0% found this document useful (0 votes)
50 views45 pages

Ls GMCNT

This document provides instructions for connecting LS ELECTRIC Co., Ltd. programmable logic controllers (PLCs) to a display unit. It describes the system configurations, connection methods, cable diagrams, and setup examples for various PLC models that support either RS-232C, RS-422 or RS-485 serial interfaces. Settings for communication between the display and PLCs are explained for common scenarios.

Uploaded by

peebin097
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
50 views45 pages

Ls GMCNT

This document provides instructions for connecting LS ELECTRIC Co., Ltd. programmable logic controllers (PLCs) to a display unit. It describes the system configurations, connection methods, cable diagrams, and setup examples for various PLC models that support either RS-232C, RS-422 or RS-485 serial interfaces. Settings for communication between the display and PLCs are explained for common scenarios.

Uploaded by

peebin097
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 45

LS ELECTRIC Co., Ltd.

GLOFA Series
Cnet Driver

1 System Configuration....................................................................................................... 3
2 Selection of External Device ............................................................................................ 8
3 Example of Communication Setting ................................................................................. 9
4 Setup Items .................................................................................................................... 25
5 Cable Diagram ............................................................................................................... 30
6 Supported Device........................................................................................................... 43
7 Device Code and Address Code.................................................................................... 44
8 Error Messages.............................................................................................................. 45

1
GLOFA Series Cnet Driver

Introduction
This manual describes how to connect the Display and the External Device (target PLC).
In this manual, the connection procedure will be described by following the below sections:

1 System Configuration
)"1 System Configuration" (page 3)
This section shows the types of External
Devices which can be connected and SIO
type.

2 Selection of External Device


)"2 Selection of External Device" (page 8)
Select a model (series) of the External
Device to be connected and connection
method.

3 Example of Communication Settings


)"3 Example of Communication Setting"
This section shows setting examples for
(page 9)
communicating between the Display and
the External Device.

4 Setup Items
)"4 Setup Items" (page 25)
This section describes communication
setup items on the Display.
Set communication settings of the Display
with GP-Pro Ex or in offline mode.

5 Cable Diagram
)"5 Cable Diagram" (page 30)
This section shows cables and adapters
for connecting the Display and the
External Device.

Operation

GP-Pro EX Device/PLC Connection Manual 2


GLOFA Series Cnet Driver

1 System Configuration

The system configuration in the case when the External Device of LS ELECTRIC Co., Ltd. and the Display are
connected is shown.

Setting Cable
Series CPU Link I/F SIO Type
Example Diagram

GM1-CPUA "Setting Example 1" "Cable Diagram 1"


CH1 on G3L-CUEA RS232C
GM1-CPUB (page 9) (page 30)
GM1/2
GM2-CPUA RS422/485 "Setting Example 2" "Cable Diagram 2"
GM2-CPUB CH2 on G3L-CUEA
(4 wire) (page 11) (page 33)
"Setting Example 1" "Cable Diagram 1"
CH1 on G3L-CUEA RS232C
(page 9) (page 30)
GM3 GM3-CPUA
RS422/485 "Setting Example 2" "Cable Diagram 2"
CH2 on G3L-CUEA
(4 wire) (page 11) (page 33)
"Setting Example 1" "Cable Diagram 1"
GM4-CPUA CH1 on G4L-CUEA RS232C
(page 9) (page 30)
GM4 GM4-CPUB
GM4-CPUC RS422/485 "Setting Example 2" "Cable Diagram 2"
CH2 on G4L-CUEA
(4 wire) (page 11) (page 33)
"Setting Example 3" "Cable Diagram 3"
Port on CPU unit RS232C
(page 13) (page 41)
GM6-CPUA "Setting Example 1" "Cable Diagram 1"
G6L-CUEB RS232C
GM6-CPUC (page 9) (page 30)
RS422/485 "Setting Example 2" "Cable Diagram 2"
G6L-CUEC
(4 wire) (page 11) (page 33)
GM6
RS422/485 "Setting Example 4" "Cable Diagram 2"
CH1 on CPU unit
(4 wire) (page 15) (page 33)
"Setting Example 1" "Cable Diagram 1"
GM6-CPUB G6L-CUEB RS232C
(page 9) (page 30)
RS422/485 "Setting Example 2" "Cable Diagram 2"
G6L-CUEC
(4 wire) (page 11) (page 33)
G7M-DR10A(/DC)
"Setting Example 5" "Cable Diagram 3"
G7M-DR20A(/DC) Port on CPU unit RS232C
(page 17) (page 41)
G7M-DR30A(/DC)
G7M-DR40A(/DC)
G7M-DR60A(/DC) "Setting Example 5" "Cable Diagram 1"
GM7 G7L-CUEB RS232C
G7M-DT10A (page 17) (page 30)
G7M-DT20A
G7M-DT30A
RS422/485 "Setting Example 6" "Cable Diagram 2"
G7M-DT40A G7L-CUEC
(4 wire) (page 19) (page 33)
G7M-DT60A

GP-Pro EX Device/PLC Connection Manual 3


GLOFA Series Cnet Driver

Setting Cable
Series CPU Link I/F SIO Type
Example Diagram
G7M-DR20U(/DC)
G7M-DR30U(/DC)
"Setting Example 7" "Cable Diagram 3"
G7M-DR40U(/DC) Ch0 on CPU unit RS232C
(page 21) (page 41)
G7M-DR60U(/DC)
G7M-DRT20U(/DC)
G7M-DRT30U(/DC)
G7M-DRT40U(/DC)
G7M-DRT60U(/DC) "Setting Example 7" "Cable Diagram 1"
GM7U G7L-CUEB RS232C
G7M-DT20U(N)(/DC) (page 21) (page 30)
G7M-DT30U(N)(/DC)
G7M-DT40U(N)(/DC)
G7M-DT60U(N)(/DC)
G7M-DT20U(P)(/DC)
RS422/485 "Setting Example 8" "Cable Diagram 2"
G7M-DT30U(P)(/DC) G7L-CUEC
(4 wire) (page 23) (page 33)
G7M-DT40U(P)(/DC)
G7M-DT60U(P)(/DC)

„ Connection Configuration
• 1:1 Connection

External Device
Display

• 1:n Connection

External Device External Device External Device

Display The max number of Display: 16

GP-Pro EX Device/PLC Connection Manual 4


GLOFA Series Cnet Driver

„ IPC COM Port


When connecting IPC with an External Device, the COM port used depends on the series and SIO type. Please
refer to the IPC manual for details.

Usable port

Usable Port
Series
RS-232C RS-422/485(4 wire) RS-422/485(2 wire)
COM1*1 , COM2,
PS-2000B - -
COM3*1, COM4
PS-3450A, PS-3451A,
COM1, COM2*1*2 COM2*1*2 COM2*1*2
PS3000-BA, PS3001-BD
PS-3650A (T41 model),
COM1*1 - -
PS-3651A (T41 model)
PS-3650A (T42 model),
COM1*1*2, COM2 COM1*1*2 COM1*1*2
PS-3651A (T42 model)
PS-3700A (Pentium®4-M) COM1*1, COM2*1,
COM3*2 COM3*2
PS-3710A COM3*2 , COM4
PS-3711A COM1*1, COM2*2 COM2*2 COM2*2
PS4000*3 COM1, COM2 - -
COM1*1*2, COM2*1,
PL3000 COM1*1*2 COM1*1*2
COM3, COM4
PE-4000B Atom N270 COM1, COM2 - -
*4 COM4*4, COM3*4, COM4*4,
COM3 ,
PE-4000B Atom N2600 COM1, COM2
COM5*4, COM6*4 COM5*4, COM6*4
PS5000 (Slim Panel Type
COM1, COM2*4 COM2*4 COM2*4
Core i3 Model) *5 *6
PS5000 (Slim Panel Type
Atom Model) COM1, COM2*7 COM2*7 COM2*7
*5 *6

PS5000 (Enclosed Panel


COM1 - -
Type)*8
PS5000 (Modular Type
PFXPU/PFXPP)*5 *6
COM1*7 COM1*7 COM1*7
PS5000 (Modular Type
PFXPL2B5-6)
PS5000 (Modular Type
COM1, COM2*7 COM2*7 COM2*7
PFXPL2B1-4)
PS6000 COM1*9 *10 *10

*1 The RI/5V can be switched. Use the IPC’s switch to change if necessary.
*2 Set up the SIO type with the DIP Switch. Please set up as follows according to SIO type to be used.
*3 When making communication between an External Device and COM port on the Expansion slot,
only RS-232C is supported. However, ER (DTR/CTS) control cannot be executed because of the
specification of COM port.
For connection with External Device, use user-created cables and disable Pin Nos. 1, 4, 6 and 9.
Please refer to the IPC manual for details of pin layout.
*4 Set up the SIO type with the BIOS. Please refer to the IPC manual for details of BIOS.

GP-Pro EX Device/PLC Connection Manual 5


GLOFA Series Cnet Driver

*5 When setting up communication between an External Device and the RS-232C/422/485 interface
module, use the IPC (RS-232C) or PS5000 (RS-422/485) cable diagrams. However, when using
PFXZPBMPR42P2 in a RS-422/485 (4-wire) configuration with no flow control, connect 7.RTS+
and 8.CTS+, and connect 6.RTS- and 9.CTS-.
When using RS-422/485 communication with External Devices, you may need to reduce the
transmission speed and increase the TX Wait time.
*6 To use RS-422/485 communication on the RS-232C/422/485 interface module, the DIP Switch
setting is required. Please refer to "Knowledge Base" (FAQs) on the support site. (http://www.pro-
face.com/trans/en/manual/1001.html)

Settings FAQ ID
PFXZPBMPR42P2, RS422/485 change method FA263858
PFXZPBMPR42P2 termination resistor setting FA263974
PFXZPBMPR44P2, RS422/485 change method FA264087
PFXZPBMPR44P2 termination resistor setting FA264088

*7 Set up the SIO type with the DIP Switch. Please refer to the IPC manual for details of DIP Switch.
The BOX Atom has not a switch to set the RS-232C, RS-422/485 mode. Use the BIOS for the
setting.
*8 For the connection with the External Device, on the user-created cable read as if the connector on
the Display-side is a M12 A-coding 8 pin socket. The pin assignment is the same as described in
the cable diagram. For the M12 A-coding connector, use PFXZPSCNM122.
*9 In addition to COM1, you can also use the RS-232C COM port on the optional interface.
*10 Install the optional interface in the expansion slot.

DIP Switch settings (PL3000 / PS3000 Series)


RS-232C

DIP Switch Setting Description


1 OFF*1 Reserved (always OFF)
2 OFF
SIO type: RS-232C
3 OFF
4 OFF Output mode of SD (TXD) data: Always output
5 OFF Terminal resistance (220Ω) insertion to SD (TXD): None
6 OFF Terminal resistance (220Ω) insertion to RD (RXD): None
7 OFF Short-circuit of SDA (TXA) and RDA (RXA): Not available
8 OFF Short-circuit of SDB (TXB) and RDB (RXB): Not available
9 OFF
RS (RTS) Auto control mode: Disabled
10 OFF
*1 When using PS-3450A, PS-3451A, PS3000-BA and PS3001-BD, turn ON the set value.

GP-Pro EX Device/PLC Connection Manual 6


GLOFA Series Cnet Driver

RS-422/485 (4 wire)

DIP Switch Setting Description


1 OFF Reserved (always OFF)
2 ON
SIO type: RS-422/485
3 ON
4 OFF Output mode of SD (TXD) data: Always output
5 OFF Terminal resistance (220Ω) insertion to SD (TXD): None
6 OFF Terminal resistance (220Ω) insertion to RD (RXD): None
7 OFF Short-circuit of SDA (TXA) and RDA (RXA): Not available
8 OFF Short-circuit of SDB (TXB) and RDB (RXB): Not available
9 OFF
RS (RTS) Auto control mode: Disabled
10 OFF

RS-422/485 (2 wire)

DIP Switch Setting Description


1 OFF Reserved (always OFF)
2 ON
SIO type: RS-422/485
3 ON
4 OFF Output mode of SD (TXD) data: Always output
5 OFF Terminal resistance (220Ω) insertion to SD (TXD): None
6 OFF Terminal resistance (220Ω) insertion to RD (RXD): None
7 ON Short-circuit of SDA (TXA) and RDA (RXA): Available
8 ON Short-circuit of SDB (TXB) and RDB (RXB): Available
9 ON
RS (RTS) Auto control mode: Enabled
10 ON

GP-Pro EX Device/PLC Connection Manual 7


GLOFA Series Cnet Driver

2 Selection of External Device

Select the External Device to be connected to the Display.

Setup Items Setup Description


Number of Devices/
Enter an integer from 1 to 4 to define the number of Devices/PLCs to connect to the display.
PLCs
Manufacturer Select the manufacturer of the External Device to connect. Select "LS ELECTRIC Co., Ltd.".
Select the External Device model (series) and the connection method. Select "GLOFA Series
Cnet".
Series In System configuration, make sure the External Device you are connecting is supported by
"GLOFA Series Cnet".
) "1 System Configuration" (page 3)
Port Select the Display port to connect to the External Device.
Check this option to synchronize the system data area of the Display and the device (memory)
of the External Device. When synchronized, you can use the External Device’s ladder program
to switch the display or display the window on the Display.
Cf. GP-Pro EX Reference Manual "LS Area (Direct Access Method Area)"
Use System Area
This feature can also be set in GP-Pro EX or in the Display's offline mode.
Cf. GP-Pro EX Reference Manual "System Settings [Display Unit] - [System Area]
Settings Guide"
Cf. Maintenance/Troubleshooting Guide "Main Unit - System Area Settings"

GP-Pro EX Device/PLC Connection Manual 8


GLOFA Series Cnet Driver

3 Example of Communication Setting

The following shows examples of communication settings of the Display and the External Device, which is
recommended by Pro-face.

3.1 Setting Example 1


„ Settings of GP-Pro EX
‹ Communication Settings
To display the setup screen, from the [Project] menu, point to [System Settings] and select [Device/PLC].

‹ Device Setting
To display the [Individual Device Settings] dialog box, from [Device-Specific Settings] in the [Device/PLC]
window, select the external device and click [Settings] .
To connect multiple External Devices, from [Device-Specific Settings] in the [Device/PLC] window, click [Add
Device] to add another External Device.

GP-Pro EX Device/PLC Connection Manual 9


GLOFA Series Cnet Driver

„ Settings of External Device


Use the mode switch on the link I/F and the setting tool (Cnet Frame Editor) to configure communication settings
for the External Device.
Refer to your External Device manual for details.

‹ Mode Switch
• When using G6L-CUEB/G6L-CUEC.

Rotary Switch Setting Description


1 Dedicated

• When using G3L-CUEA/G4L-CUEA.

Rotary Switch Setting Description


*1
1 Dedicated
*1 Set to 1, when using in the External Device
Interlocking mode.
Set to 3, when using in the External Device
Stand-alone mode.

‹ Setting Tool
1 Start up the setting tool.
2 Set [channel] and [Basic Parameters] setup items as follows.

Setup Item Setting Value


Channel RS232 side
Station 0
Type Null Modem
Baud Rate 38400
Data Bit 8
Parity None
Stop Bit 1
Monitor Entry 16x20

3 Transfer the setting contents to External Device.

GP-Pro EX Device/PLC Connection Manual 10


GLOFA Series Cnet Driver

3.2 Setting Example 2


„ Settings of GP-Pro EX
‹ Communication Settings
To display the setup screen, from the [Project] menu, point to [System Settings] and select [Device/PLC].

‹ Device Setting
To display the [Individual Device Settings] dialog box, from [Device-Specific Settings] in the [Device/PLC]
window, select the external device and click [Settings] .
To connect multiple External Devices, from [Device-Specific Settings] in the [Device/PLC] window, click [Add
Device] to add another External Device.

GP-Pro EX Device/PLC Connection Manual 11


GLOFA Series Cnet Driver

„ Settings of External Device


Use the mode switch on the link I/F and the setting tool (Cnet Frame Editor) to configure communication settings
for the External Device.
Refer to your External Device manual for details.

‹ Mode Switch
• When using G6L-CUEB/G6L-CUEC.

Rotary Switch Setting Description


1 Dedicated

• When using G3L-CUEA/G4L-CUEA.

Rotary Switch Setting Description


*1
1 Dedicated
*1 Set to 1, when using in the External Device
Interlocking mode.
Set to 3, when using in the External Device
Stand-alone mode.

‹ Setting Tool
1 Start up the setting tool.
2 Set [channel] and [Basic Parameters] setup items as follows.

Setup Item Setting Value


Channel RS422 side
Station 0
Type Null Modem
Baud Rate 38400
Data Bit 8
Parity None
Stop Bit 1
Monitor Entry 16x20

3 Transfer the setting contents to External Device.

GP-Pro EX Device/PLC Connection Manual 12


GLOFA Series Cnet Driver

3.3 Setting Example 3


„ Settings of GP-Pro EX
‹ Communication Settings
To display the setup screen, from the [Project] menu, point to [System Settings] and select [Device/PLC].

‹ Device Setting
To display the [Individual Device Settings] dialog box, from [Device-Specific Settings] in the [Device/PLC]
window, select the external device and click [Settings] .
To connect multiple External Devices, from [Device-Specific Settings] in the [Device/PLC] window, click [Add
Device] to add another External Device.

GP-Pro EX Device/PLC Connection Manual 13


GLOFA Series Cnet Driver

„ Settings of External Device


Use the ladder software (GMWIN) to configure communication settings for the External Device.
Refer to your External Device manual for details.

1 Start up the ladder software.


2 Create the project. Select the using External Device.
3 Select [Basic Parameters] from [Parameter] tab of tree view.
4 Set the setting items as below in the displayed dialog box.

Setup Item Setting Value


Station number 0
Baud rate 38400
Master/Slave Slave

GP-Pro EX Device/PLC Connection Manual 14


GLOFA Series Cnet Driver

3.4 Setting Example 4


„ Settings of GP-Pro EX
‹ Communication Settings
To display the setup screen, from the [Project] menu, point to [System Settings] and select [Device/PLC].

‹ Device Setting
To display the [Individual Device Settings] dialog box, from [Device-Specific Settings] in the [Device/PLC]
window, select the external device and click [Settings] .
To connect multiple External Devices, from [Device-Specific Settings] in the [Device/PLC] window, click [Add
Device] to add another External Device.

GP-Pro EX Device/PLC Connection Manual 15


GLOFA Series Cnet Driver

„ Settings of External Device


Use the ladder software (GMWIN) to configure communication settings for the External Device.
Refer to your External Device manual for details.

1 Start up the ladder software.


2 Create the project. Select the using External Device.
3 Select [Basic Parameters] from [Parameter] tab of tree view.
4 Set the setting items as below in the displayed dialog box.

Setup Item Setting Value


Station number 0
Baud rate 38400
Master/Slave Slave

GP-Pro EX Device/PLC Connection Manual 16


GLOFA Series Cnet Driver

3.5 Setting Example 5


„ Settings of GP-Pro EX
‹ Communication Settings
To display the setup screen, from the [Project] menu, point to [System Settings] and select [Device/PLC].

‹ Device Setting
To display the [Individual Device Settings] dialog box, from [Device-Specific Settings] in the [Device/PLC]
window, select the external device and click [Settings] .
To connect multiple External Devices, from [Device-Specific Settings] in the [Device/PLC] window, click [Add
Device] to add another External Device.

GP-Pro EX Device/PLC Connection Manual 17


GLOFA Series Cnet Driver

„ Settings of External Device


Use the dip switch on the CPU and the ladder software (GMWIN) to configure communication settings for the
External Device.
Refer to your External Device manual for details.

‹ Dip Switch

Dip Switch Setting Value


BUILTIN CNET ON

• Turn OFF the BUILTIN CNET switch, when using the Cnet port on G7L-CUEB.

‹ Ladder Software
1 Start up the ladder software.
2 Create the project. Select the using External Device.
3 Select [Communication Parameters] from [Parameter] tab of tree view.
4 Set the setting items as below in the displayed dialog box.

Setup Item Setting Value


Station No. 0
Baud rate 38400
Data bit 8
Parity bit None
Stop bit 1
RS232C Null Modem or
Communication channel
RS422/485
Dedicated Slave

GP-Pro EX Device/PLC Connection Manual 18


GLOFA Series Cnet Driver

3.6 Setting Example 6


„ Settings of GP-Pro EX
‹ Communication Settings
To display the setup screen, from the [Project] menu, point to [System Settings] and select [Device/PLC].

‹ Device Setting
To display the [Individual Device Settings] dialog box, from [Device-Specific Settings] in the [Device/PLC]
window, select the external device and click [Settings] .
To connect multiple External Devices, from [Device-Specific Settings] in the [Device/PLC] window, click [Add
Device] to add another External Device.

GP-Pro EX Device/PLC Connection Manual 19


GLOFA Series Cnet Driver

„ Settings of External Device


Use the dip switch on the CPU and the ladder software (GMWIN) to configure communication settings for the
External Device.
Refer to your External Device manual for details.

‹ Dip Switch

Dip Switch Setting Value


BUILTIN CNET OFF

‹ Ladder Software
1 Start up the ladder software.
2 Create the project. Select the using External Device.
3 Select [Communication Parameters] from [Parameter] tab of tree view.
4 Set the setting items as below in the displayed dialog box.

Setup Item Setting Value


Station No. 0
Baud rate 38400
Data bit 8
Parity bit None
Stop bit 1
RS232C Null Modem or
Communication channel
RS422/485
Dedicated Slave

GP-Pro EX Device/PLC Connection Manual 20


GLOFA Series Cnet Driver

3.7 Setting Example 7


„ Settings of GP-Pro EX
‹ Communication Settings
To display the setup screen, from the [Project] menu, point to [System Settings] and select [Device/PLC].

‹ Device Setting
To display the [Individual Device Settings] dialog box, from [Device-Specific Settings] in the [Device/PLC]
window, select the external device and click [Settings] .
To connect multiple External Devices, from [Device-Specific Settings] in the [Device/PLC] window, click [Add
Device] to add another External Device.

GP-Pro EX Device/PLC Connection Manual 21


GLOFA Series Cnet Driver

„ Settings of External Device


Use the dip switch on the CPU and the ladder software (GMWIN) to configure communication settings for the
External Device.
Refer to your External Device manual for details.

‹ Dip Switch

Dip Switch Setting Value


BUILTIN CNET ON

• Turn OFF the BUILTIN CNET switch, when using the Cnet port on G7L-CUEB.

‹ Ladder Software
1 Start up the ladder software.
2 Create the project. Select the using External Device.
3 Select [Communication Parameters] from [Parameter] tab of tree view.
4 Select [Channel 0] in [Communication Parameter Selection] dialog box.
5 Set the setting items as below in the displayed dialog box.

Setup Item Setting Value


Station No. 0
Baud rate 38400
Data bit 8
Parity bit None
Stop bit 1
RS232C Null Modem or
Communication channel
RS422/485
Dedicated Slave

GP-Pro EX Device/PLC Connection Manual 22


GLOFA Series Cnet Driver

3.8 Setting Example 8


„ Settings of GP-Pro EX
‹ Communication Settings
To display the setup screen, from the [Project] menu, point to [System Settings] and select [Device/PLC].

‹ Device Setting
To display the [Individual Device Settings] dialog box, from [Device-Specific Settings] in the [Device/PLC]
window, select the external device and click [Settings] .
To connect multiple External Devices, from [Device-Specific Settings] in the [Device/PLC] window, click [Add
Device] to add another External Device.

GP-Pro EX Device/PLC Connection Manual 23


GLOFA Series Cnet Driver

„ Settings of External Device


Use the dip switch on the CPU and the ladder software (GMWIN) to configure communication settings for the
External Device.
Refer to your External Device manual for details.

‹ Dip Switch

Dip Switch Setting Value


BUILTIN CNET OFF

‹ Ladder Software
1 Start up the ladder software.
2 Create the project. Select the using External Device.
3 Select [Communication Parameters] from [Parameter] tab of tree view.
4 Select [Channel 0] in [Communication Parameter Selection] dialog box.
5 Set the setting items as below in the displayed dialog box.

Setup Item Setting Value


Station No. 0
Baud rate 38400
Data bit 8
Parity bit None
Stop bit 1
RS232C Null Modem or
Communication channel
RS422/485
Dedicated Slave

GP-Pro EX Device/PLC Connection Manual 24


GLOFA Series Cnet Driver

4 Setup Items

Set communication settings of the Display with GP-Pro EX or in offline mode of the Display.
The setting of each parameter must be identical to that of External Device.
)"3 Example of Communication Setting" (page 9)
4.1 Setup Items in GP-Pro EX
„ Communication Settings
To display the setup screen, from the [Project] menu, point to [System Settings] and select [Device/PLC].

Setup Items Setup Description


SIO Type Select the SIO type to communicate with the External Device.
Speed Select speed between the External Device and the Display.
Data Length Select data length.
Parity Select how to check parity.
Stop Bit Select stop bit length.
Display the communication control method to prevent overflow of transmission and
Flow Control
reception data.
Use an integer from 1 to 127 to enter the time (s) for which the Display waits for the
Timeout
response from the External Device.
In case of no response from the External Device, use an integer from 0 to 255 to enter how
Retry
many times the Display retransmits the command.
Use an integer from 0 to 255 to enter standby time (ms) for the Display from receiving
Wait To Send
packets to transmitting next commands.

GP-Pro EX Device/PLC Connection Manual 25


GLOFA Series Cnet Driver

Setup Items Setup Description


You can switch RI/VCC of the 9th pin when you select RS232C for SIO type.
RI/VCC It is necessary to change RI/5V by changeover switch of IPC when connect with IPC.
Please refer to the manual of the IPC for more detail.

• Refer to the GP-Pro EX Reference Manual for Indirect Device.

Cf. GP-Pro EX Reference Manual "Changing the Device/PLC at Runtime (Indirect


Device)"

„ Device Setting
To display the [Individual Device Settings] dialog box, from [Device-Specific Settings] in the [Device/PLC]
window, select the external device and click [Settings] .
To connect multiple External Devices, from [Device-Specific Settings] in the [Device/PLC] window, click [Add
Device] to add another External Device.

Setup Items Setup Description


BCC BCC of the External Device is set to "Enable / Disable". (Initial value [Enable])
Use an integer from 0 to 31 to enter the Station No. of the External Device. (Initial value
Station No.
[0])
When the Cnet I/F module is Ver.1.4 or later, select the check box. (Initial value: Check
Cnet I/F module Ver.
box is selected.)
1.4 or later
To check the Cnet I/F module version, look at the labels on the module.

GP-Pro EX Device/PLC Connection Manual 26


GLOFA Series Cnet Driver

4.2 Setup Items in Offline Mode

• Refer to the Maintenance/Troubleshooting guide for information on how to enter offline mode
or about the operation.

Cf. Maintenance/Troubleshooting Guide "Offline Mode"

• The number of the setup items to be displayed for 1 page in the offline mode depends on the
Display in use. Please refer to the Reference manual for details.

„ Communication Settings
To display the setting screen, touch [Device/PLC Settings] from [Peripheral Settings] in offline mode. Touch the
External Device you want to set from the displayed list.

Setup Items Setup Description


Select the SIO type to communicate with the External Device.

To make the communication settings correctly, confirm the serial interface specifications of
SIO Type Display unit for [SIO Type].
We cannot guarantee the operation if a communication type that the serial interface does not
support is specified.
For details concerning the serial interface specifications, refer to the manual for Display
unit.
Speed Select speed between the External Device and the Display.
Data Length Select data length.
Parity Select how to check parity.
Stop Bit Select stop bit length.
Display the communication control method to prevent overflow of transmission and
Flow Control
reception data.

GP-Pro EX Device/PLC Connection Manual 27


GLOFA Series Cnet Driver

Setup Items Setup Description


Use an integer from 1 to 127 to enter the time (s) for which the Display waits for the
Timeout (s)
response from the External Device.
In case of no response from the External Device, use an integer from 0 to 255 to enter how
Retry
many times the Display retransmits the command.
Use an integer from 0 to 255 to enter standby time (ms) for the Display from receiving
Wait To Send (ms)
packets to transmitting next commands.

„ Device Setting
To display the setting screen, touch [Device/PLC Settings] from [Peripheral Equipment Settings]. Touch the
External Device you want to set from the displayed list, and touch [Device].

Setup Items Setup Description


Select the External Device to set. The device name is set up in GP-Pro EX. (Initial value
Device/PLC name
[PLC1])
BCC BCC of the External Device is set to "Enable / Disable". (Initial value [Enable])
Use an integer from 0 to 31 to enter the Station No. of the External Device. (Initial value
Station No.
[0])
Cnet I/F module Ver. When the Cnet I/F module is Ver.1.4 or later, select "Enable". (Initial value [Enable])
1.4 or later To check the Cnet I/F module version, look at the labels on the module.

GP-Pro EX Device/PLC Connection Manual 28


GLOFA Series Cnet Driver

„ Option
To display the setting screen, touch [Device/PLC Settings] from [Peripheral Equipment Settings]. Touch the
External Device you want to set from the displayed list, and touch [Option].

Setup Items Setup Description


Switches RI/VCC of the 9th pin.
RI/VCC It is necessary to change RI/5V by changeover switch of IPC when connect with IPC.
Please refer to the manual of the IPC for more detail.

• GP-4100 series, GP-4*01TM, GP-Rear Module, LT-4*01TM and LT-Rear Module do not
have the [Option] setting in the offline mode.

GP-Pro EX Device/PLC Connection Manual 29


GLOFA Series Cnet Driver

5 Cable Diagram

The cable diagram shown below may be different from the cable diagram recommended by LS ELECTRIC Co.,
Ltd. Please be assured there is no operational problem in applying the cable diagram shown in this manual.
• The FG pin of the External Device body must be D-class grounded. Please refer to the manual of the External
Device for more details.
• SG and FG are connected inside the Display. When connecting SG to the External Device, design the system
not to form short-circuit loop.
• Connect the isolation unit, when communication is not stabilized under the influence of a noise etc.

Cable Diagram 1

Display
Cable Notes
(Connection Port)
GP3000 (COM1)
GP4000*1 (COM1)
SP5000*2 (COM1/2)
SP-5B00 (COM1)
ST3000 (COM1)
1A User-created cable Cable length: 15m or less
ST6000 (COM1)
STM6000 (COM1)
LT3000 (COM1)
IPC*3
PC/AT
GP-4105 (COM1)
GP-4115T (COM1) 1B User-created cable Cable length: 15m or less
GP-4115T3 (COM1)
LT-4*01TM (COM1) RJ45 RS-232C Cable (5m) by Pro-face
LT-Rear Module (COM1) 1C PFXZLMCBRJR21 Cable length: 5m or less

*1 All GP4000 models except GP-4100 Series and GP-4203T


*2 Except SP-5B00
*3 Only the COM port which can communicate by RS-232C can be used.
) "„ IPC COM Port" (page 5)

GP-Pro EX Device/PLC Connection Manual 30


GLOFA Series Cnet Driver

1A)
Display side External Device side
D-Sub 9pin (socket) Shield D-Sub 9pin (plug)
Pin Signal name Pin Signal name
Display
1 CD 1 CD
2 RD(RXD) 3 TxD
3 SD(TXD) 2 RxD
4 ER(DTR) 4 DTR
5 SG 5 SG
6 DR(DSR) 6 DSR
7 RS(RTS) 7 RTS
8 CS(CTS) 8 CTS
Shell

1B)

Display side External Device side


Terminal block Shield D-Sub 9pin (plug)
Signal name Pin Signal name
SD(TXD) 2 RxD
Display RD(RXD) 3 TxD
ER(DTR) 1 CD
DR(DSR) 4 DTR
SG 5 SG
RS(RTS) 6 DSR
CS(CTS) 7 RTS
CD 8 CTS
CI Shell

GP-Pro EX Device/PLC Connection Manual 31


GLOFA Series Cnet Driver

1C)

External Device side


D-Sub 9pin (plug)
Pin Signal name
1 CD
Display RXD
3 TxD
TXD
2 RxD
(1) 4 DTR
5 SG
GND
6 DSR
7 RTS
8 CTS
Shell

Number Name Notes

RJ45 RS-232C Cable (5m) by Pro-face


(1) PFXZLMCBRJR21

GP-Pro EX Device/PLC Connection Manual 32


GLOFA Series Cnet Driver

Cable Diagram 2

Display
Cable Notes
(Connection Port)
COM port conversion adapter by Pro-face
GP3000*1 (COM1) CA3-ADPCOM-01
AGP-3302B (COM2) +
GP-4*01TM (COM1) 2A Terminal block conversion adapter by Pro-face Cable length:
GP-Rear Module (COM1) CA3-ADPTRM-01 500m or less
ST3000*2 (COM2) +
LT3000 (COM1) User-created cable
IPC*3
2B User-created cable
Online adapter by Pro-face
CA4-ADPONL-01
+
2C Terminal block conversion adapter by Pro-face
CA3-ADPTRM-01
+ Cable length:
GP3000*4 (COM2)
User-created cable 500m or less

Online adapter by Pro-face


CA4-ADPONL-01
2D
+
User-created cable
GP-4106 (COM1) Cable length:
2E User-created cable
GP-4116T (COM1) 500m or less
GP4000*5 (COM2) RS-422 Terminal Block Conversion Adapter by Pro-face
GP-4201T (COM1) PFXZCBADTM1*8
2F
SP5000*6 (COM1/2) +
SP-5B00 (COM2) User-created cable Cable length:
ST6000*7 (COM2) 500m or less
ST-6200 (COM1)
STM6000 (COM1) 2B User-created cable

PE-4000B*9
Cable length:
PS5000*9 2G User-created cable
500m or less
PS6000*9
*1 All GP3000 models except AGP-3302B
*2 Except AST-3211A and AST-3302B
*3 Only the COM port which can communicate by RS-422/485 (4 wire) can be used. (Except PE-4000B, PS5000,
and PS6000)
) "„ IPC COM Port" (page 5)
*4 All GP3000 models except GP-3200 series and AGP-3302B
*5 All GP4000 models except GP-4100 Series, GP-4*01TM, GP-Rear Module, GP-4201T and GP-4*03T
*6 Except SP-5B00
*7 Except ST-6200
*8 When using a Terminal Block Conversion Adapter (CA3-ADPTRM-01) instead of the RS-422 Terminal Block
Conversion Adapter, refer to Cable Diagram 2A.
*9 Only the COM port which can communicate by RS-422/485 (4 wire) can be used.
) "„ IPC COM Port" (page 5)

GP-Pro EX Device/PLC Connection Manual 33


GLOFA Series Cnet Driver

2A)
• 1:1 Connection
Display side
Terminal Terminal block External Device
resistance Signal name Shield Signal name
120 Ω (1/2W)
SDA RDA Terminal
resistance
Display
CA3-ADPCOM-01 SDB RDB 120 Ω (1/2W)
RDA SDA Terminal
resistance
RDB SDB 120 Ω (1/2W)
CA3-ADPTRM-01
TERM SG
SG FG

User-created cable

• 1:n Connection
Display side External Device External Device
Terminal Terminal block No.1 No.n
resistance Signal name Shield Signal name Shield Signal name
120 Ω (1/2W)
SDA RDA RDA Terminal
resistance
Display
CA3-ADPCOM-01 SDB RDB RDB 120 Ω (1/2W)
RDA SDA SDA Terminal
resistance
RDB SDB SDB 120 Ω (1/2W)
CA3-ADPTRM-01
TERM SG SG
SG FG FG

User-created cable

GP-Pro EX Device/PLC Connection Manual 34


GLOFA Series Cnet Driver

2B)
• 1:1 Connection
Display side
D-Sub 9pin (socket) Shield External Device side
Pin Signal name Signal name
3 SDA RDA
Display
7 SDB RDB
1 RDA SDA
2 RDB SDB
5 SG SG
4 ERA FG
8 CSA
9 ERB
6 CSB

• 1:n Connection
Display side External Device External Device
D-Sub 9pin (socket) Shield No.1 Shield No.n
Pin Signal name Signal name Signal name
3 SDA RDA RDA
Display
7 SDB RDB RDB
1 RDA SDA SDA
2 RDB SDB SDB
5 SG SG SG
4 ERA FG FG
8 CSA
9 ERB
6 CSB

GP-Pro EX Device/PLC Connection Manual 35


GLOFA Series Cnet Driver

2C)
• 1:1 Connection
Display side
Terminal Terminal block External Device
resistance Signal name Shield Signal name
120 Ω (1/2W)
SDA RDA Terminal
resistance
Display
CA3-ADPONL-01 SDB RDB 120 Ω (1/2W)
RDA SDA Terminal
resistance
RDB SDB 120 Ω (1/2W)
CA3-ADPTRM-01
TERM SG
SG FG

User-created cable

• 1:n Connection
Display side External Device External Device
Terminal Terminal block No.1 No.n
resistance Signal name Shield Signal name Shield Signal name
120 Ω (1/2W)
SDA RDA RDA Terminal
resistance
Display
CA3-ADPONL-01 SDB RDB RDB 120 Ω (1/2W)
RDA SDA SDA Terminal
resistance
RDB SDB SDB 120 Ω (1/2W)
CA3-ADPTRM-01
TERM SG SG
SG FG FG

User-created cable

GP-Pro EX Device/PLC Connection Manual 36


GLOFA Series Cnet Driver

2D)
• 1:1 Connection

Display side
D-Sub 9pin (plug) Shield
Pin Signal name External Device
9 TERMTX Signal name
Display
3 SDA RDA
8 SDB RDB

CA4-ADPONL-01 2 RDA SDA


7 RDB SDB
1 TERMRX SG
5 SG FG

User-created cable

• 1:n Connection
Display side
D-Sub 9pin (plug) Shield Shield
External Device External Device
Pin Signal name No.1 No.n
9 TERMTX Signal name Signal name
Display
3 SDA RDA RDA
8 SDB RDB RDB

CA4-ADPONL-01 2 RDA SDA SDA


7 RDB SDB SDB
1 TERMRX SG SG
5 SG FG FG

User-created cable

GP-Pro EX Device/PLC Connection Manual 37


GLOFA Series Cnet Driver

2E)
• 1:1 Connection
Display side
Terminal block Shield External Device

Termination Signal name Signal name


resistance*1
SDA RDA
Display
SDB RDB
RDA SDA
RDB SDB
Termination
resistance*1 SG SG
ERA FG
CSA
ERB
CSB

• 1:n Connection
Display side External Device External Device
Terminal block Shield No.1 Shield No.n
Termination Signal name Signal name Signal name
resistance*1
SDA RDA RDA
Display
SDB RDB RDB
RDA SDA SDA
RDB SDB SDB
Termination
resistance*1 SG SG SG
ERA FG FG
CSA
ERB
CSB

*1 The resistance in the Display is used as the termination resistance. Set the value of the DIP Switch on the
rear of the Display as shown in the table below.

DIP Switch No. Set Value


1 ON
2 ON
3 ON
4 ON

GP-Pro EX Device/PLC Connection Manual 38


GLOFA Series Cnet Driver

2F)
• 1:1 Connection
Display side
Terminal Terminal block External Device
resistance Signal name Shield Signal name
120 Ω (1/2W)
SDA RDA Terminal
resistance
Display
SDB RDB 120 Ω (1/2W)
RDA SDA Terminal
resistance
RDB SDB 120 Ω (1/2W)
PFXZCBADTM1
TERM SG
SG FG

User-created cable

• 1:n Connection
Display side External Device External Device
Terminal Terminal block No.1 No.n
resistance Signal name Shield Signal name Shield Signal name
120 Ω (1/2W)
SDA RDA RDA Terminal
resistance
Display
SDB RDB RDB 120 Ω (1/2W)
RDA SDA SDA Terminal
resistance
RDB SDB SDB 120 Ω (1/2W)
PFXZCBADTM1
TERM SG SG
SG FG FG

User-created cable

GP-Pro EX Device/PLC Connection Manual 39


GLOFA Series Cnet Driver

2G)
• 1:1 Connection
Display side
D-Sub 9pin (socket) Shield External Device side
Pin Signal name Signal name
2 Tx+ RDA
Display
1 Tx- RDB
3 Rx+ SDA
4 Rx- SDB
5 GND SG
7 NC FG
8 NC
9 NC
6 NC

• 1:n Connection

Display side External Device External Device


D-Sub 9pin (socket) Shield No.1 Shield No.n
Pin Signal name Signal name Signal name
2 Tx+ RDA RDA
Display
1 Tx- RDB RDB
3 Rx+ SDA SDA
4 Rx- SDB SDB
5 GND SG SG
7 NC FG FG
8 NC
9 NC
6 NC

GP-Pro EX Device/PLC Connection Manual 40


GLOFA Series Cnet Driver

Cable Diagram 3

Display
Cable Notes
(Connection Port)

GP3000 (COM1)
GP4000*1 (COM1)
SP5000*2 (COM1/2)
SP-5B00 (COM1)
ST3000 (COM1)
3A User-created cable Cable length: 15m or less
ST6000 (COM1)
STM6000 (COM1)
LT3000 (COM1)
IPC*3
PC/AT

GP-4105 (COM1)
GP-4115T (COM1) 3B User-created cable Cable length: 15m or less
GP-4115T3 (COM1)

LT-4*01TM (COM1)
RJ45 RS-232C Cable (5m) by Pro-face
LT-Rear Module
3C PFXZLMCBRJR21 Cable length: 5m or less
(COM1)

*1 All GP4000 models except GP-4100 Series and GP-4203T


*2 Except SP-5B00
*3 Only the COM port which can communicate by RS-232C can be used.
)"„ IPC COM Port" (page 5)

3A)
Display side External Device side
D-Sub 9pin (socket) Shield D-Sub 9pin (plug)
Pin Signal name Pin Signal name
2 RD(RXD) 7 TxD2
Display
3 SD(TXD) 4 RxD2
4 ER(DTR) 5 SG
5 SG Shell
6 DR(DSR)
7 RS(RTS)
8 CS(CTS)

User-created cable

GP-Pro EX Device/PLC Connection Manual 41


GLOFA Series Cnet Driver

3B)
Display side External Device side
Terminal Block Shield D-Sub 9pin (plug)
Signal name Pin Signal name
RD(RXD) 7 TxD2
Display
SD(TXD) 4 RxD2
ER(DTR) 5 SG
SG Shell
DR(DSR)
RS(RTS)
CS(CTS)

User-created cable

3C)
External Device side
D-Sub 9pin (plug)
Pin Signal name
Display RXD
7 TxD2
TXD
4 RxD2
(1) GND
5 SG
Shell

Number Name Notes

RJ45 RS-232C Cable (5m) by Pro-face


(1) PFXZLMCBRJR21

GP-Pro EX Device/PLC Connection Manual 42


GLOFA Series Cnet Driver

6 Supported Device

Range of supported device address is shown in the table below.

This address can be specified as system data area.

Device Bit Address Word Address 32bits Notes


*1
Input Points %IX0.0.0 - %IX9.7.63 %IW0.0.0 - %IW9.7.3
Output Points %QX0.0.0 - %QX9.7.63 %QW0.0.0 - %QW9.7.3 *1

Data Memory %MX000000 - %MX524287 %MW00000 - %MW32767


*1 Device explanation:
%IX 0 . 0 . 0 %QW 0 . 0 . 0
Module Contact Number (0 to 63) Module Word Number (0 to 3)
Slot Number (0 to 7) Slot Number (0 to 7)
Base Number (0 to 9) Base Number (0 to 9)
Device Name (I: Input, X: Bit Size) Device Name (Q: Output, W: 16 Bit Size)

• Please note that the actually supported range of the devices varies depending on the External
Device to be used. Please check the actual range in the manual of your External Device.
• Please refer to the GP-Pro EX Reference Manual for system data area.
Cf. GP-Pro EX Reference Manual "LS Area (Direct Access Method Area)"
• Please refer to the precautions on manual notation for icons in the table.

) "Manual Symbols and Terminology"

GP-Pro EX Device/PLC Connection Manual 43


GLOFA Series Cnet Driver

7 Device Code and Address Code

Use device code and address code when you select "Device Type & Address" for the address type in data displays.

Device Device Code


Device Address Code
Name (HEX)
%IX
Input Points 0080 Word Address
%IW
%QX
Output Points 0081 Word Address
%QW
%MX
Data Memory 0082 Word Address
%MW

GP-Pro EX Device/PLC Connection Manual 44


GLOFA Series Cnet Driver

8 Error Messages

Error messages are displayed on the screen of Display as follows: "No. : Device Name: Error Message (Error
Occurrence Area)". Each description is shown below.

Item Description
No. Error No.
Name of External Device where error occurs. Device name is a title of External Device set
Device Name
with GP-Pro EX. (Initial value [PLC1])
Error Message Displays messages related to the error which occurs.
Displays IP address or device address of External Device where error occurs, or error codes
received from External Device.

Error Occurrence Area


• IP address is displayed such as "IP address (Decimal): MAC address (Hex)".
• Device address is displayed such as "Address: Device address".
• Received error codes are displayed such as "Decimal [Hex]".

Display Examples of Error Messages


"RHAA035:PLC1: Error has been responded for device write command (Error Code: 2 [02H])"

• Refer to your External Device manual for details on received error codes.
• Refer to "Display-related errors" in "Maintenance/Troubleshooting Guide" for details on the
error messages common to the driver.

GP-Pro EX Device/PLC Connection Manual 45

You might also like