Calculate Effective and Low-Impedance Grounding For Power Systems - Technical Articles
Calculate Effective and Low-Impedance Grounding For Power Systems - Technical Articles
Calculate Effective and Low-Impedance Grounding For Power Systems - Technical Articles
Technical Article
The best method to control overvoltages is effective, or solid, grounding. It’s important to properly calculate the resistors
required for this type of grounding. This article shows how to calculate effective and low-impedance grounding through a
step-by-step example.
These methods supply phase-to-neutral connected loads without the risk of finding dangerous neutral-to-ground voltages
when a ground-fault arises. An effectively grounded system also has the highest values of ground-fault currents, which may
range from zero to three times the three-phase short-circuit current.
In the USA, low-resistance grounding is the most popular method utilized to limit ground-fault current. The value of
resistance is much lower than that of the high-resistance method and ranges from 5% to 20% of the three-phase fault
current. Some applications limit the ground current to around 50A to 600A.
A typical resistor of 400A will allow enough current flow to operate the protective relays for fast fault clearing. These
resistors are also time-rated. A standard figure is 10s because, like in effective grounding, the branch will shut down after
the first ground-fault.
Note:
Zb = Base impedance (This is part of the per-unit system used to analyze power systems)
https://eepower.com/technical-articles/how-to-calculate-effective-and-low-impedance-grounding-for-power-systems/# 1/6
11/15/22, 8:02 AM How to Calculate Effective and Low-impedance Grounding for Power Systems - Technical Articles
A symmetrical synchronous generator operated at no load (i.e., with the main circuit breaker open), and rated 500 MVA,
22kV, is wye connected and solidly grounded.
Generator constants:
Xd’’= X1 = X2 = 15% ; X0 = 5%
1. Find the subtransient single line-to-ground fault current in the generator windings.
https://eepower.com/technical-articles/how-to-calculate-effective-and-low-impedance-grounding-for-power-systems/# 2/6
11/15/22, 8:02 AM How to Calculate Effective and Low-impedance Grounding for Power Systems - Technical Articles
Figure 2. Unloaded, solidly grounded generator with a three-phase short circuit at its terminals
Note: The line-to-ground fault current is 28.6% higher than the three-phase fault current. It may damage the generator.
5. Find the reactance of a neutral grounding reactor to limit the line-to-ground fault current to 100% of the three-phase fault
current.
If1ɸ = 3∙I0 = If3ɸ = 87.48 kA = 3∙VLN/(X1 + X2 + X0 + 3∙XN) = (√3∙√3∙ VLL/√3)/(X1 + X2 + X0 + 3∙XN) = √3∙22
kV/(0.1452 + 0.1452 + 0.0484 + 3∙XN) Ω = 38.106 kV/(0.3388 + 3∙XN) Ω => XN = 0.03226 Ω
https://eepower.com/technical-articles/how-to-calculate-effective-and-low-impedance-grounding-for-power-systems/# 3/6
11/15/22, 8:02 AM How to Calculate Effective and Low-impedance Grounding for Power Systems - Technical Articles
6. Find the ratio Xₒ/X1 with the neutral grounding reactor of question 5.
With the neutral grounding reactor inserted in the zero-sequence circuit X0 = 5% + 10% = 15% = X1
Xₒ/X1 = 15%/15% = 1
Note 1: The fault current contribution of one winding of this generator to a line-to-ground fault, outside the machine, will
not be higher than the three-phase fault current of the generator.
Note 2: Xₒ/X1 < 3 —> By definition, the system is not low-reactance grounded, despite having a reactance inserted in the
neutral.
7. Find the reactance of a neutral grounding reactor to limit the line-to-ground fault current to 60% of the three-phase fault
current.
If1ɸ = 3∙I0 = 0.60∙If3ɸ = 0.60∙87.48 kA = 52.49 kA = 38.106 kV/(0.3388 + 3∙XN) Ω => XN = 0.1291 Ω
8. Find the ratio Xₒ/X1 with the neutral grounding reactor of question 7.
X0 = 5% + 40% = 45%
https://eepower.com/technical-articles/how-to-calculate-effective-and-low-impedance-grounding-for-power-systems/# 4/6
11/15/22, 8:02 AM How to Calculate Effective and Low-impedance Grounding for Power Systems - Technical Articles
Xₒ/X1 = 45%/15% = 3
Note: 60% of If3ɸ is the maximum ground-fault current for the system to be low-reactance grounded.
9. Find the reactance of a neutral grounding reactor to limit the line-to-ground fault current to 25% of the three-phase fault
current.
If1ɸ = 3∙I0 = 0.25∙If3ɸ = 0.25∙87.48 kA = 21.87 kA = 38.106 kV/(0.3388 + 3∙XN) Ω => XN = 0.4679 Ω
10. Find the ratio Xₒ/X1 with the neutral grounding reactor of question 9.
X0 = 5% + 145% = 150%
Xₒ/X1 = 150%/15% = 10
Note: To control transient overvoltages, the ground-fault current with a reactor should not be less than 25% of the three-
phase fault current
11. Find the resistance of a neutral grounding resistor to limit the line-to-ground fault current to 100% of the three-phase
fault current.
If1ɸ = 3∙I0 = If3ɸ = 87.48∠ kA = 3∙VLN/j(X1 + X2 + X0) + 3∙RN = 38.106 kV/j(0.3388) + 3∙RN Ω
(RN)² = 0.00836 Ω²
12. Find the resistance of a neutral grounding resistor to limit the line-to-ground fault current to 400 A.
(RN)² = 1 008.32 Ω²
https://eepower.com/technical-articles/how-to-calculate-effective-and-low-impedance-grounding-for-power-systems/# 5/6
11/15/22, 8:02 AM How to Calculate Effective and Low-impedance Grounding for Power Systems - Technical Articles
Note: when the resistance value is significant compared with the system impedance, its value can be computed directly as
RN = VLN/If1ɸ.
https://eepower.com/technical-articles/how-to-calculate-effective-and-low-impedance-grounding-for-power-systems/# 6/6