flashing cursor shows which character field of the password can be changed. Press the up or down
cursor keys to change each character (tip: pressing the up arrow once will return an upper case "A" as
required by the default level 3 password).
2. Use the left and right cursor keys to move between the character fields of the password.
3. Press the Enter keyto confirm the password. If you enter an incorrect password, an invalid password
message is displayed then the display reverts to Enter password. On entering a valid password a
message appears indicating that the password is correct and which level of access has been
unlocked. If this level is sufficient to edit the selected setting, the display returns to the setting page to
allow the edit to continue. If the correct level of password has not been entered, the password prompt
page appears again.
4. To escape from this prompt press the Clear key. Alternatively, enter the password using the Password
setting in the SYSTEM DATA column. If the keypad is inactive for 15 minutes, the password protection
of the front panel user interface reverts to the default access level.
To manually reset the password protection to the default level, select Password, then press the CLEAR key
instead of entering a password.
Note:
In the SECURITY CONFIG column, you can set the maximum number of attemps, the time window in which the
failed attempts are counted and the time duration for which the user is blocked.
P94V-TM-EN-5 63
Chapter 4 - Configuration P94V
Press Clear To
Reset Alarms
3. To clear all alarm messages, press the Clear key. To return to the display showing alarms or faults
present, and leave the alarms uncleared, press the Read key.
4. Depending on the password configuration settings, you may need to enter a password before the
alarm messages can be cleared.
5. When all alarms are cleared, the yellow alarm LED switches off. If the red LED was on, this will also
be switched off.
Note:
To speed up the procedure, you can enter the alarm viewer using the Read key and subsequently pressing the Clear
key. This goes straight to the fault record display. Press the Clear key again to move straight to the alarm reset
prompt, then press the Clear key again to clear all alarms.
Note:
Sometimes the term "Setting" is used generically to describe all of the three types.
64 P94V-TM-EN-5
P94V Chapter 4 - Configuration
SYSTEM DATA (Col 00) VIEW RECORDS (Col 01) MEASUREMENTS 1 (Col 02) …
Password (Row 02) Menu Cell Ref (Row 02) IA Phase Angle (Row 02) …
Sys Fn Links (Row 03) Time & Date (Row 03) IB Magnitude (Row 03) …
… … … …
It is convenient to specify all the settings in a single column, detailing the complete Courier address for each
setting. The above table may therefore be represented as follows:
Setting Column Row Description
SYSTEM DATA 00 00 First Column definition
Language (Row 01) 00 01 First setting within first column
Password (Row 02) 00 02 Second setting within first column
Sys Fn Links (Row 03) 00 03 Third setting within first column
… … …
VIEW RECORDS 01 00 Second Column definition
Select Event [0...n] 01 01 First setting within second column
Menu Cell Ref 01 02 Second setting within second column
Time & Date 01 03 Third setting within second column
… … …
MEASUREMENTS 1 02 00 Third Column definition
IA Magnitude 02 01 First setting within third column
IA Phase Angle 02 02 Second setting within third column
IB Magnitude 02 03 Third setting within third column
… … …
The first three column headers are common throughout much of the product ranges. However the rows
within each of these column headers may differ according to the product type. Many of the column headers
are the same for all products within the series. However, there is no guarantee that the addresses will be the
same for a particular column header. Therefore you should always refer to the product settings
documentation and not make any assumptions.
P94V-TM-EN-5 65
Chapter 4 - Configuration P94V
9. For protection group settings and disturbance recorder settings, the changes must be confirmed
before they are used. When all required changes have been entered, return to the column heading
level and press the Down cursor key. Before returning to the default display, the following prompt
appears.
Update settings?
ENTER or CLEAR
10. Press the Enter key to accept the new settings or press the Clear key to discard the new settings.
Note:
For the protection group and disturbance recorder settings, if the menu time-out occurs before the changes have
been confirmed, the setting values are discarded. Control and support settings, howeverr, are updated immediately
after they are entered, without the Update settings? prompt.
The availability of these functions is controlled by the Direct Access cell in the CONFIGURATION column.
There are four options: Disabled, Enabled, CB Ctrl only and Hotkey only.
For the Setting Group selection and Control inputs, this cell must be set to either Enabled or Hotkey
only. For CB Control functions, the cell must be set to Enabled or CB Ctrl only.
Use the right cursor keys to enter the SETTING GROUP menu.
¬Menu User01®
SETTING GROUP 1
Nxt Grp Select
66 P94V-TM-EN-5
P94V Chapter 4 - Configuration
Select the setting group with Nxt Grp and confirm by pressing Select. If neither of the cursor keys is pressed
within 20 seconds of entering a hotkey sub menu, the device reverts to the default display.
Press the right cursor key twice to get to the first control input, or the left cursor key to get to the last control
input.
¬STP GP User02®
Control Input 1
EXIT SET
Now you can execute the chosen function (Set/Reset in this case).
If neither of the cursor keys is pressed within 20 seconds of entering a hotkey sub menu, the device reverts
to the default display.
Plant Reference
MiCOM
HOTKEY CLOSE
To close the circuit breaker (in this case), press the key directly below CLOSE. You will be given an option to
cancel or confirm.
Execute
CB CLOSE
Cancel Confirm
More detailed information on this can be found in the Monitoring and Control chapter.
P94V-TM-EN-5 67
Chapter 4 - Configuration P94V
FUNCTION KEYS
Fn Key Status
0000000000
The next cell down (Fn Key 1) allows you to activate or disable the first function key (1). The Lock setting
allows a function key to be locked. This allows function keys that are set to Toggled mode and their DDB
signal active ‘high’, to be locked in their active state, preventing any further key presses from deactivating the
associated function. Locking a function key that is set to the Normal mode causes the associated DDB
signals to be permanently off. This safety feature prevents any inadvertent function key presses from
activating or deactivating critical functions.
FUNCTION KEYS
Fn Key 1
Unlocked
The next cell down (Fn Key 1 Mode) allows you to set the function key to Normal or Toggled. In the
Toggle mode the function key DDB signal output stays in the set state until a reset command is given, by
activating the function key on the next key press. In the Normal mode, the function key DDB signal stays
energised for as long as the function key is pressed then resets automatically. If required, a minimum pulse
width can be programmed by adding a minimum pulse timer to the function key DDB output signal.
FUNCTION KEYS
Fn Key 1 Mode
Toggled
The next cell down (Fn Key 1 Label) allows you to change the label assigned to the function. The default
label is Function key 1 in this case. To change the label you need to press the enter key and then
change the text on the bottom line, character by character. This text is displayed when a function key is
accessed in the function key menu, or it can be displayed in the PSL.
FUNCTION KEYS
Fn Key 1 Label
Function Key 1
Subsequent cells allow you to carry out the same procedure as above for the other function keys.
The status of the function keys is stored in non-volatile memory. If the auxiliary supply is interrupted, the
status of all the function keys is restored. The IED only recognises a single function key press at a time and
a minimum key press duration of approximately 200 ms is required before the key press is recognised. This
feature avoids accidental double presses.
68 P94V-TM-EN-5
P94V Chapter 4 - Configuration
The LocalTime Offset setting allows you to enter the local time zone compensation from -12 to + 12 hours
at 15 minute intervals.
These settings are described in the DATE AND TIME settings table in the configuration chapter.
P94V-TM-EN-5 69
Chapter 4 - Configuration P94V
70 P94V-TM-EN-5
VOLTAGE PROTECTION FUNCTIONS
CHAPTER 5
Chapter 5 - Voltage Protection Functions P94V
72 P94V-TM-EN-5
P94V Chapter 5 - Voltage Protection Functions
1 CHAPTER OVERVIEW
The device provides a wide range of voltage protection functions. This chapter describes the operation of
these functions including the principles, logic diagrams and applications.
This chapter contains the following sections:
Chapter Overview 73
Undervoltage Protection 74
Overvoltage Protection 77
Rate of Change of Voltage Protection 80
Residual Overvoltage Protection 82
Negative Sequence Overvoltage Protection 86
Moving Average Voltage Functions 88
P94V-TM-EN-5 73
Chapter 5 - Voltage Protection Functions P94V
2 UNDERVOLTAGE PROTECTION
Undervoltage conditions may occur on a power system for a variety of reasons, some of which are outlined
below:
● Undervoltage conditions can be related to increased loads, whereby the supply voltage will decrease
in magnitude. This situation would normally be rectified by voltage regulating equipment such as AVRs
(Auto Voltage Regulators) or On Load Tap Changers. However, failure of this equipment to bring the
system voltage back within permitted limits leaves the system with an undervoltage condition, which
must be cleared.
● If the regulating equipment is unsuccessful in restoring healthy system voltage, then tripping by means
of an undervoltage element is required.
● Faults occurring on the power system result in a reduction in voltage of the faulty phases. The
proportion by which the voltage decreases is dependent on the type of fault, method of system
earthing and its location. Consequently, co-ordination with other voltage and current-based protection
devices is essential in order to achieve correct discrimination.
● Complete loss of busbar voltage. This may occur due to fault conditions present on the incomer or
busbar itself, resulting in total isolation of the incoming power supply. For this condition, it may be
necessary to isolate each of the outgoing circuits, such that when supply voltage is restored, the load
is not connected. Therefore, the automatic tripping of a feeder on detection of complete loss of voltage
may be required. This can be achieved by a three-phase undervoltage element.
● Where outgoing feeders from a busbar are supplying induction motor loads, excessive dips in the
supply may cause the connected motors to stall, and should be tripped for voltage reductions that last
longer than a pre-determined time.
You set this using the V<1 Function and V<3 Function cells depending on the stage.
The IDMT characteristic is defined by the following formula:
t = K/( M-1)
where:
● K = Time multiplier setting
● t = Operating time in seconds
● M = Measured voltage / IED setting voltage (V< Voltage Set)
The undervoltage stages can be configured either as phase-to-neutral or phase-to-phase voltages in the
V< Measure't mode cell.
There is no Timer Hold facility for Undervoltage.
Stage 2 can have definite time characteristics only. This is set in the V<2 status cell.
74 P94V-TM-EN-5
P94V Chapter 5 - Voltage Protection Functions
Three stages are included in order to provide multiple output types, such as alarm and trip stages.
Alternatively, different time settings may be required depending upon the severity of the voltage dip. For
example, motor loads will be able to cope with a small voltage dip for a longer time than a major one.
Outputs are available for single or three-phase conditions via the V<Operate Mode cell for each stage.
Figure 21: Undervoltage - single and three phase tripping mode (single stage)
The Undervoltage protection function detects when the voltage magnitude for a certain stage falls short of a
set threshold. If this happens a Start signal, signifying the "Start of protection", is produced. This Start signal
can be blocked by the VTS Fast Block signal and an All Poles Dead signal. This Start signal is applied to
the timer module to produce the Trip signal, which can be blocked by the undervoltage timer block signal
(V<(n) Timer Block). For each stage, there are three Phase undervoltage detection modules, one for each
phase. The three Start signals from each of these phases are OR'd together to create a 3-phase Start signal
(V<(n) Start), which can be be activated when any of the three phases start (Any Phase), or when all three
phases start (Three Phase), depending on the chosen V< Operate Mode setting.
The outputs of the timer modules are the trip signals which are used to drive the tripping output relay. These
tripping signals are also OR'd together to create a 3-phase Trip signal, which are also controlled by the V<
Operate Mode setting.
If any one of the above signals is low, or goes low before the timer has counted out, the timer module is
inhibited (effectively reset) until the blocking signal goes high.
P94V-TM-EN-5 75
Chapter 5 - Voltage Protection Functions P94V
In some cases, we do not want the undervoltage element to trip; for example, when the protected feeder is
de-energised, or the circuit breaker is opened, an undervoltage condition would obviously be detected, but
we would not want to start protection. To cater for this, an All Poles Dead signal blocks the Start signal for
each phase. This is controlled by the V<Poledead Inh cell, which is included for each of the stages. If the
cell is enabled, the relevant stage will be blocked by the integrated pole dead logic. This logic produces an
output when it detects either an open circuit breaker via auxiliary contacts feeding the opto-inputs or it
detects a combination of both undercurrent and undervoltage on any one phase.
76 P94V-TM-EN-5
P94V Chapter 5 - Voltage Protection Functions
3 OVERVOLTAGE PROTECTION
Overvoltage conditions are generally related to loss of load conditions, whereby the supply voltage increases
in magnitude. This situation would normally be rectified by voltage regulating equipment such as AVRs (Auto
Voltage Regulators) or On Load Tap Changers. However, failure of this equipment to bring the system
voltage back within permitted limits leaves the system with an overvoltage condition which must be cleared.
Note:
During earth fault conditions on a power system there may be an increase in the healthy phase voltages. Ideally, the
system should be designed to withstand such overvoltages for a defined period of time.
You set this using the V>1 Function and V>3 Function cells depending on the stage.
The IDMT characteristic is defined by the following formula:
t = K/( M - 1)
where:
● K = Time multiplier setting
● t = Operating time in seconds
● M = Measured voltage setting voltage (V> Voltage Set)
The overvoltage stages can be configured either as phase-to-neutral or phase-to-phase voltages in the
V> Measure't mode cell.
There is no Timer Hold facility for Overvoltage.
Stage 2 can have definite time characteristics only. This is set in the V>2 status cell.
Three stages are included in order to provide multiple output types, such as alarm and trip stages.
Alternatively, different time settings may be required depending upon the severity of the voltage increase.
Outputs are available for single or three-phase conditions via the V>Operate Mode cell for each stage.
P94V-TM-EN-5 77
Chapter 5 - Voltage Protection Functions P94V
Figure 22: Overvoltage - single and three phase tripping mode (single stage)
The Overvoltage protection function detects when the voltage magnitude for a certain stage exceeds a set
threshold. If this happens a Start signal, signifying the "Start of protection", is produced. This Start signal can
be blocked by the VTS Fast Block signal. This start signal is applied to the timer module to produce the Trip
signal, which can be blocked by the overvoltage timer block signal (V>(n) Timer Block). For each stage,
there are three Phase overvoltage detection modules, one for each phase. The three Start signals from each
of these phases are OR'd together to create a 3-phase Start signal (V>(n) Start), which can then be
activated when any of the three phases start (Any Phase), or when all three phases start (Three Phase),
depending on the chosen V> Operate Mode setting.
The outputs of the timer modules are the trip signals which are used to drive the tripping output relay. These
tripping signals are also OR'd together to create a 3-phase Trip signal, which are also controlled by the V>
Operate Mode setting.
If any one of the above signals is low, or goes low before the timer has counted out, the timer module is
inhibited (effectively reset) until the blocking signal goes high.
78 P94V-TM-EN-5
P94V Chapter 5 - Voltage Protection Functions
This type of protection must be co-ordinated with any other overvoltage devices at other locations on the
system.
P94V-TM-EN-5 79
Chapter 5 - Voltage Protection Functions P94V
80 P94V-TM-EN-5
P94V Chapter 5 - Voltage Protection Functions
P94V-TM-EN-5 81
Chapter 5 - Voltage Protection Functions P94V
You set this using the VN>1 Function and VN>3 Function cells depending on the stage.
Stages 1 and 3 also provide a Timer Hold facility as described in Timer Hold facility
Stage 2 can have definite time characteristics only. This is set in the VN>2 status cell
The device derives the residual voltage internally from the three-phase voltage inputs supplied from either a
5-limb VT or three single-phase VTs. These types of VT design provide a path for the residual flux and
consequently permit the device to derive the required residual voltage. In addition, the primary star point of
the VT must be earthed. Three-limb VTs have no path for residual flux and are therefore unsuitable for this
type of protection.
82 P94V-TM-EN-5
P94V Chapter 5 - Voltage Protection Functions
VN>1 Start
VN
P94V-TM-EN-5 83
Chapter 5 - Voltage Protection Functions P94V
IED
E00800
84 P94V-TM-EN-5
P94V Chapter 5 - Voltage Protection Functions
IED
E00801
P94V-TM-EN-5 85
Chapter 5 - Voltage Protection Functions P94V
V 2> Start
V2
Start
V2> Voltage Set & & DT V2> Trip
Counter
VTS Fast Block
V2> Accelerate
V00805
86 P94V-TM-EN-5
P94V Chapter 5 - Voltage Protection Functions
Note:
Standing levels of NPS voltage (V2) are displayed in the V2 Magnitude cell of the MEASUREMENTS 1 column.
The operation time of the element depends on the application, but a typical setting would be in the region of
5 seconds.
P94V-TM-EN-5 87
Chapter 5 - Voltage Protection Functions P94V
88 P94V-TM-EN-5
P94V Chapter 5 - Voltage Protection Functions
1
&
1 Vavg<1 Trip
&
Vavg<Oper Mode &
Any Phase
Three Phase V00807
P94V-TM-EN-5 89
Chapter 5 - Voltage Protection Functions P94V
1
&
1 Vavg>1 Trip
&
Vavg>Oper Mode &
Any Phase
Three Phase V00808
V0avg>1 Delay
V00809
V1avg>1 Delay
V00810
90 P94V-TM-EN-5
P94V Chapter 5 - Voltage Protection Functions
P94V-TM-EN-5 91
Chapter 5 - Voltage Protection Functions P94V
92 P94V-TM-EN-5
FREQUENCY PROTECTION
FUNCTIONS
CHAPTER 6
Chapter 6 - Frequency Protection Functions P94V
94 P94V-TM-EN-5
P94V Chapter 6 - Frequency Protection Functions
1 CHAPTER OVERVIEW
The device provides a range of frequency protection functions. This chapter describes the operation of these
functions including the principles, logic diagrams and applications.
This chapter contains the following sections:
Chapter Overview 95
Frequency Protection Overview 96
Underfrequency Protection 97
Overfrequency Protection 99
Independent R.O.C.O.F Protection 101
Frequency-supervised R.O.C.O.F Protection 104
Average Rate of Change of Frequency Protection 107
Load Shedding and Restoration 110
P94V-TM-EN-5 95
Chapter 6 - Frequency Protection Functions P94V
Each stage can be disabled or enabled with the Stage (n) setting. The frequency protection can also be
blocked by an undervoltage condition if required.
96 P94V-TM-EN-5
P94V Chapter 6 - Frequency Protection Functions
3 UNDERFREQUENCY PROTECTION
A reduced system frequency implies that the net load is in excess of the available generation. Such a
condition can arise, when an interconnected system splits, and the load left connected to one of the
subsystems is in excess of the capacity of the generators in that particular subsystem. Industrial plants that
are dependent on utilities to supply part of their loads will experience underfrequency conditions when the
incoming lines are lost.
Many types of industrial loads have limited tolerances on the operating frequency and running speeds (e.g.
synchronous motors). Sustained underfrequency has implications on the stability of the system, whereby any
subsequent disturbance may damage equipment and even lead to blackouts. It is therefore essential to
provide protection for underfrequency conditions.
Freq Averaging
DT
Stg (n) f+t Freq & Stg (n) f+t Trp
Stage (n)
Enabled
V<B Status
Enabled
1
UV Block
V00850
P94V-TM-EN-5 97
Chapter 6 - Frequency Protection Functions P94V
The effectiveness of each load shedding stage depends on the proportion of power deficiency it represents.
If the load shedding stage is too small compared with the prevailing generation deficiency, then there may be
no improvement in the frequency. This should be taken into account when forming the load groups.
Time delays should be sufficient to override any transient dips in frequency, as well as to provide time for the
frequency controls in the system to respond. These should not be excessive as this could jeopardize system
stability. Time delay settings of 5 - 20 s are typical.
An example of a four-stage load shedding scheme for 50 Hz systems is shown below:
Stage Element Frequency Setting (Hz) Time Setting (Sec)
1 Stage 1(f+t) 49.0 20 s
2 Stage 2(f+t) 48.6 20 s
3 Stage 3(f+t) 48.2 10 s
4 Stage 4(f+t) 47.8 10 s
The relatively long time delays are intended to provide sufficient time for the system controls to respond. This
will work well in a situation where the decline of system frequency is slow. For situations where rapid decline
of frequency is expected, this load shedding scheme should be supplemented by rate of change of
frequency protection elements.
98 P94V-TM-EN-5
P94V Chapter 6 - Frequency Protection Functions
4 OVERFREQUENCY PROTECTION
An increased system frequency arises when the mechanical power input to a generator exceeds the
electrical power output. This could happen, for instance, when there is a sudden loss of load due to tripping
of an outgoing feeder from the plant to a load centre. Under such conditions, the governor would normally
respond quickly to obtain a balance between the mechanical input and electrical output, thereby restoring
normal frequency. Overfrequency protection is required as a backup to cater for cases where the reaction of
the control equipment is too slow.
Freq Averaging
DT
Stg (n) f+t Freq & Stg (n) f+t Trp
Stage (n)
Enabled
V<B Status
Enabled
1
UV Block
V00851
P94V-TM-EN-5 99
Chapter 6 - Frequency Protection Functions P94V
An example of two-stage overfrequency protection is shown below using stages 5 and 6 of the f+t elements.
However, settings for a real system will depend on the maximum frequency that equipment can tolerate for a
given period of time.
Stage Element Frequency Setting (Hz) Time Setting (Sec.)
1 Stage 5(f+t) 50.5 30
2 Stage 6(f+t) 51.0 20
The relatively long time delays are intended to provide time for the system controls to respond and will work
well in a situation where the increase of system frequency is slow.
For situations where rapid increase of frequency is expected, the protection scheme above could be
supplemented by rate of change of frequency protection elements.
In the system shown below, the generation in the MV bus is sized according to the loads on that bus,
whereas the generators linked to the HV bus produce energy for export to utility. If the links to the grid are
lost, the generation will cause the system frequency to rise. This rate of rise could be used to isolate the MV
bus from the HV system.
To utility
IPP generation
HV bus
Load
MV bus
Local generation
Load
E00857
100 P94V-TM-EN-5
P94V Chapter 6 - Frequency Protection Functions
P94V-TM-EN-5 101
Chapter 6 - Frequency Protection Functions P94V
Frequency
V
determination
df/dt Stg1 df /dt+t Sta
df /dt Avg.Cycles
-1
Stage (n)
Enabled
V<B Status
Enabled
1 1
UV Block
Stg(n) Block
Freq High
Freq Low
V00852
102 P94V-TM-EN-5
P94V Chapter 6 - Frequency Protection Functions
In this scheme, tripping of the last two stages is accelerated by using the independent rate of change of
frequency element. If the frequency starts falling at a high rate (> 3 Hz/s in this example), then stages 3 & 4
are shed at around 48.5 Hz, with the objective of improving system stability. Stage 5 serves as an alarm and
gives operators advance warning that the situation is critical.
P94V-TM-EN-5 103
Chapter 6 - Frequency Protection Functions P94V
The device will also indicate when an incorrect setting has been applied if the frequency threshold is set to
the nominal system frequency. There is no intentional time delay associated with this element, but time
delays could be applied using the PSL if required.
104 P94V-TM-EN-5
P94V Chapter 6 - Frequency Protection Functions
Frequency
V determination
df/dt
Frequency Frequency
V determination averaging
Stage (n)
Enabled
V<B Status
Enabled
1 1
UV Block
Stg(n)Block
Freq High
Freq Low
V00853
P94V-TM-EN-5 105
Chapter 6 - Frequency Protection Functions P94V
E00858
It may be possible to further improve the speed of load shedding by changing the frequency setting on the f
+df/dt element. In the settings outlined below, the frequency settings for this element have been set slightly
higher than the frequency settings for the f+t element. This difference will allow for the measuring time, and
will result in the tripping of the two elements at approximately the same frequency value. Therefore, the slow
frequency decline and fast frequency decline scenarios are independently monitored and optimised without
sacrificing system security.
Frequency Supervised Rate of Change of Frequency "f
Frequency "f+t [81U/81O]" Elements
+df/dt [81RF]" Elements
Frequency Setting Time Setting Frequency Setting Rate of Change of Frequency Setting
Stage
(Hz) (Sec.) (Hz) (Hz/sec.)
1 49 20 49.2 1.0
2 48.6 20 48.8 1.0
3 48.2 10 48.4 1.0
4 47.8 10 48.0 1.0
106 P94V-TM-EN-5
P94V Chapter 6 - Frequency Protection Functions
E00856
P94V-TM-EN-5 107
Chapter 6 - Frequency Protection Functions P94V
After time ∆t, the element is blocked from further operation until the frequency recovers to a value above the
supervising frequency threshold. If the element has operated, the trip DDB signal will be ON until the
frequency recovers to a value above the supervising frequency threshold.
The average rate of change of frequency is then measured based on the frequency difference, ∆f over the
settable time period, ∆t.
The following settings are relevant for Df/Dt protection:
● f+Df/Dt (n) Status: determines whether the stage is for falling or rising frequency conditions
● f+Df/Dt (n) Freq: defines the frequency pickup setting
● f+Df/Dt (n) Dfreq: defines the change in frequency that must be measured in a set time period
● f+Df/Dt (n) Dtime: sets the time period over which the frequency is monitiored
Frequency Frequency
V determination Averaging
Stg1 df /dt+t Sta
Frequency
& 1 comparision
Stg1 df /dt+t Trp
V<B Status
Enabled
1 1
UV Block
Stg(n)Block
Freq High
Freq Low
V00859
108 P94V-TM-EN-5
P94V Chapter 6 - Frequency Protection Functions
supervised rate of change function, "f+df/dt". With high Dt settings, the element acts as a frequency trend
monitor.
Although the element has a wide range of setting possibilities we recommend that the Dt setting is set
greater than 100 ms to ensure the accuracy of the element.
A possible four stage load shedding scheme using the average rate of change frequency element is shown
in the following table:
Frequency Average Rate of Change of Frequency "f+Df/Dt [81RAV]"
"f+t [81U/81O]" Elements Elements
(f+Df/Dt) f
(f+t) f Frequency (f+t) t (f+Df/Dt) Df Frequency (f+Df/Dt) Dt Time
Stage Frequency Setting
Setting (Hz) Time Setting (Sec.) Diff Setting, (Hz) Period, (Sec.)
(Hz)
1 49 20 49 0.5 0.5
2 48.6 20 48.6 0.5 0.5
3 48.2 10 48.2 0.5 0.5
4 47.8 10 47.8 0.5 0.5
In the above scheme, the faster load shed decisions are made by monitoring the frequency change over
500 ms. Therefore tripping takes place more slowly than in schemes employing frequency-supervised df/dt,
but the difference is not very much at this setting. If the delay jeopardises system stability, then the scheme
can be improved by increasing the independent "f" setting. Depending on how much this value is increased,
the frequency at which the "f+Df/Dt" element will trip also increases and so reduces the time delay under
more severe frequency fluctuations. For example, with the settings shown below, the first stage of load
shedding would be tripped approximately 300 msecs after 49.0 Hz is reached and at a frequency of
approximately 48.7 Hz.
Frequency Average Rate of Change of Frequency
"f+t [81U/81O]" Elements "f+Df/Dt [81RAV]" Elements
(f+Df/Dt) f (f+Df/Dt) Df
(f+t) f Frequency (f+t) t (f+Df/Dt) Dt Time
Stage Frequency Setting Frequency Diff
Setting (Hz) Time Setting (Sec) Period, (Sec.)
(Hz) Setting (Hz)
1 49 20 49.2 0.5 0.5 s
2 48.6 20 48.8 0.5 0.5 s
3 48.2 10 48.4 0.5 0.5 s
4 47.8 10 48.0 0.5 0.5 s
P94V-TM-EN-5 109
Chapter 6 - Frequency Protection Functions P94V
110 P94V-TM-EN-5
P94V Chapter 6 - Frequency Protection Functions
System Frequency
Restoration
Frequency
Holding Band
Shedding
Frequency
Trip
Underfrequency
Element Off
Complete
Holding
Timer Off
Time less than
Complete Holding Timer Setting
Restoration
Timer Off
On
Stage 1 Restore Start
Off
On
Stage 1 Restore Enable
Off
Underfrequency Trip System Frequency Partial System Frequency Restoration Time
Underfrequency Completes Stage
Stage (n) Load Decay Restoration Timer Recovery Continues
Element Pick -up Suspended (n) Load
Shedding Restoration Timer
System Frequency Resumes Timing
Restoration
Recovery Starts
Restoration Time Starts
Time
V00854
Figure 41: Load restoration with short deviation into holding band
If the system frequency remains in the holding band for too long it is likely that other system frequency
problems are occurring and it would be prudent to reset the restoration timer for that stage. For this reason,
as soon as the system frequency is measured to be within the holding band, the "Holding Timer" is initiated.
If the system frequency doesn’t leave the holding band before the holding timer setting has been exceeded,
the load restoration time delay for that stage is immediately reset.
Note:
The holding timer has a common setting for all stages of load restoration.
An example of the case when the time in the holding band is excessive is shown below.
P94V-TM-EN-5 111
Chapter 6 - Frequency Protection Functions P94V
System Frequency
Restoration
Frequency
Holding Band
Shedding
Frequency
Underfrequency Trip
Element Off
Holding Complete
Timer
Off
Restoration Time greater than
Holding Timer Setting
Timer Complete
Off
V00855
Figure 42: Load restoration with long deviation into holding band
112 P94V-TM-EN-5
P94V Chapter 6 - Frequency Protection Functions
V<B Status
Enabled
1 1
UV Block
Stg(n)Block
Freq High
Freq Low
Frequency Frequency
V determination Averaging
V00860
In this scheme, the time delays ensure that the most critical loads are reconnected (assuming that the higher
stages refer to more important loads). By restoring the load sequentially, system stability should normally be
P94V-TM-EN-5 113
Chapter 6 - Frequency Protection Functions P94V
maintained. These time settings are system dependent; higher or lower settings may be required depending
on the particular application.
It is possible to set up restoration schemes involving multiple frequencies. This allows faster restoration of
loads, but there is the possibility of continuous system operation at frequencies far removed from the
nominal. A typical scheme using two frequencies is illustrated below:
Restore Freq. Restoration Frequency Restore DelayRestoration Time Delay
Stage Holding Time Delay (S)
Setting (Hz) (S)
1 49.5 Hz 120 sec 20 sec
2 49.5 Hz 60 sec 20 sec
3 49.0 Hz 120 sec 20 sec
4 49.0 Hz 60 sec 20 sec
Staggered time settings may be used in this scheme as well, but the time separation among the restoration
of stages will be a function of the frequency recovery pattern. Time coordinated restoration can only be
guaranteed for those stages with a common restoration frequency setting.
114 P94V-TM-EN-5
AUTORECLOSE
CHAPTER 7
Chapter 7 - Autoreclose P94V
116 P94V-TM-EN-5
P94V Chapter 7 - Autoreclose
1 CHAPTER OVERVIEW
Selected models of this product provide sophisticated Autoreclose (AR) functionality. The purpose of this
chapter is to describe the operation of this functionality including the principles, logic diagrams and
applications.
This chapter contains the following sections:
Chapter Overview 117
Introduction to 3-phase Autoreclose 118
Implementation 119
Autoreclose Function Inputs 120
Autoreclose Function Outputs 123
Autoreclose Function Alarms 125
Autoreclose Operation 126
Setting Guidelines 143
P94V-TM-EN-5 117
Chapter 7 - Autoreclose P94V
Autoreclosing provides an important benefit on circuits using time-graded protection, in that it allows the use
of instantaneous protection to provide a high speed first trip. With fast tripping, the duration of the power arc
resulting from an overhead line fault is reduced to a minimum. This lessens the chance of damage to the
line, which might otherwise cause a transient fault to develop into a permanent fault. Using instantaneous
protection also prevents blowing of fuses in teed feeders, as well as reducing circuit breaker maintenance by
eliminating pre-arc heating.
When instantaneous protection is used with autoreclosing, the scheme is normally arranged to block the
instantaneous protection after the first trip. Therefore, if the fault persists after re-closure, the time-graded
protection will provide discriminative tripping resulting in the isolation of the faulted section. However, for
certain applications, where the majority of the faults are likely to be transient, it is common practise to allow
more than one instantaneous trip before the instantaneous protection is blocked.
Some schemes allow a number of re-closures and time-graded trips after the first instantaneous trip, which
may result in the burning out and clearance of semi-permanent faults. Such a scheme may also be used to
allow fuses to operate in teed feeders where the fault current is low.
When considering feeders that are partly overhead line and partly underground cable, any decision to install
auto-reclosing should be subject to analysis of the data (knowledge of the frequency of transient faults). This
is because this type of arrangement probably has a greater proportion of semi-permanent and permanent
faults than for purely overhead feeders. In this case, the advantages of autoreclosing are small. It can even
be disadvantageous because re-closing on to a faulty cable is likely to exacerbate the damage.
118 P94V-TM-EN-5
P94V Chapter 7 - Autoreclose
3 IMPLEMENTATION
Autoreclose functionality is a software option, which is selected when ordering the device, so this description
only applies to models with this option.
The P94V does not have any CT inputs, therefore Autoreclose cannot be initiated by an internal current
protection function. It can only be initiated by an external signal originating from another device such as a
P14N, P14D, or P14x. In this case, the relevant opto-input would be mapped to the DDB signal Ext AR Prot
Strt and Ext AR Prot Trip.
The Autoreclose function for P40Agile products with current protection (P14D and P14N) can be started by
their internal SEF protection function which produces an internal SEF Protection Start signal and an internal
SEF Protection Trip signal. These in turn are used to drive internal AR SEF logic. There is one external DDB
signal associated with the SEF logic, which is the Block SEF Protection DDB signal (AR Blk SEF).
The P94V does not provide SEF protection, therefore cannot provide internal SEF protection Start and Trip
signals. However, it is highly desirable to a) keep the Autoreclose internal logic identical to the other products
in the range, and b) continue providing the AR Blk SEF DDB signal in case it needs to be used externally.
This allows the device to be used as an independent Autoreclose device, which can interact with all Alstom
products without any reduction of functionality.
For these reasons, the P94V provides two additional DDB signals - Ext AR SEF Start and Ext AR SEF Trip.
These external signals can start and trip the internal AR SEF logic, which can consequently produce an AR
Blk SEF DDB signal. This signal is therefore available for sending to an external device or feeding back to
the initiating device, if so desired.
The Autoreclose-specific settings are contained in the AUTORECLOSE column. In addition to the settings
contained in this column, the Autoreclose function may also need some settings in other columns such as
CB CONTROL and SYSTEM CHECKS, as well as in the blocking cells of relevant protection columns.
The Autoreclose function can be set to perform a single-shot, two-shot, three-shot or four-shot cycle. You
select this by the Number of Shots cell in the AUTORECLOSE column. You can also initiate a separate
Autoreclose cycle for the SEF protection, with a different number of shots, selected by the Number SEF
Shots cell. Dead times for all shots can be adjusted independently.
The dead time starts in one of two cases; when the circuit breaker has tripped, or when the protection has
reset. You select which method with the Start Dead t On setting.
At the end of the relevant dead time, a CB close 3ph signal is given, providing it is safe for the circuit
breaker to close. This is determined by checking that certain system conditions are met as specified by the
System Checks functionality.
It is safe to close the circuit breaker providing that:
● only one side of the circuit breaker is live (either dead line / live bus, or live line / dead bus), or
● if both bus and line sides of the circuit breaker are live, the system voltages are synchronised.
In addition, the energy source powering the circuit breaker (for example the closing spring) must be fully
charged. This is indicated from the CB Healthy DDB input.
When the CB has closed, the reclaim time starts. If the circuit breaker does not trip again, the Autoreclose
function resets at the end of the set reclaim time. If the protection operates during the reclaim time the device
either advances to the next shot in the Autoreclose cycle, or if all reclose attempts have been made, goes to
lockout.
CB Status signals must also be available, so the default setting for CB Status Input in the CB CONTROL
column, should be modified according to the application. The default PSL requires 52A, 52B and CB Healthy
logic inputs, so a setting of both 52A and 52B would be required for the CB Status Input if used with the
default PSL.
P94V-TM-EN-5 119
Chapter 7 - Autoreclose P94V
4.1 CB HEALTHY
It is necessary to establish if there is sufficient energy in the circuit breaker (spring charged, gas pressure
healthy, etc.) before the CB can be closed. This CB Healthy input is used to ensure this before initiating a
CB closed 3ph command. If on completion of the dead time, the CB Healthy input is low, and remains low
for a period given by the CB Healthy Time timer, lockout will result and the circuit breaker will remain open.
The majority of circuit breakers are only capable of providing a single trip-close-trip cycle, in which case the
CB Healthy signal would stay low after one Autoreclose shot, resulting in lockout.
This check can be disabled by not allocating an opto-input for the CB Healthy signal, whereby the signal
defaults to a High state.
4.2 BLOCK AR
The Block AR input blocks the Autoreclose function and causes a lockout. It can be used when protection
operation without Autoreclose is required. A typical example is on a transformer feeder, where Autoreclose
may be initiated by the feeder protection but blocked by the transformer protection.
120 P94V-TM-EN-5
P94V Chapter 7 - Autoreclose
4.15 AR RESTART
In some applications, it is sometimes necessary to initiate an Autoreclose cycle by means of connecting an
external signal to an opto-input. This would be when the normal interlock conditions are not all satisfied, i.e.
when the CB is open and the associated feeder is dead. If the AR Restart input is mapped to an opto-input,
activation of that opto-input will initiate an Autoreclose cycle irrespective of the status of the CB in Service
input, provided the other interlock conditions, are still satisfied.
P94V-TM-EN-5 121
Chapter 7 - Autoreclose P94V
122 P94V-TM-EN-5
P94V Chapter 7 - Autoreclose
5.1 AR IN PROGRESS
This signal is present during the complete re-close cycle from the start of protection to the end of the reclaim
time or lockout.
5.5 AR IN SERVICE
The AR In Service output indicates whether the Autoreclose is in or out of service. Autoreclose is In Service
when the device is in Auto mode and Out of Service when in the Non-Auto and Live Line modes.
P94V-TM-EN-5 123
Chapter 7 - Autoreclose P94V
124 P94V-TM-EN-5
P94V Chapter 7 - Autoreclose
6.2 AR CB UNHEALTHY
The AR CB Unhealthy alarm indicates that the CB Healthy input was not energised at the end of the CB
Healthy Time, leading to a lockout condition. This alarm is latched and must be reset manually.
6.3 AR LOCKOUT
The AR Lockout alarm indicates that the device is in a lockout status and that further re-close attempts will
not be made. This alarm can configured to reset automatically (self-reset) or manually as determined by the
setting Reset Lockout by in the CB CONTROL column.
P94V-TM-EN-5 125
Chapter 7 - Autoreclose P94V
7 AUTORECLOSE OPERATION
The Autoreclose function is a complex function consisting of several modules interacting with one another.
This is described in terms of separate logic diagrams, which link together by means of Internal signals
(depicted by the pink-coloured boxes. To help you with the analysis of the various Autoreclose modules, the
following table describes how these internal signals link up in the various logic diagrams. Each internal signal
is allocated with an ID, and the diagrams on which they appear are also identified.
Internal Appearing in
Input to AR function Appearing in diagrams Output from AR function
signal ID diagrams
1 Autoreclose Disabled V00505, V00507 Autoreclose Disabled V00501
2 Live Line Mode V00505, V00507, V00514 Live Line Mode V00501
3 Non Auto Mode V00505, V00507, V00514 Non Auto Mode V00501
4 Auto Mode (int) V00505, V00507, V00512 Auto Mode (int) V00501
5 Main Protection Start V00504, V00505, V00507, V00511, V00512 Main Protection Start V00502
6 SEF Protection Start V00504, V00505, V00511, V00512 SEF Protection Start V00502
7 Main Protection Trip V00505, V00513, V00514 Main Protection Trip V00503
8 SEF Protection Trip V00505, V00507, V00513, V00514 SEF Protection Trip V00503
9 Block Autoreclose V00513 Block Autoreclose V00515
10 SC Count >= Main Shots V00504 SC Count >= Main Shots V00505
11 SC Count >= SEF Shots V00504 SC Count >= SEF Shots V00505
12 Main High Shots V00505, V00513 Main High Shots V00504
13 SEF High Shots V00505, V00513 SEF High Shots V00504
14 Autoreclose Inhibit V00505, V00507, V00514 Autoreclose Inhibit V00512
15 Autoreclose Start V00508, V00509, V00511, V00513 Autoreclose Start V00505
16 Autoreclose Initiate V00508, V00513 Autoreclose Initiate V00505
17 SC Count > 4 V00506 SC Count > 4 V00505
18 Block Main Prot Trips V00507 Block Main Prot Trips V00506
19 Block SEF Prot Trips V00507 Block SEF Prot Trips V00506
20 Hold Reclaim Output V00511 Hold Reclaim Output V00509
Note:
Live Line Mode provides extra security for live line working on the protected feeder.
The Autoreclose function must first be enabled in the CONFIGURATION column. You can then select the
operating mode according to application requirements. The basic method of mode selection is determined by
the setting AR Mode Select in the AUTORECLOSE column, as summarised in the following table:
126 P94V-TM-EN-5
P94V Chapter 7 - Autoreclose
The Live Line Mode is controlled by AR Live Line Mode. If this is high, the scheme is forced into Live Line
Mode irrespective of the other signals.
MODE SETTINGS
4 POSITION SELECTOR SWITCH AUTO COMMAND MODE
OPTO SET MODE
USER SET MODE
AUTO
AUTO AUTO
LOGIC INPUT
IED
E00500
P94V-TM-EN-5 127
Chapter 7 - Autoreclose P94V
Auto-Reclose
Disable Autoreclose disabled 1
Enable
& Live Line Mode (int) 2
AR LiveLine Mode
AR Mode Select
Opto Set Mode
&
&
User Set Mode Non Auto Mode 3
&
&
Pulse Set Mode
& &
&
Command Mode
& 1 &
1
S
Autoreclose Mode Q Auto Mode (int) 4
&
Auto R
No Operation 1
&
Non Auto
&
&
& Enable
Output pulse on
rising edge of ‘Tele’
& Enable
&
Telecontrol Mode
V00501
In addition, the setting Ext Prot should be set to Initiate Main AR.
128 P94V-TM-EN-5
P94V Chapter 7 - Autoreclose
Although a protection start and a protection trip can initiate an AR cycle, several checks still have to be
performed before the initialisation signal is given. Some of the checks are listed below:
● Auto Mode has been selected
● Live line mode is disabled
● The number of main protection and SEF shots have not been reached
● Sequence co-ordination is enabled (for protection start to initiate AR. This is not necessary if a
protection trip is doing the initiating)
● The CB Ops Lockout DDB signal is not set
● The CB in Service DDB signal is high
V00518
AR Init TripTest
1 AR Trip Test
Test Autoreclose
3 pole Test
V00519
DDB: 032
Input L 1
DDB: 239
1 Block AR
DDB: 274
VN>1 Trip
Note:
This is not a default mapping . You must define this mapping in PSL .
V00520
P94V-TM-EN-5 129
Chapter 7 - Autoreclose P94V
V00504
Sequence Co-ord
Enabled
Disabled
Autoreclose Start
& S
1
Q DAR in Progress
R
CB in Service Autoreclose Initiate
S
Autoreclose Inhibit Q AR in Progress
R
AR Restart Increment on falling AR SeqCounter 0
edge
DAR Complete AR SeqCounter 1
1
AR SeqCounter 2
Lockout Alarm
AR SeqCounter 3
SC Counter
Reclaim Complete AR SeqCounter 4
Non Auto Mode 1 Reset SC Count > 4
Number of Shots SC Count >= Main Shots
Autoreclose Disabled
Number of SEF Shots SC Count >= SEF Shots
Live Line Mode
V00505
130 P94V-TM-EN-5
P94V Chapter 7 - Autoreclose
autoreclose cycle. These allow the instantaneous elements of phase, earth fault and SEF protection to be
selectively blocked for a CB trip sequence. For example, if Trip 1 Main is set to No Block and Trip 2 Main
is set to Block Inst Prot, the instantaneous elements of the phase and earth fault protection will be
available for the first trip but blocked afterwards for the second trip during the Autoreclose cycle. The logic for
this is shown below.
P94V-TM-EN-5 131
Chapter 7 - Autoreclose P94V
AR SeqCounter 0
No Block
AR SeqCounter 1
AR SeqCounter 2
Trip 3 Main
& 1 Block Main Prot Trips
Block Inst Prot
No Block
AR SeqCounter 3
AR SeqCounter 4
1
SC Count > 4
&
Trip 5 Main
Block Inst Prot
No Block
AR SeqCounter 0
AR SeqCounter 1
AR SeqCounter 2
AR SeqCounter 3
Trip 4 SEF
&
Block Inst Prot
No Block
AR SeqCounter 4
1
SC Count > 4
&
Trip 5 Main
Block Inst Prot
No Block
V00506
132 P94V-TM-EN-5
P94V Chapter 7 - Autoreclose
P94V-TM-EN-5 133
Chapter 7 - Autoreclose P94V
Autoreclose disabled
Lockout Alarm
Pre-Lockout
&
EFF Maint Lock
Block Inst Prot
No Block
Lockout Alarm
AR Lockout &
Block Inst Prot 1
No Block
AR Deselected
&
Block Inst Prot
No Block
AR In Prog
CB Closed 3 ph &
1
Auto Mode (int) &
20ms
Autoreclose inhibit
Manual Close
Block Inst Prot
No Block
V00507
134 P94V-TM-EN-5
P94V Chapter 7 - Autoreclose
indicate that the circuit breaker is healthy. Mapping the Dead Time Enabled function in PSL increases the
flexibility by allowing it to be triggered by other conditions such as Live Line/Dead Bus. If Dead Time
Enabled is not mapped in PSL, it defaults to high, so the dead time can run.
The dead time control logic is shown below.
AR with ChkSyn
Scheme 2 (Voltage models only)
Enable
&
Disable
1 &
AR Sync Check
1
DeadTime Enabled
AR SeqCounter 1 &
AR SeqCounter 4 &
CB Open 3ph
1
DT OK To Start & S
Q Reclose Checks
R
AR In Progress
Sequence Co-ord
Enable
&
Disable
Start Dead t On
&
Protection Reset
CB Trips
V00508
P94V-TM-EN-5 135
Chapter 7 - Autoreclose P94V
Reset Total AR
Yes Total Shot Counter
No (Increment on +ve edge)
CB Cls Fail
& Auto Close
CB Open 3ph
& S
Q
R
& S
DT Complete Q
R
Autoreclose Start &
Lockout Alarm
& S
Q
R
CB Closed 3ph
& AR CB Unhealthy
CB Healthy
&
& AR No Sys Check
AR SysChecks OK
V00509
136 P94V-TM-EN-5
P94V Chapter 7 - Autoreclose
AR SysChecks
1 AR SysChecks OK
SysChk on Shot 1
Enabled
&
AR SeqCounter 1
No system Checks
Enabled
1 AR SysChecks OK
AR with ChkSyn
Enabled
&
1 AR Sync Check
Check Sync 1 OK
AR with SysSyn
Enabled
&
Check Sync 2 OK
Reclose Checks
V00510
P94V-TM-EN-5 137
Chapter 7 - Autoreclose P94V
Lockout Reset
Yes
HMI Clear 1
Reset Lockout
Reset
Lockout alarm
& Lockout
CB Closed 3 ph
Reset Lockout by
CB Close
User Interface
CB Open 3 ph
& S
Autoclose Q
1 & S
R
Q Successful close
CB Closed 3 ph R
&
AR In Progress
Reclaim In Prog
tReclaim Extend
On Prot Start &
& & Reclaim Complete
No Operation 1
DT Complete
1
Autoreclose Start &
Sequence Co -ord
Enabled
AR SeqCounter 1
& nc Successful
Reset 1st shot Counter
AR SeqCounter 2
& nc Successful
Reset 2nd shot Counter
AR SeqCounter 3
& nc Successful
Reset 3rd shot Counter
AR SeqCounter 4
& nc Successful
Reset 4th shot Counter
CB Open 3 ph
& nc Persistant
AR Lockout
Reset Faults Counter
Reset Total AR
Yes
V00511
138 P94V-TM-EN-5
P94V Chapter 7 - Autoreclose
AR on Man Close
Inhibited
Enabled
&
Main Protection Start
1
SEF Protection Start
V00512
P94V-TM-EN-5 139
Chapter 7 - Autoreclose P94V
Reclaim Complete
&
CB Open 3ph
DT complete &
Autoreclose Start
AR in Progress
& S
Block Autoreclose Q
R
AR CB Unhealthy
1
CB Status Alarm
CB Cls Fail
S
HMI Clear Q AR Lockout
1 R
Lockout Reset
Yes
Reset
Lockout
Reset lockout
Lockout Alarm
&
CB Closed 3ph
Reset Lockout by
User Interface
CB Close
Man No Checksync
Protection Lockt
V00513
140 P94V-TM-EN-5
P94V Chapter 7 - Autoreclose
Autoreclose inhibit
Trip AR Inactive
Lockout
No Lockout
V00514
Note:
Lockout can also be caused by the CB condition monitoring functions in the CB MONITOR SETUP column.
The Reset Lockout input can be used to reset the Autoreclose function following lockout and reset any
Autoreclose alarms, provided that the signals that initiated the lockout have been removed. Lockout can also
be reset from the clear key or the command Lockout Reset from the CB CONTROL column.
There are two different Reset Lockout by settings. One in the CB CONTROL column and one in the
AUTORECLOSE column.
The Reset Lockout by setting in the CB CONTROL column is used to enable or disable reset of lockout
automatically from a manual close after the manual close time Man Close Rst Dly.
The Reset Lockout by setting in the AUTORECLOSE column is used to enable/disable the resetting of
lockout when the IED is in the Non-auto operating mode. The reset lockout methods are summarised in the
following table:
Reset Lockout Method When Available?
User Interface via the Clear key.
Always
Note: This will also reset all other protection flags
User interface via CB CONTROL command Lockout Reset Always
Opto-input Reset lockout Always
Following a successful manual close if CB CONTROL setting Reset Lockout by is
Only when set
set to CB Close
By selecting Non-Auto mode, provided AUTORECLOSE setting Reset Lockout by
Only when set
is set to Select NonAuto
P94V-TM-EN-5 141
Chapter 7 - Autoreclose P94V
You should program both the upstream and downstream Autoreclose IEDs with the same number of shots to
lockout and number of instantaneous trips before instantaneous protection is blocked. This will ensure that
for a persistent downstream fault, both Autoreclose IEDs will be on the same sequence count and will block
instantaneous protection at the same time. When sequence co-ordination is disabled, the circuit breaker has
to be tripped to start the dead time, and the sequence count is advanced by one.
When using sequence co-ordination for some applications such as downstream pole-mounted reclosers, it
may be desirable to re-enable instantaneous protection when the recloser has locked out. When the
downstream recloser has locked out there is no need for discrimination. This allows you to have
instantaneous, then IDMT, then instantaneous trips again during an Autoreclose cycle. Instantaneous
protection may be blocked or not blocked for each trip in an Autoreclose cycle using the Trip (n) Main and
Trip (n) SEF settings, where n is the number of the trip in the autoreclose cycle.
142 P94V-TM-EN-5
P94V Chapter 7 - Autoreclose
8 SETTING GUIDELINES
P94V-TM-EN-5 143
Chapter 7 - Autoreclose P94V
Typical first shot dead time settings on 11 kV distribution systems are 5 to 10 seconds. In situations where
two parallel circuits from one substation are carried on the same towers, it is often arranged for the dead
times on the two circuits to be staggered, e.g. one at 5 seconds and the other at 10 seconds, so that the two
circuit breakers do not reclose simultaneously following a fault affecting both circuits.
For multi-shot Autoreclose cycles, the second shot and subsequent shot dead times are usually longer than
the first shot, to allow time for semi-permanent faults to burn clear, and for the CB to recharge. Typical
second and third shot dead time settings are 30 seconds and 60 seconds respectively.
144 P94V-TM-EN-5
P94V Chapter 7 - Autoreclose
protection. To avoid this condition the dead time must be set in excess of the slowest reset time of either the
local device or any downstream protection.
Typical 11/33 kV dead time settings are as follows:
1st dead time = 5 - 10 seconds
2nd dead time = 30 seconds
3rd dead time = 60 - 180 seconds
4th dead time = 1 - 30 minutes
The reclaim time must be long enough to allow any time-delayed protection initiating Autoreclose to operate.
Failure to do so would result in premature resetting of the Autoreclose scheme and re-enabling of
instantaneous protection. If this condition arose, a permanent fault would effectively look like a number of
transient faults, resulting in continuous autoreclosing, unless additional measures are taken such as
excessive fault frequency lockout protection.
Sensitive earth fault protection is applied to detect high resistance earth faults and usually has a long time
delay, typically 10 - 15 seconds. This longer time may have to be taken into consideration, if autoreclosing
from SEF protection. High resistance earth faults are rarely transient and may be a danger to the public. It is
therefore common practise to block Autoreclose by operation of sensitive earth fault protection and lockout
the circuit breaker.
A typical 11/33 kV reclaim time is 5 - 10 seconds. This prevents unnecessary lockout during thunderstorms.
However, reclaim times of up to 60 - 180 seconds may be used elsewhere in the world.
P94V-TM-EN-5 145
Chapter 7 - Autoreclose P94V
146 P94V-TM-EN-5
MONITORING AND CONTROL
CHAPTER 8
Chapter 8 - Monitoring and Control P94V
148 P94V-TM-EN-5
P94V Chapter 8 - Monitoring and Control
1 CHAPTER OVERVIEW
As well as providing a range of protection functions, the product includes comprehensive monitoring and
control functionality.
This chapter contains the following sections:
Chapter Overview 149
Event Records 150
Disturbance Recorder 154
Measurements 155
CB Condition Monitoring 156
CB State Monitoring 157
Circuit Breaker Control 159
System Checks 164
P94V-TM-EN-5 149
Chapter 8 - Monitoring and Control P94V
2 EVENT RECORDS
Alstom Grid devices record events in an event log. This allows you to establish the sequence of events that
led up to a particular situation. For example, a change in a digital input signal or protection element output
signal would cause an event record to be created and stored in the event log. This could be used to analyse
how a particular power system condition was caused. These events are stored in the IED's non-volatile
memory. Each event is time tagged.
The event records can be displayed on an IED's front panel but it is easier to view them through the settings
application software. This can extract the events log from the device and store it as a single .evt file for
analysis on a PC.
The event records are detailed in the VIEW RECORDS column. The first event (0) is always the latest event.
After selecting the required event, you can scroll through the menus to obtain further details.
If viewing the event with the settings application software, simply open the extracted event file. All the events
are displayed chronologically. Each event is summarised with a time stamp (obtained from the Time & Date
cell) and a short description relating to the event (obtained from the Event Text cell. You can expand the
details of the event by clicking on the + icon to the left of the time stamp.
The following table shows the correlation between the fields in the setting application software's event viewer
and the cells in the menu database.
Field in Event Viewer Equivalent cell in menu DB Cell reference User settable?
Left hand column header VIEW RECORDS ® Time & Date 01 03 No
Right hand column header VIEW RECORDS ® Event Text 01 04 No
Description SYSTEM DATA ® Description 00 04 Yes
Plant reference SYSTEM DATA ® Plant Reference 00 05 Yes
Model number SYSTEM DATA ® Model Number 00 06 No
Address Displays the Courier address relating to the event N/A No
Event type VIEW RECORDS ® Menu Cell Ref 01 02 No
Event Value VIEW RECORDS ® Event Value 01 05 No
Evt Unique Id VIEW RECORDS ® Evt Unique ID 01 FE No
150 P94V-TM-EN-5
P94V Chapter 8 - Monitoring and Control
Standard events are further sub-categorised internally to include different pieces of information. These are:
● Protection events (starts and trips)
● Maintenance record events
● Platform events
Note:
The first event in the list (event 0) is the most recent event to have occurred.
P94V-TM-EN-5 151
Chapter 8 - Monitoring and Control P94V
The same information is also shown in the Alarm Status (n) cells in the SYSTEM DATA column. This
information is updated continuously, whereas the information in the event log is a snapshot at the time when
the event was created.
V01234
Note:
We recommend that you do not set the triggering contact to latching. This is because if you use a latching contact,
the fault record would not be generated until the contact has been fully reset.
152 P94V-TM-EN-5
P94V Chapter 8 - Monitoring and Control
P94V-TM-EN-5 153
Chapter 8 - Monitoring and Control P94V
3 DISTURBANCE RECORDER
The disturbance recorder feature allows you to record selected current and voltage inputs to the protection
elements, together with selected digital signals. The digital signals may be inputs, outputs, or internal DDB
signals. The disturbance records can be extracted using the disturbance record viewer in the settings
application software. The disturbance record file can also be stored in the COMTRADE format. This allows
the use of other packages to view the recorded data.
The integral disturbance recorder has an area of memory specifically set aside for storing disturbance
records. The number of records that can be stored is dependent on the recording duration. The minimum
duration is 0.1 s and the maximum duration is 10.5 s.
When the available memory is exhausted, the oldest records are overwritten by the newest ones.
Each disturbance record consists of a number of analogue data channels and digital data channels. The
relevant CT and VT ratios for the analogue channels are also extracted to enable scaling to primary
quantities.
The fault recording times are set by a combination of the Duration and Trigger Position cells. The Duration
cell sets the overall recording time and the Trigger Position cell sets the trigger point as a percentage of the
duration. For example, the default settings show that the overall recording time is set to 1.5 s with the trigger
point being at 33.3% of this, giving 0.5 s pre-fault and 1 s post fault recording times.
With the Trigger Mode set to Single, if further triggers occurs whilst a recording is taking place, the
recorder will ignore the trigger. However, with the Trigger Mode set to Extended, the post trigger timer will
be reset to zero, extending the recording time.
You can select any of the IED's analogue inputs as analogue channels to be recorded. You can also map
any of the opto-inputs output contacts to the digital channels. In addition, you may also map a number of
DDB signals such as Starts and LEDs to digital channels.
You may choose any of the digital channels to trigger the disturbance recorder on either a low to high or a
high to low transition, via the Input Trigger cell. The default settings are such that any dedicated trip output
contacts will trigger the recorder.
It is not possible to view the disturbance records locally via the front panel LCD. You must extract these
using suitable setting application software such as MiCOM S1 Agile.
154 P94V-TM-EN-5
P94V Chapter 8 - Monitoring and Control
4 MEASUREMENTS
P94V-TM-EN-5 155
Chapter 8 - Monitoring and Control P94V
5 CB CONDITION MONITORING
The device records various statistics related to each circuit breaker trip operation, allowing an accurate
assessment of the circuit breaker condition to be determined. The circuit breaker condition monitoring
counters are incremented every time the device issues a trip command.
These statistics are available in the CB CONDITION column. The menu cells are counter values only, and
cannot be set directly. The counters may be reset, however, during maintenance. This is achieved with the
setting Reset CB Data.
Note:
When in Commissioning test mode the CB condition monitoring counters are not updated.
156 P94V-TM-EN-5
P94V Chapter 8 - Monitoring and Control
6 CB STATE MONITORING
CB State monitoring is used to verify the open or closed state of a circuit breaker. Most circuit breakers have
auxiliary contacts through which they transmit their status (open or closed) to control equipment such as
IEDs. These auxiliary contacts are known as:
● 52A for contacts that follow the state of the CB
● 52B for contacts that are in opposition to the state of the CB
This device can be set to monitor both of these types of circuit breaker state indication. If the state is
unknown for some reason, an alarm can be raised.
Some CBs provide both sets of contacts. If this is the case, these contacts will normally be in opposite
states. Should both sets of contacts be open, this would indicate one of the following conditions:
● Auxiliary contacts/wiring defective
● Circuit Breaker (CB) is defective
● CB is in isolated position
Should both sets of contacts be closed, only one of the following two conditions would apply:
● Auxiliary contacts/wiring defective
● Circuit Breaker (CB) is defective
If any of the above conditions exist, an alarm will be issued after a 5 s time delay. An output contact can be
assigned to this function via the programmable scheme logic (PSL). The time delay is set to avoid unwanted
operation during normal switching duties.
In the CB CONTROL column there is a setting called CB Status Input. This cell can be set at one of the
following four options:
● None
● 52A
● 52B
● Both 52A and 52B
Where None is selected no CB status is available. Where only 52A is used on its own then the device will
assume a 52B signal opposite to the 52A signal. Circuit breaker status information will be available in this
case but no discrepancy alarm will be available. The above is also true where only a 52B is used. If both 52A
and 52B are used then status information will be available and in addition a discrepancy alarm will be
possible, according to the following table:
Auxiliary Contact Position CB State Detected Action
52A 52B
Open Closed Breaker open Circuit breaker healthy
Closed Open Breaker closed Circuit breaker healthy
Closed Closed CB failure Alarm raised if the condition persists for greater than 5 s
Open Open State unknown Alarm raised if the condition persists for greater than 5 s
P94V-TM-EN-5 157
Chapter 8 - Monitoring and Control P94V
CB Status Input
None
52A
52B
Both 52A and 52B
&
CB Aux 3ph(52-A)
& 1 CB Closed 3 ph
& 1
Plant Status
CB1 Closed
X1
CB1 Open
& 1
& 1 CB Open 3 ph
&
V01200
158 P94V-TM-EN-5
P94V Chapter 8 - Monitoring and Control
Circuit Breaker control is only possible if the circuit breaker in question provides auxiliary contacts. The CB
Status Input cell in the CB CONTROL column must be set to the type of circuit breaker. If no CB auxiliary
contacts are available then this cell should be set to None, and no CB control will be possible.
For local control, the CB control by cell should be set accordingly.
The output contact can be set to operate following a time delay defined by the setting Man Close Delay.
One reason for this delay is to give personnel time to safely move away from the circuit breaker following a
CB close command.
The control close cycle can be cancelled at any time before the output contact operates by any appropriate
trip signal, or by activating the Reset Close Dly DDB signal.
The length of the trip and close control pulses can be set via the Trip Pulse Time and Close Pulse Time
settings respectively. These should be set long enough to ensure the breaker has completed its open or
close cycle before the pulse has elapsed.
If an attempt to close the breaker is being made, and a protection trip signal is generated, the protection trip
command overrides the close command.
The Reset Lockout by setting is used to enable or disable the resetting of lockout automatically from a
manual close after the time set by Man Close RstDly.
If the CB fails to respond to the control command (indicated by no change in the state of CB Status inputs)
an alarm is generated after the relevant trip or close pulses have expired. These alarms can be viewed on
the LCD display, remotely, or can be assigned to output contacts using the programmable scheme logic
(PSL).
Note:
The CB Healthy Time and Sys Check time set under this menu section are applicable to manual circuit breaker
operations only. These settings are duplicated in the AUTORECLOSE menu for autoreclose applications.
The Lockout Reset and Reset Lockout by settings are applicable to CB Lockouts associated with manual
circuit breaker closure, CB Condition monitoring (Number of circuit breaker operations, for example) and
autoreclose lockouts.
The device includes the following options for control of a single circuit breaker:
● The IED menu (local control)
● The Hotkeys (local control)
● The function keys (local control)
● The opto-inputs (local control)
● SCADA communication (remote control)
P94V-TM-EN-5 159
Chapter 8 - Monitoring and Control P94V
For this to work you have to set the CB control by cell to option 1 Local, option 3 Local + Remote,
option 5 Opto+Local, or option 7 Opto+Local+Remote in the CB CONTROL column.
If the CB is currently closed, the command text on the bottom right of the LCD screen will read Trip.
Conversely, if the CB is currently open, the command text will read Close.
If you execute a Trip, a screen with the CB status will be displayed once the command has been
completed. If you execute a Close, a screen with a timing bar will appear while the command is being
executed. This screen also gives you the option to cancel or restart the close procedure. The time delay is
determined by the Man Close Delay setting in the CB CONTROL menu. When the command has been
executed, a screen confirming the present status of the circuit breaker is displayed. You are then prompted
to select the next appropriate command or exit.
If no keys are pressed for a period of 5 seconds while waiting for the command confirmation, the device will
revert to showing the CB Status. If no key presses are made for a period of 25 seconds while displaying the
CB status screen, the device will revert to the default screen.
To avoid accidental operation of the trip and close functionality, the hotkey CB control commands are
disabled for 10 seconds after exiting the hotkey menu.
The hotkey functionality is summarised graphically below:
Default Display
HOTKEY CB CTRL
Hotkey Menu
CB closed CB open
TRIP EXIT CONFIRM CANCEL EXIT CLOSE CANCEL CONFIRM CANCEL RESTART
E01209
160 P94V-TM-EN-5
P94V Chapter 8 - Monitoring and Control
Note:
Not all models provide function keys.
P94V-TM-EN-5 161
Chapter 8 - Monitoring and Control P94V
Protection Trip
Trip
Remote
Control
Trip Close
Remote
Control
Close
Local
Remote
Trip Close
E01207
162 P94V-TM-EN-5
P94V Chapter 8 - Monitoring and Control
&
Init close CB 1 Close in Prog
Trip Command In 1
1
Ext. Trip 3ph
Control Trip
CB Open 3ph
1
CB Closed 3ph
CB healthy window
C/S window
Voltage models only
& Man No Checksync
Man Check Synch
V01208
P94V-TM-EN-5 163
Chapter 8 - Monitoring and Control P94V
8 SYSTEM CHECKS
In some situations it is possible for both "bus" and "line" sides of a circuit breaker to be live when a circuit
breaker is open - for example at the ends of a feeder that has a power source at each end. Therefore, it is
normally necessary to check that the network conditions on both sides are suitable, before closing the circuit
breaker. This applies to both manual circuit breaker closing and autoreclosing. If a circuit breaker is closed
when the line and bus voltages are both live, with a large phase angle, frequency or magnitude difference
between them, the system could be subjected to an unacceptable shock, resulting in loss of stability, and
possible damage to connected machines.
The System Checks functionality involves monitoring the voltages on both sides of a circuit breaker, and if
both sides are live, performing a synchronisation check to determine whether any differences in voltage
magnitude, phase angle or frequency are within permitted limits.
The pre-closing system conditions for a given circuit breaker depend on the system configuration, and for
autoreclosing, on the selected autoreclose program. For example, on a feeder with delayed autoreclosing,
the circuit breakers at the two line ends are normally arranged to close at different times. The first line end to
close usually has a live bus and a dead line immediately before reclosing. The second line end circuit
breaker now sees a live bus and a live line.
If there is a parallel connection between the ends of the tripped feeder the frequencies will be the same, but
any increased impedance could cause the phase angle between the two voltages to increase. Therefore just
before closing the second circuit breaker, it may be necessary to perform a synchronisation check, to ensure
that the phase angle between the two voltages has not increased to a level that would cause unacceptable
shock to the system when the circuit breaker closes.
If there are no parallel interconnections between the ends of the tripped feeder, the two systems could lose
synchronism altogether and the frequency at one end could "slip" relative to the other end. In this situation,
the second line end would require a synchronism check comprising both phase angle and slip frequency
checks.
If the second line-end busbar has no power source other than the feeder that has tripped; the circuit breaker
will see a live line and dead bus assuming the first circuit breaker has re-closed. When the second line end
circuit breaker closes the bus will charge from the live line (dead bus charge).
8.1.1 VT CONNECTIONS
The device provides inputs for a three-phase "Main VT" and at least one single-phase VT for check
synchronisation. Depending on the primary system arrangement, the Main VT may be located on either the
line-side of the busbar-side of the circuit breaker, with the Check Sync VT on the other. Normally, the Main
VT is located on the line-side (as per the default setting), but this is not always the case. For this reason, a
setting is provided where you can define this. This is the Main VT Location setting, which is found in the CT
AND VT RATIOS column.
The Check Sync VT may be connected to one of the phase-to-phase voltages or phase-to-neutral voltages.
This needs to be defined using the CS Input setting in the CT AND VT RATIOS column. Options are, A-B, B-
C, C-A, A-N, B-N, or C-N.
164 P94V-TM-EN-5
P94V Chapter 8 - Monitoring and Control
P94V-TM-EN-5 165
Chapter 8 - Monitoring and Control P94V
E01204
166 P94V-TM-EN-5
P94V Chapter 8 - Monitoring and Control
& CS Vline<
CS Vbus<
& CS Vbus<
CS Vline> Vbus
& CS Vline>Vbus
CS Vline< Vbus
& CS Vline<Vbus
CS1 Fline > Fbus
& CS1 Fline >Fbus
CS1 Fline < Fbus
& CS1 Fline <Fbus
CS1 Angle not OK+
& CS1 Ang Not OK+
CS1 Angle not OK-
& CS1 Ang Not OK-
CS2 Fline > Fbus
& CS2 Fline >Fbus
CS2 Fline < Fbus
& CS2 Fline <Fbus
CS2 Angle not OK+
& CS2 Ang Not OK+
CS2 Angle not OK-
& CS2 Ang Not OK-
Angle rotating anticlockwise
& CS Ang Rot ACW
Angle rotating clockwise
VTS Fast Block & CS Ang Rot CW
1
F out of Range
CS1 Status
Enabled & Check Sync1 OK
CS1 Enabled
CS2 Status
Enabled & Check Sync2 OK
CS2 Enabled
SS Status
Enabled & System Split
SysSplit Enabled
V01205
P94V-TM-EN-5 167
Chapter 8 - Monitoring and Control P94V
SysChks Inactive
Check Sync 1 OK
Check Sync 2 OK
&
Dead Line
&
Live Bus
V02028
Examples
For CS1, where the Phase Angle setting is 30° and the Timer setting is 3.3 s, the “slipping” vector has to
remain within +/- 30° of the reference vector for at least 3.3 seconds. Therefore a synchronisation check
output will not be given if the slip is greater than 2 x 30° in 3.3 seconds.
Therefore, the maximum slip frequency = 2x30/360x3.3 = 0.0505 hz.
For CS2, where the Phase Angle setting is 10° and the Timer setting is 0.1 sec., the slipping vector has to
remain within 10° of the reference vector, with the angle decreasing, for 0.1 sec. When the angle passes
through zero and starts to increase, the synchronisation check output is blocked. Therefore an output will not
be given if the slip is greater than 10° in 0.1 second.
Therefore, the maximum slip frequency = 10/360x0.1 = 0.278 Hz.
Slip control by Timer is not practical for “large slip/small phase angle” applications, because the timer
settings required are very small, sometimes less than 0.1 seconds. For these situations, slip control by
frequency is better.
168 P94V-TM-EN-5
P94V Chapter 8 - Monitoring and Control
If Slip Control by Frequency + Timer is selected, for an output to be given, the slip frequency must be less
than BOTH the set Slip Freq. value and the value determined by the Phase Angle and Timer settings.
By enabling both CS1 and CS2, the device can be configured to allow CB closure if either of the two
conditions is detected.
For manual circuit breaker closing with synchronism check, some utilities might prefer to arrange the logic to
check initially for condition 1 only. However, if a System Split is detected before the condition 1 parameters
are satisfied, the device will switch to checking for condition 2 parameters instead, based on the assumption
that a significant degree of slip must be present when system split conditions are detected. This can be
arranged by suitable PSL logic, using the System Check DDB signals.
P94V-TM-EN-5 169
Chapter 8 - Monitoring and Control P94V
170 P94V-TM-EN-5
SUPERVISION
CHAPTER 9
Chapter 9 - Supervision P94V
172 P94V-TM-EN-5
P94V Chapter 9 - Supervision
1 CHAPTER OVERVIEW
This chapter describes the supervison functions.
This chapter contains the following sections:
Chapter Overview 173
DC Supply Monitor 174
Trip Circuit Supervision 176
P94V-TM-EN-5 173
Chapter 9 - Supervision P94V
2 DC SUPPLY MONITOR
This product can be powered using either a DC or AC supply. As a DC supply is normally used, a DC Supply
Monitoring feature is included to indicate the DC supply status. The nominal DC Station supply is 48 V DC,
which is provided by a bank of batteries. It is sometimes possible for this nominal supply to fall below or rise
above acceptable operational limits. If the voltage is too high, it may indicate overcharging. If the voltage is
too low, it may indicate a failing battery.
In such cases it is very useful to have DC supply monitoring functionality. The P40 Agile products provide
such functionality by measuring the auxiliary DC supply fed into the device and processing this information
using settings to define certain limits. In addition, the DC Auxiliary Supply value can be displayed on the front
panel LCD to a resolution of 0.1 V DC. The measuring range is from 19 V DC to 300 V DC.
Zone 1 (undervoltage)
174 P94V-TM-EN-5
P94V Chapter 9 - Supervision
Vdc
Vdc1 Status
Enabled
InhibitDC SupMon
V01220
P94V-TM-EN-5 175
Chapter 9 - Supervision P94V
Note:
A 52a CB auxiliary contact follows the CB position. A 52b auxiliary contact is the opposite.
+ve
Blocking diode
52B
176 P94V-TM-EN-5
P94V Chapter 9 - Supervision
Warning:
If your IED has Opto Mode settings (Opto 9 Mode, Opto 10 Mode, Opto 11
Mode) in the OPTO CONFIG column, these settings MUST be set to TCS.
0 0
Opto Input dropoff straight *Output Relay
400 0
50
& pickup Latching LED
0
User Alarm
P94V-TM-EN-5 177
Chapter 9 - Supervision P94V
+ve
52B
R1 Opto-input 1
Circuit Breaker
-ve
R2 Opto-input 2
V01215
Warning:
If your IED has Opto Mode settings (Opto 9 Mode, Opto 10 Mode, Opto 11
Mode) in the OPTO CONFIG column, these settings MUST be set to TCS.
50
& pickup Latching LED
0
User Alarm
178 P94V-TM-EN-5
P94V Chapter 9 - Supervision
+ve
R3
Output Relay Trip coil
Trip path 52A
R2
52B
Warning:
If your IED has Opto Mode settings (Opto 9 Mode, Opto 10 Mode, Opto 11
Mode) in the OPTO CONFIG column, these settings MUST be set to TCS.
P94V-TM-EN-5 179
Chapter 9 - Supervision P94V
0 0
Opto Input dropoff straight *Output Relay
400 0
50
& pickup Latching LED
0
User Alarm
+ve
52B
R1 Opto-input 1
Circuit Breaker
-ve
R2 Opto-input 2
V01222
180 P94V-TM-EN-5
P94V Chapter 9 - Supervision
ceases to flow, resulting in both opto-inputs outputting logic 0. This will open the output relay and energise
the user alarm.
For the momentary tripping condition, none of the opto-inputs are energised. To tide over this normal CB
operation, a drop-off time delay of about 400 ms is added in the PSL.
Warning:
If your IED has Opto Mode settings (Opto 9 Mode, Opto 10 Mode, Opto 11
Mode) in the OPTO CONFIG column, these settings MUST be set to TCS.
Opto-input 1
0 0
1 dropoff straight NC Output Relay
400 0
Opto-input 2
50
& pickup Latching LED
0
User Alarm
V01223
P94V-TM-EN-5 181
Chapter 9 - Supervision P94V
182 P94V-TM-EN-5
DIGITAL I/O AND PSL
CONFIGURATION
CHAPTER 10
Chapter 10 - Digital I/O and PSL Configuration P94V
184 P94V-TM-EN-5
P94V Chapter 10 - Digital I/O and PSL Configuration
1 CHAPTER OVERVIEW
This chapter introduces the PSL (Programmable Scheme Logic) Editor, and describes the configuration of
the digital inputs and outputs. It provides an outline of scheme logic concepts and the PSL Editor. This is
followed by details about allocation of the digital inputs and outputs, which require the use of the PSL Editor.
A separate "Settings Application Software" document is available that gives a comprehensive description of
the PSL, but enough information is provided in this chapter to allow you to allocate the principal digital inputs
and outputs.
This chapter contains the following sections:
Chapter Overview 185
Configuring Digital Inputs and Outputs 186
Scheme Logic 187
Configuring the Opto-Inputs 190
Assigning the Output Relays 191
Fixed Function LEDs 192
Configuring Programmable LEDs 193
Function Keys 195
Control Inputs 196
P94V-TM-EN-5 185
Chapter 10 - Digital I/O and PSL Configuration P94V
186 P94V-TM-EN-5
P94V Chapter 10 - Digital I/O and PSL Configuration
3 SCHEME LOGIC
The product is supplied with pre-loaded Fixed Scheme Logic (FSL) and Programmable Scheme Logic (PSL).
The Scheme Logic is a functional module within the IED, through which all mapping of inputs to outputs is
handled. The scheme logic can be split into two parts; the Fixed Scheme Logic (FSL) and the Programmable
Scheme Logic (PSL). It is built around a concept called the digital data bus (DDB). The DDB encompasses
all of the digital signals (DDBs) which are used in the FSL and PSL. The DDBs included digital inputs,
outputs, and internal signals.
The FSL is logic that has been hard-coded in the product. It is fundamental to correct interaction between
various protection and/or control elements. It is fixed and cannot be changed.
The PSL gives you a facility to develop custom schemes to suit your application if the factory-programmed
default PSL schemes do not meet your needs. Default PSL schemes are programmed before the product
leaves the factory. These default PSL schemes have been designed to suit typical applications and if these
schemes suit your requirements, you do not need to take any action. However, if you want to change the
input-output mappings, or to implement custom scheme logic, you can change these, or create new PSL
schemes using the PSL editor.
The PSL consists of components such as logic gates and timers, which combine and condition DDB signals.
The logic gates can be programmed to perform a range of different logic functions and. The number of inputs
to a logic gate are not limited. The timers can be used either to create a programmable delay or to condition
the logic outputs. Output contacts and programmable LEDs have dedicated conditioners.
The PSL logic is event driven. Only the part of the PSL logic that is affected by the particular input change
that has occurred is processed. This minimises the amount of processing time used by the PSL ensuring
industry leading performance.
The following diagram shows how the scheme logic interacts with the rest of the IED.
P94V-TM-EN-5 187
Chapter 10 - Digital I/O and PSL Configuration P94V
SL outputs
SL inputs
Opto-inputs Programmable LEDs
PSL and FSL
Goose outputs
Control inputs
Goose inputs
V02011
188 P94V-TM-EN-5
P94V Chapter 10 - Digital I/O and PSL Configuration
Example:
Date/time: This cell displays the date and time when the PSL scheme was downloaded to the IED.
Example:
18 Nov 2002
08:59:32.047
Grp(n) PSL ID: This cell displays a unique ID number for the downloaded PSL scheme.
Example:
Grp(n) PSL ID
ID - 2062813232
P94V-TM-EN-5 189
Chapter 10 - Digital I/O and PSL Configuration P94V
190 P94V-TM-EN-5
P94V Chapter 10 - Digital I/O and PSL Configuration
Note:
Contact Conditioners are only available if they have not all been used. In some default PSL schemes, all Contact
Conditioners might have been used. If that is the case, and you want to use them for something else, you will need to
re-assign them.
On the toolbar there is another button associated with the relay outputs. The button looks like this:
This is the "Contact Signal" button. It allows you to put replica instances of a conditioned output relay into the
PSL, preventing you having to make cross-page connections which might detract from the clarity of the
scheme.
P94V-TM-EN-5 191
Chapter 10 - Digital I/O and PSL Configuration P94V
You enable the automatic self-resetting with the Sys Fn Links cell in the SYSTEM DATA column. A '0'
disables self resetting and a '1' enables self resetting.
The reset occurs when the circuit is reclosed and the Any Pole Dead signal has been reset for three
seconds providing the Any Start signal is inactive. The reset is prevented if the Any Start signal is active
after the breaker closes.
The Trip LED logic is as follows:
Any Trip
Trip LED Trigger
Reset
1
Reset Relays/LED
Sys Fn Links
Trip LED S/Reset
&
Any Start
V01211
192 P94V-TM-EN-5
P94V Chapter 10 - Digital I/O and PSL Configuration
DDB signals are mapped in the PSL and used to illuminate the LEDs. For single-coloured programmable
LEDs there is one DDB signal per LED. For tri-coloured LEDs there are two DDB signals associated with the
LED. Asserting LED # Grn will illuminate the LED green. Asserting LED # Red will illuminate the LED red.
Asserting both DDB signals will illuminate the LED amber.
The illumination of an LED is controlled by means of a conditioner. Using the conditioner, you can decide
whether the LEDs reflect the real-time state of the DDB signals, or whether illumination is latched pending
user intervention.
To map an LED in the PSL you should use the LED Conditioner button in the toolbar to import it. You then
condition it according to your needs. The output(s) of the conditioner respect the attribute you have
assigned.
The toolbar button for a tri-colour LED looks like this:
Note:
LED Conditioners are only available if they have not all been used up, and in some default PSL schemes they might
be. If that is the case and you want to use them for something else, you will need to re-assign them.
On the toolbar there is another button associated with the LEDs. For a tri-coloured LED the button looks like
this:
P94V-TM-EN-5 193
Chapter 10 - Digital I/O and PSL Configuration P94V
It is the "LED Signal" button. It allows you to put replica instances of a conditioned LED into the PSL,
preventing you having to make cross-page connections which might detract from the clarity of the scheme.
194 P94V-TM-EN-5
P94V Chapter 10 - Digital I/O and PSL Configuration
8 FUNCTION KEYS
For most models, a number of programmable function keys are available. This allows you to assign function
keys to control functionality via the programmable scheme logic (PSL). Each function key is associated with
a programmable tri-colour LED, which you can program to give the desired indication on activation of the
function key.
These function keys can be used to trigger any function that they are connected to as part of the PSL. The
function key commands are found in the FUNCTION KEYS column.
Each function key is associated with a DDB signal as shown in the DDB table. You can map these DDB
signals to any function available in the PSL.
The Fn Key Status cell displays the status (energised or de-energised) of the function keys by means of a
binary string, where each bit represents a function key starting with bit 0 for function key 1.
Each function key has three settings associated with it, as shown:
● Fn Key (n), which enables or disables the function key
● Fn Key (n) Mode, which allows you to configure the key as toggled or normal
● Fn Key (n) label, which allows you to define the function key text that is displayed
The Fn Key (n) cell is used to enable (unlock) or disable (unlock) the function key signals in PSL. The Lock
setting has been provided to prevent further activation on subsequent key presses. This allows function keys
that are set to Toggled mode and their DDB signal active ‘high’, to be locked in their active state therefore
preventing any further key presses from deactivating the associated function. Locking a function key that is
set to the “Normal” mode causes the associated DDB signals to be permanently off. This safety feature
prevents any inadvertent function key presses from activating or deactivating critical functions.
When the Fn Key (n) Mode cell is set to Toggle, the function key DDB signal output will remain in the set
state until a reset command is given. In the Normal mode, the function key DDB signal will remain energised
for as long as the function key is pressed and will then reset automatically. In this mode, a minimum pulse
duration can be programmed by adding a minimum pulse timer to the function key DDB output signal.
The Fn Key Label cell makes it possible to change the text associated with each individual function key. This
text will be displayed when a function key is accessed in the function key menu, or it can be displayed in the
PSL.
The status of all function keys are recorded in non-volatile memory. In case of auxiliary supply interruption
their status will be maintained.
P94V-TM-EN-5 195
Chapter 10 - Digital I/O and PSL Configuration P94V
9 CONTROL INPUTS
The control inputs are software switches, which can be set or reset locally or remotely. These inputs can be
used to trigger any PSL function to which they are connected. There are three setting columns associated
with the control inputs: CONTROL INPUTS, CTRL I/P CONFIG and CTRL I/P LABELS. These are listed in
the Settings and Records appendix at the end of this manual.
196 P94V-TM-EN-5
COMMUNICATIONS
CHAPTER 11
Chapter 11 - Communications P94V
198 P94V-TM-EN-5
P94V Chapter 11 - Communications
1 CHAPTER OVERVIEW
This product supports Substation Automation System (SAS), and Supervisory Control and Data Acquisition
(SCADA) communication. The support embraces the evolution of communications technologies that have
taken place since microprocessor technologies were introduced into protection, control, and monitoring
devices which are now ubiquitously known as Intelligent Electronic Devices for the substation (IEDs).
As standard, all products support rugged serial communications for SCADA and SAS applications. By option,
any product can support Ethernet communications for more advanced SCADA and SAS applications.
P94V-TM-EN-5 199
Chapter 11 - Communications P94V
2 COMMUNICATION INTERFACES
The MiCOM P40 Agile products have a number of standard and optional communication interfaces. The
standard and optional hardware and protocols are summarised below:
Local settings
Front Standard USB Courier
Firmware download
SCADA
Rear serial port 1 Standard RS485 / K-Bus Remote settings Courier, MODBUS, IEC 60870-5-103, DNP3.0
IRIG-B
SCADA
Rear serial port 2
Optional RS485 Remote settings Courier
(order option)
IRIG-B
Rear Ethernet SCADA Courier, DNP3.0 over Ethernet, IEC 61850
Optional Ethernet/copper
port Remote settings (order option)
Rear Ethernet SCADA Courier or DNP3.0 over Ethernet
Optional Ethernet/fibre
port Remote settings (order option)
Note:
Optional communication boards are always fitted into slot C and only slot C.
It is only possible to fit one optional communications board, therefore Serial and Ethernet communications are
mutually exclusive.
200 P94V-TM-EN-5
P94V Chapter 11 - Communications
3 SERIAL COMMUNICATION
The physical layer standards that are used for serial communications for SCADA purposes are:
● Universal Serial Bus (USB)
● EIA(RS)485 (often abbreviated to RS485)
● K-Bus (a proprietary customization of RS485)
USB is a relatively new standard, which replaces EIA(RS232) for local communication with the IED (for
transferring settings and downloading firmware updates)
RS485 is similar to RS232 but for longer distances and it allows daisy-chaining and multi-dropping of IEDs.
K-Bus is a proprietary protocol quite similar to RS485, but it cannot be mixed on the same link as RS485.
Unlike RS485, K-Bus signals applied across two terminals are not polarised.
It is important to note that these are not data protocols. They only describe the physical characteristics
required for two devices to communicate with each other.
For a description of the K-Bus standard see K-Bus (on page202) and Alstom Grid's K-Bus interface guide
reference R6509.
A full description of the RS485 is available in the published standard.
P94V-TM-EN-5 201
Chapter 11 - Communications P94V
(due to retries), increasing message error counts, erratic communications, and in the worst case, complete
failure to communicate.
Note:
Some devices may be able to provide the bus bias, in which case external components would not be required.
6 – 9 V DC
180 Ω bias
Master 120 Ω
180 Ω bias
0V 120 Ω
V01000
Warning:
It is extremely important that the 120 Ω termination resistors are fitted.
Otherwise the bias voltage may be excessive and may damage the devices
connected to the bus.
3.3 K-BUS
K-Bus is a robust signalling method based on RS485 voltage levels. K-Bus incorporates message framing,
based on a 64 kbps synchronous HDLC protocol with FM0 modulation to increase speed and security.
The rear interface is used to provide a permanent connection for K-Bus, which allows multi-drop connection.
A K-Bus spur consists of up to 32 IEDs connected together in a multi-drop arrangement using twisted pair
wiring. The K-Bus twisted pair connection is non-polarised.
It is not possible to use a standard EIA(RS)232 to EIA(RS)485 converter to convert IEC 60870-5 FT1.2
frames to K-Bus. A protocol converter, namely the KITZ101, KITZ102 or KITZ201, must be used for this
purpose. Please consult Alstom Grid for information regarding the specification and supply of KITZ devices.
The following figure demonstrates a typical K-Bus connection.
202 P94V-TM-EN-5
P94V Chapter 11 - Communications
RS232 K-Bus
Note:
An RS232-USB converter is only needed if the local computer does not provide an RS232 port.
Further information about K-Bus is available in the publication R6509: K-Bus Interface Guide, which is
available on request.
P94V-TM-EN-5 203
Chapter 11 - Communications P94V
204 P94V-TM-EN-5
P94V Chapter 11 - Communications
5 DATA PROTOCOLS
The products supports a wide range of protocols to make them applicable to many industries and
applications. The exact data protocols supported by a particular product depend on its chosen application,
but the following table gives a list of the data protocols that are typically available.
The relationship of these protocols to the lower level physical layer protocols are as follows:
IEC 60870-5-103
MODBUS IEC 61850
Data Protocols
DNP3.0 DNP3.0
Courier Courier Courier Courier
Data Link Layer EIA(RS)485 Ethernet USB K-Bus
Physical Layer Copper or Optical Fibre
5.1 COURIER
This section should provide sufficient detail to enable understanding of the Courier protocol at a level
required by most users. For situations where the level of information contained in this manual is insufficient,
further publications (R6511 and R6512) containing in-depth details about the protocol and its use, are
available on request.
Courier is an Alstom Grid proprietary communication protocol. Courier uses a standard set of commands to
access a database of settings and data in the IED. This allows a master to communicate with a number of
slave devices. The application-specific elements are contained in the database rather than in the commands
used to interrogate it, meaning that the master station does not need to be preconfigured. Courier also
provides a sequence of event (SOE) and disturbance record extraction mechanism.
P94V-TM-EN-5 205
Chapter 11 - Communications P94V
With the exception of the Disturbance Recorder settings, changes made to the control and support settings
are implemented immediately and stored in non-volatile memory. Changes made to the Protection settings
and the Disturbance Recorder settings are stored in ‘scratchpad’ memory and are not immediately
implemented. These need to be committed by writing to the Save Changes cell in the CONFIGURATION
column.
Method 1
This uses a combination of three commands to perform a settings change:
First, enter Setting mode: This checks that the cell is settable and returns the limits.
1. Preload Setting: This places a new value into the cell. This value is echoed to ensure that setting
corruption has not taken place. The validity of the setting is not checked by this action.
2. Execute Setting: This confirms the setting change. If the change is valid, a positive response is
returned. If the setting change fails, an error response is returned.
3. Abort Setting: This command can be used to abandon the setting change.
This is the most secure method. It is ideally suited to on-line editors because the setting limits are extracted
before the setting change is made. However, this method can be slow if many settings are being changed
because three commands are required for each change.
Method 2
The Set Value command can be used to change a setting directly. The response to this command is either a
positive confirm or an error code to indicate the nature of a failure. This command can be used to implement
a setting more rapidly than the previous method, however the limits are not extracted. This method is
therefore most suitable for off-line setting editors such as MiCOM S1 Agile, or for issuing preconfigured
control commands.
206 P94V-TM-EN-5
P94V Chapter 11 - Communications
Event Types
The IED generates events under certain circumstances such as:
● Change of state of output contact
● Change of state of opto-input
● Protection element operation
● Alarm condition
● Setting change
● Password entered/timed-out
P94V-TM-EN-5 207
Chapter 11 - Communications P94V
The Menu Database contains tables of possible events, and shows how the contents of the above fields are
interpreted. Fault and Maintenance records return a Courier Type 3 event, which contains the above fields
plus two additional fields:
● Event extraction column
● Event number
These events contain additional information, which is extracted from the IED using the RECORDER
EXTRACTION column B4. Row 01 of the RECORDER EXTRACTION column contains a Select Record
setting that allows the fault or maintenance record to be selected. This setting should be set to the event
number value returned in the record. The extended data can be extracted from the IED by uploading the text
and data from the column.
The PSL settings can be uploaded and downloaded to and from the IED using this mechanism. The settings
application software must be used to edit the settings. It also performs checks on the validity of the settings
before they are transferred to the IED.
208 P94V-TM-EN-5
P94V Chapter 11 - Communications
COMMUNICATIONS
RP1 Protocol
Courier
4. Move down to the next cell (RP1 Address). This cell controls the address of the RP1 port on thje
device. Up to 32 IEDs can be connected to one spur. It is therefore necessary for each IED to have a
unique address so that messages from the master control station are accepted by one IED only.
Courier uses an integer number between 1 and 254 for the Relay Address. It is set to 255 by default,
which has to be changed. It is important that no two IEDs share the same address.
COMMUNICATIONS
RP1 Address
100
5. Move down to the next cell (RP1 InactivTimer). This cell controls the inactivity timer. The inactivity
timer controls how long the IED waits without receiving any messages on the rear port before revoking
any password access that was enabled and discarding any changes. For the rear port this can be set
between 1 and 30 minutes.
COMMUNICATIONS
RP1 Inactivtimer
10.00 mins.
6. If the optional fibre optic connectors are fitted, the RP1 PhysicalLink cell is visible. This cell controls
the physical media used for the communication (Copper or Fibre optic).
COMMUNICATIONS
RP1 PhysicalLink
Copper
7. Move down to the next cell (RP1 Card Status). This cell is not settable. It displays the status of the
chosen physical layer protocol for RP1.
COMMUNICATIONS
RP1 Card Status
K-Bus OK
8. Move down to the next cell (RP1 Port Config). This cell controls the type of serial connection. Select
between K-Bus or RS485.
P94V-TM-EN-5 209
Chapter 11 - Communications P94V
COMMUNICATIONS
RP1 Port Config
K-Bus
9. If using EIA(RS)485, the next cell (RP1 Comms Mode) selects the communication mode. The choice
is either IEC 60870 FT1.2 for normal operation with 11-bit modems, or 10-bit no parity. If using K-Bus
this cell will not appear.
COMMUNICATIONS
RP1 Comms Mode
IEC 60870 FT1.2
10. If using EIA(RS)485, the next cell down controls the baud rate. Three baud rates are supported; 9600,
19200 and 38400. If using K-Bus this cell will not appear as the baud rate is fixed at 64 kbps.
COMMUNICATIONS
RP1 Baud rate
19200
The IED address and baud rate can be selected using the front panel menu or by a suitable application such
as MiCOM S1 Agile.
210 P94V-TM-EN-5
P94V Chapter 11 - Communications
5.2.2 INITIALISATION
Whenever the device has been powered up, or if the communication parameters have been changed a reset
command is required to initialize the communications. The device will respond to either of the two reset
commands; Reset CU or Reset FCB (Communication Unit or Frame Count Bit). The difference between the
two commands is that the Reset CU command will clear any unsent messages in the transmit buffer,
whereas the Reset FCB command does not delete any messages.
The device will respond to the reset command with an identification message ASDU 5. The Cause of
Transmission (COT) of this response will be either Reset CU or Reset FCB depending on the nature of the
reset command. The content of ASDU 5 is described in the IEC 60870-5-103 section of the Menu Database,
available from Alstom Grid separately if required.
In addition to the above identification message, it will also produce a power up event.
The IEC 60870-5-103 profile in the Menu Database contains a complete listing of all events produced by the
device.
5.2.7 COMMANDS
A list of the supported commands is contained in the Menu Database. The device will respond to other
commands with an ASDU 1, with a cause of transmission (COT) indicating ‘negative acknowledgement’.
P94V-TM-EN-5 211
Chapter 11 - Communications P94V
Note:
IEC 60870-5-103 only supports up to 8 records.
COMMUNICATIONS
RP1 Protocol
IEC 60870-5-103
4. Move down to the next cell (RP1 Address). This cell controls the IEC 60870-5-103 address of the
IED. Up to 32 IEDs can be connected to one spur. It is therefore necessary for each IED to have a
unique address so that messages from the master control station are accepted by one IED only.
IEC 60870-5-103 uses an integer number between 0 and 254 for the address. It is important that no
two IEDs have the same IEC 60870 5 103 address. The IEC 60870-5-103 address is then used by the
master station to communicate with the IED.
COMMUNICATIONS
RP1 address
162
5. Move down to the next cell (RP1 Baud Rate). This cell controls the baud rate to be used. Two baud
rates are supported by the IED, 9600 bits/s and 19200 bits/s. Make sure that the baud rate
selected on the IED is the same as that set on the master station.
212 P94V-TM-EN-5
P94V Chapter 11 - Communications
COMMUNICATIONS
RP1 Baud rate
9600 bits/s
6. Move down to the next cell (RP1 Meas Period). The next cell down controls the period between
IEC 60870-5-103 measurements. The IEC 60870-5-103 protocol allows the IED to supply
measurements at regular intervals. The interval between measurements is controlled by this cell, and
can be set between 1 and 60 seconds.
COMMUNICATIONS
RP1 Meas Period
30.00 s
7. If the optional fibre optic connectors are fitted, the RP1 PhysicalLink cell is visible. This cell controls
the physical media used for the communication (Copper or Fibre optic).
COMMUNICATIONS
RP1 PhysicalLink
Copper
8. The next cell down (RP1 CS103Blcking) can be used for monitor or command blocking.
COMMUNICATIONS
RP1 CS103Blcking
Disabled
9. There are three settings associated with this cell; these are:
Setting: Description:
Disabled No blocking selected.
When the monitor blocking DDB Signal is active high, either by energising an opto input or control input,
Monitor Blocking reading of the status information and disturbance records is not permitted. When in this mode the device
returns a "Termination of general interrogation" message to the master station.
When the command blocking DDB signal is active high, either by energising an opto input or control input, all
Command Blocking remote commands will be ignored (i.e. CB Trip/Close, change setting group etc.). When in this mode the
device returns a "negative acknowledgement of command" message to the master station.
P94V-TM-EN-5 213
Chapter 11 - Communications P94V
The DNP 3.0 protocol is defined and administered by the DNP Users Group. For further information on
DNP 3.0 and the protocol specifications, please see the DNP website (www.dnp.org).
The IED address and baud rate can be selected using the front panel menu or by a suitable application such
as MiCOM Agile.
When using a serial interface, the data format is: 1 start bit, 8 data bits, 1 stop bit and optional configurable
parity bit.
214 P94V-TM-EN-5
P94V Chapter 11 - Communications
Control Input
(Latched)
Aliased Control
Input
(Latched)
Control Input
(Pulsed )
Aliased Control
Input
(Pulsed )
The pulse width is equal to the duration of one protection iteration
V01002
P94V-TM-EN-5 215
Chapter 11 - Communications P94V
Analogue values can be reported to the master station as primary, secondary or normalized values (which
takes into account the IED’s CT and VT ratios), and this is settable in the COMMUNICATIONS column in the
IED. Corresponding deadband settings can be displayed in terms of a primary, secondary or normalized
value. Deadband point values can be reported and written using Object 34 variations.
The deadband is the setting used to determine whether a change event should be generated for each point.
The change events can be read using Object 32 or Object 60. These events are generated for any point
which has a value changed by more than the deadband setting since the last time the data value was
reported.
Any analogue measurement that is unavailable when it is read is reported as offline. For example, the
frequency would be offline if the current and voltage frequency is outside the tracking range of the IED. All
Object 30 points are reported as secondary values in DNP 3.0 (with respect to CT and VT ratios).
DNP 3.0
Device Profile Document
Vendor Name: ALSTOM GRID
216 P94V-TM-EN-5
P94V Chapter 11 - Communications
DNP 3.0
Device Profile Document
Device Name: MiCOM P40Agile Protection Relays – compact and modular range
Models Covered: All models
Highest DNP Level Supported*: For Requests: Level 2
*This is the highest DNP level FULLY supported. Parts of level 3 are For Responses: Level 2
also supported
Device Function: Slave
Notable objects, functions, and/or qualifiers supported in addition to the highest DNP levels supported (the complete list is described in the DNP
3.0 Implementation Table):
For static (non-change event) object requests, request qualifier codes 00 and 01 (start-stop), 07 and 08 (limited quantity), and 17 and 28 (index)
are supported in addition to the request qualifier code 06 (no range (all points))
Static object requests sent with qualifiers 00, 01, 06, 07, or 08 will be responded with qualifiers 00 or 01
Static object requests sent with qualifiers 17 or 28 will be responded with qualifiers 17 or 28
For change-event object requests, qualifiers 17 or 28 are always responded
16-bit and 32-bit analogue change events with time may be requested
The read function code for Object 50 (time and date) variation 1 is supported
Analogue Input Deadbands, Object 34, variations 1 through 3, are supported
Floating Point Analogue Output Status and Output Block Objects 40 and 41 are supported
Sequential file transfer, Object 70, variations 2 through 7, are supported
Device Attribute Object 0 is supported
Maximum Data Link Frame Size (octets): Transmitted: 292
Received: 292
Maximum Application Fragment Size (octets) Transmitted: Configurable (100 to 2048). Default 2048
Received: 249
Maximum Data Link Retries: Fixed at 2
Maximum Application Layer Retries: None
Requires Data Link Layer Confirmation: Configurable to Never or Always
Requires Application Layer Confirmation: When reporting event data (Slave devices only)
When sending multi-fragment responses (Slave devices only)
Timeouts while waiting for:
Data Link Confirm: Configurable
Complete Application Fragment: None
Application Confirm: Configurable
Complete Application Response: None
Others:
Data Link Confirm Timeout: Configurable from 0 (Disabled) to 120s, default 10s.
Application Confirm Timeout: Configurable from 1 to 120s, default 2s.
Select/Operate Arm Timeout: Configurable from 1 to 10s, default 10s.
Need Time Interval (Set IIN1-4): Configurable from 1 to 30, default 10min.
Application File Timeout 60 s
Analog Change Event Scan Period: Fixed at 0.5s
Counter Change Event Scan Period Fixed at 0.5s
Frozen Counter Change Event Scan Period Fixed at 1s
Maximum Delay Measurement Error: 2.5 ms
Time Base Drift Over a 10-minute Interval: 7 ms
Sends/Executes Control Operations:
Write Binary Outputs: Never
P94V-TM-EN-5 217
Chapter 11 - Communications P94V
DNP 3.0
Device Profile Document
Select/Operate: Always
Direct Operate: Always
Direct Operate - No Ack: Always
Count > 1 Never
Pulse On Always
Pulse Off Sometimes
Latch On Always
Latch Off Always
Queue Never
Clear Queue Never
Note: Paired Control points will accept Pulse On/Trip and Pulse On/Close, but only single point will accept the Pulse Off control command.
Reports Binary Input Change Events when no specific variation Configurable to send one or the other
requested:
Reports time-tagged Binary Input Change Events when no specific Binary input change with time
variation requested:
Sends Unsolicited Responses: Never
Sends Static Data in Unsolicited Responses: Never
No other options are permitted
Default Counter Object/Variation: Configurable, Point-by-point list attached
Default object: 20
Default variation: 1
Counters Roll Over at: 32 bits
Sends multi-fragment responses: Yes
Sequential File Transfer Support:
Append File Mode No
Custom Status Code Strings No
Permissions Field Yes
File Events Assigned to Class No
File Events Send Immediately Yes
Multiple Blocks in a Fragment No
Max Number of Files Open 1
218 P94V-TM-EN-5
P94V Chapter 11 - Communications
Request Response
Object
(Library will parse) (Library will respond with)
Object Variation Function Codes (dec) Qualifier Codes Function Codes Qualifier Codes (hex)
Description (dec)
Number Number (hex)
1 2 Binary Input with Flag 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index - see note 2)
07, 08 (limited qty)
17, 28 (index)
2 0 Binary Input Change - Any 1 (read) 06 (no range, or all)
Variation 07, 08 (limited qty)
2 1 Binary Input Change without Time 1 (read) 06 (no range, or all) 129 response 17, 28 (index)
07, 08 (limited qty)
2 2 Binary Input Change with Time 1 (read) 06 (no range, or all) 129 response 17, 28 (index)
07, 08 (limited qty)
10 0 Binary Output Status - Any 1 (read) 00, 01 (start-stop)
Variation 06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
10 2 Binary Output Status 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
(default - see 06 (no range, or all) 17, 28 (index - see note 2)
note 1) 07, 08 (limited qty)
17, 28 (index)
12 1 Control Relay Output Block 3 (select) 17, 28 (index) 129 response echo of request
4 (operate)
5 (direct op)
6 (dir. op, noack)
20 0 Binary Counter - Any Variation 1 (read) 00, 01 (start-stop)
22 (assign class) 06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
7 (freeze) 00, 01 (start-stop)
8 (freeze noack) 06 (no range, or all)
9 (freeze clear) 07, 08 (limited qty)
10 (frz. cl. Noack)
20 1 32-Bit Binary Counter with Flag 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index - see note 2)
07, 08 (limited qty)
17, 27, 28 (index)
20 2 16-Bit Binary Counter with Flag 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index - see note 2)
07, 08 (limited qty)
17, 27, 28 (index)
20 5 32-Bit Binary Counter without Flag 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
(default - see 06 (no range, or all) 17, 28 (index - see note 2)
note 1) 07, 08 (limited qty)
17, 27, 28 (index)
20 6 16-Bit Binary Counter without Flag 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index - see note 2)
07, 08 (limited qty)
17, 27, 28 (index)
21 0 Frozen Counter - Any Variation 1 (read) 00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
21 1 32-Bit Frozen Counter with Flag 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index - see note 2)
07, 08 (limited qty)
17, 27, 28 (index)
21 2 16-Bit Frozen Counter with Flag 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index - see note 2)
07, 08 (limited qty)
17, 27, 28 (index)
21 5 32-Bit Frozen Counter with Time of 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
Freeze 06 (no range, or all) 17, 28 (index - see note 1)
07, 08 (limited qty)
17, 27, 28 (index)
21 6 16-Bit Frozen Counter with Time of 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
Freeze 06 (no range, or all) 17, 28 17, 28 (index - see note 1)
07, 08 (limited qty)
17, 27, 28 (index)
P94V-TM-EN-5 219
Chapter 11 - Communications P94V
Request Response
Object
(Library will parse) (Library will respond with)
Object Variation Function Codes (dec) Qualifier Codes Function Codes Qualifier Codes (hex)
Description (dec)
Number Number (hex)
21 9 32-Bit Frozen Counter without Flag 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
(default - see 06 (no range, or all) 17, 28 (index - see note 2)
note 1) 07, 08 (limited qty)
17, 27, 28 (index)
21 10 16-Bit Frozen Counter without Flag 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index - see note 2)
07, 08 (limited qty)
17, 27, 28 (index)
`22 0 Counter Change Event - Any 1 (read) 06 (no range, or all)
Variation 07, 08 (limited qty)
22 1 32-Bit Counter Change Event 1 (read) 06 (no range, or all) 129 response 17, 28 (index)
(default - see without Time 07, 08 (limited qty)
note 1)
22 2 16-Bit Counter Change Event 1 (read) 06 (no range, or all) 129 response 17, 28 (index)
without Time 07, 08 (limited qty)
22 5 32-Bit Counter Change Event with 1 (read) 06 (no range, or all) 129 response 17, 28 (index)
Time 07, 08 (limited qty)
22 6 16-Bit Counter Change Event with 1 (read) 06 (no range, or all) 129 response 17, 28 (index)
Time 07, 08 (limited qty)
23 0 Frozen Counter Event (Variation 0 1 (read) 06 (no range, or all)
is used to request default variation) 07, 08 (limited qty)
23 1 32-Bit Frozen Counter Event 1 (read) 06 (no range, or all) 129 response 17, 28 (index)
(default - see 07, 08 (limited qty)
note 1)
23 2 16-Bit Frozen Counter Event 1 (read) 06 (no range, or all) 129 response 17, 28 (index)
07, 08 (limited qty)
23 5 32-Bit Frozen Counter Event with 1 (read) 06 (no range, or all) 129 response 17, 28 (index)
Time 07, 08 (limited qty)
23 6 16-Bit Frozen Counter Event with 1 (read) 06 (no range, or all) 129 response 17, 28 (index)
Time 07, 08 (limited qty)
30 0 Analog Input - Any Variation 1 (read) 00, 01 (start-stop)
22 (assign class) 06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
30 1 32-Bit Analog Input 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index - see note 2)
07, 08 (limited qty)
17, 27, 28 (index)
30 2 16-Bit Analog Input 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index - see note 2)
07, 08 (limited qty)
17, 27, 28 (index)
30 3 32-Bit Analog Input without Flag 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
(default - see 06 (no range, or all) 17, 28 (index - see note 2)
note 1) 07, 08 (limited qty)
17, 27, 28 (index)
30 4 16-Bit Analog Input without Flag 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index - see note 2)
07, 08 (limited qty)
17, 27, 28 (index)
30 5 Short floating point 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index - see note 2)
07, 08 (limited qty)
17, 27, 28 (index)
32 0 Analog Change Event - Any 1 (read) 06 (no range, or all)
Variation 07, 08 (limited qty)
32 1 32-Bit Analog Change Event 1 (read) 06 (no range, or all) 129 response 17, 28 (index)
(default - see without Time 07, 08 (limited qty)
note 1)
32 2 16-Bit Analog Change Event 1 (read) 06 (no range, or all) 129 response 17, 28 (index)
without Time 07, 08 (limited qty)
32 3 32-Bit Analog Change Event with 1 (read) 06 (no range, or all) 129 response 17, 28 (index)
Time 07, 08 (limited qty)
32 4 16-Bit Analog Change Event with 1 (read) 06 (no range, or all) 129 response 17, 28 (index)
Time 07, 08 (limited qty)
220 P94V-TM-EN-5
P94V Chapter 11 - Communications
Request Response
Object
(Library will parse) (Library will respond with)
Object Variation Function Codes (dec) Qualifier Codes Function Codes Qualifier Codes (hex)
Description (dec)
Number Number (hex)
32 5 Short floating point Analog Change 1 (read) 06 (no range, or all) 129 response 17, 28 (index)
Event without Time 07, 08 (limited qty)
32 7 Short floating point Analog Change 1 (read) 06 (no range, or all) 129 response 17, 28 (index)
Event with Time 07, 08 (limited qty)
34 0 Analog Input Deadband (Variation 0 1 (read) 00, 01 (start-stop)
is used to request default variation) 06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
34 1 16 Bit Analog Input Deadband 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index - see note 2)
07, 08 (limited qty)
17, 27, 28 (index)
2 (write) 00, 01 (start-stop)
07, 08 (limited qty)
17, 27, 28 (index)
34 2 32 Bit Analog Input Deadband 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
(default - see 06 (no range, or all) 17, 28 (index - see note 2)
note 1) 07, 08 (limited qty)
17, 27, 28 (index)
2 (write) 00, 01 (start-stop)
07, 08 (limited qty)
17, 27, 28 (index)
34 3 Short Floating Point Analog Input 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
Deadband 06 (no range, or all) 17, 28 (index - see note 2)
07, 08 (limited qty)
17, 27, 28 (index)
2 (write) 00, 01 (start-stop)
07, 08 (limited qty)
17, 27, 28 (index)
40 0 Analog Output Status (Variation 0 is 1 (read) 00, 01 (start-stop)
used to request default variation) 06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
40 1 32-Bit Analog Output Status 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
(default - see 06 (no range, or all) 17, 28 (index - see note 2)
note 1) 07, 08 (limited qty)
17, 27, 28 (index)
40 2 16-Bit Analog Output Status 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index - see note 2)
07, 08 (limited qty)
17, 27, 28 (index)
40 3 Short Floating Point Analog Output 1 (read) 00, 01 (start-stop) 129 response 00, 01 (start-stop)
Status 06 (no range, or all) 17, 28 (index - see note 2)
07, 08 (limited qty)
17, 27, 28 (index)
41 1 32-Bit Analog Output Block 3 (select) 17, 28 (index) 129 response echo of request
4 (operate) 27 (index)
5 (direct op)
6 (dir. op, noack)
41 2 16-Bit Analog Output Block 3 (select) 17, 28 (index) 129 response echo of request
4 (operate) 27 (index)
5 (direct op)
6 (dir. op, noack)
41 3 Short Floating Point Analog Output 3 (select) 17, 27, 28 (index) 129 response echo of request
Block 4 (operate)
5 (direct op)
6 (dir. op, noack)
1 1 (read) 07 (limited qty = 1) 129 response 07 (limited qty = 1)
50 (default - see Time and Date
note 1)
2 (write) 07 (limited qty = 1)
60 0 Not defined
60 1 Class 0 Data 1 (read) 06 (no range, or all)
60 2 Class 1 Data 1 (read) 06 (no range, or all)
07, 08 (limited qty)
22 (assign class) 06 (no range, or all)
P94V-TM-EN-5 221
Chapter 11 - Communications P94V
Request Response
Object
(Library will parse) (Library will respond with)
Object Variation Function Codes (dec) Qualifier Codes Function Codes Qualifier Codes (hex)
Description (dec)
Number Number (hex)
60 3 Class 2 Data 1 (read) 06 (no range, or all)
07, 08 (limited qty)
22 (assign class) 06 (no range, or all)
60 4 Class 3 Data 1 (read) 06 (no range, or all)
07, 08 (limited qty)
22 (assign class) 06 (no range, or all)
70 0 File Event - Any Variation 1 (read) 06 (no range, or all)
07, 08 (limited qty)
22 (assign class) 06 (no range, or all)
70 2 File Authentication 29 (authenticate) 5b (free-format) 129 response 5B (free-format)
70 3 File Command 25 (open) 5b (free-format)
27 (delete)
70 4 File Command Status 26 (close) 5b (free-format) 129 response 5B (free-format)
30 (abort)
70 5 File Transfer 1 (read) 5b (free-format) 129 response 5B (free-format)
70 6 File Transfer Status 129 response 5B (free-format)
70 7 File Descriptor 28 (get file info) 5b (free-format) 129 response 5B (free-format)
Note:
A Default variation refers to the variation responded to when variation 0 is requested and/or in class 0, 1, 2, or 3
scans.
Note:
For static (non-change-event) objects, qualifiers 17 or 28 are only responded to when a request is sent with qualifiers
17 or 28, respectively. Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded to
with qualifiers 00 or 01. For change-event objects, qualifiers 17 or 28 are always responded to.
222 P94V-TM-EN-5
P94V Chapter 11 - Communications
P94V-TM-EN-5 223
Chapter 11 - Communications P94V
Note:
Code numbers 10 through to 126 are reserved for future use.
COMMUNICATIONS
RP1 Protocol
DNP3.0
4. Move down to the next cell (RP1 Address). This cell controls the DNP3.0 address of the IED. Up to 32
IEDs can be connected to one spur, therefore it is necessary for each IED to have a unique address
so that messages from the master control station are accepted by only one IED. DNP3.0 uses a
decimal number between 1 and 65519 for the Relay Address. It is important that no two IEDs have the
same address.
224 P94V-TM-EN-5
P94V Chapter 11 - Communications
COMMUNICATIONS
RP1 Address
1
5. Move down to the next cell (RP1 Baud Rate). This cell controls the baud rate to be used. Six baud
rates are supported by the IED 1200 bps, 2400 bps, 4800 bps, 9600 bps, 19200 bps and 38400 bps.
Make sure that the baud rate selected on the IED is the same as that set on the master station.
COMMUNICATIONS
RP1 Baud rate
9600 bits/s
6. Move down to the next cell (RP1 Parity). This cell controls the parity format used in the data frames.
The parity can be set to be one of None, Odd or Even. Make sure that the parity format selected on
the IED is the same as that set on the master station.
COMMUNICATIONS
RP1 Parity
None
7. If the optional fibre optic connectors are fitted, the RP1 PhysicalLink cell is visible. This cell controls
the physical media used for the communication (Copper or Fibre optic).
COMMUNICATIONS
RP1 PhysicalLink
Copper
8. Move down to the next cell (RP1 Time Sync). This cell affects the time synchronisation request from
the master by the IED. It can be set to enabled or disabled. If enabled it allows the DNP3.0
master to synchronise the time on the IED.
COMMUNICATIONS
RP1 Time Sync
Enabled
P94V-TM-EN-5 225
Chapter 11 - Communications P94V
mode of operation where the outstation spontaneously transmits a response without having received a
specific request for data. This mode is useful when the system has many outstations and the master requires
notification as soon as possible after a change occurs. Rather than waiting for a master station polling cycle,
the outstation transmits the change immediately. It is thus event driven rather than poll driven.
This feature requires a new group of settings, which are found under the DNP SETTINGS column (Courier
cell range 1B). These can be found in the settings tables available as an interactive PDF at the back of the
manual.
5.4 MODBUS
This section describes how the MODBUS standard is applied to the Px40 platform. It is not a description of
the standard itself. The level at which this section is written assumes that the reader is already familiar with
the MODBUS standard.
The MODBUS protocol is a master/slave protocol, defined and administered by the MODBUS Organization
For further information on MODBUS and the protocol specifications, please seethe Modbus web site
(www.modbus.org).
The MODBUS interface uses ‘RTU’ mode communication rather than ‘ASCII’ mode as this provides more
efficient use of the communication bandwidth. This mode of communication is defined by the MODBUS
standard.
The IED address and baud rate can be selected using the front panel menu or by a suitable application such
as MiCOM Agile.
When using a serial interface, the data format is: 1 start bit, 8 data bits, 1 parity bit with 1 stop bit, or 2 stop
bits (a total of 11 bits per character).
226 P94V-TM-EN-5
P94V Chapter 11 - Communications
Note:
The "extended memory file" (6xxxx) is not supported.
Note:
MODBUS convention is to document register addresses as ordinal values whereas the actual protocol addresses are
literal values. The MiCOM relays begin their register addresses at zero. Therefore, the first register in a memory page
is register address zero. The second register is register address 1 and so on.
Note:
The page number notation is not part of the address.
P94V-TM-EN-5 227
Chapter 11 - Communications P94V
register is set then the device has non-extracted events available. To select the next event for sequential
extraction, the master station writes a value of 1 to the record selection register 40400 (G18 data type). The
event data together with any fault/maintenance data can be read from the registers specified below. Once
the data has been read, the event record can be marked as having been read by writing a value of '2' to
register 40400.
For each of the above registers a value of 0 represents the most recent stored record. The following
registers can be read to indicate the numbers of the various types of record stored.
● 30100: Number of stored records
● 30101: Number of stored fault records
● 30102: Number of stored maintenance records
Each fault or maintenance record logged causes an event record to be created. If this event record is
selected, the additional registers allowing the fault or maintenance record details will also become populated.
If a fault record or maintenance record is directly selected using the manual mechanism then the data can be
read from the register ranges specified above. The event record data in registers 30103 to 30111 will not be
available.
228 P94V-TM-EN-5
P94V Chapter 11 - Communications
It is possible using register 40401(G6 data type) to independently clear the stored relay event/fault and
maintenance records. This register also provides an option to reset the device indications, which has the
same effect on the relay as pressing the clear key within the alarm viewer using the HMI panel menu.
MODBUS registers
MODBUS Register Name Description
Provides the status of the relay as bit flags:
b0: Out of service
b1: Minor self test failure
b2: Event
b3: Time synchronization
3x00001 Status register b4: Disturbance
b5: Fault
b6: Trip
b7: Alarm
b8 to b15: Unused
A ‘1’ on b4 indicates the presence of a disturbance
Indicates the total number of disturbance records currently stored in the
3x00800 No of stored disturbances
relay, both extracted and non-extracted.
Indicates the unique identifier value for the oldest disturbance record stored
Unique identifier of the oldest in the relay. This is an integer value used in conjunction with the ‘Number of
3x00801
disturbance record stored disturbances’ value to calculate a value for manually selecting
records.
This register is used to manually select disturbance records. The values
written to this cell are an offset of the unique identifier value for the oldest
Manual disturbance record
4x00250 record. The offset value, which ranges from 0 to the Number of stored
selection register
disturbances - 1, is added to the identifier of the oldest record to generate
the identifier of the required record.
This register is used during the extraction process and has a number of
commands. These are:
b0: Select next event
Record selection command b1: Accept event
4x00400
register b2: Select next disturbance record
b3: Accept disturbance record
b4: Select next page of disturbance data
b5: Select data file
3x00930 - 3x00933 Record time stamp These registers return the timestamp of the disturbance record.
This register informs the master station of the number of registers in the
3x00802 No of registers in data page
data page that are populated.
These 127 registers are used to transfer data from the relay to the master
3x00803 - 3x00929 Data page registers
station. They are 16-bit unsigned integers.
P94V-TM-EN-5 229
Chapter 11 - Communications P94V
Note:
Register addresses are provided in reference code + address format. E.g. 4x00001 is reference code 4x, address 1
(which is specified as function code 03, address 0x0000 in the MODBUS specification).
The disturbance record status register will report one of the following values:
230 P94V-TM-EN-5
P94V Chapter 11 - Communications
Start
Get number of
disturbances from
register 3x00800
End
V01003
Method 1
Method 1 is simpler and is better at extracting single disturbance records (when the disturbance recorder is
polled regularly).
P94V-TM-EN-5 231
Chapter 11 - Communications P94V
Start
Is disturbance bit No
(bit 4) set?
Yes
Error
Method 2
Method 2 is more complex to implement but is more efficient at extracting large quantities of disturbance
records. This may be useful when the disturbance recorder is polled only occasionally and therefore may
have many stored records.
232 P94V-TM-EN-5
P94V Chapter 11 - Communications
Start
FirstTime = True
FirstTime = True
Is disturbance bit
(bit 4) set? No
Yes
No
FirstTime = False
P94V-TM-EN-5 233
Chapter 11 - Communications P94V
Start
(Record selected)
To parent
procedure
Read DR status value Busy
from register 3x00934
Check DR status
for error
conditions or Error
Busy status
Page ready
Read number of
registers in data page
from address 3x00802
V01006
234 P94V-TM-EN-5
P94V Chapter 11 - Communications
Start
(Configuration
complete)
To parent
procedure
Read DR status value Busy
from register 3x00934
Check DR status
for error
conditions or Error
Busy status
Page ready
Read number of
registers in data page
from address 3x00802
Record complete (mark Store data to binary file Send ‘Get next page of
record as extracted; in the order the data data’ to register
automatic extraction only) were received 4x00400
V01007
P94V-TM-EN-5 235
Chapter 11 - Communications P94V
In addition to the basic editing of the protection setting groups, the following functions are provided:
● Default values can be restored to a setting group or to all of the relay settings by writing to register
4x0402.
● It is possible to copy the contents of one setting group to another by writing the source group to
register 40406 and the target group to 4x0407.
236 P94V-TM-EN-5
P94V Chapter 11 - Communications
The setting changes performed by either of the two operations defined above are made to the scratchpad
area. These changes must be confirmed by writing to register 4x0405.
The active protection setting groups can be selected by writing to register 40404. An illegal data response
will be returned if an attempt is made to set the active group to one that has been disabled.
Key to table:
● m = milliseconds: 0 to 59,999
● I = minutes: 0 to 59
● H = hours: 0 to 23
● W = day of the week: 1 to 7 starting from Monday
● D = day of the month: 1 to 31
● M = month of the year: 1 to 12 starting from January
● Y = year of the century: 0 to 99
● R = reserved: 0
● SU = summertime: 0 = GMT, 1 = summertime
● IV = invalid: 0 = invalid value, 1 = valid value
Since the range of the data type is only 100 years, the century must be deduced. The century is calculated
as the one that will produce the nearest time value to the current date. For example: 30-12-99 is 30-12-1999
when received in 1999 & 2000, but is 30-12-2099 when received in 2050. This technique allows 2 digit years
to be accurately converted to 4 digits in a ±50 year window around the current date.
The invalid bit has two applications:
● It can indicate that the date-time information is considered inaccurate, but is the best information
available.
● It can indicate that the date-time information is not available.
P94V-TM-EN-5 237
Chapter 11 - Communications P94V
The summertime bit is used to indicate that summertime (day light saving) is being used and, more
importantly, to resolve the alias and time discontinuity which occurs when summertime starts and ends. This
is important for the correct time correlation of time stamped records.
The day of the week field is optional and if not calculated will be set to zero.
The concept of time zone is not catered for by this data type and hence by the relay. It is up to the end user
to determine the time zone. Normal practice is to use UTC (universal co-ordinated time).
Note:
The G29 values must be read in whole multiples of three registers. It is not possible to read the G28 and G27 parts
with separate read commands.
238 P94V-TM-EN-5
P94V Chapter 11 - Communications
The Three-phase Active Power displayed on the measurement panel on the front display of the IED would
be 21.94 MW
The registers related to the Three-phase Active Power are: 3x00327, 3x00328, 3x00329
Register Address Data read from these registers Format of the data
3x00327 116 G28
3x00328 2 G27
3x00329 57928 G27
The Equivalent G27 value = [216 * Value in the address 3x00328 + Value in the address 3x00329] = 216*2
+ 57928 = 189000
The Equivalent value of power G29 = G28 * Equivalent G27 =116 * 189000 =21.92 MW
Note:
The above calculated value (21.92 MW) is same as the power value measured on the front panel display.
COMMUNICATIONS
RP1 Protocol
Modbus
4. Move down to the next cell (RP1 Address). This cell controls the Modbus address of the IED. Up to
32 IEDs can be connected to one spur, therefore it is necessary for each IED to have a unique
address so that messages from the master control station are accepted by only one IED. Modbus
uses a decimal number between 1 and 247 for the Relay Address. It is important that no two IEDs
have the same address.
P94V-TM-EN-5 239
Chapter 11 - Communications P94V
COMMUNICATIONS
RP1 Address
1
5. Move down to the next cell (RP1 InactivTimer). This cell controls the inactivity timer. The inactivity
timer controls how long the IED waits without receiving any messages on the rear port before it reverts
to its default state, including revoking any password access that was enabled. For the rear port this
can be set between 1 and 30 minutes.
COMMUNICATIONS
RP1 Inactivtimer
10.00 mins
6. Move down to the next cell (RP1 Baud Rate). This cell controls the baud rate to be used. Six baud
rates are supported by the IED 1200 bits/s, 2400 bits/s, 4800 bits/s, 9600 bits/s, 19200 bits/s and
38400 bits/s. Make sure that the baud rate selected on the IED is the same as that set on the master
station.
COMMUNICATIONS
RP1 Baud rate
9600 bits/s
7. Move down to the next cell (RP1 Parity). This cell controls the parity format used in the data frames.
The parity can be set to be one of None, Odd or Even. Make sure that the parity format selected on
the IED is the same as that set on the master station.
COMMUNICATIONS
RP1 Parity
None
8. Move down to the next cell (Modbus IEC Time). This cell controls the order in which the bytes of
information are transmitted. There is a choice of Standard or Reverse. When Standard is selected
the time format complies with IEC 60870-5-4 requirements such that byte 1 of the information is
transmitted first, followed by bytes 2 through to 7. If Reverse is selected the transmission of
information is reversed.
COMMUNICATIONS
Modbus IEC Time
Standard
240 P94V-TM-EN-5
P94V Chapter 11 - Communications
There are two editions of IEC 61850; IEC 61850 edition 1 and IEC 61850 edition 2. The edition which this
product supports depends on your exact model. An additional section for edition 2 models is documented
later in this chapter if applicable.
The standard adheres to the requirements laid out by the ISO OSI model and therefore provides complete
vendor interoperability and flexibility on the transmission types and protocols used. This includes mapping of
data onto Ethernet, which is becoming more and more widely used in substations, in favour of RS485. Using
Ethernet in the substation offers many advantages, most significantly including:
● Ethernet allows high-speed data rates (currently 100 Mbps, rather than tens of kbps or less used by
most serial protocols)
● Ethernet provides the possibility to have multiple clients
● Ethernet is an open standard in every-day use
● There is a wide range of Ethernet-compatible products that may be used to supplement the LAN
installation (hubs, bridges, switches)
P94V-TM-EN-5 241
Chapter 11 - Communications P94V
Data Attributes
stVal q t PhA PhB PhC
Data Objects
Pos A
Logical Nodes : 1 to n
LN1: XCBR LN2: MMXU
V01008
242 P94V-TM-EN-5
P94V Chapter 11 - Communications
The IEC 61850 compatible interface standard provides capability for the following:
● Read access to measurements
● Refresh of all measurements at the rate of once per second.
● Generation of non-buffered reports on change of status or measurement
● SNTP time synchronization over an Ethernet link. (This is used to synchronize the IED's internal real
time clock.
● GOOSE peer-to-peer communication
● Disturbance record extraction by file transfer. The record is extracted as an ASCII format COMTRADE
file
Note:
Setting changes are not supported in the current IEC 61850 implementation. Currently these setting changes are
carried out using the settings application software.
P94V-TM-EN-5 243
Chapter 11 - Communications P94V
● UINT16
● UINT32
● UINT8
244 P94V-TM-EN-5
P94V Chapter 11 - Communications
Note:
Some configuration data is available in the IEC61850 CONFIG. column, allowing read-only access to basic
configuration data.
Any new configuration sent to the IED is automatically stored in the inactive configuration bank, therefore not
immediately affecting the current configuration.
Following an upgrade, the IEC 61850 Configurator tool can be used to transmit a command, which
authorises activation of the new configuration contained in the inactive configuration bank. This is done by
switching the active and inactive configuration banks. The capability of switching the configuration banks is
also available using the IEC61850 CONFIG. column of the HMI.
The SCL Name and Revision attributes of both configuration banks are available in the IEC61850 CONFIG.
column of the HMI.
P94V-TM-EN-5 245
Chapter 11 - Communications P94V
Note:
For IEC 60870-5-103, Read Only Mode function is different from the existing Command block feature.
246 P94V-TM-EN-5
P94V Chapter 11 - Communications
Using the PSL, these signals can be activated by opto-inputs, Control Inputs and function keys if required.
P94V-TM-EN-5 247
Chapter 11 - Communications P94V
7 TIME SYNCHRONISATION
In modern protection schemes it is necessary to synchronise the IED's real time clock so that events from
different devices can be time stamped and placed in chronological order. This is achieved in various ways
depending on the chosen options and communication protocols.
● Using the IRIG-B input (if fitted)
● Using the SNTP time protocol (for Ethernet IEC 61850 versions + DNP3 OE)
● By using the time synchronisation functionality inherent in the data protocols
IRIG-B
V01040
The first four time-slots define the time in BCD (Binary Coded Decimal). Time-slots 5 and 6 are used for
control functions, which control deletion commands and allow different data groupings within the
synchronisation strings. Time-slots 7-10 define the time in SBS (Straight Binary Second of day).
248 P94V-TM-EN-5
P94V Chapter 11 - Communications
7.2 SNTP
SNTP is used to synchronise the clocks of computer systems over packet-switched, variable-latency data
networks, such as IP. SNTP can be used as the time synchronisation method for models using IEC 61850
over Ethernet.
The device is synchronised by the main SNTP server. This is achieved by entering the IP address of the
SNTP server into the IED using the IEC 61850 Configurator software described in the settings application
software manual. A second server is also configured with a different IP address for backup purposes.
This function issues an alarm when there is a loss of time synchronisation on the SNTP server. This could be
because there is no response or no valid clock signal.
The HMI menu does not contain any configurable settings relating to SNTP, as the only way to configure it is
using the IEC 61850 Configurator. However it is possible to view some parameters in the
COMMUNICATIONS column under the sub-heading SNTP parameters. Here you can view the SNTP server
addresses and the SNTP poll rate in the cells SNTP Server 1, SNTP Server 2 and SNTP Poll rate
respectively.
The SNTP time synchronisation status is displayed in the SNTP Status cell in the DATE AND TIME column.
P94V-TM-EN-5 249
Chapter 11 - Communications P94V
250 P94V-TM-EN-5
CYBER-SECURITY
CHAPTER 12
Chapter 12 - Cyber-Security P94V
252 P94V-TM-EN-5
P94V Chapter 12 - Cyber-Security
1 OVERVIEW
In the past, substation networks were traditionally isolated and the protocols and data formats used to
transfer information between devices were often proprietary.
For these reasons, the substation environment was very secure against cyber-attacks. The terms used for
this inherent type of security are:
● Security by isolation (if the substation network is not connected to the outside world, it cannot be
accessed from the outside world).
● Security by obscurity (if the formats and protocols are proprietary, it is very difficult to interpret them).
The increasing sophistication of protection schemes, coupled with the advancement of technology and the
desire for vendor interoperability, has resulted in standardisation of networks and data interchange within
substations. Today, devices within substations use standardised protocols for communication. Furthermore,
substations can be interconnected with open networks, such as the internet or corporate-wide networks,
which use standardised protocols for communication. This introduces a major security risk making the grid
vulnerable to cyber-attacks, which could in turn lead to major electrical outages.
Clearly, there is now a need to secure communication and equipment within substation environments. This
chapter describes the security measures that have been put in place for our range of Intelligent Electronic
Devices (IEDs).
Note:
Cyber-security compatible devices do not enforce NERC compliance, they merely facilitate it. It is the responsibility of
the user to ensure that compliance is adhered to as and when necessary.
P94V-TM-EN-5 253
Chapter 12 - Cyber-Security P94V
The threats to cyber-security may be unintentional (e.g. natural disasters, human error), or intentional (e.g.
cyber-attacks by hackers).
Good cyber-security can be achieved with a range of measures, such as closing down vulnerability
loopholes, implementing adequate security processes and procedures and providing technology to help
achieve this.
Examples of vulnerabilities are:
● Indiscretions by personnel (users keep passwords on their computer)
● Bad practice (users do not change default passwords, or everyone uses the same password to access
all substation equipment)
● Bypassing of controls (users turn off security measures)
● Inadequate technology (substation is not firewalled)
To help tackle these issues, standards organisations have produced various standards. Compliance with
these standards significantly reduces the threats associated with lack of cyber-security.
254 P94V-TM-EN-5
P94V Chapter 12 - Cyber-Security
3 STANDARDS
There are several standards, which apply to substation cyber-security. The standards currently applicable to
Alstom Grid IEDs are NERC and IEEE1686.
Standard Country Description
NERC CIP (North American Electric Reliability
USA Framework for the protection of the grid critical Cyber Assets
Corporation)
BDEW (German Association of Energy and Water
Germany Requirements for Secure Control and Telecommunication Systems
Industries)
ICS oriented then Relevant for EPU completing existing standard
ANSI ISA 99 USA
and identifying new topics such as patch management
IEEE 1686 International International Standard for substation IED cyber-security capabilities
IEC 62351 International Power system data and Comm. protocol
ISO/IEC 27002 International Framework for the protection of the grid critical Cyber Assets
NIST SP800-53 (National Institute of Standards and
USA Complete framework for SCADA SP800-82and ICS cyber-security
Technology)
CPNI Guidelines (Centre for the Protection of National Clear and valuable good practices for Process Control and SCADA
UK
Infrastructure) security
P94V-TM-EN-5 255
Chapter 12 - Cyber-Security P94V
256 P94V-TM-EN-5
P94V Chapter 12 - Cyber-Security
P94V-TM-EN-5 257
Chapter 12 - Cyber-Security P94V
● IED functions and features are assigned to different password levels. The assignment is fixed.
● The audit trail is recorded, listing events in the order in which they occur, held in a circular buffer.
● Records contain all defined fields from the standard and record all defined function event types where
the function is supported.
● No password defeat mechanism exists. Instead a secure recovery password scheme is implemented.
● Unused ports (physical and logical) may be disabled.
258 P94V-TM-EN-5
P94V Chapter 12 - Cyber-Security
4 CYBER-SECURITY IMPLEMENTATION
The Alstom Grid IEDs have always been and will continue to be equipped with state-of-the-art security
measures. Due to the ever-evolving communication technology and new threats to security, this requirement
is not static. Hardware and software security measures are continuously being developed and implemented
to mitigate the associated threats and risks.
This section describes the current implementation of cyber-security. This is valid for the release of platform
software to which this manual pertains. This current cyber-security implementation is known as Cyber-
security Phase 1.
At the IED level, these cyber-security measures have been implemented:
● NERC-compliant default display
● Four-level access
● Enhanced password security
● Password recovery procedure
● Disabling of unused physical and logical ports
● Inactivity timer
● Security events management
External to the IEDs, the following cyber-security measures have been implemented:
● Antivirus
● Security patch management
If you try to change the default display from the NERC-compliant one, a further warning is displayed:
The default display navigation map shows how NERC-compliance is achieved with the product's default
display concept.
P94V-TM-EN-5 259
Chapter 12 - Cyber-Security P94V
NERC compliant
banner
System Current
Access Level
Measurements
System Voltage
System Frequency
Measurements
System Power
Plant Reference
Measurements
V00403
Password levels
Level Meaning Read Operation Write Operation
SYSTEM DATA column:
Description
Plant Reference
Model Number
Serial Number
S/W Ref.
Access Level Password Entry
Read Some
0 Security Feature LCD Contrast (UI only)
Write Minimal
SECURITY CONFIG column:
User Banner
Attempts Remain
Blk Time Remain
Fallback PW level
Security Code (UI only)
260 P94V-TM-EN-5
P94V Chapter 12 - Cyber-Security
BLANK PASSWORD
ENTERED CONFIRM
Blank passwords cannot be configured if the lower level password is not blank.
Blank passwords affect the fall back level after inactivity timeout or logout.
The ‘fallback level’ is the password level adopted by the IED after an inactivity timeout, or after the user logs
out. This will be either the level of the highest-level password that is blank, or level 0 if no passwords are
blank.
P94V-TM-EN-5 261
Chapter 12 - Cyber-Security P94V
Key:
HMI = Human Machine Interface
FPort = Front Port
RPrt = Rear Port
Lvl = Level
262 P94V-TM-EN-5
P94V Chapter 12 - Cyber-Security
NERC COMPLIANT
P/WORD WAS SAVED
If the password entered is not NERC-compliant, the user is required to actively confirm this, in which case
the non-compliance is logged.
If the entered password is not NERC compliant, the following text is displayed:
NERC COMPLIANCE
NOT MET CONFIRM?
On confirmation, the non-compliant password is stored and the following acknowledgement message is
displayed for 2 seconds.
NON-NERC P/WORD
SAVED OK
If the action is cancelled, the password is rejected and the following message is displayed for 2 seconds.
NON-NERC P/WORD
NOT SAVE
If the password is entered through a communications port using Courier or Modbus protocols, the device will
store the password, irrespective of whether it is NERC-compliant or not. It then uses appropriate response
codes to inform the client of the NERC-compliancy status. You can then choose to enter a new NERC-
compliant password or accept the non-NERC compliant password just entered.
P94V-TM-EN-5 263
Chapter 12 - Cyber-Security P94V
If you try to enter the password while the interface is blocked, the following message is displayed for 2
seconds.
NOT ACCEPTED
ENTRY IS BLOCKED
A similar response occurs if you try to enter the password through a communications port.
The parameters can then be configured using the Attempts Count, Attempts Timer and Blocking Timer
settings in the SYSTEM CONFIG column.
As soon as the security code is displayed on the LCD, a validity timer is started. This validity timer is set to
72 hours and is not configurable. This provides enough time for the contact centre to manually generate and
send a recovery password. The Service Level Agreement (SLA) for recovery password generation is one
working day, so 72 hours is sufficient time, even allowing for closure of the contact centre over weekends
and bank holidays.
To prevent accidental reading of the IED security code, the cell will initially display a warning message:
PRESS ENTER TO
READ SEC. CODE
The security code is displayed on confirmation. The validity timer is then started. The security code can only
be read from the front panel.
264 P94V-TM-EN-5
P94V Chapter 12 - Cyber-Security
passwords. Each password should be appropriate for its intended function, ensuring NERC compliance, if
required.
On this action, the following message is displayed:
PASSWORDS HAVE
BEEN SET TO
DEFAULT
The recovery password can be applied through any interface, local or remote. It will achieve the same result
irrespective of which interface it is applied through.
REAR PORT 1 TO BE
DISABLED.CONFIRM
Note:
It is not possible to disable a port from which the disabling port command originates.
Note:
We do not generally advise disabling the physical Ethernet port.
Note:
The port disabling setting cells are not provided in the settings file. It is only possible to do this using the HMI front
panel.
P94V-TM-EN-5 265
Chapter 12 - Cyber-Security P94V
Note:
If any of these protocols are enabled or disabled, the Ethernet card will reboot.
266 P94V-TM-EN-5
P94V Chapter 12 - Cyber-Security
where:
● int is the interface definition (UI, FP, RP1, RP2, TNL, TCP)
● prt is the port ID (FP, RP1, RP2, TNL, DNP3, IEC, ETHR)
● grp is the group number (1, 2, 3, 4)
● crv is the Curve group number (1, 2, 3, 4)
P94V-TM-EN-5 267
Chapter 12 - Cyber-Security P94V
Each new event has an incremented unique number, therefore missing events appear as ‘gap’ in the
sequence. The unique identifier forms part of the event record that is read or uploaded from the IED.
Note:
It is no longer possible to clear Event, Fault, Maintenance, and Disturbance Records.
DO YOU WANT TO
LOG OUT?
You will only be asked this question if your password level is higher than the fallback level.
If you confirm, the following message is displayed for 2 seconds:
LOGGED OUT
Access Level #
LOGOUT CANCELLED
Access Level #
268 P94V-TM-EN-5
INSTALLATION
CHAPTER 13
Chapter 13 - Installation P94V
270 P94V-TM-EN-5
P94V Chapter 13 - Installation
1 CHAPTER OVERVIEW
This chapter provides information about installing the product.
This chapter contains the following sections:
Chapter Overview 271
Handling the Goods 272
Mounting the Device 273
Cables and Connectors 280
Case Dimensions 285
P94V-TM-EN-5 271
Chapter 13 - Installation P94V
Caution:
Before lifting or moving the equipment you should be familiar with the Safety
Information chapter of this manual.
272 P94V-TM-EN-5
P94V Chapter 13 - Installation
Caution:
Do not use conventional self-tapping screws, because they have larger heads
and could damage the faceplate.
Alternatively, you can use tapped holes if the panel has a minimum thickness of 2.5 mm.
For applications where the product needs to be semi-projection or projection mounted, a range of collars are
available.
If several products are mounted in a single cut-out in the panel, mechanically group them horizontally or
vertically into rigid assemblies before mounting in the panel.
Caution:
Do not fasten products with pop rivets because this makes them difficult to
remove if repair becomes necessary.
If the product is mounted on a BS EN60529 IP52 compliant panel, fit a metallic sealing strip between
adjoining products (part no GN2044 001) and fit a sealing ring around the complete assembly, according to
the following table.
Width Sealing ring for single tier Sealing ring for double tier
P94V-TM-EN-5 273
Chapter 13 - Installation P94V
Width Sealing ring for single tier Sealing ring for double tier
274 P94V-TM-EN-5
P94V Chapter 13 - Installation
Caution:
Risk of damage to the front cover molding. Do not use conventional self-tapping
screws, including those supplied for mounting MiDOS products because they
have slightly larger heads.
Once the tier is complete, the frames are fastened into the racks using mounting angles at each end of the
tier.
P94V-TM-EN-5 275
Chapter 13 - Installation P94V
The old K-series products can be removed by sliding the cradle out of the case. The new P40 Agile cradle
can then be inserted into the old case as shown below:
276 P94V-TM-EN-5
P94V Chapter 13 - Installation
P94V-TM-EN-5 277
Chapter 13 - Installation P94V
E01407
If there is any doubt as to the integrity of any of these aspects, contact your local representative.
Caution:
After removing the K-series product from its case, refit it into the case that came
with your device, for storage or reuse in another location.
The difference between a standard device and a K-series retrofit device is that the retrofit device has internal
links between terminals 7 and 13, and terminals 8 and 14 respectively. This is so that equipment driven by
the K-series field voltage conected to terminals 7 and 8, will continue to be driven indirectly via terminals 13
and 14 when replaced by P40 Agile products.
A K-series device provides a 48 V DC field voltage between terminals 7 and 8. This field voltage is intended
for driving auxiliary equipment such as opto-inputs. P40 Agile devices DO NOT provide this field voltage. For
this reason, P40 Agile retrofit devices have internal shorting links between terminals 7 and 13, and terminals
8 and 14 respectively. The intention of this is to provide the auxiliary supply voltage to terminals 7 and 8 in
lieue of the field voltage.
Caution:
The voltage on terminals 7 and 8 mirrors that of the auxiliary supply voltage. If
the auxiliary supply voltage on terminals 13 and 14 is not 48 V DC, then the
voltage on terminals 7 and 8 is also not 48 V DC.
278 P94V-TM-EN-5
P94V Chapter 13 - Installation
Caution:
When retrofitting a K-series device, ensure the load on terminals 7 and 8 is
limited to a maximum of 5A. A jumplead with a 5A ceramic timelag fuse is fitted
internally.
3.2.1 CONVENTIONS
The P40 Agile products have different conventions from the K-series products when it comes to numbering
some hardware components. It is very important that you are aware of this. This is just a matter of
convention and does not affect the terminal compatibility.
The equivalencies are as follows:
Component P40 Agile products K-series products
Output relay RL1 RL0
Output relay RL2 RL1
Output relay RL3 RL2
Output relay RL4 RL3
Output relay RL5 RL4
Output relay RL6 RL5
Output relay RL7 RL6
Output relay RL8 RL7
Opto-input L1 L0
Opto-input L2 L1
Opto-input L3 L2
Opto-input L4 L3
Opto-input L5 L4
Opto-input L6 L5
Opto-input L7 L6
Opto-input L8 L7
Note:
Software-only products are licensed for use with devices with specific serial numbers.
Caution:
Do not attempt to upgrade an existing device if the software has not been
licensed for that speciific device.
P94V-TM-EN-5 279
Chapter 13 - Installation P94V
Caution:
Before carrying out any work on the equipment you should be familiar with the
Safety Section and the ratings on the equipment’s rating label.
280 P94V-TM-EN-5
P94V Chapter 13 - Installation
Caution:
Protect the auxiliary power supply wiring with a maximum 16 A high rupture
capacity (HRC) type NIT or TIA fuse.
Use a wire size of at least 2.5 mm2 terminated with a ring terminal.
Due to the physical limitations of the ring terminal, the maximum wire size you can use is 6.0 mm2 using ring
terminals that are not pre-insulated. If using pre insulated ring terminals, the maximum wire size is reduced
to 2.63 mm2 per ring terminal. If you need a greater cross-sectional area, use two wires in parallel, each
terminated in a separate ring terminal.
The wire should have a minimum voltage rating of 300 V RMS.
Note:
To prevent any possibility of electrolytic action between brass or copper ground conductors and the rear panel of the
product, precautions should be taken to isolate them from one another. This could be achieved in several ways,
including placing a nickel-plated or insulating washer between the conductor and the product case, or using tinned
ring terminals.
Due to the physical limitations of the ring terminal, the maximum wire size you can use is 6.0 mm2 using ring
terminals that are not pre-insulated. If using pre insulated ring terminals, the maximum wire size is reduced
to 2.63 mm2 per ring terminal. If you need a greater cross-sectional area, use two wires in parallel, each
terminated in a separate ring terminal.
The wire should have a minimum voltage rating of 300 V RMS.
Caution:
Current transformer circuits must never be fused.
Note:
If there are CTs present, spring-loaded shorting contacts ensure that the terminals into which the CTs connect are
shorted before the CT contacts are broken.
Note:
For 5A CT secondaries, we recommend using 2 x 2.5 mm2 PVC insulated multi-stranded copper wire.
P94V-TM-EN-5 281
Chapter 13 - Installation P94V
To guarantee the performance specifications, you must ensure continuity of the screen, when daisy chaining
the connections. The device is supplied with an earth link pack (part number ZA0005092) consisting of an
earth link and a self-tapping screw to facilitate this requirement.
The earth link is fastened to the Midos block just below terminal number 56 as shown:
E01402
282 P94V-TM-EN-5
P94V Chapter 13 - Installation
Caution:
Protect the opto-inputs and their wiring with a maximum 16 A high rupture
capacity (HRC) type NIT or TIA fuse.
P94V-TM-EN-5 283
Chapter 13 - Installation P94V
284 P94V-TM-EN-5
P94V Chapter 13 - Installation
5 CASE DIMENSIONS
99.0mm
A = Clearance holes
10.5mm 78.0mm B = Mounting holes
A B B A
159.0mm 168.0mm
243.1mm
A B B A
213.1mm
177.0mm
102.4mm
E01403
P94V-TM-EN-5 285
Chapter 13 - Installation P94V
151.0mm
10.75 129.5mm A = Clearance hole
B = Mounting hole
A B B A
159.0mm 168.0mm
A B B A
242.7mm
8 holes 3.4mm
23.7mm 103.6mm
213.1mm
177.0mm
154.2mm
E01404
286 P94V-TM-EN-5
COMMISSIONING INSTRUCTIONS
CHAPTER 14
Chapter 14 - Commissioning Instructions P94V
288 P94V-TM-EN-5
P94V Chapter 14 - Commissioning Instructions
1 CHAPTER OVERVIEW
This chapter contains the following sections:
Chapter Overview 289
General Guidelines 290
Commissioning Test Menu 291
Commissioning Equipment 293
Product Checks 294
Setting Checks 301
Protection Timing Checks 303
Onload Checks 305
Final Checks 306
P94V-TM-EN-5 289
Chapter 14 - Commissioning Instructions P94V
2 GENERAL GUIDELINES
Alstom Grid IEDs are self-checking devices and will raise an alarm in the unlikely event of a failure. This is
why the commissioning tests are less extensive than those for non-numeric electronic devices or electro-
mechanical relays.
To commission the devices, you (the commissioning engineer) do not need to test every function. You need
only verify that the hardware is functioning correctly and that the application-specific software settings have
been applied. You can check the settings by extracting them using the settings application software, or by
means of the front panel interface (HMI panel).
The menu language is user-selectable, so you can change it for commissioning purposes if required.
Note:
Remember to restore the language setting to the customer’s preferred language on completion.
Caution:
Before carrying out any work on the equipment you should be familiar with
the contents of the Safety Section or Safety Guide SFTY/4LM as well as the
ratings on the equipment’s rating label.
Warning:
With the exception of the CT shorting contacts check, do not disassemble the
device during commissioning.
290 P94V-TM-EN-5
P94V Chapter 14 - Commissioning Instructions
Note:
When the Test Mode cell is set to Contacts Blocked, the relay output status indicates which contacts would
operate if the IED was in-service. It does not show the actual status of the output relays, as they are blocked.
P94V-TM-EN-5 291
Chapter 14 - Commissioning Instructions P94V
Once testing is complete, return the device back into service by setting the Test Mode Cell back to
Disabled.
Caution:
When the cell is in Test Mode, the Scheme Logic still drives the output relays,
which could result in tripping of circuit breakers. To avoid this, set the Test
Mode cell to Contacts Blocked.
Note:
Test mode and Contacts Blocked mode can also be selected by energising an opto-input mapped to the Test
Mode signal, and the Contact Block signal respectively.
Note:
When the Test Mode cell is set to Contacts Blocked the Relay O/P Status cell does not show the current status
of the output relays and therefore cannot be used to confirm operation of the output relays. Therefore it will be
necessary to monitor the state of each contact in turn.
Note:
When the status in both Red LED Status and Green LED Status cells is ‘1’, this indicates the LEDs illumination is
yellow.
292 P94V-TM-EN-5
P94V Chapter 14 - Commissioning Instructions
4 COMMISSIONING EQUIPMENT
P94V-TM-EN-5 293
Chapter 14 - Commissioning Instructions P94V
5 PRODUCT CHECKS
These product checks are designed to ensure that the device has not been physically damaged prior to
commissioning, is functioning correctly and that all input quantity measurements are within the stated
tolerances.
If the application-specific settings have been applied to the IED prior to commissioning, you should make a
copy of the settings. This will allow you to restore them at a later date if necessary. This can be done by:
● Obtaining a setting file from the customer.
● Extracting the settings from the IED itself, using a portable PC with appropriate setting software.
If the customer has changed the password that prevents unauthorised changes to some of the settings,
either the revised password should be provided, or the original password restored before testing.
Note:
If the password has been lost, a recovery password can be obtained from Alstom Grid.
Warning:
The following group of tests should be carried out without the auxiliary supply
being applied to the IED and, if applicable, with the trip circuit isolated.
The current and voltage transformer connections must be isolated from the IED for these checks. If a P991
test block is provided, the required isolation can be achieved by inserting test plug type P992. This open
circuits all wiring routed through the test block.
Before inserting the test plug, you should check the scheme diagram to ensure that this will not cause
damage or a safety hazard (the test block may, for example, be associated with protection current
transformer circuits). The sockets in the test plug, which correspond to the current transformer secondary
windings, must be linked before the test plug is inserted into the test block.
Warning:
Never open-circuit the secondary circuit of a current transformer since the
high voltage produced may be lethal and could damage insulation.
If a test block is not provided, the voltage transformer supply to the IED should be isolated by means of the
panel links or connecting blocks. The line current transformers should be short-circuited and disconnected
from the IED terminals. Where means of isolating the auxiliary supply and trip circuit (for example isolation
links, fuses and MCB) are provided, these should be used. If this is not possible, the wiring to these circuits
must be disconnected and the exposed ends suitably terminated to prevent them from being a safety hazard.
Caution:
Check the rating information provided with the device. Check that the IED
being tested is correct for the line or circuit.
Carefully examine the IED to see that no physical damage has occurred since installation.
294 P94V-TM-EN-5
P94V Chapter 14 - Commissioning Instructions
Ensure that the case earthing connections (bottom left-hand corner at the rear of the IED case) are used to
connect the IED to a local earth bar using an adequate conductor.
5.1.2 INSULATION
Insulation resistance tests are only necessary during commissioning if explicitly requested.
Isolate all wiring from the earth and test the insulation with an electronic or brushless insulation tester at a
DC voltage not exceeding 500 V. Terminals of the same circuits should be temporarily connected together.
The insulation resistance should be greater than 100 MW at 500 V.
On completion of the insulation resistance tests, ensure all external wiring is correctly reconnected to the
IED.
Caution:
Check that the external wiring is correct according to the relevant IED and
scheme diagrams. Ensure that phasing/phase rotation appears to be as
expected.
The auxiliary DC voltage supply uses terminals 13 (supply positive) and 14 (supply negative). Unlike the K-
series products, the P40Agile series does not provide a field voltage supply. For K-series retrofit applications
where pin-to-pin compatibility is required, the equivalent P40 Agile products emulate the field voltage supply
by having internal links between pins 7 and 13, and pins 8 and 14, respectively.
Warning:
Do not energise the IED or interface unit using the battery charger with the
battery disconnected as this can irreparably damage the power supply
circuitry.
Caution:
Energise the IED only if the auxiliary supply is within the specified operating
ranges. If a test block is provided, it may be necessary to link across the front
of the test plug to connect the auxiliary supply to the IED.
P94V-TM-EN-5 295
Chapter 14 - Commissioning Instructions P94V
Warning:
The current and voltage transformer connections must remain isolated from
the IED for these checks. The trip circuit should also remain isolated to
prevent accidental operation of the associated circuit breaker.
The following group of tests verifies that the IED hardware and software is functioning correctly and should
be carried out with the supply applied to the IED.
Caution:
Before applying a contrast setting, make sure that it will not make the display
so light or dark such that menu text becomes unreadable. It is possible to
restore the visibility of a display by downloading a setting file, with the LCD
Contrast set within the typical range of 7 - 11.
296 P94V-TM-EN-5
P94V Chapter 14 - Commissioning Instructions
If the time and date is not being maintained by an IRIG-B signal, ensure that the IRIG-B Sync cell in the
DATE AND TIME column is set to Disabled.
1. Set the date and time to the correct local time and date using Date/Time cell or using the serial
protocol.
P94V-TM-EN-5 297
Chapter 14 - Commissioning Instructions P94V
3. Connect a continuity tester across the terminals corresponding to output relay 1 as shown in the
external connection diagram.
4. To operate the output relay set the Contact Test cell to Apply Test.
5. Check the operation with the continuity tester.
6. Measure the resistance of the contacts in the closed state.
7. Reset the output relay by setting the Contact Test cell to Remove Test.
8. Repeat the test for the remaining output relays.
9. Return the IED to service by setting the Test Mode cell in the COMMISSION TESTS menu to
Disabled.
E01402
298 P94V-TM-EN-5
P94V Chapter 14 - Commissioning Instructions
RS232 K-Bus
P94V-TM-EN-5 299
Chapter 14 - Commissioning Instructions P94V
Note:
If a PC connected to the IED using the rear communications port is being used to display the measured current, the
process will be similar. However, the setting of the Remote Values cell in the MEASURE’T SETUP column will
determine whether the displayed values are in primary or secondary Amperes.
Corresponding VT ratio
Cell in MEASUREMENTS 1
(in TRANS. RATIOS column)
VAN magnitude
VBN magnitude Main VT Primary / Main VT Sec'y
VCN magnitude
C/S Voltage Mag C/S VT Primary / C/S VT Secondary
300 P94V-TM-EN-5
P94V Chapter 14 - Commissioning Instructions
6 SETTING CHECKS
The setting checks ensure that all of the application-specific settings (both the IED’s function and
programmable scheme logic settings) have been correctly applied.
Note:
If applicable, the trip circuit should remain isolated during these checks to prevent accidental operation of the
associated circuit breaker.
Note:
The device name may not already exist in the system shown in System Explorer. In this case, perform a Quick
Connect to the IED, then manually add the settings file to the device name in the system. Refer to the Settings
Application Software help for details of how to do this.
P94V-TM-EN-5 301
Chapter 14 - Commissioning Instructions P94V
8. Press the Enter key to confirm the new setting value or the Clear key to discard it. The new setting is
automatically discarded if it is not confirmed within 15 seconds.
9. For protection group settings and disturbance recorder settings, the changes must be confirmed
before they are used. When all required changes have been entered, return to the column heading
level and press the down cursor key. Before returning to the default display, the following prompt
appears.
Update settings?
ENTER or CLEAR
10. Press the Enter key to accept the new settings or press the Clear key to discard the new settings.
Note:
If the menu time-out occurs before the setting changes have been confirmed, the setting values are also discarded.
Control and support settings are updated immediately after they are entered, without the Update settings prompt.
It is not possible to change the PSL using the IED’s front panel HMI.
Caution:
Where the installation needs application-specific PSL, the relevant .psl files,
must be transferred to the IED, for each and every setting group that will be
used. If you do not do this, the factory default PSL will still be resident. This
may have severe operational and safety consequences.
302 P94V-TM-EN-5
P94V Chapter 14 - Commissioning Instructions
Note:
If using the default PSL, use output relay 3 as this is already mapped to the DDB signal Trip Command Out.
For all characteristics, allowance must be made for the accuracy of the test equipment being used.
Note:
For definite time and inverse characteristics there is an additional delay of up to 0.02 second and 0.08 second
respectively. You may need to add this the IED's acceptable range of operating times.
P94V-TM-EN-5 303
Chapter 14 - Commissioning Instructions P94V
Caution:
On completion of the tests, you must restore all settings that were disabled
for testing purposes.
304 P94V-TM-EN-5
P94V Chapter 14 - Commissioning Instructions
8 ONLOAD CHECKS
The objectives of the on-load checks are to:
● Confirm the external wiring to the voltage inputs is correct
● Check the phase rotation
● Check the magnitudes of the phase voltages and the check synchronisation voltage
These checks can only be carried out if there are no restrictions preventing the energisation of the plant, and
the other devices in the group have already been commissioned.
Remove all test leads and temporary shorting links, then replace any external wiring that has been removed
to allow testing.
Warning:
If any external wiring has been disconnected for the commissioning process,
replace it in accordance with the relevant external connection or scheme
diagram.
If the Local Values cell is set to Secondary, the values displayed should be equal to the applied secondary
voltage. The values should be within 1% of the applied secondary voltages. However, an additional
allowance must be made for the accuracy of the test equipment being used.
If the Local Values cell is set to Primary, the values displayed should be equal to the applied secondary
voltage multiplied the corresponding voltage transformer ratio set in the TRANS. RATIOS column. The
values should be within 1% of the expected values, plus an additional allowance for the accuracy of the test
equipment being used.
P94V-TM-EN-5 305
Chapter 14 - Commissioning Instructions P94V
9 FINAL CHECKS
1. Remove all test leads and temporary shorting leads.
2. If you have had to disconnect any of the external wiring in order to perform the wiring verification tests,
replace all wiring, fuses and links in accordance with the relevant external connection or scheme
diagram.
3. The settings applied should be carefully checked against the required application-specific settings to
ensure that they are correct, and have not been mistakenly altered during testing.
4. Ensure that all protection elements required have been set to Enabled in the CONFIGURATION
column.
5. Ensure that the IED has been restored to service by checking that the Test Mode cell in the
COMMISSION TESTS column is set to ‘Disabled’.
6. If the IED is in a new installation or the circuit breaker has just been maintained, the circuit breaker
maintenance and current counters should be zero. These counters can be reset using the Reset All
Values cell. If the required access level is not active, the device will prompt for a password to be
entered so that the setting change can be made.
7. If the menu language has been changed to allow accurate testing it should be restored to the
customer’s preferred language.
8. If a P991/MMLG test block is installed, remove the P992/MMLB test plug and replace the cover so that
the protection is put into service.
9. Ensure that all event records, fault records, disturbance records, alarms and LEDs and
communications statistics have been reset.
Note:
Remember to restore the language setting to the customer’s preferred language on completion.
306 P94V-TM-EN-5
MAINTENANCE AND
TROUBLESHOOTING
CHAPTER 15
Chapter 15 - Maintenance and Troubleshooting P94V
308 P94V-TM-EN-5
P94V Chapter 15 - Maintenance and Troubleshooting
1 CHAPTER OVERVIEW
The Maintenance and Troubleshooting chapter provides details of how to maintain and troubleshoot products
based on the Px4x and P40Agile platforms. Always follow the warning signs in this chapter. Failure to do so
may result injury or defective equipment.
Caution:
Before carrying out any work on the equipment you should be familiar with the
contents of the Safety Section or the Safety Guide SFTY/4LM and the ratings on
the equipment’s rating label.
The troubleshooting part of the chapter allows an error condition on the IED to be identified so that
appropriate corrective action can be taken.
If the device develops a fault, it is usually possible to identify which module needs replacing. It is not possible
to perform an on-site repair to a faulty module.
If you return a faulty unit or module to the manufacturer or one of their approved service centres, you should
include a completed copy of the Repair or Modification Return Authorization (RMA) form.
This chapter contains the following sections:
Chapter Overview 309
Maintenance 310
Troubleshooting 312
P94V-TM-EN-5 309
Chapter 15 - Maintenance and Troubleshooting P94V
2 MAINTENANCE
Although some functionality checks can be performed from a remote location, these are predominantly
restricted to checking that the unit is measuring the applied currents and voltages accurately, and checking
the circuit breaker maintenance counters. For this reason, maintenance checks should also be performed
locally at the substation.
Caution:
Before carrying out any work on the equipment you should be familiar with the
contents of the Safety Section or the Safety Guide SFTY/4LM and the ratings on
the equipment’s rating label.
2.1.1 ALARMS
First check the alarm status LED to see if any alarm conditions exist. If so, press the Read key repeatedly to
step through the alarms.
After dealing with any problems, clear the alarms. This will clear the relevant LEDs.
2.1.2 OPTO-ISOLATORS
Check the opto-inputs by repeating the commissioning test detailed in the Commissioning chapter.
310 P94V-TM-EN-5
P94V Chapter 15 - Maintenance and Troubleshooting
Caution:
If the repair is not performed by an approved service centre, the warranty will be
invalidated.
Caution:
Before carrying out any work on the equipment, you should be familiar with the
contents of the Safety Information section of this guide or the Safety Guide
SFTY/4LM, as well as the ratings on the equipment’s rating label. This should
ensure that no damage is caused by incorrect handling of the electronic
components.
Warning:
Before working at the rear of the unit, isolate all voltage and current supplying it.
Note:
The Alstom Grid products have integral current transformer shorting switches which will close, for safety reasons,
when the terminal block is removed.
2.3 CLEANING
Warning:
Before cleaning the device, ensure that all AC and DC supplies and transformer
connections are isolated, to prevent any chance of an electric shock while
cleaning.
Only clean the equipment with a lint-free cloth dampened with clean water. Do not use detergents, solvents
or abrasive cleaners as they may damage the product's surfaces and leave a conductive residue.
P94V-TM-EN-5 311
Chapter 15 - Maintenance and Troubleshooting P94V
3 TROUBLESHOOTING
Record whether the same error code is displayed when the IED is
2 Record displayed error and re-apply IED supply. rebooted, then contact the local service centre stating the error code and
product details.
The IED displays a message for corrupt settings and The power-up tests have detected corrupted IED settings. Restore the
3 prompts for the default values to be restored for the default settings to allow the power-up to complete, and then reapply the
affected settings. application-specific settings.
Programmable scheme logic error due to excessive execution time.
Restore the default settings by powering up with both horizontal cursor
keys pressed, then confirm restoration of defaults at the prompt using the
The IED resets when the power-up is complete. A record
4 Enter key. If the IED powers up successfully, check the programmable
error code is displayed.
logic for feedback paths.
Other error codes relate to software errors on the main processor board,
contact the local service centre.
312 P94V-TM-EN-5
P94V Chapter 15 - Maintenance and Troubleshooting
P94V-TM-EN-5 313
Chapter 15 - Maintenance and Troubleshooting P94V
314 P94V-TM-EN-5
P94V Chapter 15 - Maintenance and Troubleshooting
A recovered scheme is logically correct but much of the original graphical information is lost. Many signals
are drawn in a vertical line down the left side of the canvas. Links are drawn orthogonally using the shortest
path from A to B. Any annotation added to the original diagram such as titles and notes are lost.
Sometimes a gate type does not appear as expected. For example, a single-input AND gate in the original
scheme appears as an OR gate when uploaded. Programmable gates with an inputs-to-trigger value of 1
also appear as OR gates
P94V-TM-EN-5 315
Chapter 15 - Maintenance and Troubleshooting P94V
316 P94V-TM-EN-5
TECHNICAL SPECIFICATIONS
CHAPTER 16
Chapter 16 - Technical Specifications P94V
318 P94V-TM-EN-5
P94V Chapter 16 - Technical Specifications
1 CHAPTER OVERVIEW
This chapter describes the technical specifications of the product.
This chapter contains the following sections:
Chapter Overview 319
Interfaces 320
Performance of Voltage Protection Functions 322
Performance of Frequency Protection Functions 324
Performance of Monitoring and Control Functions 327
Measurements and Recording 328
Standards Compliance 329
Mechanical Specifications 330
Ratings 331
Power Supply 332
Input / Output Connections 333
Environmental Conditions 335
Type Tests 336
Electromagnetic Compatibility 338
P94V-TM-EN-5 319
Chapter 16 - Technical Specifications P94V
2 INTERFACES
320 P94V-TM-EN-5
P94V Chapter 16 - Technical Specifications
P94V-TM-EN-5 321
Chapter 16 - Technical Specifications P94V
322 P94V-TM-EN-5
P94V Chapter 16 - Technical Specifications
P94V-TM-EN-5 323
Chapter 16 - Technical Specifications P94V
Accuracy
Pick-up Setting +/- 10 mHz
Drop-off Setting -20 mHz +/- 10 mHz
Operating timer +/- 2% or 50 ms, whichever is greater
Reference conditions: Tested using step changed in frequency with Freq. Av Cycles setting = 0 and no
intentional time delay.
Fs = start frequency – frequency setting
Ff = frequency setting – end frequency
Accuracy
Pick-up Setting +/- 10 mHz
Drop-off Setting + 20 mHz +/- 10 mHz
Operating timer +/- 2% or 50 ms, whichever is greater
Reference conditions: Tested using step changed in frequency with Freq. Av Cycles setting = 0 and no
intentional time delay.
Fs = start frequency – frequency setting
Ff = frequency setting – end frequency
Accuracy
Pick-up (f) Setting +/- 10 mHz
Pick-up (df/dt) Setting +/- 3% or +/- 10 mHz/s, whichever is greater
324 P94V-TM-EN-5
P94V Chapter 16 - Technical Specifications
Accuracy
Drop-off (f, underfrequency) (Setting + 20 mHz) +/- 10 mHz
Drop-off (f, overfrequency) (Setting - 20 mHz) +/- 10 mHz
Drop-off (df/dt, falling, for settings between 10 mHz/s and
(Setting + 5 mHz/s) +/- 10 mHz/s
100 mHz/s)
Drop-off (df/dt, falling, for settings greater than (Setting + 50 mHz/s) +/- 5% or +/- 55 mHz/s, whichever is
100 mHz/s) greater
Drop-off (df/dt, rising, for settings between 10 mHz/s and
(Setting - 5 mHz/s) +/- 10 mHz/s
100 mHz/s )
Drop-off (df/dt, rising, for settings greater than (Setting - 50 mHz/s) +/- 5% or +/- 55 mHz/s, whichever is
100 mHz/s) greater
Accuracy
Pick-up (df/dt) Setting +/- 3% or +/- 10 mHz/s, whichever is greater
Drop-off (df/dt, falling, for settings between 10 mHz/s
(Setting + 5 mHz/s) +/- 10 mHz/s
and 100 mHz/s)
Drop-off (df/dt, falling, for settings greater than (Setting + 50 mHz/s) +/- 5% or +/- 55 mHz/s, whichever is
100 mHz/s) greater
Drop-off (df/dt, rising, for settings between 10 mHz/s
(Setting - 5 mHz/s) +/- 10 mHz/s
and 100 mHz/s)
Drop-off (df/dt, rising, for settings greater than (Setting - 50 mHz/s) +/- 5% or +/- 55 mHz/s, whichever is
100 mHz/s) greater
Operating timer +/- 2% or 50 ms, whichever is greater
Referecne Conditions: Tested with df/dt Average Cycles = 0 for df/dt settings greater than 0.1 Hz/s, and no
intentional time delay.
Accuracy
Pick-up (f) Setting +/- 10 mHz
Pick-up (Df/Dt) Setting +/- 100 mHz/s
Drop-off (falling) (Setting + 20 mHz) +/- 10 mHz
Drop-off (rising) (Setting - 20 mHz) +/- 10 mHz
Operating timer +/- 2% or 30 ms, whichever is greater
P94V-TM-EN-5 325
Chapter 16 - Technical Specifications P94V
Operating time
Operating time (Freq. Av Cycles setting = 0) <125 ms
Reference conditions: To maintain accuracy, the minimum time delay setting should be:
Dt> 0.375 x Df + 0.23 (f0r Df setting <1 Hz)
Dt> 0.156 x Df + 0.47 (for Df setting >= 1 Hz)
326 P94V-TM-EN-5
P94V Chapter 16 - Technical Specifications
Note:
* Tested at 21°C
P94V-TM-EN-5 327
Chapter 16 - Technical Specifications P94V
6.1 GENERAL
328 P94V-TM-EN-5
P94V Chapter 16 - Technical Specifications
7 STANDARDS COMPLIANCE
Compliance with the European Commission Directive on EMC and LVD is demonstrated by self certification
against international standards.
Protective Class
IEC 60255-27: 2005 Class 1 (unless otherwise specified in equipment documentation). This equipment
requires a protective conductor (earth) to ensure user safety.
Installation category
IEC 60255-27: 2005 Overvoltage Category 3. Equipment in this category is qualification tested at 5kV peak,
1.2/50 mS, 500 Ohms, 0.5 J, between all supply circuits and earth and also between independent circuits.
Environment
IEC 60255-27: 2005, IEC 60255-26:2009. The equipment is intended for indoor use only. If it is required for
use in an outdoor environment, it must be mounted in a cabinet with the appropriate degree of ingress
protection.
P94V-TM-EN-5 329
Chapter 16 - Technical Specifications P94V
8 MECHANICAL SPECIFICATIONS
Physical Measurements
20TE
Case Types
30TE
Weight (20TE case) 2 kg – 3 kg (depending on chosen options)
Weight (30TE case) 3 kg – 4 kg (depending on chosen options)
Dimensions in mm (w x h x l) (20TE case) W: 102.4mm H: 177.0mm D: 243.1mm
Dimensions in mm (w x h x l) (30TE case) W: 154.2mm H: 177.0mm D: 243.1mm
Mounting Panel, rack, or retrofit
Against dust and dripping water (front face) IP52 as per IEC 60529:2002
Protection against dust (whole case) IP50 as per IEC 60529:2002
Protection for sides of the case (safety) IP30 as per IEC 60529:2002
Protection for rear of the case (safety) IP10 as per IEC 60529:2002
330 P94V-TM-EN-5
P94V Chapter 16 - Technical Specifications
9 RATINGS
AC Measuring Inputs
Nominal frequency 50 Hz or 60 Hz (settable)
Operating range 40 Hz to 70 Hz (SW version 55: 40 Hz to 65 Hz)
Phase rotation ABC or CBA
AC Voltage
Nominal voltage 100 V to 120 V
Nominal burden per phase < 0.1 VA at Vn
Thermal withstand Continuous: 2 x Vn, 10 s: 2.6 x Vn
P94V-TM-EN-5 331
Chapter 16 - Technical Specifications P94V
10 POWER SUPPLY
24-250 V DC +/-20%
Nominal operating range
110-240 V AC -20% + 10%
Maximum operating range 19 to 300 V DC
Frequency range for AC supply 45 – 65 Hz
Ripple <15% for a DC supply (compliant with IEC 60255-11:2008)
Note:
Maximum loading = all inputs/outputs energised.
Note:
Quiescent or 1/2 loading = 1/2 of all inputs/outputs energised.
332 P94V-TM-EN-5
P94V Chapter 16 - Technical Specifications
Nominal battery
Logic levels: 60-80% DO/PU Logic Levels: 50-70% DO/PU Logic Levels: 58-75% DO/PU
voltage
24/27 V Logic 0 < 16.2V, Logic 1 > 19.2V Logic 0 <12V, Logic 1 > 16.8V Logic 0 <15.7V, Logic 1 > 18V
30/34 Logic 0 < 20.4V, Logic 1 > 24V Logic 0 < 15V, Logic 1 > 21V Logic 0 < 19.7V, Logic 1 > 22.5V
48/54 Logic 0 < 32.4V, Logic 1 > 38.4V Logic 0 < 24V, Logic 1 > 33.6V Logic 0 < 31.3V, Logic 1 > 36V
110/125 Logic 0 < 75V, Logic 1 > 88V Logic 0 < 55.V, Logic 1 > 77V Logic 0 < 72.5V, Logic 1 > 82.5V
220/250 Logic 0 < 150V, Logic 1 > 176V Logic 0 < 110V, Logic 1 > 154V Logic 0 < 145V, Logic 1 > 165V
Note:
Filter is required to make the opto-inputs immune to induced AC voltages.
P94V-TM-EN-5 333
Chapter 16 - Technical Specifications P94V
334 P94V-TM-EN-5
P94V Chapter 16 - Technical Specifications
12 ENVIRONMENTAL CONDITIONS
P94V-TM-EN-5 335
Chapter 16 - Technical Specifications P94V
13 TYPE TESTS
13.1 INSULATION
336 P94V-TM-EN-5
P94V Chapter 16 - Technical Specifications
Note:
Exceptions are communications ports and normally-open output contacts, where applicable.
P94V-TM-EN-5 337
Chapter 16 - Technical Specifications P94V
14 ELECTROMAGNETIC COMPATIBILITY
IEC 60255-22-4: 2008 and EN61000-4-4:2004. Test severity level lll and lV,
Compliance
IEC 60255-26:2013
Applied to communication inputs Amplitude: 2 kV, burst frequency 5 kHz and 100 KHz (level 4)
Applied to power supply and all other
Amplitude: 4 kV, burst frequency 5 kHz and 100 KHz (level 4)
inputs except for communication inputs
338 P94V-TM-EN-5
P94V Chapter 16 - Technical Specifications
P94V-TM-EN-5 339
Chapter 16 - Technical Specifications P94V
Note:
Compliance is achieved using the opto-input filter.
340 P94V-TM-EN-5
WIRING DIAGRAMS
CHAPTER 17
Chapter 17 - Wiring Diagrams P94V
342 P94V-TM-EN-5
P94V Chapter 17 - Wiring Diagrams
1 CHAPTER OVERVIEW
This chapter contains the wiring diagrams for all possible situations.
This chapter contains the following sections:
Chapter Overview 343
I/O Option A with NVD Input 344
I/O Option A with Check Synchronisation 345
I/O Option A with NVD Input and Ethernet 346
I/O Option A with Check Synchronisation and Ethernet 347
I/O Option B with NVD Input and 2 x RS485 Serial Inputs 348
I/O Option B with Check Synchronisation Input and 2 x RS485 Serial Inputs 349
I/O Option B with NVD Input and TCS 350
I/O Option C with Check Synchronisation Input and TCS 351
I/O Option D with NVD Input 352
I/O Option D with Check Synchronisation Input 353
I/O Option E with NVD Input 354
I/O Option F with NVD Input 355
I/O Option E with Check Synchronisation Input 356
I/O Option F with Check Synchronisation Input 357
P94V-TM-EN-5 343
Chapter 17 - Wiring Diagrams P94V
W02323
Figure 101: P94V Voltage and Frequency IED with NVD Input (Model B)
344 P94V-TM-EN-5
P94V Chapter 17 - Wiring Diagrams
W02324
Figure 102: P94V Voltage and Frequency IED with Check Synchronisation input (Model P)
P94V-TM-EN-5 345
Chapter 17 - Wiring Diagrams P94V
W02327
Figure 103: P94V Voltage and Frequency IED with 8 inputs, 8 outputs, NVD Input and Ethernet (Model
B)
346 P94V-TM-EN-5
P94V Chapter 17 - Wiring Diagrams
W02328
Figure 104: P94V Voltage and Frequency IED with 8 inputs, 8 outputs, Check Synchronisation input
and Ethernet (Model P)
P94V-TM-EN-5 347
Chapter 17 - Wiring Diagrams P94V
W02369
Figure 105: P94V Voltage and Frequency IED with 11 inputs, 12 outputs, NVD Input and 2 RS485
serial ports (Model B)
348 P94V-TM-EN-5
P94V Chapter 17 - Wiring Diagrams
W02370
Figure 106: P94V Voltage and Frequency IED with 11 inputs, 12 outputs, Check Synchronisation input
and 2 RS485 serial ports (Model P)
P94V-TM-EN-5 349
Chapter 17 - Wiring Diagrams P94V
W02371
Figure 107: P94V Voltage and Frequency IED with 11 inputs, 12 outputs and NVD Input, for Trip
Circuit Supervision (Model B)
350 P94V-TM-EN-5
P94V Chapter 17 - Wiring Diagrams
W02372
Figure 108: P94V Voltage and Frequency IED with 11 inputs, 12 outputs and Check Synchronisation
Input, for Trip Circuit Supervision (Model P)
P94V-TM-EN-5 351
Chapter 17 - Wiring Diagrams P94V
W02373.eps
Figure 109: P94V Voltage and Frequency IED with 13 inputs, 12 outputs and NVD Input (Model B)
352 P94V-TM-EN-5
P94V Chapter 17 - Wiring Diagrams
W02374.eps
Figure 110: P94V Voltage and Frequency IED with 13 inputs, 12 outputs and Check Synchronisation
Input (Model P)
P94V-TM-EN-5 353
354
12
A A
W02465
C
A B C
C B
PHASE ROTATION
N
SEE NOTES 2 & 3
Chapter 17 - Wiring Diagrams
VA
17 1
VB 18
VC 19
20
I/O OPTION E WITH NVD INPUT
46
48
NOTES: 1 50
3 4
5 6 52
7 8
(b) SHORT TERMINALS BREAK BEFORE (c). 9 10
(c) LONG TERMINAL.
(d) PIN TERMINAL (P.C.B. TYPE) 13 14
17 18
19 20
21 22
23 24
13 +
25 26
27 28 14 -
Figure 111: P94V Voltage and Frequency IED with 3 inputs, 4 outputs and NVD Input (Model B)
(WITH INTEGRAL CASE
EARTH STRAP)
10P94V11-1B
P94V-TM-EN-5
P94V
13
A A
P94V
W02466
A B C
C B
PHASE ROTATION
P94V-TM-EN-5
N
VA 17
18
VB
19
VC 20
NOTES:
50
52
1 57 58
3 4 74
59 60
5 6 61 62
7 8 76
63 64
9 10 65 66 78
67 68
13 14 69 70 80
71 72 13 +
17 18 73 74 82
19 20 75 76 14 -
21 22 77 78 84
23 24 79 80
25 26 81 82
27 28 83 84
Figure 112: P94V Voltage and Frequency IED with 6 inputs, 8 outputs and NVD Input (Model B)
MODULE TERMINAL BLOCKS
VIEWED FROM REAR 10P94V12-1B
(WITH INTEGRAL CASE
EARTH STRAP)
355
Chapter 17 - Wiring Diagrams
356
14
A
A
B
W02467
A B C
C B C B A
Input (Model P)
PHASE ROTATION
N
Chapter 17 - Wiring Diagrams
1
VA 17
18
VB
19
VC 20
46
NOTES:
48
1
(a) C.T. SHORTING LINKS MAKE 3 4
BEFORE (b) & (c) DISCONNECT. 5 6 50
(b) SHORT TERMINALS BREAK BEFORE (c). 7 8
(c) LONG TERMINAL. 9 10 52
(d) PIN TERMINAL (P.C.B. TYPE)
13 14
17 18
19 20
21 22
23 24
25 26
27 28 13 +
14 -
MODULE TERMINAL BLOCKS
VIEWED FROM REAR
I/O OPTION E WITH CHECK SYNCHRONISATION INPUT
10P94V13-1B
Figure 113: P94V Voltage and Frequency IED with 3 inputs, 4 outputs and Check Synchronisation
P94V-TM-EN-5
P94V
15
A
P94V
B
C B
C
W02468
PHASE ROTATION A B C
C B A
P94V-TM-EN-5
N
Input (Model P)
N
VA 17
18
VB
19
VC 20
NOTES:
50
52
74
1 57 58 76
3 4 59 60
5 6 61 62 78
7 8 63 64
9 10 65 66 80
67 68 13 +
82
13 14 69 70
71 72 14 -
84
17 18 73 74
19 20 75 76
21 22 77 78
23 24 79 80
I/O OPTION F WITH CHECK SYNCHRONISATION INPUT
25 26 81 82
27 28 83 84
Figure 114: P94VP Voltage and Frequency IED with 6 inputs, 8 outputs and Check Synchronisation
EARTH STRAP)
357
Chapter 17 - Wiring Diagrams
Chapter 17 - Wiring Diagrams P94V
358 P94V-TM-EN-5
ORDERING OPTIONS
APPENDIX A
Appendix A - Ordering Options P94V
360 P94V-TM-EN-5
P94V Appendix A - Ordering Options
Application
Base (with measured NVD) B
Check Synch (with derived NVD) P
Check Synch + Autoreclose (with derived NVD) R
Current/Voltage transformers
Voltage Only 1
SEF CT 2
Hardware Options
EIA RS485/IRIG-B (demodulated) 1
Two ports - EIA RS485/IRIG-B (demodulated) and Ethernet - Single channel Fibre/Copper 6
Two ports - EIA RS485/IRIG-B (demodulated) and EIA RS485 8
I/O Options
Standard (8 logic inputs + 8 relay outputs) A
Total (11 logic inputs + 12 relay outputs) B
Total (11 logic inputs + 12 relay outputs) suitable for trip circuit supervision C
Total (13 logic inputs + 12 relay outputs) D
Total (3 logic inputs + 4 relay outputs) E
Total (6 logic inputs + 8 relay outputs) suitable for trip circuit supervision F
Communication protocol
K-Bus 1
Modbus 2
IEC60870-5-103 (VDEW) 3
DNP3.0 4
IEC 61850 over Ethernet and Courier via rear K-Bus/RS485 6
IEC 61850 over Ethernet over Ethernet and with IEC60870-5-103 via rear EIA RS485 7
DNP3.0 over Ethernet and Courier via K-Bus/RS485 8
IEC 61850 over Ethernet and Modbus via rear K-Bus/RS485 9
IEC 61850 over Ethernet and DNP3.0 via rear K-Bus/RS485 A
Case
20TE Flush (no function keys, 4 programmable LEDs) B
30TE Flush (3 function keys with LEDs, 8 programmable LEDs) C
Software only 0
30TE Flush (Additional shorting link) 6
Language
Multilingual (English, French, German, Spanish) 0
Multilingual (English, Russian, Italian, Portuguese) 6
Chinese, English or French via HMI, with English or French only via Communications port C
Software Reference
Unless specified the latest version will be delivered **
Customisation / Regionalisation
Default 0
Customer specific A
P94V-TM-EN-5 A1
Appendix A - Ordering Options P94V
A2 P94V-TM-EN-5
SETTINGS AND SIGNALS
APPENDIX B
Appendix B - Settings and Signals P94V
Tables, containing a full list of settings, measurement data and DDB signals for each product model, are
provided in a separate interactive PDF file attached as an embedded resource.
Tables are organized into a simple menu system allowing selection by language (where available), model
and table type, and may be viewed and/or printed using an up-to-date version of Adobe Reader.
362 P94V-TM-EN-5
Alstom Grid
www.alstom.com/grid/contactcentre/
www.alstom.com