SIP5 7SS85 V09.30 Manual C019-G en
SIP5 7SS85 V09.30 Manual C019-G en
SIP5 7SS85 V09.30 Manual C019-G en
Table of Contents
Introduction 1
SIPROTEC 5 Basic Structure of the Function 2
Low-Impedance Busbar
Protection
System Functions 3
7SS85 Engineering 4
Function-Group Types and Bay Proxy 5
V9.30 and higher
Protection and Automation Functions 6
Control Functions 7
8
Manual
Supervision Functions
Measured Values and Supervision of the
Primary System 9
Functional Tests 10
Technical Data 11
Appendix A
Literature
Glossary
Index
C53000-G5040-C019-G
NOTE
i For your own safety, observe the warnings and safety instructions contained in this document, if available.
Target Audience
Protection system engineers, commissioning engineers, persons entrusted with the setting, testing and main-
tenance of automation, selective protection and control equipment, and operational crew in electrical installa-
tions and power plants.
Scope
This manual applies to the SIPROTEC 5 device family.
Further Documentation
[dw_product-overview_SIP5_device-manual, 5, en_US]
• Device manuals
Each Device manual describes the functions and applications of a specific SIPROTEC 5 device. The printed
manual and the online help for the device have the same informational structure.
• Hardware manual
The Hardware manual describes the hardware building blocks and device combinations of the SIPROTEC 5
device family.
• Operating manual
The Operating manual describes the basic principles and procedures for operating and assembling the
devices of the SIPROTEC 5 range.
• Security manual
The Security manual describes the security features of the SIPROTEC 5 devices and DIGSI 5.
• Product information
The Product information includes general information about device installation, technical data, limiting
values for input and output modules, and conditions when preparing for operation. This document is
provided with each SIPROTEC 5 device.
• Engineering Guide
The Engineering Guide describes the essential steps when engineering with DIGSI 5. In addition, the Engi-
neering Guide shows you how to load a planned configuration to a SIPROTEC 5 device and update the
functionality of the SIPROTEC 5 device.
• SIPROTEC 5 catalog
The SIPROTEC 5 catalog describes the system features and the devices of SIPROTEC 5.
Indication of Conformity
This product complies with the directive of the Council of the European Communities
on harmonization of the laws of the Member States concerning electromagnetic
compatibility (EMC Directive 2014/30/EU), restriction on usage of hazardous
substances in electrical and electronic equipment (RoHS Directive 2011/65/EU), and
electrical equipment for use within specified voltage limits (Low Voltage Directive
2014/35/EU).
This conformity has been proved by tests performed according to the Council Directive
in accordance with the product standard EN 60255-26 (for EMC directive), the standard
EN IEC 63000 (for RoHS directive), and with the product standard EN 60255-27 (for
Low Voltage Directive) by Siemens.
The device is designed and manufactured for application in an industrial environment.
The product conforms with the international standards of IEC 60255 and the German
standard VDE 0435.
Standards
IEEE Std C 37.90
Additional Support
For questions about the system, contact your Siemens sales partner.
Training Courses
Inquiries regarding individual training courses should be addressed to our Training Center:
Siemens AG
Siemens Power Academy TD Phone: +49 911 9582 7100
Humboldtstraße 59 E-mail: [email protected]
90459 Nuremberg Internet: www.siemens.com/poweracademy
Germany
Notes on Safety
This document is not a complete index of all safety measures required for operation of the equipment (module
or device). However, it comprises important information that must be followed for personal safety, as well as
to avoid material damage. Information is highlighted and illustrated as follows according to the degree of
danger:
! DANGER
DANGER means that death or severe injury will result if the measures specified are not taken.
² Comply with all instructions, in order to avoid death or severe injuries.
! WARNING
WARNING means that death or severe injury may result if the measures specified are not taken.
² Comply with all instructions, in order to avoid death or severe injuries.
! CAUTION
CAUTION means that medium-severe or slight injuries can occur if the specified measures are not taken.
² Comply with all instructions, in order to avoid moderate or minor injuries.
NOTICE
NOTICE means that property damage can result if the measures specified are not taken.
² Comply with all instructions, in order to avoid property damage.
NOTE
i Important information about the product, product handling or a certain section of the documentation
which must be given attention.
Proper Use
The equipment (device, module) may be used only for such applications as set out in the catalogs and the
technical description, and only in combination with third-party equipment recommended and approved by
Siemens.
Problem-free and safe operation of the product depends on the following:
• Proper transport
• The equipment must be grounded at the grounding terminal before any connections are made.
• All circuit components connected to the power supply may be subject to dangerous voltage.
• Hazardous voltages may be present in equipment even after the supply voltage has been disconnected
(capacitors can still be charged).
• Operation of equipment with exposed current-transformer circuits is prohibited. Before disconnecting the
equipment, ensure that the current-transformer circuits are short-circuited.
• The limiting values stated in the document must not be exceeded. This must also be considered during
testing and commissioning.
OpenSSL
This product includes software developed by the OpenSSL Project for use in OpenSSL Toolkit (http://
www.openssl.org/).
This product includes software written by Tim Hudson ([email protected]).
This product includes cryptographic software written by Eric Young ([email protected]).
Preface.......................................................................................................................................................... 3
1 Introduction................................................................................................................................................29
1.1 General.............................................................................................................................30
1.2 Properties of SIPROTEC 5................................................................................................... 31
3 System Functions....................................................................................................................................... 51
3.1 Indications........................................................................................................................ 52
3.1.1 General....................................................................................................................... 52
3.1.2 Reading Indications on the On-Site Operation Panel..................................................... 52
3.1.3 Reading Indications from the PC with DIGSI 5............................................................... 54
3.1.4 Displaying Indications.................................................................................................. 55
3.1.5 Logs............................................................................................................................ 57
3.1.5.1 General..................................................................................................................57
3.1.5.2 Operational Log..................................................................................................... 59
3.1.5.3 Fault Log................................................................................................................60
3.1.5.4 Setting-History Log.................................................................................................61
3.1.5.5 User Log................................................................................................................ 63
3.1.5.6 Security Log........................................................................................................... 65
3.1.5.7 Device-Diagnosis Log............................................................................................. 66
3.1.5.8 Communication Log............................................................................................... 67
3.1.5.9 Communication-Supervision Log............................................................................ 69
3.1.6 Saving and Deleting the Logs....................................................................................... 70
3.1.7 Spontaneous Indication Display in DIGSI 5....................................................................72
3.1.8 Spontaneous Fault Display on the On-Site Operation Panel...........................................72
3.1.9 Stored Indications in the SIPROTEC 5 Device.................................................................74
3.1.10 Resetting Stored Indications of the Function Group ..................................................... 75
3.1.11 Test Mode and Influence of Indications on Substation Automation Technology ............75
3.2 Measured-Value Acquisition ............................................................................................. 76
3.3 Sampling-Frequency Tracking and Frequency Tracking Groups...........................................78
3.3.1 Overview.....................................................................................................................78
3.3.2 Sampling-Frequency Tracking...................................................................................... 78
3.3.3 Frequency Tracking Groups..........................................................................................81
4 Engineering.............................................................................................................................................. 231
4.1 Overview........................................................................................................................ 232
4.1.1 General..................................................................................................................... 232
4.1.2 Differentiation of the Busbar-Protection Variants........................................................232
4.1.3 Engineering Example.................................................................................................235
4.1.4 Busbars and Bays....................................................................................................... 236
4.1.5 Procedure ................................................................................................................. 236
4.1.6 Creating the Project and Representing the System Graphically in the Single-Line
Editor........................................................................................................................ 238
4.2 Selecting and Creating Devices........................................................................................240
4.2.1 Significant Features for Centralized and Distributed Busbar Protection
(IEC 61850 Compliant).............................................................................................. 240
4.2.2 Significant Features for the Distributed Busbar Protection ..........................................242
4.2.3 Creating Devices........................................................................................................243
4.2.4 Inserting and Connecting Bus Zones.......................................................................... 245
4.3 Configuration for the Centralized Busbar Protection and Distributed Busbar Protec-
tion (IEC 61850 Compliant)............................................................................................. 248
4.3.1 Differences in Project Engineering for the Different Busbar-Protection Variants...........248
4.3.2 Adding Bays, Function Groups, and Functions in 7SS85..............................................248
4.3.3 Current Measuring Points.......................................................................................... 249
4.3.3.1 Current Measuring Points for the Centralized Busbar Protection and Current
Measured Values for the Distributed Busbar Protection (IEC 61850 Compliant)......249
4.3.3.2 Adding Measuring Points for Centralized Busbar Protection 7SS85........................ 250
4.3.4 Current Measured Values (SMV) for the Distributed Busbar Protection (IEC
61850 Compliant)..................................................................................................... 252
4.3.4.1 Procedure for the Transmission of the Current Measured Values from the
Merging Unit to the Client.................................................................................... 252
4.3.4.2 Create and Check the Network Topology.............................................................. 252
4.3.4.3 Adding and Routing Measuring Points.................................................................. 256
4.3.4.4 IEC 61850 System Configurator (IEC 61850 Compliant)........................................ 259
4.3.4.5 Checking the Measuring-Point Routing in DIGSI ................................................... 263
4.3.5 Assigning Device Functions in the Single-Line Editor.................................................. 263
4.3.6 Transmitting Binary Information via GOOSE............................................................... 267
4.3.6.1 General................................................................................................................267
4.3.6.2 Carrying Out Routings ......................................................................................... 268
4.3.6.3 IEC 61850 System Configurator (GOOSE)..............................................................268
4.3.7 Information for Efficient Project Engineering of a Distributed Busbar Protection
(IEC 61850 Compliant) ............................................................................................. 271
4.4 Configuration for the Distributed Busbar Protection......................................................... 273
4.4.1 Creating and Checking the Network Topology............................................................ 273
4.4.2 Configuring Merging Units ........................................................................................276
4.4.3 Updating the Central Unit (Step 1) ............................................................................ 278
4.4.4 IEC 61850 System Configurator ................................................................................ 280
4.4.5 Updating the Central Unit (Step 2) ............................................................................ 283
4.4.6 Notes for Efficient Project Engineering of a Distributed Busbar Protection .................. 285
4.4.7 Routing Manager.......................................................................................................287
4.5 Additional Engineering Information.................................................................................292
4.5.1 General Information.................................................................................................. 292
4.5.2 Bus Coupler Bays....................................................................................................... 292
4.5.3 Combined Bus Coupler Bays.......................................................................................293
4.5.4 Transfer Busbars........................................................................................................ 294
4.5.5 Bus Section without Measuring System...................................................................... 295
4.5.6 Bus-Section Bays........................................................................................................298
4.5.7 Detecting the Line Disconnector ............................................................................... 298
4.5.8 Truck-Type Switchgear...............................................................................................299
4.5.9 Enabling of Tripping by Undervoltage Protection........................................................ 302
4.5.10 Backup Protection Functions ..................................................................................... 304
6.1.5 Application and Setting Notes for Measuring Point Voltage 3‑Phase (V-3ph)............... 392
6.1.6 Settings.....................................................................................................................396
6.1.7 Information List......................................................................................................... 399
6.2 Busbar Differential Protection..........................................................................................402
6.2.1 Overview of Functions............................................................................................... 402
6.2.2 Structure of the Function........................................................................................... 402
6.2.3 Function Description..................................................................................................403
6.2.4 Method of Measurement and Characteristic Curves.................................................... 404
6.2.5 Measurands...............................................................................................................407
6.2.6 Algorithms................................................................................................................ 410
6.2.6.1 Evaluation of the Measurands When a Fault Occurs.............................................. 410
6.2.6.2 Algorithm with Filtered Measured Values..............................................................410
6.2.7 Tripping.................................................................................................................... 411
6.2.7.1 Busbar Differential Protection Trip Logic............................................................... 411
6.2.7.2 Phase-Selective Release of Tripping...................................................................... 412
6.2.7.3 Zone-Specific Release of Tripping......................................................................... 412
6.2.7.4 Cross Stabilization ............................................................................................... 413
6.2.8 Disconnector Image .................................................................................................. 413
6.2.9 Check Zone............................................................................................................... 414
6.2.10 Supervision............................................................................................................... 415
6.2.11 Function Limits of the Busbar Differential Protection.................................................. 415
6.2.12 Application and Setting Notes – Busbar Differential Protection – General....................416
6.2.13 Application and Setting Notes – Busbar – General...................................................... 418
6.2.14 Application and Setting Notes – Check Zone ............................................................. 420
6.2.15 Application and Setting Notes – Cross Stabilization ....................................................422
6.2.16 Settings.....................................................................................................................422
6.2.17 Information List......................................................................................................... 423
6.3 Circuit-Breaker Failure Protection (1-Pole/3-Pole)............................................................. 427
6.3.1 Overview of Function................................................................................................ 427
6.3.2 Structure of the Function........................................................................................... 427
6.3.3 Function Description..................................................................................................428
6.3.4 Circuit-Breaker Failure Protection in Busbar Protection................................................438
6.3.5 Application and Setting Notes....................................................................................439
6.3.6 Settings.....................................................................................................................448
6.3.7 Information List......................................................................................................... 450
6.4 Circuit-Breaker Failure Protection (3-Pole)........................................................................451
6.4.1 Overview of Functions............................................................................................... 451
6.4.2 Structure of the Function........................................................................................... 451
6.4.3 Function Description..................................................................................................452
6.4.4 Circuit-Breaker Failure Protection in Busbar Protection................................................459
6.4.5 Application and Setting Notes....................................................................................461
6.4.6 Settings.....................................................................................................................470
6.4.7 Information List......................................................................................................... 471
6.5 Inherent Circuit-Breaker Failure Protection.......................................................................473
6.5.1 Overview of Functions .............................................................................................. 473
6.5.2 Structure of the Function........................................................................................... 473
6.5.3 Function Description..................................................................................................474
10 Functional Tests........................................................................................................................................909
10.1 General Notes................................................................................................................. 910
10.2 Checking the System Configuration and the Disconnector Image..................................... 911
10.3 System Visualization .......................................................................................................912
10.4 Checking with Secondary Quantities - General Information.............................................. 915
10.5 Pickup Characteristic of Busbar Protection....................................................................... 916
10.5.1 Overview...................................................................................................................916
10.5.2 Busbar-Selective Protection........................................................................................916
10.5.3 Check Zone............................................................................................................... 917
10.6 Differential Current Supervision.......................................................................................919
10.6.1 Busbar-Selective Protection........................................................................................919
10.6.2 Check Zone............................................................................................................... 919
10.6.3 Time Delay................................................................................................................ 920
10.7 Testing with Primary Values............................................................................................ 921
10.7.1 General..................................................................................................................... 921
10.7.2 Testing with a Test Current........................................................................................ 921
10.7.3 Testing with Operating Current..................................................................................922
10.8 Tests for Circuit-Breaker Failure Protection.......................................................................923
10.8.1 General..................................................................................................................... 923
10.8.2 Pickup Threshold of the Circuit-Breaker Failure Protection.......................................... 925
10.8.3 Time Delay of the Circuit-Breaker Failure Protection................................................... 926
10.9 Circuit-Breaker Test......................................................................................................... 927
10.10 Functional Test of the Trip-Circuit Supervision ................................................................ 930
10.11 Functional Test Protection Interfaces............................................................................... 931
10.11.1 Checking the Communication.................................................................................... 931
10.12 Functional Test of the Inrush-Current Detection .............................................................. 933
A Appendix................................................................................................................................................ 1033
A.1 Order Configurator and Order Options...........................................................................1034
A.2 Ordering Accessories.....................................................................................................1035
A.3 Typographic and Symbol Conventions........................................................................... 1037
A.4 Standard Variants for 7SS85 ......................................................................................... 1040
A.5 Requirements for Phase Current Transformers .............................................................. 1044
A.6 Connection Examples for Current Transformers............................................................. 1049
A.7 Connection Examples of Voltage Transformers for Modular Devices............................... 1050
A.8 Preroutings 7SS85.........................................................................................................1056
Literature................................................................................................................................................ 1057
Glossary.................................................................................................................................................. 1059
Index.......................................................................................................................................................1081
1.1 General 30
1.2 Properties of SIPROTEC 5 31
1.1 General
The digital multifunctional protection and bay controllers of the SIPROTEC 5 device series are equipped with a
powerful microprocessor. As a result, all tasks, from acquiring measurands to entering commands in the
circuit breaker, are processed digitally.
Analog Inputs
The measuring inputs transform the currents and voltages sent by the instrument transformers and adapt
them to the internal processing level of the device. A SIPROTEC 5 device consists of inputs for measuring
current and voltage. The current inputs are intended for the detection of phase currents and ground current.
The ground current can be detected sensitively using a core balance current transformer. The voltage inputs
detect the measuring voltage of device functions requiring current or voltage measured values.
The analog values are digitized in the microprocessor for data processing.
Microprocessor System
All device functions are processed in the microprocessor system.
This includes, for example:
• Recording of indications, fault data, and fault values for fault analysis
• Administration of the operating system and its functions, for example data storage, real-time clock,
communication, interfaces
Front Elements
For devices with an integrated or offset operation panel, LEDs and an LC display on the front provide informa-
tion on the device function and report events, states, and measured values. In conjunction with the LC display,
the integrated keypad enables on-site operation of the device. All device information such as setting parame-
ters, operating and fault indications or measured values can be displayed, and setting parameters changed. In
addition, system equipment can be controlled via the user interface of the device.
Serial Interfaces
The serial interface in the front cover enables communication with a personal computer when using the DIGSI
operating program. As a result, the operation of all device functions is possible. Additional interfaces on the
back are used to realize various communication protocols.
Power Supply
The individual functional units of the device are powered by an internal power supply. Brief interruptions in
the supply voltage, which can occur during short circuits in the system auxiliary voltage supply, are bridged by
capacitor storage (see also the Technical Data).
General Properties
• Powerful microprocessor
• Fully digital measured-value processing and control, from sampling and digitizing of measurands to
closing and tripping decisions for the circuit breaker
• Complete galvanic and interference-free isolation of the internal processing circuits from the system
measuring, control, and supply circuits through instrument transformers, binary input and output
modules, and DC and AC voltage converters
• Easy operation using an integrated operator and display panel, or using a connected personal computer
with user interface
• Storage of fault indications for system incidents (faults in system) with real-time assignment and instan-
taneous values for fault recording
• Continuous monitoring of the measurands as well as the device hardware and software
• Communication with central control and storage devices possible via the device interface
Modular Concept
The SIPROTEC 5 modular concept ensures the consistency and integrity of all functionalities across the entire
device series. Significant features here include:
• Functional integration of various applications, such as protection, control, and fault recorder
• The same expansion and communication modules for all devices in the family
• Innovative terminal technology with easy assembly and interchangeability and the highest possible
degree of safety
• The same functions can be configured individually across the entire family of devices
• Automatic logging of access attempts and security-critical operations on the devices and systems
Redundant Communication
SIPROTEC 5devices maintain full communication redundancy:
• Redundant and independent protocols to control centers possible (such as IEC 60870-5-103 and
IEC 61850, either single or redundant)
NOTE
i The availability of certain settings and options depends on the device type and the functions available on
the device.
EXAMPLE
Here, a busbar-protection bay is used as an example. The following functions are required for application
(simplified and reduced):
• Circuit breaker
• Current transformer
• Disconnector
Several predefined function packages that are tailored to specific applications exist for each device family. A
predefined functional scope is called an application template. The existing application templates are offered
for selection automatically when you create a new device in DIGSI 5.
The application template Basic application template, 7SS85 busbar protection is available for the 7SS85
device.
EXAMPLE
If you install a device, you have the usually preferred option to use the product code to completely define the
device directly or to configure the device yourself. Select a device from the hardware catalog using the Signifi-
cant features. A basic variant of the hardware is specified using the Significant features. Later, you can also
expand the device with additional parts, one at a time. After selecting additional device characteristics, for
example, the voltage variant, and after selecting the application template Busbar protection basics, you
complete this step.
Then, add the necessary functional scope (see chapter 2.2 Adjustment of Application Templates/Functional
Scope).
Bay
For every feeder, bus coupler, or bus section disconnector of the busbar protection, a bay is used as superordi-
nate instance. In the bays, the function groups, for example, FG Circuit breaker or FG Disconnector, are
combined for this feeder.
• Assignment of functions to current and/or voltage transformers (assignment of functions to the meas-
uring points and thus to the protected object)
EXAMPLE
The selected application template Basic application template, 7SS85 busbar protection includes the basic
functions:
• Device settings
• Power-system data
• FG Busbars
Then, you can add busbar-specific functions, function groups, and bays.
The following figure shows the embedding of functions via function groups and bays.
[dw_bb_over, 2, en_US]
Depending on the type of device, there are different types of function groups:
Protection function groups bundle functions that are assigned to a protected object, for example, to the
busbar. Depending on the device type and nature of the protected object, there are different types of protec-
tion function groups (busbar protection, etc.).
Circuit-breaker function groups bundle functions (such as processing of tripping, circuit-breaker failure protec-
tion) assigned to the local switches, that is, circuit breakers and disconnectors.
You can add, copy, or even delete function groups for a specific application. You can also adapt the functional
scope within a function group according to the use case. Detailed information on this can be found in the
DIGSI 5 Online help manual.
EXAMPLE
As an example, in the previous figure, the currents of the transformer BE1 are assigned to Measuring point
I-3ph 2. The auxiliary contacts of the circuit breaker and the disconnector are assigned to the 1st bay.
The user can change the assignment as needed, that is, function groups can be assigned to any available
measuring points of the device.
To check or change the assignment of measuring points to the function groups, double-click Function-group
connections in the DIGSI 5 project tree.
[sc_bbp_fgverb, 1, en_US]
In the working area, the window for routing the measuring points opens.
[sc_bbp_msfgbb, 1, en_US]
NOTE
i For busbar protection, Siemens recommends making the assignment via the Single-line Editor (see chapter
4, Engineering).
NOTE
i As connection terminals, use protection-class current transformer terminals (type current 4x protection)
exclusively, for example, for the selection from the hardware catalog for the busbar protection.
• Which circuit breaker(s) is/are started by the protection functions of the protection FG.
• Starting the Circuit-breaker failure protection function (if available in the Circuit-breaker function
group) through the protection functions of the connected protection function group
NOTE
i The currents and the OFF signals are assigned dynamically for the circuit breakers by the disconnector
image for busbar differential protection, circuit-breaker failure protection, and external tripping.
Besides the general assignment of the protection function group(s) to the circuit-breaker function groups, you
can also configure the interface for specific functionalities in detail.
The user can change this connection, as needed. That is, the protection function groups can be assigned to
the Circuit-breaker function groups as desired.
To check or change the assignment of the protection function groups to the circuit-breaker function groups,
double-click Function group connections in the DIGSI 5 project tree → Name of device (see following
figure).
[sc_fgverb, 1, en_US]
In the working area, the window for general routing of the function groups opens.
[sc_bbp-fgcols, 1, en_US]
Figure 2-5 Connection of Protection Function Group with Circuit-Breaker Function Group
Besides the general assignment of the protection function group(s) to the circuit-breaker function groups, you
can also configure the interface for specific functionalities in detail. Proceed as follows:
• Open the appropriate protection function group in the DIGSI 5 project tree, for example, Curr. trans-
former 1.
[sc_bbp-ls_inta, 1, en_US]
• The window for detailed configuration of the interface between the protection function group and the
circuit-breaker function group(s) opens in the working area.
[sc_bbp-detail, 1, en_US]
Figure 2-7 Configuration of the Interface Between the Protection Function Group and the Circuit-Breaker
Function Group(s) (Detail)
• Which operate indications of the protection functions go into the generation of the trip command
• Single-line configuration
• Information routing
• Function settings
Siemens recommends the Single-line configuration Editor to adjust the functional scope.
Complete missing functionalities from the Global DIGSI 5 Library. Then, the default settings of the added func-
tionality are active. You can copy within a device and between devices as well. Settings and routings are also
copied when you copy functionalities.
NOTE
i If you delete a parameterized function group, function, or tripping stage from the device, all settings and
routings will be lost. The function group, function, or tripping stage can be added again, but then the
default settings are active.
In most cases, the adjustment of the functional scope consists of adding and deleting functions, tripping
stages, and function blocks. As previously described, the functions, tripping stages, and function blocks auto-
matically connect themselves to the measuring points assigned to the function group.
You can add function groups or bays. Check these newly added function groups for included (protection) func-
tions and add to these for your specific application. Connect the protection or circuit-breaker function group to
the measuring points (for this, see 2.1 Function Embedding in the Device ). You must connect newly added
protection function groups to a circuit-breaker function group (see 2.1 Function Embedding in the Device ).
Take note of the following:
• Check the routing of binary outputs with respect to fast and normal relays.
• Check the CFC charts for the group-warning indications and group-fault indications.
Functions, tripping stages, function blocks, and function groups can be added up to a certain maximum
number. The maximum number can be found in the respective function and function-group descriptions.
NOTE
i The availability of certain settings and setting options depends on the device type and the functions avail-
able on the device!
Function Points
Function points (FP) and bays are assigned to specific functions, but not to other functions. You can find more
detailed information in the description of application templates in the following chapter.
The device is supplied with the acquired function-point credit. Functions with function points can be loaded
into the device only within the available function-point credit. The functional scope cannot be loaded into the
device if the required number of points of the functional scope is higher than the function-point credit. You
must either delete functions or upgrade the function-point credit of the device.
In addition to function-point classes (10, 20, 30, 40, 50, 75, 100 to 1400) beginning with firmware version
V09.20, any function-point values in the range from 0 to 5000 are supported as a credit in the device. Thus,
the precise function-point credit required can be loaded into the device by the Function-Point Manager. Alter-
natively, you can order classless devices with 0 points (new option beginning with V09.20) or class-bound
with the required function-point class.
• Determine the function-point requirement of certain functions, for example, with DIGSI 5 or the
SIPROTEC 5 Configurator.
• Create a signed license file for your device with the SIPROTEC Function-Point Manager at www.siprotec-
function-point-manager.siemens.com or order the license file from your sales partner.
• Once you have ordered the license file using the Function-Point Manager, you can download it from
there directly.
• Once you have ordered the license file from your sales partner, you will receive it by e-mail or to down-
load.
• Use DIGSI 5 to load the signed license file onto your device. The procedure is described in the Online Help
of DIGSI 5.
NOTE
i Simplifying functions and function control will be discussed in the following. The description also applies
to tripping stage control and function block control.
Functions can be switched to different operating modes. You use the parameter Mode to define whether you
want a function to run (on) or not (off). In addition, you can temporarily block a function or switch it into test
mode for the purpose of commissioning (parameter Mode = test). Additionally, the state of the stage can be
influenced using the controllable Mod in the IEC 61850 representation. The controllable Mod (_:51 Mode
(controllable) in the DIGSI 5 Information routing) supports the states On, Off, Test, Relay blocked,
and Test/Relay blk..
The function shows the current status – such as an Alarm – via the Health signal.
The following explains the different operating modes and mechanisms and how you set the functions into
these modes. The function control is shown in Figure 2-8. It is standardized for all functions. Therefore, this
control is not discussed further in the individual function descriptions.
[lo_steurg, 2, en_US]
State Control
You can control the state of a function via the parameter Mode, the controllable Mod and the input Superor-
dinate state.
You set the specified operating state of the function via the parameter Mode. You can set the function mode
to on, off, and test. The operating principle is described in Table 2-2. You can set the parameter Mode via:
• DIGSI 5
• IEC 61850-8-1
• CFC
The superordinate state can have the values On, Relay blocked, Test, and Test/Relay blk..
The state of the function resulting from the parameter Mode, the controllable Mod, and the superordinate
state is shown in the following table. The resulting state of the functions results from the combination of all
sources (parameter Mode, controllable Mod, and superordinate state). As a simplification, the table only
shows the combination of 2 sources.
1 With the parameter (_:151) Oper.bin.outp. under test, you can set whether the relay outputs are to be activated by functions in the
Test state. If this parameter is deactivated (default setting), the Test state of a function is changed to Test/Relay blk..
NOTE
i The browser-based user interface shows a clear list of the states of all functions, if they differ from the On
state.
Note:
Logics outside this function block, for example, superordinate group indications, are not
affected by the blocking. Issuing these indications to a relay still leads to an activation.
Off The function is turned off. It does not create any information. The health of a disabled func-
tion always has the value OK.
Health
Health signals if a selected function can perform its designated functionality. If so, the health is OK. In case the
functionality is only possible in a limited way or not at all, due to state or problems within the device, the
health will signal Warning (limited functionality) or Alarm (no functionality).
Internal self-monitoring can cause functions to assume the health Alarm (see chapter 8 Supervision Func-
tions). If a function assumes the health state Alarm, it is no longer active (indication not active is gener-
ated).
Only a few functions can signal the health state Warning. The health state Warning results from function-
specific supervision and - where it occurs - it is explained in the function description. If a function assumes the
Warning status, it will remain active, that is, the function can continue to work in a conditional manner and
trip in the case of a protection function.
Not Active
The indication Not active signals that a function is currently not working. The indication Not active is
active in the following cases:
• Function is disabled
• All protection-function steps are disabled via the Enable protection controllable (state = false). The
indication Protection inactive is active.
2.4 Text Structure and Reference Number for Settings and Indications
Each parameter and each indication has a unique reference number within every SIPROTEC 5 device. The
reference number gives you a clear reference, for example, between an indication entry in the buffer of the
device and the corresponding description in the manual. You can find the reference numbers in this docu-
ment, for example, in the application and setting notes, in the logic diagrams, and in the parameter and infor-
mation lists.
In order to form unique texts and reference numbers, each bay, each function group, function, function block/
stage, and indication or parameter has a text and a number. This means that structured overall texts and
numbers are created.
The structure of the texts and reference numbers follows the already shown in Figure 2-1, hierarchy:
EXAMPLE
The busbar protection also includes the bays, which can in turn contain function groups themselves, in
parallel with or superordinate to the function groups.
The text and reference-number structure is shown as an example for the binary input >Acquisition
blocking and the indication Health (see the following figure). The illustration is simplified.
[dw_fg_tr_02, 1, en_US]
The following table shows the texts and numbers of the hierarchy elements concerned:
Name Number of the Instance Number
Type
Bay Bay 50 02
Function group Disconnector 70 1
Function Disconnector 5401 –
Binary input >Acquisition blocking 500 –
Indication Health 53 –
The number of the type is preassigned. The instance numbers result as follows:
• Bay: Bay 02
2nd instance, for the 2nd bay of n bays
The structure is simplified accordingly for parameters and indications with fewer hierarchy levels.
EXAMPLE:
The following table shows the types for some data types as examples:
Data Type Type
ENS O
ACD O
ACT O
SPS I or O
SPC C
MV O
3.1 Indications 52
3.2 Measured-Value Acquisition 76
3.3 Sampling-Frequency Tracking and Frequency Tracking Groups 78
3.4 Processing Quality Attributes 87
3.5 Fault Recording 103
3.6 Protection Communication 111
3.7 Date and Time Synchronization 188
3.8 User-Defined Objects 196
3.9 Other Functions 203
3.10 General Notes for Setting the Threshold Value of Protection Functions 214
3.11 Device Settings 218
3.12 Using a SIPROTEC 5 Device as a Client or Merging Unit 226
3.13 Power Quality Basics 229
3.1 Indications
3.1.1 General
During operation, indications deliver information about operational states. These include:
• Measured data
• Power-system data
• Device supervisions
• Device functions
NOTE
i All indications are assigned to certain device functions. The text of each indication contains the corre-
sponding function designation. You can find explanations of the meaning of indications in the corre-
sponding device functions. However, you can also define indications yourself and group them into your
own function blocks. These can be set by binary inputs or CFC logic.
Reading Indications
To read the indications of your SIPROTEC 5 device you can use the on-site operation panel of the device or a PC
on which you have installed DIGSI 5. The subsequent section describes the general procedure.
Procedure
The menus of the logs begin with a header and 2 numbers at the top right corner of the display. The number
after the slash signifies the number of indications that are available. The number before the slash indicates
how many indications have just been selected or shown. The end of the indication list is closed with the entry
***END***.
[sc_oprlog, 1, en_US]
To reach the desired log from the main menu, use the navigation keys of the on-site operation panel.
² Navigate inside the log using the navigation keys (top/bottom). You will find the most current indication
at the top of the list. The selected indication is shown with a dark background.
Which indications can be shown in the selected log depends on the assignments in the DIGSI 5 information
routing matrix or is predefined. Every indication contains date, time, and its state as additional information.
You will find information about this in chapter 3.1.5.1 General.
In some logs, you are given the option of deleting the entire indication list by softkey in the footer of the
display. To learn more about this, read chapter 3.1.6 Saving and Deleting the Logs.
NOTE
Procedure
To read the indications with DIGSI 5 your PC must be connected via the USB user interface of the on-site
operation panel or via an Ethernet interface of the device. You can establish a direct connection to your PC
via the Ethernet interfaces. It is also possible to access all connected SIPROTEC 5 devices via a data network
from your DIGSI 5 PC.
² You reach the desired logs of the SIPROTEC 5 device using the project-tree window. If you have not
created the device within a project, you can also do this via the Online access menu item.
After selecting the desired log, you are shown the last state of the log loaded from the device. To update, it is
necessary to synchronize with the log in the device.
² Synchronize the log. For this purpose, click the appropriate button in the headline of the log (see the
ground-fault indications example in Figure 3-2 a)).
[sc_grflmd, 1, en_US]
You will find additional information about deleting and saving logs in chapter 3.1.6 Saving and Deleting the
Logs.
Which indications can be shown in the selected log depends on the assignments in the DIGSI 5 information
routing matrix or is predefined. You will find information about this in chapter 3.1.5.1 General.
Displayed indications are supplemented in DIGSI 5 and on the on-site operation panel with the following infor-
mation:
Indication Columns
The following table shows the meaning of the individual columns in the log:
Indication Column Meaning
Time stamp Time stamp of the indication in device time using the local time
zone of the device or the query time for the motor log
Relative time Relative time to a reference entry
Error number Number of the error that occurred in the device. This number incre-
ments continuously.
Entry number Entry identification of buffer entries. This identification displays the
sequence of buffer entries.
Indication number Number of the indication that occurred in the device. This number
increments continuously and is necessary for an analysis by
Siemens.
Indication Indication text
Function structure Path of the signal with the signal name
Name Signal name
Value Current state of the command. Also pay attention to the value
quality to check whether the value is up to date.
Quality The quality of the value shows the source of the value and whether
the value is up to date.
Cause Additional information such as the cause and validity
Number DIGSI address of the signal
3.1.5 Logs
3.1.5.1 General
Indications are saved in logs inside the device and are available for later analyses. Different logs allow catego-
rization of indication logging based on operating states (for example, operational and fault logs) and based on
fields of application.
Log Logging
Operational log Operational indications
Fault log Fault indications
Switching-device log Switching operation and circuit-breaker statistics
Setting-history log Setting changes
User-defined log User-defined indication scope
Security log Access with safety relevance
Device-diagnosis log Error of the device (software, hardware) and the connection circuits
Log Logging
Communication log Status of communication interfaces
Communication-supervision log Communication supervision (GOOSE)
Log Management
Logs have a ring structure and are automatically managed. If the maximum capacity of a log is exhausted, the
oldest entries disappear before the newest entries. If the maximum capacity of the fault log is reached, the
number of the last fault is output via the signal Fault recording buffer is full. You can route this signal in the
information routing. If indications in the information routing of DIGSI 5 are routed to a log, then they are also
saved. During a supply-voltage failure, recorded data are securely held by means of battery buffering or
storage in the flash memory. You can read and analyze the log from the device with DIGSI 5. The device
display and the navigation allow you to read and evaluate the logs on site using keys.
Configurability of Logs
The indication capacity to be recorded in configurable logs (for example, ground-fault log) is laid down in
columns of the information routing (matrix) of DIGSI 5 specifically defined for this purpose.
Procedure
To reach the information routing of your SIPROTEC 5 device, use the project-tree window. Access is only
through the project:
[sc_infpuf, 2, en_US]
For non-configurable logs (for example, setting-history logs) scope and type of logged indications are
described separately (see following chapter about logs).
• Measured data
• Power-system data
Exceeding or dropping below limiting values is output as an operational indication. Short circuits in the
network are indicated as an operational indication Fault with sequential fault number. For detailed informa-
tion about the recording of system incidents, please refer to the description of the fault log (chapter
3.1.5.3 Fault Log). Up to 2000 indications can be stored in the log.
• To reach the operational log of your SIPROTEC 5 device, use the project-tree window.
Project → Device → Process Data → Log → Operational log
• The status of the operational log last loaded from the device is shown to you. To update (synchronization
with the device), click the button Read log entries in the headline of the indication list (Figure 3-4 a)).
[sc_betrmd, 1, en_US]
• To reach the operational log via the main menu, use the navigation keys of the on-site operation panel.
Main Menu → Indications → Operational log
• You can navigate within the displayed indication list using the navigation keys (up/down) on the on-site
operation panel.
• Using the Info softkey, you can retrieve auxiliary information on the entry depending on the context.
[sc_operlog1, 2, en_US]
Deletability
The operational log of your SIPROTEC 5 device can be deleted. This is done usually after testing or commis-
sioning the device. To know more about this, read chapter 3.1.6 Saving and Deleting the Logs.
Configurability
The indication scope of the operational log is configured in a specifically defined column of the information
routing (matrix) of DIGSI 5:
Target → Log → Operational log column
Selected application templates and functions from the library bring with them a predefined set of operational
indications which you can adjust individually at any time.
Fault Definition
In general, a fault is started by the raising pickup of a protection function and ends with the cleared pickup
after the trip command.
When using an automatic reclosing function, the complete reclosing cycle (successful or unsuccessful) is pref-
erably integrated into the fault. If evolving faults appear within reclosing cycles, the entire clearing process is
logged under one fault number even in multiple pickup cycles. Without automatic reclosing function every
pickup is also recorded as its own fault.
User-defined configuration of a fault is also possible.
NOTE
i The definition of the fault is done through settings of the fault recording (see Device manual). Events are
logged in the fault log even when fault recording is switched off.
Apart from the recording of fault indications in the fault log, spontaneous display of fault indications of the
last fault on the device display is also done. You will find details about this in chapter 3.1.8 Spontaneous Fault
Display on the On-Site Operation Panel.
Deletability
The fault log of your SIPROTEC 5 device can be deleted. For more details about this, refer to chapter
3.1.6 Saving and Deleting the Logs.
• To reach the fault log from the main menu, use the navigation keys of the on-site operation panel.
Main Menu → Indications → Fault logs
• You can navigate within the displayed indication list using the navigation keys (up/down) on the on-site
operation panel.
[sc_faullg, 1, en_US]
Figure 3-6 Reading the Fault Log on the On-Site Operation Panel of the Device
Configurability
The indication scope of the fault log is configured in a specifically defined column of the information routing
(matrix) of DIGSI 5:
Target → Log → Fault log column
Selected application templates and functions from the library already bring a predefined set of operational
indications with them which you can adjust individually at any time.
The operational measured values and the measured values of the fundamental components and symmetrical
components (see Device Manual) are calculated every 9 cycles (at 50 Hz, this is every 180 ms). However, this
can mean that the data are not synchronized with the sampled values of the analog channels. The recording
of these measured values can be used to analyze the slowly changing processes.
• To reach the log for setting changes of your SIPROTEC 5 device, use the project-tree window.
Project → Device → Process data → Log → Setting changes
The status of the setting-history log last loaded from the device is shown to you.
• To update (synchronization with the device), click the Read log entries button in the headline of the
indication list (Figure 3-7).
[sc_paramd, 1, en_US]
• To reach the setting-history log from the main menu, use the navigation keys of the on-site operation
panel.
Main menu → Indications → Setting changes
• You can navigate within the displayed indication list using the navigation keys (up/down) on the on-site
operation panel.
[sc_hislog, 1, en_US]
Figure 3-8 Reading the Setting-History Log on the On-Site Operation Panel of the Device
NOTE
• The log, which is organized as a ring buffer, cannot be deleted by the user!
• If you want to archive security-relevant information of the device without loss of information, you
must regularly read this log.
• To reach the user-defined log of your SIPROTEC 5 device, use the project-tree window.
Project → Device → Process Data → Log → User log 1/2
The status of the user-defined log last loaded from the device is shown to you.
• To update (synchronization with the device), click the Read log entries button in the headline of the
indication list (Figure 3-9 a)).
[sc_application_md, 2, en_US]
• To reach user-specific logs from the main menu, use the navigation keys of the on-site operation panel.
Main Menu → Indications → User-defined log 1/2
• You can navigate within the displayed indication list using the navigation keys (up/down) on the on-site
operation panel.
• Using the Info softkey, you can retrieve auxiliary information on the entry depending on the context.
[sc_userrlog1, 1, en_US]
Figure 3-10 Reading the User-Defined Log on the On-Site Operation Panel of the Device
Deletability
The user-defined log of your SIPROTEC 5 device can be deleted. You will find details about this in chapter
3.1.6 Saving and Deleting the Logs.
[sc_diu1u2, 1, en_US]
• To reach the security log of your SIPROTEC 5 device, use the project-tree window. The device must be in
Online access.
Project → Online access → Device → Device Information → Logs tab → Security logs
The state of the security log last loaded from the device is displayed.
• Before this, refresh the contents by clicking the update arrows in the headline.
[sc_secmld, 2, en_US]
• To reach the security log from the main menu, use the navigation keys of the on-site operation panel.
Main menu → Test & Diagnosis → Logs → Security log
• You can navigate on the on-site operation panel using the navigation keys (top/bottom) inside the
displayed indication list.
[sc_seclog, 1, en_US]
Figure 3-13 Reading the Security Log on the On-Site Operation Panel of the Device
NOTE
• This log, which is organized as a ring buffer, cannot be deleted by the user!
• If you want to archive security-relevant information of the device without loss of information, you
must regularly read this log.
• Compatibility problems
Up to 500 indications can be stored in the device-diagnosis log. In normal operation of the device, it is suffi-
cient for diagnostic purposes to follow the entries of the operational log. This specific significance is assumed
by the device-diagnosis log when the device is no longer ready for operation due to hardware defect or
compatibility problems and the fallback system is active.
• To reach the device-diagnosis log of your SIPROTEC 5 device, use the project-tree window.
Project → Online access → Device → Device information → Logs tab → Device-diagnosis log
The status of the device-diagnosis log last loaded from the device is shown to you.
• Before this, refresh the contents by clicking the update arrows in the headline.
[sc_devdia, 1, en_US]
Reading on the Device through the On-Site Operation Panel in Normal Operation
• To reach the diagnosis log from the main menu, use the navigation keys of the on-site operation panel.
Main Menu → Test & Diagnosis → Logs → Device diagnosis
• You can navigate on the on-site operation panel using the navigation keys (top/bottom) inside the
displayed indication list.
[sc_devdia_01, 1, en_US]
Figure 3-15 Reading the Device-Diagnosis Log on the On-Site Operation Panel of the Device
NOTE
• Use the project-tree window to reach the communication logs of your SIPROTEC 5 device.
Online access → Device → Test suite → Communication module
• Then select:
J:Onboard Ethernet → Communication log
The communication log is shown to you in the state last loaded from the device.
• Before this, refresh the contents by clicking the update arrows in the headline.
[sc_compuf, 2, en_US]
• To reach the communication log from the main menu, use the navigation keys on the on-site operation
panel.
Main Menu → Test & Diagnosis → Logs → Communication logs
• You can navigate within the displayed indication list using the navigation keys (up/down) on the on-site
operation panel.
[sc_commlg, 1, en_US]
Figure 3-17 Reading the Communication Log on the On-Site Operation Panel of the Device
Deletability
The communication logs of your SIPROTEC 5 device can be deleted. Read details about this in chapter
3.1.6 Saving and Deleting the Logs.
Configurability
The communication logs are not freely configurable. The entries are preconfigured.
• To reach the communication-supervision log of your SIPROTEC 5 device, use the project-tree window.
Project → Device → Process data → Logs → Com supervision log
The status of the communication-supervision log last loaded from the device is shown.
• To update (synchronization with the device), click the button Read log entries in the headline of the
indication list.
[sc_comsuperv, 1, en_US]
• To reach the communication-supervision log from the main menu, use the navigation keys on the on-site
operation panel.
Main menu → Logs → Com supervision log
• You can navigate within the displayed indication list using the navigation keys (up/down) on the on-site
operation panel.
[sc_comsupervlg, 1, en_US]
Figure 3-19 Reading the Communication-Supervision Log on the On-Site Operation Panel of the Device
Deletability
The communication-supervision log of your SIPROTEC 5 device can be deleted. Read details about this in
chapter 3.1.6 Saving and Deleting the Logs.
Configurability
The communication-supervision log cannot be freely configured. The entries are preconfigured.
Deleting the logs of the device in the operating state is unnecessary. If storage capacity is no longer sufficient
for new indications, the oldest indications are automatically overwritten with new incoming events. In order
for the memory to contain information about the new faults in the future, for example, after a revision of the
system, a deletion of the log makes sense. Resetting the logs is done separately for the various logs.
NOTE
i Before you delete the content of a log on your SIPROTEC 5 device, save the log with DIGSI 5 on the hard
disk drive of your PC.
NOTE
i Not all logs of your SIPROTEC 5 device can be deleted. These limitations apply especially to logs with rele-
vance for security and after-sales (security log, device-diagnosis log, setting-history log).
NOTE
i Upon deletion of the fault log, the associated fault records are also deleted. In addition, the meters for fault
number and fault-record number are reset to 0. In contrast, if you delete fault records, the content of the
fault log, including the allocated fault numbers, remains.
NOTE
i If the device executes an initial start, for example after an update of the device software, the following logs
are automatically deleted:
• Operational log
• Fault log
• Switching-device log
• Setting-history log
• User-defined log
• Communication-supervision log
Back up the deletable logs using DIGSI 5.
NOTE
• To reach the selected log from the main menu, use the navigation keys of the on-site operation panel
(example operational log):
Main menu → Logs → Operational log
[sc_oprlog, 1, en_US]
Figure 3-20 Deleting the Operational Log on the On-Site Operation Panel
• You can navigate within the displayed indication list using the navigation keys (up/down) on the on-site
operation panel.
• The option to delete the entire log is offered to you in the footer of the display at the bottom left. Use the
softkeys below under the display to activate the command prompts. Confirm the request to Delete.
• After being requested, enter the password and confirm with Enter.
• After being requested, confirm the Deletion of all entries with Ok.
• To reach the selected log of your SIPROTEC 5 device, use the project-tree window (for example opera-
tional log).
Project → Device → Process data → Logs → Operational log
With DIGSI 5 you have the possibility of displaying all currently transmitted indications of the selected device
in a special indication window.
Procedure
• Call up the spontaneous indications of your selected device in the navigation window under Online
access.
• The raising indications appear immediately without you having to wait for a cyclical update or initiate the
manual update.
[sc_spnmld, 2, en_US]
After a fault, the most important data of the last fault can be displayed automatically on the device display
without further operational measures. In SIPROTEC 5 devices, protected objects and even circuit breakers can
be freely created and configured depending on the application (even several instances). In DIGSI 5, several
spontaneous fault displays can be configured, depending on the application, with each individual one being
assigned a particular circuit breaker. These displays remain stored in the device until they are manually
confirmed or released by LED reset.
• To reach the Fault-display configuration of your SIPROTEC 5 device, use the project-tree window.
Project → Device → Display pages → Fault-display configuration
• In the main window, all configured circuit breakers are displayed. A list of a maximum of 6 configurable
display lines is offered for each circuit breaker. The activation of a spontaneous fault display occurs for
each circuit breaker by selection via checkmark in the column Display.
• With the parameter (_:139) Fault-display (under Device → Parameter → Device settings) you
determine whether spontaneous fault displays should be shown for each pickup or only pickups with the
trip command.
[sc_konstf, 2, en_US]
For every display line the following display options can be selected:
[sc_stfanz, 1, en_US]
• Press the softkey button Quit in the base bar of the display. The display is irretrievably closed. Repeat this
step until no further spontaneous fault displays appear.
• After completion of all confirmations the last display view is showed before the faults.
Method 2: Acknowledgment via LED reset
• An LED reset (device) causes the reset of all stored LEDs and binary output contacts of the device and also
to the confirmation of all fault displays stored in the display.
You can find more details on the topic of LED reset in chapter 3.1.9 Stored Indications in the SIPROTEC 5
Device
In your SIPROTEC 5 device, you can also configure indications as stored. This type of configuration can be
used for LEDs as well as for output contacts. The configured output (LED or contact) is activated until it is
acknowledged. Acknowledgment occurs via:
• DIGSI 5
• Binary input
• Right-click the routing field of your binary indication in the desired LED or binary output column in the
routing range of the targets.
You are offered the following options:
You can configure indications of individual functions as "stored" in a function group. This type of configuration
can be used for LEDs as well as for output contacts. The configured output (LED or contact) is activated until it
is acknowledged.
The protection and the circuit-breaker function groups contain the block Reset LED FG. The block
Reset LED FG is visible only in the Information routing under the corresponding function group in DIGSI 5.
You use the binary input signal >Reset LED to reset the stored LEDs in the respective function group. The
configured outputs (contacts) are not reset.
If the test mode of the device or of individual functions is switched on, the SIPROTEC 5 device marks indica-
tions sent to substation automation technology station control system with an additional test bit. This test bit
makes it possible to determine that an indication was set during a test. Necessary reactions in normal opera-
tion on the basis of an indication can thus be suppressed.
• Sampling-frequency tracking:
The analog input channels are scanned for valid signals in cycles. The current power frequency is deter-
mined and the required sampling frequency is defined by using a resampling algorithm. The tracking is
effective in the frequency range between 10 Hz and 90 Hz.
The following figure shows the basics of dealing with sampled values (SAV) in the measured-value acquisition
chain. It shows to whom the various sampling frequencies are made available. In order to limit the bandwidth
of the input signals, a low-pass filter (anti-aliasing filter to maintain the sampling theorem) is installed down-
stream. After sampling, the current input channels are adjusted. Meaning that the magnitude, phase, and the
transformer time constant are corrected. The compensation is designed to ensure that the current transformer
terminal blocks can be exchanged randomly between the devices.
[dw_mesess, 2, en_US]
fa Sampling frequency
SMV Sampled measured value
CMV Conventional measured value
LPIT Low-power instrument transformer
The internal sampling frequency of the SIPROTEC 5 devices is fixed at 16 kHz (sampling rate: 320 samplings
per 50-Hz cycle). All current and voltage inputs are sampled. If the magnitude, phase, and transformer time
constant are corrected, the sampling frequency is reduced to 8 kHz (160 samplings per 50-Hz cycle). This is
the basic sampling frequency to which various processes, such as fault recording, RMS measured values, refer.
For the RMS measurement, the measured-value window is adjusted on the basis of the power frequency. For
numerous measurement and protection applications 20 samplings per cycle are sufficient (if frated = 50 Hz:
sampling every 1 ms). This sampling rate is an adequate compromise between accuracy and the parallel
processing of the functions (multi-functionality).
The 20 samplings per cycle will be made available to the algorithms processed in the function groups in 2
variants:
NOTE
i The measuring points for current and voltage are in the Power-system data (starting in 5.10 Power-System
Data). Each measuring point has its own parameters.
3.3.1 Overview
Starting from platform version V07.80, you can merge measuring points into Frequency tracking groups in
SIPROTEC 5 devices. The device operates with a maximum of 6 Frequency tracking groups.
The chapter 3.3.2 Sampling-Frequency Tracking provides the necessary hints on the operating principle of
sampling-frequency tracking and its application.
The chapter 3.3.3 Frequency Tracking Groups describes the principle and application of frequency tracking
groups.
SIPROTEC 5 devices are equipped with powerful sampling-frequency tracking as explained in the chapter
3.2 Measured-Value Acquisition . This ensures high measuring accuracy over a wide frequency operating
range (10 Hz to 90 Hz).
To determine the actual sampling frequency, the voltage and current measuring points are checked for valid
input signals, the actual power frequency is determined and the tracking frequency (sampling
frequency = 20 ⋅ tracking frequency) is adapted. The method is implemented in such a way that the number of
samplings per actual power frequency or the frequency of the system is always constant. The number of
samplings is 20 per cycle, as per chapter 3.2 Measured-Value Acquisition .
During engineering, you set the parameters specifying which measuring points are used for frequency
tracking. All 3-phase voltage and current measuring points and 1-phase voltage and current measuring points
are allowed.
NOTE
i Using a measuring point for sampling-frequency tracking requires this measuring point to be suitable for
reliably determining the power frequency. This is the case, as long as the measuring point is connected to
the power system and the rated voltages and currents are measured. If the measured values for the rated
voltages and currents are unavailable, the sampling-frequency tracking must be switched off for this meas-
uring point.
Examples of these kind of conditions are as follows:
• 1-phase measuring points: Measuring points that measure zero-sequence voltages or zero-sequence
currents must not be used for frequency tracking.
• 3-phase measuring points: Measuring points that measure unbalanced currents and voltages for a
capacitor bank must not be used for frequency tracking.
The following figure shows where you set the parameters for the corresponding measuring point and activate
sampling-frequency tracking in the DIGSI 5 project tree under Settings → Power-system data.
Figure 3-25 Using the Measuring Point to Determine the Sampling Frequency
If the parameter Tracking = active, the measuring point is used to determine the actual tracking
frequency. If the parameter Tracking is set to active for several measuring points, the ID of the measuring
point determines the sequence in which these are checked for valid input signals. The algorithm starts with
the lowest ID number, as follows:
• First, the 3-phase measuring points are scanned. If no valid voltage is found, the selected current meas-
uring points are next. In this case, the following sequence applies:
3-phase voltage measuring point → 3-phase current measuring point → 1-phase voltage measuring point
→ 1-phase current measuring point
If a trigger signal comes from a current measuring point, the voltage measuring points are still continu-
ously scanned for valid voltages and switched immediately if a voltage is found.
• If the true RMS value is greater than 2.5 % of the set secondary device rated value, a measuring point is
valid. For example, this is 2.5 V at 100 V, 25 mA at 1 A or 125 mA at 5 A.
• The tracking frequency is tracked using different interval steps. If the tracking frequency deviates only
slightly from the measured frequency, the frequency is tracked using small steps of 0.010 Hz. In the case
of greater deviations, the interval is 1 Hz. To react faster in the event of larger deviations, for example in
switchover conditions, tracking occurs in 5-Hz steps. When switching on measurands immediately the
measured tracking frequency is used.
• If no tracking frequency can be determined, the appropriate rated frequency of the electrical power
system is used as the tracking frequency. This case occurs before the measurands are switched on, after
they are switched off or when the device is powered on. If the measurands are switched on, the starting
frequency is the set power frequency, for example 50 Hz or 60 Hz. Since rated-frequency input variables
can be assumed for most applications, the measuring algorithms start with the fixed sampling frequency,
for example, 1 kHz for 50 Hz and 1.2 kHz for 60 Hz.
Figure 3-26 shows the behavior of sampling-frequency tracking across the frequency band and at the
frequency limits.
The x-axis shows the actual power frequency (fsys) and the y-axis shows the set tracking frequency (ftrack).
Between 10 Hz and 90 Hz, the relationship is linear. If the actual power frequency is less than 10 Hz, the
tracking frequency is kept at 10 Hz. In this case, sampling occurs at 20 ⋅ 10 Hz = 200 Hz. If the power
frequency is greater than 90 Hz, the tracking frequency is kept constant at 90 Hz.
If the frequency is outside the frequency operating range (10 Hz to 90 Hz), frequency tracking generates the
indication Freq. out of range. The individual protection functions evaluate this indication. If an over-
function can occur, the protection functions are blocked internally to avoid a failure.
You can find more detailed information on the behavior of the protection functions in the chapter 11 Tech-
nical Data.
[dw_working-area_sampling-frequency-tracking, 2, en_US]
Siemens recommends routing the calculated power frequency (fsys) and the determined tracking frequency
(ftrack) as a measured value trace in the fault record. In this way, you can document the behavior of the device
in transient conditions. The following figure shows that you find the both measured values in the information
routing under Power-system data → General:
EXAMPLE:
Figure 3-28 shows the behavior of sampling-frequency tracking using an example.
The voltage was reduced linearly from 57.7 V (100 V phase-to-phase) to 35 V (60.6 V phase-to-phase) and, at
the same time, the frequency was reduced from 50 Hz to 35 Hz, for example motor coasting down. Then, an
abrupt switch to the rated values of 57.7 V at 50 Hz was made.
The upper trace shows the power-system voltage on 1 phase (A) as an example. The center trace is the calcu-
lated power frequency and the lower trace is the determined tracking frequency. If you multiply the deter-
mined tracking frequency of the lower trace by 20, you can determine the sampling frequency.
Figure 3-28 Example of Frequency Tracking and Reaction to a Step Change in the Input Variable
In the SIPROTEC 5 devices before platform version V07.80, sampling-frequency tracking applies to the entire
device. This means that the 1st valid measuring point, for example, a 3-phase voltage measuring point, deter-
mines the selected tracking frequency based on the detected frequency.
If all measuring points in a system are galvanically coupled to each other, the power frequency is identical for
all measuring points.
There are problems with electrical power system states or system states where galvanic separation is possible
and measuring points of the separated system parts are connected to the SIPROTEC 5 device. For these prob-
lematic electrical power system states or system states, different frequencies are possible for a limited time.
Depending on the measuring point set for tracking, the device selects which frequency to use. As a result,
measuring errors and a failure of protection functions are possible.
Starting with platform version V7.80, you can assign the measuring points to different frequency tracking
groups. This ensures high flexibility and high measuring accuracy for a variety of applications. In this case,
every frequency tracking group specifies its own sampling frequency. In the case of galvanic separation and
different system frequencies, different sampling frequencies arise as a result. This occurs temporarily in
systems with rotating machines, for example. A way to achieve galvanic separation is to use an open circuit
breaker.
NOTE
i In the measured-value acquisition chain in in the chapter 3.2 Measured-Value Acquisition , only the data
stream designated as tracked is adapted. The data stream represented as fixed derives its sampling
frequency exclusively from the set rated frequency. In this case, the constant sampling frequency of 1 kHz
at frated = 50 Hz and 1.2 kHz at frated = 60 Hz is used. This applies to every measuring point, regardless of the
frequency tracking group to which it is assigned.
EXAMPLE:
Figure 3-29 shows an example for the necessity of frequency tracking groups. The generator circuit breaker
(GCB) and the high-voltage circuit breaker (HVCB) are the galvanic disconnection points. In this way, different
switching states are possible. The device uses current measuring points (CTs 1 to 6) and voltage measuring
points (VTs 1 to 4) located on different sides of the circuit breakers. In addition, it is assumed that the gener-
ator is started using a starting-frequency converter. In a gas-turbine application, the starting-frequency
converter accelerates the generator from 0 Hz to about 70 % of the rated speed (roughly 35 Hz at
frated = 50 Hz). After this, the gas turbine is fired up and brings the generator to the rated speed. Then, the
voltage is built up to the rated voltage and synchronized. During this start-up operation, the GCB is open and
the HVCB is closed. As a result, the measuring points VT 1, CTs 1, 2, 4 have a frequency that deviates from the
other measuring points during start-up operation. The other measuring points are usually at the rated
frequency due of the connection to the power system.
Furthermore, protection tripping can result in a switching state where the HVCB is open and the GCB remains
closed. In this case, the generator and a generator transformer can assume a frequency that deviates from the
power frequency. In the event of load shedding, the generator accelerates before the speed controller inter-
venes. This is particularly pronounced in hydro generators.
An evaluation of the individual scenarios shows that different frequencies can occur at the different meas-
uring points for a limited time. For this reason, 3 frequency tracking groups are necessary in this example.
These groups are marked with different colors in the following figure.
NOTE
i The measuring point (CT 4) marked with 1) in the following figure will be discussed later.
[dw_example_frequency-tracking-groups, 1, en_US]
To strike a balance between application flexibility and the required computing power, the number of addi-
tional frequency tracking groups was limited to 5. Together with the basic functionality, a total of 6 frequency
tracking groups are possible.
If you wish to use frequency tracking groups, use the following engineering recommendations. Before starting
work, make sure you know how many frequency tracking groups are needed. Select only the required
number.
If you start with an application template that you have expanded by the necessary measuring points, you must
load the necessary number of additional frequency tracking groups from the Global DIGSI 5 Library into the
Power system folder.
If you instantiate an additional frequency tracking group, the system automatically assigns the ID of the
frequency tracking group in DIGSI using consecutive numbers. As the device already has 1 frequency tracking
group, the ID numbering for additional frequency tracking groups starts with 2.
NOTE
i If you have activated several frequency tracking groups during engineering and you then delete a
frequency tracking group again later, the assigned ID is also deleted. All other frequency tracking groups
retain their assigned IDs.
Try to avoid discontinuities by deleting the frequency tracking group with the highest ID if possible.
You will find the frequency measured values and the indications of the corresponding frequency tracking
group in the routing matrix (see Figure 3-27).
Assign the measuring points to the frequency tracking groups in the Function-group connections Editor. As
soon as you have instantiated another frequency tracking group from the Global DIGSI 5 Library, the addi-
tional column Frequency tracking group ID appears in the routing matrix. In this column, you select the
number of the corresponding frequency tracking group for each measuring point using the list box.
Figure 3-32 Assignment of the Measuring Point to the Frequency Tracking Group
NOTE
i Keep the following in mind when assigning the measuring points to the frequency tracking groups:
• The function groups (FGs) can operate only with 1 frequency tracking group.
• This applies also to interconnections between the function groups as for the Transformer differential
protection.
In the case of the Transformer differential protection, the Transformer side FG is interconnected
with the Transformer FG and all Transformer side FGs of one transformer must operate in the same
frequency tracking group.
The same applies when the neutral-point current is measured using a 1-phase function group.
There are also exceptions such as the FG Circuit breaker. The voltage measured values are processed by
the Synchronization function which operates only with a fixed sampling frequency. In this way, voltage
measuring points from different frequency tracking groups can be connected.
The cited rules are checked using scripts and infractions reported during engineering.
Now, you can select the measuring points to be used to determine the tracking frequency for the appropriate
frequency tracking group as explained in chapter 3.3.2 Sampling-Frequency Tracking. If possible, use at least
1 voltage measuring point and 1 current measuring point. Give preference to 3-phase measuring points.
When the tracking frequency has been determined, all measuring points of the frequency tracking group are
set to this frequency and the tracked sampling frequency is adapted.
NOTE
i As described in the chapter 3.2 Measured-Value Acquisition , the measured-value current with fixed
sampling frequency is unaffected by this.
To avoid errors, the ID of the measuring point and the ID of the assigned frequency tracking group are
displayed in the setting sheet of the measuring points in DIGSI 5 (see Figure 3-33).
Figure 3-33 Example: Settings of the 3-Phase Current Measuring Point; Additional Display of the ID for the
Frequency Tracking Group
In addition, the ID of the frequency tracking group is displayed in the function group in the General block (see
Figure 3-34). Here, you can also check the consistency.
Figure 3-34 Display of the ID for the Frequency Tracking Group in the Block General of the Function Group
3.4.1 Overview
The IEC 61850 standard defines certain quality attributes for data objects (DO), the so-called Quality. The
SIPROTEC 5 system automatically processes some of these quality attributes. In order to handle different appli-
cations, you can influence certain quality attributes and also the values of the data objects depending on these
quality attributes. This is how you can ensure the necessary functionality.
The following figure describes roughly the general data flow within a SIPROTEC 5 device. The following figure
also shows at which points the quality can be influenced. The building blocks presented in the figure are
described in more detail in the following.
[lo_quali1, 2, en_US]
• In the Information routing editor for binary input signals of device-internal functions
The following chapters describe in more detail the options regarding this influence as well as the automatic
quality processing.
If a GOOSE connection is the data source of a binary input signal of a device-internal function, you can influ-
ence processing of the quality at 2 locations: at the GOOSE connection and at the input signal of the function.
This is based on the following: A GOOSE date can be distributed within the receiving device to several func-
tions. The GOOSE connection setting (influence) affects all functions. However, if different functions require
customized settings, these are then set directly at the binary input signal of the function.
The properties of quality processing have changed with the introduction of GOOSE Later Binding. You can find
information about the former quality processing in chapter Previous Quality Processing/Affected by the User
for Received GOOSE Values, Page 92.
In the Information Routing Editor, you can influence the data value and quality of all data types. The
following figure shows the possible influence using the example of a DPC data type. All setting options are
effective for the device receiving the data.
• Select either the desired signal in the External Signals group or the signal of a function activated via the
GOOSE column.
• Open the Properties window and select the Processing Quality Attributes sheet.
[sc_LB_GOOSE_2, 2, en_US]
Figure 3-36 Influence Option When Linking a DPC Type Data Object
Depending on the selected data type of the object, various selection options are offered to you for the Safe
state item in the Common settings section. At this point, you select the manually updated values that allow
a safe operating state as soon as the data access via the communication path is disturbed.
• Open the Properties window and select the Advanced quality attributes sheet.
[sc_LB_GOOSE_1, 2, en_US]
With the following advanced quality attributes, you can filter the transmitted GOOSE indications and check
and set their quality. The values that have been adapted, if necessary, are forwarded to the receiver.
For the tests, you can select from the following setting options depending on the data type.
These settings of the Advanced quality attributes apply to the advanced quality attributes listed below. The
selection can vary depending on the data type.
[sc_LB_GOOSE_3, 2, en_US]
You can also forward the quality attributes unchanged. To do this, you must mark the Keep flag check box.
Communication Outage
There is communication disturbance (time allowed to live) between the transmitter and the receiver indicated
by the transmitter. The indication is set in accordance with the settings (Table 3-8).
Invalidity
The transmitting device sends this indication with the quality information Validity = invalid. The receiver
recognizes this for this indication and reacts according to the settings (Table 3-8).
Questionable
The transmitting device sends this indication with the quality information Validity = questionable. The
receiver recognizes this for this indication and reacts according to the settings (Table 3-8).
Test Mismatch
The transmitting device or the function in the transmitting device that issues this indication is in test mode. As
a result, the indication is transmitted with the quality information test. The receiving function block recog-
nizes this for this indication and reacts, depending on its own test-mode state (specified in IEC 61850-7-4
Annex A), according to the settings (Table 3-8).
NOTE
i Follow the sequence of tests. First, the Functional logoff by operator blocked is tested. Then comes
Communication outage and so on. If a case is recognized as active, the test chain is canceled with the
configured setting for the active case.
In the case of Invalidity, the tests are first performed for Functional logoff by operator blocked (not appli-
cable) and then for Communication outage (not applicable) and canceled with the configured action for
Invalidity.
If an indication is routed into the log, manual updating of a value is also logged based on the conditions listed
above and on the reason for the manual update. Manually updating a value based on the conditions listed
above causes a change in the Health Warning function block, inherited up to Device health (specified
in IEC 61850-7-4).
Keep Flag
The quality attributes and values indicated by the transmitter are accepted without change. Quality processing
must be performed by the user via a logic diagram. The outputs of the logic diagram following the user-
specific quality processing can be connected to the function-block inputs as before.
For controllable types, the following substitute values apply in addition to the settable state values or meas-
ured values:
ctlNum = 0
stSeld = False
origin.orIdent = Substituted by quality processing
origin.orCat = AUTOMATIC_BAY
• Open the Properties window and select the Processing Quality Attributes sheet.
Figure 3-39 Influence Option When Linking a DPC Type Data Object
The setting options work for the device receiving the data.
Quality Attribute: Validity
The validity values reserved and questionable are replaced at the receiving end by the invalid value.
• Check box is not set. The validity attribute and data value are forwarded
without change.
• Check box is set and receipt of Validity = good
Check box is set and receipt of Validity = invalid is • The validity attribute is set to good and
set (also applies to values reserved and ques- processed further using this value.
tionable). • The data value is set to the defined substitute
value and processed further using this substitute
value.
In DIGSI 5, you can control the quality processing of CFC charts. In the project tree, you can find the CFC
building block (see the following figure) under Device name →, Settings → Device settings in the editor:
[sc_quali_cfc, 1, en_US]
With the CFC chart quality handling parameter, you control whether you want to influence the
quality of CFC charts in a Manual or Automatic (default setting) manner.
If you select Manual, the quality attribute of the CFC chart is always valid regardless of the quality of indi-
vidual signals (Validity = good)!
Only the Test quality attribute of the CFC chart is processed. If the device is in test mode or the input TEST of
the CHART_STATE CFC building block is set, the quality attribute of the CFC chart is set to Test.
If you select Automatic, the quality processing of the CFC charts is influenced as follows:
In the case of CFC charts, a distinction has to be made between the general quality processing and certain CFC
building blocks that are specifically designed for quality processing.
General Processing
Most of the CFC building blocks do not have an explicit quality processing. For these building blocks, the
following general mechanisms shall apply.
Quality Attribute: Validity
If one invalid signal is received in the case of CFC input data, then all CFC output data will also be set to
invalid if they originate from building blocks without explicit quality processing. In other words, the
quality is not processed sequentially from building block to building block but the output data are set glob-
ally.
This does not apply to CFC output data that originate from building blocks with explicit quality processing
(see next section).
BUILD_BSC
BUILD_DPS
BUILD_ENS
BUILD_SPS
BUILD_XMV
CFC charts have a standard behavior in the processing of signals. If an input signal of the CFC chart has the
quality invalid, all output signals of the CFC chart also get the quality invalid. This standard behavior is
not desirable in some applications. If you use the building blocks for quality processing, the quality attributes
of the input signals in the CFC chart are processed.
• The interlocking condition for switchgear interlocking protection is stored in the device as a CFC chart.
• The removed device sends the release signal for the interlocking condition via a GOOSE telegram.
If the communication connection has been interrupted, the release signal (GOOSEStr) incoming via the
GOOSE telegram gets the quality invalid. If the CFC chart obtains an invalid input signal, there are the
following possibilities: The last signal valid before the communication interruption is used (quality = good) or
a substitute data value with the quality good is used (True, False).
To do this, you have to create a separate CFC chart in addition to the interlocking plan of the switchgear inter-
locking. Use the building blocks for quality processing in a separate CFC chart. With the SPLIT_SPS building
block, split the input signal (data type = SPS) into data value and quality information. You can then continue to
process these signals separately in the CFC chart. Use the quality information as an input signal for a
BUILD_SPS building block and assign the quality good to the signal. You obtain an SPS signal as a result, with
the quality good. You can use this to process release messages correctly. You can process the release
messages with the quality good in the CFC chart of the actual interlocking. Therefore, the release signal for a
switch illustrated in the interlocking logic is available as a valid result with the quality good. The following
figure shows an example of the CFC chart with the building blocks for quality processing:
[sc_cfc_ran, 1, en_US]
Figure 3-41 CFC Chart with Building Blocks for Quality Processing (Switchgear Interlocking via GOOSE)
If you do not want to convert the invalid release signal to a valid signal, as described, during the communica-
tion interruption, you can also assign a defined data value to the release signal. Proceed as follows: With the
SPLIT_SPS building block, split the input signal (data type = SPS) into data value and quality information. Link
the VALID output of the SPLIT_SPS building block with the data value of the input signal (AND gate). This way,
you can set the value to a non-risk state with the valid input signals. In the example, the output of the CFC
chart is set to the value FALSE when the input signal is invalid.
Figure 3-42 provides an overview for processing the quality of data objects within a device-internal function.
A function can receive internal data or input data that is routable by the user (binary input signal or double
commands). The respective quality attributes supported are evaluated by the function on the input side. The
attributes are not passed through the specific algorithm/the specific logic of the function. The output data are
supplied with a quality that is specified by the function state and device-operating mode.
NOTE
i Take into account that pickup of chatter blocking (see chapter 3.9.1 Signal Filtering and Chatter Blocking
for Input Signals) sets the corresponding Validity attribute to invalid.
[lo_quali3, 2, en_US]
• CFC chart: See description in chapter 3.4.3 Quality Processing/Affected by the User in CFC Charts
• GOOSE connection: See description in chapter 3.4.2 Quality Processing/Affected by the User for Received
GOOSE Values
[lo_quali2, 2, en_US]
For this signal type (SPS), you can influence the processing of the quality, see overview in Figure 3-42.
The following figure shows the possible influence on a binary input signal of a protection stage.
• In the Properties window, select the Details entry. There, you will find the item Processing quality
attributes.
[sc_influence, 1, en_US]
Figure 3-44 Influence Options for a Binary Input Signal (SPS Input Signal)
Output Data
The quality is not processed through the actual algorithm/logic of the function. The following table displays
the conditions required to set the quality of output signals of a function.
Cause D0 Value Quality Attribute
After internal (to To the IEC 61850
the SIPROTEC 5 interface, in buffer
system, for example,
in the direction of a
CFC chart)
Functional state = Test Unchanged Test = TRUE Test = TRUE
(thus, result of device operating
mode = Test or function mode
= Test)
Functional state = Off Function-specific, corre- Validity = good Validity = invalid
(thus, result of device operating sponding to the definition for
mode = Off) switched off
All SIPROTEC 5 devices have a fault memory in which fault recordings are kept securely. Fault recording docu-
ments operations within the power system and the way in which protection devices respond to them. You can
read out fault recordings from the device and analyze them afterwards using evaluation tools such as SIGRA.
A fault record contains the following information:
• Any binary signals (for example, pickup signals and trip signals of protection functions)
You can individually configure the signals to be recorded. Furthermore, you can define the starting condition,
the record duration, and the saving criterion of a recording. Fault records saved in the device are also available
after a loss of auxiliary voltage.
The Fault recorder function is a central device function. Both the recording criterion and the measured-value
and binary channels to be recorded are functionally preconfigured through the application templates. You are
able to individually adapt the configuration in DIGSI 5. The fault recording and the fault log are subject to the
same control. This ensures that real time, relative time, and numbering of the fault data are synchronized.
This means that all fault recordings function on the same real-time and relative-time basis.
The data read out via the DIGSI-PC are saved in COMTRADE format. Fault recording data can be transferred to
the substation automation technology by request in accordance with the standards via existing communica-
tion connections (such as IEC 61850, IEC 60870-5-103). The central device analyzes the data using appro-
priate programs.
The Fault recorder function records the sampled values, specific to each device, of all analog inputs, the inter-
nally calculated measured values, and the binary signals. The configuration, which is predefined for each
device via an application template, can be adapted individually.
NOTE
i For detailed information about selecting and deleting fault records, refer to the Operating Manual
(C53000-G5040-C003).
The fault memory of the device is automatically updated with every recording. When the fault memory is filled
completely, the oldest recordings are overwritten automatically. Thus, the most recent recordings are always
stored safely. The maximum size of all recordings is 32 MB.
Sampling Frequency
The analog measuring channels are sampled at a different sampling rate for fault recording. The Sampling
frequency parameter is used to set the desired sampling frequency. Possible setting values are 1 kHz and
2 kHz . This setting value applies only to fault recording and does not affect protection functions or calculated
measured values.
Record Duration
The overall duration of a single fault recording comprises the total duration of the configurable recording
criterion, the Pre-trigger time and the Post-trigger time. You can set the parameters for these
components individually.
[dw_sigrar, 2, en_US]
With the Fault recording parameter, you specify the start criterion of the recording.
You can set the following values:
• with pickup:
The fault recording records the complete fault until dropout. The resulting pickup and trip signals of all
function groups are taken into account.
• user-defined:
With this setting value, you can individually specify the recording criterion for the fault recording in
DIGSI 5. Function-specific recording criteria can be realized in this way.
If a recording criterion reoccurs during the post-trigger time, the recording which is currently active is
extended to include a new post-trigger time.
For a sampling frequency of 1 kHz and 24 analog channels to be recorded, the duration of one individual fault
recording can be up to 20 s.
The maximum record duration can be limited by the Maximum record time parameter.
In addition to starting the fault recording via the internal pickup and trip signals, the following alternatives are
possible:
• Externally via binary input signal >External start (for example, from an external protection device
without fault recording by an object transferred via a GOOSE message)
• By way of a configurable input signal >Manual start , you can start fault records with a configurable
length (parameter Manual record time).
• From DIGSI 5, you can start test fault records with a fixed length of 1 s.
• With a command from a central device via an existing communication connection (IEC 61850,
IEC 60870-5-103)
NOTE
i If a pickup signal is present continuously, the fault record is closed after the Maximum record time
expires and the fault recording is not restarted!
Fault Memory
The device manages its available fault memory dynamically, so that the maximum recording capacity is always
available. When exceeding the limits of the fault memory, the oldest recordings are automatically overwritten.
This means that the most recent recordings are always available. The sampling rate, length, type, and number
of measured value tracks to be recorded are the crucial variables when it comes to restricting the length and
number of recordings possible.
For the sake of simplicity, at a sampling rate of 1 kHz, approx. 5 kBps (at 2 kHz approx. 10 kBps) are recorded
per permanently prerouted channel/measured value. With a storage capacity of 32 MB and 64 measured
values, a maximum record duration of approx. 100 s results.
Fault-Record Channels
In 7SS85 , there are the following fault-record channels:
• Idiff A to Idiff C of the bus sections (with measuring system) and the check zone as instantaneous values
and filtered measured values
• Irest A to Irest C of the bus sections (with measuring system) and the check zone as instantaneous values
and filtered measured values
The following analog channels are set by default in the system configuration:
• For the check zone and for each of the bus sections, 12 analog channels each (Idiff and Irest as instanta-
neous values and filtered measured values for the 3 phases)
Example with 4 bus sections: (1 + 4) ⋅ 12 = 60
The maximum number of routable analog channels is 150; for binary values, it is 200.
In the following table, you can find output signals of the Fault recorder function:
Name Type Description
Control: Error number INS The indication of the current error number
allows a unique allocation of entries in the
message buffers for the recorded fault records.
Control: Recording started SPS Fault recording running
Control: Recording done SPS Fault recording done
Control: Tmax reduced SPS Fault recording ends before the set Maximum
record time expires, because the fault log is
full.
Control: Fault log is full INS The fault log is full.
• In the Information Routing of each device set up in DIGSI 5, you can route binary signals to LEDs and
output contacts. To do this, open the project tree.
Project -> Device -> Information routing
• Right-click the routing field of your binary indication in the desired LED or binary output column in the
routing range of the targets.
You are offered the following options:
4 Binary input
5 Binary output
6 Function key
Parameter: Storage
• Recommended setting value (_:2761:141) Sampl. freq. IEC 61850 rec. = 2 kHz
With the Sampl. freq. IEC 61850 rec. parameter, you define the sampling frequency of the fault
record that you want to download using the IEC 61850 communication protocol. Possible setting values are
1 kHz and 2 kHz.
You cannot set the Sampl. freq. IEC 61850 rec. parameter to be greater than the maximum setting
value of the Sampling frequency parameter.
If the size of the COMTRADE file exceeds the maximum permissible storage capacity of the device, the original
recording is truncated. The truncated data are discarded.
NOTE
i If you have created a fault record with a certain sampling frequency and then set the sampling frequency to
a lower value, you can no longer download this fault record using the IEC 61850 communication protocol.
You must reset the sampling frequency to the original value. Then you can download the fault record again
using the IEC 61850 communication protocol.
Parameter: Cal.zero.seq.cur.channel
• 3-phase + IN-separate
• 3-phase + IN
• 3-phase
• 3 ph-to-gnd volt. + VN
• 3 ph-to-gnd voltages
3.5.5 Settings
3.6.1 Overview
The Protection communication includes all functionalities necessary for data exchange via the protection
interface (PI).
Devices that communicate with each other via protection interfaces form a device combination. A device
combination consists of 2 to 6 devices. The devices communicate via point-to-point connections (protection
connections). In this case, a device has only one connection to another device via a protection interface (PI).
With a 2nd protection interface, you can establish a connection to another device or a redundant connection
to the same device. With their protection connections, the devices form a protection topology in the form of a
redundant ring (ring topology) or as a chain structure (chain topology).
[dw_PDC_chain_3devices, 1, en_US]
[dw_PDC_ring_3devices, 1, en_US]
[dw_PDC_ring_2devices, 1, en_US]
Within a device combination, the point-to-point connections can have different bandwidths. Depending on
the bandwidth, a certain amount of binary information and measured values can be transmitted bidirection-
ally between the devices. The connection with the lowest bandwidth defines the amount of binary informa-
tion and measured values.
The following information is important for protection communication and is transmitted additionally. You
cannot change this information:
• Topology data and values are exchanged for monitoring and testing the connection and displayed on the
device or with DIGSI 5.
• Protection data and measured values, such as line differential protection data or binary data of the tele-
protection schemes for distance protection and ground-fault protection are transmitted.
• The time synchronization of the devices is possible directly via the connection, whereby a device of the
protection topology assumes the role of the timing master.
The point-to-point connection between the devices is continuously monitored for data faults and failure and
the signal-transit time of the data is measured.
The protection communication is typically used for line differential protection and with the teleprotection
schemes for distance protection and ground-fault protection. In SIPROTEC 5, you can configure the protection
communication in all devices and use it for further protection applications. At the same time, any binary infor-
mation and measured values can be transferred between the devices.
NOTE
i The protection communication is compatible with the successor versions from firmware version V04.00
and higher.
The following figure illustrates the interaction of protection communication, protection function groups, and
communication modules. The Protection communication is integrated as follows in the overall system:
[dw_protcom_compl_system, 2, en_US]
If protection functions want to use the protection interfaces, their superordinate protection function group,
for example, the FG Line 1, must be connected to a Protection communication function group. With this
connection, each protection function in the FG Line 1 can use protection communication.
In addition, a connection must be configured between the logical protection interface in the FG Protection
communication and a channel on the physical communication module. The physical communication module
must support the protection-interface protocol.
The following chapters describe the configuration of the connections.
NOTE
Types Description
Type 1 With type 1, the Line differential protection function is the primary appli-
cation. This application requires the greatest portion of the bandwidth, so
that with type 1 the number of available customer-specific remote data is
lower. This becomes noticeable with a 64 kBit/s protection connection via a
G703.1 or X21 interface.
A maximum of 6 line ends (devices) is possible.
If the Line differential protection and Teleprotection scheme functions
are to operate in parallel in the device, the bit rate must not be less than
512 kBit/s!
Type 2 Type 2 provides considerably more bandwidth for customer-specific remote
data. The transmission of protection data and other data, for example,
measured values as well as the teleprotection scheme, is predominant here.
Using type 2 protection communication, a maximum of 6 devices can be
connected to one another and different device types (for example, 6MD,
7VK, 7SA, and 7SJ) can exchange data.
NOTE
i In the case of devices with the Line differential protection function, for example 7SD and 7SL, protection
communication type 1 is preset in the application templates of the devices. Type 2 is preset in the applica-
tion templates for other devices, and is used for other data transmission.
Type 1 and type 2 protection communication do not work together in pairs via a protection function.
[dw_interface, 1, en_US]
Figure 3-51 Data Exchange for 2 Devices, Each with Protection Connection
NOTE
i The index describes the consecutive numbering of the devices in a device combination (see parameter
Local device is device).
A maximum of 2 protection interfaces are possible per FG Protection communication in one device, see the
following figure. If the Protection communication function groups are connected to one another in the
devices via 2 protection connections of the same type, this results in 100 % redundancy regarding the trans-
mission route. The devices then search for the communication connection with the highest bandwidth (for
example, optical fiber). If this protection connection fails, the system switches over automatically to the 2nd
protection connection until the 1st protection connection is available again. As the protection connection with
lower bandwidth defines the maximum amount of transferable information, the same information is
exchanged via both protection connections. Both protection communications in the device are then of type 1.
[dw_intera, 1, en_US]
Figure 3-52 Data Exchange for 2 Devices, Each Having 2 Protection Connections, Redundant Transmission
Route
Remote Data
With the Remote data function, customer-specific indications and measured values can be communicated via
the protection interface with settable update cycles (priorities).
There are 3 different priorities for the transmission of remote data:
• Priority 1: Use Priority 1 for the transmission of fast protection signals that are transferred and updated
at a maximum of every 20 ms in a telegram.
• Priority 2: Use Priority 2 for the transmission of fast single-point or double-point indications that are
transferred and updated at a maximum of every 40 ms.
• Priority 3: Use Priority 3 for all indications, measured, and metered values that are transferred and
updated a maximum of every 100 ms.
The number of customer-specific signals, indications, and measured values available conform with the
remaining bandwidth. The remaining bandwidth is lower than with all other protection functions (type 2)
when using a line differential protection (type 1). Customer-specific measured values consume more band-
width than single-point indications.
Communication Media
The communication takes place via direct fiber-optic connections, via communication networks or via 2-wire
copper conductors. Siemens recommends a direct fiber-optic connection, as this offers a high transmission
rate and is immune to failures in the communication route while offering the shortest transmission time. This
also enables the transmission of a large amount of remote data in line differential protection applications and
the remote control of remote devices with DIGSI 5.
The distance to be bridged and the transmission paths (communication media) available determine the
settings of the protection interface. External communication converters are used for the connection to
communication networks via G703.1-, X21-, or G703.6 interfaces. The connection to 2-wire copper cores also
takes place via a communication converter. The C37.94 interface, for example, with 2 MBit/s, offers a direct
fiber-optic connection to a multiplexer with the corresponding interface.
Table 3-10 to Table 3-11 show examples of communication connections.
In the case of a direct connection, the transmission distance depends on the fiber type of the optical fiber. This
distance can also be extended via external repeaters.
The modules in the device can be replaced from outside, so that adaptation to a communication route is
possible. In the case of the 820-nm double module USART-AE-2FO, 2 protection-interface channels can be
operated on one module.
The modules can be located at slots E and F in the base device, and at slots N and P in the plug-in module
assembly with integrated power supply.
When using communication converters, the connection from the device to the communication converter by a
module is established via optical fibers.
Plug-In Modules
Plug-In Module
USART-AE-2FO
Physical Connector
1 x optical serial, 820 nm, ST connector, 1.5 km via 62.5/125 μm multimode optical fibers ●
2 x optical serial, 820 nm, ST connector, 1.5 km via 62.5/125 μm multimode optical fibers ●
Application
Protection interface (Sync. HDLC, IEEE C37.94) ● ●
NOTE
i The USART plug-in module types can be used in slots E and F in the base module as well as in slots N and P
in the CB202 expansion module. They are not suitable for use in port M in the CB202 expansion module.
[dw_multim, 1, en_US]
Figure 3-53 Connection over Short Distances, 1.5 km to 2 km via Multimode Optical Fiber
[dw_multim-02, 1, en_US]
[dw_single2, 1, en_US]
Figure 3-55 Connection via Different Distances via Singlemode Optical Fiber
[dw_attenuator, 2, en_US]
NOTE
i If you use the communication modules USART-AV-2LDFO or USART-AK-2LDFO for transmission routes
under 30 km, then connect 2 attenuators 7XV5107-0AA00. To continue using the duplex LC plug, attach
both attenuators to one end of the protection connection (see Figure 3-56).
[dw_single, 1, en_US]
[dw_multim-05, 1, en_US]
The connection to the multiplexer is established via a communication converter with a G703.1 interface (64
kBit/s) or X21 interface (64 kBit/s to 512 kBit/s). You can set the bit rate for the KU-XG-512 (for X21), KU-
XG-256 (for X21), KU-XG-128 (for X21), and KU-XG-64 (for X21 or G703.1) with the parameter Connection
via.
You can find more detailed information in Table 3-12.
[dw_multim-06, 1, en_US]
The connection to the multiplexer is established with 512 kBit/s via a communication converter with a G703.6
interface (E1 with 2 MBit/s or T1 with 1.44 MBit/s). The communication converter offers a 2nd interface for the
connection of a further protection interface.
Adjust the setting for the bit rate with KU-2M-512 at 512 kBit/s in accordance with Table 3-12 with the param-
eter Connection via.
[dw_multi_7, 1, en_US]
The connection to a communication converter with an integrated 5-kV isolation voltage is established with
128 kBit/s (KU-KU-128 setting in accordance with Table 3-12). A 20-kV isolation of the 2-wire connection is
possible via an external 7XR9516 isolating transformer.
[dw_repeat, 1, en_US]
The repeater offers an interface for connecting an additional protection interface. The connection to a
repeater is established with 512 kbit/s (repeater 512 setting in accordance with Table 3-12).
[dw_mutip8, 1, en_US]
Figure 3-62 Direct Optical Connection to a Multiplexer with a C37.94 N * 64 kBit/s Interface (Time Slot N =
1; 2 or 8)
NOTE
i The redundancy of different communication connections (for the ring topology) requires rigorous separa-
tion of all devices involved in the communication. Therefore, avoid different communication routes via the
same multiplexer board, as no more substitute paths are possible if the board fails.
• IRIG B
• DCF77
• IEEE 1588
• SNTP
For this, these time sources must be set as the 1st time source and optionally as the 2nd time source in the
timing master. If available, if the 1st time source in the timing master fails, the system switches over to the
2nd time source.
The following chapters describe how you set a device as a timing master:
• For classic protection communication, refer to Parameter: Address of Device x, Page 129.
• For advanced protection communication, refer to Parameter: Device index, Page 165.
Set the protection interface as the 1st time source in the other devices of the device combination. You can
find the setting value in DIGSI 5 via the Project tree → Parameters → Time settings → Timer → Time
source 1 → PI.
In this way, all events in the devices of the device combination are recorded with the same time and are time-
synchronized even across different switchgears. This simplifies fault analysis and the fault records are recorded
with the same time in all devices.
[dw_time_sy, 2, en_US]
Figure 3-63 shows how device 1 with index 1 is synchronized with devices 2, 3, and 4 via the protection inter-
face. Device 1 is the timing master, whose time is synchronized with a selectable, external time source.
You can find these measured values in the device under the following DIGSI mask:
Multiplex Operation
With the extended protection communication, you have the option of having a physical USART channel used
by 2 logical protection interfaces. In this way, a communication route can be double used, for example to
implement Parallel line protection with Line differential protection without additional hardware. To do this,
configure the channel according to chapter 3.6.6.4 Configuration of the Advanced Protection Communication
in DIGSI 5.
[dw_channel-mux, 1, en_US]
NOTE
i Note that in case of multiple use of a physical channel, the available bandwidth is divided equally between
the logical protection interfaces. Therefore, this operating mode is not suitable for baud rates under
128 kBit/s.
NOTE
i Do not confuse the 2 variants of the protection communication with type 1 and type 2 of the protection
communication!
[dw_decision_protcom, 1, en_US]
Figure 3-66 Decision Tree to Select the Variant of the Protection Communication
(1) Preconfigured parameter sets are new, prepared parameter sets which can be used as templates.
You start with the template and adapt the configuration of the protection communication to the
specific requirements. The retrospective adaptation of the configuration is only possible with the
advanced protection communication.
NOTE
i If you are unsure about the suitable variant for your use case during selection, use the advanced protection
communication.
NOTE
i If you want to change an existing classic protection communication to an advanced protection communica-
tion or vice versa, a window appears in DIGSI where you are asked whether you want to keep the mapping
or not - that is, the communication settings or communication-information routing that has previously
been set. In this case, click No
3.6.5.1 Overview
The classic protection communication enables the data exchange between the devices via synchronous serial
point-to-point connections from 64 kBit/s to 2 mBit/s. These connections can be directly via optical fiber or via
other communication media, for example, via dedicated lines or via communication networks. IP-based
communication is not supported.
The function groups of the classic protection communication always support a fixed number of devices in the
device combination:
[dw_simple_protcom_compl_system, 2, en_US]
(1) The device automatically routes the connection between the protection FG and the Protection
communication FG in DIGSI 5.
The classic function group Protection communication contains the following functionalities and function
blocks (FB):
• A Protection interface
• The FB External synchronization for the synchronization of the transferred data through an external
synchronous pulse (1-second-pulse, PPS12)
[dw_structure_FG_protcom_simple, 1, en_US]
The function Device combination manages the devices that exchange data via the protection communica-
tion. In the device-combination settings, you set the general settings for the device combination and the
device addresses.
The function Device combination issues the following indications:
NOTE
i In contrast to the protection interface in the extended protection communication, the protection interface
in the classic protection communication is automatically connected to a physical channel of the communi-
cation module (refer to Figure 3-67).
• Select the desired communication module in the rear view of the device.
• In the Properties of the communication module > Protocols > Channel x Protocols, select the
Protection interface protocol.
[sc_PDC_classic_protocol, 1, en_US]
• Then select the number of devices under Mapping (see next figure).
Depending on the device, the selection of device combinations can be restricted to 2 or 3 devices.
[sc_PDC_classic_mapping, 1, en_US]
NOTE
i The function groups shown in Figure 3-70 are not available in the DIGSI library.
You can change the number of devices (for example 2 protection communication devices) any way you
like via the Mapping text box.
If you change the number of devices via the Mapping text box, all activated remote data, settings of the
device combination and of the protection interface are lost.
If the module slot is not yet provided with modules, proceed as follows:
• Select the desired communication module in the rear view of the device.
• Select the module from the catalog and drag it to a channel. Thus is the channel configured with a
module. DIGSI 5 indicates whether the module can be used for protection communication under Device
Information.
• Use the Protocols text box to select the Protection interface, see Figure 3-69.
• Then use the Mapping text box to select the number of devices, for example 2 devices protection com.,
see Figure 3-70.
[sc_config1, 1, en_US]
Figure 3-71 Selecting the Protocol: Communication via the Protection Interface
[sc_config, 4, en_US]
Changes in the device-combination settings are always visible on the other channel as well. All further param-
eters can be set separately for individual channels.
NOTE
i The number of device addresses displayed corresponds to that of the number selected during the device-
combination configuration.
NOTE
• Under Address of device 1, set the address for the timing-master device.
• Parameterize the other devices in such a way that they get their time from the timing-master device
via the protection connections.
For more information, refer to 3.7.3 Function Description. Select Protection interface as the
adjustable synchronization option.
In the timing-master device, you must not set the protection interface as the synchronization source!
APPLICATION EXAMPLE
You have a device combination with 2 devices.
For example, in DIGSI 5, select the parameter setting Address of device 1 with the parameter value 101
for device 1 and the parameter setting Address of device 2 with the parameter value 102 for device 2.
Then, use the Local device is device parameter to set the index of the local device. The local device is
the device that you parametrize.
The addresses must be set identically for all devices in the device combination. A functional protection
communication requires that you also assign the same index in all devices of the device combination for a
device with a unique address.
number of selected and self-created signals and measured values which are to be transmitted within the
device combination (refer to 3.6.5.9 Configuring Remote Data).
Apart from the default value, you can also set the following bit rates:
• 128 kBit/s
• 512 kBit/s
• 2048 kBit/s
NOTE
i If you use optical fibers for a connection between the devices, set the value to 2048 kBit/s.
NOTE
i The Number of devices parameter is only visible for device combinations with more than 2 devices.
Set the same number of devices used in all devices that are part of the device combination.
Connection mode
• Priority 2: Use Priority 2 for the transmission of fast single-point or double-point indications.
• Priority 3: Use Priority 3 for all indications, measured and metered values.
The number of customer-specific signals, indications, and measured values conform with the remaining band-
width. Customer-specific measured values consume more bandwidth than single-point indications.
NOTE
i The parameter Difference Tx and Rx time only appears when the function Line differential protec-
tion is instantiated and the parameter External synch. only is not set to Synchronization.
NOTE
i If you use a multiplexer with a C37.94 interface as a means of communication, Siemens recommends a
setting value of 0.25 ms to 0.6 ms.
Parameter: Synchronization
The parameter External synchronization is visible only if the parameter Synchronization is not set
to External synchron. off.
External synchronization is possible separately for each protection interface.
Parameter Value Description
PPS electrical (Port G) The electrical synchronous pulse of a satellite receiver (1-second-pulse,
PPS13) is the synchronization source on the port G, the time synchronization
interface.
IEEE 1588 The time synchronization protocol IEEE 1588 for an Ethernet-BD communi-
cation module is used for synchronization.
NOTE
i The configuration option IEEE 1588 is only visible if the device has an Ethernet-BD communication
module and you have selected the communication protocol IEEE 1588, see the following figure.
[sc_BD_1588, 1, en_US]
Figure 3-73 Ethernet-BD Communication Module: Selection of the IEEE 1588 Protocol
NOTE
i External synchronization takes into account the signal-transit time in the transmission and reception direc-
tions. If external synchronization fails for a short time, for example, due to a receiving interference or an
unfavorable satellite position for a brief period, internal synchronization via telegram measurement is still
active.
NOTE
i In contrast to the protection interface in extended protection communication, the protection interface in
classic protection communication is automatically connected to a channel of a communication module (see
Figure 3-67).
• Priority 1: Use Priority 1 for the transmission of fast protection signals that are transferred and updated
at a maximum of every 20 ms in a telegram.
• Priority 2: Use Priority 2 for the transmission of fast single-point or double-point indications that are
transferred and updated at a maximum of every 40 ms.
• Priority 3: Use Priority 3 for all indications, measured, and metered values that are transferred and
updated a maximum of every 100 ms.
The number of customer-specific signals, indications, and measured values conform with the remaining band-
width. Customer-specific measured values consume more bandwidth than single-point indications.
NOTE
i The inaccuracy of the synchronization source enters the stabilization of the Line differential protection as
an error signal.
This means that a greater inaccuracy increases the calculated restraining quantity and makes the Line
differential protection less sensitive.
If IEEE 1588 is used as the synchronization source in the synchronization status SmpSynch = global, accu-
racy values are supplied with the synchronization signals and the parameter Max. inaccuracy is not used.
If the supplied accuracy values become invalid, the value set in the parameter Max. inaccuracy is used.
If the synchronization source IEEE 1588 works in the synchronization status SmpSynch = local, then the
value set in the parameter Max. inaccuracy is used as permanently available inaccuracy.
If the synchronization source PPS electrical (Port G) or PPS optical (USART) is used, then the value set in the
parameter Max. inaccuracy is used as permanently available inaccuracy.
If a USART communication module with the PPS protocol and the PPS generatoroperating mode is also used
as a synchronization source at the same time, the value set in the parameter Max. inaccuracy is used as
permanently available inaccuracy.
If both synchronization sources are working in the synchronization statusSmpSynch = local, that is decou-
pled from a global reference time, an additional check is conducted as to whether the synchronization source
(gmIdentity) is the same. Synchronicity can only be guaranteed if the synchronization sources are the
same.
If the synchronization sources display a different synchronization status, that is one displays the synchroniza-
tion status SmpSynch = local and the other the synchronization status SmpSynch = global, synchroniza-
tion cannot be guaranteed.
Siemens recommends using the default setting Check synchron.-source = yes.
If you have problems with the synchronization-source check, you can switch off the synchronization-source
check. Switch off the synchronization-source check only if the synchronization sources are synchronous at the
end of their protection connection.
The parameter Check synchron.-source is visible only if the parameter (_:5161:113) Synchroni-
zation is set to External synch. only.
NOTE
i If you use PPS electrical (Port G) as the synchronization source, the synchronization status (SmpSynch) is
permanently set to global.
If you use PPS optical (USART) as the synchronization source, you can use the setting (_:107)
Received. SmpSynch to set the synchronization status to (SmpSynch) local or global.
For synchronization with microsecond accuracy, for example with the Line differential protection, adjust
the setting (_:107) to Accepted. SmpSynch = global.
Indication Description
initialized: The protection interface is not connected and is in the Initial state.
PI connected: The protection interface is connected to the protection interface of the
partner device.
PI data fault: The protection interface has not received any valid telegrams for the time
set in parameter (_:5161:107) Disturbance alarm after.
PI data failure: The protection interface has not received any valid telegrams for the time
set in parameter (_:5161:108) Transm. fail. alarm after.
not existing: The protection interface has not been assigned to a communication
channel.
NOTE
i You can reset the measured values of the protection interface directly in the device. Proceed as follows:
Device functions > x Device protection comm. > Protection interface y > Release measured values.
Indication Description
(_:9181:500) >Block This indication shows the blocking of the external synchronization via a
stage binary input. The external synchronization can be set to inactive through
this binary input indication.
(_:9181:501) >PPS pulse The binary input (_:9181:501) >PPS pulse loss can be used to
loss signal an externally detected failure in the PPS synchronous pulse (for
example, an error message from the satellite receiver). Setting this binary
input also leads to the indication (_:9181:301) PPS pulse loss. The
external synchronization detects immediately that there is a problem with
the connected synchronization pulse. Otherwise, the problem will only be
noticed after approx. 2.1 s – after the test for synchronous-pulse failure.
(_:9181:301) PPS pulse This indication shows that the synchronization has failed. This can be due to
loss the following reasons:
[lo_pps_syn, 2, en_US]
Figure 3-74 Logic for the Generation of the Indication PPS pulse loss
[dw_data, 1, en_US]
The data bar is divided into 3 priorities, which also have different transmission rates and data volumes.
For all signals to be sent, the basic principle is that only pure data contents are transmitted. The quality (for
example, Valid) is not automatically transmitted as well. If you want to transmit the quality as well (for
example, for further processing of GOOSE messages), the quality must be transmitted separately (for example,
by using CFC). If a signal that has a test flag is transmitted (because its function is in test mode, for example),
all signals are provided with a test flag on the receiving side. If the connection is broken, all received signals
are flagged with the quality Invalid. If desired, the value can also be set to a predefined state after a select-
able dropout time or the last value received can be retained (Hold setting). This can be configured separately
for each received signal (see Table 3-17).
NOTE
Signals that are transferred data fields of priority 1 are sent with every telegram. They are preferably used for
the transmission of rapid signals, for example, release for circuit-breaker intertripping. A strictly deterministic,
rapid transmission is required there.
Signals of priority 2 are transmitted with at least every 2nd telegram. For bit rates >256 kbit, there are no
differences between priority 1 and priority 2.
Priority 3 signals are transmitted at least every 100 ms. This priority is used for transmission of measured and
metered values. Complex values must be routed separately as the real and the imaginary part for transmission.
Measured-value thresholds that lead to an updating of a measured value are set centrally as a property of the
measured value. These measured-value thresholds apply with the corresponding reporting, for example, also
for the transfer via IEC 61850 to a substation automation technology.
Signals which are written to a data area x under a priority on the data bar must be routed to an indication of
the same type in the device reading this information. Otherwise, they are processed incorrectly on the
receiving side. The data bar is organized in terms of bits. For information on the bit requirement of each signal
type, refer to Table 3-16.
Table 3-14 and Table 3-15 show the number of data areas in the data bar in relation to the available baud
rate.
NOTE
i Set the parameter Lowest appearing bit rate in each device for the protection interfaces in a device
combination. This determines the number of data areas.
If, for example, in a device combination with 3 devices with a type 2 chain topology 2 devices are connected
via direct optical fibers and 2 devices with a bit rate of 64 kBit/s, the 64 kBit/s section is the limiting factor for
the entire device combination.
Table 3-14 Available Bits - Minimum Constellation Baud Rate 64/128 kBit/s
Table 3-15 Available Bits - Minimum Constellation Baud Rate 512/2048 kBit/s
NOTE
i If the protection link fails, these values can be set on the receiver side.
[sc_txrmbb, 1, en_US]
[sc_txcobb, 1, en_US]
Figure 3-77 Routing of a Double-Point Indication (Transmit) to the Protection Interface in Device 1
The following figure shows the routing in the 2nd device. Here, the signal with priority 1 will be routed to
position 1. As a user, you are therefore responsible for the correct routing.
[sc_rxcobb, 1, en_US]
Figure 3-78 Routing of a Double-Point Indication (Receive) to the Protection Interface in Device 2
The signals of the 1st device are linked with the signal (Receive) in the 2nd device. This takes place via the
data areas at positions 1 and 2 of the data bar, which transfer the state of the indications. Other devices can
also read this information and link it to their internal signals. Here, too, the secure state, which is assumed
when the protection connection is interrupted, is entered. This state depends on the information. For single-
point indications, the condition is 0 or 1. For double-point indications, the bit combinations 00, 01, 10 or 11
are possible. Siemens recommends indicating 00 as disturbed position with outage of the data connection.
You can transfer up to 250 customer-specific indications and measured values per device.
NOTE
i The constellation measured values are only available for the FG Line.
Each device in the device combination determines measured values predefined by Siemens, known as constel-
lation measured values. You can find the constellation measured values in the DIGSI 5 information routing
under the FG n Device protection comm. > Constell. measured values. The following measured values and
indications are issued for each device:
Measured Value Meaning
(_:1351:6811:302) Vph This measured value shows the voltage of the 3 phases that is synchronized
with all devices of the device combination. The absolute value and angle are
issued for each phase.
(_:1351:6811:303) Iph This measured value shows the current of the 3 phases that is synchronized
with all devices of the device combination. The absolute value and angle are
issued for each phase.
(_:1351:6811:300) Dev.adr. This indication shows the device address. This allows you to assign the
measured values and the circuit-breaker position in a better way.
(_:1351:6811:301) CB This indication shows the position of the local circuit breaker and can have
the following values:
• 0:
The switch position of the local circuit breaker is unknown.
• 1
The local circuit breaker is open.
• 2
The local circuit breaker is closed.
3.6.5.11 Settings
3.6.6.1 Overview
The advanced protection communication contains all functionalities of the classic protection communication.
The view of parameters and indications is structured differently in DIGSI 5. In addition, the advanced protec-
tion communication supports the IP-based communication protocol.
You can easily change the number of devices in the device combination. Further differences are in the support
of external synchronization sources.
In the Global DIGSI 5 library, you can find the available function groups for the advanced protection communi-
cation in the Advanced protection communication folder. The following function-group types can be instan-
tiated:
[dw_advanced_protcom_compl_system, 2, en_US]
(1) The following applies for the FG Line and the FG Voltage/Current 3-phase: You must route the
connection between the protection FG and the FG Protection communication in DIGSI 5.
(2) You must assign a channel to the protection interface, see Parameter: PI assignment, Page 156.
• FB Device combination
• 1 or 2 FBs for the External synchronization of the transmitted measured values by an external synchro-
nization pulse (1-second pulse, PPS) or via the IEEE 1588 synchronization protocol
You can find the FB External synchronization in the Global DIGSI 5 library under Extended protection
communication > Synchronization.
• The FB Remote data is instantiated automatically, as soon as you configure remote data.
[dw_structure_FG_protcom_advanced, 1, en_US]
Device Combination
The function Device combination manages the devices that exchange data via the protection communica-
tion.
The following FBs are preconfigured in the device combination:
• FB General
Protection Interface
The FB Protection interface transmits and receives signals and measured values to/from the partner device.
For this, the protection interface uses the channel of a communication module.
External Synchronization
Measured values that are acquired and exchanged in the devices at the same time, with microsecond accuracy
are transmitted via the protection communication. The measured values can be synchronized as follows:
• Externally via
– An external, synchronous pulse 1-second-pulse (PPS)
– Via the IEEE 1588 protocol
If you want to use an external synchronization, you must instantiate the FB External synchronization.
You can use a different synchronization procedure for the 2nd protection interface than for the 1st
protection interface.
Remote Data
If you want to exchange selected and user-specific data or measured values via the protection communication,
you must use the Remote data function. If you route a specific signal or a measured value to the protection
communication, the device automatically creates the Remote data functionality. The routed signals are then
transmitted and received via the protection interface. The available bandwidth limits the amount of remote
data that can be transmitted.
• The further parameterization depends on the selected communication module and is described in the
following under:
– Advanced Protection Interface for a USART Communication Module, Page 153
– Advanced Protection Interface for an Ethernet-BD Communication Module, Page 155
[sc_USART_01, 1, en_US]
Figure 3-82 USART Communication Module: Selection of the Protocol Advanced Protection Interface
After selecting the protocol, click Settings in the right column to get to the connection settings of the USART
protection-interface module for channel 1.
[sc_USART_02, 1, en_US]
Figure 3-83 USART Communication Module: Settings for the Advanced Protection Interface
NOTE
i For safety reasons, you cannot route 2 protection interfaces from the same device combination to one
channel, as this results in apparent redundancy.
[sc_ETH-BD_01, 1, en_US]
Figure 3-84 Ethernet-BD Communication Module: Selection of the Protocol Advanced Protection Interface
After selecting the protocol, click Settings in the right column to get to the connection settings of the
Ethernet-BD communication module for channel 1.
[sc_ETH-BD_02, 1, en_US]
Figure 3-85 Ethernet-BD Communication Module: Settings for the Advanced Protection Interface
With the UDP port parameter, you set the value of the destination port in the UDP header of the protection-
interface IP messages. You must set the same value for the parameter UDP port for all protection devices of
a device combination that use the IP-based protection interface. Different device combinations can use the
same value for the UDP port parameter. Normally, the default setting can always be applied. It can be neces-
sary, for example, due to firewall policies, to configure a UDP port that differs from the default setting.
Parameterize the IP address of the Ethernet-BD communication module in the properties of the module.
[sc_IPadr, 1, en_US]
Figure 3-86 Parameterization of the IP Address for the Ethernet-BD Communication Module
The configuration and parameterization of the protection-interface communication module is now complete.
Parameter: PI assignment
[sc_WSselect, 1, en_US]
NOTE
i TheDifference Tx and Rx time parameter only visible if the Line differential protection function is
instantiated and the parameter Synchronization is not set to External synch. only.
NOTE
i If you use a multiplexer with a C37.94 interface as a communication medium, Siemens recommends a
setting value of 0.25 ms to 0.6 ms.
Parameter: Synchronization
NOTE
i If the protection interface is connected to a channel on a USART communication module (see Parameter: PI
assignment, Page 156), the external synchronization is used to take into account the signal-transit times in
the transmission and receive direction.
If the external synchronization fails for a short time, for example, due to a receiving interference or an
unfavorable satellite position for a brief period, the internal synchronization via the telegram measurement
is still active.
NOTE
With the external synchronization, the time synchronization of the measured values with microsecond accu-
racy is possible through an external synchronization source.
The parameter FB External synchron. is only visible if you have instantiated at least 1 FB External
synchronization from the Global DIGSI 5 library into the FG Protection communication. You can instantiate a
maximum of 2 FBs for external synchronization.
With the parameter FB External synchron., you specify whether the protection interface uses the FB
Ext. synchronization 1 or the FB Ext. synchronization 2 for the synchronization. You parameterize the
synchronization source in the corresponding FB External synchronization, see 3.6.6.9 Setting Notes for
External Synchronization.
NOTE
NOTE
i If you use PPS electrical (port G) as the synchronization source, the synchronization status (SmpSynch) is
permanently set to global.
If you use PPS optical (USART) as the synchronization source, you can use the parameter (_:107)
Received. SmpSynch to set the synchronization status to (SmpSynch) local or global.
For a synchronization with microsecond accuracy, for example, for the Line differential protection, set the
parameter (_:107) Received. SmpSynch = global.
Indication Description
initialized: The protection interface is not connected and is in the Initial state.
PI connected: The protection interface is connected to the protection interface of the
partner device.
PI data fault: The protection interface has not received any valid telegrams for the time
set in parameter (_:5161:107) Disturbance alarm after.
PI data failure: The protection interface has not received any valid telegrams for the time
set in parameter (_:5161:108) Transm. fail. alarm after.
not existing: The protection interface has not been assigned to a communication
channel.
NOTE
i You can reset the measured values of the protection interface directly in the device. Proceed as follows:
Device functions > Protection comm. (Type x) > Protection interface y > Reset measured values.
EXAMPLE:
For a device combination consisting of 3 devices in a ring topology with 2 fiber-optic connections (2 MBit/s)
and a 64-kBit/s connection, set the smallest value (64 kBit/s) in each device.
Apart from the default value, you can set the following bit rates:
• 128 kBit/s
• 512 kBit/s
• 2048 kBit/s
NOTE
i If you use optical fibers for all protection connections, set the value to 2048 kBit/s.
Connection mode
NOTE
i As soon as a SIPROTEC 4 device is present in the device combination, the SIPROTEC 5 devices must operate
in a compatibility mode. For this reason, the Connection mode parameter must be set to the same value
in all SIPROTEC 5 devices in the device combination. Select the type of SIPROTEC 4 device from the
following table:
NOTE
i In the Global DIGSI 5 library, the function groups Protection communication type 1 (line diff. protection)
and Protection com. Type 2 are available for the advanced protection communication. When instantiating
the respective function group, the corresponding type of the device combination is automatically pre-
instantiated.
NOTE
i If you have instantiated the FG Protection com. Type 2, the Device combination Type 2 is automatically
pre-instantiated in this FG and the Line differential protection function is not supported.
If you subsequently want to use the Line differential protection function in the device combination of the
FG Protection com. Type 2, proceed as follows:
• In the DIGSI 5 project tree, delete the function block Device combination from the FG protection
comm. (type 2).
• Instantiate the function block Device combination type 1 (line diff. protection) from the Global
DIGSI 5 library into the FG Protection com. Type 2.
• Reroute the indications of the device combination in the DIGSI 5 information routing.
All other parameterizations and routings are retained!
NOTE
i The device with the Device index = 1 is the timing-master device in a device combination.
If all other devices in the device combination are to obtain their time from the timing-master device,
consider the following
• Parameterize the other devices in such a way that they get their time from the timing-master device
via the protection connections.
For more information, refer to 3.7.3 Function Description. Select Protection interface as the
adjustable synchronization option.
In the timing-master device, you must not set the protection interface as the synchronization source!
NOTE
i If the preset values do not fit, Siemens recommends the following procedure:
Define a number for the device combination that is unambiguous in your area of responsibility and that
must be at least 2 digits, for example, 100. The setting value of the parameter Address in Device
combi. is then calculated as follows: Number in the device combination + Device index.
For device 2, this leads to Address in Device combi. = 102.
Parameter: IP Address
NOTE
i If all devices of a device combination are equipped with an Ethernet-BD communication module and use
the IP communication, you must enter the IP addresses for all other devices in the device combination here.
The topology detection automatically sets a ring or chain topology.
NOTE
i If you have a hybrid configuration, that is not all protection connections of a device combination use the IP
communication, you must observe the following when setting the IP addresses:
• First define the order for the communication between the devices. Define chain or ring topologies for
this purpose.
The defined topology results in the partner devices for each device, with which the device communi-
cates directly.
Only set the IP addresses for the partner devices that are equipped with an Ethernet-BD communica-
tion module here.
• You can find examples of the parameterization of the IP addresses in hybrid configurations in the
chapters 3.6.8.4 Device Combination of 3 Devices and Hybrid Communication Media
and3.6.8.5 Device Combination of 6 Devices and Hybrid Communication Media.
Indication Meaning
(_:3321:2311:301) The devices form a topology via the protection connections. This indication
Status of topo. recog. shows the status of the topology detection and can have the following
values:
• Unknown:
The topology is unknown.
• Invalid:
The detected topology is not supported.
• Transient:
The topology has just been modified.
• Valid:
The topology has been detected. The indication Devices form
shows the type of the detected topology.
(_:3321:2311:302) The indication shows whether all configured devices in the device combina-
Topology is tion communicate with each other via the protection connections. The indi-
cation can have the following values:
• Unknown:
The topology is unknown.
• Incomplete:
At least one device in the device combination does not communicate
via the protection connections.
• Complete:
All configured devices in the device combination communicate via the
protection connections.
Indication Meaning
(_:3321:2311:303) This indication shows the type of the detected topology that the devices in
Devices form the device combination form via the protection connections. The indication
can have the following values:
• Unknown topol:
The topology is unknown.
• Chain topology:
The devices and their protection connections form a chain topology.
• Ring topology
The devices and their protection connections form a ring topology.
(_:3321:2311:304) The indication shows the number of devices that communicate via the
Number of detect. dev. protection connections in the device combination.
• 0:
The switch position of the circuit breaker is unknown.
• 1
The circuit breaker is open.
• 2
The circuit breaker is closed.
NOTE
i The constellation measured values are only available for the FG Line.
Each device in the device combination determines measured values predefined by Siemens, known as constel-
lation measured values. You can find the constellation measured values in the DIGSI 5 information routing
under the FG Protection comm. (Type x) > Device combination > Device x. The following measured values
and indications are issued for each device:
• Via a high-precision electrical synchronous pulse (PPS electrical (Port G), 1-second pulse) from a
satellite receiver at the time-synchronization interface (Port G)
• Via a high-precision optical synchronous pulse (PPS optical (USART), 1-second pulse) from a satel-
lite receiver at a USART communication module
With external synchronization, you can measure and display the signal-transit time of the transmission and
receive path separately. This allows you to achieve maximum sensitivity even with unequal (unbalanced)
signal-transit times in communication networks with the line differential protection. For the transmission of
protection data in the type 2 protection communication, different signal-transit times do not play a role.
If an FB External synchronization is instantiated, the parameter Synchronization is visible in the FB
Protection interf.. With this parameter, you establish the connection between the protection interface and
the type of external synchronization. See 3.6.6.5 Setting Notes for the Protection Interface.
If you use 2 protection interfaces in the FG Protection comm., you can set a different synchronization source
for each protection interface if required. For this use case, you must instantiate 2 FBs External synchroniza-
tion into the FG Protection comm. and set the desired synchronization source separately.
NOTE
i The possible setting options of the parameter Synchronization source depend on the configuration
of the protocol for the respective channel of the communication module.
To display the selection text for the selection of an optical synchronous pulse, you must configure the protocol
PPS on a USART communication module as follows:
[sc_PPS, 1, en_US]
Figure 3-89 Configuration of the Optical Synchronous Pulse (PPS) on a Channel of a USART Communication
Module
To display the selection text for the selection of the protocol IEEE 1588, you must configure the protocol IEEE
1588 on an Ethernet-BD communication module as follows:
[sc_1588, 1, en_US]
Figure 3-90 Configuration of the Protocol IEEE 1588 on an Ethernet-BD Communication Module
The setting options for the parameter Synchronization source then look as follows, for example:
[sc_syncopt, 1, en_US]
NOTE
i You can select different synchronization sources for the same protection connection in the devices
involved, for example, the synchronization via the IEEE 1588 protocol in device 1 and via the protocol PPS
electrical in device 2.
Siemens recommends using the same synchronization source for the same protection connection. If it is
not possible to use the same synchronization source, check the differential current in the line differential
protection in the mode Test on all devices. If the differential current is not in the expected range, the set
synchronization sources are not synchronous to each other and therefore not usable.
NOTE
i For detailed information on the communication protocols, refer to the SIPROTEC 5 manual Communication
Protocols.
NOTE
i The inaccuracy of the synchronization source enters the stabilization of the Line differential protection as
an error signal.
This means that greater inaccuracy increases the calculated stabilization quantity and makes the Line
differential protection less sensitive.
If IEEE 1588 is used as the synchronization source in the synchronization status SmpSynch = global, accu-
racy values are supplied with the synchronization signals and the parameter Max. inaccuracy is not used.
If the supplied accuracy values become invalid, the value set in the parameter Max. inaccuracy is used.
If the synchronization source IEEE 1588 works in the synchronization status SmpSynch = local, then the
value set in the parameter Max. inaccuracy is used as permanently available inaccuracy.
If PPS electrical (Port G) or PPS optical (USART) are used as synchronization source, then the value set in the
parameter Max. inaccuracy is used as permanently available inaccuracy.
If a USART communication module with the PPS protocol and the PPS generator operating mode is also used
as a synchronization source at the same time, the value set in the parameter Max. inaccuracy is used as
permanently available inaccuracy.
Indication Description
(_:501) >PPS pulse loss The indication (_:501) >PPS pulse loss is only visible with the
following setting options of the parameter (_:117) Synchronization
source:
• G:Timesynchron.PPS
• [Port]:USART-AD-1FO.Channel x.PPS
• [Port]:USART-AE-2FO.Channel x.PPS
The binary input (_:501) >PPS pulse loss can be used to signal an
externally detected failure in the PPS synchronous pulse, for example, an
error message from the satellite receiver. If the binary input (_:501)
>PPS pulse loss is set, this leads to the indication (_:304)
Synchronization loss. The external synchronization detects immedi-
ately that there is a problem with the connected synchronization pulse.
Otherwise, the problem will only be noticed after approx. 2.1 s – after the
test for synchronous-pulse failure.
(_:304) Synchronization The synchronization has failed. This can be due to a problem with the
loss synchronization source.
The indication (_:304) Synchronization loss shows that the
synchronization has failed. This can be due to the following reasons:
[lo_pps_syn, 2, en_US]
Figure 3-92 Logic for the Generation of the Indication >PPS pulse loss
3.6.6.12 Settings
If protection functions want to use the protection interfaces in a protection function group, you must route
the connection of the protection function group, for example, the FG Line 1, with a function group Protection
communication in DIGSI 5. Then, each protection function in the FG Line 1 can use the protection communi-
cation.
Route the connection between the FG Line and the FG Protection communication in DIGSI 5 as follows:
Project tree > Function-group connections > Tab Protection FG ↔ Protection FG. Right-click to route the
connection in the desired line/column.
[sc_PDC_rout1, 1, en_US]
Figure 3-93 Routing of the Connection between the Protection FG and the FG Protection Communication
in DIGSI 5
NOTE
i If only one protection function group and one FG Protection communication are instantiated in the
device, DIGSI 5 connects both function groups automatically.
3.6.8.1 Overview
The advanced protection communication supports the IP communication via MPLS15 communication
networks.
• If existing systems are to be upgraded for protection-interface communication via IP, you must retrofit an
Ethernet-BD communication module in the respective SIPROTEC 5 devices.
• In a device, only one Ethernet-BD communication module can be used per device combination.
• However, another device combination can use the same Ethernet-BD communication module of the
device.
The following application examples show what you must consider when using the IP communication via MPLS
communication networks.
• You can use the redundancy mechanisms of the LAN and the Ethernet-BD communication module (PRP,
HSR, RSTP). In this case, the redundant communication route runs through the same Ethernet-BD
communication module.
• You can set up a 2nd communication connection via a physically separate path. It is best to use a
different medium for this, for example, a fiber-optic direct connection, a direct cable connection (pilot
wire), or a connection based on C37.94. That is, for the 2nd communication connection, you must use
another communication module in each device. The following figure shows this case from a physical and
logical view:
[dw_network_with_2-device_redundant-comm, 1, en_US]
Figure 3-94 Device Combination with 2 Devices and Redundant Communication Connection
[dw_network_with_3-device_redundant-comm, 1, en_US]
The Protection interface 1B takes over the settings of Protection interface 1, that is Protection interface 1B
does not have its own settings view. The Protection interface 1B has its own indications and measured
values, which you can see in the information routing.
NOTE
i If you use 3 devices in the device combination with IP communication, the aim of the topology detection is
to form a ring topology, as in addition to a redundant connection, shorter transmission times are also
possible.
If you have instantiated a 2nd protection interface, for example to establish a communication connection via
another medium, the device hides the Protection interface 1B.
NOTE
i In the following cases, the Protection interface 1B becomes inactive and does not have any messages or
measured values:
device are the 2 devices previously present in the system. This device combination is to be extended by adding
the right SIPROTEC 5 device. The communication between the middle and the right device is to take place via
an IP communication network.
[dw_network_with_3-device_mixed-comm, 1, en_US]
Figure 3-96 Device Combination with 3 Devices and Hybrid Communication Media
For this configuration of a 3-device chain topology, you must configure a device combination with 3 devices
in all devices.
In the middle device, an Ethernet-BD communication module is additionally required. Configure the protocol
Advanced protection interface in the properties of the Ethernet-BD communication module. Instan-
tiate the function block Protection interface 2 in the FG Protection communication. Assign the Ethernet-BD
communication module to the Protection interface 2.
The device on the right must also have an Ethernet-BD communication module. Also configure here the
protocol Advanced protection interface in the properties of the Ethernet-BD communication module
and assign the Ethernet-BD communication module to the Protection interface 1. Protection interface 1B is
created here as a special feature, but it is not used.
If a redundant communication connection is required for this configuration, Siemens recommends estab-
lishing a 3-device ring topology. For this purpose, you must connect the left and right devices via another
communication channel. This creates the 3-device ring topology. The following figure shows this configura-
tion:
[dw_3-device_and_mixed-comm, 1, en_US]
Figure 3-97 Device Combination with 3 Devices and Hybrid Communication Media and Redundant
Communication Connection
The SIPROTEC 4 device (left device) does not support any IP communication. In this case, you must switch to
another communication medium and retrofit a corresponding SIPROTEC 4 communication module. In any
case, the communication medium used is also supported by the SIPROTEC 5 device on the right side, by retro-
fitting a corresponding equivalent communication module there. Configure this communication module with
the protocol Advanced protection interface, add an additional Protection interface 2 to the FG
Protection communication. Assign the Protection interface 2 to the communication module.
[dw_network_with_6-device_redundant-comm, 1, en_US]
Another example shows 2 device groups whose devices are connected to each other via IP networks. The 2
device groups are connected to each other by a different communication medium. The topology detection in
turn forms a 6-device chain topology.
To establish this communication route, you may only parameterize the IP addresses of their direct communica-
tion partners in the devices. The following example applies:
[dw_network_with_6-device, 1, en_US]
NOTE
[dw_non-supported-confic_network_with_3-device, 1, en_US]
NOTE
i If you use the IP communication, the aim of the topology detection is to form a chain topology if there are
4 or more devices. For certain configurations, the topology detection cannot form a working chain
topology.
The following figure shows an example of a device combination with 6 devices and hybrid communication
media. In this case, the topology detection cannot form a functioning 6-device chain topology.
[dw_non-supported-confic_network_with_6-device, 1, en_US]
Timely recording of process data requires precise time synchronization of the devices. The integrated date/
time synchronization allows the exact chronological assignment of events to an internally managed device
time that is used to time stamp events in logs, which are then transmitted to a substation automation tech-
nology or transferred via the protection interface. A clock module internal to the device and having battery
backup is synchronized cyclically with the current device time so that the right device time is available and
used even in case of auxiliary-voltage failure. At the same time, this permits hardware-supported monitoring
of the device time.
The integrated date/time synchronization is a supervisory device function. Setting parameters and indications
can be found in the following menus for the DIGSI and the device:
Set date and time:
• DIGSI: Online access -> Interface -> Device -> Device Information -> Time Information
• DIGSI: Project -> Device -> Information routing ->Time keeping or Time Sync.
Every SIPROTEC 5 device maintains an internal device time with date. The date and time can also be set on the
device via the on-site operation panel or via DIGSI 5. Within a system, or even beyond, it is usually necessary to
record the time of process data accurately and to have exact time synchronization of all devices. For SIPROTEC
5 devices, the sources of time and synchronization options can be configured.
• Telegram
The time is synchronized via a telegram with an appropriately configured communication interface in
accordance with the IEC 60870-5-103 or DNP3 protocol.
• Ethernet
The time synchronization is done via Ethernet-based SNTP protocol (Simple Network Time Protocol), for
example with IEC 61850 stations or via IEEE 1588. If you enable both services during configuration of
Ethernet interfaces, these protocols are available as an option for the time synchronization.
• Protection interface
The time synchronization takes place via the protection interfaces configured for your SIPROTEC 5 device.
Here, the timing master takes over the time management.
• 2 time sources can be taken into consideration with the SIPROTEC 5 devices. For each time source, the
synchronization type may be selected based on the options provided.
• Time source 1 takes precedence over Time source 2, that is, Time source 2 will be effective for
the synchronization of the device time only if Time source 1 fails. If only one time source is available
and it fails, then only the internal clock continues unsynchronized. The status of the time sources is indi-
cated.
• For every time source, it is possible to define via the Time zone time source 1 parameter (or Time
zone time source 2) if this source transmits its time by UTC (universal time) or if the settings corre-
spond to the local time zone of the device.
NOTE
i Make sure that the settings for the time sources coincide with the actual hardware configuration of your
SIPROTEC 5 device. In any event, incorrect settings cause the status indications of time sources to pick up.
• Day.Month.Year: 24.12.2009
• Month/Day/Year: 12/24/2009
• Year-Month-Day: 2009-12-24
NOTE
i • For time sources that transmit the status of the switch to daylight saving time, this will be taken into
account automatically when creating the internal device time in the UTC format. The differential time
of the daylight saving time set in the device (parameter Offset daylight saving time) is taken into
consideration. However, in contrast, the settings of the start of daylight saving time and end of the
daylight saving times are ignored when converting into the device internal UTC format.
• For active time sources, it is not possible to set the time via the device display or DIGSI 5.An exception
is setting the calendar year for active time protocol IRIG B.
Indication Description
Device: This indication signals a high difference between the
Clock fail internally managed time and the time of the clock
module that is not permissible. The pickup of the indi-
cation can point to a defect in the clock module or to
an unacceptable high drift of the system quartz
crystal. The time maintained internally is marked as
invalid.
Time management: This indication signals whether daylight saving time
Daylight saving time has been enabled.
Time management: This indication signals that the device time has been
Clock set manually set manually via the on-site operation panel or via
DIGSI 5.
Time synchronization: These 2 indications signal whether the active time
Status time source 1 sources are recognized as valid and active from the
Status time source 2 device point of view. When the indications pick up, it
can also be an indication that an incorrect configura-
tion of the port or channel numbers was done at the
on-site operation panel.
Time synchronization: This indication signals after the parameterized time
Time sync. error Fault indication after that synchronization
using an external time source has failed.
Time synchronization: This indication signals that a Leap second has
Leap second occurred during time synchronization using an
external GPS receiver (protocol variant IRIG B
005(004) with extension according to IEEE
C37.118-2005).
Time synchronization: This indication signals that the device is synchronized
High accuracy with an accuracy better than 1 μs The indication is
only of significance when the PMU function is used.
NOTE
i In case of a missing or discharged battery, the device starts without active external time synchronization
with the device time 2011-01-01 00:00:00 (UTC).
For the device, DIGSI 5 provides a compact overview of the status of the time synchronization of your
SIPROTEC 5 device in online mode. All displays are updated continuously. You can access the overview in the
project-tree window via Online access.
DIGSI: Online access -> Interface -> Device -> Device Information -> Time Information
[sc_time_dg, 1, en_US]
• Whether the device time is currently synchronized from the time source
The lower section displays the device time, which is continuously updated. If the internal device time and the
infeed time source were synchronous at the time of telegram receipt, both displayed times are identical.
NOTE
i All times displayed (also the time source) take into consideration the local time settings (zone and daylight
saving time of the device) in the form of a numerical offset for UTC (universal time).
• Default setting Time zone time source 1 = local, Time zone time source 2 = local
With the Time zone time source 1 and Time zone time source 2 parameters, you define the
handling of time zones of the external timer.
• IRIG-B 002(003)
The control function bits of the signal are not occupied. The missing
year is formed from the current device time. In this case, it is possible
to set the year via the online access in DIGSI 5.
• IRIG-B 006(007)
The bits for the calendar year are not equal to 00. The calendar year is
set automatically by the time protocol.
• IRIG-B 005(004) with extension according to IEEE C37.118-2005
If, in the time signal, other control function bits are occupied in addi-
tion to the calendar year, then the device takes the additional informa-
tion into consideration for leap seconds, daylight saving time, time
offset (zone, daylight saving time), and time accuracy.
Time zone time source 1 or Time zone time source 2: The
value of this setting is not evaluated by the device, since this protocol
either transmits in UTC or in the case of local time, specifies the appro-
priate offset to UTC in each set time telegram.
DCF77 Time synchronization by an external DCF 77 receiver
Time zone time source 1 or Time zone time source 2 = local
Please note: There are also clocks that generate a DCF77 signal representing
UTC. In this case, UTC must be set.
PI The time synchronization takes place via the protection interfaces config-
ured for your SIPROTEC 5 device. Here, the timing master takes over the
time management. Signal-transit times of the protection interface commu-
nication are calculated automatically.
Time zone time source 1 or Time zone time source 2 = UTC
A slave that receives a time or a SIPROTEC 5 master, receives its system time
kept in UTC.
[sc_time_zo, 1, en_US]
Figure 3-103 Settings for Time Zone and Daylight Saving Time in DIGSI
3.7.5 Settings
3.8.1 Overview
With help from user-defined function groups and user-defined functions you can group user-defined objects,
for example user-defined function blocks. 2 user-defined function blocks are available (see following figure).
[sc_udef_lib, 1, en_US]
The user-defined function block allows you to add (see following figure) single-point indications, pickup indi-
cations, operate indications (ADC, ACT), single and double commands, commands with a controllable whole
number as well as measured values. You can assign the group a superordinate name (for example process
indications for a group of single-point indications which are read via binary inputs). This function can be deac-
tivated using the mode. The standby mode is also analyzed or displayed.
The user-defined function blocks can be instantiated at the highest level (alongside other function groups) as
well as within function groups and functions.
In addition, there is a user-defined function block [control]. Alongside the aforementioned possibilities
presented by user-defined function blocks, this block offers additional tests for user-defined control signals,
for example SPC or DPC.
[sc_user, 1, en_US]
Figure 3-105 Information Routing with Incorporated User-Defined Function Block: Process Indications and
some Single-Point Indications
The following data types are available for user-defined objects in the DIGSI 5 library under the heading User-
defined signals. Additionally, a folder for external signals is available (see chapter 3.8.5 External Signals).
User-Defined Signals
[sc_LB_userdefsig, 1, en_US]
EXAMPLE
Acquisition using binary input, further processing in a CFC and/or signaling using an LED.
[sc_spsfas, 1, en_US]
Figure 3-107 Single-Point Indication SPS Unsaved (Example: 7KE85 Fault Recorder)
EXAMPLE
Acquisition of a disconnector or circuit-breaker switch position.
EXAMPLE
The output of the CFC block ADD_D can, for example, be connected with the data type INS. The result can be
shown on the display of the device.
NOTE
i Additional data types can be found under other headings in the DIGSI 5 library as well as in the corre-
sponding function blocks. This applies to the following data types:
• Transformer taps
• Metered values
The status indications for the ACT data type are built as follows:
[lo_ACT-information, 1, en_US]
[lo_ACD-information, 1, en_US]
Table 3-20 Building of the Direction Information for the Data Type ACD
Pulse-Metered Values
Pulse-metered values are available as data types BCR (Binary Counter Reading) in the DIGSI library under User-
defined Functions.
.
The following data types are also used in the system, but they are not contained in the information catalog for
general use:
• SEQ (Sequence)
User-defined signals of different types (see Figure 3-110) are available for GOOSE Later Binding. After instan-
tiation in a logical node, an external reference is generated during IID export and provided to a IEC 61850
system tool (for example, System Configurator) for GOOSE Later Binding (according to the Later-Binding
procedure specified in IEC 61850-6).
[sc_LB_extsign, 1, en_US]
NOTE
i Consider the chapter on GOOSE Later Binding in the DIGSI Online Help. User-defined signals exist as
external signals and as preconfigured inputs that have been activated via the GOOSE column.
Input signals can be filtered to suppress brief changes at the binary input. Chatter blocking can be used to
prevent continuously changing indications from clogging the event list. After an adjustable number of
changes, the indication is blocked for a certain period.
The settings for indication filtering can be found at the individual signals. The next figure shows the settings
using the example of a controllable (circuit-breaker switch position).
NOTE
i The software filtering time is available only for the circuit breaker and disconnector in the controllable
Cmd. with feedback (control function block), as this is used for logging purposes. The controllable posi-
tion (circuit breaker or disconnector function block) is used for interlocking conditions and must always
show the unfiltered position of the switching object.
[sc_lposi, 1, en_US]
The setting range for the Software filter time parameter ranges from 0 ms to 100 000 ms in ms incre-
ments. The Retrigger filter check box can be used to select whether to restart the filtering time when-
ever a status change is performed within the software filtering time. When activated, the Indication
timestamp before filtering check box backdates the time stamp by the set software filtering time. In
this case, the time stamp corresponds to the actual status change of the signal. If you activate the Suppress
intermediate position check box, the intermediate position is suppressed for the duration of this soft-
ware filtering time.
If you leave the software filtering time at 0 ms, the time for the suppression of the intermediate position is
also 0 ms. The activated Suppress intermediate position check box then remains ineffective.
If you do not activate the Suppress intermediate position check box, the software filtering time
affects the on, off, intermediate, and disturbed positions of the circuit breaker or disconnector switch.
With the parameter Spontaneous position changes filtered by:, you set how such position
changes are to be filtered. Spontaneous position changes are caused by external switching commands, for
example. If you select the General software filter setting, the general settings for software filtering of
spontaneous position changes and for position changes caused by a switching command apply. The settings
for spontaneous position changes then cannot be edited. A separate filtering for spontaneous position
changes is activated with the Spontaneous software filter setting and you can edit the settings for
this.
Chatter blocking can be activated or deactivated as an input parameter, for example as a parameter of the
position in the Circuit breaker or Disconnector function block.
[sc_flatte, 1, en_US]
The settings for the chatter blocking function are set centrally for the entire device in DIGSI. They are acces-
sible as settings in the General function group (see the following figure).
The chatter-blocking settings have the following meaning (see also Figure 3-113 and Figure 3-114 in the
examples shown in the following):
[dw_chatter-block-01, 1, en_US]
Figure 3-113 Signal Change during Chatter Blocking with too Important Number of Signal State Changes
During 2nd Subsequent Test Time
(1) The input signal is permanently blocked starting from this point in time.
[dw_chatter-block-02, 1, en_US]
Figure 3-114 Signal Change during Chatter Blocking with Permissible Number of Signal State Changes
During 2nd Subsequent Test Time
During commissioning, maintenance, or testing, a brief interruption of the connection between the logical
signals and binary inputs may be useful. It allows you to manually update the status of a switching device that
is not providing feedback correctly. Before this can take place, you must first set acquisition blocking.
To set the acquisition blocking, proceed as follows:
• Using the navigation keys, move in the main menu of the device display to
Commands→Equipment→Aq.blkman. update.
• Select the appropriate device (for example, a circuit breaker) from among the several switching devices
using the navigation keys.
• Enter the confirmation ID (not relevant for active role-based access control (RBAC) in the device).
[sc_detection, 1, en_US]
Manual updating of the switching device is possible from within the same menu.
• Select the switching device setting to be manually updated using the navigation keys (for example, off,
Figure 3-117).
[sc_status, 1, en_US]
[sc_statu2, 1, en_US]
[sc_statu3, 1, en_US]
NOTE
i For security reasons, manual updating is possible only directly through the on-site operation panel of the
device and not through DIGSI 5.
NOTE
i Setting acquisition blocking and the subsequent manual updating are also possible via the IEC 61850
system interface.
You can set acquisition blocking also via a binary input. If you want to put in the feeder or the switching
device in revision, you can set the acquisition blocking with an external toggle switch for one or more
switching devices. For this purpose, every switching device in the Switch function block (circuit breaker or
disconnector switch) has the input signal >Acquisition blocking. This signal can also be set from the
CFC.
[sc_beerfa, 1, en_US]
Figure 3-119 Input Signals >Acquisition Block and >Release Acquisition Block & Manual
Updating on the Switching Device
With acquisition blocking, the feedback does not correspond to the switch position of the disconnectors (for
example, when checking the auxiliary contacts or switched off auxiliary voltage for disconnector position indi-
cation). In this case, the previous disconnector status is frozen and remains the same until removing the func-
tion. Monitoring of the disconnectors and the resulting indications are suppressed for this time period.
NOTE
i Interlockings are carried out with the status changes of the switching device. Remove acquisition blocking
again manually. Otherwise, position changes of the switching device are not detected and interlockings are
ineffective.
If the acquisition blocking and the manually updated position are set using the operation panel of the device
or the system interface IEC 61850, these are retained until the acquisition blocking is manually deactivated.
When you initially start the device, the acquisition blocking is deactivated.
Except for a restart, the acquisition blocking and the manually updated position are retained.
If the acquisition blocking is activated via the input signal >Acquisition blocking, it is retained as long as
the binary input is active.
To set the acquisition blocking of a switching device, the following sources are possible:
NOTE
i When the acquisition blocking is activated or the switching device updated manually while the entire
device or the switching device is in test mode, these states are not saved. The acquisition blocking and the
manual updating are not retained after a restart.
The acquisition blocking and the manual update for the circuit breaker, the disconnector, and the tap changer
are reset by way of the >Reset AcqBlk&Subst binary input. Setting acquisition blocking and manual
update is blocked with the input activated.
In addition to the switching commands, which are issued as pulse commands, and stored for the standard
switching devices (circuit breaker, disconnector switch), persistent commands are also possible. In this case, a
distinction must be drawn between controllables with the Continuous output operating mode and a stored
signal output that is immune to reset.
You can change a controllable from pulse to persistent command with the Command output parameter.
[sc_command, 1, en_US]
Select Pulse output or Continuous output for the command output type. If a persistent command is
selected, the Pulse parameter is irrelevant.
3.9.4.1 Overview
In the case of multibay functions, a device uses information from one or more other devices. For some applica-
tions, it may be necessary for you to remove a device with all effective functions temporarily from the plant
and even to switch it off. These applications are, for example:
• Maintenance work
• System upgrades
NOTE
i If you need to remove a device temporarily from the plant, you must log off the device.
Protection functions distributed to several devices operate in a healthy manner with the remaining devices
only if you have logged off the device.
• Via the binary inputs, general: >Dev. funct.logout on (_:507) or >Dev. funct.logout off
(_:508)
You can find the controllable and the binary inputs in the DIGSI 5 project tree under Name of the device →
Information routing in the working area in the General block.
During the log-off process, the device checks whether all conditions for a logout have been met. If the condi-
tions for the log off have not been met, the logout is rejected.
The logout is rejected under the following conditions:
• The devices are communicating via the protection interface and switching off the device leads to an
interruption in protection-interface communication.
NOTE
i The path used to log the device off is stored in the operational log.
Even if you switch off the device after logout, the Device logged off (_:315) state is stored.
If you want to establish the initial state again after logging off the device, you must log on the device again.
To log on the device, you must use the same option used for logout. For example, if you have logged off the
device via binary inputs, you must log it on again via the binary inputs. This applies in similar manner if you
have logged off the device via DIGSI or via on-site operation.
• Via the binary inputs, general: >Dev. funct.logout on (_:507) or >Dev. funct.logout off
(_:508)
The conditions for a successful logout of the device result from the conditions for every activated protection
function.
Logoff of a Device from a Device Combination with Communication via the IEC 61850-8-1 (GOOSE) Protocol
If devices are exchanging data using the IEC 61850-8-1 (GOOSE) protocol – for example in the case of substa-
tion interlocking – for each received data point the value of this data point can be set in the receiver device
when the transmitter device logs off. This value remains effective in the receiver device until the logout is
canceled by the transmitter device, even if the transmitter and/or the receiver are switched off in the mean-
time.
• Logging off and switching off a device in a device combination must not result in an interruption in the
protection communication.
• For series-connected topologies, the device must be located at one end of the communication chain as
otherwise the protection communication is interrupted when the device is logged off and switched off.
For this reason, devices not at one of the ends in series-connected topologies cannot be logged off.
Figure 3-122 External Push-Button Wiring for Logging off the Device
If a switch is being used for control, route the binary input >Dev. funct.logout on as H (active with
voltage) and the binary input >Dev. funct.logout off as L (active without voltage). If the
switch S is closed, the device is logged off.
Figure 3-123 External Switch Wiring for Logging off the Device
Indications
The logged-off device reports the status ((_:315) Device logged off) and cause of the logout.
If you have logged off the device using binary inputs, the indication (_:313) Logged off via BI is
issued.
If you have logged off the device using on-site operation, via DIGSI 5 or via the protection interface,the indica-
tion (_:314) Logged off via control is issued.
The indications are stored in the operational log.
3.10.1 Overview
You can set the threshold values of protection functions directly on the device or by using DIGSI 5.
An innovative design was implemented for the protection settings.
You can switchover the edit mode between the following setting views:
• Primary
• Secondary
• Percent
If you change settings in a setting view, DIGSI 5 calculates the settings of the 2 inactive views in the back-
ground. If you wish to save, for example, conversion to secondary values, then select the primary view.
Configure all the settings and switchover to the secondary view.
• First set the transformation ratios of the transformers. You can find these under Power-system data.
• In addition, set the reference parameters for the percent setting. You will find these parameters in func-
tion group .
The following setting example shows how you can change the transformer ratio in DIGSI 5, and what impact
this has on the settings in the setting views Primary and Secondary. The protection setting is shown in the
example of the Power-system data function.
The following output data are assumed:
Current transformer: 1000 A/1 A
The following figure shows the protection setting in the Power-system data function in the secondary view.
[sc_mod_s_bbp-oh, 1, en_US]
When you click the green arrow in the setting sheet at the upper left, you get to the window for switching
over to the setting view (see the following figure). Select the setting view you prefer.
[sc_mod_u_bbp-oh, 1, en_US]
In the example, the current-transformer ratio changes from 1000 A/1 A to 1000 A/5 A. Change the secondary
rated current of the current transformer in the setting sheet of the transformer data from 1 A to 5 A (Edit
mode: Secondary). If you change the transformer data, a window will appear (see the following figure) that
will ask you for the action desired.
[sc_fragewbbp, 1, en_US]
Figure 3-126 Query after Changing the Transformer Data (Setting View: Secondary)
If you have already set the settings in the secondary view by including the new transformation ratio of the
transformer in the calculation, then answer the question with No. In this case, the protection settings in the
secondary view remain unchanged. DIGSI 5 recalculates the settings (threshold values) of the primary view.
In the delivery setting, the device is preset to secondary values. Only secondary values can be set directly on
the device.
If you change transformer data directly on the device, it is not followed by a query, like in DIGSI 5 (see
previous image). Instead, the device assumes that all settings remain unchanged in the secondary view.
NOTE
i If the device works with IEC 61850 protocol, then change the transformer data only via DIGSI 5 and not
directly on the device. If you change the transformer data directly on the device, the IEC 61850 configura-
tion of the measurement and metered values can be faulty.
Activation
If you want to use the Settings group switching function, you must first set at least 2 settings groups in DIGSI
5 (parameter Number of settings groups > 1). You can set up a maximum of 8 settings groups. The settings
groups set in DIGSI 5 are subsequently loaded into the device.
Table 3-21 Binary Codes of the Input Signals and Applicable Settings Groups
3.11.1.5 Settings
3.11.2.1 Overview
In Device settings in DIGSI 5, you find the following general settings.
[sc_deSeDe1, 1, en_US]
[sc_deSeAl, 4, en_US]
[sc_deSeBB, 1, en_US]
The following list shows you the chapters containing the desired information.
You can find more about:
• Chatter blocking in chapter 3.9.1 Signal Filtering and Chatter Blocking for Input Signals.
• Continuous Function Chart Quality Treatment in chapter 3.4.3 Quality Processing/Affected by the User
in CFC Charts.
Under Device, you set the parameters for the device that are valid across functions.
With Test support, indications issued via communication interfaces are labeled with an additional test bit, if
this is supported by the protocol. With this test bit you can determine whether an indication is generated in a
test and whether all or individual functions of the device are in the test mode. In this manner the reactions
that are necessary in normal operation due to an indication can be suppressed in other devices that receive
these indications. You can also permit, for example, a trip command to close an energized binary output for
test purposes. Siemens recommends deactivating the Test support again after the test phase.
Parameter: Fault-display
NOTE
i The device remains in test mode during every restart until you intentionally set the device back into the
process mode or you have carried out an initial start.
You can set the process mode by switching the parameter Activate device test mode to inactive
again (removing the check mark) or by deactivating the test mode again via the IEC 61850-8-1 protocol.
NOTE
i Besides the cross device test mode, you also have the option to place an individual function or stage into
test mode depending on the supported operating modes of a function or stage. To do this, see the descrip-
tion of the relevant function or stage.
When you place an individual function or stage into the test mode, all indications issued by this function or
stage are given a test bit.
When you activate the test mode for an individual function or stage, but not the parameter
Oper.bin.outp. under test, the routed relay outputs of the function or stage are not activated by
the generated indications.
An individual function or stage remains in the test mode during every restart until you have intentionally
deactivated the test mode for this function or stage again or carried out an initial start.
NOTE
i If the Oper.bin.outp. under test parameter is inactive (default setting), the Test state of a function
or stage is changed to Test/Relays blocked.
3.11.2.3 Settings
• Process bus: for cross-device transmission of the measured values for current and voltage
• GOOSE: For cross-device transmission of the position information of disconnectors and circuit breakers,
their trip commands and additional signals
• Further information
Process Bus:
The process bus is available for the modular SIPROTEC 5 devices. The current and voltage measured values can
be transmitted across devices using the process bus. Prerequisite: a ETH-BD-2FO communication module with
the appropriate communication protocols. In the following figure, you can see the 7SS85 as an example of the
client, and the 6MU85 and other modular SIPROTEC 5 devices as merging units.
[dw_bb8_proj-71-star, 2, en_US]
Figure 3-128 Star Structure for Distributed Busbar Protection with Merging Units Connected via Optical
Fibers
Prerequisites for the Merging Units for the Distributed Busbar Protection (IEC 61850 Compliant)
You can use all modular SIPROTEC 5 devices (except the railway protection devices 7ST8x and 6MD89) and
other IEC 61850 compliant devices as merging units. The following prerequisites apply:
• All clients and merging units must have the firmware version V8.0x or higher.
• All clients and merging units must be connected to the ETH-BD-2FO communication module and must
use the process-bus protocols. These include:
– Consistent use of IEC 61850 Edition 2.x. Siemens recommends IEC 61850 Edition 2.1.
– Process-bus protocol 9-2 Merging Unit for Merging Units and 9-2 Client for clients
– Joint time synchronization. Siemens recommends the IEEE 1588 protocol.
• The current and voltage transformers suitable for the target application in the client must be present in
the merging units.
GOOSE:
As an alternative to using the local binary inputs and binary outputs of a SIPROTEC 5 device, you can use the
inputs and outputs of other SIPROTEC 5 devices and transmit them via IEC 61850 including GOOSE.
Examples of binary routings for transmission using GOOSE.
• Circuit-breaker and disconnector position information from the transmitters to the receivers
• Transmission of current measured values (SMV) as per IEC 61850-9-2 (process bus) from the merging
units
• External tripping
NOTE
i You can find these functional enhancements in the Global DIGSI 5 Library in the respective device, under
FG Circuit breaker > dBBP Function extensions. You can find the function Measuring point out of
service under Measuring inputs > Current 3-phase > dBBP Function extensions in the respective device.
• Additional Include in distributed busbar system check box for current transformers, circuit breakers,
and disconnectors in the Properties tab.
[sc_bbp8_SLE_incl, 1, en_US]
Figure 3-129 Extension in the Properties Tab if the Distributed Busbar Protection is Available
Further Information
NOTE
i Analog measured values, binary inputs, and binary outputs are routed across devices in the IEC 61850
System Configurator.
For a detailed description of how to use it as a Merging Unit/bay unit for the distributed busbar protection or
distributed busbar protection (IEC 61850 compliant), refer to the following Project Engineering chapter.
For further information on the process bus, GOOSE, IEC 61850 System Configurator, descriptions of stream
types, GOOSE Later Binding, VLAN priority, network redundancies, for example, PRP protocol or the sample
and time synchronization using IEEE 1588, refer to the Process Bus, Communication Protocols, IEC 61850
System Configurator and the DIGSI 5 Help manuals.
• Voltage Variation
• Voltage Unbalance
Voltage variation
The Voltage variation function is used for measuring and monitoring a short-duration variation of the voltage
in distribution and industrial power systems. The power-quality events such as voltage dips, swells, and inter-
ruptions in 3-phase systems are detected. By measuring the RMS value of the voltage, the function obtains the
maximum dip or swell magnitude and the duration, even in case of an interruption.
Voltage unbalance
In a 3-phase power system, the voltages are normally balanced, as well as the connected loads. In some cases,
however, the balanced conditions can be disturbed due to various influences.
Voltage unbalances can be caused by various factors:
• Unbalanced load, for example, caused by different consumers in the individual phases
• Phase failure, for example, due to a tripped 1-phase fuse or a broken conductor
• Detects the voltage-unbalance conditions in the distribution and industrial power systems.
• TDD values within the demand interval, indicated in the following as demand TDD values
If the demand TDD values exceed the threshold, warnings are generated.
You can find a detailed description of the Power quality basic functions in the device manual Merging Unit
6MU85.
4.1 Overview
4.1.1 General
Use DIGSI 5 for engineering and parameterization purposes of the devices. Create and configure the devices
according to their hardware-specific and functional design. To do this, the functions of the DIGSI 5 Libraries
are available. With the single-line configuration, you can create a topological image of your system configura-
tion and connect the equipment with the used functions. For the Single-Line Editor, you need the standard or
premium version of DIGSI 5.
In the following chapters, an example is used to describe the specific components for the engineering and
configuration of a 7SS85. You can find the basic procedure during engineering and configuration in the
manual SIPROTEC 5 Engineering Guide DIGSI 5.
You can use 7SS85 busbar protection as centralized busbar protection, as distributed busbar protection
(IEC 61850 compliant) or as distributed busbar protection with the current measured values and switch
positions detected in separate merging units and transmitted via optical fibers.
Table 4-1 Variants of the 7SS85 Busbar Protection and its Significant Features:
Topologies
[dw_bb8_proj-71-star, 2, en_US]
Figure 4-1 Star Topology for Distributed Busbar Protection with Merging Units Connected via Optical
Fibers
[dw_7ss85_HSR-ringstruktur, 1, en_US]
Figure 4-2 HSR Ring Topology for a Central Unit with Bay Units in up to 3 Rings with up to 15 Devices
At the time of publication of the manual, Siemens recommends using the HSR ring structure.
Prerequisites for the Merging Units for Distributed Busbar Protection (IEC 61850 Compliant)
You can use all modular SIPROTEC 5 devices (except the railway protection devices 7ST8x and 6MD89) and
other IEC 61850 compliant devices as merging units. The following prerequisites apply.
• All clients and merging units must have the firmware version V8.0x or higher.
• All clients and merging units must be connected to the ETH-BD-2FO communication module and must
use the process bus protocols. These include:
– Consistent use of IEC 61850 Edition 2.x. Siemens recommends IEC 61850 Edition 2.1.
– Process bus protocol 9-2 Merg.Unit for merging units and 9-2 Client for clients
– Joint time synchronization. Siemens recommends the IEEE 1588 protocol.
• The current and voltage transformers suitable for the target application in the client must be present in
the merging units.
• For distributed busbar protection, you must create all merging units in the same DIGSI 5 project as the
7SS85CU.
• All merging units require an ETH-BD-2FO communication module using the 9-2 MU 7SS85CU protocol.
• All merging units require 1 up to a maximum of 8 protection current transformers (current 4x protection)
as Measuring point I-3ph with 3-phase + IN connection type.
• A sufficient supply of function points must be available for the 9-2 MU 7SS85CU protocol and the
required functions.
The engineering example includes the following system parts with all disconnectors, current transformers,
and the circuit breaker:
• Double busbar
[sc_slbges, 2, en_US]
Figure 4-3 Engineering Example for Centralized and Distributed Busbar Protection (IEC 61850 Compliant)
Use the DIGSI 5 Single-Line Editor to configure the graphical representation of the busbars and the various
bay types. In doing this, you define the assignment of the switching devices and current transformers among
one another in the bays and the assignment to the busbars.
You can configure the following bay types:
• Feeder
4.1.5 Procedure
The following description of the procedure is limited to one option for engineering.
For engineering a busbar-protection system and configuring the devices, proceed as follows:
• Creating project and system graphically in the Single-Line Editor (SLE) or importing an existing single-line
diagram (.SSD).
[sc_bbp8_proj_10_overall, 2, en_US]
(1) Project tree with the created project and the devices it contains, including their function groups
and parameterization
(2) Single-line-configuration with the graphical representation of the busbar system and the protec-
tion devices used, including the functions and their connections to the switching devices and
current transformers in the bays.
(3) Global libraries with the device-specific functions in the upper section and the graphical single-
line elements in the lower section.
NOTE
i The prerequisite is that the required device drivers (for example Devices_BusbarProt_FW...ddd and for
distributed measured-value acquisition also other device drivers such as Devices_MergingUnit_FW...ddd)
have been imported. For more detailed information on this, refer to the DIGSI 5 Online Help.
4.1.6 Creating the Project and Representing the System Graphically in the Single-
Line Editor
• To create a new project, open the Project menu and click New. The project appears in the Project tree.
• Generate a graphical representation of the busbars and bays with their switching devices and current
transformers using the Global DIGSI 5 Library. Alternatively, you can also import an existing single-line
diagram (.SSD).
To do so, click Single-line configuration.
[sc_bbp8_proj_15_SLE_over, 2, en_US]
The graphical representation of the system in the Single-Line Editor shows the layout of the switching equip-
ment and current transformers and their connections to the busbars.
Proceed as follows:
Busbars
• Click Global DIGSI 5 library > Types > Single-line and display elements.
The available graphical elements are displayed.
• Click Horizontal busbar and drag and drop the busbar into the working area. Repeat the procedure for
the second busbar BB2.
Bay 1:
• Drag and drop the Circuit breaker into the working area. Bay 1 is generated in the working area with the
circuit breaker QA1.
• Drag and drop the Disconnector into the bay. Repeat the procedure for a 2nd disconnector. Connect
disconnector QB1 with busbar BB1 and disconnector QB2 with busbar BB2.
• Connect circuit breaker QA1 with the disconnectors QB1 and QB2.
• Drag and drop the Current transformer 3-phase into the Bay below the circuit breaker (external current
transformer).
• Click a Feeder and drag and drop it into Bay and connect it with circuit breaker QA1.
Bay 2:
• Select Bay 1, copy it (for example, <CTRL> + C), click the target position, insert it (for example, <CTRL> +
V).
• Delete the connections to circuit breaker QA1 and current transformer BE1.
• Move circuit breaker QA1 and current transformer BE1 and establish the connections again (internal
current transformer). Establish also the connections up to the busbar.
Bay 3:
• Select a bay, copy it, click the target position, and insert it.
• Change the designation for the bay, for example E03 Bus Coupler Bay.
When ordering the 7SS85, use Significant features to select the type and scope of the configurable busbar
sections. One busbar section corresponds to one protection range. You require 4 current transformers for a
measuring point.
For the centralized busbar protection, the number of configurable bays is limited by the expansion of the
device hardware. The number of no-cost bays contained in the variants of the respective Significant features
is listed in the following table.
The distributed busbar protection (IEC 61850 compliant) is functionally identical to the centralized busbar
protection. Project engineering must be performed in a similar manner in the Single-Line Editor. It is distin-
guished by the sampled measured values (SMV), switch positions, and their routings provided by the merging
units via the process bus. Considering the hardware, the current transformers are therefore not necessary, but
at least one communication module with the process-bus protocol is mandatory. Siemens recommends
configuring the 7SS85 in such a way that no more than 14 current measuring points (14 * (3-phase + IN) = 56
analog current inputs) are received by one ETH-BD-2FO communication module. For a larger number, you
need an additional communication module in the 7SS85.
A maximum of 20 measuring points are possible for central busbar protection, of which up to 4 voltage meas-
uring points are possible. Up to 24 current measuring points are possible for distributed busbar protection
(IEC 61850-compliant). Instantiate the backup protection and circuit-breaker failure protection only in the
Merging Units.
The following maximum scope is provided:
• 20 ⋅ 3-phase current measuring points locally on the 7SS85 (current transformers with the connection
type 3-phase + IN) or 24 ⋅ 3-phase current measuring points via IEC 61850-9-2
• Triple busbar
NOTE
i For the centralized busbar protection, keep in mind that as the number of current and voltage measuring
points increases, the maximum possible number of binary inputs and outputs decreases. As a result, with a
configuration having 20 current measuring points, only 43 binary inputs and 43 binary outputs are
possible. Siemens recommends in this case detecting the disconnector-switch positions with only one
binary input or using protection communication or GOOSE.
NOTE
i During project engineering of resource-intensive functions such as the VI 3ph function group, for example
with impedance protection, keep in mind that you can instantiate a maximum of 12 VI 3ph function
groups. For more information on monitoring resource consumption, see also 8.2.1 Load Model.
NOTE
i If you use 24 ⋅ 3-pole current measuring points via IEC 61850-9-2, you cannot instantiate a backup protec-
tion function in 7SS85. End-fault protection is possible, circuit-breaker failure protection or overcurrent
protection are not permitted.
In the device configuration, you first select one of the standard hardware variants, and then select one of the
Significant features. The following table shows in the column Significant features the number of possible
busbar sections and the free bays included.
Significant Features Standard Variant Applications
9 1 bus zone without discon- V1 12 I-trans- T-network, single busbar
nector image formers 1 1/2 circuit-breaker arrangement
3 bus zones without meas- 15 BIs
uring system 13 BOs
A 2 bus zones without discon- V2 16 I-trans- Single busbars,
nector image formers 1 1/2 circuit-breaker arrangement,
3 bus zones without meas- 11 BIs Double busbar/double circuit-breaker system
uring system 11 BOs with current transformer,
H switch
B 2 bus zones with discon- V2 16 I-trans- Double busbar (with or without combined
nector image formers busbar),
3 bus zones without meas- 11 BIs Single busbar with transfer busbar
uring system 11 BOs
C 6 bus zones without discon- V3 24 I-trans- Single busbars,
nector image formers 1 1/2 circuit-breaker arrangement,
3 bus zones without meas- 15 BIs Double busbar/double circuit-breaker system
uring system 15 BOs with current transformer,
Ring bus,
Meshed system
D 6 bus zones with discon- V3 24 I-trans- Double busbar (with or without combined
nector image formers busbar),
3 bus zones without meas- 15 BIs Single, double, or triple busbar or double
uring system 15 BOs busbar with transfer busbar
Gnd Only Circuit-breaker failure V3 24 I-trans- Double busbar (with or without combined
protection formers busbar),
6 bus zones with discon- 15 BIs Single, double, or triple busbar or double
nector image 15 BOs busbar with transfer busbar
3 bus zones without meas-
uring system
9 to E as above V4 19 BI As above
11 BOs The V4 standard variant is the preferred
Communication variant for the distributed busbar protection
module (ETH- (IEC 61850 compliant)
BD-2FO)
With Significant features = E, the system configuration is possible as with D but the following functions are
not available:
NOTE
i A significant feature with disconnector image is always necessary if the current transformer of a feeder
can be assigned to more than one bus zone. Line disconnector switches, bus section disconnector switches,
or disconnectors in bus couplers are also available in Significant features without a disconnector image.
The Distributed busbar protection is a distributed protection system with the central unit (CU) 7SS85 and
other SIPROTEC 5 devices (merging units) as bay units.
When ordering the 7SS85, select the Significant features F, G, H, J, or K for the distributed busbar protec-
tion. In this way, you also define the type and scope of the configurable busbar sections. One busbar section
corresponds to one protection range.
One 7SS85 can receive and process the SMVs of up to 45 current measuring points. Siemens recommends
configuring the 7SS85 in such a way that no more than 15 current measuring points (15 * (3-phase + IN) = 60
analog current values) are received by one ETH-BD-2FO communication module. For a larger number, you
require an additional communication module in the 7SS85. A merging unit can send a maximum of 8 meas-
uring points (32 SMV channels).
The following table provides a description of the Significant features of the 7SS85CU.
The 7SS85 distributed busbar protection is intended for the following maximum scope:
• 45 ⋅ 3-phase current measuring points (current transformers with the connection type 3-phase + IN)
NOTE
i For the distributed busbar protection, keep in mind that all the currents must be provided by the merging
units. Mixing local current transformers in the central unit and current measured values of the merging
units is not allowed.
NOTE
i In case of extensive configurations it is helpful to reduce the scope of IEC 61850 messages for memory
reasons. To do this, deactivate messages that are not required in the IEC structure.
With Significant features = H, the system configuration is possible as with K, but the following functions are
not available:
NOTE
i A significant feature with disconnector image is always necessary if the current transformer of a feeder
can be assigned to more than one bus zone. Line disconnector switches, bus section disconnector switches,
or disconnectors in bus couplers are also available in Significant features without a disconnector image.
Creating 7SS85
With the hardware selection and the Significant features, you decide which busbar protection you create.
Proceed as follows:
• In the DIGSI 5 project tree, click Add new device, and enter the product code of your device in the
subsequent dialog, for example
– 7SS85-DAAA-AA0-0AAAA0-A9D212-53113A-EAC000-000AC0-CC1BA2-CC1CC1-CC1CE0
for a centralized busbar protection with locally included current transformers
– 7SS85-DAAA-AA0-0AAAA0-A9D212-13113A-ABD000-000AC0-CG0BA2
for a distributed busbar protection (IEC 61850 compliant) with process-bus communication
– 7SS85-DAAA-AA0-0AAAA0-A9K212-13113A-ABD000-000AC0-CG0BA2
for a distributed busbar protection without integral current transformers
• If you have created a distributed busbar protection variant (even IEC 61850 compliant), open the device
information, adapt the Name, for example, 7SS85CU, and the IEC 61850 name, for example CU for
central unit, and select IEC 61850 Edition 2.x.
Siemens recommends activating the GOOSE supervision. In the project tree, click [Device name] >
Settings > Device settings and activate the check box Enable GOOSE Supervision. Thus, additional
GOOSE messages are available under communication supervision during information routing.
[sc_bbp8_proj_20_ZE_create, 2, en_US]
The devices appear in the project tree and in the Single-line configuration.
NOTE
i If you configure a distributed busbar protection, select the device with the ETH-BD-2FO communication
module in the hardware selection and make sure to use ...CU only ... in the F to K selection in the Signifi-
cant features. For an existing device, you see the Significant features used in the project tree under
[Device name] > Settings > Device settings > Important feature.
The Significant features are an integral part of the device function and can only be changed within the 2
groups 9 to E for centralized busbar protection or F to K for distributed busbar protection with a simulta-
neous function update.
• Current measuring points with instantiated current protection function, for example, FG Line or FG VI.
• Circuit breaker
• Disconnector
In the Function-group connections Editor, check and add the assignments of the current measuring points and
the circuit breakers or add the assignment later in the single-line configuration. For additional information on
adding function groups and functions, refer to the corresponding device manuals.
• In the project tree, click Single-line configuration and open the 7SS85.
• In the global DIGSI 5 library, click Types > Busbar protection > 7SS85 Busbar protection > FG Busbar >
Busbar protection > Function extensions and drag and drop a Bus zone into the Busbar function
group.
[sc_bbp8_proj_25_SLE_BB2, 2, en_US]
Connecting Busbars
Proceed as follows:
• In the function group Busbar, click the Bus zone 1 icon and connect it to busbar BB1.
If you have selected the busbar, you can specify in the Properties the color used for representing the bar in
the online display Single-line supervision.
[sc_bbp_sle_color, 1, en_US]
Centralized Busbar Protection and Distributed Busbar Protection (IEC 61850 Compliant)
The editing process in the single-line diagram is the same for the centralized and the distributed busbar
protection (IEC 61850 compliant). There are essential differences in the measuring-point routing between the
measuring points contained in the 7SS85 and the SMV values of the merging units transmitted via the process
bus. You can find the description of this in the following chapters.
• In the global DIGSI 5 library, click Types > 7SS85 Busbar protection > Bay and drag and drop a Bay into
the device.
Repeat the procedure for 2 additional bays.
• Click for example FG Circuit breaker 1/3pole and drag and drop a Circuit brk. 1/3pol into Bay 1.
Repeat the procedure for Bay 2 and the Bus coupler bay.
• Click FG Current transformer and drag and drop a Curr. transformer into Bay 1.
Repeat the procedure for Bay 2.
Add 2 current transformers into the bus coupler bay.
• Drag and drop 2 disconnectors into Bay 2 and 2 disconnectors into the Bus coupler bay.
[sc_slfeei, 1, en_US]
4.3.3.1 Current Measuring Points for the Centralized Busbar Protection and Current Measured Values for the
Distributed Busbar Protection (IEC 61850 Compliant)
There are 2 options for detecting current measured values in the busbar protection:
• Current transformers available in other devices (merging units), the current measured values (SMV) of
which are transmitted to the 7SS85 via optical fibers according to IEC 61850-9-2 (process bus)
In the following figures, you can see both options for creating the current measuring points.
[sc_bbp_IEC_22_MP, 2, en_US]
Any Device
The following figure shows any device, here, as an example, the 6MU85, with a physically available current
transformer in the device.
The measuring points should already be renamed here according to their use, for example MU01_E01 I-3ph 1.
This facilitates subsequent assignments in the IEC 61850 System Configurator.
[sc_bbp_IEC_23_MP, 1, en_US]
Figure 4-11 Local Current Measuring Point with the Assigned 3 Phases and Ground
Proceed as follows:
• Go to the Working area and route the phase currents and the ground current to the current-transformer
inputs of the device.
[sc_mesran, 2, en_US]
[sc_bbp8_proj_36_FG-verb, 2, en_US]
4.3.4 Current Measured Values (SMV) for the Distributed Busbar Protection (IEC
61850 Compliant)
4.3.4.1 Procedure for the Transmission of the Current Measured Values from the Merging Unit to the Client
In a distributed system, the current transformers are physically present in the merging units. These current
measured values must be transmitted to the target device (process-bus client), for example the 7SS85.
Proceed as follows:
Overview
The process bus is available for most of the modular SIPROTEC 5 devices. With the process bus, the current and
voltage measured values can be transmitted across devices. A requirement for this is an ETH-BD-2FO commu-
nication module with the corresponding activated communication protocols. You can find a detailed descrip-
tion of how to use IEC 61850-9-2 in the Process Bus manual, and a description for IEC 61850-8-1 GOOSE in
the Communication manual.
In the following figure, you can see the 7SS85 as an example of the destination device (client), and the
6MU85 and other modular SIPROTEC 5 devices as merging units.
[dw_bb8_proj-71-star, 2, en_US]
Use the IEC 61850 System Configurator to determine the cross-device routings.
All participating devices must have the same IEC 61850 edition 2.x. You can check or change this by opening
the device information for each device in the project tree and selecting IEC 61850 Edition 2 or IEC 61850
Edition 2.1. Siemens recommends using IEC 61850 Edition 2.1.
• Select the communication protocols under Devices and power systems in the Device view in Proper-
ties under Protocols once the ETH-BD-2FO communication module has been selected. For example for
the merging units 9-2 Merg.Unit for sending sample measured values (SMV) and 9-2 Client for receiving
sample measured values in the process-bus client (7SS85). IEC 61850-8-1 is selected automatically,
provided that 9-2 Merg.Unit or 9-2 Client is active.
• Activate the protocol necessary for time synchronization, for example, IEEE 1588.
• Check and change the Ethernet addresses for all ETH-BD-2FO communication modules in Properties. All
devices must be in the same subnetwork, for example x.x.x.60 for the client and for the merging units,
for example x.x.x.1, ...2, ...3 consecutively.
You can find other descriptions of network redundancy, for example PRP, or sample and time synchronization
via IEEE 1588, as well as information on the Ethernet modules, in the SIPROTEC 5 Communication Protocols
manual.
[sc_bbp_IEC_20, 1, en_US]
Check your devices before you create a new IEC 61850 station:
• In the device properties, have you provided the IEC 61850 names with meaningful names such as
MU01_E01?
• Did you assign an unambiguous IP address for each communication module within the same subnet-
work?
• Create a new IEC 61850 station for your project via the project tree.
• For the properties, select the same IEC 61850 Edition 2.x as the one used in the devices.
• Determine the storage path for the IEC 61850 Substation Configuration Description file.
[sc_bbp_IEC_40, 1, en_US]
NOTE
i For example, use the project path as the storage path. If you are copying projects, consider copying the IEC
61850 Substation Configuration Description and updating the path in the IEC 61850 station properties
accordingly.
Open the IEC 61850 station and select the device(s) you require from the Available devices.
• Current transformers
• All routings
• IP addresses
• Measuring-point names
[sc_bbp_IEC_50, 1, en_US]
Overview
The physical current and voltage transformers are in the merging units, the logical measuring points are
located in the client, for example 7SS85. You define the connection of the physical measuring points to the
logical measuring points via the process bus using the IEC 61850 System Configurator.
Protection Device as a Process-Bus Client, for Example 7SS85 Distributed Busbar Protection (IEC 61850 Compliant)
To add measuring points, proceed as follows:
• In the project tree, click the client, [Device name] > Measuring-point routing.
• In the Current-measuring points tab, use the Add new button to add, for example, 4 I-3ph current
measuring points.
You can also set up 1-phase or 3-phase voltage measuring points in the Voltage-measuring points tab.
You subsequently also have to route these analogously to the described current measuring points.
• Route the measuring points in the working area to the PB Client column.
[sc_bbp_proj_05_prerouting_smv, 1, en_US]
Incomplete routings are indicated by a warning symbol in the project tree. To display or change the parame-
ters of the added measuring points, if required, go to Power system in the project tree in the device.
NOTE
i Measuring points routed to the process-bus client require further parameterization steps in the IEC 61850
System Configurator in order to connect the merging unit to the process-bus client. After successful import
of the IEC 61850 station, the connection details are shown in the measuring-point properties and the
warning symbol is removed.
[sc_bbp8_proj_36_FG-verb, 2, en_US]
Merging Unit
A current measuring point is already available for most SIPROTEC 5 devices by selecting the device and appli-
cation template. The insertion of an additional measuring point is thus only occasionally required. If you must
insert an additional measuring point, first check in Devices and networks whether you have also physically
provided an appropriate number of current transformers (for example, current 4x protection).
To be able to add and transfer measuring points, proceed as follows:
• In the project tree, click [Device name] > Measuring-points routing and create the required current
measuring points by clicking the Add new button. You can select between I-1ph and I-3ph. Use I-3ph for
the example.
You can also set up 1-phase or 3-phase voltage measuring points in the Voltage-measuring points tab.
You subsequently also have to route these analogously to the described current measuring points.
• Add a Voltage/current 3ph FG to the device from the global DIGSI 5 Library, if required.
• Open the Function-group connections editor and connect the Meas.points I-3ph to the VI 3ph function
groups.
• Open the Merging-unit routing editor and check/route the measuring point to be transferred.
[sc_bbp_proj_13_routing_smv, 1, en_US]
With the module selected, you can view and change the parameters such as Stream Type in the Properties
tab. Siemens recommends activating the GOOSE supervision. Siemens recommends leaving the setting IEC
61869-9 for Stream type and 4000 Hz, 1 ASDU for Sampling-rate config..
You can find additional information regarding the process bus, GOOSE, the IEC 61850 System Configurator, as
well as descriptions of the stream types, GOOSE Later Binding, VLAN priority, network redundancy, for
example PRP or sample and time synchronization via IEEE 1588 in the Process Bus, Communication Protocols,
IEC 61850 System Configurator, and DIGSI 5 Online Help manuals.
NOTE
i The Merging-unit routing editor is only visible in the merging unit if you have selected the 9-2 Merg.Unit
communication protocol for the communication module ETH-BD-2FO.
Incomplete routings are indicated by a warning symbol in the project tree. To display or change the parame-
ters of the added measuring points, if required, go to Power system in the project tree in the device.
NOTE
i For the busbar protection, you require the Meas.point I-3ph, type 3-phase + IN.
Export the device data to an IID file for the IEC 61850 System Configurator. Proceed as follows:
• Select the IEC 61850 station in the project tree and add a New station ..., if necessary.
• Drag the respective devices (client and merging units) to the IEC 61850 station.
• Export the IEC 61850 station for the system configurator. This starts the IEC 61850 System Configu-
rator.
To do this, use the context menu or the Export changes to IEC 61850 System Configurator button.
[sc_bbp_proj_07_export_iid, 1, en_US]
Figure 4-21 Exporting the Device Data to the IEC 61850 System Configurator using the Left Marked
Button
• All the measured values routed in the Merging-unit routing editor appear as sources. You must connect
them to the measured values set up in 7SS85
A list of the available SMV values is then displayed in the SMV view. Drag and drop the measuring points
available in the Destination catalog to the SMV values in the SMV message area. You can connect indi-
vidual measured values or entire measuring points to one another.
[sc_bbp_proj_syscon, 1, en_US]
You can find further information in the Process Bus and IEC 61850 System Configurator manuals.
Importing the Measuring Points from the IEC 61850 System Configurator
To complete the measuring-point routing via the process bus, open the IEC station in DIGSI and reimport the
file previously processed and saved in the IEC 61850 System Configurator.
To do this, use the context menu or the Import changes from IEC 61850 System Configurator button.
[sc_bbp8_proj_syscon_import, 1, en_US]
Figure 4-23 Importing Data from the IEC 61850 System Configurator with Confirmation Screen
[sc_bbp_proj_11-pb_smv, 1, en_US]
Figure 4-24 Example of a Completed Measuring Point Mapping via the Process Bus
Moving Bays
For better arrangement, use the Single-Line Editor, detach the bays from the device and drag them beneath
the graphical bay representation. Only then you can create the connector lines.
[sc_sle_movebay, 1, en_US]
• Go to Bay 1 and click the Curr. transformer 1 symbol, connecting it with the current transformer BE1 in
Bay 1.
• In the following dialog, select the measuring point to which the current transformer is routed.
• Connect the current transformer for Bay 2 and both current transformers of the Bus coupler bay in the
same way.
A green line is displayed to indicate this connection.
[sc_slmszu, 1, en_US]
NOTE
i If you have selected the current transformer icon in the single-line configuration, you can set the
grounding direction of the primary current transformer using the Change grounding direction context
menu. This means a change in the direction of electric current in the busbar differential protection.
If you have set the parameter (_:8881:116) Neutr.point in dir.of ref.obj = no in the power-
system data of the merging unit, set the parameter Invert currents = yes in the 7SS85.
• Go to Bay 1 and click the Circuit breaker symbol and connect it with the circuit breaker QA1 in Bay 1.
• In CB 1/3pol 1, click the Meas.point I-3ph 1 icon and connect it to Current transformer 1.
• Connect the circuit breaker for the bus coupler bay to the current transformer that is to be used for the
circuit-breaker failure protection in the busbar protection.
When using systems with transfer busbars and combined bus coupler bays, the specific parameter
settings must be considered for the assignment of the current transformer and circuit breaker. You can
find more information in the following chapter 4.5.3 Combined Bus Coupler Bays.
A dashed line is displayed to indicate the connections.
[sc_slfezu, 1, en_US]
Connecting Disconnectors
Proceed as follows:
• In the Bus coupler bay, click the Disconnector icon and connect it to the disconnector QB1.
• Connect the disconnectors QB2 of the bus coupler and the disconnectors of Bay 1 and Bay 2 in the same
way.
A dashed line is displayed to indicate the connections.
[sc_slkuzu, 1, en_US]
Figure 4-28 Connecting System Parts with the Device, Example: Bus Coupler
4.3.6.1 General
You can use the inputs and outputs of the merging unit and transfer them via GOOSE as an alternative to
using local binary inputs and binary outputs, for example, of the 7SS85.
The following example shows the 7SS85 as the receiver of the contact positions and the 6MU85 as the trans-
mitter. The main requirements in terms of hardware and communication protocols have already been met by
having the option to transfer current measured values from the merging unit to the client. Both devices can be
transmitters and receivers.
Examples of binary routings for transmission using GOOSE:
• Circuit breaker and disconnector position information from the transmitters to the receiver (7SS85 in this
example)
• Circuit-breaker trip commands from the transmitter (7SS85 in this example) to the receivers.
A requirement for this is a functioning network topology, as described in chapter 4.3.4.2 Create and Check the
Network Topology.
• In the transmitter, for example, the merging unit, route the disconnector and circuit-breaker positions in
the Information routing to the binary inputs.
• In the receiver, for example, a 7SS85, add a 1 in the GOOSE column for the corresponding element.
In this way, you determine that the disconnector position of the merging unit can be transmitted via GOOSE
and received in the client. Carry out consecutive, unambiguous assignment later in the IEC 61850 System
Configurator. For further information on the GOOSE Later Binding, refer to the Communication Protocols
manual.
[sc_bbp_goose, 1, en_US]
Cross-Device Routings for Binary Inputs and Binary Outputs in the IEC 61850 System Configurator
For the added routings of the measuring unit to be available in the client, you must create the IEC 61850
System Configurator project or update an existing one.
• Open the IEC 61850 station in the DIGSI 5 project tree and click the Export changes to IEC 61850
System Configurator icon or use the context menu.
The IEC 61850 System Configurator is started automatically. The available devices are shown in the Device
view. The GOOSE view as shown in the following figure consists of the following 3 sections:
• GOOSE messages at the top, which contain the Source on the left and the Destination on the right
[sc_bbp_IEC_60, 1, en_US]
Select your IEC station in the GOOSE messages and add GOOSE applications for disconnector positions or
trip commands via the context menu. For example, a GOOSE application merging unit => 7SS85 and a
GOOSE application 7SS85 => Merging Unit. Change the names of the GOOSE applications in the Properties
window.
The aim is to connect the required binary information of the transmitter to the appropriate binary information
of the receiver.
Proceed as follows, for example for the QA1 circuit-breaker switch position:
• Expand the Source catalog as far as necessary and drag the desired binary information from the trans-
mitter to the upper left to the source in the GOOSE application. An example would be the circuit breaker
(CB1) position (XCBR1/Pos) of the merging unit (MU01); see the following figure. MU01/CB1/XCBR1/Pos
here corresponds to the IEC 61850 path of the circuit-breaker switch position in the properties for the
information routing.
• Expand the Destination catalog as far as necessary and drag and drop the desired destinations from the
receiver, for example the circuit-breaker switch positions of the 7SS85, upward and to the right onto the
appropriate destination line of the GOOSE application. An example would be CU/Bay1_CB3p1/XCBR1/
RxPos1; see the following figure.
Carry out analogous routings for other circuit breakers or disconnectors, such as QB1.
[sc_bbp_IEC_70, 1, en_US]
The same applies for the routing of circuit-breaker trip commands from the 7SS85 to the merging unit.
• In the Source catalog, expand the 7SS85 and use the Trip indication in the trip logic.
• To send the trip commands from the 7SS85 to the merging unit, an FG VI 3ph function group with func-
tion External trip must be available and connected to the Circuit-breaker function group. Route the Trip
indication from the 7SS85 to the indication >External trip of the function External trip. This pres-
ents the advantage, that the trip command uses the circuit-breaker object of the merging unit (CB main-
tenance).
In the previous figure, you see in the GOOSE application GOOSE 7SS85 the trip/close commands from the
7SS85 to the merging unit (MU02) and in GOOSE MU02 E02 the operate command T2 of the circuit-breaker
failure protection in the bay as examples. For this, additional parameterizations are necessary in the devices,
for example for circuit-breaker failure protection in the merging unit Start via binary input and the
routing of the binary inputs and outputs in the information routing.
The IEC 61850 paths necessary for the assignment in the IEC 61850 System Configurator are displayed in the
DIGSI 5 information routing in the Properties dialog of the selected element.
Repeat the process for all required binary routings, for example for all circuit breakers and disconnectors for
each bay. Complete the routing for the binary inputs and binary outputs in the IEC 61850 System Configurator
by clicking Save.
For more information on the IEC 61850 System Configurator, refer to the IEC 61850 System Configurator
manual.
For Efficient Project Engineering with Identical Merging Units, for Example 6MU85, Siemens Recommends the
Following Procedure:
If you use consistent devices, this facilitates project engineering because you can create typicals. For example,
6MU85 for feeder bays and busbar couplers or 7UT85 for transformer bays.
• Create a project with the 7SS85 and the typicals. Drive this project as far as possible.
• Conclude the single-line configuration with the assignments to the 7SS85 functions.
• Carry out all the settings and routings for these typicals.
• Copy these processed typicals and adapt the (IEC) names, IP addresses, and measuring-point designa-
tions.
This facilitates the assignments of the measuring points (process bus) and binary inputs and outputs (GOOSE)
between the 7SS85 and the merging units that are necessary in the IEC 61850 System Configurator.
In the following, you can find an overview of the topics already described. Proceed as follows:
• Create 7SS85 including all required elements (busbar sections, measuring points, bays and the discon-
nectors, circuit breakers, and current transformers contained in them).
• Connect the elements with the functions of the 7SS85 in the Single-Line Editor.
• Copy typicals, insert them multiple times, adapt names, IP addresses, and measuring-point designations,
and check the routings.
• Generate an IEC station, add devices, and export the data from DIGSI 5 to the IEC 61850 System Configu-
rator.
• In the IEC 61850 System Configurator, create the connection in the GOOSE and SMV views
– Create SMV connections.
– Create GOOSE connections. Siemens recommends creating a GOOSE application with one dataset
per device.
• In DIGSI 5, import the data from the IEC 61850 System Configurator. Check the connections in DIGSI 5 (at
the receivers)
For further information regarding the process bus, GOOSE, IEC 61850 System Configurator and descriptions of
stream types, GOOSE Later Binding, VLAN priority, network redundancy, for example PRP or sample and time
synchronization via IEEE 1588, refer to the Process Bus, Communication Protocols, IEC 61850 System Configu-
rator, and DIGSI 5 Help manuals.
You have now completed a simple project engineering for the centralized busbar protection or the distributed
busbar protection. For more detailed information, for example, regarding the various bay types, refer to the
chapters starting at 4.5.2 Bus Coupler Bays. The following chapter describes the Project engineering for the
distributed busbar protection.
Network Topology
In the following figure, you can see the 7SS85 as an example of the target device (client), and the 6MU85 and
other modular SIPROTEC 5 devices as merging units.
[dw_bb8_proj-71-star, 2, en_US]
All participating devices must have the same IEC 61850 edition 2.x. You can check or change this by opening
the Device information for each device in the project tree and selecting IEC 61850 Edition 2 or IEC 61850
Edition 2.1. Siemens recommends IEC 61850 Edition 2.1.
Every communication module of the distributed busbar protection 7SS85 can receive up to 15 current meas-
ured values. If you need more than 15 current measuring points, plug in another communication module and
use it to connect additional merging units. Keep the IP project engineering in mind for the different subnet-
works of the communication topology.
You can make the assignment to the subnetworks and the IP addresses later in the IEC 61850 System Config-
urator.
In Figure 4-33, you see an HSR ring structure with 3 rings connected to a central unit as an example.
[dw_7ss85_HSR-ringstruktur, 1, en_US]
With the HSR ring topology, the bay units are connected to the central unit in up to 3 rings with up to
15 devices. The central unit in this surface mounting is the Grandmaster clock (GMC) IEEE 1588 for synchroni-
zation of the sampled values. Since an external switch is not required, this surface mounting is more cost-
effective than the star topology.
For further information, see manual IEEE 1588, C53000-L1840-C055-9.
Protocol Selection
• Select the ETH-BD-2FO communication module under Devices and networks in the Device view and
select the communication protocols in Properties under Protocols. Select for example 9-2 MU 7SS85CU
for the merging units and 9-2 CL 7SS85CU for the 7SS85.
• Check and change the Ethernet addresses for the ETH-BD-2FO communication modules of the 7SS85CU
under Properties.
[sc_dbbp_cu_bd, 1, en_US]
You can find other descriptions of sample and time synchronization via IEEE 1588, as well as information on
the Ethernet modules, in the SIPROTEC 5 Communication Protocols manual.
Network
Check the IP addresses and adapt them as needed. To do this, double-click the communication module in the
Device view. You can find the IP addresses under Properties in the Ethernet addresses section.
[sc_bbp8_proj_95_adr, 2, en_US]
• Circuit breaker
• Disconnector
• Connect the functions of the circuit breaker, measuring point, and disconnector of the merging unit to
their graphical representations in the bay.
[sc_dBBP_SLE, 1, en_US]
Connections between the switching devices and the functions of the merging units are shown as black dashed
lines.
Connections to the current transformers are shown as green lines.
[sc_bbp8_SLE_incl, 1, en_US]
Figure 4-37 Expanded Properties Dialog Box for Existing Distributed Busbar Protection
After completing the engineering, you must update the central unit in the Single-line configuration. During
this update operation, the system configuration created in the Single-Line Editor is simulated in the 7SS85CU
using the representations of the connected bays, circuit breakers, disconnectors, and measuring points.
During this process, all necessary elements are automatically created in the 7SS85CU. These elements are
visible in the project tree of the 7SS85CU or in the information routing.
Proceed as follows:
• In the Single-line configuration > CU – BU Assignment tab, click the [Update central unit] button.
[sc_bbp8_proj_SLE_update, 1, en_US]
The bays are automatically assigned to the central unit. The bays and the functions that are important func-
tions for busbar protection, such as current transformers, circuit breakers, and disconnectors are displayed in
the central unit. The designations are identical to those in the Single-line configuration.
You can find the bay assignment as a table in the Topology tab and the representation of the bays in the
project tree within the central unit.
NOTE
i The prerequisites for the assignment of bay functions to the central unit are:
• Assignment of the current transformers and switching devices to the function groups
NOTE
i If you have made changes in the parameterization or in the Single-line configuration, also update the
central unit again.
[sc_bbp8_proj_60_pnv, 2, en_US]
Figure 4-39 Representations shown in the Central Unit for the Bays, Including the Contained Functions for
Current Transformers, Circuit Breakers, and Disconnectors
You must export the SMV information of the merging units from DIGSI to the IEC 61850 System Configu-
rator, assign them, and reimport them into DIGSI.
Export the device data into an IID file for the IEC 61850 System configurator. Check the SMV assignments and
reimport them. Proceed as follows:
• Select the IEC 61850 station in the project tree and add a New station ..., if necessary.
• Incorporate the respective devices (client and merging units) into the IEC 61850 station.
• Export the IEC 61850 station for the system configurator. This starts the IEC 61850 System configurator.
[sc_bbp_proj_07_export_iid, 1, en_US]
Figure 4-40 Exporting the Device Data to the IEC 61850 System Configurator using the Left Marked
Button
Network View
Every communication module of the distributed 7SS85 can receive up to 15 current measuring points. If you
need more than 15 current measuring points, plug in an additional communication module and use it to
connect additional merging units.
In the Network view of the IEC 61850 System Configurator, you can assign the merging units to the subnet-
works based on the existing physical connection, and change the IP addresses.
[sc_bbp8_proj_syscon_net, 1, en_US]
SMV Assignment
In the IEC 61850 System Configurator, you start the automatic assignment of the physical measuring points of
the merging units to the central unit in the SMV view with the SMV Mapping Through Topology context
menu. Any completed assignment is indicated by an asterisk (*) in the Destination column.
[sc_syscon_smv_map, 1, en_US]
Importing the Measuring Points from the IEC 61850 System Configurator
• To finish the measuring-point routing, open the IEC station in DIGSI and import the data from the IEC
61850 System Configurator.
To do this, use the context menu or the button Import changes from IEC 61850 system configurator.
[sc_bbp8_proj_syscon_import, 1, en_US]
Figure 4-43 Importing Data from the IEC 61850 System Configurator with the Confirmation Screen
• To check the assignment of the measuring points, open the Measuring-points routing in DIGSI.
[sc_dbbp_proj_11_smv_check, 1, en_US]
When updating the central unit (steps 1 and 2) and editing in the IEC 61850 system configurator, the
following functions are also instantiated:
[sc_dbbp_proj_15_sam_check, 1, en_US]
The following figure shows an example of a function for monitoring the busbar-protection internal communi-
cation to a connected bay unit 6MU85. This supervision function is automatically instantiated in the central
device. This type of monitoring is only performed on the 7SS85CU.
[sc_dbbp_proj_16_sam_check, 1, en_US]
Figure 4-46 Function for Monitoring the Busbar-Protection Internal Communication to a Bay Unit 6MU85
(7SS85CU only)
For an efficient parameterization of the distributed busbar protection (Significant features F to K), Siemens
recommends using SIPROTEC 5 merging units with an identical product code. A SIPROTEC 5 merging unit can
be completely parameterized (typical) and then any number of them can be created using copy and paste.
Create Typical
Using consistent devices facilitates project engineering because you can create typicals. For example, the
6MU85 for feeder bays and busbar couplers or the 7UT85 for transformer bays.
• Create a project with the 7SS85 and a merging unit as a typical. Drive this project as far as possible.
• Copy this edited bay including the merging unit and paste it (see the following figure).
– Drag and drop the connections to the busbars for the bays that were pasted.
– Adapt the bay name in each case, for example, E01 ⇒ E02.
– Adapt the device names, IEC names, and measuring-point designations, etc., via the project tree.
– Adapt the IP addresses of the integrated Ethernet interface (RJ45) and of the ETH-BD-2FO communi-
cation module.
• Repeat the previous points until there is a complete busbar protection system image.
• In the Single-Line Editor, switch to the CU – BU assignment tab, update the central unit, and check the
result, for example, in the project tree.
• Open the IEC 61850 station and add the pasted devices. Export the changes to the IEC 61850 System
Configurator and then import them again.
[sc_bbp8_proj_55_SLE_cop, 2, en_US]
Figure 4-47 Selecting, Copying, Pasting, and Adapting the Bay and Merging Unit Together
In order be able to access the bay units without separate station bus, the access is possible via the 7SS85
central unit. The 7SS85 central unit transmits the data to the bay units via the protection-device network. The
access is possible via DIGSI 5 as well as via the browser-based user interface. The PC with DIGSI 5 or the
browser-based user interface must be connected to the 7SS85 central unit via port J or via USB. The bay units
can be accessed via the IP address of Port J.
[dw_applikation_7ss, 1, en_US]
Figure 4-48 Example Application for 7SS85 Central Unit and Merging Unit
NOTE
i The Routing Manager affects the bandwidth. Siemens therefore recommends using it during commis-
sioning only since delayed operate times are possible.
• In order to assure the transmission of data, the IP address assignment must be selected carefully.
• In order to transmit the DIGSI communication from the PC to the 7SS85 central unit, you must set the IP
addresses of the PC and of the devices accordingly.
• The PC and the 7SS85 central unit must be in a different subnetwork than the bay unit.
In order to access the devices of the Merging Units via the 7SS85 central unit, proceed as follows:
• Open the command line with administrator rights on the DIGSI 5 PC.
• Enter the following command for information regarding the Ethernet interface:
route print
[sc_route_prt, 1, en_US]
NOTE
i The IP addresses of the protection-device network via Port E, F, ... must be different from Port J.
• Open the command line with administrator rights on the DIGSI 5 PC.
[sc_protpropcu, 1, en_US]
Field Device:
[sc_protpropmu, 1, en_US]
NOTE
Single-Line Configuration
NOTE
i The following figures of the single-line configuration show the centralized busbar protection as an
example.
Single-line configuration is the same for centralized busbar protection and distributed busbar protection (IEC
61850 compliant).
NOTE
i You can rename devices in the project tree. The change of device name comes into effect immediately.
For bus coupler bays with circuit breaker, it is advisable to configure the End-fault protection function block.
The end-fault protection is effective for errors between the open circuit breaker and the transformer. The end-
fault protection guarantees the selectivity for open circuit breakers and thus a faster fault clearing compared
to the tripping by the circuit-breaker failure protection. For more information on the End-fault protection,
refer to chapter 6.6.5 Function Description.
For bus couplers with 2 current transformers, the following applies: Connect the circuit breaker for the bus
coupler bay to the current transformer that must be used for the circuit-breaker failure protection in the
busbar protection.
When using plants with transfer busbars and combined bus coupler bays, consider the specific parameter
settings during the assignment of the current transformer and circuit breaker. For more information on this,
refer to chapter 4.5.3 Combined Bus Coupler Bays.
NOTE
i If you have selected the current transformer icon in the single-line configuration, you can set the
grounding direction of the primary current transformer using the Change grounding direction context
menu. This means a change in the direction of electric current in the busbar differential protection.
A combined bus coupler bay can function as a coupler or as a feeder. Its function depends on the respective
switch position of the busbar disconnector.
[sc_slkkzu, 2, en_US]
The dashed-line disconnector must not be drawn in the SLE and not parameterized.
Using the parameter Combi coupler = yes, you set the parameters for the combined bus coupler bay.
Under the following conditions, a combined bus coupler bay behaves like a normal bus coupler bay:
• At least one busbar disconnector is closed on both sides of the bus coupler.
• All busbar disconnectors on both sides of the bus coupler are open.
Under the following conditions, a combined bus coupler bay behaves like a feeder:
• At least one busbar disconnector is closed on one side, and the disconnectors on the other side are open.
During feeder operation, the behavior depends on the setting of the Overlapping CT parameter.
• For parameter Overlapping CT = yes, there is always a feeder with line-side transformers in a
combined coupler bay with 2 current transformers. When using the end-fault protection, wiring of the
transfer tripping command to the opposite end is necessary. In order for the end-fault protection to
create the transfer-trip signal, you must always connect the line side current transformer with the circuit
breaker.
• For parameter Overlapping CT = no, there is a feeder with busbar side transformers. The transfer-trip
command must not be sent to the opposite end.
Use the Single-Line Editor to connect the busbar-side current transformer with the circuit breaker.
NOTE
i If the combined bus coupler operates in feeder mode, you must ensure that the current flows across the
current transformer and the circuit breaker. Otherwise, the busbar section cannot be protected.
The parameters Combi coupler and Overlapping CT can be found in the Bay under General.
You can find additional information about the bay image and the bay types in chapter 5.2.1 The Field in
Centralized or Distributed Busbar Protection (IEC 61850-Compliant) .
In the circuit-breaker substitution mode, the feeder circuit breaker that is switched over to the transfer busbar
is replaced by the circuit breaker of the bus coupler. Monitoring the switch positions of the feeder discon-
nector and the bus coupler ensures that this occurs only after opening the busbar or line disconnector. Inter-
mediate switch positions occur until the final circuit-breaker substitution mode. The assignment of the respec-
tive feeder to the busbar section during that time depends on the arrangement of the current transformer
(internal or external).
In case of external transformers, a transfer busbar can be protected selectively. If a fault occurs, the circuit-
breaker substitute (bus coupler) trips and a transfer-trip command is triggered for tripping the circuit breaker
at the opposite end of the line.
Using the parameter Transfer bus disconnector, you specify for the disconnector QB7 of the bus
coupler whether the protection range ends at the transformer of the bus coupler.
• With the setting Transfer bus disconnector = no, the transfer busbar is protected with a closed
coupling disconnector. This applies if no feeders, or only feeders in the circuit-breaker substitution mode
with an external transformer, are assigned to the transfer busbar.
• With the setting Transfer bus disconnector = yes, the protection range with a closed coupling
disconnector ends at the transformer of the bus coupler. The transfer busbar is not protected. The current
of the bus coupler however is considered by the check zone measurement. This applies if no feeders, or
only feeders in the circuit-breaker substitution mode with internal transformers, are assigned to the
transfer busbar.
NOTE
i If the transfer busbar is to be protected, it must be configured as a busbar section with measuring system.
If you do not want any protection of the transfer busbar and are not configuring the QB7 (transfer busbar
disconnector) of the feeders, set the parameter Transfer busbar disconnector of the QB7 of the bus
coupler to yes.
In case of internal current transformers, the transfer busbar cannot be protected. With closed coupling discon-
nector, the current of the coupling however is included in the check zone measurement. The transfer busbar
can be planned with internal current transformers as a busbar section without measuring system.
If the bus coupler contains 2 current transformers, the behavior depends on the setting of the Overlapping
CT parameter. You can find the description in the section 4.5.3 Combined Bus Coupler Bays.
Combined bus couplers cannot be used with transfer busbars.
NOTE
i Internal and external current transformers must not be operated simultaneously on a transfer busbar.
[sc_uskupl, 2, en_US]
In the following section, you will find 2 examples of bus sections without a measuring system.
You can assign bus sections without measuring system (BS without MS) to the 2 center busbars (BB3 and
BB4). When the busbar disconnectors left (E01) or right (E02) are closed, the center bus section is assigned to
the corresponding bus section and protected. If the disconnectors of both sides are closed, the higher-level
measuring system takes precedence. If the disconnectors of both sides are opened, the system is dead.
[sc_bbp_coupl_zone, 1, --_--]
If you use current transformers on the bus side as in the following configuration, the transfer busbar cannot
be protected. Use a bus section without measuring system for this bay. The protection range ends at the
current transformer of the bus coupler bay.
[sc_bbp_transf_bus, 1, --_--]
Figure 4-55 Transfer Bus with Current Transformers on the Bus Side
If the bus zones are connected by a bus section disconnector, you should insert a bay for this. The bay
contains only the disconnectors, but not any circuit breakers, current transformers, etc. There can be 1 or
more disconnectors in one bay. The disconnectors can be connected to any desired bay unit.
[sc_bbp_3discon, 1, en_US]
In the normal case, the line disconnector QB9 is not needed. In case of double lines, the short-circuit current
can lead to the induction of a current in the line that is switched off and grounded. This current is processed
without QB9 as a differential current in the Busbar protection (see the following figure). Including the line
disconnector QB9 in the disconnector logic prevents an unwanted tripping.
[dw_bbp_line_discon, 1, en_US]
The busbar protection can be used for truck-type switchgear that is common in the medium-voltage range. In
these systems, the circuit breaker also performs the task of the otherwise standard disconnectors. This means
that the position of the circuit breaker serves the busbar differential protection as a criterion for the assign-
ment of the current transformer to the bus sections. In the protection device, only 3-pole circuit breakers are
supported for truck-type switchgear.
In the case of the busbar protection, 4 types of bays are possible for truck-type switchgear. The truck-type
switchgear can be combined in any desired way with bays that are not structured as truck-type switchgear. It
is characteristic for these 4 possible bay types that the circuit breaker is always directly connected to a bus
section.
These 4 bay types are described below:
Line feeder on 2 bus sections: The line feeder is connected via 2 circuit breakers with 2 busbars. The feeder
current is assigned to these sections depending on the position of these circuit breakers. If both circuit
breakers are closed, both sections are unified into one measuring system (preferred).
[sc_bbp_tt_abzweig_1ct_2cb, 1, en_US]
Line feeder on 2 bus sections and with line disconnectors: In addition to the preceding configuration, a line
disconnector is present. The measured current is then assigned to the bus sections according to the circuit-
breaker switch position only if this disconnector is closed.
[sc_bbp_tt_abzweig_1ct_2cb_1dc, 1, en_US]
NOTE
i Keep in mind during engineering that a maximum of only 26 3-pole circuit breakers can be configured, for
example in a centralized busbar protection (significant features 9 to E). This limits the maximum possible
number of line sections for switchgear trucks to 13.
NOTE
i Keep in mind that, with truck-type switchgear, the auxiliary contacts of the circuit breaker are also
processed according to the logic of not off = on (see the disconnector auxiliary contacts). As the circuit
breaker moves faster than the disconnector, it must be ensured that the definitive OFF position is exited
before (8 ms) the arcing distance is reached.
Bus coupler with 1 current transformer on 2 bus sections: The bus coupler connects 2 bus sections. The
current is measured only with only one transformer. If both circuit breakers are closed, the measured current
is assigned to both sections.
[sc_bbp_tt_coupl_1ct_2cb, 1, en_US]
Figure 4-60 Truck-Type Switchgear Bay: Bus Coupler with 1 Current Transformer
Bus coupler with 2 current transformers on 2 bus sections: The bus coupler connects 2 bus sections. The
current is measured by 2 transformers. If both circuit breakers are closed, each measured current is assigned
to one section. The current assignment can be overlapping or non-overlapping.
[sc_bbp_tt_coupl_2ct_2cb, 1, en_US]
Figure 4-61 Truck-Type Switchgear Bay: Bus Coupler with 2 Current Transformers
• In the Single-Line Editor, add the icon for the Voltage transformer and connect it to the bar and the
V-3ph 1 measuring point.
The connections are shown with blue lines.
[sc_bbp_proj_V, 1, en_US]
You can make the tripping of a busbar or a bus section depend on an additional undervoltage criterion.
• Create a Voltage 3-phase or VI 3ph function group type (see chapter 5.6.1 Overview) for each voltage
measuring point used as an additional tripping criterion.
• Create the appropriate voltage function in this function group, for example, undervoltage protection with
3-phase voltage (see chapter 6.16.1.1 Overview of Functions) and adapt the parameters according to
your plant.
• Place a CONNECT building block in this plan in order to connect the single-point indication values.
• Then connect the input of the building block to the output signal of the undervoltage function, for
example, the Group indicat.:Operate (General).
• Connect the output of the building block to the release signal, for example, Bus zone 1:>Trip release
[sc_bbp_cfc_trip, 1, en_US]
Alternatively:
You can also establish the connection between the undervoltage function and the tripping release by routing
the operate indication to a binary output and the tripping release to a binary input and wiring them to each
other directly. Note that, as a function of the relay type used, this solution produces greater time delays than
the CFC solution (2 to 3 ms in the Fast Event-triggered process level).
For the distributed busbar protection (IEC 61850 compliant), proceed as follows:
• Create a VI 3ph function group type (see chapter 5.7.1 Overview) in the merging unit for each voltage
measuring point used as an additional tripping criterion.
• Create the appropriate voltage function in this function group, for example, undervoltage protection with
3-phase voltage (see chapter 6.16.1.1 Overview of Functions) and adapt the parameters according to
your plant.
You can also establish the connection between the undervoltage function of the merging unit and the tripping
release of the busbar protection by routing the operate indication to a binary output and the tripping release
to a binary input and wiring them to each other directly or by routing via GOOSE.
NOTE
i If you want to send an OFF signal directly to the circuit breaker for a voltage function, you have to connect
the corresponding circuit breaker with the function group VI 3ph or Voltage 3-phase in the Function-
group connections Editor. Then route the stages of the voltage function directly to the circuit breaker in
the Circuit-breaker interaction of the VI 3-phase or Voltage 3-phase.
In addition to the busbar differential protection of the 7SS85, you can use various backup protection functions
such as overcurrent protection in the bay.
For example, to trip via the overcurrent protection, proceed as follows:
• In the circuit-breaker interaction matrix, assign the created overcurrent protection functions to the circuit
breakers and to the circuit-breaker failure protection if necessary.
The busbar protection provides various options to block certain functions or entire busbar sections, that is,
selective zones.
You can set the following blocking via binary inputs.
NOTE
i If one measuring system has precedence, for example, by installing a busbar shunt by disconnectors, then
the status of the higher-value measuring system applies.
Blocking Signal
End-Fault Protection
Busbar Differential
Failure Protection
External Tripping
External Tripping
Integrated CBFP
Circuit-Breaker
Protection
Bus Zone
from Bay
Busbar: Busbar protection:Diff.Prot. general: X - - - - -
>Block (1021.1831.11821.82)
Busbar: Busbar protection:CB fail. gen.: - X - - - -
>Block (1021.1831.11941.500)
Busbar: Busbar protection:Ext. trip BZ: - - - X X -
>Block (1021.1831.11971.503)
Busbar: Busbar protection:Bus zone #:>Block X X - X X -
Via BI (1021.1831.11881.500)
Via controllable (1021.1831.11881.320)
Busbar: Busbar protection:Bus zone #:>Block diff. prot. X - - - - -
Via BI (1021.1831.11881.503)
Via controllable (1021.1831.11881.321)
Busbar: Busbar protection:Bus zone #:>Block CB fail. prot. - X - - - -
Via BI (1021.1831.11881.504)
Via controllable (1021.1831.11881.322)
Bay_x: CB_x: 50BF Ad.CBF #:>Block function - X - - - -
(101.301.18781.82)
Bay_x: CB_x:50BF Inherent:>Block function - - X - - -
(101.301.12511.82)
Bay_x: CB_x:Ext. trip BZ:>Block function (101.301.12331.82) - - - - X -
Bay_x: CB_x:50EF 1/3pole:>Block function - - - - - X
(101.301.12361.82)
Bay_x: CB_x: EFP 3-pole:>Block function (102.201.12361.82) - - - - - X
Blocking Signal
End-Fault Protection
Busbar Differential
Failure Protection
External Tripping
External Tripping
Integrated CBFP
Circuit-Breaker
Protection
Bus Zone
from Bay
Busbar: Busbar protection:Bus zone 1:Block. by discon.fault X X - - - X
(11881.312)
Cause: Disconnector faults
Information Routing
In the Project tree, select the Information routing editor to check the routing of the circuit breaker and
disconnector positions to the binary inputs. Add the routings you require for the function keys, binary outputs,
LEDs, and logs.
[sc_bbp8_proj_45_Info_rout, 2, en_US]
NOTE
i Siemens recommends always using 2 binary inputs for detecting the position of a disconnector. If only one
binary input is available, the auxiliary contact with OH (open/active with voltage) or OL (open/active
without voltage) must be used for the routing.
If you connect current transformers to the device functions in the single-line configuration, DIGSI 5 checks the
primary and secondary currents of the current transformer. If the currents of the single-line configuration are
different from those of the measuring point on the device, the bay frame is then colored red. When you select
a current transformer, you can change the transformer currents in the Properties tab under Details. If you
select the device in the single-line configuration and Synchronize it, the transformer values from the single-
line configuration are imported into the device.
Breaker-and-a-Half Layout
[sc_bbp8_proj_54_SLE_1_5LS, 2, en_US]
Figure 4-65 Example for Breaker-and-a-Half Layout with 2 Circuit Breakers and 2 Current Transformers for
Distributed Busbar Protection (Excerpt from the Single-Line Configuration)
[sc_slfilt, 2, en_US]
Figure 4-66 List Box for the Device Completeness Check of the Assignment
In the working area, only the elements are shown that are connected to the selected device. The incomplete
or implausible parts of the configuration are shown under Info > Inconsistencies.
In this view, you also see the measured-value boxes that you can arrange and that serve as the default setting
for the online display of the single-line monitoring.
You can instantiate local protection functions of the merging units, such as overcurrent protection, where
available and use them independently of busbar protection.
• If you instantiate the Circuit-breaker failure protection in the 7SS85, the use of the unbalanced oper-
ating mode is the default setting.
• If you use the Circuit-breaker failure protection locally in the merging unit, the unbalanced operating
mode cannot be activated in the busbar protection. In the case of a 7SS85 failure, it would thus be
possible to clarify a circuit-breaker failure at least at the opposite end of the feeder by the merging unit.
For the selective tripping of a busbar, first instantiate the function block Busbar external tripping (from the
bay) (Ext. trip BZ) in the circuit breaker of the 7SS85. If you instantiate the Circuit-breaker failure protection in
the 7SS85, keep in mind that the indications for the CBFP start (>Start 3-pole or >Start pole A,
>Start pole B, and >Start pole C) and optional release and CB positioning (Position 3-pole or
Position 1-pole phsA, Position 1-pole phsB, and Position 1-pole phsC) are required in the
7SS85. This can either be directly wired to the 7SS85 or detected in the merging unit and transmitted to the
7SS85 via GOOSE.
If the Circuit-breaker failure protection is used locally in the merging unit, Siemens recommends transmitting
the Trip T2 (reserve tripping) also to the busbar protection (via GOOSE). With the Trip T2, the binary
inputs >Start pole A ... C of the Ext. trip BZ block should be triggered. For security reasons, the >Release
should use a different signal, for example the pickup of the circuit-breaker failure protection or the pickup of
the feeder protection, directly.
General Information
With the distributed busbar protection, the protection functions are distributed to the bay units/merging units
and the 7SS85CU central unit.
In the 7SS85CU central unit, you configure busbar protection-specific functions:
• Instantiate and configure the following functions and parameters in the central unit in the bay represen-
tations. You must have previously updated the central unit for this.
– Bus coupler differential protection
– For extensions of the Circuit breaker function-group type, refer to the following paragraph Special
Features in the Function-Group Type Circuit Breaker in the Central Unit
• Overcurrent protection
Special Features in the Function-Group Type Circuit Breaker in the Central Unit
Only few of the parameters can be edited in the representations of the 7SS85CU. They are only displayed after
a successful update of the central unit. You can find the parameters in the project tree under [7SS85CU]
device > Settings > [Bay] > [Circuit breaker] > General.
[sc_dbbp_proj_12_CU_set, 1, en_US]
Figure 4-67 Distributed Busbar Protection with Settable Parameters in the Representations
[sc_dbbp_proj_13_CU_i3p, 1, en_US]
Figure 4-68 Distributed Busbar Protection with Jump Option to the Merging Units
5.1.1 Overview
The Busbar function group represents the primary busbar, including all busbar sections in the 7SS85.
It represents the protected object into which the appropriate protection and supervision functions are placed.
The Busbar function group exists one time per 7SS85 and is permanently pre-instantiated. In the function
group, the Busbar protection function is permanently pre-instantiated with a FB Bus zone. To protect the
sections of a busbar, you connect these sections in the Single-Line Editor (SLE) of DIGSI 5 to the appropriate
building blocks of the Busbar protection.
You will find the Busbar function group under the device type 7SS85 in the function library in DIGSI 5. The
Busbar function group contains all of the protection, control, and supervision functions that you can use for
this device type.
You can find the Bus zone, the Busbar section without measuring system, and the Cross stabilization func-
tion blocks under the Busbar protection function. In the Busbar function group, you can instantiate up to 6
(20) function blocks Bus zones and 3 (12) function blocks Busbar sections without measuring system.
Values in brackets apply to the distributed busbar protection.
Current transformers connected to a Busbar section without measuring system are only included in the
calculation of the check zone. Only via the preference, for example via a connected busbar-section discon-
nector, is this Busbar section without measuring system assigned to a Busbar section (with measuring
system).
[sc_fgbusb-bbp, 1, en_US]
Figure 5-1 Busbar Function Group – Functional Scope for Device Type 7SS85
You will find more information on the Busbar protection function in chapter 6.2.1 Overview of Functions.
• FN Supervision (settings and indications for differential current supervision and zero-crossing supervi-
sion)
• FB Group indications
• FB External tripping
• FB Bus zone
In addition, you can also instantiate the following function blocks under the Busbar protection function:
• FB Bus zone
[dw_fg_bb01, 1, en_US]
• Bays (Circuit breaker function group , Disconnector function group, and Current transformer func-
tion group)
Interfaces to Bay/Bays
The Busbar function group contains the necessary information from the following function groups in the
appropriate bays:
• Circuit breaker
Parameter: Mode
• The Inherent circuit-breaker failure protection remains active in the bay, but can no longer be started
by a protection function.
You use the Mode parameter, setting Test, to switch on the entire Busbar function group including the Busbar
protection function contained in it and the associated supervision in the test mode.
• All indications within the FG Busbar are generated with a test flag.
The output relay is not controlled via the generated test flag, a busbar trip command is not sent to the
hardware.
• With an external CBFP start in the bay, only indications are generated, but no trip command sent to the
hardware.
The individual states of function control are discussed in 2.3 Function Control. For this reason, it is not
described in greater detail here.
You can find additional application and setting notes for the various functions in Protection Functions and
Supervision Functions.
• Busbar trip command of the circuit-breaker failure protection (after time T2) by way of an external start in
a feeder
• Busbar trip command of the inherent circuit-breaker failure protection (after unbalancing) in the bus
coupler
• Busbar trip command by external tripping (directly to the busbar or from the bay)
The indication _:12151:56 BBP trip relays blocked signals that the trip relays for busbar protection
are blocked. If the function is activated, every tripping of the busbar differential protection issues the indica-
tion _:4261:326 BBP trip relays blocked. This indication is given for each circuit breaker.
5.1.4 Settings
• For the centralized and the distributed busbar protection (IEC 61850 compliant), add the bays in the
7SS85 device with the function groups and functions contained therein, such as current transformer and
circuit breaker. The connections between busbar and the functions with graphical elements in the Single-
Line Editor, the assignment is done directly for the bay proxy. This is described in the following chapter.
• For the distributed busbar protection, only connect the busbar protection functions of the 7SS85 device
with the busbar protection in the Single-Line Editor. Connect the current transformers, circuit breakers,
and disconnectors of the bays in the single-line diagram with the corresponding merging-unit functions.
Open the CU – BU Assignment tab and click the Update central unit button to create the bay proxy or
update it. This creates or updates the bay representations in the central unit. Refer to chapter
4.4.3 Updating the Central Unit (Step 1) .
The following chapters from 5.2.2 Structure of the Function and the bay types also apply to all busbar-protec-
tion variants.
In the 7SS85 (centralized or distributed IEC-compliant), the Bay proxy is present once for each feeder bay, bus
coupler bay, or bus section disconnector bay and is preinstantiated with the General function block. In the
Single-Line Editor (SLE) of DIGSI 5, you can connect the switching devices and current transformers with the
switching devices in the instantiated bays.
The Bay proxy:
• Provides the basis for bay-specific activities, for example, taking a bay out of service, and communicates
this to the busbar protection/disconnector image
[sc_aom_bay, 1, en_US]
Figure 5-3 Bay Proxy – Functional Scope for Device Type 7SS85
• FG Current transformer
• FG Disconnector
[dw_fg_aom1, 1, en_US]
• 3-phase current + IN
The measurands from the 3-phase power system are supplied via this interface. The Circuit-breaker and
Current-transformer function groups must always be connected.
5.2.3.1 Overview
The following bay types are used in the busbar-protection system:
• Feeder bays
The bay types are connected to the busbar sections via a direct connection or disconnector. You must
configure all bay types individually.
• Truck-type switchgear
NOTE
[sc_bayty_1, 1, en_US]
[sc_bayty_2, 1, en_US]
[sc_bbp_bypass_cb, 2, en_US]
In the case of an internal transformer and closed QB7, the current is always extracted from the measurement.
[sc_bbp_bypass_cb-ct, 2, en_US]
[sc_bbp_tt_bay, 1, en_US]
NOTE
i Siemens recommends that you instantiate the End-fault protection function for all connection types for
protection of the dead zone. The term dead zone is used to designate the busbar section between the
circuit breaker and current transformer in a bus coupler.
This prevents a possible overfunction of the busbar protection.
Only with instantiated End-fault protection and an open circuit breaker a fault between circuit breaker and
current transformer is tripped selectively and fast.
For a bus coupler with 2 current transformers, the busbar protection offers the possibility of protecting the
dead zone via a bus coupler differential protection.
You will find more information on the End-fault protection function in the chapter 6.6.1 Overview of Func-
tions .
You will find more information on the Bus coupler differential protection function in the chapter 6.9.1 Over-
view of Functions .
The permissible bus coupler types are listed in the following.
[sc_1ct1qa, 1, en_US]
Figure 5-10 Bus Coupler with One Current Transformer and Circuit Breaker
[sc_2ct1qa, 1, en_US]
Figure 5-11 Bus Coupler with 2 Current Transformers and Circuit Breaker
Bus couplers can also be configured with 2 current transformers, one on either side of the circuit breaker. The
currents are assigned to the zones here via the parameter Overlapping CT. The advantage of the Overlap-
ping setting is the instantaneous, but nonselective, tripping of both zones in the event of a fault between the
2 current transformers.
With the Non-overlapping setting, the zones can be tripped selectively by the Bus coupler differential
protection or by an external protection device, but with a time delay.
[sc_bbp_cpl_wo_cb, 1, en_US]
Figure 5-12 Bus Coupler with One Current Transformer and No Circuit Breaker
Some busbar sections are connected by a load breaking switch, not by a circuit breaker. Both of the coupled
busbar sections are tripped, since the load breaking switch cannot disconnect the short-circuit current. In
order to identify the section affected in the event of a fault, the current at the coupling point is acquired. The
indication Trip by transfer trip appears for the tripped busbar.
[sc_comcpl, 1, en_US]
(1) The marked (dashed-line) part must not be drawn in the SLE and not parameterized.
Truck-Type Switchgear
[sc_bbp_tt_coupler_1ct, 1, en_US]
[sc_bbp_tt_coupler_2ct, 1, en_US]
[sc_1qbsec, 1, en_US]
Parameter: Overlapping CT
A configured bay in a 7SS85 or 7SS85CU device can be placed in the Bay out of service operating state. The
requirement for this is for the physical bay to actually be out of service on the primary side, that is, that
current cannot flow through the bay.
You can set the Bay out of service operating state via a control command or a binary input for the relevant
bay.
NOTE
i A bay can only be put back into operation in the same way that it was taken out of operation, that is via the
binary input or via a control command.
The following functions are deactivated by the operating state Bay out of service:
• External tripping
The disconnectors for the affected bay are processed as open by the 7SS85 or 7SS85CU device. The assign-
ment of the bay to the check zone (= disconnector-independent measuring system) is maintained even if all
disconnectors are detected as open. Furthermore, disconnector supervision in the bay and the resulting indi-
cations are blocked.
For more information, refer to 5.2.8 Deactivating the Sampled Value Monitoring and 5.2.9 Deactivating
GOOSE Monitoring.
In case of a 7SS85CU-based distributed busbar protection system, alongside the previously described bay out
of operation operating state that can only be used on a bay in the 7SS85CU device, there is also the option of
taking a measuring point of the distributed busbar protection in a bay unit out of operation.
For more information on decommissioning a measuring point, refer to 6.1.4 Operating State: Measuring Point
for Distributed Busbar Protection out of Service.
For more information, refer to 5.2.8 Deactivating the Sampled Value Monitoring and 5.2.9 Deactivating
GOOSE Monitoring.
Physical bays that are not yet available or that have not yet been commissioned on the primary side, but which
have already been projected in the DIGSI configuration can be deactivated in the 7SS85 or the 7SS85CU device
via the Bay off operating mode for the affected bay. To do this, set the Mode parameter of the affected bay in
the General function block to Off.
This switches off all functions within this bay in the 7SS85 or 7SS85CU device. The current measured value
from this bay is not taken into account for the selective zone or for the check zone.
You can activate or deactivate this Bay off operating mode in the affected bay in the 7SS85 or the 7SS85CU
device via parameterization or via the control system.
NOTE
i A bay can only be switched on again in the same way that it was switched off, that is via parameterization
or via a control command.
NOTE
i Changing the operating state of a bay in the 7SS85CU affects the following points of monitoring communi-
cation to the bay units connected to the 7SS85CU:
For more information, refer to 5.2.8 Deactivating the Sampled Value Monitoring, 5.2.9 Deactivating GOOSE
Monitoring, and 8.7 Supervision of Communication Connections.
When a bay in a 7SS85CU device changes to the operating state Bay off, the monitoring of the communica-
tion to the associated merging unit is automatically deactivated in the 7SS85CU.
For more information, refer to Supervision of the Busbar-Protection Internal Communication (Only 7SS85CU),
Page 822.
If a bay that is projected in a distributed busbar protection system in DIGSI is placed into the Bay out of
service or Bay off operating mode or if an assigned measuring point in a bay unit is taken out of operation,
the sampled value monitoring that is automatically activated in the 7SS85 or 7SS85CU device is still active.
The sampled value monitoring is used for the sampled values received by this bay/measuring point. This
means, for example, that the relevant status and fault indications are issued if the sampled values fail to mate-
rialize.
If this is not required, switch off the relevant sampled value monitoring instance in this 7SS85 or 7SS85CU
device separately via corresponding control commands, or switch it on again when recommissioning the bay/
measuring point.
For details on control commands via IEC 61850, refer to the SIPROTEC 5 Communication protocols manual,
chapter 2.6.5 Control via IEC 61850.
The contents of this chapter are only required if you have subscribed to GOOSE indications from the bay units
in the 7SS85 or 7SS85CU device for a distributed busbar protection system and if the GOOSE-indication super-
vision is additionally activated in the 7SS85 and 7SS85CU device.
For more details on activating/deactivating GOOSE supervision, refer to the SIPROTEC 5 Communication proto-
cols manual, chapter 11.1.14.3 GOOSE connection monitoring.
If a bay which is projected in a distributed busbar protection system in DIGSI is placed into the Bay out of
service or Bay off operating mode or if an assigned measuring point in a bay unit is taken out of operation,
the monitoring system for GOOSE indications received by this bay/measuring point, that may be automatically
activated in the 7SS85 or 7SS85CU device, is still active. This means, for example, that the relevant status and
fault indication are issued if the GOOSE indications fail to materialize.
If this is not required, switch off the relevant GOOSE-supervision instance in the 7SS85 or 7SS85CU device
separately via relevant control commands, or switch it on again when recommissioning the bay/measuring
point.
You can route the Acquisition blocking input signal to a binary input in the information routing for circuit
breakers and disconnectors.
During maintenance work on primary switches (disconnectors and circuit breakers), the feedback may not
correspond to the actual switch position, for example a switched-off feedback voltage.
With the Acquisition blocking, the instantaneous disconnector status is frozen. By combining the binary
signals, different switching devices can be assigned to a revision range. Several revision ranges can be defined
in one bay.
You can find more information on acquisition blocking in chapter 3.9.2 Acquisition Blocking and Manual
Updating and in chapter Commissioning of the SIPROTEC 5 Operating manual.
5.2.11 Settings
5.3.1 Overview
The Circuit-breaker function group combines all the user functions that relate to a circuit breaker. The Circuit-
breaker function group represents the physical circuit breaker in the SIPROTEC 5 device.
You can find the Bay, and below the Circuit-breaker 1-/3-pole and Circuit-breaker 3-pole function groups,
under the device type 7SS85 in the Global DIGSI 5 library. Both function groups contain all the protection,
control, and supervision functions that you can use for this device type.
[sc_fgls01, 1, en_US]
The FG Circuit breaker 1-pole/3-pole can issue the switching command both for 3 poles (phases A, B, and C)
as well as for 1 pole (phase A or B or C). The FG Circuit breaker 3-pole can issue the switching command only
for 3 poles.
The 1-pole CBFP (T1) of the 1-pole/3-pole circuit breaker trips via the Circuit-breaker failure protection
protection function in the bay and not via the Circuit-breaker function in the Circuit-breaker function group.
The Circuit-breaker function group contains specific functionalities that are needed in addition to the user
functions.
• FB General
• FB Trip logic
• Circuit-breaker supervision
• Circuit-breaker test
• Control
• Interlocking
Only the circuit-breaker test, the control, and the interlocking can be deleted from the Circuit-breaker func-
tion group.
In addition to the functions described, the following features can be created in the Circuit-breaker function
group.
• End-fault protection
• External tripping
• Trip-circuit supervision
[dw_fg_ls_01, 1, en_US]
• 3-phase current + IN
The measurands from the 3-phase current system are supplied via this interface. The function group must
always be connected to this measuring point.
NOTE
i The Circuit-breaker function group must always be connected to this measuring point. The configuration
is done via the Function-group connections editor in DIGSI 5.
For more detailed information, refer to chapter 2.1 Function Embedding in the Device .
If a user function is used in the function group but the required measuring point is not connected to it,
DIGSI 5 reports an inconsistency. This inconsistency provides an indication of the missing measuring-point
connection.
Overcurrent Release
When a short circuit occurs in the busbar, busbar protection provides the option of disconnecting only the
feeders with currents above the limiting value that can be set. Set the limiting values for each feeder individu-
ally using the parameters (_:2311:121) Current thres. trip release and (_:2311:122)
Current thr. trip rel. sens.. The set threshold Current thres. trip release applies to trip-
ping cases of the busbar differential protection with the default characteristic curve. The threshold Current
thr. trip rel. sens. applies to tripping cases of the busbar differential protection with sensitive charac-
teristic curve and tripping cases of the busbar circuit-breaker failure protection. To satisfy the tripping crite-
rion, at least one of the phase currents must be greater than or equal to the threshold set by the parameter.
With the default setting of 0 A, the function has no effect and disconnection occurs without considering the
current.
You will find the settings in the 7SS85 device under -> Parameters -> Bay -> Circuit breaker -> General.
NOTE
i If the device works with the IEC 61850 protocol, then you change the setting value of the parameter only
via DIGSI 5 and not directly on the device. If you change the setting value directly on the device, then the
IEC 61850 configuration of the metered values can be faulty.
With the Current thresh. CB open parameter, you specify the current threshold below which the circuit-
breaker pole or the circuit breaker is recognized as open.
Set the Current thresh. CB open parameter so that the current measured when the circuit-breaker pole
is open will certainly fall below the parameterized value. If parasitic currents (for example, due to induction)
are excluded with the line deactivated, you can make a secondary setting of the value with a high degree of
sensitivity, to 0.05 A for example.
If no special requirements exist, Siemens recommends retaining the setting value of 0.10 A for secondary
purposes.
[sc_dbbp_proj_12_CU_set, 1, en_US]
Figure 5-19 Distributed Busbar Protection with Adjustable Parameters in the Representations
With Trip T2 of the circuit-breaker failure protection in currentless operation Figure 6-27, disconnection
does not use unbalancing but rather the disconnector image. This does not affect the Inherent circuit-breaker
failure protection.
NOTE
i If you use the circuit-breaker failure protection locally in the merging unit in the distributed busbar protec-
tion (IEC 61850 compliant), the unbalancing operating mode cannot be activated in the busbar protection.
You can find more detailed information on this in the chapter 6.3.4 Circuit-Breaker Failure Protection in
Busbar Protection
5.3.4 Settings
5.3.6.1 Overview
The basic tasks of this function block are the operation of the circuit breaker and the acquisition of the circuit-
breaker auxiliary contacts and other circuit-breaker information.
The Circuit-breaker function block also provides information about:
• Breaking current
• Circuit-breaker tripping as a consequence of Ext. trip bus zone (via binary input)
NOTE
i The following chapter is always describing the 1-pole/3-pole circuit breaker. The inputs for the phase-selec-
tive evaluation of the circuit-breaker switch position are not applicable for an only 3-pole circuit breaker.
[lo_lsausl, 1, en_US]
NOTE
i Siemens recommends always using 2 binary inputs for determining the circuit-breaker switch position. If
you set the circuit-breaker failure protection parameters taking the auxiliary contacts into consideration,
you must route the On position. For the end-fault protection and the correct detection of the disconnector
image in the truck-type switchgear, the Off position is needed.
Before loading the configuration into the device, DIGSI checks the prerouting of the OFF contacts of the
disconnectors and circuit breakers.
[lo_ls_info, 1, en_US]
The signal or signals must be routed to the binary inputs that are connected to the circuit-breaker auxiliary
contacts. The open and closed signals do not necessarily have to be both routed. The advantage of parallel
routing is that it can be used to determine an intermediate or disturbed position. On the other hand, this is not
possible if only one signal is routed.
In the monitoring direction, the position signals generate the following information when the open and
closed positions are detected (see following table). This information is further processed by the Circuit-
breaker position recognition and Control function blocks.
Information Type Description
Off SPS Circuit-breaker switch position is opened.
On SPS Circuit-breaker switch position is closed.
Intermediate position SPS Circuit-breaker switch position is in intermediate position.
You can find more information in the chapter 8.3.8.3 Function Description.
Other input signals are:
Signal Type Description
>Acquisition SPS The acquisition blocking of the circuit-breaker auxiliary contact is activated
blocking using this input signal
You can find more information on this in the chapters 3.9.2 Acquisition
Blocking and Manual Updating and 5.2.10 Operating State Acquisition Blocking
>Ready SPS The active signal indicates that the circuit breaker is ready for an OFF-ON-OFF
cycle.
The signal remains active as long as the circuit breaker is unable to trip. The
signal is used in the Circuit-breaker test function.
• Phase-selective circuit breaker in the 1-pole Off position, phases A, B, C (CB Off)
The signals must be routed to the binary inputs that are connected to the circuit-breaker auxiliary contacts. For
safety reasons, Siemens recommends an external logical operation with phase-selective auxiliary contacts and
3-pole auxiliary-contact activation in the circuit breaker.
[dw_lser_3p, 1, en_US]
[dw_lser_13, 1, en_US]
Figure 5-23 Acquisition of Circuit-Breaker Information with 3-Pole or 1-Pole Phase-Selective Activation
[lo_untbbp, 1, en_US]
With truck-type switchgear, it is possible that the circuit breaker has pulled out of the switching element. In
this case, the auxiliary contacts must correctly replicate the open state. The means the 3-pole closed signal (if
used) must be inactive and 3-pole open (if used) must be active. You can achieve this via an external intercon-
nection of these signals, for example:
[lo_bbp-tt-cb-open, 2, en_US]
Figure 5-25 Consideration of the Switchgear Truck Pulled Out Circuit-Breaker Signal
[lo_ausinf, 2, en_US]
[lo_ls_stat, 2, en_US]
• The device can execute 3-pole tripping via the Busbar protection.
• The device can execute 1-pole and 3-pole tripping via the Circuit-breaker failure protection.
[lo_ls_control, 1, en_US]
NOTE
i You must route the Trip/open cmd. 3-pole signal for 3-pole tripping/opening for each phase to 1
binary output.
By routing the Trip/open cmd. 3-pole signal to 1 or 2 binary outputs for each phase, you can carry out 1-
pole, 1.5-pole, and 2-pole activations of the circuit breaker. You can find a detailed description of this in
chapter 7.2.2.3 Connection Variants of the Circuit Breaker.
NOTE
i Do not confuse these 1-pole, 1.5-pole, and 2-pole activations of the circuit breaker with 1-pole or 3-pole
tripping of the circuit breaker.
[lo_evaluation, 1, en_US]
Figure 5-29 Recommended Analysis of the Circuit-Breaker Switch Position when Used as a Protection
Device
Route to a binary input as C_ (closed). In the following figure, routing is executed as CH, in which H stands for
active with voltage.
[sc_polges, 1, en_US]
Figure 5-30 Pole Closed: Routing for the Acquisition of Pole Closed Information
[lo_evaluation2, 1, en_US]
Figure 5-31 CB 3-Pole: Recommended Analysis of the Circuit-Breaker Switch Position when Used as a
Protection and Control Device
[lo_ausw_3p, 1, en_US]
Figure 5-32 CB 1-Pole/3-Pole: Recommended Analysis of the Circuit-Breaker Switch Position when Used as
a Protection and Control Device
Execute the routing of the Position 3-pole signal as O_ (open). In the following figure, routing is
executed as OH, in which H stands for active with voltage.
[sc_polg3p, 1, en_US]
Figure 5-33 CB 3-Pole: Routing for Acquisition of the Circuit-Breaker Switch Position via 2 Auxiliary
Contacts
[sc_poloff, 1, en_US]
Figure 5-34 CB 1-Pole/3-Pole: Routing for the Acquisition that Circuit Breaker Is Open in 3 Poles
Depending on the design of the circuit breaker, other auxiliary contacts can be available in the system. In this
case, the device allows all routing options and acquires the necessary information automatically.
The device can also function without the analysis from the circuit-breaker auxiliary contacts. Routing of auxil-
iary contacts is not absolutely required, this rather depends on the protection function used.
! CAUTION
Do not set a time that is too short.
If you set a time that is too short, there is a danger that the device contacts will interrupt the control
circuit. If this happens, the device contacts will burn out.
² Set a time that is long enough to ensure that the circuit breaker reliably reaches its final position
(open or closed) after a control operation.
Measured Values
If a protection function trips the circuit breaker, the following measured values are stored in the fault log.
• Break.-current phs A
• Break.-current phs B
• Break.-current phs C
• Break. current 3I0/IN
• Break. voltage phs A
• Break. voltage phs B
• Break. voltage phs C
The measured value Break. current 3I0/IN is the neutral-point current.
whenever the output signal Alarm suppression becomes active so that tripping or a switching operation
does not cause an alarm (see the logic in 5.3.6.3 Acquisition of Circuit-Breaker Auxiliary Contacts and Further
Information for more details).
[lo_schalt, 2, en_US]
5.3.6.7 Settings
5.3.7.1 Overview
This function block calculates the position of the circuit breaker from the evaluation of the auxiliary contacts
and the current flow. The calculation is performed phase-selectively.
This information is needed in the following protection-related additional function:
• End-fault protection
Its use is described in the respective chapters.
The control does not use this information. The control evaluates the circuit-breaker auxiliary contacts.
[lo_sf-status, 1, en_US]
Based on the connection between the information from the auxiliary contacts and the current flow, the circuit
breaker can assume the following conditions for each phase:
Circuit-Breaker Condition, Phase-Selective Description
Open The circuit-breaker pole is detected unambiguously as
open according to both criteria.
Closed The circuit-breaker pole is detected unambiguously as
closed according to both criteria.
5.4.1 Overview
The Current-transformer function group represents the physical current transformer in the SIPROTEC 5 device
together with the measuring point.
You can find the Bay under device type 7SS85 in the Global DIGSI 5 library, and the Current-transformer
function group below that.
[sc_bbp-fgct01, 2, en_US]
Figure 5-37 Current-Transformer Function Group – Functional Scope for Device Type 7SS85
The Current transformer function group contains certain functionalities that are essential for general
purposes and therefore cannot be loaded or deleted:
• General data
The following figure shows the structure of the Current transformer function group.
[dw_fg_ct_01, 1, en_US]
• 3-phase current + IN
The measurands from the 3-phase current system are supplied via this interface.
NOTE
i The Current transformer function group must always be connected to this measuring point. The configu-
ration is done via the Function-group connections Editor or in the Single-Line Editor in DIGSI 5.
You can find more detailed information on this in the chapter 2.1 Function Embedding in the Device .
If a user function is used in the function group but the required measuring point is not connected to it,
DIGSI 5 reports an inconsistency. This inconsistency provides an indication of the missing measuring-point
connection.
To fulfill the protection task under different operating states of the protected object, the position of the
current transformer is important. The position of the current transformer in the different bays is automatically
determined from the configuration in the Single-Line Editor and processed in the protection.
[sc_ctloca, 1, en_US]
5.5.1 Overview
The Disconnector function group represents the physical disconnector in the SIPROTEC 5 device. The function
group detects the position of a disconnector and indicates its current position.
You will find the Bay proxy function group, and the Disconnector function group below that, under the
device type 7SS85 in the Global DIGSI 5 library. The Disconnector function group contains all switching and
supervision functions you can use for this device type.
[sc_fgdisc, 1, en_US]
Figure 5-40 Disconnector Function Group – Functional Scope for Device Type 7SS85
• Busbar disconnector
• Transfer-busbar disconnector
• Busbar-section disconnector
• Line disconnector
NOTE
i The Disconnector function group processes only disconnectors without activation (only the current posi-
tion). This also applies to representatives with distributed busbar protection.
For the merging units, you can use the correspondingly available disconnectors.
Besides the user functions, the Disconnector function group contains certain functionalities that are essential
for general purposes and therefore cannot be loaded or deleted:
• General data
• Monitoring
[dw_fg_tr_01, 1, en_US]
NOTE
i The parameter Switching-device type is effective only on the IEC 61850 interface. Use this param-
eter to set the disconnector type for communication via an IEC 61850 interface. This is a required data
object in the IEC 61850 Standard and has no effect on the functionality of the busbar protection.
[dw_fg_tr_02, 1, en_US]
Figure 5-42 Logical Inputs and Outputs of the Disconnector Function Block
If the quality of the input signal assumes the status Quality = invalid, then the standby status (Health) of the
Disconnector function block is set to Warning.
The feedback is routed via the position with the disconnector.
You can find more detailed information on the disconnector supervision function in the chapter Supervision
Functions.
NOTE
i Siemens recommends always using 2 binary inputs for determining the position of a disconnector.
If there is only one binary input available, the auxiliary contact with OH (open/active with voltage) should
be used for the routing.
If none or only the On position is routed, the health state of the device switches to Warning and is
handled as closed in the disconnector image.
5.5.4 Parameter
5.6.1 Overview
In the Voltage 3-phase function group, all functions can be used for protecting and for monitoring a
protected object or equipment which allows a 3-phase voltage measurement. The function group also
contains the operational measurement for the protected object or equipment (on this topic, see chapter
9 Measured Values and Supervision of the Primary System). Applicable functions are, for example, Voltage
protection or Frequency protection.
[sc_bbp_fg_u_01_de, 1, en_US]
Figure 5-43 Voltage 3-Phase Function Group – Functional Scope for Device Type 7SS85
If you wish to use a busbar protection-related voltage protection function such as Release of tripping by
undervoltage protection, use the protection functions of the Voltage 3-phase function-group type.
The Voltage 3-phase function group has interfaces to the measuring points and the Circuit-breaker function
group.
[dw_bbp-3volt, 1, en_US]
[sc_3_voltage1, 1, en_US]
Figure 5-45 Connecting Measuring Points to the Voltage 3-Phase Function Group
If you add functions to the Voltage 3-phase function group, these are connected to the measuring point auto-
matically.
You can connect multiple measuring points with this interface. For more information, refer to chapter
6.23 Voltage Measuring-Point Selection.
The measurands from the 3-phase voltage system are supplied via the V 3-ph interface. Depending on the
connection type of the transformers, for example, VA, VB, VC, Vgnd. All values that can be calculated from the
measurands are also provided via this interface.
Table 5-3 Operational Measured Values of the Voltage 3-Phase Function Group
NOTE
i If you intend to send an OFF signal of a voltage function directly to a circuit breaker, use the Function
group connections Editor to connect the respective circuit breaker with the function group Voltage 3-
phase. Then route the stages of the voltage function directly to the circuit breaker in the circuit-breaker
interaction of the FG Voltage 3-phase.
5.6.5 Settings
5.7.1 Overview
In the Voltage-current 3-phase function group, you can use all the functions for protection and supervision
of a protected object or equipment that allows 3-phase current and voltage measurement. The function group
also contains the operational measurement for the protected object or equipment.
You will find the Voltage-current 3-phase function group under each device type in the Global DIGSI 5 library.
You will find all protection and supervision functions that you can use for this function-group type in the func-
tion group Voltage-current 3-phase.
For more information about the embedding of the functions in the device, refer to chapter 2 Basic Structure of
the Function.
If you wish to use expanded backup protection functions such as directional overcurrent protection or impe-
dance protection etc. in the bay, use the protection functions of the Voltage/current 3-ph function-group
type.
The following additional protection functions are available to you in the FG VI
• Impedance protection
• Arc protection
• Inrush-current detection
NOTE
i Keep in mind that, when using resource-intensive functions such as the VI 3ph function group, for example
with impedance protection, the maximum possible number of line sections is reduced to 10. You can find
further information on monitoring resource consumption in chapter 8.2.1 Load Model.
• Process monitor
[dw_fg_ui3p, 4, en_US]
• Measuring points
• 3-phase current
The measurands from the 3-phase current system are supplied via this interface. Depending on the
connection type of the transformers, these are, for example, IA, IB, IC, IN or 3I0. All values that can be
calculated from the measurands are also provided via this interface. The function group must always be
connected to the I-3ph measuring point.
You can connect the 3-phase current interface to a maximum of four 3-phase current measuring points,
(for example, for 1 1/2 circuit-breaker layouts). If 2 current measuring points have been connected with
the 3-phase current interface, the total current is also determined from measured values from both
measuring points in the function group. All functions in the function group have access to these values.
• Which circuit breaker(s) is/are activated by the protection functions of the protection function group
• Starting the Circuit-breaker failure protection function (if available in the Circuit-breaker function group)
through the protection functions of the connected protection function group
• Starting the Automatic reclosing function (AREC, if available in the Circuit-breaker function group)
through the protection functions of the connected Protection function group
Besides the general allocation of the protection function group to the Circuit-breaker function groups, you can
also configure the interface for certain functionalities in detail. Configure the details in DIGSI 5 using the
Circuit-breaker interaction Editor in the protection function group.
In the detail configuration of the interface, you define:
• Which operate indications of the protection functions go into the generation of the trip command
Process Monitor
The process monitor is always present in the Voltage-current 3-phase function group and cannot be
removed.
The process monitor provides the following information in the Voltage-current 3-phase function group:
• Current-flow criterion:
Detection of an open/activated protected object/equipment based on the flow of leakage current
• Closure detection:
Detection of the switching on of the protected object/equipment
The following table shows the operational measured values of the Voltage-current 3-phase function group:
Table 5-4 Operational Measured Values of the Voltage-Current 3-Phase Function Group
For a more detailed explanation of the operational measured values, refer to 9.3 Operational Measured
Values.
Output Logic
The output logic treats the pickup and trip signals of the protection and supervision functions that are avail-
able in the function group separately, in a pickup logic and a trip logic, respectively. The pickup and trip logic
generate the overreaching indications (group indications) of the function group. These group indications are
transferred via the Protection information interface to the Circuit-breaker function group and are processed
further there.
The pickup signals of the protection and supervision functions in the Voltage-current 3-phase function group
are combined in a phase-selective manner and output as a group indication.
[lo_anrlin, 3, en_US]
Figure 5-47 Creation of the Pickup Indication of the Voltage-Current 3-Phase Function Group
The trip signals from the protection and supervision functions of the Voltage-current 3-phase function group
always result in 3-pole tripping of the device.
[lo_auslin, 3, en_US]
Figure 5-48 Creation of the Operate Indication of the Voltage-Current 3-Phase Function Group
If the device works with the IEC 61850 protocol, then you change only the setting value of the parameter via
DIGSI 5 and not directly on the device. If you change the setting value directly on the device, then the
IEC 61850 configuration of the metered values can be faulty.
NOTE
i If the device works with the IEC 61850 protocol, then you change the setting value of the parameter only
via DIGSI 5 and not directly on the device. If you change the setting value directly on the device, then the
IEC 61850 configuration of the metered values can be faulty.
The settings listed here are used primarily for understanding during configuration of the function groups. They
are calculated on the basis of other settings and cannot be directly changed.
Addr. Parameters C Range of Values Default Setting
Network data
_:103 General:rated apparent power 0.20 MVA to 5 000.00 MVA 692.82 MVA
NOTE
i For more detailed information on the process monitor, refer to 5.7.8 Process Monitor.
5.7.6 Settings
• Current-flow criterion
• Circuit-breaker condition
• Closure detection
[dw_pro3pt, 2, en_US]
You can activate the cold-load pickup detection as needed. All other stages of the process monitor run perma-
nently in the background and are not displayed in DIGSI.
The following figure shows the relationships of the individual function blocks.
[lo_pro_3pt, 2, en_US]
Logic
[lo_proikr, 2, en_US]
The phase currents are provided via the interface to the protection function group.
The I open signal of one phase is generated if one of the following conditions is met:
• A phase current falls below the set threshold of the Current thresh. CB open parameter. The
hysteresis stabilizes the signal.
• The corresponding phase current, for example, I A, falls below 10 % of the phase current when the trip
command arrives. If the current does not drop until after a delay due to current transformer influences,
an open pole can therefore be detected quickly even after a high-current fault on the line.
With the Current thresh. CB open parameter, you define the minimum current as the criterion for a
deactivated line. The parameter lies in the Circuit-breaker function group. It acts both in the Circuit-breaker
function group, for example circuit-breaker position recognition, and also for the process monitor in the
protection function group.
If a protection function group with integrated process monitor is connected to several Circuit breaker FGs,
the Current thresh. CB open parameter is present in each FG Circuit breaker. The smallest setting
value of the parameter Current thresh. CB open is used.
Logic
[lo_prolsz, 2, en_US]
Figure 5-52 Logic Diagram of the Circuit-Breaker Condition for the Protected-Object Function Block
The circuit-breaker position recognition in the Circuit-breaker (CB) function group provides the circuit-breaker
condition by way of the internal signal CB pos. recogn. prot. obj..
If a protected object is supplied via 2 circuit breakers (CBs), for example with the 1 1/2 circuit-breaker layout,
then the circuit-breaker switch position of the protected object must be determined with the aid of both circuit
breakers. In this case, the Circuit-breaker position recognition for the protected object function block
connects the individual CB states. The connection provides the internal CB pos. recogn. prot. obj.
signal to the other function blocks of the process monitor and to other functions, for example, Trip in the
event of weak infeed and Echo function for teleprotection method, within the same function group.
If one of the following 2 conditions is met, the CB pos. recogn. prot. obj. signal is in the Open state:
• At least one of the connected circuit breakers signals the Closed state internally.
Logic
[lo_ein_6md, 1, en_US]
For an applied binary input signal (_:6541:300) Detected (from function block Manual close), the indica-
tion (_:4681:300) Closure is active.
Logic
[lo_pro_cls, 2, en_US]
Figure 5-54 Logic Diagram of the Cold-Load Pickup Detection Function Block
The Cold-load pickup detection function block detects that a specific time has been exceeded after deactiva-
tion of the line or protected object. If you want to connect the protected object again, you must note that an
increased load-current requirement exists for a limited time after connection. This results from the nature of
the load.
The Cold-load pickup detection function block ensures that different parameters are used for an adjustable
time after connection. For example, for the time of the Min. CB-open time parameter, you can increase
the threshold value of a protection function or you can select a special characteristic curve.
If the Cold-load pickup detection function block detects an open feeder and the set time of the Min. CB-
open time parameter has expired, the indication >Activate cold-load is generated.
With the >Activate cold-load indication, you can activate a parameter set of the Cold-load pickup func-
tion. Via the binary input signal >Activate cold-load, you can also activate the >Activate cold-load
indication directly.
If the Cold-load pickup detection function block detects closure and the corresponding load current, it starts
the time set in the Dropout delay CB closed parameter. The >Activate cold-load indication and
the activated parameter set are deactivated after this time has elapsed.
If, for the time set in the Dropout delay curr.crit. parameter, the maximum phase current falls below
the threshold value Dropout threshold current, the parameter set for the Cold-load pickup detection
function block is also deactivated. As a result, if the load current is very low, the action time Dropout delay
curr.crit. of the >Activate cold-load indication can be shortened.
NOTE
i The settings and indications described in this chapter are only available when using the optional Cold-load
pickup detection function block.
With the Min. CB-open time parameter, you set the time after which the dynamic parameter set is acti-
vated in the event of cold-load pickup when the line is opened.
5.7.8.10 Settings
5.8.1 Overview
You can find a detailed description of the function group Analog units in the device manual Distance protec-
tion, line differential protection and switch management for 1-pole and 3-pole tripping 7SA87, 7SD87, 7SL87,
7VK87.
5.9.1 Overview
The device has a flash memory in which records can be saved. The recording documents operations within the
power system and how devices respond to them. You can read out records from the device and analyze them.
Depending on the recorder, the records are available in different file formats (see the following table).
[dw_fg_recorder, 4, en_US]
NOTE
i If you want to use one of the following functions, the device must be equipped with the CP300 CPU printed
circuit board assembly:
• Slow-scan recorder
• Continuous recorder
• Trend recorder
The Recording function group is a central device function. Both the recording criterion and the measured-
value and binary channels to be recorded are functionally preconfigured through the application templates.
You can individually adapt the configuration in DIGSI 5.
For more information on the Fault recorder function, refer to Fault Recording, starting at 3.5.1 Overview of
Functions .
For more information on the Recording function group, refer to the Manual for the Recording function group
(C53000-H5040-C089).
5.10.1 Overview
The Power-system data are provided with each SIPROTEC 5 device and cannot be deleted. You will find them
in DIGSI 5 under Parameter → Power-system data.
The Power-system data function group (FG Power-system data) groups the user functions related to current
transformers and voltage transformers. Together with the measuring points created in the SIPROTEC 5 device,
the Power-system data represent the physical current transformer.
NOTE
The FG Power-system data only processes 3-phase measuring points with ground current (IN) in the busbar
protection device. The configuration is done using the Measured-value editor in DIGSI 5.
You can find more detailed information on this in chapter 2.1 Function Embedding in the Device
If the connection is missing, DIGSI 5 reports an inconsistency. This inconsistency provides an indication of the
missing phase routing or summation-current routing.
You can find further information on the Power-system data in chapter 6.1.2 Structure of the Power-System
Data.
6.1.1 Overview
The Power-system data are provided with each SIPROTEC 5 device and cannot be deleted. You will find them
in DIGSI under Parameter → Power-system data.
The Power-system data contain the block General and the Measuring points of the device. The following
figure shows the structure of the Power-system data:
[dw_power_7ke, 2, en_US]
In order to adjust its functions to the application, the device requires some data about the power system. The
necessary settings can be found in the Power-system data under General as well as in the Measuring points.
The busbar protection uses the Current 3-phase (Measuring point I 3-ph) and the Voltage 3-phase (Meas-
uring point V 3-ph) measuring points.
The measuring points have interfaces to the following function groups:
• Current transformer
• Voltage transformer
• Circuit breaker
6.1.3 Application and Setting Notes for Measuring-Point Current 3-Phase (I-3ph)
The following example of the Measuring-point current I-3ph (current 3-phase) describes the settings for the
current measuring points. The supervision function settings are also located in the current measuring point.
You can find the description of these settings in the chapter Supervision Functions.
Parameter: CT connection
Parameter: Tracking
NOTE
i To prevent unwanted frequency deviations for low-current feeders, switch off the sampling-frequency
tracking function.
6.1.4 Operating State: Measuring Point for Distributed Busbar Protection out of
Service
In a 7SS85CU-based distributed busbar protection system, you can use the service function Measuring point
for distributed busbar protection out of service to revoke the assignment of a measuring point, that is, of
the feeder current to a selective measuring system of the distributed busbar protection at the bay unit. The
residual protection functionality of the merging unit is unaffected by this.
If the measuring point is assigned to a distributed busbar protection measuring system, deactivating the meas-
uring point at the bay unit deactivates the affected bay for the distributed busbar protection. The decommis-
sioning of a measuring point is reported in the affected bay proxy in the 7SS85CU device.
The service function Measuring point for distributed busbar protection out of service is not pre-instanti-
ated by default in a measuring point for a bay unit. If required, the service function must be instantiated from
the DIGSI library into the desired measuring point of the respective bay unit.
The following figure shows the storage location for this service function in the DIGSI library, using the
example of the 6MU85 Merging Unit device type.
[sc_measure_poioutoford, 1, en_US]
If this service function is instantiated in a measuring point, you can take the measuring point out of operation
or put it back into operation using the control commands MP out of service cmd or via the binary input
>Out of service.
NOTE
i A measuring point can only be put back into operation in the same way that it was taken out of operation,
that is via the binary input or via a control command.
For more information on the Bay out of service and Measuring point out of service operating states, refer to
5.2.5 Operating State: Bay Out of Service and 5.2.6 Operating State: Measuring Point out of Operation.
6.1.5 Application and Setting Notes for Measuring Point Voltage 3‑Phase (V-3ph)
Settings for the supervision functions are also located in the voltage measuring point. You can find the
description of these settings in supervision functions.
With the parameter Rated primary voltage, you set the primary rated voltage of the voltage trans-
former.
The zero-sequence voltage is calculated as phase-to-ground voltages. The residual voltage is measured on the
broken-delta winding of the voltage transformer. For 1-phase voltage transformers, the residual voltage is
measured in the generator or the transformer neutral point.
NOTE
i The measurement residual voltage VN sec is converted to a zero-sequence voltage in the device as follows:
EXAMPLE 1:
[dw_bsp1uwdl_anpassfaktor, 2, en_US]
When the type of connection for the voltage transformer is 3 ph-to-gnd volt. + VN (parameter: VT
connection) and the voltage input V4 is connected to the broken-delta winding of the voltage transformer
(da/dn), the Matching ratio Vph / VN is as follows:
When changing the neutral point according to Figure 6-3, this results in the following values:
• The calculated secondary zero-sequence voltage V0 sec is equal to the secondary phase-to-ground voltage.
Expressed as secondary transformer rated voltage, then Vrated sec/√3.
• The measured residual voltage on the broken-delta winding is the sum of the voltage drops on the
3 sides. Expressed with the side ratio, the result is VN, sec = 3 Vrated sec /3.
[fo_example_1, 2, en_US]
In example 1 Vrated sec, the phase-to-ground voltage and the secondary voltage on the broken-delta winding
were identical. If these voltages are different, use the actual numerical values in the calculation.
EXAMPLE 2:
[fo_example_2, 1, en_US]
[fo_conversion2, 2, en_US]
NOTE
i During the ground-fault test, the set adaptation factor can be checked by comparing the operational meas-
ured values. The operational measured values contain the calculated zero-sequence voltage V0 sec and the
measured residual voltage VN sec. Proceed with the compilation as follows:
The Matching ratio Vph / VN parameter is significant for the following functions:
• Measured-value supervision
Parameter: VT connection
• 3 ph-to-gnd volt. + VN
• 3 ph-to-gnd voltages
• 3 ph-to-ph volt. + VN
• 3 ph-to-ph voltages
• 2 ph-to-ph volt. + VN
• 2 ph-to-ph voltages
• 2 ph-to-gnd volt. + VN
• 2 ph-to-gnd voltages
Depending on the connection type selected, you must route the measured values to the terminals of the
voltage measuring point in DIGSI 5. You can find connection examples for voltage transformers in A.7 Connec-
tion Examples of Voltage Transformers for Modular Devices. The connection examples provide assistance
when selecting the type of connection.
Parameter: Tracking
the device switches to another channel (etc.). Once switched to a current channel, the system automatically
switches back to this channel if a voltage channel is valid again.
Parameter Value Description
active If you set the parameter Tracking = active, the measuring point will be
included when determining the sampling frequency. If possible, only the 3-
phase measuring points shall be considered.
Siemens recommends using the default setting.
Note: If the parameter Tracking is active, the determined sampling
frequency applies to all functions in the device not using fixed sampling
rates.
inactive If the channels of the measuring point are not to be considered for deter-
mining the sampling frequency, select the setting value inactive.
Parameter: Measuring-point ID
NOTE
i The Magnitude correction parameter has nothing to do with the internal adjustment of the input
circuit.
6.1.6 Settings
General
The busbar protection is a selective, safe, and quick protection if busbar short circuits should occur and if
circuit breakers fail. The protection can be utilized for a variety of busbar configurations in medium, high, and
extra-high voltage systems.
Busbar protection is suitable for switchgear with closed iron core or linearized current transformers.
Busbar protection employs a phase-selective method of measurement.
[dw_struss, 2, en_US]
The check zone function blocks, 1 busbar section, and the function-specific parameters are always available.
Additional busbar sections and the function blocks for the busbar sections without measuring system are
optional.
[dw_buszone, 1, en_US]
Figure 6-5 Interaction Check Zone and Busbar Section with Busbar Differential Protection
General
Busbar differential protection is characterized by the following functions and properties:
• Decision to trip based on 2 independent measurements. One measurement is performed for the bus
zone, the second measurement takes into account all bus zones without the disconnector image (check
zone).
• Restraint to prevent unwanted tripping in the event of external faults and saturation of the current trans-
formers
• Pickup of differential-current supervision selectively for the busbar section and phase-selectively with and
without blocking
• Detecting disconnector faults, faults in the feeder, or measuring errors with and without blocking
• Independently selectable operate curves for the check zone and the busbar zones. Both a normal pickup
characteristic and the sensitive characteristic are available.
• Adaptation to different transformation ratios of the current transformers without use of interposing
transformers
• Selective detection of short circuits, even on the transfer busbar (TB) with command output for tripping
of the circuit breaker at the opposite end.
Basis
The method of measurement is based on Kirchhoff's current law. This law states that the sum of all currents
flowing into a closed region is 0 if the sign is taken into account. This natural law applies to alternating
currents at all times. The sum of the currents from all feeders connected to a busbar must thus be 0 at all
times.
[dw_ssnabz, 1, en_US]
In the healthy state, the following equation applies to the currents I1, I2, I3 to In in the feeders of the busbar.
I1 + I2 + I3 ... In = 0
A prerequisite is standardized orientation of the currents. For instance, currents flowing to the busbar are posi-
tive, currents flowing away are negative.
If this equation is not satisfied, current must be flowing along an impermissible path. There must be a fault.
This rule forms the basis for busbar differential protection. The sum of the currents is the only quantity that
identifies a healthy state. This quantity can be calculated at any time. The current sum remains 0 as long as
there is no fault.
The above considerations apply to the primary-side processes in the high-voltage system. The currents flowing
in the high-voltage system cannot be employed directly for the busbar protection measurements. The protec-
tion equipment is connected with current transformers. The current transformers reduce the currents precisely
on the basis of the transformation ratio of the current transformer. The vector orientation of the currents is
retained.
The installation location of the current transformer specifies the range limit for the busbar protection. The
following equation results from the proportional conversion of the primary currents (Iprim) into secondary
currents (Isec) for the healthy state:
I1 sec · w1 + I2 sec · w2 + I3 sec · w3 ..... + in sec · wn = 0
At the busbar level, the currents from all bays must be referenced to a common transformer ratio. This is why
the currents associated with the individual bays are normalized during the engineering for the system. The
normalization factor is calculated from the Irated (feeder) /Irated,obj ratio. Where Irated,obj is the common normaliza-
tion current for the entire system.
Busbar protection designed in this way detects every short circuit within the protection range. Transformation
errors in the transformers can result in unwanted disconnection, for example, in the event of a nearby short
circuit on a feeder. In this case, the current flowing in the short circuit is divided among several bays on the
infeed side. The transformers in the feeding bays each receive only a fraction of the short-circuit current to be
transformed. The transformer set in the faulty feeder conducts the full short-circuit current on the primary
side. With a very high short-circuit current, this transformer set can provide only a fraction of the set point
value on the secondary side as the result of saturation. The remaining current transformers operate correctly
because the current is divided. Although the sum of the currents is 0 on the primary side, the sum of the
secondary-side currents is not 0 in such a case.
To compensate for such situations during operation, busbar differential protection serves as a stabilizing func-
tion.
Stabilization
Stabilization reduces the effects of the different transformation ratios in the current transformers on the meas-
urement of the feeder currents and, in this way, prevents a faulty response of the protection. Busbar differen-
tial protection forms the vector sum of the secondary transformer currents and the sum of their magnitudes.
The vector sum acts in a triggering sense. The sum of the magnitudes acts in opposition to pickup.
[dw_istmod, 1, en_US]
The restraint current obtained in this manner is smoothed by the software in order to ensure stability even in
cases of extreme saturation.
Characteristic Curves
The range from the lowest to the highest short-circuit current can vary considerably, depending on the layout
of the system. In addition, the data and loads for the connected current transformers play a significant role.
Once the protection has been configured and set, the neutral point in the grid is important as well. For these
reasons, the busbar protection must have suitable adaptability.
[dw_char_sensitive, 3, en_US]
The diagram shows the operate curve for the busbar differential protection. The horizontal axis represents the
sum of the magnitudes of all currents Irest,mod flowing through the busbar. The vertical axis is assigned to their
vector sum Idiff. The horizontal and vertical axes have the same scaling.
In the event of a busbar short circuit with the same vector orientation as the infeed currents, Idiff equals Irest.
The fault characteristic then follows a straight line at an angle of 45 ° in the diagram. Differences in the vector
orientation of the fault currents result in an inconsequential lowering of the fault characteristic. Since Idiff is
approximately equal to 0 during healthy operation, the x-axis forms the operating characteristic.
The stabilization factors can be selected from within the range k = 0.10 to 0.80 for busbar-selective busbar
protection, and from within the range k = 0.10 to 0.80 for the check zone. Straight lines at a corresponding
angle represent the operate curves associated with the factors. The busbar differential protection determines
whether the value pairs Idiff/Irest lie within the tripping range or the stabilization range.
[dw_empken, 2, en_US]
6.2.5 Measurands
Displacement
If the short circuit does not occur at the voltage maximum of the periodic cycle, the short-circuit current
initially has a direct-current component imposed on it. It decays with the time constant τ = L/R of the external
impedance. Time constant τ values of around 60 ms are encountered frequently in high-voltage power
systems. In the vicinity of large machinery, values of 100 ms and longer are possible.
Saturation
Direct-current components cause a one-sided, increasing bias in the transformer core. The transmission
behavior can be seriously compromised by transformer saturation.
The basic principle underlying the busbar differential protection must be augmented by additional measures
under these difficult operating conditions. In the protection device, these ensure the restraint of the protec-
tion in the event of external high-current short circuits. At the same time, they make a tripping decision
possible when an internal short circuit occurs within one period of the power system.
The following figures show the conditions for the extreme case of an initially fully displaced short-circuit
current. In addition, biasing of the current transformer being considered has been assumed to make the situa-
tion more difficult.
The curve representing the initially fully displaced primary current is shown. At the beginning of the process,
the direct-current component has the peak value of the short-circuit current and decays with τ = approx.
50 ms. It is assumed that the current is flowing through a current transformer that is just able to transmit the
alternating current without saturation if it and the magnetic flux in the iron are not displaced.
[dw_kl_prim, 1, en_US]
Figure 6-10 Qualitative Representation of the Primary and Secondary Current in a Transformer
Approaching Saturation in the Event of a Fault (Direct-Current Component with a Time
Constant of Approx. 50 ms).
Because of the superimposed direct-current component and the unfavorable magnetic flux at the start of the
short circuit, saturation occurs in the current transformer after about 6 ms. The magnetic flux can no longer
increase and the transformer induces no more current on the secondary circuit. Transmission to the secondary
circuit is possible only after current flows in the opposite direction following zero crossover. As a consequence,
the currents below the axis are transmitted correctly. From the currents above the axis, the current trans-
former can form on the secondary circuit only that amount of the current-time area that contains the previous
negative half wave.
[dw_klkurz, 2, en_US]
Figure 6-11 Differential and Restraint Current in the Event of an External Short Circuit and Transformer
Saturation
With a stabilizing factor of k = 0.65, the measurands lie in the tripping range after about 8 ms following the
start of the short circuit. This state lasts for about 4 ms before stabilization prevails. The current flowing in the
opposite direction following zero crossover is processed correctly and does not cause tripping.
As a consequence of the second positive half wave in the direction supported by the direct-current compo-
nent, the measurands once again lie in the tripping range. This condition lasts for about 3 ms. As time
progresses, the direct-current component decays. This restores the ability of the initially highly saturated
current transformer to function properly. The tripping differential current Idiff no longer equals the restraint
current k · Irest,mod.
The tripping quantity clearly increases beyond the restraining quantity twice. The algorithms used in the
protection device however ensure restraint and prevent an overfunction.
[dw_klglat, 1, en_US]
Figure 6-12 Differential and Restraint Current in the Event of an External Short Circuit - Restraint Current
Smoothed
[dw_klinks, 1, en_US]
Figure 6-13 Differential and Smoothed Restraint Current in the Event of an Internal Short Circuit
Comparison of the measured values in cases of an external and an internal short circuit illustrates 2 essential
product features:
• After several periods, during which the direct-current component has largely decayed, the correct meas-
ured values are present in each half wave. These measured values correspond to the location of the fault
in relation to the set operate curve.
• At the start of the short circuit, the correct measured value is likewise formed during each process. This
measured value corresponds to the location of the fault.
These 2 product features are used in the busbar protection to distinguish between external and internal short
circuits.
The following properties result:
6.2.6 Algorithms
6.2.7 Tripping
[lo_ssdiff, 3, en_US]
[lo_zuskrt, 3, en_US]
The timing of the release signal for tripping of a busbar can be monitored. Use the parameter Trip release
supervision to set whether the monitoring reacts with or without blocking. The monitoring time for the
release signal is fixed at 15 s.
[lo_auscom, 4, en_US]
The assignment of the feeder currents to the measuring systems of the bus zones is performed automatically
using the disconnector positions. For this purpose, the Off position is evaluated. As a result, there are no
special requirements for the disconnector auxiliary contacts (for example, adjustment). The On position is
used only for disconnector-status monitoring (disconnector disturbance, disconnector intermediate position).
The status changes of both information signals Disconnector off and Disconnector on are used to determine
the disconnector runtime. For this reason, a true image of the disconnector runtime results from the use of
limit switches such as those often used in systems control. The following figure shows the principle connec-
tion.
[dw_bbp_line_discon_image, 2, en_US]
Preferably, you connect the 3 auxiliary contacts of the position feedback Off or On in series. This ensures that
one disconnector is treated as open only if all 3 poles are opened. In all other cases, the disconnector is
processed as closed. With the DIGSI 5 single-line monitoring, you see the entire disconnector image in graphic
form.
A bus coupler bay is assigned to the appropriate bus zones only when at least one disconnector is activated on
both sides of the bus coupler (left and right of the circuit breaker). Operational current flow is not possible
until then. The busbar feeding of the error trips immediately with closing of the 1st disconnector and short
circuit in the bus-coupler area, independent of the fault location and instantaneous circuit-breaker switch posi-
tion.
The measuring system for the check zone detects a short circuit in the entire busbar. In this case, the discon-
nector positions are not taken into account. The disconnector positions must be taken into account in conjunc-
tion with the check zone only in special cases, for example, for transfer busbars or combined busbars.
When the restraint current is calculated, overstabilization may result in the case of multiple busbars. The over-
stabilization is caused by the current flowing through the bays that are not connected to the faulty busbar.
To prevent overstabilization, the restraint current is obtained in the following manner:
Σ | Ip | = Sum of the magnitudes of the currents that are flowing to the busbar
Σ | In | = Sum of the magnitudes of the currents that are flowing away from the busbar
Irest = the smaller of the 2 sums
In this calculation, only half of the load current flowing acts as the restraint current.
The short-circuit current does not stabilize the check zone and acts only as a differential current.
The following figure and equations explain the behavior with and without special treatment.
[dw_stabcz, 1, en_US]
Figure 6-18 Treatment of the Restraint Current for the Check Zone
Idiff= | I1 + I2 + I3 + I4 − I3 − I4 | = | I1 + I2 |
Restraint current without special treatment:
Irestr = | I1 | + | I2 | + | I3 | + | I4 | + | I3 + I4 |
The load currents I3 and I4 are taken into account twice when calculating the restraint current. This results in
overstabilization.
With special treatment, the following situation results:
Σ | Ip | = | I1 | + | I2 | + | I3 | + | I4 |
Σ | In | = | I3 + I4 |
Irestr = Σ | In | = | I3 + I4 |
Irestr corresponds to half of the magnitude of the entire load current
The restraint current is modified for the characteristic-curve query. You will find information about this in the
chapter 6.2.4 Method of Measurement and Characteristic Curves under Restraint.
The phase-angle difference between the short-circuit and load currents can result in differences in the sum
obtained.
You can switch off the measuring system for the check zone using the Check zone parameter.
6.2.10 Supervision
In the following situations, a bus section of the differential protection becomes inactive (Health = Alarm):
• Invalid measured values, for example, pickup of the fast current-sum supervision, module-connection
errors (PCB link)
20 With blocking of 1 or 2 phases, Health switches to the Warning mode, the state remains active.
In the following situations, the check zone of the differential protection becomes inactive (Health = Alarm):
• Invalid measured values (for example, pickup of the fast current-sum supervision, module-connection
errors)
The following conditions cause group indications and group warnings by the differential protection:
• Group warning:
– Invalid measured values, for example, pickup of the fast current-sum supervision, module-connec-
tion errors
– Frequency outside the permissible range of 10 Hz to 90 Hz
– Blocking by differential-current supervision
– Blocking by supervision of the additional criterion
– Blocking by zero-crossing supervision
– Blocking by supervision of the trip release signal
– Blocking by supervision of the release signal for the sensitive characteristic curve
– External tripping – Signal error (tripping, release)
• Group indication:
– Pickup of the differential-current supervision without blocking
– Pickup of the supervision of the additional criterion without blocking
– Pickup of the supervision of the trip release signal without blocking
You use this parameter to activate the monitoring of switching to the sensitive characteristic curve. If the
binary input for switchover of the sensitive characteristic curve is on for longer than 15 s, the activation of the
sensitive characteristic curve is withdrawn.
Parameter Value Description
off Monitoring of the input signal >Sens. characteristic is deactivated.
on Monitoring of the input signal >Sens. characteristic is active.
This chapter describes the parameters that apply to all busbar sections.
With this parameter, you set the reach of the sensitive characteristic curve in regards to the restraint current.
For larger restraint currents, the standard characteristic curve is used. The parameter is used by busbar-selec-
tive busbar protection.
If the restraint current reaches the set value, the operating point exits the area of the sensitive characteristic
curve.
The parameter is visible only if (_:11821:105) Sens. characteristic is set to existent.
The setting depends on the maximum restraint current expected and the current transformer behavior.
Threshold Is /sens.char. = 1.2 · (Imax load + IEF).
Imax load = Sum of the magnitudes of all load currents flowing in and out
IEF = Ground-fault current
• Comparison
For the current transformer, the following must be satisfied: K´ssc (actual) > K´ssc (required)
Calculation example:
The following data are known for a transformer:
Transformer: 600/1, 5P10, 15 VA
Resistance, secondary winding (Rct): 4 Ω
Winding: 50 m, 4 mm2 CU
Device burden (Rdevice): 0.1 Ω
Resistivity of copper ρcu: 0.0179 Ω mm2/m
Calculation of the required K'ssc where Iscc max = 30 kA
Required K'ssc > K'td • Iscc max / IN = 0.5 • 30 kA / 600 A = 25
Calculation of the actual K'ssc = Kssc • (Rb + Rct) / (R'b + Rct) = 10 • (15 + 4) / (0.55 + 4) = 42
Thus, the requirement of K´ssc (actual) > K´ssc (required) is satisfied with the values selected in the
following.
Kssc = 10
Rb = Sn / Isn2 = 15 VA / 1 A2 = 15 Ω
Rct = 4
R'b = Rl + Rdevice = 2ρ • l / A = 2 • 0.0179 (Ω mm2/m) • 50 / 4 (m/mm2) + 0.1 Ω = 0.55 Ω
This calculation is an initial, rough estimate. If K´ssc (actual) is less than K´ssc (required), adjust the stabi-
lization factor k.
• Final evaluation
If the above-mentioned conditions are met, the current transformer is suitable for connection to busbar
protection and the default stabilization factor can be retained. More calculations are then unnecessary. Other-
wise, the stability can be increased by suitable selection of the stabilization factor. To do this, however, exten-
sive calculations would be necessary, for example, using the CTDim program.
Perform the tests for every current transformer. A relation between the smallest and largest current trans-
former ratio need not be considered.
The following settings are visible only if _:12151:102 Check zone is set to on.
You use this parameter to set the threshold value for the sensitivity of the check zone in the case of low fault
currents.
If the set threshold is exceeded, busbar differential protection picks up. If the current drops below the limit,
the trip command drops out.
The maximum permissible setting value is based on the lowest fault current that can be expected in the event
of a busbar short circuit. In addition, the setting value should have a pickup margin about 20 %.
The lowest permissible setting value is 30 % above the maximum operating current of all feeders: Imax feeder +
30 %.
1.3 Imax feeder < Threshold Idiff < 0.8 Iscc min.
Iscc min corresponds to the minimum continuous short-circuit current.
Parameter: Mode
6.2.16 Settings
The Circuit-breaker failure protection function (ANSI 50BF) monitors the tripping of the associated circuit-
breaker (CB) and generates a backup trip signal if the circuit-breaker fails.
The circuit-breaker failure protection in the busbar protection has the following tasks:
• Tripping of the circuit breaker in the bay in the event of errors on the line.
The description for this function is in the following chapters.
• Tripping of all circuit breakers of a busbar section in the event of unsuccessful tripping by the circuit-
breaker failure protection in the bay.
The description of the additional operating modes for this function are in chapter 6.3.4 Circuit-Breaker
Failure Protection in Busbar Protection.
• Monitoring of all circuit breakers in the event of errors within the protection range of the busbar protec-
tion (internal tripping of the busbar section). In the event of unsuccessful tripping of the circuit breaker, a
transfer-trip signal can be transmitted to the opposite end.
The description of this function can be found in chapter 6.5.1 Overview of Functions .
Starting with version V7.50, the previous function CB failure has been replaced with the new circuit-breaker
failure protection with an adaptive algorithm Adaptive CB failure protection. In this way, you achieve a
faster, more reliable detection of the opening of the circuit breaker in the event of complex signal histories.
The 2 functions are identical, with the exception of a slightly increased processor load, in terms of setting
options, logic and indications. Siemens recommends using the adaptive circuit-breaker failure protection and
avoiding mixing the protection types in one device. You can find additional information on the processor load
in DIGSI for each device under Device information in the Resource consumption tab.
The function Circuit-breaker failure protection (CBFP) can be used in the Circuit-breaker function group.
[dw_strbfp, 1, en_US]
Figure 6-20 shows the functionalities and the function control of the function.
The start is initiated by an external protection. Along with the start, the current-flow criterion or the circuit-
breaker auxiliary contact criterion is used to check whether the circuit breaker is closed. If the circuit breaker is
closed, the function picks up and starts the time delay. During the time delay, the system continuously checks
whether the circuit breaker has opened. If this is the case, the function drops out. If the circuit breaker is not
opened, the function trips upon expiration of the time delay.
The following description elaborates on the detailed functionality of the individual function blocks.
[lo_svs_bfp, 3, en_US]
The function is started via the device-internal protection functions and/or externally (via a binary input or
interface, for example, GOOSE). The start can be done 1-pole or 3-pole. Figure 6-21 and Figure 6-22 show the
functionality.
Internal Start
In the case of busbar protection, each device-internal protection, such as the differential protection, that has
to control the local circuit breaker starts the inherent circuit-breaker failure protection (see 6.5.1 Overview of
Functions ). You can configure other protection functions, such as overcurrent protection for the internal start,
via the circuit-breaker interaction matrix. The function is started by the tripping of the protection stage. In case
of phase-selective tripping, the start will also be phase-selective. In the default setting, the starting signal
Internal start (see Figure 6-21) is held when the pickup signal is cleared or the protection function has
tripped. The Circuit-breaker failure protection function can in this case only drop out if the circuit breaker is
detected to be open. This is detected using the current flow or circuit-breaker auxiliary-contact criterion. If
necessary, the Circuit-breaker failure protection function can also drop out when the pickup signal is cleared
or the protection function trips (internal starting signal is not held).
Using routing, you can specify whether individual protection stages or protection functions are to be used as
the starting source or whether starting happens only externally.
The internal starting sources are routed in the protection function groups via the Circuit-breaker interaction
entry (for this see 2.1 Function Embedding in the Device , Project tree in DIGSI 5 (excerpt)).
[lo_intsta_bbp, 2, en_US]
External Start
The parameter Start via binary input is used to set whether the external start is initiated by a 1-
channel or 2-channel signal. The required routing of the input signals is compared with the setting. If a
routing is missing, an error message is generated. The Health signal changes to the state Warning.
[lo_anwext2, 2, en_US]
Figure 6-22 Configuration of the External Start of the Circuit-Breaker Failure Protection Function
In 1-channel mode, start for 1-pole tripping is initiated only with the binary input signals >Start pole A,
>Start pole B or >Start pole C. In the case of 3-pole tripping, start is initiated only with the input
signal>Start 3-pole (see Figure 6-23).
In 2-channel mode, to initiate the start, the binary input signal >Release 1-polemust also be activated, in
case of the 1-pole start, and >Release 3-pole in case of the 3-pole start. In the default setting, the internal
starting signals External start phsx and External start 3-pole drop out immediately when the
binary input signals are cleared (see Figure 6-23). If necessary, the internal starting signal can be held. In this
case, the start remains active when the binary input signals are cleared.
The input signals are monitored to avoid an unwanted pickup of the function.
If either of the signals >Start or >Release is active for more than the set monitoring time of the appro-
priate signal without the function picking up, a fault in the binary input circuit is assumed. The corresponding
signal is blocked to exclude an external pickup of the function. An indication to this effect is output, and the
Health signal changes to the state Warning. The blocking is reset as soon as the binary input signal drops out.
Supervision is disabled in the following cases:
• On pickup of the Circuit-breaker failure protection function (only in the case of an external start). This
prevents an unwanted pickup of the supervision if the external protection that starts the Circuit-breaker
failure protection function uses a lockout functionality. When the starting signal drops out, supervision is
enabled again.
• As long as the function or the device is in test mode. This allows to check the function without the super-
vision blocking the function.
If the >Start signal is active and no release signal is present after elapse of a settable monitoring time for the
starting signal, the pickup is blocked and an indication to this effect is output. The Health signal changes to
the state Warning. The blocking is reset with the dropout of the starting signal.
The binary input signals only take effect if the binary inputs are activated for at least 10 ms (SW filter, see
Figure 6-23).
[lo_ex_lsvs, 4, en_US]
Figure 6-23 External Start of the Circuit-Breaker Failure Protection Function, Logic
[lo_veranw, 2, en_US]
Current-Flow Criterion
The current-flow criterion is the primary criterion for determining the circuit-breaker switch position. A circuit-
breaker pole is supposed to be closed, and the current-flow criterion fulfilled, as soon as one of the phase
currents exceeds the phase-current threshold value, and at the same time a plausibility current exceeds the
associated threshold value. The plausibility current can be either a 2nd phase current (to compare with the
threshold value for phase currents) or the zero-sequence or negative-sequence current (to compare with the
sensitive threshold value). The additional evaluation of the plausibility current increases the safety of a crite-
rion.
In the case of ground faults, the sensitive threshold value can be dynamically applied to the phase currents as
well. The current-flow criterion is in this case fulfilled when the currents exceed the sensitive threshold value.
The phase-current threshold value is then ineffective. The binary signal >Threshold sensitive is used for
the switchover.
If you set the parameter 3I0 criterion to Direct release, you block the plausibility check of the zero-
sequence current. In this way a pickup can only be achieved by way of this current. The Threshold 3I0
dir. release parameter is used to set the threshold value to be exceeded.
If you set the parameter I2 criterion to Direct release, you also switch off the plausibility check of
the negative-sequence current. The Threshold I2 dir. release parameter is used to set the threshold
value to be exceeded.
If you set the parameter I2 criterion to Direct release, plausibility is checked via the phase currents
with 1/3 * Threshold I2 dir. release. This is to prevent a false pickup of the current-flow criterion in
the open pole after a 1-pole OFF.
The measuring algorithm is optimized for fast dropout when the value drops below the threshold value.
[lo_currentk, 4, en_US]
• In this function, circuit-breaker auxiliary contacts are not used for determining the CB position.
• The position is determined (pole-selective) via the double-point indications Position phsx (from the
Circuit breaker function block).
• The double-point indication 3-pole position (from theCircuit breaker function block) is used to
determine whether all 3 poles of the circuit breaker are closed.
If the double-point indications are not routed, an error message is issued. The Health signal changes to the
state Warning. You must do the routing with the closed contact or the closed and open contact. If this is not
the case, an error message is output, and the Health signal changes to the Warning state.
A detected static disturbed position (not an intermediate position) has the effect that the circuit-breaker auxil-
iary-contact criterion is not used (the signals Aux.co.crit. CB Clsd phsx are inactive).
[lo_hikols, 1, en_US]
Pickup/Dropout
After the start, a check is performed whether the circuit breaker or the individual circuit-breaker pole is closed.
The current-flow criterion and the circuit-breaker auxiliary-contact criterion are available for this purpose.
Even if the circuit-breaker auxiliary-contact criterion is permitted, preference is given to the fulfilled current-
flow criterion because it is the most reliable criterion for determining whether the CB or CB pole is closed. This
means that the CB or CB pole is considered to be closed if it is closed according to the current-flow criterion
but, at the same time, open according to the circuit-breaker auxiliary-contact criterion.
If no current is flowing at the start time, the function can only pick up on the basis of the circuit-breaker auxil-
iary-contact criterion. For this purpose, the circuit-breaker auxiliary contacts must be permitted as criterion.
When the current begins to flow after the start, the function switches over to the current-flow criterion.
If the circuit breaker or a circuit-breaker pole is detected as closed and a start occurs in this pole, the function
picks up.
The pickup starts a time delay (see Delay/Tripping). While the time delay is running, the system checks contin-
uously whether the circuit breaker or a CB pole has opened. In the default setting, the opening of the circuit
breaker is checked on the basis of the currently valid criterion, which is normally the current-flow criterion
because it is preferred. If until expiration of the time delay, no current flow above the set threshold values has
been detected, the circuit-breaker auxiliary-contact criterion becomes effective.
The function has also a setting in which dropout is only possible if both criteria detect in parallel the CB or CB
pole to be open (dropout with auxiliary-contact and current-flow criterion).
In the default setting, the internal starting signal is held (see Figure 6-21 and Figure 6-23). This means that
dropout is controlled solely by the current or the circuit-breaker auxiliary-contact criterion. If dropout is also to
occur with a cleared starting signal (that is, with a cleared pickup signal or operate of the protection function),
holding of the start signal must be disabled.
[lo_pickup, 3, en_US]
Delay/Tripping
In a first step, tripping at the local circuit breaker can be repeated. Tripping is repeated after expiration of the
settable delay T1. You can set various T1 times for a 1-pole and multipole start. In case of a 1-pole start, trip-
ping can be repeated in a 1-pole or 3-pole way depending on the setting. If the local CB was not yet tripped,
for example, in the event of an external start of the circuit-breaker failure protection, the trip logic of the
circuit breaker itself is activated when the time delay T1 elapses.
Time delay T2 (backup tripping) can commence in parallel either with the start of time T1 or after expiration of
time T1. You can set various T2 times for a 1-pole and multipole start.
If the assigned 1-pole period is initially started by a 1-pole start and a multiphase short circuit and multiphase
start occur subsequently, the corresponding multiphase period is also started so that the both periods run in
parallel. Tripping is determined by the period that expires first.
When there is a 1-pole start with 3-pole trip repeat, the 3-pole T2 time is started.
If time delay T2 expires without a dropout of the function, a circuit-breaker failure is assumed, and the backup
tripping signal Trip T2 is generated. The Trip T2 activates busbar protection. This tripping is always 3-
pole. A transfer-trip signal can be sent to the opposite end if necessary. Thus, the circuit breaker on the oppo-
site end can be tripped without delay.
If the >CB defect input signal is valid, any repetition of the trip signal is suppressed, and the backup tripping
signal T2 is generated immediately (without delay). The binary input of the >CB defect input signal must be
activated for at least 20 ms before the signal becomes valid.
With the CB failure pole indication, you can determine the phase currents that are above the set
threshold value at the tripping time T2.
The Minimum operate time parameter defines the minimum duration for tripping the function. In contrast
to other protection functions, the parameter is set within its own function. As a result, the setting is inde-
pendent of the identically named superordinate parameter that is set in the Device settings.
[lo_bbp-verzau-1ph, 6, en_US]
With the Immediate dropout parameter, you determine whether the circuit-breaker switch position is
checked continuously or before expiration of the T1 and T2 time delays. If the circuit-breaker switch position is
checked once the time delays have expired, the function picks up using Start.
The circuit-breaker failure protection in busbar protection specifies a circuit-breaker failure with a short circuit
in the feeder or with a short circuit in the busbar.
If a short circuit occurs in the feeder, a circuit-breaker failure leads to selective disconnection of the busbar
section on which the feeder with the defective circuit breaker is connected. In addition, an intertripping
command is output in order to also switch off the opposite line end.
If a short circuit in the busbar and a circuit-breaker failure occur, at the opposite end of the line the infeed of
the current must be interrupted. For this purpose, the Trip T2 is output.
If the circuit-breaker failure protection works together with the busbar protection, with pick up of Trip T2,
the busbar protection is activated. If the circuit breaker has not opened, the busbar protection trips the
assigned busbar section.
There are 2 operating modes available for tripping the busbar:
• Unbalancing
• I> Query
NOTE
i If an active end-fault protection has already set the feeder current to 0, no unbalancing will be performed.
The operating mode is set in the Circuit breaker function group under General separately for each bay. In this
way, the function can be optimally adapted to the operating conditions, for example to the type of feeder or
the short-circuit currents.
NOTE
i You must differentiate between the centralized busbar protection, the distributed busbar protection (IEC
61850 compliant), and the distributed busbar protection.
• Centralized: The start occurs in parallel with the Trip T2 for the busbar function group.
• Decentralized (IEC 61850-compliant): Route the Trip T2 from the merging unit to the external trip-
ping in the bay using GOOSE.
• Distributed: If you have set the CBFP interact. with dBBP parameter to Yes for the circuit-
breaker failure protection in the merging units, the starting signal is transferred.
[dw_ls_ssys, 3, en_US]
The corresponding application and setting notes are in chapter 5.3.3 Application and Setting Notes
• No danger of undesirable tripping even with longer dropout times since the current flow from the circuit
breaker is already interrupted and thus no differential current occurs due to the unbalancing.
• Use of the same algorithms and the same trip logic as the busbar differential protection.
[dw_char_svs, 2, en_US]
Figure 6-31 gives an overview of the functions involved in an external start of the CBFP function. In the case of
an internal start, there is no external protection device and the protection functionality is located in the CBFP
device.
[lo_aus_1bf, 2, en_US]
Figure 6-31 Circuit-Breaker Failure Protection with External Pole-Selective Start, Pole-Selective Tripping
Repetition, and 3-Pole Tripping (T2)
EXAMPLE
EXAMPLE
NOTE
i Siemens would like to point out that, with a hold signal, the CBFP generates a trip signal each time a
starting pulse is received and the current flow is high enough. Remember this particularly in the case of an
external start!
If you are working with the Off repetition, tripping only occurs in this feeder in the event of a false pickup.
• Recommended setting value (_:102) Threshold phase current = approx. 0.50 Isc, min
In order to ensure that the disconnection of the fault is promptly detected and the function can drop out
quickly, Siemens recommends setting both thresholds to half the minimum short-circuit current (Isc, min).
If – depending on the neutral-point treatment and/or load conditions – ground faults lead to relatively low
fault currents, a sensitive setting of the parameter Threshold sensitive must be selected according to
the rule (0.5 Isc, min). There can also be values which are noticeably below the rated or load current.
NOTE
i The setting value Direct release can cause inadvertent tripping of the circuit-breaker failure protection
when 1-pole tripping of the circuit breaker is set.
If you set the parameter 3I0 criterion to Direct release, Siemens recommends that you also set the
parameter Op. mode BFP to I> query. In the event of a tripping of the circuit-breaker failure protection
caused solely by a ground current, reversing the poles of the bay current does not result in a reliable fault
clearing by busbar protection.
If you have set the Threshold phase current to be larger than the maximum load current, overfunction
because of a false start is impossible. To ensure Circuit-breaker failure protection for smaller ground faults
even with this setting, you can select 3I0 criterion to be Direct release and Threshold 3I0 dir.
release to be appropriately smaller than Threshold phase current.
Parameter: I2 criterion
If you set the parameter I2 criterion to Direct release, Siemens recommends that you also set the
parameter Op. mode BFP to I> query. In the event of a tripping of the circuit-breaker failure protection
caused only by a negative-sequence current, reversing the poles of the bay current does not result in a reliable
fault clearing by busbar protection.
If you have set the Threshold phase current to be larger than the maximum load current, overfunction
because of a false start is impossible. To have Circuit-breaker failure protection function for smaller unbal-
anced faults even with this setting, you can select I2 criterion to be Direct release and Threshold
3I0 dir. release to be appropriately smaller than Threshold phase current.
With these parameters, you set the monitoring time of the binary inputs >Start/>Release. If the Circuit-
breaker failure protection does not pick up during this monitoring time, a failure in the binary-input circuit is
assumed. Siemens recommends retaining the default setting of 15 s.
EXAMPLES
• Tripping of protection functions whose tripping decision is not based on a current measurement in
combination with voltage or frequency protection functions
Parameter: Dropout
Parameter: Retrip
• If the minimum fault-clearing time has top priority, Siemens recommends setting the time to 0. This
setting causes initiation of the retrip immediately upon the start. The drawback is that a defect of the 1st
trip circuit is not detected.
• With a small time delay of, for instance, 50 ms, the defect of the 1st trip circuit can be detected based on
the evaluation of the fault record.
• With a long time delay, which reliably ensures the dropout of the CBFP with the CB open, the rising edge
indication of the trip repeat Retrip T1 is a sure signal for a fault in the 1st trip circuit. The following
example shows how this time is determined.
EXAMPLE
Determining the T1 Time that Reliably Ensures the Dropout of the CBFP with the CB Open:
EXAMPLE
EXAMPLE
Determining the T2 Time that Reliably Ensures the Dropout of the CBFP with the CB Open:
If T1 and T2 are started in parallel, take into account the time T1 for the setting of T2.
EXAMPLE
Various times can be set for a 1-pole and 3-pole (multipole) start. In the presence of 1-phase short circuits –
that do not jeopardize network stability – it can make sense to allow more time to the local CB (such as twice
the clearance time: 2 x 130 ms = 260 ms), expecting that the CB will open yet. This way, tripping of the
surrounding CBs can be avoided.
! CAUTION
Too short setting times for the minimum tripping duration
If you set a time that is too short for tripping, there is a risk (dropout of the function without the
current-flow criterion) that the device contacts will interrupt the control loop. If this happens, the
device contacts will burn out.
² Set a minimum time period that is long enough to ensure that the circuit breaker reliably reaches the
end position Open after a control operation.
6.3.6 Settings
Table 6-1 Starting with V8.40, the Merging Units have the Following Enhancement that is Especially
Intended for Use with the Distributed Busbar Protection and Evaluated there:
The Circuit-breaker failure protection function (ANSI 50BF) monitors the tripping of the associated circuit-
breaker (CB) and generates a backup trip signal if the circuit-breaker fails.
The circuit-breaker failure protection in the busbar protection has the following tasks:
• Tripping of the circuit breaker in the bay in the event of errors on the line.
The description for this function is in the following chapters.
• Tripping of all circuit breakers of a busbar section in the event of unsuccessful tripping by the circuit-
breaker failure protection in the bay.
The description of the additional operating modes for this function are in chapter 6.3.4 Circuit-Breaker
Failure Protection in Busbar Protection.
• Monitoring of all circuit breakers in the event of errors within the protection range of the busbar protec-
tion (internal tripping of the busbar section). In the event of unsuccessful tripping of the circuit breaker, a
transfer-trip signal can be transmitted to the opposite end.
The description of this function can be found in chapter 6.5.1 Overview of Functions .
Starting with version V7.50, the previous function CB failure has been replaced with the new Circuit-breaker
failure protection with an adaptive algorithm Adaptive CB failure protection. In this way, you achieve a
faster, more reliable detection of the opening of the circuit breaker in the event of complex signal histories.
The 2 functions are identical, with the exception of a slightly increased processor load, in terms of setting
options, logic and indications. Siemens recommends using the adaptive circuit-breaker failure protection and
avoiding mixing the protection types in one device. You can find additional information on the processor load
in DIGSI for each device under Device information in the Resource consumption tab.
The function Circuit-breaker failure protection (CBFP) can be used in the Circuit-breaker function group.
[dw_strbfp, 1, en_US]
Figure 6-20 shows the functionalities and the function control of the function.
The start is initiated by an external protection. Along with the start, the current-flow criterion or the circuit-
breaker auxiliary contact criterion is used to check whether the circuit breaker is closed. If the circuit breaker is
closed, the function picks up and starts the time delay. During the time delay, the system continuously checks
whether the circuit breaker has opened. If this is the case, the function drops out. If the circuit breaker is not
opened, the function trips upon expiration of the time delay.
The following description elaborates on the detailed functionality of the individual function blocks.
[lo_svs_bfp, 3, en_US]
The circuit-breaker failure protection function is started by device-internal protection functions and/or exter-
nally (via a binary input or an interface, such as GOOSE). Figure 6-34 and Figure 6-35 show the functionality.
Internal Start
In the case of busbar protection, each device-internal protection, such as the differential protection that has to
control the local circuit breaker starts the integrated circuit-breaker failure protection (see 6.5.1 Overview of
Functions ). You can configure other protection functions, such as overcurrent protection for the internal start,
via the circuit-breaker interaction matrix. The function is started by the tripping of the protection stage. In the
default setting, the starting signal Internal start (see Figure 6-34) is held when the pickup signal has a
falling edge or the protection function has tripped. The circuit-breaker failure protection function can in this
case only drop out if the circuit breaker is detected to be open. This is detected using the current flow or
circuit-breaker auxiliary contact criterion. If necessary, the circuit-breaker failure protection function can also
drop out when the pickup signal has a falling edge or the protection function trips (internal starting signal is
not held).
You can use routing to determine whether individual protection stages or protection functions are used as a
starting source or whether the start is only supposed to be external.
The internal starting sources are routed in the protection function groups via the Circuit-breaker interaction
entry (for this, see 2.1 Function Embedding in the Device ).
[lo_anwint, 2, en_US]
External Start
The parameter Start via binary input is used to set whether the external start is initiated by a 1-
channel or 2-channel signal. The required routing of the input signals is compared with the setting. If a
routing is missing, an error message is generated. The Health signal changes to the state Warning.
[lo_anwext, 1, en_US]
Figure 6-35 Configuration of the External Start of the Circuit-Breaker Failure Protection Function
In 1-channel operation, the start is initiated with the binary input signal >Start only.
In 2-channel operation, the binary input signal >Release must also be activated to initiate the start. In the
default setting, the starting signal External start drops out immediately when the input signals have a
falling edge (see Figure 6-36). If necessary, the starting signal can be held. In this case, the start remains
active when the binary input signals have a falling edge.
The input signals are monitored to avoid an unwanted pickup of the function.
If either of the signals >Start or >Release is active for more than the set supervision time of the corre-
sponding signal without the function being picked up, an error in the binary input circuit is assumed. The
corresponding signal is blocked to exclude an external pickup of the function. An indication to this effect is
output, and the Health signal changes to the state Warning. The blocking is reset as soon as the binary input
signal drops out.
• On pickup of the circuit-breaker failure protection function (only in the case of an external start). This
prevents an unwanted pickup of the supervision if the external protection that starts the circuit-breaker
failure protection function uses a lockout functionality. When the starting signal drops out, supervision is
enabled again.
• As long as the function or the device is in test mode. This allows to check the function without the super-
vision blocking the function.
If the >Start signal is active and no release signal is present after elapse of the settable supervision time for
the starting signal, the pickup is blocked and an indication to this effect is output. The Health signal changes
to the state Warning. The blocking is reset with the dropout of the starting signal.
The binary input signals only take effect if the binary inputs are activated for at least 10 ms (SW filter, see
Figure 6-36).
[lo_ext, 3, en_US]
Figure 6-36 External Start of the Circuit-Breaker Failure Protection Function, Logic
Current-Flow Criterion
The current-flow criterion is the primary criterion for determining the circuit-breaker switch position. A circuit-
breaker pole is supposed to be closed, and the current-flow criterion fulfilled, as soon as one of the phase
currents exceeds the phase-current threshold value, and at the same time a plausibility current exceeds the
associated threshold value. The plausibility current can be either a 2nd phase current (to compare with the
threshold value for phase currents) or the zero-sequence or negative-sequence current (to compare with the
sensitive threshold value). The additional evaluation of the plausibility current increases the safety of the crite-
rion.
In the case of ground faults, the sensitive threshold value can be dynamically applied to the phase currents as
well. The current-flow criterion is fulfilled when the currents exceed the sensitive threshold value. The phase-
current threshold value is then ineffective. The binary signal >Threshold sensitive is used for the switch-
over.
If you set the parameter 3I0 criterion to Direct release, you block the plausibility check of the zero-
sequence current. In this way, a pickup can only be achieved by way of this current. The Threshold 3I0
dir. release parameter is used to set the threshold value to be exceeded.
If you set the parameter I2 criterion to Direct release, you also switch off the plausibility check of
the negative-sequence current. The Threshold I2 dir. release parameter is used to set the threshold
value to be exceeded.
If you set the parameter I2 criterion to Direct release, a plausibility check is performed via the phase
currents with 1/3 * Threshold I2 dir. release.
The measuring algorithm is optimized for fast dropout when the value drops below the threshold value.
[lo_current1, 4, en_US]
[lo_criter, 1, en_US]
Pickup/Dropout
After the start, a check is performed whether the circuit breaker is closed. The current-flow criterion and the
circuit-breaker auxiliary contact criterion are available for this purpose.
Even if the circuit-breaker auxiliary contact criterion is permitted, preference is given to the fulfilled current-
flow criterion because the current-flow criterion is the most reliable criterion for detecting whether the circuit
breaker is closed. This means that the circuit breaker is deemed to be closed if it is closed according to the
current-flow criterion but at the same time open according to the circuit-breaker auxiliary contact criterion.
If no current is flowing at the start time, the function can only pick up on the basis of the circuit-breaker auxil-
iary contact criterion. For this purpose, the circuit-breaker auxiliary contacts must be permitted as criterion.
When the current begins to flow after the start, the function switches over to the current-flow criterion.
If the circuit breaker is detected as closed and the starting condition is present, the function picks up.
The pickup starts a time delay (see Delay/Tripping). While the delay is running, the system checks continuously
whether the circuit breaker has opened. In the default setting, the opening of the circuit breaker is checked on
the basis of the currently valid criterion, which is normally the current-flow criterion because it is preferred. If
until expiration of the time delay, no current flow above the set threshold values has been detected, the
circuit-breaker auxiliary contact criterion becomes effective.
The function has also a setting in which dropout is only possible if both criteria in parallel detect the circuit
breaker to be open (dropout with auxiliary contact and current-flow criterion).
In the default setting, the internal starting signal is held (see Figure 6-34 and Figure 6-36). This means that
dropout is controlled solely by the current or the circuit-breaker auxiliary contact criterion. If dropout is also to
occur on the falling edge of the starting signal (that is, when the pickup signal has a falling edge or the protec-
tion function trips), holding of the start signal must be disabled.
[lo_pickup1, 4, en_US]
Delay/Tripping
In a first step, tripping at the local circuit breaker can be repeated. Tripping is repeated after expiration of the
settable delay T1. If the local CB was not yet tripped, for example, in the event of an external start of the
circuit-breaker failure protection, the trip logic of the circuit breaker itself is activated when the time delay T1
elapses.
Time delay T2 (backup tripping) can commence in parallel either with the start of time T1 or after expiration of
time T1.
If time delay T2 expires without a dropout of the function, a circuit-breaker failure is assumed and the backup
tripping signal Tripping T2 is output. The Trip T2 activates the integrated circuit-breaker failure protec-
tion. If needed a transfer-trip signal is sent to the opposite end. Thus, the circuit breaker on the opposite end
can be tripped without delay.
If the >CB defect input signal is valid, any repetition of the trip signal is suppressed, and the backup tripping
signal T2 is generated immediately (without delay). The binary input of the >CB defect input signal must be
activated for at least 20 ms before the signal becomes valid.
With help of the CB failure pole indication, you can determine the phase currents that are above the
threshold value at the tripping time T2.
The Minimum operate time parameter defines the minimum duration for tripping the function. In contrast
to other protection functions, the parameter is set within its own function. As a result, the setting is inde-
pendent of the identically named global parameter that is set in the Device settings.
[lo_bbp-verza-3ph, 6, en_US]
With the Immediate dropout parameter, you determine whether the circuit-breaker switch position is
checked continuously or on expiration of the T1 and T2 time delays. If the circuit-breaker switch position is
checked once the time delays have expired, the function picks up using Start.
The circuit-breaker failure protection in busbar protection specifies a circuit-breaker failure with a short circuit
in the feeder or with a short circuit in the busbar.
If a short circuit occurs in the feeder, a circuit-breaker failure leads to selective disconnection of the busbar
section on which the feeder with the defective circuit breaker is connected. In addition, an intertripping
command is output in order to also switch off the opposite line end.
If a short circuit in the busbar and a circuit-breaker failure occur, at the opposite end of the line the infeed of
the current must be interrupted. For this purpose, the Trip T2 is output.
If the circuit-breaker failure protection works together with the busbar protection, with pick up of Trip T2,
the busbar protection is activated. If the circuit breaker has not opened, the busbar protection trips the
assigned busbar section.
There are 2 operating modes available for tripping the busbar:
• Unbalancing
• I> Query
NOTE
i If an active end-fault protection has already set the feeder current to 0, no unbalancing will be performed.
The operating mode is set in the Circuit breaker function group under General separately for each bay. In this
way, the function can be optimally adapted to the operating conditions, for example to the type of feeder or
the short-circuit currents.
NOTE
i You must differentiate between the centralized busbar protection, the distributed busbar protection (IEC
61850 compliant), and the distributed busbar protection.
• Centralized: The start occurs in parallel with the Trip T2 for the busbar function group.
• Decentralized (IEC 61850-compliant): Route the Trip T2 from the merging unit to the external trip-
ping in the bay using GOOSE.
• Distributed: If you have set the CBFP interact. with dBBP parameter to Yes for the circuit-
breaker failure protection in the merging units, the starting signal is transferred.
[dw_ls_ssys, 3, en_US]
The corresponding application and setting notes are in chapter 5.3.3 Application and Setting Notes
• No danger of undesirable tripping even with longer dropout times since the current flow from the circuit
breaker is already interrupted and thus no differential current occurs due to the unbalancing.
• Use of the same algorithms and the same trip logic as the busbar differential protection.
[dw_char_svs, 2, en_US]
Figure 6-43 gives an overview of the functions involved in an external start of the CBFP function. In the case of
an internal start, there is no external protection device and the protection functionality is located in the CBFP
device.
[lo_aus_3bf, 2, en_US]
Figure 6-43 Circuit-Breaker Failure Protection with External Start, Tripping Repetition, and 3‑Pole Tripping
(T2)
EXAMPLE
EXAMPLE
NOTE
i Siemens would like to point out that, with a hold signal, the CBFP generates a trip signal each time a
starting pulse is received and the current flow is high enough. Remember this particularly in the case of an
external start.
If you are working with the Off repetition, tripping only occurs in this feeder in the event of a false pickup.
• Recommended setting value (_:102) Threshold phase current = approx. 0.50 Isc, min
In order to ensure that the disconnection of the fault is promptly detected and the function can drop out
quickly, Siemens recommends setting both thresholds to half the minimum short-circuit current (Isc, min).
If – depending on the neutral-point treatment and/or load conditions – ground faults lead to relatively low
fault currents, a sensitive setting of the parameter Threshold sensitive must be selected according to
the rule (0.5 Isc, min). There can also be values which are noticeably below the rated or load current.
If you set the parameter 3I0 criterion to Direct release, Siemens recommends that you also set the
parameter Op. mode BFP to I> query. In the event of a tripping of the circuit-breaker failure protection
caused solely by a ground current, reversing the poles of the bay current does not result in a reliable fault
clearing by busbar protection.
If you have set the Threshold phase current to be larger than the maximum load current, overfunction
because of a false start is impossible. To ensure Circuit-breaker failure protection for smaller ground faults
even with this setting, you can select 3I0 criterion to be Direct release and Threshold 3I0 dir.
release to be appropriately smaller than Threshold phase current.
Parameter: I2 criterion
If you set the parameter I2 criterion to Direct release, Siemens recommends that you also set the
parameter Op. mode BFP to I> query. In the event of a tripping of the circuit-breaker failure protection
caused only by a negative-sequence current, reversing the poles of the bay current does not result in a reliable
fault clearing by busbar protection.
If you have set the Threshold phase current to be larger than the maximum load current, overfunction
because of a false start is impossible. To have Circuit-breaker failure protection function for smaller unbal-
anced faults even with this setting, you can select I2 criterion to be Direct release and Threshold
3I0 dir. release to be appropriately smaller than Threshold phase current.
EXAMPLES
• Tripping of protection functions whose tripping decision is not based on a current measurement in
combination with voltage or frequency protection functions
Parameter: Dropout
Parameter: Retrip
• If the minimum fault-clearing time has top priority, Siemens recommends setting the time to 0. This
setting causes initiation of the retrip immediately upon the start. The drawback is that a defect of the 1st
trip circuit is not detected.
• With a small time delay of, for instance, 50 ms, the defect of the 1st trip circuit can be detected based on
the evaluation of the fault record.
• With a long time delay, which reliably ensures the dropout of the CBFP with the CB open, the rising edge
indication of the trip repeat Retrip T1 is a sure signal for a fault in the 1st trip circuit. The following
example shows how this time is determined.
EXAMPLE
Determining the T1 Time that Reliably Ensures the Dropout of the CBFP with the CB Open:
EXAMPLE
Determining the T2 Time that Reliably Ensures the Dropout of the CBFP with the CB Open:
If T1 and T2 are started in parallel, take into account the time T1 for the setting of T2.
EXAMPLE
! CAUTION
Too short setting times for the minimum tripping duration
If you set a time that is too short for tripping, there is a risk (dropout of the function without the
current-flow criterion) that the device contacts will interrupt the control loop. If this happens, the
device contacts will burn out.
² Set a minimum time period that is long enough to ensure that the circuit breaker reliably reaches the
end position Open after a control operation.
• The mode (unbalancing / I> query), as well as the phase-current threshold values and ground-current
threshold values, must each be identical in the 2 circuit-breaker functions.
• External signals, for example, start, release for external start, switchover to sensitive characteristic curve,
must be routed to both circuit-breaker functions. In this case, the inputs of both circuit-breaker failure
protection functions can each be connected with an equivalent input signal in the information routing.
6.4.6 Settings
Table 6-2 Starting with V8.40, the Merging Units Have the Following Enhancement that is Especially
Intended for Use with the Distributed Busbar Protection and Evaluated there:
The Inherent circuit-breaker failure protection acts in the event of faults within the protection range of the
busbar protection system.
If external errors occur, you need the circuit-breaker failure protection for supervision purposes and for the
busbar protection reserve disconnection of all circuit-breakers that are assigned to the busbars.
The function Inherent circuit-breaker failure protection is preconfigured in the Circuit breaker function
group and does not need to be connected manually.
[dw_strinh, 1, en_US]
The function Inherent circuit-breaker failure protection monitors the opening of circuit breakers of a faulty
busbar section with the following functions:
[lo_int_svs, 2, en_US]
Figure 6-45 Overview of the Logic of the Inherent Circuit-Breaker Failure Protection Function
The function Inherent circuit-breaker failure protection is started by the trip command of the previously
mentioned protection functions. Upon starting, the current-flow criterion is used to determine whether the
circuit breaker is closed.
If the current-flow criterion determines that the circuit breaker is closed, the function is initiated and the time
delay T2 is started. While the time delay is running, the current-flow criterion is used to check whether the
circuit breaker has opened. If this is the case, the function drops out. If the circuit breaker has not opened, the
function trips upon expiration of time delay T2. The tripping is always 3-pole. The operate indication can be
used to open the circuit breaker at the opposite end since the error cannot be resolved locally (transfer-trip
signal).
If a coupling circuit breaker opens in response to an error on the busbar, the 2 busbars are disconnected. If the
coupling circuit breaker does not open, the faulty busbar continues to conduct current. In order to finally
resolve the error, the busbar must be switched off. In this case, the Inherent circuit-breaker failure protec-
tion disconnects the busbar. If the feeder bay is a bus coupler, the Inherent circuit-breaker failure protec-
tion always operates with unbalancing to disconnect the feeding busbar.
The Inherent circuit-breaker failure protection function can be blocked separately for each bay by the input
signal >Block function.
The function is also blocked if the bay to which the Circuit-breaker function group is assigned is not in opera-
tion.
Start
The busbar protection starts the Inherent circuit-breaker failure protection function in response to the trip
command sent to the circuit breaker. Starting is maintained by pickup of the function and the function does
not drop out until the value of the current falls below the current threshold for inherent circuit-breaker failure
protection.
[lo_staint, 1, en_US]
Current-Flow Criterion
The current-flow criterion is the primary criterion for determining the circuit-breaker switch position. A circuit-
breaker pole is supposed to be closed and the current-flow criterion fulfilled, as soon as one of the phase
currents exceeds the phase-current threshold value and a plausibility current exceeds the associated threshold
value at the same time. The plausibility current can be either a 2nd phase current (to compare with the phase-
current threshold value) or the zero-sequence or negative-sequence current (to compare with the sensitive
threshold value). The additional evaluation of the plausibility current increases the safety of the criterion.
In the case of ground faults, the sensitive threshold value can be dynamically applied to the phase currents as
well. The current-flow criterion is fulfilled when the currents exceed the sensitive threshold value. The phase-
current threshold value is then ineffective. The binary signal >Threshold sensitive is used for the switch-
over.
If you set the 3I0 criterion parameter to Direct release, you prevent the plausibility check of the
zero-sequence current. In this way, a pickup only by way of this current can be achieved. With the Threshold
3I0 dir. release parameter, you set the threshold value to be exceeded.
If you set the I2 criterion parameter to Direct release, you also switch off the plausibility check of
the negative-sequence current. With the Threshold I2 dir. release parameter, you set the threshold
value to be exceeded.
If you set the I2 criterion parameter to Direct release, plausibility is checked via the phase currents
with 1/3 * Threshold I2 dir. release.
The measuring algorithm is optimized for fast dropout when the value drops below the threshold value.
[lo_current1, 4, en_US]
Pickup/Dropout
After the start, a check is performed whether the circuit breaker is closed. Only the reliable current-flow crite-
rion in the inherent circuit-breaker failure protection is available in this case. If the current exceeds the pickup
threshold (parameter Threshold phase current or Threshold sensitive) the function picks up. The
time delay T2 starts on pickup and whether the circuit breaker has opened (see also Figure 6-37 or
Figure 6-25) is continuously checked via the current-flow criterion.
[lo_anrres, 1, en_US]
Delay/Tripping
If time delay T2 expires without dropout of the function, a circuit-breaker failure is assumed, and the Trip T2
is generated. The tripping is always 3-pole.
The operate indication can also be routed to a binary output. A transfer trip signal can be sent to the opposite
end if necessary.
If the coupling circuit breaker does not open, after elapse of T2 the coupler current becomes unbalanced.
Through this, the busbar that is connected through the coupler is tripped and the error is finally cleared.
If the >CB defect input signal is valid, the T2 tripping is generated without a delay. For the >CB defect
input signal to be considered valid, the corresponding binary input must be active for at least 20 ms.
With the CB failure pole indication, you can specify the phase currents that exceed the set threshold
value at the time of the tripping T2.
[lo_bbp-verzaus-int, 5, en_US]
Parameter: Mode
This setting has to ensure that after opening of the local CB the function drops out reliably and that backup
tripping is avoided under all circumstances.
Follow the setting instructions for 1-pole/3-pole and 3-pole circuit-breaker failure protection.
! CAUTION
Too short setting times for the minimum tripping duration
If you set a time that is too short for tripping, there is a risk (dropout of the function without the
current-flow criterion) that the device contacts will interrupt the control loop. If this happens, the
device contacts will burn out.
² Set a minimum time period that is long enough to ensure that the circuit breaker reliably reaches the
end position Open after a control operation.
If you set the parameter 3I0 criterion to Direct release, Siemens recommends that you also set the
parameter Op. mode BFP to I> query. In the event of a tripping of the circuit-breaker failure protection
caused solely by a ground current, reversing the poles of the bay current does not result in a reliable fault
clearing by busbar protection.
Parameter: I2 criterion
If you set the parameter I2 criterion to Direct release, Siemens recommends that you also set the
parameter Op. mode BFP to I> query. In the event of a tripping of the circuit-breaker failure protection
caused only by a negative-sequence current, reversing the poles of the bay current does not result in a reliable
fault clearing by busbar protection.
• The mode (unbalancing / I> query), as well as the phase-current threshold values and ground-current
threshold values, must each be identical in the 2 circuit-breaker functions.
• External signals, for example, switchover to a sensitive characteristic curve, must be routed to both
circuit-breaker functions. In this case, the inputs of both inherent circuit-breaker failure protection func-
tions can each be connected with an equivalent input signal in the information routing.
6.5.5 Settings
The end-fault protection protects the section between the current transformer and the open circuit breaker.
The switch position of the circuit breaker must be available for the effectiveness of the function.
The protection range is determined by the installation location of the current transformer.
[dw_efpss_2, 2, en_US]
[dw_efpss_1, 2, en_US]
In the normal case, the current transformer forms the limit of the protection range. The section between the
current transformer and circuit breaker is called the dead zone. By using the end-fault protection in the bus
coupler, improved behavior of the protection is achieved with an open circuit breaker. The protection range is
extended by the dead zone between the current transformer and circuit breaker.
[dw_dzpss_4, 2, en_US]
Figure 6-52 Fault in the Dead Zone of the Bus Coupler, Example 1 Current Transformer in the Bus Coupler
[dw_dzpss_3, 2, en_US]
Figure 6-53 Fault in the Dead Zone of the Bus Coupler, Example 2 Current Transformer in the Bus Coupler
End-fault protection is active only with the circuit breaker open. With the circuit breaker closed, the protection
behaves just like when there is no end-fault protection.
NOTE
i If you configure end-fault protection, you must route the open position of the circuit breaker. Otherwise,
the complete protection switches to the alarm state.
The End-fault protection function can be used in the Circuit breaker function group.
[dw_strefp, 2, en_US]
Only one End-fault protection function block is assigned to the Circuit breaker function group.
Activating/Blocking
End-fault protection is active only with the circuit breaker open. The circuit-breaker switch position is detected
by way of the circuit-breaker auxiliary contacts. The current-flow criterion is not used for evaluating the circuit-
breaker switch position.
Using an adjustable time delay Delay CB open, you can prevent the end-fault protection from being acti-
vated before the circuit breaker is actually open. This time delay is necessary because of the signal of the
circuit-breaker auxiliary contacts can precede the actual position of the circuit breaker.
End-fault protection is blocked during the following events and operating states:
• With the circuit breaker closed – in the case of a feeder with a truck-type switchgear, it is sufficient if one
of the circuit breakers is closed.
• After issuing the close command for the circuit breaker for a fixed 200 ms
• For backup breaker operation with external current transformers (line side)
For external current transformers and closed transfer disconnector, the circuit-breaker switch position
has no relation to the measured current.
Logic
The active end-fault protection sets the current of the assigned current transformer for the busbar differential
protection to 0. Through this, the busbar differential protection can detect a fault for current transformers
arranged on the busbar side or for a busbar coupler with 1 or 2 current transformers. The calculated current
results in disconnection of the faulty busbar by the busbar differential protection.
In the case of current transformers arranged on the line side, the fault must be disconnected by the circuit
breaker at the opposite end. To explain such a fault, the end-fault protection monitors an adjustable threshold
value. If the operate indication is transferred to a protection device at the opposite end, the fault clearing can
be done there. The busbar remains connected because the end-fault protection has set the flowing current to
0.
The end-fault protection checks whether the measured current has exceeded an adjustable threshold
Threshold 1. If the threshold value is exceeded in at least one phase, the phase-specific indication Pickup
is issued. After the adjustable time delay Operate delay elapses, Operate delay expired and
Operate are indicated. The operate indication is maintained for an adjustable time (parameter Minimum
operate time).
For low-current faults, the threshold value of the phase current can be changed by the input signal >Thresh
change to a more responsive parameterized Threshold 2.
The following figure shows the logic diagram of the end-fault protection.
The feedback of the switch position must be ensured for all eventualities of a CLOSE control command. The
close command can be issued by manual closing using the control discrepancy switch, remote control of the
circuit breaker using remote or substation automation technology, or automatic reclosing.
Parameter: Threshold 1
Parameter: Threshold 2
NOTE
i When setting the parameter Delay CB open, consider that due to the cycle filter used, current will still be
measured for one period after disconnection by the circuit breaker. Add the period duration plus a safety
margin of 10 ms to the expected circuit breaker trip time.
6.6.7 Parameter
The External tripping of a busbar section (direct) makes it possible to link an external signal for tripping all
bays of one busbar section. The busbar protection evaluates the disconnector image to determine which bays
are connected to the affected busbar section. The external trip signal can be sent from a binary input or via
protection communication. A typical application is tripping of a busbar section by an external arc protection.
The External tripping of a busbar section (direct) can be used in the Busbar protection function of the
Busbar function group.
[dw_strexb, 1, en_US]
Figure 6-56 Embedding the External Tripping of a Busbar Section (direct) Function
Tripping for the circuit breakers of all bays of a busbar section can be started by the external trip command
>Ext. trip. To increase the response reliability of the busbar protection, the busbar protection also
processes the release signal >Rel. ext. trip for the trip decision.
The external trip command is provided for each busbar section. The release signal is available once for the
function
The input signals for the trip command and the release signal are monitored. Time supervision is adjustable.
Time-outs are indicated. The supervision conditions are described in more detail in the following in the Time
Supervision section.
The External tripping of a busbar section (direct) trips the busbar section when the following conditions are
satisfied:
[lo_dir_ein, 7, en_US]
Figure 6-57 Logic Diagram of the External Tripping of a Busbar Section (Direct)
Time Supervision
Time supervision of the inputs is always active and cannot be switched off. The external trip command and the
release signal are monitored.
Supervision picks up under the following conditions:
• If the trip command for a busbar section is active longer than the adjustable supervision time before the
release command is received, the No Ext. trip release indication is output.
The indication is provided for each busbar section.
The supervision time is set using the parameter Superv.t. Rel. ext. trip BZ.
This supervision detects faults in the control circuit of the release signal that cause signal outage.
[dw_fre_ino, 1, en_US]
Figure 6-58 Signal Form for Supervision (_:11881:315) No Ext. trip release
• If the release signal is present for longer than 15 s without a trip command for the busbar section
arriving, the indication BI rel. ext.trip dist. is output.
The indication is provided once for the function.
This type of supervision detects faults in the control circuit of the release signal that cause persistent acti-
vation of the signal.
[dw_bi_free, 1, en_US]
Figure 6-59 Signal Form for Supervision (_:11971:302) BI rel. ext.trip dist.
• If the trip command is present for longer than 15 s without a release signal arriving, the indication BI
External trip dist. is output for the busbar section.
The indication is provided for each busbar section.
This type of supervision detects faults in the control circuit of the external trip command that cause
persistent activation of the input signal.
[dw_bi_star, 1, en_US]
Figure 6-60 Signal Form for Supervision (_:11881:314) BI External trip dist.
If supervision picks up, all external tripping actions are blocked for all busbar sections.
The supervision drops out once all inputs of the function are inactive.
If an external trip signal results in tripping of the busbar section, all supervision actions of the inputs become
inactive. Even if the tripping is generated for longer than the permanently set supervision time, supervision no
longer picks up.
6.7.5 Settings
The External tripping of a busbar section (from bay) function makes it possible to connect a command to
externally trip a busbar section, for example, from an external CBFP device. The function incorporates this
external command into the busbar protection. The busbar protection evaluates the disconnector image to
determine which bays are connected to the affected busbar section. The external trip signal can be sent from a
binary input or via protection communication. A typical application is an external circuit-breaker failure protec-
tion device and tripping of the busbar by the busbar protection.
The External tripping busbar section (from bay) function block can be used in the Circuit-breaker function
group.
[dw_strexf, 1, en_US]
Figure 6-61 Embedding the External Tripping Busbar Section (from Bay) Function
The function picks up on a phase-selective basis if the input signals for the start and release signal were acti-
vated within a supervision time that can be set. The Busbar protection function trips without delay.
The function External tripping busbar section (from bay) continually monitors the input signal >Release
and the phase-specific input signals >Start pole A, >Start pole B and >Start pole C.
If you have only one input signal available for starting, route it to all 3 phase-specific input signals.
The function picks up on a phase-selective basis if the following conditions are fulfilled:
If the release signal is not received within the set supervision time Sup.time f. release signal after
activation of the starting signal, for example >Start pole A, the failure indication Fail. no BI
release is issued.
If, 15 s after activation of one of the input signals, the other input signal remains inactive, the indication
Fault BI Start or Fault BI Release is issued. In addition, the duration of the starting signals is moni-
tored to ensure that it does not exceed 15 s.
If one of the monitored input signals becomes inactive, tripping drops out.
Logic
[lo_ext_ein, 5, en_US]
Figure 6-62 Logic Diagram of the External Trip of a Busbar Section from the Bay
With the Sup.time f. release signal parameter, you set the supervision time which may lie at most
between the phase-specific starting signal, for example, >Start pole A, and the arrival of the release signal
>Release.
6.8.5 Settings
If you set the assignment to the zones as non-overlapping in a coupler bay with 2 current transformers,
the bus coupler differential protection is used to protect the section between the 2 current transformers (dead
zone). With this current transformer assignment, a fault between the 2 current transformers merely results in
the tripping of the circuit breaker in the bus coupler. The end-fault protection provides for a selective tripping
of the busbar involved in a 2nd step.
[dw_coup_deadzone, 2, en_US]
Figure 6-63 Fault in the Dead Zone of the Bus Coupler with 2 Current Transformers
Depending on the amount of the differential current measured in the bus coupler, the assignment of current
can temporarily be switched from non-overlapping to overlapping. As a result, a fault in the dead zone is
very quickly cleared by the busbar differential protection. Connected with this is the disadvantage of a non-
selective tripping of the 2 busbars that are connected at the bus coupler.
If you use a coupler bay with 2 current transformers, you can configure the bus coupler differential protection
as a part of the bay proxy. You can find the Coupler zone function in the bay under the function extensions.
The bus coupler differential protection uses the currents measured by the two current transformers that are
present in the bay. The trip command of the bus coupler differential protection acts on the circuit breaker that
is present in the bay.
To be able also to selectively trip the busbar section generating the fault, you must configure an end-fault
protection for the circuit breaker in the bus coupler.
[lo_coup_diffprot, 3, en_US]
Tripping of the Bus Section Generating the Fault in the Dead Zone
After the bus coupler differential protection has opened the circuit breaker in the bus coupler, the fault current
is still fed into the bus coupler, but only from one side. When the circuit breaker in the bus coupler opens, the
end-fault protection configured for the circuit breaker picks up. The end-fault protection sets the currents
measured by both bus coupler current transformers to 0 for the connected busbar section. The differential
current resulting for the busbar section then results in the selective tripping of the corresponding busbar
section.
If, when the coupler circuit breaker opens, end-fault protection is inactive (for example it is temporarily
blocked due to a close command) and the busbar sections feeding the error are not therefore disconnected,
the currents measured by the bus coupler current transformers get unbalanced once time stage T2 of the
inherent CBFP has expired. This unbalancing of currents will occur regardless of whether or not the inherent
CBFP is started. The type of unbalancing varies: When the inherent CBFP is started, the current polarities will
be negated, whereas if the inherent CBFP is not started, the currents will be set to 0 (after time T2 + 10 ms has
expired). This ensures safe fault clearing even when end-fault protection is inactive.
• Differential-current supervision
The method of operation corresponds to the differential-current supervision for the busbar sections. The
same setting parameters apply as for differential-current supervision of the bus zones.
• Zero-crossing supervision
The method of operation is identical to the zero-crossing supervision for the bus zones.
Temporary Switchover of the Current Assignment in the Bus Coupler from Non-Overlapping to Overlapping
In order to achieve a very fast, but not busbar-selective fault clarification by the busbar differential protection
with high currents in the dead zone, there is the option of temporarily switching the current assignment from
non-overlapping to overlapping. To do this, the differential current of the 2 bus coupler current transformers is
compared to the 2 threshold values set as parameters Thres.1-ph.f.CT overl and Thresh.mul-
ph.f.CT overl.. As soon as the differential current exceeds the threshold Thres.1-ph.f.CT overl in
only 1 phase or as soon as the differential current exceeds the threshold Thresh.mul-ph.f.CT overl. in
2 or 3 phases, the assignment of current immediately switches over to overlapping. This protects the
section between the 2 current transformers within the measuring range of the 2 connected busbar sections.
The switchover of the current assignment is available for the respective busbar sections as an indication Sw.
over to CT overl.. If this switchover of the current assignment is not desired, the option exists to set the
threshold-value parameters used for the switchover to infinity (∞), thereby making it ineffective.
If the threshold-value parameter is set lower than the minimum differential current threshold, this results in
the corresponding fault type always being clarified quickly and on an unselective basis in overlapping mode.
The following figure shows an application in which the multiphase short circuits more critical for power
quality are always clarified in overlapping mode, but the non-critical 1-pole faults are not clarified until there
is a very high differential current.
[dw_coup_kl, 1, en_US]
Parameter: Mode
With the parameter Mode, you can switch the bus coupler differential protection function on or off. The
setting on causes the bus coupler differential protection to be switched on. The setting off causes the bus
coupler differential protection to be switched off, that is, there is no protection in the dead zone.
If you do not use the bus coupler differential protection, remove it again and set the parameter Overlapping
CT = yes so that the dead zone is protected again.
[dw_coup_deadzone_err, 2, en_US]
[dw_coup_diffprot_time, 2, en_US]
Figure 6-67 Currents with Fault in the Bus Coupler Bay without Switchover to Current Transformer Over-
lapping
(1) The end-fault protection sets the bus coupler bay current to 0. This causes a differential current in
busbar section 1.
6.9.5 Settings
• Can be used as backup or emergency overcurrent protection in addition to the main protection
The Overcurrent protection, phases function is used in the Current-transformer function group. 2 kinds of
functions are available for the 3-phase overcurrent protection:
[dw_ocp_bp_1, 3, en_US]
6.10.3.1 Description
[lo_bbp-ocp_3b1, 3, en_US]
Figure 6-69 Logic Diagram of the Definite-Time Overcurrent Protection (Phases) – Basic
• Via the binary input signal >Block stage from an external or internal source
• Default setting (_:661:6) Operate delay = 0.30 s (for the 1st stage)
Set the Threshold and Operate delay parameters for the specific application.
The following details apply to a 2-stage characteristic curve (1st stage = definite-time overcurrent protection
stage and 2nd stage = high-current stage).
1st stage (overcurrent stage):
The setting depends on the maximum occurring operating current. Pickup by overload must be excluded since
overcurrent protection operates with short tripping times as short-circuit protection and not as overload
protection. Therefore, set the Threshold parameter for lines to approx. 10 %, for transformers and motors to
approx. 20 % above the maximum load that is expected.
EXAMPLE
Overcurrent-protection stage: 110-kV overhead line, 150 mm2 cross-section
Maximum transmittable power
Pmax = 120 MVA
Correspondingly
Imax = 630 A
Current transformer = 600 A/5 A
Safety factor = 1.1
[fo_ocp_ph1, 2, en_US]
The Operate delay to be set is derived from the time-grading schedule that has been prepared for the
system. Where overcurrent protection is used in emergency mode, shorter time delays might be reasonable
(one grading time above fast tripping), since the emergency mode only operates if the main protection func-
tion fails.
EXAMPLE
High-current stage: 110-kV overhead line, 150 mm2 cross-section
s (length) = 60 km
ZL/s = 0.46 Ω/km
Ratio of zero-sequence impedance and positive-sequence impedance of the line: ZL0/ZL1 = 4
Short-circuit power at the beginning of the line:
Ssc' = 2.5 GVA
Ratio of zero-sequence impedance and positive-sequence impedance of the source impedance at the begin-
ning of the line: ZP0/ZP1 = 2
Current transformer = 600 A/5 A
Resulting in the following values for the line impedance ZL and the source impedance ZP:
[fo_ocp_002, 1, en_US]
[fo_ocp_003, 1, en_US]
The 3-phase short-circuit current at the end of the line is Isc end:
[fo_ocp_ph4, 1, en_US]
The settings in primary and secondary values result in the following setting values which include a safety
margin of 10 %:
[fo_ocp_004, 2, en_US]
If short-circuit currents exceed 2365 A (primary) or 19.7 A (secondary), there is a short circuit on the line to be
protected. The overcurrent protection can cut off this short circuit immediately.
Note: The amounts in the calculation example are accurate enough for overhead lines. If the source impe-
dance and line impedance have different angles, you have to use complex numbers to calculate the
Threshold .
6.10.3.3 Settings
6.10.4.1 Description
[lo_bbp-ocp_3b2, 3, en_US]
Pickup and Dropout Behaviors of the Inverse-Time Characteristic Curve according to IEC and ANSI (Basic and
Advanced Stage)
When the input variable exceeds the threshold value by a factor of 1.1, the inverse-time characteristic curve is
processed. An integrating method of measurement summarizes the weighted time. The weighted time results
from the characteristic curve. For this, the time that is associated with the present current value is determined
from the characteristic curve. Once the weighted time exceeds the value 1, the stage operates.
When the measured value falls below the pickup value by a factor of 1.045 (0.95 ⋅ 1.1 ⋅ threshold value), the
dropout is started. The pickup will be indicated as clearing. You can influence the dropout behavior via setting
parameters. You can select between instantaneous dropout (totalized time is deleted) or dropout according to
the characteristic curve (reduction of totalized time depending on the characteristic curve). The dropout
according to characteristic curve (disk emulation) is the same as turning back a rotor disk. The weighted
reduction of the time is initiated from 0.9 of the set threshold value.
The characteristic curve and associated formulas are shown in the Technical Data.
• Via the binary input signal >Block stage from an external or internal source
Parameter: Threshold
The setting depends on the maximum occurring operating current. Pickup by overload must be excluded since
overcurrent protection operates with short tripping times as short-circuit protection and not as overload
protection. Set the Threshold parameter for lines to approx. 10 %, for transformers and motors to approx.
20 % above the maximum expected load.
Note that a safety margin is set between pickup value and threshold value. The stage only picks up at approx.
10 % above the Threshold.
EXAMPLE
Overcurrent-protection stage: 110-kV overhead line, 150 mm2 cross-section
Maximum transmittable power
Pmax = 120 MVA
Correspondingly
Imax = 630 A
Current transformer = 600 A/5 A
[fo_ocp_005, 2, en_US]
Parameter: Reset
6.10.4.3 Settings
• Can be used as backup or emergency overcurrent protection in addition to the main protection
The Overcurrent protection, ground function is used in the Current-transformer function group. 2 kinds of
functions are available for the 3-phase overcurrent protection:
[dw_ocp_gb1, 4, en_US]
6.11.3.1 Description
[lo_bbp-ocp_gb1, 2, en_US]
• Via the binary input signal >Block stage from an external or internal source
• Default setting (_:751:6) Operate delay = 0.300 s (for the first stage)
Set the Threshold and Operate delay parameters for the specific application.
The following details apply to a 2-stage characteristic curve (1st stage = definite-time overcurrent protection
stage and 2nd stage = high-current stage).
EXAMPLE
High-current stage: 110-kV overhead line, 150 mm2 cross-section
s (length) = 60 km
ZL/s = 0.46 Ω/km
Ratio of zero-sequence impedance and positive-sequence impedance of the line: ZL0/ZL1 = 4
Short-circuit power at the beginning of the line:
Ssc' = 2.5 GVA
Ratio of zero-sequence impedance and positive-sequence impedance of the source impedance at the
beginning of the line: ZP0/ZP1 = 2
Current transformer = 600 A/5 A
Resulting in the following values for the line impedance ZL and the source impedance ZP:
[fo_ocp_002, 1, en_US]
[fo_ocp_003, 1, en_US]
The 1-pole short-circuit current at the end of the line is IscG end:
[fo_ocp_005, 1, en_US]
The settings in primary and secondary values result in the following setting values which include a safety
margin of 10 %:
[fo_ocp_gr4, 3, en_US]
In case of short-circuit currents exceeding 1246 A (primary) or 10.39 A (secondary) there is a short-circuit on
the line to be protected. The overcurrent protection can cut off this short circuit immediately.
Note: The amounts in the calculation example are accurate enough for overhead lines. If the source impe-
dance, line impedance and zero-sequence impedance have very different angles, you have use complex
numbers to calculate the Threshold.
6.11.3.3 Settings
6.11.4.1 Description
[lo_bbp-ocp_gr2, 3, en_US]
Pickup and Dropout Behaviors of the Inverse-Time Characteristic Curve According to IEC and ANSI (Basic and
Advanced Stage)
When the input variable exceeds the threshold value by a factor of 1.1, the inverse-time characteristic curve is
processed. An integrating method of measurement summarizes the weighted time. The weighted time results
from the characteristic curve. For this, the time that is associated with the present current value is determined
from the characteristic curve. Once the weighted time exceeds the value 1, the stage operates.
When the measured value falls below the pickup value by a factor of 1.045 (0.95 ⋅ 1.1 ⋅ threshold value), the
dropout is started. The pickup will be indicated as clearing. You can influence the dropout behavior via setting
parameters. You can select between instantaneous dropout (totalized time is deleted) or dropout according to
the characteristic curve (reduction of totalized time depending on the characteristic curve). The dropout
according to characteristic curve (disk emulation) is the same as turning back a rotor disk. The weighted
reduction of the time is initiated from 0.9 of the set threshold value.
The characteristic curve and associated formulas are shown in the Technical Data.
• Via the binary input signal >Block stage from an external or internal source
If the setting is left on its default value of 0 s, this parameter has no effect on the inverse-time characteristic
curve.
This parameter is only required for time coordination in recloser schemes. For all other applications, Siemens
recommend keeping the default setting of 0 s.
Parameter: Threshold
Parameter: Reset
6.11.4.3 Settings
• Ensures selective fault detection for parallel lines or transformers with infeed at one end
• Ensures selective fault detection in cable runs with infeed at both ends or in lines connected to form ring
topologies
The Directional overcurrent protection, phases function is used in protection function groups. 2 function
types are offered:
• Pickup
• Operate
[dw_diocba, 5, en_US]
Figure 6-74 Structure/Embedding the Function Directional Overcurrent Protection, Phases – Basic
If the device-internal functions listed in the following are present in the device, these functions can influence
the pickup values and tripping delays of the stages or block the stages. The stage can also be affected by an
external source via a binary input signal.
6.12.3.1 Description
Logic
The following figure represents the stage control. It applies to all types of stages.
[lo_docp_32, 2, en_US]
• From inside on pickup of the Measuring-voltage failure detection function (see chapter 8.3.2.1 Over-
view of Functions)
• From an external source via the binary input signal >Open of the function block Volt.-transf. c.
b., which links in the tripping of the voltage-transformer circuit breaker
The Blk. by meas.-volt. failure parameter can be set so that measuring-voltage failure detection
blocks the stage or does not block it.
A measuring-voltage failure can only be detected if one of the following two conditions is met:
• The binary input signal >Open of the function block VTCB is connected to the voltage-transformer circuit
breaker (see chapter 8.3.4.1 Overview of Functions).
6.12.4.1 Description
[lo_docg6b, 2, en_US]
Figure 6-76 Logic Diagram of the Directional, Definite-Time Overcurrent Protection, Phases - Basic
Directional Mode
You use the Directional mode parameter to define whether the stage works in a forward or reverse direc-
tion.
Direction determination itself works across stages (see section 6.12.6.1 Description ).
Method of Measurement
You use the Method of measurement parameter to define whether the stage uses the fundamental
comp. or the calculated RMS value.
• Externally or internally via the binary input signal >Block stage (see chapter 6.12.3.1 Description )
Parameter: Threshold
• Default setting (_:8131:6) Operate delay = 0.300 s (for the 1st stage)
The Operate delay to be set is derived from the time-grading schedule that has been prepared for the system.
6.12.4.3 Settings
6.12.5.1 Description
[lo_doci6b, 2, en_US]
Figure 6-77 Logic Diagram of the Directional, Inverse-Time Overcurrent Protection, Phases - Basic
Directional Mode
You use the Directional mode parameter to define whether the stage works in a forward or reverse direc-
tion.
The direction determination works across stages (see chapter 6.12.6.1 Description ).
Pickup and Dropout Behaviors of the Inverse-Time Characteristic Curve According to IEC and ANSI
When the input variable exceeds the threshold value by a factor of 1.1, the inverse-time characteristic curve is
processed. An integrating method of measurement summarizes the weighted time. The weighted time results
from the characteristic curve. For this, the time that is associated with the present current value is determined
from the characteristic curve. Once the weighted time exceeds the value 1, the stage operates.
When the measured value falls below the pickup value by a factor of 1.045 (0.95 ⋅ 1.1 ⋅ threshold value), the
dropout is started. The pickup will be indicated as clearing. You can influence the dropout behavior via setting
parameters. You can select between instantaneous dropout (totalized time is deleted) or dropout according to
the characteristic curve (reduction of totalized time depending on the characteristic curve). The dropout
according to characteristic curve (disk emulation) is the same as turning back a rotor disk. The weighted
reduction of the time is initiated from 0.9 of the set threshold value.
The characteristic curve and associated formulas are shown in the Technical Data.
• Externally or internally via the binary input signal >Block stage (see chapter 6.12.3.1 Description )
Parameter: Threshold
The same considerations apply to setting the threshold value as for non-directional overcurrent protection.
Therefore, refer to chapter 6.10.4.2 Application and Setting Notes for further information.
Parameter: Reset
6.12.5.3 Settings
6.12.6.1 Description
General
Every phase has a separate direction-measuring element. If the threshold value in a phase is exceeded, the
direction determination is started for this phase. If there are multiphase short circuits, all measuring elements
involved perform direction determination independently. If one of the determined directions matches the set
direction, the stage picks up (see descriptions of the stage logic).
The direction is determined by calculating the phase angle between the short-circuit current and a reference
voltage.
[dw_docp_02, 1, en_US]
The following table shows how measurands are assigned for direction-determination purposes in the event of
different types of fault.
Direction Determination
As mentioned in the General section, the direction is determined by calculating the phase angle between
short-circuit current and reference voltage. To take different system conditions and applications into account,
the reference voltage can be rotated through an adjustable angle (Rotation angle of ref. volt.
parameter). This moves the vector of the rotated reference voltage close to the vector of the short-circuit
current. Consequently, the result of direction determination is as reliable as possible. Figure 6-79 illustrates
the relationship based on a 1-phase ground fault in phase A. The short-circuit current IscA lags the short-circuit
voltage by the short-circuit angle φsc. The reference voltage, in this case VBC for measuring element A, is
rotated positively (counterclockwise) by the setting value of the Rotation angle of ref. volt. param-
eter. In the scenario illustrated here, the rotation is +45o.
[dw_docp_33, 2, en_US]
The rotated reference voltage defines the forward and reverse range, as shown in Figure 6-80. The forward
range is calculated as ±88o around the rotated reference voltage Vref,rot. If the short-circuit current vector is
located in this range, the device decides on the forward direction. In the mirrored range, the device decides on
the backward direction. In the intermediate range, the direction is undetermined.
[dw_docp_34, 2, en_US]
to 60° inductive. Therefore, in most cases, the default setting of +45o can be retained to position the reference
voltage, as it ensures a reliable directional result.
Some example settings for special applications appear in the following (Table 6-4). Please note that for phase-
to-ground faults (PG faults), the reference voltage (fault-free voltage) is vertical in relation to the short-circuit
voltage. This results in the following setting for the rotation angle:
Rotation angle of ref. volt. = 90 - φsh phase-measuring elements (PG faults)
Please also note that for phase-to-phase faults, the reference voltage is rotated between 0° (distant fault) and
30o (close-up fault) dependent upon the collapse of the faulted voltage (see Figure 6-79). You can take this
into account with an average value of 15°.
Rotation angle of ref. volt. = 90 - φsh - 15o phase-measuring elements (PP faults)
[dw_docp_05, 1, en_US]
• Ensures selective ground-fault detection for parallel lines or transformers with infeed at one end
• Ensures selective ground-fault detection in cable runs with infeed at both ends or in lines connected to
form ring topologies
The Directional overcurrent protection, ground function can be used in protection function groups which
provide zero-sequence current and zero-sequence voltage measurements. 2 function types are offered:
• Pickup
• Operate
[dw_rdirba, 2, en_US]
Figure 6-82 Structure/Embedding of the Function Directional Overcurrent Protection, Ground – Basic
If the following listed device-internal functions are present in the device, these functions can influence the
pickup values and operate delays of the stages or block the stages. The stage can also be affected by an
external source via a binary input signal.
6.13.3.1 Description
Logic
The following figure represents the stage control. It applies to all types of stages.
[lo_sta_con, 2, en_US]
• From an internal source on the pickup of the Measuring-voltage failure detection function
• From an external source via the binary input signal >Open of the function block Voltage-transformer
circuit breaker, which links to the trip of the voltage-transformer circuit breaker
The Blk. by meas.-volt. failure parameter can be set to either block or not block the stage when the
Measuring-voltage failure detection function picks up.
• The device-internal Measuring-voltage failure detection function is configured and switched on.
• The binary input signal >Open of the function block Voltage-transformer circuit breaker is connected to
the voltage-transformer circuit breaker.
6.13.4.1 Description
[lo_dirovb, 2, en_US]
Figure 6-84 Logic Diagram of the Directional Definite-Time Overcurrent Protection, Ground – Basic
• Externally or internally via the binary input signal >Block stage (see chapter 6.13.3.1 Description)
Parameter: Threshold
• Default setting (_:4861:6) Operate delay = 0.300 s (for the 1st stage)
The Operate delay to be set is derived from the time-grading chart that has been prepared for the system.
Typical examples of grading times are provided in sections 6.12.7 Application Notes for Parallel Lines .
6.13.4.3 Settings
6.13.5.1 Description
[lo_diinvb, 3, en_US]
Figure 6-85 Logic Diagram of the Directional Inverse-Time Overcurrent Protection, Ground – Basic
Pickup and Dropout Behaviors of the Inverse-Time Characteristic Curve According to IEC and ANSI (Basic and
Advanced Stage)
When the input variable exceeds the threshold value by a factor of 1.1, the inverse-time characteristic curve is
processed. An integrating method of measurement summarizes the weighted time. The weighted time results
from the characteristic curve. For this, the time that is associated with the present current value is determined
from the characteristic curve. Once the weighted time exceeds the value 1, the stage operates.
When the measured value falls below the pickup value by a factor of 1.045 (0.95 ⋅ 1.1 ⋅ threshold value), the
dropout is started. The pickup will be indicated as clearing. You can influence the dropout behavior via setting
parameters. You can select between instantaneous dropout (totalized time is deleted) or dropout according to
the characteristic curve (reduction of totalized time depending on the characteristic curve). The dropout
according to characteristic curve (disk emulation) is the same as turning back a rotor disk. The weighted
reduction of the time is initiated from 0.9 of the set threshold value.
The characteristic curve and associated formulas are shown in the Technical Data.
• Externally or internally via the binary input signal >Block stage (see chapter 6.13.3.1 Description)
Blocking of the Operate Delay and Operate Signal via the Device-Internal Inrush-Current Detection Function (Basic
and Advanced Stage)
Blocking of the operate delay and the operate signal via the device-internal Inrush-current detection function
is described in chapter Blocking of the Tripping by Device-Internal Inrush-Current Detection
Parameter: Threshold
You can use the Time dial parameter to displace the characteristic curve in the time direction.
The setting value for the Time dial parameter is derived from the time-grading chart that has been
prepared for the electrical power system.
Where no time grading and therefore no displacement of the characteristic curve is required, leave the Time
dial parameter at 1 (default setting).
Parameter: Reset
6.13.5.3 Settings
6.14.1 Description
The function block Group indications of the overcurrent protection functions uses the pickup and operate
indications of the following functions:
• Pickup
• Operate
The pickup and operate indications are output, where present, with direction information.
[lo_oc_grin, 4, en_US]
• Detects 1-phase or 2-phase short circuits in the electrical power system with clearly increased sensitivity
compared to the classical overcurrent protection
• Provides optional tripping release for the differential protection, zone-selective and/or phase-segregated
as a main use case
• Protects equipment (for example, plant components and machines) against damages caused by under-
voltage
• In the DIGSI 5 library, 2 variants of this function are available for the protection devices of the 87 series:
with and without blocking with 1-pole open circuit breaker.
[lo_bbp-uvp3ph-stage_control, 2, en_US]
[lo_uvp_3ph, 3, en_US]
Figure 6-88 Logic Diagram of the Definite-Time Undervoltage Protection with 3-Phase Voltage
Method of Measurement
With the Method of measurement parameter, you select the relevant method of measurement, depending
on the application.
Measured Value
With the Measured value parameter, you define whether the stage analyzes the phase-to-phase voltages
VAB, VBC, and VCA, or the phase-to-ground voltages VA, VB, and VC.
If the measured value is set to phase-to-phase, the function reports those measuring elements that have
picked up.
Pickup Stabilization
To enable the pickup stabilization, you set the Stabilization counter parameter to a value other than 0.
Then, if the input voltage keeps being below the Threshold for a specified number (1 + Stabilization
counter value) of successive measuring cycles, the stage picks up. For 50 Hz, the measuring cycle time is 10
ms.
If you set this parameter to 0 (default value), the stabilization is not applied. The pickup signal is issued after
the input voltage falls below the threshold value.
Pickup Mode
With the Pickup mode parameter, you define whether the stage picks up when there is a lower threshold-
value violation in one measuring element (1 out of 3) or when there is a lower threshold-value violation in
all 3 measuring elements (3 out of 3).
Pickup Delay
The Pickup delay parameter is only available and of relevance if you are using the current-flow criterion of
the function (parameter Current-flow criterion = on).
If the circuit breaker opens when the current-flow criterion is being used, the undervoltage detection and
current-flow dropout functions conflict with one another. Depending on the threshold value settings for
undervoltage detection and current-flow criterion, it is possible that the undervoltage is detected before the
current-flow criterion has dropped out. In this case, the stage picks up briefly. Use the Pickup delay param-
eter to prevent the stage from briefly picking up in this way when the circuit breaker opens. This is achieved
by delaying the pickup by approximately 40 ms.
Current-Flow Criterion
The undervoltage protection stages work optionally with a current-flow criterion. The Current-flow
criterion works across all tripping stages.
When the Current-flow criterion setting is switched on, the undervoltage protection stages only pick
up when the current-flow criterion has been set to met via the binary input signal >Current flow-crite-
rion. The function reports when the current-flow criterion is fulfilled.
The previous figure illustrates the influence of the current-flow criterion.
NOTE
i If the (_:2311:104) Current-flow criterion parameter is deactivated, the device picks up imme-
diately if a missing measuring voltage is detected while the undervoltage protection is active. The param-
eter setting can be changed even when the device has picked up.
• Via the binary input signal >Block stage from an external or internal source
• From an external source via the binary input signal >Open of the function block Volt.-transf. c.
b., which links in the tripping of the voltage-transformer circuit breaker. The Blk. by meas.-volt.
failure parameter can be set so that measuring-voltage failure detection blocks the stage or does not
block it.
Parameter: Threshold
EXAMPLE:
[fo_schw_lw, 2, en_US]
A measuring-voltage failure can only be detected if one of the following two conditions is met:
• The binary input signal >Open of the function block VTCB is connected to the voltage-transformer circuit
breaker (see 8.3.4.1 Overview of Functions).
• If they are located on the supply side, the voltage still exists.
• If they are located on the junction side, the voltage does not exist.
6.16.1.5 Settings
[lo_uvp_3ph_in_stage_control_7SS8x, 2, en_US]
Method of Measurement
With the Method of measurement parameter, you define whether the stage uses the fundamental
comp. or the RMS value.
Measured Value
With the Measured value parameter, you define whether the stage analyzes the phase-to-phase voltages
VAB, VBC, and VCA, or the phase-to-ground voltages VA, VB, and VC.
If the measured value is set to phase-to-phase, the function reports those measuring elements that have
picked up.
Pickup Stabilization
To enable the pickup stabilization, you set the Stabilization counter parameter to a value other than
zero. Then, if the input voltage keeps being below the pickup value for a specified number (1 + Stabiliza-
tion counter value) of successive measuring cycles, the stage picks up. For 50 Hz, the measuring cycle
time is 10 ms.
If you set this parameter to 0 (default value), the stabilization is not applied. The pickup signal is issued after
the input voltage falls below the pickup value.
Pickup Mode
With the Pickup mode parameter, you define whether the stage picks up when there is a lower threshold-
value violation in one measuring element (1 out of 3) or when there is a lower threshold-value violation in
all 3 measuring elements (3 out of 3).
After pickup the time value TInv is calculated for every input voltage less than the dropout value. An integrator
accumulates the value 1/TInv. Once the accumulated integral reaches the fixed value 1, the inverse-time delay
expires. The stage operates after the additional time delay.
The inverse-time delay is calculated with the following formula:
[fo_uvp_3ph_inverse, 2, en_US]
Where
[dw_uvp_3ph_inverse, 1, en_US]
Pickup Delay
The Pickup delay parameter is only available and of relevance if you are using the current-flow criterion of
the function (parameter Current-flow criterion = on).
If the circuit breaker opens when the current-flow criterion is being used, the undervoltage detection and
current-flow dropout functions conflict with one another. Depending on the threshold value settings for
undervoltage detection and current-flow criterion, it is possible that the undervoltage is detected before the
current-flow criterion has dropped out. In this case, the stage picks up briefly. Use the Pickup delay param-
eter to prevent the stage from briefly picking up in this way when the circuit breaker opens. This is achieved
by delaying the pickup by approximately 40 ms.
Dropout Behavior
When the voltage exceeds the dropout value (1.05 x pickup factor x threshold value), the pickup signal is
going and the dropout is started. You can define the dropout behavior via parameter Reset time. Instanta-
neous reset takes place by setting Reset time to 0 s. A delayed reset takes place by setting the desired delay
time.
During the Reset time (> 0 s), the elapsed operate delay is frozen. If the stage picks up again within this
period, the stage operates when the rest of operate delay expires.
Current-Flow Criterion
The undervoltage protection stages work optionally with a current-flow criterion. The Current-flow
criterion works across all tripping stages.
When the Current-flow criterion setting is switched on, the undervoltage protection stages only pick
up when the current-flow criterion has been set to met via the binary input signal >Current flow-crite-
rion. The function reports when the current-flow criterion is fulfilled.
The previous figure illustrates the influence of the current-flow criterion.
NOTE
i If the (_:2311:104) Current-flow criterion parameter is deactivated, the device picks up imme-
diately if a missing measuring voltage is detected while the undervoltage protection is active. The param-
eter setting can be changed even when the device has picked up.
• Via the binary input signal >Block stage from an external or internal source
• From an external source via the binary input signal >Open of the function block Volt.-transf. c.
b., which links in the tripping of the voltage-transformer circuit breaker. The Blk. by meas.-volt.
failure parameter can be set so that measuring-voltage failure detection blocks the stage or does not
block it.
• The binary input signal >Open of the function block VTCB is connected to the voltage-transformer circuit
breaker (see 8.3.4.1 Overview of Functions).
• If they are located on the supply side, the voltage still exists.
• If they are located on the junction side, the voltage does not exist.
6.16.1.9 Settings
• Protects equipment (for example, plant components and machines) from damages caused by under-
voltage
2-phase short circuits or ground faults lead to an unbalanced voltage collapse. In comparison to three 1-phase
measuring systems, such events have no noticeable impact on the positive-sequence voltage. This makes this
function particularly suitable for the assessment of stability problems.
[lo_bbp-uvp-mit-3p, 2, en_US]
Figure 6-91 Logic Diagram of the Stage Undervoltage Protection with Positive-Sequence Voltage
Method of Measurement
The stage uses the positive-sequence voltage. The positive-sequence voltage is calculated from the measured
phase-to-ground voltages according to the defining equation.
Pickup Delay
The Pickup delay parameter is only available and of relevance if you are using the current-flow criterion of
the function (parameter Current-flow criterion = on).
If the circuit breaker opens when the current-flow criterion is being used, the undervoltage detection and
current-flow dropout functions conflict with one another. Depending on the threshold value settings for
undervoltage detection and current-flow criterion, it is possible that the undervoltage is detected before the
current-flow criterion has dropped out. In this case, the tripping stage picks up briefly. Use the Pickup
delay parameter to prevent the tripping stage from briefly picking up in this way when the circuit breaker
opens. This is achieved by delaying pickup by approximately 40 ms.
Current-Flow Criterion
The undervoltage-protection stages work optionally with a current-flow criterion. The current-flow criterion
works across all stages.
When the Current-flow criterion parameter is switched on, the undervoltage protection stages only
pick up when the current-flow criterion has been set to fulfilled via the binary input signal >Current flow-
criterion. The function reports when the current-flow criterion is fulfilled.
Figure 6-91 illustrates the influence of the current-flow criterion.
NOTE
i If the Current-flow criterion parameter is switched off, the device picks up immediately if a missing
measuring voltage is detected while the undervoltage protection is active. The parameter setting can be
changed even when the device has picked up.
• Via the binary input signal >Block stage from an external or internal source
• From an external source via the binary input signal >Open of the function block Volt.-transf. c.
b., which links in the tripping of the voltage-transformer circuit breaker. The Blk. by meas.-volt.
failure parameter can be set so that measuring-voltage failure detection blocks the stage or does not
block it.
Parameter: Threshold
• If they are located on the supply side, the voltage still exists.
• If they are located on the output side, the voltage does not exist.
6.16.2.5 Settings
Logic of a Stage
[lo_uvp_Vx_any-volt, 2, en_US]
Figure 6-92 Logic Diagram of a Stage: Undervoltage Protection with Any Voltage
Method of Measurement
The Method of measurement parameter allows you to define whether the function works with the funda-
mental component or the calculated RMS value.
Measured Value
The parameter Measured value allows you to select whether the stage uses a measured (directly
connected) voltage or a calculated phase-to-phase voltage.
Current-Flow Criterion
The undervoltage-protection stages work optionally with a current-flow criterion. The current-flow criterion
works across all stages.
When the Current-flow criterion parameter is switched on, the undervoltage protection stages only
pick up when the current-flow criterion has been set to fulfilled via the binary input signal >Current flow-
criterion. The function reports when the current-flow criterion is fulfilled.
Figure 6-92 illustrates the influence of the current-flow criterion.
NOTE
i If the (_:2311:101) Current-flow criterion parameter is deactivated, the device picks up imme-
diately if a missing measuring voltage is detected while the undervoltage protection is active. The param-
eter setting can be changed even when the device has picked up.
NOTE
i From V7.30 on, the value VN measured is no longer provided. If you have selected this value in earlier
versions, you can select the value V0 calculated instead after upgrading the configuration to V7.30 or a
later version.
Parameter: Threshold
NOTE
i If the function is used in a Voltage-current 1-phase function group connected to the 1-phase voltage
measuring point with the voltage type VN broken-delta, you set the threshold value based on the
equivalent zero-sequence voltage.
Calculate the equivalent zero-sequence voltage V0 equiv. sec from the measured voltage VN sec with the
following formula:
For more information about the parameter Matching ratio Vph / VN, refer to 6.1.5 Application and
Setting Notes for Measuring Point Voltage 3‑Phase (V-3ph).
NOTE
i Because of the flexible setting options of the voltage measurand, the function itself does not determine the
current associated with the voltage. A suitable current-flow monitoring function must be created by the
user with the Continuous Function Chart (CFC), and connected to the binary input signal >Current
flow-criterion.
6.16.3.5 Settings
• Protect equipment (for example, plant components, machines, etc.) against damages caused by over-
voltage
[lo_3phas_i, 5, en_US]
Figure 6-93 Logic Diagram of the Definite-Time Overvoltage Protection with 3-Phase Voltage
Method of Measurement
Use the Method of measurement parameter to define whether the stage uses the fundamental comp.
or the RMS value.
Pickup Stabilization
To enable the pickup stabilization, you set the Stabilization counter parameter to a value other than
zero. Then, if the input voltage keeps exceeding the Threshold for a specified number (1 + Stabiliza-
tion counter value) of successive measuring cycles, the stage picks up. For 50 Hz, the measuring cycle
time is 10 ms.
If you set this parameter to 0 (default value), the stabilization is not applied. The pickup signal is issued imme-
diately after the input voltage exceeds the Threshold.
Pickup Mode
The Pickup mode parameter defines whether the protection stage picks up if all 3 measuring elements
detect the overvoltage condition (3 out of 3) or if only 1 measuring element detects the overvoltage
condition (1 out of 3).
Measured Value
Use the Measured value parameter to define whether the tripping stage analyzes the phase-to-phase
voltages VAB, VBC, and VCA, or the phase-to-ground voltages VA, VB, and VC.
If the measured value is set to phase-to-phase, the function reports those measuring elements that have
picked up.
Parameter: Threshold
EXAMPLE
Example for 2-stage overvoltage protection
The example describes the possible settings for a 2-stage overvoltage protection function. We will look at the
settings of the parameters Threshold and Operate delay.
• 1. Stage:
To detect stationary overvoltages, set the threshold value of the first overvoltage-protection element at
least 10 % above the max. stationary phase-to-phase voltage anticipated during normal operation. When
setting the parameter Measured value to phase-to-phase voltage and a secondary rated voltage of
100 V, the secondary setting value of the first overvoltage-protection element is calculated as follows:
• 2. Stage:
The second overvoltage-protection stage is intended for high overvoltages with short duration. A high
pickup value is selected here, for example, 1.5 times the rated voltage. A time delay setting of 0.1 s to
0.2 s is sufficient then.
6.16.4.5 Settings
[lo_3ph_inv, 4, en_US]
Figure 6-94 Logic Diagram of the Inverse-Time Overvoltage Protection with 3-Phase Voltage
Method of Measurement
Use the Method of measurement parameter to define whether the stage uses the fundamental comp.
or the RMS value .
Pickup Stabilization
To enable the pickup stabilization, you set the Stabilization counter parameter to a value other than
zero. Then, if the input voltage keeps exceeding the pickup value for a specified number (1 + Stabiliza-
tion counter value) of successive measuring cycles, the stage picks up. For 50 Hz, the measuring cycle
time is 10 ms.
If you set this parameter to 0 (default value), the stabilization is not applied. The pickup signal is issued imme-
diately after the input voltage exceeds the pickup value.
Pickup Mode
With the Pickup mode parameter, you define whether the protection stage picks up if all 3 measuring
elements detect the overvoltage condition ( 3 out of 3 ) or if only 1 measuring element detects the over-
voltage condition ( 1 out of 3 ).
Measured Value
Use the Measured value parameter to define whether the stage analyzes the phase-to-phase voltages VAB,
VBC, and VCA, or the phase-to-ground voltages VA, VB, and VC.
If the measured value is set to phase-to-phase, the function reports those measuring elements that have
picked up.
Where
Top Operate delay
Tinv Inverse-time delay
Tadd Additional time delay (parameter Additional time delay )
After pickup, the time value Tinv is calculated for every input voltage that exceeds the threshold. An integrator
accumulates the value 1/Tinv. Once the accumulated integral reaches the fixed value 1, the inverse-time delay
expires. The additional time delay Tadd starts. The stage operates after the additional time delay expires.
[dw_ovp_inv, 2, en_US]
Where
Tinv Inverse-time delay
Tp Time multiplier (parameter Time dial )
V Measured voltage
Vthresh Threshold value (parameter Threshold )
k Curve constant k (parameter Charact. constant k )
α Curve constant α (parameter Charact. constant α )
c Curve constant c (parameter Charact. constant c )
When V/Vthresh is equal to or greater than 20, the inverse-time delay does not decrease any further.
Dropout Behavior
When the voltage falls below the dropout threshold (0.95 × pickup factor × threshold value), the pickup signal
is going and the dropout is started. You can define the dropout behavior via parameter Reset time . Instan-
taneous reset takes place by setting Reset time to 0 s. A delayed reset takes place by setting the desired
delay time.
During the Reset time (> 0 s), the elapsed operate delay is frozen. If the pickup value is exceeded again
within this period, the stage operates when the rest of operate delay expires.
For example, if you set this parameter to 1, the pickup signal is issued when the voltage keeps exceeding the
pickup value for 2 successive measuring cycles. For 50 Hz, the measuring cycle time is 10 ms.
6.16.4.9 Settings
• Supervise the voltage range if the positive-sequence voltage is the decisive quantity
Unbalanced overvoltages, for example, caused by ground faults and unbalanced faults, are not detected due
to the evaluation of the positive-sequence voltage.
Logic of a Stage
[lo_govpu1, 2, en_US]
Figure 6-96 Logic Diagram of a Stage: Overvoltage Protection with Positive-Sequence Voltage
Method of Measurement
The stage uses the positive-sequence voltage. The positive-sequence voltage is calculated from the measured
phase-to-ground voltages according to the defining equation.
Parameter: Threshold
General Notes
If the overvoltage is high, the first stage can trip with a short time delay. If overvoltages are lower, the second
stage can either only signal the threshold value violation (see Operation as monitoring function) or trip with a
longer delay to allow the voltage controller to regulate the voltage back into the nominal range.
6.16.5.5 Settings
• The most common cause is unbalanced load, caused by different consumers in the individual phases, for
example.
• Other causes can include faults in the primary system, for example, at the transformer or in installations
for reactive-power compensation.
• Voltage unbalance can also be caused by phase failure, for example, due to a tripped 1-phase fuse.
• In the DIGSI 5 library, 2 variants of this function are available for the protection devices of the 87 series:
with and without blocking with 1-pole open circuit breaker.
6.16.6.3 Description
Measurand
The average value of negative-sequence voltage is determined by a settable time interval (parameter: Meas-
uring window). With the parameter Measuring window, you can adapt this function to all power-system
conditions.
You can set the parameter Measuring window with a large value to get a more accurate calculated result,
which leads to a longer pickup time however.
• The binary input signal >Open of the function block VTCB is connected to the voltage-transformer circuit
breaker (see chapter 8.3.4.1 Overview of Functions).
6.16.6.5 Settings
6.16.6.7 Description
Logic of a Stage
[lo_ovp_v2_3pol, 4, en_US]
Figure 6-97 Logic Diagram of the Stage: Overvoltage Protection with Negative-Sequence Voltage
Method of Measurement
The stage uses the average value of the negative-sequence voltage, which is calculated from the function
block General Functionality. For more information, refer to chapter 6.16.6.3 Description.
• From an external or internal source via the binary input signal >Block stage
Parameter: Threshold
Example 1:
Releasing an overcurrent protection stage for unbalanced faults
The following section describes how to set the function to release an Overcurrent-protection stage when
unbalanced faults occur. Set the Overcurrent-protection stage only slightly higher than the load current, that
is very sensitive. To prevent the Overcurrent-protection stage from picking up inadvertently, the Overcur-
rent-protection stage is released when the Negative-sequence voltage stage picks up. The Overcurrent-
protection stage remains blocked as long as the Negative-sequence voltage stage has not picked up.
Figure 6-98 shows the voltage phasors during a 2-phase local fault between phases B and C. The phase-to-
phase voltage VBC is virtually 0.
[dw_ua_zeig, 1, en_US]
A 2-phase local fault generates a relatively large negative-sequence voltage of up to 50 % referred to the
phase-to-ground voltage. The portion of the negative-sequence decreases in case of a remote fault. The lower
setting limit results from the possible unbalance at full load. If you assume for example 5 % negative-
sequence voltage, the pickup value must be higher. A setting value of 10 % warrants sufficient stability during
unbalanced operating states and sufficient sensitivity to release the Overcurrent-protection stage when a
fault occurs.
For a secondary rated voltage of 100 V, set the following secondary threshold value:
You can keep the default setting of 0.95 for the dropout ratio. This avoids chattering of the stage.
Set the Negative-sequence voltage stage so that it does not generate a fault when it picks up and does not
initiate tripping. The Overcurrent-protection stage generates a fault indication. The pickup of the Negative-
sequence voltage stage is used as the release criterion because the Short-circuit function must be released
immediately when the Negative-sequence voltage stage has picked up. The time delay is thus not relevant
and can be left at the default setting.
You implement the release of the Overcurrent-protection stage using a logic block chart. An inverter links
the pickup of the Negative-sequence voltage stage with the Overcurrent-protection stage blocking.
[lo_invert, 1, en_US]
Example 2:
A negative-sequence voltage in the auxiliary system of the power plant causes negative-sequence currents on
motors. This leads to a thermal overload of the rotors. The following estimation can be used as a basis: 1 %
negative-sequence voltage can lead to approximately 5 % or 6 % negative-sequence current.
A negative-sequence voltage can be caused by a broken conductor on the high-voltage side. If a negative-
sequence voltage occurs, this can, for example, initiate a switching of the infeed in order to prevent a protec-
tion trip of an unbalanced-load protection of the motors.
Siemens recommends using multiple stages for a better grading, whereby a sensitive setting of the threshold
permits an increased tripping delay.
For a reference, only 2 stages are discussed.
The first stage has a pickup threshold of 10 % with a time delay of 1.5 s. The second stage has a pickup
threshold of 3 % with a time delay of 8 s, see Table 6-5. Further, it is assumed that the voltage transformer is
well adapted to the rated voltage.
[fo_ovp_v2_secondary_threshold2, 1, en_US]
6.16.6.9 Settings
• In the DIGSI 5 library, 2 variants of this function are available for the protection devices of the 87 series:
with and without blocking with 1-pole open circuit breaker.
[lo_ovp_u_03, 3, en_US]
Figure 6-100 Logic Diagram of the Definite-Time Overvoltage Protection with Zero-Sequence Voltage/
Residual Voltage
zero‑sequence voltage V0 is calculated from the measured phase-to-ground voltages VA, VB, and VC using the
defining equation.
With the parameter Method of measurement, you select the relevant method of measurement, depending
on the application:
• fund. comp. long filter (fundamental component over 2 cycle filters with triangular window):
This method of measurement processes the sampled voltage values and filters out the fundamental
component numerically. The extended filter length compared to the standard filter and the use of the
triangular window results in a particularly strong attenuation of harmonics and transient faults. The
extended filter length causes the pickup time to increase slightly compared to the standard filter (refer to
the technical data in 11.19.4 Overvoltage Protection with Zero-Sequence Voltage/Residual Voltage ).
Pickup, Dropout
The stage compares the Threshold with the zero-sequence voltage V0. The parameter Pickup delay
allows you to delay the pickup of the stage depending on the residual voltage.
With the parameter Dropout ratio, you can define the ratio of the dropout value to the Threshold.
Parameter: Threshold
• Since virtually the full residual voltage occurs during ground faults in isolated or arc-suppression-coil-
grounded systems, the setting value is uncritical there. It should range between 20 V and 40 V. A higher
sensitivity (= lower threshold value) can be necessary for high fault resistances.
• You should select a more sensitive (smaller) value in a grounded system. This value must be higher than
the maximum residual voltage anticipated during operation caused by system unbalances.
EXAMPLE
For an isolated system
The residual voltage is measured via the broken-delta winding:
• If the ground fault is fully unbalanced, a residual voltage of 100 V is present at the device terminals.
• The threshold value should be set so that the stage picks up on 50 % of the full residual voltage.
21 The specific setting limits depend on the transformer data and transformer connections set.
A measuring-voltage failure can only be detected if one of the following 2 conditions is met:
• The binary input signal >Open of the function block Voltage-transformer circuit breaker is
connected to the voltage-transformer circuit breaker (refer to 8.3.4.1 Overview of Functions).
22 The specific setting limits depend on the transformer data and transformer connections set.
6.16.7.5 Settings
[lo_ovp_V0_3pole_inverse, 1, en_US]
Figure 6-101 Logic Diagram of the Inverse-Time Overvoltage Protection with Zero-Sequence Voltage/
Residual Voltage
With the parameter Method of measurement, you select the relevant method of measurement, depending
on the application:
• fund. comp. long filter (fundamental component over 2 cycle filters with triangular window):
This method of measurement processes the sampled voltage values and filters out the fundamental
component numerically. The extended filter length compared to the standard filter and the use of the
triangular window results in a particularly strong attenuation of harmonics and transient faults. The
extended filter length causes the pickup time to increase slightly compared to the standard filter (refer to
the technical data in 11.19.4 Overvoltage Protection with Zero-Sequence Voltage/Residual Voltage ).
Where
Top Operate delay
Tinv Inverse-time delay
Tadd Additional time delay (parameter Additional time delay)
After pickup, the inverse-time delay Tinv is calculated for every input voltage that exceeds the threshold. An
integrator accumulates the value 1/Tinv. Once the accumulated integral reaches the fixed value 1, the inverse-
time delay expires. The additional time delay Tadd starts. The stage operates after the additional time delay
expires.
[dw_ovp_inv, 2, en_US]
Where
Tinv Inverse-time delay
Tp Time multiplier (parameter Time dial)
V Zero-sequence voltage
Vthresh Threshold value (parameter Threshold)
k Curve constant k (parameter Charact. constant k)
α Curve constant α (parameter Charact. constant α)
c Curve constant c (parameter Charact. constant c)
When V/Vthresh is equal to or greater than 20, the inverse-time delay does not decrease any further.
Dropout Behavior
When the voltage falls below the dropout threshold (0.95 ⋅ pickup factor ⋅ threshold value), the dropout is
initiated. You can define the dropout behavior via the parameter Reset time. An instantaneous reset takes
place by setting Reset time to 0 s. A delayed reset takes place by setting the desired time delay.
During the Reset time (> 0 s), the elapsed operate delay is frozen. If the pickup value is exceeded again
within this period, the stage operates when the rest of the operate delay expires.
threshold value V> healthy ph-to-gnd volt. and 1 phase falls below the threshold value V< faulty
ph-to-gnd volt., the last phase is considered to be affected by the ground fault and is signaled as such.
• The binary input signal >Open of the function block Voltage-transformer circuit breaker is
connected to the voltage-transformer circuit breaker (refer to 8.3.4.1 Overview of Functions).
23 The specific setting limits depend on the transformer data and transformer connections set.
The setting value must be smaller than the minimum phase-to-ground voltage occurring during operation.
Siemens recommends using the default setting of 40.000 V.
6.16.7.9 Settings
Logic of a Stage
[lo_ovp_Vx_any-volt, 2, en_US]
Figure 6-103 Logic Diagram of a Stage: Overvoltage Protection with Any Voltage
Method of Measurement
The Method of measurement parameter allows you to define whether the function works with the funda-
mental component or the calculated RMS value.
Measured Value
The parameter Measured value allows you to select whether the stage uses a measured (directly
connected) voltage or a calculated phase-to-phase voltage.
NOTE
i From V7.30 on, the value VN measured is no longer provided. If you have selected this value in earlier
versions, you can use either the following methods instead after upgrading the configuration to V7.30 or a
later version:
• Select the value V0 calculated for the Measured value parameter in the function Overvoltage
protection with any voltage.
Parameter: Threshold
Depending on the measured value, the Threshold is set either as Measured voltage or as Phase-to-
phase quantity.
NOTE
i If the function is used in a Voltage-current 1-phase function group connected to the 1-phase voltage
measuring point with the voltage type VN broken-delta, you set the threshold value based on the
equivalent zero-sequence voltage.
Calculate the equivalent zero-sequence voltage V0 equiv. sec from the measured voltage VN sec with the
following formula:
For more information about the parameter Matching ratio Vph / VN, refer to 6.1.5 Application and
Setting Notes for Measuring Point Voltage 3‑Phase (V-3ph).
6.16.8.5 Settings
• Monitor the power system and electric machines for voltage unbalances
• The most common cause is unbalanced load, caused by different consumers in the individual phases, for
example.
• Voltage unbalance can also be caused by phase failure, for example due to a tripped 1-phase fuse, a
broken conductor, etc.
• Other causes can include faults in the primary system, for example, at the transformer or in installations
for reactive-power compensation.
[lo_structure_V2_V1, 2, en_US]
6.16.9.3 Description
Logic
The following figure represents the logic of the average-value calculation of the ratio of negative-sequence
voltage to positive-sequence voltage. The average value is forwarded to all subordinate stages.
Measurand
The average value of the ratio of negative-sequence voltage to positive-sequence voltage is determined by a
settable time interval (parameter: Measuring window). With the parameter Measuring window, you can
adapt this function to all power-system conditions.
You can set the parameter Measuring window with a large value to get a more accurate calculated result,
which leads to a longer pickup time however.
• From inside on pick up of the Measuring-voltage failure detection function (see section 8.3.2.1 Over-
view of Functions).
• From an external source via the binary input signal >Open of the function block Volt.-transf. c. b., which
links in the tripping of the voltage-transformer circuit breaker.
The parameter Blk. by meas.-volt. failure can be set so that the measuring-voltage failure detection
blocks the function or does not block it.
You use the Blk. by meas.-volt. failure parameter to control the behavior of the function when a
measuring-voltage failure is detected.
A measuring-voltage failure can only be detected if one of the following 2 conditions is met:
• The binary input signal >Open of the function block VTCB is connected to the voltage-transformer circuit
breaker (see chapter 8.3.4.1 Overview of Functions).
6.16.9.5 Settings
6.16.9.8 Description
Logic of a Stage
[lo_V2_V1_Prov, 2, en_US]
Figure 6-106 Logic Diagram of the Stage: Overvoltage Protection with Negative-Sequence Voltage/Positive-
Sequence Voltage
Method of Measurement
The stage uses the average value of the negative-sequence voltage/positive-sequence voltage, which is calcu-
lated from the function block General Functionality. For more information, refer to chapter 6.16.9.3 Descrip-
tion.
• From an external or internal source via the binary input signal >Block stage
Parameter: Threshold
Example 1:
Releasing an overcurrent protection stage for unbalanced faults
The following section describes how to set the function to release an Overcurrent-protection stage when
unbalanced faults occur. Set the Overcurrent-protection stage only slightly higher than the load current, that
is very sensitive. To prevent the Overcurrent-protection stage from picking up inadvertently, the Overcur-
rent-protection stage is released when the Negative-sequence voltage stage picks up. The Overcurrent-
Protection stage remains blocked as long as the Negative-sequence voltage stage has not picked up.
Figure 6-107 shows the voltage phasors during a 2-phase local fault between phases B and C. The phase-to-
phase voltage VBC is virtually 0.
[dw_ua_zeig, 1, en_US]
A 2-phase local fault generates a relatively large negative-sequence voltage of up to 100 % referred to the
positive-sequence voltage. The portion of the negative-sequence decreases in case of a remote fault. The
lower setting limit results from the possible unbalance at full load. If you assume for example 5 % of the nega-
tive-sequence voltage to positive-sequence voltage, the pickup value must be higher. A setting value of 10 %
warrants sufficient stability during unbalanced operating states and sufficient sensitivity to release the Over-
current-protection stage when a fault occurs.
You can keep the default setting of 0.95 for the dropout ratio. This avoids chattering of the stage.
Set the Negative-sequence voltage stage so that it does not generate a fault when it picks up and does not
initiate tripping. The Overcurrent-protection stage generates a fault indication. The pickup of the Negative-
sequence voltage stage is used as the release criterion because the Short-circuit function must be released
immediately when the Negative-sequence voltage stage has picked up. The time delay is thus not relevant
and can be left at the default setting.
You implement the release of the Overcurrent-protection stage using a logic block chart. An inverter links
the pickup of the Negative-sequence voltage stage with the Overcurrent-protection stage blocking.
Example 2:
A negative-sequence voltage in the auxiliary system of the power plant causes negative-sequence currents on
motors. This leads to a thermal overload of the rotors. The following estimation can be used as a basis: 1 %
negative-sequence voltage can lead to approximately 5 % or 6 % negative-sequence current.
A negative-sequence voltage can be caused by a broken conductor on the high-voltage side. If a negative-
sequence voltage occurs, this can, for example, initiate a switching of the infeed in order to prevent a protec-
tion trip of an unbalanced-load protection of the motors.
Siemens recommends using multiple stages for a better grading, whereby a sensitive setting of the threshold
permits an increased tripping delay.
For a reference, only 2 stages are discussed.
The first stage has a pickup threshold of 10 % with a time delay of 1.5 s. The second stage has a pickup
threshold of 3 % with a time delay of 8 s, seeTable 6-6.
6.16.9.10 Settings
Logic of a Stage
[lo_stofqp, 2, en_US]
Frequency-Measurement Method
Underfrequency protection is available in 2 functional configurations. These work with different frequency-
measurement methods. You select the frequency-measurement method in dependence of the application.
Both methods of measurement are characterized by a high measuring accuracy combined with a short
response time. Disturbance values such as harmonics, high frequency disturbances, phase-angle jumps during
switching operations and compensation processes due to power swings are effectively suppressed.
NOTE
Frequency-Measurement Method
The frequency measurement method is selected with the functional configuration from the DIGSI functions
library. The letter at the end of the function name describes the method of measurement.
Redundant solutions can be implemented by combining 2 different methods of frequency measurement. You
can implement a 2-out-of-2 decision by connecting the operate indications of both functions in a CFC with a
logical AND gate. This increases the reliability of protection.
Frequency-Measurement Description
Method
Angle difference method Select this method of measurement if the frequency protection stage is
(method A) used for the protection of machines.
Filtering method (method B) Select this method of measurement if the frequency protection stage is
used in an electrical power system.
Parameter: Threshold
With the parameter Threshold, you define the pickup threshold of the overfrequency protection stage in
dependence of the application. 50.20 Hz is a typical warning threshold in 50-Hz systems.
In the angle-difference method, the setting value relates to the positive-sequence system.
NOTE
i If in DIGSI you switch over the settings view of the parameters to Percent, the phase-to-phase value of
the rated voltage is the reference value for the Minimum voltage in both methods of measurement.
NOTE
i This table shows one example of a possible frequency protection setting. The setting values can differ
depending on the application.
6.17.1.5 Settings
• Disconnect generating units when the power system frequency is critical (for example, f < 0.95 frated)
Frequency deviations are caused by an unbalance between the active power generated and consumed. Under-
frequency is caused by an increase of the consumers' active power demand or by a decrease of the power
generated. These conditions occur in the case of power system disconnection, generator failure, or distur-
bances of the power and frequency controller.
Underfrequency protection is available in 2 functional configurations (selectable from the DIGSI functions
library). The functional configurations differ in the frequency measurement method they use.
Logic of a Stage
[lo_stuf_qp, 3, en_US]
Frequency-Measurement Method
Underfrequency protection is available in 2 functional configurations. These work with different frequency-
measurement methods. You select the frequency-measurement method in dependence of the application.
Both methods of measurement are characterized by a high measuring accuracy combined with a short
response time. Disturbance values such as harmonics, high frequency disturbances, phase-angle jumps during
switching operations and compensation processes due to power swings are effectively suppressed.
NOTE
• Via the binary input signal >Block stage from an external or internal source
Frequency-Measurement Method
The frequency measurement method is selected with the functional configuration from the DIGSI functions
library. The letter at the end of the function name describes the method of measurement.
Redundant solutions can be implemented by combining 2 different methods of frequency measurement. You
can implement a 2-out-of-2 decision by connecting the operate indications of both functions in a CFC with a
logical AND gate. This increases the security of protection.
Method of Measurement Description
Angle-difference method Select this method of measurement if the frequency protection stage is
(method A) used for the protection of machines.
Filtering method (method B) Select this method of measurement if the frequency protection stage is
used in an electrical power system.
Parameter: Threshold
With the parameter Threshold, you define the pickup threshold of the underfrequency protection stage in
dependence of the application. 49.8 Hz is a typical warning threshold in 50-Hz systems.
For Vrated = 100 V secondary, the setting value of the Minimum voltage is calculated as follows:
In the angle-difference method, the setting value relates to the positive-sequence system.
NOTE
i If in DIGSI you switch over the settings view of the parameters to Percent, the phase-to-phase value of
the rated voltage is the reference value for the Minimum voltage in both methods of measurement.
Frequency Activity
49.80 Hz Alarm and activation of reserves following an established plan
49.00 Hz Undelayed disconnection of 10 % to 15 % of the power system load
48.70 Hz Undelayed disconnection of another 10 % to 15 % of the power system load
48.40 Hz 3rd load-shedding stage. Another 15 % to 20 % of the power system load is
disconnected.
47.50 Hz Power plants are decoupled from the electrical power system
For this application, 3 stages of the underfrequency protection are used. 2 of these stages are used for load
shedding. The following table shows a setting suggestion.
Stage Caused by Setting Values
At frated = 50 Hz At frated = 60 Hz Delay
f1< Warning 49.80 Hz 59.80 Hz 10.00 s
f2< 1st load shedding 49.00 Hz 59.00 Hz 0.00 s
f3< 2nd load shedding 48.70 Hz 58.70 Hz 0.00 s
NOTE
i This table shows one example of a possible frequency protection setting. The setting values can differ
depending on the application.
6.17.2.5 Settings
• Prevent the system from not secure states caused by unbalance between the generated and consumed
active power
• Network decoupling
• Load shedding
• df/dt rising
• df/dt falling
The function Rate of frequency change protection is preconfigured by the manufacturer with 1 df/dt rising
stage and 1 df/dt falling stage. A maximum of 5 df/dt rising stages and 5 df/dt falling stages can operate simul-
taneously within the function. Both of the function block types are similar in structure.
Undervoltage check and df/dt calculation are general functionalities and take place on the function level. All
stages use these general functionalities.
6.17.3.3 Description
Logic
The following figure represents the logic of undervoltage check and df/dt calculation. It applies to all types of
stages.
[lo_dfdtgf, 2, en_US]
Measurand
This function uses the frequency calculated via the angle difference algorithm.
For more information, refer to chapter 6.17.1.3 Overfrequency-Protection Stage.
The frequency difference is calculated over a settable time interval (default setting: 5 periods).
The ratio between the frequency difference and the time difference reflects the frequency change which can
be positive or negative.
A stabilization counter works to avoid overfunction. This counter is increased if the set threshold value is
exceeded. If the value drops below the threshold value, the counter is reset immediately. The counter is set to
8 internally and is activated at each half system cycle.
Undervoltage Blocking
If the measuring voltage drops below the Minimum voltage, the Rate of frequency change protection is
blocked because precise frequency values cannot be calculated anymore.
Value Description
df/dt Calculated rate of frequency change
6.17.3.5 Description
[lo_dfdt_st, 2, en_US]
(1) For the stage type df/dt rising, the value df/dt rising is used.
Frequency Rising/Falling
The stage df/dt falling is used to detect frequency falling and the stage df/dt rising is used to detect
frequency rising.
You set the threshold value as an absolute value. You define the frequency-change direction via the selected
stage type.
• Via the undervoltage blocking when the voltage drops below the Minimum voltage
Parameter: Threshold
frequency rises and causes a positive frequency change. On the other hand, a failure of generators leads to a
deficit of active power. The frequency drops and results in a negative frequency change.
The following relations can be used as an example for estimation. They apply for the change rate at the begin-
ning of a frequency change (approximate 1 s).
Where:
frated Rated frequency
ΔP Active power change
ΔP = PConsumption - PGeneration
Srated Rated apparent power of the machines
H Inertia constant
EXAMPLE
frated = 50 Hz
H=3s
Case 1: ΔP/Srated = 0.12
Case 2: ΔP/Srated = 0.48
Case 1: df/dt = -1 Hz/s
Case 2: df/dt = -4 Hz/s
NOTE
i In case of power-system incidents, especially in case of transmission incidents and influence of voltage-
stabilizing measures via power-electronic components (reactive-power compensation through SVC), the
magnitude and the phase angle of the voltage can change. Sensitive settings can lead to overfunction.
Therefore, it is reasonable to block the Rate of Frequency Change Protection if other protection func-
tions, for example, residual voltage or negative-sequence voltage, pick up. To do this, use the blocking
input >Block stage and connect it via CFC.
6.17.3.7 Settings
• Is used as a backup protection for the transformer and the generator in the block units of power stations
• Functions as backup protection in the event of energy recovery to faults in the upstream electrical power
system beyond a transformer
The Impedance protection function is used in protection function groups which provide current and voltage
measurement values.
The Impedance protection function is preconfigured at the factory with the function block (FB) General and
one zone. A maximum of 4 zones can be operated simultaneously in the function. The zones are structured
identically.
The protection function is structured in that way that the settings in the FB General are valid for all zones.
[dw_strimpedanceprot, 3, en_US]
6.18.3 Description
• Impedance is transferred to the side to be measured using the quadrant of the transformer ratio.
• For star-delta transformers, an opposite phase rotation occurs in the positive-sequence and negative-
sequence system, depending on the vector group. This changes the fault situation on the other side. A
2‑phase short circuit on the star side appears as a 3-phase short circuit with different current distribution
on the delta side (see Figure 6-115).
Since star-delta transformers do not permit the zero-sequence system to be transferred, a 1-phase
ground fault on the star side appears as a 2-phase short circuit on the delta side (see Figure 6-116).
• In the case of auto transformers and transformers grounded on both sides in the star-star connection,
measurement through the transformer is possible. Here, distance protection for lines can be used
without any problems.
[dw_ratio-2pol-ifault, 2, en_US]
[dw_ratio-1pol-fault, 2, en_US]
The changed measurand mapping also leads to a different impedance mapping. Figure 6-117 and
Figure 6-118 show, for example, for a 2-phase or 1-phase short circuit on the star side, the resulting phasors
on the delta side. To simplify it, the transformer ratio was assumed to be 1.
[dw_imp-2pol-short-ciruit, 2, en_US]
[dw_imp-1pol-short-ciruit, 2, en_US]
With a 2-phase short circuit, the phase-to-ground impedance of the phase corresponds to the double phase
current of the actual fault impedance via the transformer. The impedance is correctly measured. All other
impedances are measured as considerably larger. Subtracting the currents results in an infinite impedance
measured value for the C-A loop.
A 1-phase ground fault results in the smallest impedance value based on the calculation with phase-to-phase
voltages (in the example, C-A). Because the zero-sequence system cannot be transferred via a star-delta trans-
former, an impedance is measured that is too large by the amount of the zero-sequence impedances (trans-
former, line). The actual fault location is seen as being farther away.
With a 3-phase short circuit, the impedance measurement for all measuring loops is correct.
The following table summarizes the results of the impedance measurement for a star-delta transformer:
Table 6-8 Fault Mapping and Measuring Errors during the Impedance Measurement of a Star-Delta
Transformer
[lo_dis-impedance-protection, 3, en_US]
[lo_block_imp, 3, en_US]
Loop Selection
The function Impedance protection can be used in electrical power systems and plants with different neutral
points. With the Loop selection parameter, you control which parameters influence the loop release.
In power systems with effective neutral point grounding – solidly or low-impedance grounded neutral point –
all impedance loops (phase-to-ground and phase-to-phase loops) can work parallel to each other. When all
loops are working in parallel, the loop release is controlled by the parameter Min. phase-current
thresh (see following figure).
Figure 6-121 Effective Parameter for Loop Release for All Loops
In power systems with a non-effective neutral point grounding – isolated, grounded, or high-impedance
grounded neutral point – the control for the loop selection is necessary to avoid an overfunction, for example,
a ground fault. The loop selection is controlled by the Current-dependent parameter. The following figure
shows which parameter controls the loop selection.
In case of a ground fault, the voltage collapsed – ideally to 0 – and the phase-to-ground loop measures either
a small impedance or 0 Ω. The phase-selective overcurrent detection releases the loops (parameter Overcur-
rent threshold). The undervoltage seal-in (parameter Undervoltage seal in) keeps the overcurrent
erect. The undervoltage seal-in is necessary for use in power plants when an exciting transformer is connected
to the generator bus. During a near short circuit, the excitation voltage collapses and results in a decreased
synchronous generated voltage. Thereby the fault current sinks below the rated current and thereby the
current threshold value (parameter Overcurrent threshold). The parameter V-seal-in threshold
monitors the positive-sequence voltage. The undervoltage seal-in drops out when the threshold value V-
seal-in threshold is topped or the undervoltage seal-in time (parameter Duration of V-seal-in
time) runs out.
• In the event of 2-phase pickup, an associated phase-to-phase loop with the applicable phase-to-phase
voltage is used for the impedance calculation.
• In the event of a 3-phase pickup, the loop selection is dependent on the ratio of the current amplitudes of
the phases to one another.
The following table shows the measuring-loop selection:
Pickup Measuring Loops
1-phase A Phase-to-ground A-gnd
B B-gnd
C C-gnd
2-phase A, B Phase-to-phase A-B
B, C B-C
C, A C-A
Impedance Measurement
From the sampled values of the phase currents and the phase-to-ground voltages, the fundamental phasors
are determined per period using an FIR filter (FIR = Finite Impulse Response). The impedances are calculated
from the fundamental phasors. By using the frequency-tracking sampled values, the impedance is measured
using another frequency range. This is advantageous for island networks or block-unit power plants, for
example, for start-up processes.
There is an impedance measuring element available for each of the 6 possible phase loops A-gnd, B-gnd, C-
gnd, A-B, B-C, C-A. If another fault occurs during analysis, the impedances are calculated using the current
cyclical measurands. The analysis thus always works with the measurands of the current fault condition.
The impedance for phase-to-phase loops is calculated as follows:
[fo_loop_ZLL, 2, en_US]
[fo_loop_ZLE, 2, en_US]
Mode of Operation
If the phase currents exceed the set Min. phase-current thresh. All released impedance loops are
calculated.
To release phase-to-ground loops, it is sufficient if the corresponding phase current exceeds the Min.
phase-current thresh. For phase-to-phase loops, both phase currents and the loop current must exceed
the Min. phase-current thresh.
There is no special ground-fault detection, such as distance protection for lines.
If the released impedance loop(s) lie in one zone, the Impedance protection function generates a pickup indi-
cation with loop information. At the same time, a pickup indication in the picked up zone occurs with specifi-
cation of the relevant phase and direction. The direction is subsequently determined for all picked up impe-
dance loops and the associated time delay started. The output logic processes the pickup and trip signals of
the zones and forms the pickup and trip signals of the function.
Direction Determination
The direction is determined either using a stored prefault voltage or negative-sequence system variables. If the
measured negative-sequence voltage or the negative-sequence current exceed 10 % of the rated values of the
device, the variables of the negative-sequence system are used exclusively. For the direction decision, the
angle between the negative-sequence current I2 and the negative-sequence voltage V2 is evaluated.
Figure 6-123 shows the defined directional areas on impedance level.
For 3-phase symmetrical short circuits, there is no negative-sequence system. In this case, the memory voltage
is used. If the memory voltage is not available either, for example when switching onto a fault, all zones –
regardless of their parameterized direction – pick up and generate an operate indication after the time delay
has expired.
Optionally, you can link the Impedance protection function with the Instantaneous tripping at switch onto
fault function (see chapter 6.18.4 Application and Setting Notes). This enables the selected Impedance-
protection zones to trip without delay.
[dw_ritgkl, 2, en_US]
Inrush-Current Detection
If the device is equipped with the Inrush-current detection function, you can stabilize the zones against trip-
ping due to transformer inrush currents.
Impedance Polygon
The quadrilateral operate curve (impedance polygon) in the zone is a rectangle in the R-X plane. The polygon
is defined by the parameters X reach (ph-g), X reach (ph-ph), R reach (ph-g), and R reach
(ph-ph) and the Directional mode. This means that, in special situations, a different setting is possible
for phase-to-phase and phase-to-ground loops.
To stabilize the quadrilateral limits, the characteristics have a hysteresis of 5 %. If the fault impedance lies
within a polygon, the limits are increased by 5 % in all directions. The following figure shows an example with
2 non-directional zones:
[dw_klpoly-impedanceprot, 2, en_US]
Sample Configuration
The following figure is an example of how the Impedance protection function is used at a feeder point in a
medium-voltage power system.
[dw_example-protection, 1, en_US]
The medium-voltage power system is fed on the high-voltage side with a YNd5 transformer. In addition, there
is an infeed that enables energy recovery to faults occurring on the high-voltage side.
The protection device installed on the delta side of the transformer functions as distance protection, which is
the backup protection for the medium-voltage power system.
In addition to distance protection, the protection device on the delta side functions as impedance protection,
which looks in the transformer direction. The power system on the high-voltage side is a meshed system and
also contains distance protection devices.
In the following, you can find recommendations for the protection setting values and a view of the setting
problems. Figure 6-126 shows a possible setting approach.
Zone TZ 1 should be coordinated with the protection system and delayed by approx. 100 ms. The delay makes
preferred tripping possible due to the differential protection and a dropout of the zone.
Zone TZ 2 is intended as a directional reserve stage, whose time must, without fail, be coordinated with the
protection system. At the same time, this stage can be used if, when switching the transformer on, it switches
onto a fault.
In exchange, the function Instantaneous tripping at switch onto fault must be present and set accordingly.
[dw_config-staffel, 1, en_US]
Line (transformed to
20 kV):
The sample calculation clearly shows that the line reactance can be disregarded compared to transformer
reactance due to the quadratic transformation.
To avoid overfunction, select the following setting values for the 1st zone (TZ 1)
X1 = 0.9 ⋅ XTr = 0.9 ⋅ 0.96 Ω = 0.864 Ω
For the 2nd zone, select the double transformer impedance and set the time delay correspondingly high.
X2 = 2 ⋅ XTr = 2 ⋅ 0.96 Ω = 1.92 Ω.
With the selected setting, Zone TZ 1 does not protect the transformer completely, especially if you take into
account the incorrect measurement for a 1-phase short circuit.
If you want to achieve a reliable tripping for all fault situations (see Table 6-8), the setting value must extend
far beyond the transformer. One possible strategy for the time grading is a setting value of approx. 1.5 XTr.
You must guarantee the selectivity using the Time criterion. The following figure shows the time-grading
chart:
[dw_grading-x1-xtr, 3, en_US]
The zone range in the R direction must take into account the fault resistance on the fault location. The fault
resistance is added to the impedance of the fault loop as an additional effective resistance. This fault resis-
tance is, for example, the arc resistance or the dissipation resistance of ground phases. For the zone range in
the R direction, you do not have to take the fault resistance on the upper-voltage side and the line resistance
into account. These are also divided by the transformer-ratio quadrant and can be mostly disregarded.
However, fault resistances on the upper-voltage side during high-current feed on the upper-voltage side also
impact the reactance and resistance measurement on the undervoltage side. This impact is unavoidable and
can result in a short circuit with fault resistance on the upper-voltage side not being detected by the under-
voltage side until the high-current feed on the upper-voltage side is cleared. Do not set the reserve resistance
any larger than necessary. The setting can be adjusted to the maximum load in the direction of the line section
to be protected, in other words, in the transformer direction. The setting value for the R range must be lower
than the resistance under maximum load conditions (RL max). For a sufficient distance to the load range,
Siemens recommends a value of about 20 % to 50 % RL max. This means an incorrect measurement is avoided
by the apparent impedances (seeFigure 6-117 and Figure 6-118).
NOTE
i The parameter (_:2311:102) Loop selection = All loops is visible only if you set the parameter
Min. phase-current thresh.
EXAMPLE:
The rated generator current is calculated as:
Taking into account the transformer ratios, the secondary setting value is calculated as follows:
EXAMPLE:
For the calculation, the data from Table 6-9 apply.
X range = 150 %
The primary setting value is calculated as follows:
Xprim = 150 %/100 % ⋅ ZKT = 1.5 ⋅ 0.96 Ω = 1.44 Ω (primary)
Taking into account the transformer ratios, the secondary setting value is calculated as follows:
[fo_Xrange_sec, 2, en_US]
EXAMPLE:
For the calculation, the data from Table 6-9 apply.
The rated transformer current is assumed as the rated load current. The current is 1443 A on the 20 kV side.
The smallest impedance measured under maximum load conditions (Zmax) is calculated as follows assuming
10 % undervoltage and 10 % overcurrent:
[fo_Zmax_trafo_RLE, 2, en_US]
For the R reach, 20 % ⋅ Zmax is specified. This means the primary setting value of the R reach (ph-g)
parameter is calculated as follows:
R reach (ph-g) = 0.2 ⋅ 6.55 Ω = 1.31 Ω
This value corresponds to approx. the X value so that you can select, as a practical setting, R range = X range.
Taking into account the transformer ratios, the secondary setting value is calculated as follows:
[fo_r_range_sek, 2, en_US]
EXAMPLE:
For the calculation, the data from Table 6-9 apply.
Set the range for phase-to-phase loops just like for phase-to-ground loops. This results in the following setting
values:
R reach (ph-ph) = R reach (ph-g) = 1.45 Ω (primary)
R reach (ph-ph) = R reach (ph-g) = 10.9 Ω (secondary)
6.18.5 Settings
• Detects arcs in air-insulated switchgear parts without delay and in a fail-safe way
The Arc protection function can be added to function groups that provide current measured values.
The Arc protection function consists of the following blocks.
• General
• 3 stages
[dw_structure_arcprot, 2, en_US]
[lo_fb0_arcprot, 3, en_US]
[lo_stage_arcprotection, 2, en_US]
The Arc protection function uses a locally connected optical arc sensor or an external trip initiation by other
devices in order to detect arcs.
NOTE
i Install the arc sensors inside the switchgear in such a way that they are not hidden behind other system
components!
Shadowing of the arc sensors must be avoided!
NOTE
i Once an optical sensor has detected an arc, you must replace the affected optical sensor!
Within the Arc protection function, you can use a fast current-flow criterion as an additional release criterion.
The parameters for the current-flow criterion can be found in the General block. For each stage, you can
select individually whether the current-flow criterion must be evaluated as well.
NOTE
i If using the current-flow criterion in addition to the light, prevent a potential overfunction caused by the
suddenly occurring light signal.
If you use the current-flow criterion, arcs are typically detected in 4 ms!
Self Monitoring
The Arc protection function uses a self-monitoring circuit. This circuit monitors the optical arc sensors and the
fiber-optic cables. The arc-protection module uses the fiber-optic cable to send a cyclic test signal (light) to the
arc sensors. If the channel is operating properly, the test signal is sent back to the arc protection module. If the
test signal is not returned to the arc protection module, the indication channel # Sensor failure is
generated.
If the self-monitoring function detects a fault, the indication Health is set to Alarm and the stage/function is
blocked.
Go to General under the function Arc protection and set the following parameters. The setting values apply
to all stages.
NOTE
i If you set the parameter CT connection = 3-phase, 2 primary CT for the 3-phase current meas-
uring point, the parameter Threshold 3I0> has no effect.
Parameter: Sensor
Parameter: Channel
6.19.6 Settings
6.19.8 Application Example for Arc Protection with Point Sensors in Operating Mode:
Light Only
6.19.8.1 Description
Overview
The example describes the Arc protection function in a medium-voltage switchgear with one infeed and
2 feeders. The Arc protection function operates with the Operating mode = light only.
The following items are considered in the example below:
• Connecting the optical point sensors to the protection devices in the feeders and the infeed
• Number of necessary stages of the functions in the protection devices of the feeders and the infeed
• Setting notes about the selected parameters in the stages of the function
The following figure shows the arrangement and the connection of the optical point sensors:
[dw_arcprot-light-only, 2, en_US]
Figure 6-131 Layout and Connection of the Optical Point Sensors (Operating Mode = Light only)
• The circuit breaker of the infeed must be switched off. This ensures that the arcs in the busbar compart-
ments of the infeed and the feeders or in the circuit-breaker compartment of the feeders are off.
Install the optical point sensors in the busbar compartments (BB compartment) of the infeed and feeders.
Install additional optical point sensors in the circuit-breaker compartment (CB compartment) of the
feeders. Connect all optical point sensors to the protection device of the infeed.
• The optical point sensors in the cable-connection compartment of the feeders detect arcs in this compart-
ment. Install one optical point sensor in the cable-connection compartment of the feeders and connect it
to the protection device of the feeder. This allows for the selective clearing of arcs inside the cable-
connection compartment.
Due to the pressure waves that occur during the formation of an arc, partitions can deform and cause
undesirable light influences in adjacent compartments. This can result in a non-selective tripping.
• If there is an arc in the circuit-breaker compartment and in the cable-connection compartment of the
infeed, the superordinate protection device must switch off.
NOTE
i If the Arc protection function operates in Operating mode = light only, the effects of external light
can result in non-selective tripping.
NOTE
i It must be considered that the number of arc protection modules connected to the device depends on the
hardware configuration of the device.
When using modular devices, a maximum of 15 sensors can be connected. If using non-modular devices, a
maximum of 6 sensors (3 sensors per module) can be connected.
General Notes
• Connect one optical point sensor from the cable-connection compartment in feeder 1 to the protection
device in feeder 1. Arcs in the cable-connection compartment are cleared selectively by the circuit
breaker in feeder 1.
• Connect one optical point sensor from the cable-connection compartment in feeder 2 to the protection
device in feeder 2. Arcs in the cable-connection are cleared selectively by the circuit breaker in feeder 2.
• Connect optical point sensors from all busbar compartments and all circuit-breaker compartments of
feeders 1 and 2 to the protection device in the infeed. Arcs in these compartments are detected and
cleared by the device in the infeed.
The parameters in block General are not relevant since the Operating mode = light only.
6.19.9 Application Example for Arc Protection with Point Sensors in Operating Mode:
Light and Current
6.19.9.1 Description
Overview
The example describes the Arc protection function in a medium-voltage switchgear with one infeed and 2
feeders. The Arc protection function operates with the Operating mode = current and light. In the
example, all arcs are detected by the protection device in the infeed.
The following items are considered in the example:
• Connecting the optical point sensors to the protection devices in the feeders and the infeed
• Number of necessary stages of the functions in the protection devices of the feeders and the infeed
[dw_light-and-current, 2, en_US]
Figure 6-132 Layout and Connection of the Optical Point Sensors (Operating Mode = Current and Light)
• The current-flow criterion offers additional security to prevent unwanted tripping caused by sudden light
influences.
Depending on the arc location in the cable-connection compartment of the feeder, it is not always
possible to measure the current. If an arc is detected in the cable-connection compartment of the feeder,
the current will therefore be evaluated in the infeed.
• Install the optical point sensors in the busbar compartment, the circuit-breaker compartment, and the
cable-connection compartment of the feeders as well as the busbar compartment of the infeed. Connect
the optical point sensors to the protection device in the infeed.
• The protection device in the infeed clears all arcs in the busbar compartment, the circuit-breaker
compartment, and the cable-connection compartment of feeder 1 and 2. Furthermore, the protection
device clears arcs in the busbar compartment of the infeed.
• If the optical point sensors in the busbar compartment, the circuit-breaker compartment, and the cable-
connection compartment of the feeders, or in the busbar compartment of the infeed detect an arc, the
protection device in the infeed evaluates the current as well.
• If an arc occurs in the circuit-breaker compartment and in the cable-connection compartment of the
infeed, the superordinate protection device must trip.
NOTE
i If the Arc protection function operates with the Operating mode = current and light, the addi-
tional current-flow criterion prevents unwanted tripping caused by external light influences.
NOTE
i This application example requires the connection of several optical point sensors to a single protection
device. It must be considered that the number of arc-protection modules that are connected to the device
depends on the hardware configuration of the device.
When using modular devices, a maximum of 15 sensors can be connected. If you use non-modular devices,
a maximum of 6 sensors (3 sensors per module) can be connected.
General Notes
• Connect the optical point sensors from the busbar compartment, the circuit-breaker compartment, and
the cable-connection compartment of feeders 1 and 2 to the protection device in the infeed. Arcs in the
busbar compartment, the circuit-breaker compartment and the cable-connection compartment of
feeders 1 and 2 are detected and cleared by the device in the infeed.
• Connect an optical point sensor from the busbar compartment in the infeed to the protection device in
the infeed. Arcs in the busbar compartment of the infeed are cleared selectively by the circuit breaker in
the infeed.
6.19.10 Application Example for Arc Protection with Point Sensors via External Trip
Initiation
6.19.10.1 Description
Overview
The example describes the Arc protection function in a medium-voltage switchgear with one infeed and
2 feeders. The stages of the Arc protection function are triggered by External trip initiation.
The following items are considered in the example below:
• Connecting the optical point sensors to the protection devices in the feeders and the infeed
• Number of necessary stages of the functions in the protection devices of the feeders and the infeed
• Setting notes about the selected parameters in the stages of the function
[dw_arcprot-extern-input, 3, en_US]
• Install the optical point sensors in the busbar compartment, the circuit-breaker compartment, and the
cable-connection compartment of the feeder and the infeed. Connect the optical point sensors to the
respective protection device in the feeder and infeed.
• If the optical point sensors detect an arc in the busbar compartment or the circuit-breaker compartment
of the feeders, the Light detected indication is sent via binary inputs/outputs, a protection interface,
or IEC 61850 GOOSE to the protection device in the infeed. Then, the protection device in the infeed
evaluates the current as well. If the measured current exceeds the thresholds Threshold I> and/or
Threshold 3I0>, the protection device in the infeed switches off the malfunction.
You can find detailed information in chapter 6.19.10.2 Application and Setting Notes
• Arcs in the cable-connection compartment of the feeders can also be switched off selectively by the
protection device of the affected feeder. To do this, the Current detected pickup indication from the
infeed unit must be sent to the appropriate protection device in the feeder.
• If an arc occurs in the circuit-breaker compartment and in the cable-connection compartment of the
infeed, the superordinate protection device trips.
NOTE
i If the Arc protection function operates via the External trip initiation, only 3 optical point
sensors are required per feeder protection device in order to detect the arcs (only one arc-protection
module).
The number of GOOSE messages is not limited. Therefore, the number of feeders is not limited, and the
protection of complex systems is feasible.
General Notes:
• Install the optical point sensors in the busbar compartment, the circuit-breaker compartment, and the
cable-connection compartment of the feeders and the infeed to the respective protection devices.
• Arcs in the busbar compartment and the circuit-breaker compartment of the feeders must be switched
off by the protection device in the infeed. To do this, the protection devices in the feeder device must
send the indication Light detected to the infeed device. Use the binary inputs/outputs, a protection
interface, or IEC 61850 GOOSE.
The protection device in the infeed evaluates the current. If the measured current exceeds the
Threshold I> and/or Threshold 3I0> threshold values, the protection device in the infeed switches
off faults on the busbar and the circuit-breaker compartment of the feeders.
Connect the signals over 4 stages, using the external trip initiation or a CFC chart.
• Arcs in the cable-connection compartment of the feeders are switched off locally. The protection device
in the infeed evaluates the current. If the measured current exceeds the threshold values Threshold
I> and/or Threshold 3I0>, the Current detected indication is sent to the protection devices in
the feeders. If, at the same time, an optical sensor in a cable-connection compartment detects light, the
protection device trips in the corresponding feeder.
6.19.11 Application Example for Arc Protection with a Line Sensor in Operating Mode:
Light and Current
6.19.11.1 Description
Overview
The example describes the Arc protection function in a medium-voltage switchgear with 1 infeed and
2 feeders. The Arc protection function operates with the Operating mode = current and light. In the
example, all arcs are detected by the protection device in the infeed.
The following items are considered in the example below:
• Setting notes about the selected parameters in the stages of the function
Figure 6-134 Layout and Connection of the Optical Line Sensors (Operating Mode = Current and Light)
• The current-flow criterion offers additional protection to prevent unwanted tripping caused by the
sudden effects of light.
• Figure 6-134 shows how the optical line sensors should be routed. Start in the infeed busbar compart-
ment and route the optical line sensor along the busbar and back again to the protection device in the
infeed. Connect the optical line sensor to the protection device in the infeed.
• Depending on the routing options in the control cabinet, you can also route the optical line sensor
through the circuit-breaker and cable-connection compartments of the feeders.
If this is not possible, you can detect arcs in these compartments using point sensors. For more detailed
information, see chapters 6.19.8 Application Example for Arc Protection with Point Sensors in Operating
Mode: Light Only and 6.19.9 Application Example for Arc Protection with Point Sensors in Operating
Mode: Light and Current.
• If an arc occurs in the circuit-breaker compartment and in the cable-connection compartment of the
infeed, the superordinate protection device will shut off.
NOTE
i If the Arc protection function operates with the Operating mode = current and light, the addi-
tional current-flow criterion will prevent unwanted tripping caused by external light effects.
NOTE
i Note that the number of arc protection modules that are connected to the device depend on the hardware
configuration of the equipment.
When using modular equipment, a maximum of 15 sensors can be connected. If using non-modular equip-
ment, a maximum of 6 sensors (3 sensors per module) can be connected.
Depending on the use case, you can combine point and line sensors.
• Parameter: Channel = Arc mod. 1 channel 1 (Stage 1) → Busbar compartment supervision (infeed,
feeder 1, feeder 2)
You can find more information about the settings of the parameters Threshold I> and Threshold 3I0>
in chapter 6.19.4 Application and Setting Notes – General Settings.
• Generates a blocking signal for protection functions that protect the transformer (protected object) or for
protection functions that are affected in undesirable ways when transformers are switched on
[dw_irsh01, 1, en_US]
[lo_inru_02, 3, en_US]
Harmonic Analysis
For this method of measurement, the content of the 2nd harmonic and the fundamental component (1st
harmonic) are determined for each of the phase currents IA, IB, and IC and the quotient I2nd harm / I1st harm is
formed from this. If this quotient exceeds the set threshold value, a phase-selective signal is issued.
If 75 % of the set threshold value is exceeded, this leads to a pickup reset (dropout ratio = 0.75).
[lo_inrush_10, 1, en_US]
[dw_inrush_03, 1, en_US]
The following figure shows the logic diagram of the CWA method.
From the present fundamental-component current (1st harmonic), the threshold value for identification of the
flat areas is derived via an internal factor.
[lo_inrush_05, 1, en_US]
[lo_inrush_12, 2, en_US]
NOTE
i Make sure that at least one process is activated. Siemens recommends retaining the advised setting values.
Parameter: Cross-blocking
6.20.1.5 Settings
• Detects the content of 2nd harmonics in the neutral-point phase current IN or in the calculated zero-
sequence current 3I0.
• Generates a blocking signal for protection functions that use the neutral-point phase current IN or the
calculated zero-sequence current 3I0 as a measured value
harmonic ground detection function must be in the same function group as the Inrush-current detection
function and the functions that are to be blocked.
Logic
[lo_2harm_detec_gnd, 2, en_US]
Harmonic Analysis
For this method of measurement, the content of the 2nd harmonic and the fundamental component (1st
harmonic) is determined for the neutral-point phase current IN or the calculated zero-sequence current 3I0
and the quotient I2nd harm/I1st harm is formed from this. If this quotient exceeds the set threshold value, a
blocking signal is issued.
NOTE
i During a transformer saturation, the high content of the 2nd harmonic in the ground current must not lead
to a pickup of the function.
NOTE
i If the ground current is measured in case of a sensitive transformer and the measured value exceeds the
saturation threshold of 1.6 ⋅ IN, the function switches to the calculated 3I0 value.
[lo_harmon-analyse, 1, en_US]
6.20.2.5 Settings
• Generation of an indication when the measurands change by more than a configured threshold value
from one system cycle to the next.
The function for detecting jumps in the phase or zero-sequence voltage is an additional function used for indi-
cation purposes or for further processing in user-specific CFC logics. Pick up of the function therefore neither
opens a separate fault in the fault log nor generates an operate indication.
The Voltage-jump detection function is used in protection function groups based on voltage measurement. It
can be instantiated multiple times.
[dw_struku, 1, en_US]
Voltage-jump detection operates directly with the sampled values without numeric filtering. This provides very
short response times to sudden changes in the voltage. The method used is not sensitive to slow changes of
amplitude or frequency.
By using a configurable selection of measured values, you can select from phase-to-ground voltages, phase-to-
phase voltages or the zero-sequence voltage. Voltage-jump detection is phase-selective.
The difference from the previous sampled value of a system cycle is calculated for each sampled value. The
rectified average is then determined for a ½ system cycle from this differential signal Δv(t). The rectified
average for sinusoidal measurands is then converted to a RMS value ΔV by subsequent multiplication by 1.11.
The resultant measurand ΔV is then compared with the threshold value.
If the parameter (_:101) Threshold is exceeded, the output indication Jump is generated. If the measured
value is set to phase-to-phase, the sudden change in voltage is signaled selectively for the individual meas-
uring elements that have picked up (Jump VAB, Jump VBC or Jump VCA). If you have selected the phase-to-
phase or phase-to-ground voltages for measurement, the output indication data type used includes the sepa-
rate phase information. If you have selected the zero-sequence voltage for measurement, the output indica-
tion data type used includes the N information. If the voltage-jump detection responds (ΔVLimit), the general
information is generated in the output indication in all cases.
Dropout occurs with a dynamically increased threshold value ΔULimit in accordance with the information in
Figure 6-144. Dynamic increase of the dropout threshold value achieves optimally short dropout times.
A timing element is added to the indication Jump. The element generates a pulse from this. The length of this
pulse can be set using the parameter (_:102) Minimum pulse length. This gives the output indication
Pulse a reliable minimum size. If you activate the binary input >Pulse extension, you can prolong the
pulse duration even further. If the binary input >Pulse extension has been activated, the indication
Pulse drops off when the configured time has elapsed and the falling edge of the binary input is detected. If
the measured value is set to phase-to-phase, the pulse duration is signaled selectively for the individual meas-
uring elements that have picked up (Pulse VAB, Pulse VBC or Pulse VCA).
Logic
[lo_jump_uu, 3, en_US]
Parameter: Threshold
6.22.5 Settings
• Provide the ability to switchover the voltage measuring points to be applied, if various voltage measuring
points are connected to the voltage interface of the function group
• Select the correct voltage based on the switch position of the plant
If more than one voltage measuring points are connected to the same voltage interface of the function group,
use the Voltage measuring-point selection function block in the function group to select the correct voltage
based on the switch position of the plant.
The Voltage measuring-point selection is a common functionality for the function groups of the protected
objects.
You find detailed description in the device manual Distance Protection, Line Differential Protection, and
Breaker Management for 1-Pole and 3-Pole Tripping 7SA87, 7SD87, 7SL87, 7VK87.
7.1 Introduction
7.1.1 Overview
The SIPROTEC 5 series of devices offers powerful command processing capability as well as additional func-
tions that are needed when serving as bay controllers for the substation automation technology or when
providing combi-protection. The object model for the devices is based on the IEC 61850 standard, making the
SIPROTEC 5 series of devices ideally suited for use in systems employing the IEC 61850 communication
protocol. In view of the function blocks necessary for the control functions, other logs are also used.
The concept of so-called controllables is based on the data model described in IEC 61850. Controllables are
objects that can be controlled, such as a switch with feedback. The model of a circuit breaker, for example,
contains controllables. The controllables are identifiable by their last letter C of the data type (for example,
DPC = Double Point Controllable/Double Command with feedback).
[sc_control, 1, en_US]
The trip, opening, and the close commands are connected to the relays. For the trip command, a choice
between saved and unsaved output is possible. The position is connected with 2 binary inputs (double-point
indication). In addition, signals are available that display the current state of the switch (not selected, off, on,
intermediate position, disturbed position). These signals can be queried in CFC, for example, in order to
build interlocking conditions.
Control Models
You can set the operating mode of the controllables by selecting the control model.
[dw_steuer, 2, en_US]
The figure shows the control models (right) with the respective control mechanisms (center). The standard
control model for a switching command in an IEC 61850 compliant system is SBO with feedback monitoring
(SBO w. enh. security). This control model is the default setting for newly created switching devices.
7.2.1 Overview
The following switching devices are located in the DIGSI 5 library under the Circuit breaker 1-/3-pole and the
Circuit breaker 3-pole function groups.
[sc_cb13sw, 1, en_US]
[sc_cb3swi, 1, en_US]
NOTE
i The offered switching device disconnector (only status indication) cannot be controlled in the busbar
protection device.
[sc_trnosw, 1, en_US]
[dw_breake, 1, en_US]
The circuit breaker in DIGSI 5 is linked with the binary inputs that acquire the switch position via information
routing. The circuit breaker in DIGSI 5 is also linked with the binary outputs that issue the switching
commands.
The Circuit-breaker switching device is available in the DIGSI 5 library in 2 different variants:
For the setting values of the parameter, refer to 7.2.2.2 Application and Setting Notes.
Table 7-2 Setting Options of the Controllable Command with Feedback in the Control Function
Block of the Circuit Breaker.
25 First click Position and then click the Details key in the Properties window (below).
Table 7-3 Setting Options of the Controllable Position in the Circuit-Breaker Function Block (Chatter
Blocking)
Table 7-4 Additional Settings in the Device Settings Having Effects on the Circuit Breaker
The inputs and outputs as well as the setting options of the Circuit-breaker and Control function blocks are
described in the next section (refer to 7.2.2.3 Connection Variants of the Circuit Breaker).
Interlocking
The Interlocking function block generates the releases for switchgear interlocking protection. The actual
interlocking conditions are deposited in CFC.
Circuit Breaker
The Circuit-breaker function block in the SIPROTEC 5 device represents the physical switch device. The task of
the circuit breaker is to replicate the switch position from the status of the binary inputs.
The following figure shows the logical inputs and outputs of the Circuit-breaker function block.
[dw_func_ls, 2, en_US]
Figure 7-6 Logical Inputs and Outputs of the Circuit-Breaker Function Blocks
Table 7-5 and Table 7-6 list the inputs and outputs with a description of their function and type. For inputs,
the effect of Quality = invalid on the value of the signal is described.
EXAMPLE
If the signal >Ready has the Quality = invalid, then the value is set to cleared. In problematic operating
states, the circuit breaker should signal that it is not ready for an Off-On-Off cycle.
If the quality of the input signal assumes the status Quality = invalid, then the standby status (EHealth) of the
Circuit-breaker function block is set to Warning.
Control
It is the task of the controls to execute command checks and establish communication between the command
source and the circuit breaker. Using the control settings, you specify how the commands are to be processed.
Through the function SBO (Select Before Operate, reservation26), the switching device is reserved prior to the
actual switching operation, thus it remains locked for additional commands. Feedback monitoring provides
information about the initiator of the command while the command is in process, that means, informing
whether or not the command was implemented successfully. These 2 options can be selected individually in
the selection of the control model, so that 4 combinations in total are available (see the following table).
The control makes the following settings available (see next table).
Parameters Default Setting Possible Parameter Values
(_:4201:101) Control model SBO w. enh. direct w. normal secur.
security27 SBO w. normal secur.
direct w. enh. security
SBO w. enh. security
(_:4201:102) SBO time-out 30.00 s 0.01 s to 1800 s
(Increment: 0.01 s)
(_:4201:103) Feedback monitoring time 1.00 s 0.01 s to 1800 s
(Increment: 0.01 s)
26 In the IEC 61850 standard, reservation is described as Select before Operate (SBO).
27 This default setting is the standard control model for a switching command in an IEC 61850-compliant system.
The following figure shows the logical inputs and outputs of the Control function block.
[dw_steue1, 1, en_US]
Figure 7-7 Logical Inputs and Outputs of the Control Function Block
In the information routing of DIGSI 5, you may select a function key as a possible command source. In addi-
tion, it is displayed here if the command is activated by CFC. The logging is routed here.
NOTE
i If not further described, in the following figures and tables, the 1/3-pole circuit breaker is always shown.
For a circuit breaker with only 3-poles, the following phase-selective features are omitted:
[dw_3-pole_ls, 1, en_US]
1-Pole Triggering
[dw_1-pole, 1, en_US]
[sc_ro1pol, 1, en_US]
You can select the contacts for On and Off as desired. They need not necessarily be next to one another. The
letter U represents an unlatched command. Alternatively, TL (latched tripping) can be selected.
1.5-Pole Triggering
[dw_5-pole, 1, en_US]
[sc_r15pol, 1, en_US]
2-Pole Triggering
[dw_2-pole-open, 1, en_US]
[sc_ro2pol, 1, en_US]
NOTE
i The wiring of the Circuit-breaker function group with binary inputs and binary outputs occurs once per
device , see 5.3.6.1 Overview .
The control function in this type switches all 3 poles on or off simultaneously.
The close command is always 3-pole. Optionally, only the open poles are closed.
[dw_1polls, 1, en_US]
For the circuit breaker with 1-pole triggering, triggering takes place via one relay per phase for the trip
command and via a 4th relay for the close command (see next figure).
[dw_1panls, 1, en_US]
[sc_rang_1p_cb13pz, 1, en_US]
In the previous figure, the switch is connected 1-pole. The protection trip command is routed for the 3 phases
(Trip/open cmd. 3-pole). The control always switches off the 3 poles of the switch. In addition, the 3 U
(Unlatched) routings of the trip and open command are set to 3-pole. This routing is also used by protection
functions that trip 3 poles. The close command is issued simultaneously for all 3 phases.
[dw_trip-command_between_1p-3p, 1, en_US]
[sc_ra13po, 1, en_US]
[sc_ra3po, 1, en_US]
You can find the meaning of the abbreviations in Table 7-8 and Table 7-9.
The indication Command active can also be routed to a binary output. This binary output is always active if
either a close or trip command is pending, or the switching device was selected by the command control.
• Control Functionality
7.2.2.5 Settings
Switching sequences may be running inside the device that switch the switchgear automatically in a prespeci-
fied sequence.
A switching sequence consists of a special function block Switching sequence (Swi. seq.) from the DIGSI 5
Library and the project-specific list of the switching commands that are generated in the CFC.
The function block Switching sequence is located in folder User-defined functions in the DIGSI 5 Library.
[sc_udeffb, 1, en_US]
These function blocks can be used in the information matrix on the highest level (level of the function groups)
or in a user-defined function group.
One Switching sequence function block is used per switching sequence. The function block is the interface
for controlling and monitoring the condition of the CFC switching sequence. The task of the function block is
to verify the relative conditions for control commands, for example, switching authority, interlocking condi-
tions, etc. You can connect the signals of the function block with the CFC chart. They start and stop the
switching sequence and provide data about the status of the switching sequence (see Figure 7-21). The CFC
chart is used to activate the switching device that must be switched. The CFC blocks define, among other
things, the switching devices that must be switched.
[dw_swseq1, 1, en_US]
• Input >Start during rising edge, for example, via binary input
• Controllable Start for the start via a communication protocol, for example, IEC 61850, T103, or DNP
• Input >Cancel during rising edge, for example, via binary input
• Controllable Cancel for the cancelation via a communication protocol, for example, IEC 61850, T103, or
DNP
On-Site Operation
If at least one Switching sequence function block is used in the device, a new Switching sequences entry is
shown in the first line of the Control menu. If this menu item is selected, an overview of all switching
sequences and the current status will be displayed (see Figure 7-22, example with 2 switching sequences).
You can start or cancel the switching sequences from this menu.
Figure 7-22
Overview of the Switching Sequences on the Device Display
The function block offers similar settings to the Control function block of a circuit breaker or disconnector (see
chapter 7.2.1 Overview).
[sc_ccs4pa, 1, en_US]
Information
The Switching sequence function block provides the following data:
[sc_infof1, 1, en_US]
In the Switching sequence function block, the interlocking is analog to the Interlocking function block and it
is possible to use it in the switching sequence:
• >Enable start: Connection to interlocking conditions (CFC) for the start of the entire switching
sequence. Not in effect in the non-interlocked switching mode.
• >Enable start (fixed): Non-revocable interlocking conditions for the start of the entire switching
sequence. In effect regardless of the switching mode.
If the time-out monitoring is activated (parameter Time-out monitoring), the process feedback must take
place via the inputs >Successful and >Failed. If the last switching command of the switching sequence
was executed successfully, the input >Successful usually is set. To do this, connect the feedback of the last
switching command from the CFC with this input of the function block during the device parameterization.
If a switching command fails, this feedback can be captured by the input >Failed. The active switching
sequence will be ended immediately and does not have to wait for a time-out.
The indication Execution signals the current state of the switching sequence. The events running,
canceled, failed, and successful are generated only while the time-out monitoring is activated. The
event Start Trigger is used to start the switching sequence in the CFC chart.
[dw_bspunt, 1, en_US]
The switching sequence C4 Off (Figure 7-26) should switch off feeder bay C4. The circuit breaker is opened;
followed by opening of one of the 2 busbar disconnectors.
[sc_ssc4as, 1, en_US]
Command Execution
As described in section Starting and Canceling a Switching Sequence, Page 715, the display page or the
Control menu can be used to start the switching sequence. The Start Trigger signal for indication
Execution is used to recognize the start and initiates the switching sequence by pickup of TRIG in the DPC-
DEF building block of circuit breaker QA1. Building blocks DPC-DEF and DPC-EXE are always used in pairs. The
DEF building block controls the type and nature of the command
• SELECT = Select switching device (2 = Select with a value suitable for the preset control model SBO w.
enh. security)
7.3.4 Settings
Before switching commands can be issued by the SIPROTEC 5 device, several steps are used to check the
command:
[sc_conf, 2, en_US]
• Settings 222222
• Switching 333333
• Switch./interl.check 444444
• Switch./switch.auth. 666666
If you have configured a device with key switches, the confirmation IDs for non-interlocked switching and
switching authority are not displayed or editable in DIGSI; the function is handled by the position of the key
switch.
To increase security, change these codes with DIGSI.
! DANGER
If the switching mode = non-interlocked, the switchgear interlocking protection is shut off.
Erroneous switching operations can lead to severe or fatal injuries.
² Ensure manually that all checks have been implemented.
In addition, you can set the switching mode directly with a binary input or CFC. Use the General function
block (see next figure).
[sc_moscha, 1, en_US]
The following table shows the effects of changing the switching mode to use command checks.
Switching Authority
The switching authority determines which command source is allowed. The following command sources are
possible:
• Local:
A switching command from the local control (cause-of-error source Local) is possible only if the
switching authority is set to Local and the device is capable of on-site operation. Setting the switching
authority to Local is typically accomplished with key switch S5 (Local/Remote). In this case, commands
from all other sources are rejected. If the switching authority is set to Local, the setting cannot be
changed remotely.
• DIGSI:
A switching command from DIGSI (connected via USB or Ethernet, cause-of-error source Maintenance) is
accepted only if the switching authority in the device is set to Remote. Once DIGSI has signed on the
device for command output, no commands from other command sources or a different DIGSI PC will be
executed.
• Station:
This switching authority level can be activated via a parameter in the General function block. A switching
command from the station level (cause-of-error source Station or Automatic station) is accepted if the
switching authority is set to Remote and the controllable Station switching authority is set. This is
accomplished by a command from the substation automation technology. Switching commands from the
device or from outside the station (cause-of-error source Local, Remote or Automatic remote) are
rejected.
Full support of the switching authority level is assured only when using the IEC 61850 protocol.
• Remote:
This switching authority level stands from remote control directly from the network control center or (if
the switching authority level Station is not activated) generally for Remote control. The cause-of-error
source is Automatic remote. Commands from this level are accepted if the switching authority is set to
Remote and the controllable Station switching authority is not set. Switching commands from the
device or from the station (cause-of-error source Local, Station or Automatic station) are rejected.
[sc_moscha, 1, en_US]
Figure 7-29 Display of Switching Authority and Switching Mode in Information Routing (in Function Block
General)
Sw. authority key/set and Sw.mode key/set indicate the current state of the key switch or parameter for
switching authority or switching mode and provide this information for further processing in the CFC. In the
CFC, for example, it is possible to set up an automatic routine to ensure that the switching authority is auto-
matically set to Local when the key switch is set to non-interlocked.
The following table shows the dependency of the switching mode on the key-switch position and the
switching authority. In the case of switching commands from Remote, the information on whether a locked
or non-interlocked switching should take place is also sent. For this reason, the position of the key switch is
irrelevant for the switching mode in these cases. The information in the table assumes that, in the case of
remote switching commands or those from the station, the switching mode is interlocked in each case.
Table 7-12 Dependency of the Switching Mode on the Key-Switch Position and Switching Authority
Switching Authority
Key Switch for Switching Mode Local Remote Station
Interlocked Interlocked Interlocked Interlocked
Not interlocked Non-interlocked Interlocked Interlocked
The signals shown in Figure 7-29 in DIGSI 5 information routing have the following relationship:
• In terms of switching authority and switching mode, the respective key switch position serves as the
input signal and the input signals in the matrix.
• The state of the switching authority and switching mode is indicated by corresponding output signals.
• The Switching authority and Switching mode functions link the input signals and in this way establish
the output signals (see Figure 7-30 and Figure 7-31).
[dw_authority, 1, en_US]
[dw_modsch, 1, en_US]
In the case of both functions, the input signals overwrite the state of the key switch. This allows external
inputs to also set the switching authority or switching mode, if desired (for instance, by querying an external
key switch).
The following additional settings are available for the switching authority:
[sc_BB_akt_hoh, 1, en_US]
Figure 7-32 How to Activate the Station Switching Authority and to Enable Several Switching-Authority
Levels
Table 7-13 Effect on Switching Authority when Several Switching-Authority Levels Are Enabled with/
without Activation of the Station Switching Authority
No Signed on – – DIGSI
The following table shows the result of the switching-authority check, based on the set switching authority
and the cause of the command. This overview represents a simplified normal case (no multiple command
sources when using Station and Remote).
• Specific sw.auth. valid for (for station/remote, only remote or only station):
With this parameter, you determine for which command source the extended switching-authority check
is used.
Table 7-15 Result Derived from the Combination of the Parameter Value Specific sw.auth. valid
for and the Level of the Command Source (Field Originator/orCat of the Switching
Command)
• Multiple specific sw.auth. ensures the simultaneous validity of the various command sources.
The following table shows how to determine the resulting specific switching authority when activating
the command sources of Remote or Station. If this parameter is activated, all parameterized command
sources get permissible automatically (see last row in the table) and they cannot be deactivated via the
controllable Enable sw. auth. 1 to Enable sw. auth. 5. Otherwise, the enabled command
source with the lowest number has always the highest priority and prevails against the other numbers.
Table 7-16 Determining Switching Authority if Multiple Command Sources Are Available
Multiple Enable sw. Enable sw. Enable sw. Enable sw. Enable sw. Resulting
specific auth. 1 auth. 2 auth. 3 auth. 4 auth. 5 Specific
sw.auth. Switching
Authority
No On * * * * Switch. auth. 1
No Off On * * * Switch. auth. 2
No Off Off On * * Switch. auth. 3
No Off Off Off On * Switch. auth. 4
No Off Off Off Off On Switch. auth. 5
No Off Off Off Off Off None
Yes On On On On On All
Figure 7-34 Display of Switching Authority and Switching Mode in the Information Routing (in Function
Block General), Example of 2 Activated Remote Switching Authorities
Individual Switching Authority and Switching Mode for the Switching Devices
In a standard case, the functionalities switching authority, switching mode, and specific switching authority as
described in the previous sections, are applicable to the entire bay unit and, therefore, are valid for all
switching devices that are controlled by this bay unit. In addition, you can configure an individual switching
authority and specific switching authority as well as individual switching modes for single switching devices.
Therefore, individual switching devices can accept various switching authorities and switching modes simulta-
neously.
This is offered for the following function groups and function blocks:
Figure 7-35 Additional Parameters for Switching Authorities in the Parameters of a Switching Device
When activating the parameter Swi.dev. related sw.auth., an individual switching authority as well as
an individual switching mode for this switching device are configured. Additional signals are displayed in the
Control function block of the corresponding switching device.
Figure 7-36 Expanded Parameters for the Switching Authority in the Switching Device
Figure 7-37 Individually Modifiable Switching Authority and Switching Mode for Switching Devices
The new input signals that are displayed allow you to set the individual switching authority and switching
mode for the switching devices. For this switching device, these inputs overwrite the central switching
authority and the switching mode. The outputs Switching authority and Switching mode indicate the
states only for this switching device.
When activating Specific sw. authorities, an individual specific switching authority for this switching
device is configured. Additional parameters are displayed.
The functionality of the specific switching authority for the individual switching device and the significance of
the additional parameters is identical to the operating mode of the central specific switching authority. Addi-
tional signals are displayed in the Control function block.
Figure 7-39 Specific Switching Authority, Modifiable for Each Switching Device
[sc_verbbp, 1, en_US]
By default, the status of interlocking conditions are not visible in the device, see the following figure.
[sc_HMI_WO_Position, 1, en_US]
Figure 7-41 The Status fof Interlocking Conditions are not Visible in the Control Display
[sc_HMI_WO_Position2, 1, en_US]
Figure 7-42 The Status of Interlocking Conditions are not Visible in the Control Menu
But, if you activate the parameter Shows interlock.cond. HMI by navigating to Settings > Device
settings > General > Control in DIGSI 5, you can get the status of interlocking conditions in the device.
[sc_HMI_W_Position, 1, en_US]
Figure 7-43 The Status of Interlocking Conditions are Visible in the Control Display
[sc_HMI_W_Position2, 1, en_US]
Figure 7-44 The Status fof Interlocking Conditions are Visible in the Control Menu
EXAMPLE
For interlocking
For the making direction of the circuit breaker QA in bay E01 (see the figure below), it is necessary to check
whether the disconnectors QB1, QB2, and QB9 are in the defined position, that is, either On or Off. Opening
the circuit breaker QA should be possible at any time.
The interlocking equations are: QA_On = ((QB1 = On) or (QB1 = Off)) and ((QB2 = On) or (QB2 = Off)) and
((QB9 = On) or (QB9 = Off)). There is no condition for opening.
[sc_abgang, 1, en_US]
The CFC chart that is required to implement the interlocking equation is shown in the next figure.
[sc_verpla, 1, en_US]
Since the Disconnector function block provides the defined position On or Off, the exclusive OR gate XOR is
not necessary for the linkage. A simple OR suffices.
As can be seen in the CFC chart, the result of the check is connected to the >Release on signal in the
Interlocking function block in the Circuit breaker QA function group (see Figure 7-46).
EXAMPLE
[sc_system, 1, en_US]
The circuit breaker QA in coupler bay = E02 will be considered next. As the multibay interlocking condition,
you must provide the bus-coupler circuit-breaker command block at the end:
If the 2 busbars in bay = E01 are connected, that is, if the 2 disconnectors QB1 and QB2 in bay =E01 are
closed, the circuit breaker QA in bay = E02 is not allowed to be switched off. Accordingly, bay = E01 in the CFC
of the device generates the indication Bus coupler closed from the positions of the switches QB1 and
QB2 and, using IEC 61850-GOOSE, transmits it to bay = E02 in the device. You must then store the following
interlocking condition in bay = E02:
QA_Off = NOT (= E01/Bus coupler closed)
In the CFC chart for the coupling device = E02, you must create the following CFC chart (see the figure below).
[sc_planve, 1, en_US]
[sc_double, 1, en_US]
[sc_notselected, 1, en_US]
The signal is then queried in the CFC interlocking conditions for the associated switching devices and is used
to generate the release signal (for example, >Release on).
The default setting for blocking by the protection function is therefore yes. If necessary, you can disable this
blocking. You can find the settings on the same page as the double-activation blocking (see Figure 7-49).
NOTE
i Remember, for instance, that pickup of the thermal overload protection can create a fault as well and thus
prevent switching commands.
NOTE
i The command check Blocking by protection function is only available for controlling circuit breakers,
because in this case a unique relationship with protection functions has been configured. In disconnectors,
this relationship is not always unique, precisely with regard to the 1 1/2 circuit-breaker layout, and it must
be mapped for each system using CFC charts.
To carry out the command check Blocking by protection function for disconnectors, use the following
indications (if present) in your interlocking conditions:
All commands in the sequence are logged. The command log contains:
• Reason for the transmission (SEL = Selected, OPR = Operate, CMT = Command execution end, SPN =
Spontaneous)
EXAMPLE
The following example illustrates control of a circuit breaker QA1 for various cases.
• Interrupted command
[sc_bbcon_1, 1, en_US]
[sc_bbcon_2, 1, en_US]
[sc_bbcon_3, 1, en_US]
[sc_bbcon_4, 1, en_US]
[sc_bbcon_5, 1, en_US]
[sc_bbcon_7, 1, en_US]
[sc_bbcon_8, 1, en_US]
[sc_bbcon_9, 1, en_US]
[sc_bbcon_6, 1, en_US]
Depending on the transmission reason, the desired control value or the actual state value of the controllable
and the switching device can be contained in the log.
The following table shows the relationship.
Table 7-17 Relationship between the Reason for Transmission and the Value Logged
7.4.3 Settings
The User-defined function block [control] allows the switching-authority check of a control command, the
check of whether the position has been reached, a double-activation blocking, and the definition of inter-
locking conditions for user-defined controllables.
The User-defined function block [control] is located in the folder User-defined functions in the DIGSI 5
Library.
You can instantiate the user-defined function blocks on the top level (in parallel to other function groups) as
well as within function groups and functions.
The task of the function block is to check the switching authority and the interlocking conditions for the user-
defined control commands instantiated within it. For these control commands, the function block checks
whether the required switch position is equal to the current switch position (actual/set point comparison). If
you activate the double-activation blocking, commands from switching objects and user-defined control
signals will be rejected as long as a command is still being performed for one of the other switching objects
for which double-activation blocking has also been set.
With the binary release signals, you can determine a switchgear interlocking protection for all the user-defined
control signals instantiated in the function block. Unlike the switching devices (circuit breaker, disconnector),
there is only one release input here, since there is only one switching direction for the signal types INC and
APC. The signal types DPC, SPC, and BSC have 2 switching directions, but still only one release input. This
release input can be operated based on the result of a logic created in the CFC, or can be directly connected to
a binary input or a variable. If the input >Enable is activated, the switching command can be performed. If it
is not activated, the switching command is rejected, with the reason Interlocking violation.
This applies in a similar way to the input >Enable (fixed), although with this input, the interlocking
cannot be revoked by key switch S1 or an unlocked switching authority.
The following table shows the reaction of the function to the assignment of its inputs.
Input >Enable Input >Enable (fixed) Effect on control command
1 0 Rejected
0 1 Successful if device mode = unlocked
Rejected if device mode = locked
1 1 Successful
0 0 Rejected
NOTE
i The default setting for the state of the inputs is 1, that is, the switching commands are not locked.
You can instantiate every user-defined signal (for example, SPS, DPC, INC) in the function block and route the
corresponding indications (see following figure).
[sc_user_01, 1, en_US]
Figure 7-60 Information Routing with Inserted User-Defined Function Block [Control]: Process Indications
and Some Single-Point Indications
The function block contains the parameters (_:104) Check switching authority, (_:105) Check
if pos. is reached, (_:106) Check double activat. blk., and (_:150) Check swi.auth.
for Mode. The parameter settings Check switching authority and Check if pos. is reached
affect all controllables instantiated in the function block. Other signal types are not affected by these parame-
ters and objects.
On the other hand, the parameter setting Check swi.auth. for Mode affects the controllable Mode
(controllable) of the function block.
[sc_user_02, 1, en_US]
7.5.4 Settings
If you want to process a parameter in a CFC chart and this parameter is to be changeable during runtime using
DIGSI or HMI, you can use the function blocks CFC chart of Boolean parameters, the CFC chart of integer
parameters and the CFC chart of floating-point parameters. Instantiate the appropriate function block
depending on the parameter value needed (logical, integer, or floating point). In this way, the current value of
the parameter can then be used in the CFC chart at runtime.
You can find the CFC-chart parameters Chrt sett.Bool, Chart setting Int, and Chrt sett.real in
the DIGSI library in the User-defined functions folder. Drag and drop the desired function block into a func-
tion group or a function. Set the appropriate parameter value of the function block in DIGSI using the param-
eter editor or via HMI under the Settings menu item. You can then use the parameter as an input signal in CFC
charts.
With Exp. options, you define the range and the unit of the value. This prevents users from entering incorrect
setting values.
NOTE
i The user-defined function groups and the user-defined functions can be used to group the CFC-chart
parameters. You can rename for the function block and change the parameter value in the DIGSI Informa-
tion routing matrix to suit your specific application.
[sc_cfc_param, 1, en_US]
7.6.4 Settings
8.1 Overview
SIPROTEC 5 devices are equipped with an extensive and integrated supervision concept. Continuous supervi-
sion:
• Supervision of the secondary system, including the external auxiliary power supply
SIPROTEC 5devices are freely configurable. A load model is integrated in DIGSI 5. The load model prevents you
from overloading the device with an excessively large application.
The load model shows the device utilization and the response times for device functions. If it determines that
an application created is likely to overload the device, DIGSI prevents the application from being loaded into
the device.
In this rare case, you must then reduce the application in order to be able to load it into the device.
The load model can be found in the DIGSI 5 project tree under Name of the device → Device information. In
the operating range, select the Resource consumption setting sheet. The following figure shows an example
of the view of the load model in DIGSI 5:
[sc_ress_bb, 1, en_US]
A green total display for the processor response time indicates that the device is not overloaded by the present
application. On the other hand, if you see a red exclamation mark, the planned application is overloading the
device.
The list below the total display shows the individual functional areas. These areas combine functions with the
same real-time requirements in groups. A green display in front of an area indicates that the response times of
the functions grouped in this area can be maintained. A red exclamation point indicates that functions may
have longer response times than are specified in the Technical data for the device. In such a case, loading of
the application into the device is blocked.
The following table provides an overview of the functional areas and the most important influencing quanti-
ties on device utilization:
If the load model displays a warning, bear in mind the following general instructions:
The areas named in the table are listed in descending order of real-time requirements. If a warning appears to
the effect that the guaranteed response times may be exceeded in an area, you can return to the permitted
area by taking the following measures:
• Reduce the functional scope in the marked area (red exclamation mark)
• Reduce the functional scope in another area with higher real-time requirements
When you have reduced the application, check the display in resource consumption! If a function has been
switched off, it will continue to represent a load for the area. If you do not need the function, delete it rather
than switching it off.
When you order a SIPROTEC 5device, you are also ordering a function-points account for use of additional
functions.
The following figure illustrates consumption of function points in the current application with respect to the
existing function-points account.
[sc_fpunkt, 1, en_US]
The remaining white bar shows the function points that have not yet been used up by your configuration. The
number of function points available in a device depends on the device purchase order (position 20 of the
product code). You can also order function points subsequently, and so increase the function-points account
for the device.
NOTE
i Find out the function-points requirement for the desired application before ordering the device. For this,
you can use the device configurator. Alternatively, you order the device with 0 function points and create
the license file with the required point credits ad hoc using the SIPROTEC function point manager (see
2.2 Adjustment of Application Templates/Functional Scope).
Function-Point Requirement
The following table explains the function-point requirement.
Name Function Points
Circuit-breaker failure protection 3-pole (per circuit breaker) 15
Circuit-breaker failure protection 1-pole/3-pole 25
End-fault protection (per circuit breaker) 5
Per each additional bay 50
The number of already included bays differs depending on the significant features.
All CFC function blocks can be assigned to all the task levels. There are no device-specific function blocks. If
enough ticks are available, all CFC charts can be created in the same task level. A tick is the measure of the
performance requirement of CFC blocks.
The number of available ticks for each task is calculated depending on the created device configuration. This
calculation is based on the previously described load model. In this process, it is recommended to create all
selected functions and objects first followed by configuration of the CFC charts so that a realistic information
about the remaining system capacitance for CFC charts is available. Significantly exceeding the typical
response time is prevented by the load model by limiting the number of CFC function blocks in the corre-
sponding task level via the number of ticks available.
The typical response times for CFC tasks are listed in the Technical Data.
The following figure shows an example of the CFC chart capacitances in DIGSI calculated by the load model.
The ticks available for each task are shown here. The green bars represent the ticks used in the task levels. You
reach this dialog with the following call: Device → Device information → Resource consumption.
[sc_cfc-statistic, 2, en_US]
NOTE
i High priority Event-triggered CFC charts have the highest priority and are processed before all other tasks.
At this level, a considerable smaller number of ticks are available than at all other tasks. It is recommended
to configure only very-high-priority logic functions at this task and to configure the other logic functions in
any other level.
NOTE
i Empty CFC charts also consume system resources. Empty charts that are not required any more should be
deleted.
8.3.1 Overview
The secondary circuits establish a connection to the power system from the point of view of the device. The
measuring-input circuit (currents, voltages) as well as the command circuits to the circuit breakers are moni-
tored for the correct function of the device. The connection to the station battery is ensured with the supervi-
sion of the external auxiliary voltage. The secondary system has the following supervision systems:
• Trip circuits
– Supervision of the relay activation
– Supervision of the control circuits for the circuit-breaker activation
• Non-connected transformers
• Pickup of the voltage transformer circuit breaker (in the event of short circuits in the secondary circuit)
[dw_strffm, 1, en_US]
[lo_ffm-3p_zusamm, 3, en_US]
Each subfunction creates its own monitoring indication. The function summarizes these indications via the
group indication Alarm.
The response to the detection of a measuring-voltage failure is explained in the specific protection-function
descriptions.
Logic
[lo_oppode, 5, en_US]
The criterion for detection of an unbalanced measuring-voltage failure is the voltage unbalance. This unbal-
ance is determined based on the ratio between negative and positive-sequence voltage. If the threshold value
is exceeded and the monitoring is released and not blocked, the monitoring picks up (see Figure 8-6). The
indication Asym.fail.-inst.alarm is output.
The monitoring is released as soon as a certain minimum voltage is exceeded. This prevents a spurious
response in the presence of low voltage measurands or a measurand of 0 (for example, circuit breaker open).
Instantaneous monitoring also requires the presence of a minimum current. This prevents a spurious instanta-
neous pick up of the monitoring in the presence of a weak infeed (current < 10 % of rated current) combined
with a power-system incident.
If the voltage unbalance is blocked by unbalanced faults in the primary system, the supervision is blocked. The
device detects an unbalanced fault based on the ratio between negative-sequence and positive-sequence
current.
Delay/Seal-In
In the presence of a weak infeed (current < 10 % of rated current), certain protection functions require more
time for detection of a system incident. For this purpose, monitoring can be delayed using the parameter
Asym.fail. - time delay.
If a system incident is detected during the time delay, the supervision drops off. This is because the function
assumes that the unbalance - and consequently the pickup of the supervision - is due to the system incident.
After the time delay has elapsed, it definitely assumes a measuring-voltage failure. Monitoring seals in and the
Asym.fail.-alarm indication is output. The dropout does not happen until the voltage unbalance has
disappeared after a seal-in time of 10 s. In the presence of 3-pole close-in faults outside the protection zone,
this seal-in time prevents the monitoring from dropping off too quickly and thus releasing the protection func-
tions.
The sealing-in function can be deactivated using the Asym.fail.-DO on netw.flt. parameter. As soon
as a system incident is detected, the monitoring drops off instantaneously.
Logic
[lo_symmet, 1, en_US]
• All 3 phase-to-ground voltages drop below the threshold value 3ph.fail. - VA,VB,VC <
NOTE
i If a voltage-transformer circuit breaker is installed in the secondary circuit of the voltage transformers, its
position is communicated to the device via a binary input (see chapter 8.3.4.1 Overview of Functions).
Logic
[lo_zuscha, 1, en_US]
Switching onto a 3-phase measuring-voltage failure is detected if the following criteria are fulfilled simultane-
ously:
• All 3 phase-to-ground voltages have dropped below the threshold value 3ph.fail. - VA,VB,VC <.
• The circuit breaker is detected to be in closed position. The detection takes place either via the phase
currents or via the ≥1-pole closed signal, which is generated via the circuit-breaker auxiliary contacts.
For more detailed information, refer to 5.7.8.5 Circuit-Breaker Condition for the Protected Object.
A voltage jump – such as in a 3-phase measuring-voltage failure with closed circuit breaker (refer to 8.3.2.4 3-
Phase Measuring-Voltage Failure) – does not occur in the case of switching to a 3-phase measuring-voltage
failure. If the monitoring is not blocked, the time delay SO 3ph.fail. - time delay is started. After the
time has elapsed, the indication SO 3ph.failure-alarm is displayed. A dropout of the monitoring is only
possible by a recovery of the voltage.
The supervision is blocked as soon as a pickup of a protection function is detected within a protection function
group and the time delay of the supervision has not yet elapsed.
This subfunction also covers the situation of a low load with 3-phase measuring-voltage failure and closed
circuit breaker, because the circuit-breaker position is also determined from the circuit-breaker auxiliary
contacts. The subfunction for detecting a 3-phase measuring-voltage failure (refer to 8.3.2.4 3-Phase Meas-
uring-Voltage Failure) is not released in this situation, for example, because the current flow is too low.
This subfunction can be switched on or off separately using the Switch-on 3ph. failure parameter.
• Recommended setting value (_:103) 3ph.fail. - phs.curr. jump = 0.1 A for Irated = 1 A or
0.5 A for Irated = 5 A
The 3ph.fail. - phs.curr. jump parameter is used to set the differential current between the present
current phasor and the stored phasor (from the previous period). If the value is exceeded, the function detects
a system incident and blocks the monitoring.
Siemens recommends using the default setting.
NOTE
i Adapt the SO 3ph.fail. - time delay parameter to the inherent time of protection functions which
are intended to block the monitoring function.
Note that with parameter values 0 s blocking of the monitoring function via a protection stimulation will
not be possible any more.
8.3.2.7 Settings
[dw_ivsstr, 1, en_US]
[sc_ivslib, 1, en_US]
Following the instantiation of the function group in the DIGSI project tree, it appears in the information
routing of DIGSI (see the following figure). The status indications of the supervision groups can be routed
here, for example, to existing binary outputs and/or logs.
[sc_ivsrou, 1, en_US]
Set the binary input used for signaling-voltage supervision within one input/output module using the setting
option (see the following figure). This binary input monitors the presence of the signaling voltage. If the
signaling voltage fails, this sets the quality attribute for all other binary inputs of the parameterized input/
output module to invalid. The signal status of each of these binary inputs is frozen with its last valid value
prior to the occurrence of the fault. The quality attribute of the binary inputs for other input/output modules
are not taken into consideration by this.
If the signaling voltage again exceeds the binary threshold, the quality attribute of the binary inputs is reset to
valid.
[sc_ivsgrp, 2, en_US]
NOTE
You can also combine binary inputs across modules in one Superv.Grp. function block and define any
binary input within this group for supervision of the signaling voltage. For this purpose, place a check mark at
the parameter (_:102) Enable variable group when configuring the supervision group. This extends
the parameterization menu by the sections Supervis. grp. start and Supervis. grp. end (see the
following figure).
[sc_gruppe_de, 2, en_US]
There, for example, you are able to combine 1 to n different binary inputs into one supervision group. When
doing so, the binary inputs on the input/output modules assignable to a supervision group must be related
logically. With 3 input/output modules, for example, this allows only consecutive binary inputs to be grouped
on the modules 1 and 2 or 2 and 3, but no binary inputs on modules 1 and 3. The binary inputs used for super-
vision can be located on any input/output module within the group defined in this manner.
If you have to monitor several binary inputs that, for example, work with different signaling voltages from
different sources, then you can also instantiate and configure several Superv.Grp. function blocks within
the Signaling-voltage supervision function group accordingly.
Within different supervision groups, only those consecutive binary inputs that are not already assigned to
another supervision group can be grouped. The overlapping of binary inputs in different supervision groups is
not permitted.
Error parameters are displayed to you by inconsistency indications in DIGSI.
Example
There are 4 input/output modules available.
Binary inputs of input/output modules 1 and 2 are already combined in supervision group 1. The 2 last binary
inputs on module 2 are not included in the grouping.
In supervision group 2, only these 2 binary inputs of the input/output module 2 not used in supervision group
1 as well as further consecutive binary inputs of the input/output modules 3 and 4 can be combined.
Parameter Binary input is used to define the highest binary input for the last I/O module (see (_:108)
I/O module ID) that you want to assign to a supervision group.
8.3.3.5 Settings
• Distance protection
NOTE
i If the voltage signal is generated using the optional Merging unit function, the quality of the voltage signal
is sent as invalid in the sampled value stream, depending on the status of the voltage-transformer circuit
breaker. For more information about configuring the voltage-transformer circuit breaker function for
devices with merging unit and process-bus client, refer to the Process Bus manual.
[dw_mcbstr, 1, en_US]
8.3.4.5 Settings
• Transformer defect
[dw_strdcs, 1, en_US]
The supervision pickup can be used to block the differential protection, but only the protection ranges
involved are blocked. To do this, you can set parameters for the following 3 operating modes:
• Only report:
Supervision pickup has no effect on operation of the differential protection, that is, no blocking occurs.
The Differential current supervision pickup for the protection ranges is indicated on a phase-selective basis
using a group indication.
Logic
[lo_dcsbuz_dbbp, 1, en_US]
Figure 8-16 Logic Diagram for Differential Current Supervision of the Selective Zones
[lo_dcschz_dbbp, 1, en_US]
Figure 8-17 Logic Diagram for Differential Current Supervision of the Check Zone
The following figure shows an overview of the pickup indications for the Differential current supervision
function.
[lo_dcsgri, 1, en_US]
NOTE
i Limitations with regard to teletransmission may occur for some of the following parameters. If the device
works with the IEC 61850 protocol, then you change the setting value of the parameter only via DIGSI 5
and not directly on the device. If you change the setting value directly on the device, then the IEC 61850
configuration of the measured values can be faulty.
Parameter: Mode
NOTE
i For low-load busbars, the unfavorable influence of current-transformer errors can lead to a higher differen-
tial current than with higher-loaded plants.
If you select the setting Blocking until release, the protection will be blocked independent of the
duration of the fault. The protection can be released with the operation command Reset ID MonBlk or with
the binary input >Reset ID MonBlk if the fault is corrected.
NOTE
i Keep in mind that even small differential currents caused by faults (for example, closed current transformer
terminals) are detected and indicated. In the case of larger plants, large differential currents (up to 10 % of
the normalization current) resulting from operation may occur due to current transformers having major
faults while under low loads.
Rule: As sensitive as possible, as unresponsive as necessary.
You can find additional information under information routing in DIGSI and in the previous figure.
8.3.5.5 Settings
[dw_strzcs, 1, en_US]
[dw_zcsaus, 1, en_US]
The Zero-crossing supervision logic operates phase-selectively for the individual busbar sections. Pickup
results in blocking of the phase-selective busbar section.
The following indications are generated only if the tripping criteria for the corresponding system are satisfied:
[lo_zcsbuz, 2, en_US]
Figure 8-21 Logic Diagrams for Zero-Crossing Supervision of the Selective Zones
You can find additional information on the disconnector-supervision settings and indications in chapter
5.5.1 Overview
Disconnector Positions
Siemens recommends using the following 2 binary inputs for determining the position of a disconnector.
Table 8-1 Possible States of the Disconnector Positions and the Effect on the Protection Functions
Signal Discon- Signal Discon- Meaning Effect on the Busbar Failure Indication
nector On nector Off Differential Protec-
tion and Circuit-
Breaker Failure
Protection
Active Inactive On position clearly Disconnector is –
recognizable considered closed
Inactive Active Off position clearly The disconnector is –
recognizable considered open
Inactive Inactive If all disconnectors in a bay are not in this state:
Disconnector is in The disconnector state Indication Discon-
intermediate state is considered closed nector runtime
between Off and On exceeded after the
The disconnector is disconnector runtime
assumed to be in the has elapsed
operating position
If all disconnectors in a bay are in this state:
The disconnector Depending on the No disconnector
auxiliary voltage for parameter State in auxiliary voltage
the entire bay has the absence of indication after 0.5 s
failed voltage - closed or -
last valid position
Active Active The disconnector Disconnector is Disconnector distur-
state cannot be deter- considered closed bance indication after
mined. expiration of the set
The disconnector is disconnector runtime.
considered disturbed
Unrouted Unrouted Disconnector is not No effect No supervision and no
used failure indication
One feature of the Disconnector supervision function is the following operating modes:
• Acquisition blocking
Broken-Wire Detection
When there is a wire break, apparent intermediate position is signaled (see below) and evaluated for the
disconnector image as On.
Preference
If all the following conditions are met, the preference can cause a non-selective disconnection if a bus fault
occurs:
• A wire break in the wire that provides feedback about the disconnector position
• A fault on a busbar
The first 3 items result in a preference because of the wire break. A simultaneous fault on a busbar results in
an unselective disconnection. Non-selective disconnection can be avoided through additional measures. One
such measure is, for example, interlocking of Off in the bay via additional CFC logic for overcurrent querying.
Wire breaks are indicated as a disconnector runtime error.
• Blocking the Busbar differential protection/Circuit-breaker failure protection remains in effect as long
as the criteria for pickup of disconnector supervision are satisfied.
Blocking is canceled only in response to a suitable control action after the criteria for pickup are no longer
satisfied.
• Blocking of the Busbar differential protection/Circuit-breaker failure protection starts with pickup of
disconnector supervision. Even if the pickup criteria are still present, you can remove the blocking by
appropriate control actions.
In this case, the indication Sw. gear op. prohibited is output as long as the criteria for pickup of
supervision are still present. The differential protection would not correctly recognize a change in the
disconnector position and the internal image of the protection range might no longer agree with reality,
which could cause non-selective tripping as a consequence
• When setting the disconnector monitor to Alarm only, acknowledgment is not required. With this
setting, the indication Sw. gear op. prohibited is not generated.
The states of the disconnector supervision are presented in the following table.
Acquisition of the Disconnector Meaning Protection Response
Position (Binary Input) Indication to Busbar Protection
On Off
1 0 Disconnector in On position Disconnector On
Disconnector off = closed
0 1 Disconnector in Off position Disconnector Off
Disconnector open
1 1 Disconnector in disturbed position Disconnector On
Disconnector closed
0 0 Disconnector in intermediate posi- Disconnector On (not Off)
tion
Disconnector closed
Runtime error
Wire break
Auxiliary-voltage failure
Values such as On, Off, Disturbed position can vary. A disconnector disturbance associated with the indica-
tion Disc.pos. aux. volt. lost, Disc. runtime exceeded or Disc. disturbance, issues the
indication Sw. fault alarm. This is cleared by the indication Sw. gear op. prohibited once the
disconnector disturbance has been acknowledged.
If a bay is in the state Bay out of operation or Acquisition blocking active, the disconnector feedback and
the plausibility of the disconnector position are not monitored.
If one busbar prefers another, the indication Prefers BZ appears after the disconnector runtime elapses.
The busbar preferred by another also indicates this by Preferred by BZ after the disconnector runtime
elapses. The appropriate indications are output as cleared without delay with the cleared preference.
[lo_disconnector_supervision, 3, en_US]
(1) While in intermediate position and if auxiliary voltage has not failed: after 200 ms have elapsed,
switch the previous position to On.
(2) With truck-type switchgear, the supervision of the circuit breaker is linked in the logic:
- If all circuit breakers and disconnectors of the bay are in the intermediate position, the auxiliary-
voltage failure of the bay is detected. In this case, as with the disconnectors, the parameter
Disc.pos. aux. volt. lost is used for the circuit-breaker switch position.
- Circuit-breaker failure and runtime errors are treated in the same manner as in the case of the
disconnectors.
[dw_trfaul, 1, en_US]
[dw_trblok, 2, en_US]
Figure 8-24 Blocking Behavior in the Event of Disconnector Runtime Error or Disturbed Position
[dw_tralt1, 2, en_US]
[dw_spgaux, 1, en_US]
[dw_veraux, 2, en_US]
[dw_tralt2, 1, en_US]
NOTE
8.3.7.5 Settings
• End-fault protection
– In the feeder
– In the dead zone of the bus couplers
• Circuit-breaker failure protection with blockage/release logic via circuit-breaker switch position if
circuit-breaker switch position is activated according to parameter (_:103) CB aux.cont. crit.
allowed.
[dw_cbrsup, 1, en_US]
• Phase-selective circuit breaker in the 1-pole Off position, phases A, B, C (CB Off)
Table 8-2 Possible States of the Circuit-Breaker Auxiliary Contacts and Effect on the Protection Functions
1-pole open or
Auxiliary-voltage
failure
Active Active Disturbed position Blocked Time delay blocked
2)
Auxiliary-voltage
failure
Active Active Disturbed position Blocked Time delay blocked
2)
1)Time delay active implies that the Open position during the transition from closed to open is effective
after the set time delay has elapsed.
2)Time delayed blocking indicates that the incoming blocking is delayed by the preset circuit-breaker supervi-
sion time (applicable only if the previous state was active).
3) Polex applies to all A, B, and C.
4) Only effective if the active signal is also available for all 3 poles (refer to Figure 8-15)
[lo_cbsvab, 1, en_US]
Figure 8-30 Input Logic of the Circuit-Breaker Switch Position in the Event of Acquisition Blocking
The following figure shows parts of the blocking/release logic for End-fault protection that evaluates the
circuit-breaker switch position. Preprocessing of the auxiliary-contact signals provides the input signals used
for this purpose. These signals are formed from the auxiliary-contact states acquired via the inputs (usually,
binary inputs) without consideration of the current flow.
[lo_cbsvef, 2, en_US]
Figure 8-31 Release Logic Based on the Circuit-Breaker Switch Position for End-Fault Protection
(1) Linking the Closed signal and Open signal, if routed to the input.
(2) Intermediate position and Disturbed position are possible only if the Open as well as the
Closed position are detected.
The following figure shows parts of the blocking/release logic for the low-current operating mode of the
Circuit-breaker failure protection that evaluates the circuit-breaker auxiliary contact. Preprocessing of the
auxiliary-contact signals provides the input signals used for this purpose. These signals are formed from the
auxiliary-contact states acquired via the inputs (binary inputs) without consideration of the current flow.
[lo_cbsvbf, 2, en_US]
Figure 8-32 Release Logic of the Circuit-Breaker Failure Protection with Circuit-Breaker Auxiliary-Contact
Evaluation
(1) Linking the Closed signal and Open signal, if routed to the input.
(2) Intermediate position and Disturbed position are possible only if the Open as well as the
Closed position are detected.
(3) Switching to Intermediate position and Disturbed position delayed by the parameter Circuit-
breaker supervision time
The states of the by circuit-breaker supervision are presented in the following table.
Indication of Circuit-Breaker Meaning Protection Response
Switch Position (Binary Input) Busbar Protection Indication
On Off
1 0 Circuit breaker in On position Circuit breaker On
Circuit breaker closed
0 1 Circuit breaker in Off position Circuit breaker Off
Circuit breaker open
1 1 Circuit breaker in disturbed posi- Circuit breaker On
tion
Circuit breaker closed
0 0 Circuit breaker in intermediate Circuit breaker On (not Off)
position
Circuit breaker closed
Runtime error
Wire break
Auxiliary-voltage failure
8.3.8.5 Settings
• Connection errors during commissioning or short circuits and interruptions in the secondary circuit
The voltage measurement is based on the RMS values of the fundamental component.
[dw_strusy, 2, en_US]
|Vmin| / |Vmax| < Threshold min/max, as long as Vmax > Release threshold
[lo_kenuns, 1, en_US]
Logic
[lo_sp_asym, 5, en_US]
The Threshold min/max parameter is the criterion by which a phase-to-phase voltage unbalance is meas-
ured. The device calculates the ratio between the minimum (Vmin) and the maximum (Vmax) phase-to-phase
voltage.
Enter the lower limit of the maximum phase-to-phase voltage (Vmax) with the parameter Release
threshold. This specifies the lower limit of the operating range of this function.
• A protection pickup
The pickup signal of a protection function blocks the Failure indication.
8.3.9.5 Settings
NOTE
i For the Voltage-sum supervision, the externally generated residual voltage must be connected to the 4th
voltage measuring input.
For the Voltage-sum supervision to work correctly, the Matching ratio Vph / VN parameter must be
set accordingly.
[dw_strvss, 2, en_US]
[lo_kenvss-01.tif, 1, en_US]
Logic
[lo_volt-sum-supervision, 5, en_US]
The device measures the phase-to-ground voltage and the ground voltage of the lines to be protected. The
sum of the 4 voltages must be 0.
Threshold
If the calculated fault voltage (VF) exceeds the Threshold the parameter Delay failure indication
triggers the indication Failure.
The device calculates the fault voltage (VF) with the formula:
VF = |VA + VB + VC - Vph/UN • UN|, where Vph/VN forms the Matching ratio Vph / VN parameter.
The Matching ratio Vph / VN parameter takes into account the differing transformation ratios between
the residual voltage input and the phase-voltage inputs.
You can find more information in this respect in chapter 8.3.10.1 Overview of Functions ).
• A protection pickup
The pickup signal of a protection function blocks the Failure indication.
Parameter: Threshold
8.3.10.5 Settings
[dw_strvrs, 3, en_US]
Logic
[lo_volt-phs-rotation-supervision, 5, en_US]
The phase rotation is important for protection functions which process phase, loop, and directional informa-
tion. You can set the phase sequence with the Phase sequence parameter in the function block General of
the power-system data (see chapter 5.10 Power-System Data).
To supervise the phase rotation, the device compares the measured phase sequence with the set phase
sequence. For abnormal phase sequences, the indication Failure is generated.
The connection of the voltages to the device does not depend on the selected phase sequence. The connec-
tion diagrams are shown in chapter A Appendix.
Release Condition
The supervision of the voltage phase rotation is carried out when all measured phase-to-phase voltages are
greater than 40 V.
• Via the binary input signal >Block function from an external or internal source
8.3.11.5 Settings
[dw_tcsueb, 1, en_US]
[dw_1pole_2bi, 2, en_US]
CR Command relay
CB Circuit breaker (open)
CB coil Circuit-breaker coil
AuxCon1 Circuit-breaker auxiliary contact (make contact)
AuxCon2 Circuit-breaker auxiliary contact (break contact)
V-Ctrl Control voltage (tripping voltage)
V-BI1 Input voltage for binary input 1
V-BI2 Input voltage for binary input 2
Supervision with 2 binary inputs identifies disruptions in the trip circuit and the outage of the control voltage.
It also monitors the reaction of the circuit breaker by way of the position of the circuit-breaker auxiliary
contacts.
Depending on the switch position of the command relay and circuit breaker, the binary inputs are either acti-
vated (H) or not (L). If both binary inputs are not activated, there is a fault. The fault can be a disruption or a
short circuit in the trip circuit, an outage of the battery voltage or a fault in the mechanics of the circuit
breaker. With intact trip circuits, this state will occur only briefly while the command relay is closed and the
circuit breaker has not yet been opened.
No. Command CB AuxCon1 AuxCon2 BI 1 BI 2 Dynamic State Static State
Relay
1 Open ON Closed Open H L Normal operation with closed circuit
breaker
2 Open OFF Open Closed H H Normal operation with open circuit
breaker
3 Closed ON Closed Open L L Transmission or fault Fault
4 Closed OFF Open Closed L H CR successfully activated the circuit
breaker
With the Alarm delay parameter, you can set the time delay. After fixing the fault in the trip circuit, the
failure indication will automatically expire after the same time.
If the binary input signals >Trip relay phsA to >Trip relay phsC or >CB aux.contact phsA to
>CB aux.contact phsC are not routed to the binary inputs of the device (Information routing in DIGSI 5),
then the indications PhA input sig.n.routed to PhC input sig.n.routed are generated and the
Trip-circuit supervision function is ineffective.
The following figure shows the logic diagram of the trip-circuit supervision with 2 binary inputs.
[lo_1po_2be, 2, en_US]
[dw_1pole_1bi, 2, en_US]
CR Command relay
CB Circuit breaker (activated)
CBC Circuit-breaker coil
AuxCon1 Circuit-breaker auxiliary contact (make contact)
AuxCon2 Circuit-breaker auxiliary contact (break contact)
V-Ctrl Control voltage (tripping voltage)
V-BI Input voltage for binary input
R Equivalent resistance
The supervision with 1 binary input identifies disruptions in the trip circuit and the failure of the control
voltage.
In normal operation, the binary input is activated with the command relay open and the trip circuit intact (H).
The supervision circuit is closed by means of the equivalent resistance R or by means of the auxiliary contact
AuxCon1 of the closed circuit breaker. The binary input is not activated while the command relay is closed (L).
If the binary input is not activated for a prolonged time, there is a disruption in the trip circuit or the control
voltage has failed.
No. Command CB AuxCon1 AuxCon2 BI Dynamic State Static State
Relay
1 Open ON Closed Open H Normal operation with closed circuit breaker
2 Open OFF Open Closed H Normal operation with open circuit breaker
3 Closed ON Closed Open L Transmission or fault Fault
4 Closed OFF Open Closed L CR successfully activated the circuit breaker
With the Blk.by trip/open cmd from parameter, you set which functions act on the trip circuit that is
being supervised. While these functions are active (for example, protection tripping), the trip-circuit supervi-
sion is blocked. The closed contact of the command relay does not lead to a failure indication in this case.
If the command contacts of other devices work in parallel on the trip circuit, the failure indication must be
delayed. With the Alarm delay parameter, you can set the time delay. After fixing the fault in the trip
circuit, the failure indication will automatically expire after the same time.
If the binary input signals >Trip relay phsA to >Trip relay phsC are not routed to the binary inputs
of the device (Information routing in DIGSI 5), indications PhA input sig.n.routed to PhC input
sig.n.routed are generated and the Trip-circuit supervision function is ineffective.
The following figure shows the logic diagram of the trip-circuit supervision with 1 binary input.
[lo_1po_1_be, 2, en_US]
Equivalent Resistance R
The equivalent resistance R must be dimensioned such that the circuit-breaker coil is no longer activated when
the circuit breaker is open. Simultaneously, the binary input must still be activated when the command relay is
open.
In order to ensure the minimum voltage for activating the binary input, Rmax results in:
[fo_r_max, 1, en_US]
So that the circuit-breaker coil does not remain activated, Rmin results in:
[fo_r_min, 1, en_US]
with:
VCtrlst Control voltage for the trip circuit
VBI min Minimum activate voltage for BI
RCBC Ohm's resistance of the CB coil
IBI(High) Constant current with activated BI
VCBC (Low max) Maximum voltage at the CB coil that does not lead to a tripping
You can calculate the optimal value for the equivalent resistance R from the 2 values Rmin and Rmax:
[fo_r, 1, en_US]
The following applies for the power consumption of the equivalent resistance R:
[fo_pr, 1, en_US]
• Recommended setting value (_:100) Alarm delay = 2 s (Trip-circuit supervision with 2 binary
inputs)
• Recommended setting value (_:100) Alarm delay = 300 s (Trip-circuit supervision with 1 binary
input)
With the parameter Alarm delay, you can set the time for the delayed output of the indication Trip-
circuit fail.phsA to Trip-circuit fail.phsC.
For Trip-circuit supervision with 2 binary inputs, you set the Alarm delay parameter so that the short-
term transient states do not cause the function to activate.
For the Trip-circuit supervision with 1 binary input, you set the Alarm delay so that the longest duration
of a trip command is bridged without fail. This ensures that the indication is emitted only if the trip circuit is
actually interrupted.
8.3.12.6 Settings
Binary inputs are monitored if their error behavior will most likely cause a fault of the protection function. This
supervision consists of configuring a second input, a so-called release input, or allowing the signal to remain
at the binary input for only a maximum permissible time.
The following table displays binary inputs important for the protection functions and the type of supervision.
Binary Input Release via the 2nd Binary Time Supervision of the
Input Binary Input
General
>Sensitive characteristic curve active – x
Function: Busbar protection
>Tripping release – x
>Release, ext. Tripping x x
Binary Input Release via the 2nd Binary Time Supervision of the
Input Binary Input
>Ext. Tripping busbar section x x x
>Additional criterion for A – x
>Additional criterion for B – x
>Additional criterion for C – x
Function: Circuit-breaker failure protection
>Release, 3-pole x x
>Release, 1-pole x x
>Start, 3-pole 1) x x
>Start, A 1) x x
>Start, B 1) x x
>Start, C 1) x x
Function: External tripping (bay)
>Start, A x x
>Start, B x x
>Start, B x x
>Release x x
Function: End-fault protection
>Close Command – x
Disconnector status
>Disconnector x – Status closed Plausibility check (see –
>Disconnector x – Status open chapter 11.13 Disconnector –
Supervision)
Circuit-breaker switch position
>Circuit-breaker switch position closed Plausibility check (see –
>Circuit-breaker switch position open chapter 11.14 Circuit-Breaker –
Supervision)
1) If starting in the 1-channel mode, release is not necessary.
8.4.1 Overview
The correct state of the device hardware is a requirement for the correct functioning of the device. The failure
or erroneous function of a hardware component leads to device malfunctions.
The following modules of the device hardware are monitored:
• Base module
• Expansion modules
• USB interface
• Battery voltage
• Defective module
NOTE
i If the error has not be rectified after 3 unsuccessful attempts, the system automatically recognizes it as a
severe device malfunction. The device goes permanently out of operation into a secure state (fallback
mode).
Fatal device errors with outage of central components: The device goes permanently out of operation
into a secure state (fallback mode).
Such errors are, for example:
• Supervision of the correct functioning of the device-internal analog-digital converters, based on the sum
of all currents of one measuring point in the secondary circuit.
• Blocking of protection and control functions that process the measured values from this current meas-
uring point (for example, differential protection). This avoids an overfunction of the device.
The supervision principle is based on fast current-sum supervision with connection of the neutral-point current
to the 4th current measuring input. In order to ensure that even the fast tripping stages of the protection
functions can be blocked in time before a spurious pickup, the fast current measurement is based on instanta-
neous values.
For Analog-digital converter supervision, the neutral-point current of the line to be protected must be
connected to the 4th current measuring input (IN). The 4th current measuring input must be routed via the
current-transformer neutral point (IN neutral point) (see next figure).
[ti_phase_2, 4, en_US]
Figure 8-46 Connection to a 3-Phase Current Transformer and Measured Zero-Sequence Current (Current
in Common Return Conductor)
NOTE
i The analog channel supervision via fast current sum is only available when the 4th current input is a
protection-class current transformer. In the DIGSI 5 project tree, under Device → Measuring-point
routing, set the connection type 3-phase + IN for the current measuring point. When using this func-
tion, check the correct connection of the neutral conductor/ground current by supplying an asymmetrical
current. Otherwise, a 1-pole or 2-pole fault could result in an unwanted blocking of the protection.
[dw_schstr, 1, en_US]
[lo_kenisu, 2, en_US]
Figure 8-48 Characteristic Curve of the Supervision of the Device-Internal Analog-Digital Converters
Logic
[lo_sumsch, 4, en_US]
Figure 8-49 Logic Diagram of the Supervision of the Device-Internal Analog-Digital Converters
When the output signal A/D converter monit. is active, certain protection functions are blocked to avoid
failures (see 11.32 Analog Channel Supervision via Fast Current Sum ).
NOTE
Threshold Value
The threshold value is the lower limit of the operating range of the Supervision of the device-internal
analog-digital converters function.
The threshold value is permanently set to 10 % of the device rated current.
[lo_fcsbbp, 2, en_US]
Figure 8-50 Influence of the Fast Current-Sum Supervision on Busbar Differential Protection
If fast current-sum supervision is present for less than 1 s, selective blocking occurs if the bay is connected to
the busbar. This blocking is reset after the failure is cleared.
If the fast current-sum supervision is present for more than 1 s, this failure is maintained permanently, even if
the measured values are detected as healthy again. This results in blocking for all zones assigned to the faulty
bay. To eliminate this permanent failure, you must restart the device assuming that the measured values are
not still faulty. The check zone is released immediately when the current-sum supervision picks up.
Failures which can partially be corrected by a restart of the device. The device goes briefly out of
operation.
Such errors are, for example:
• Device startup with faulty new parameter set. The old parameter set is still present.
• Program-sequence error
Fatal firmware error. The device goes permanently out of operation into a secure state (fallback mode).
Such errors are, for example:
• Device startup with faulty new parameter set. No usable parameter set is present.
• CFC-runtime error
Fatal configuration error: The device goes permanently out of operation into a secure state (fallback
mode).
Such errors are, for example:
Supervision
With the supervision of the communication connections, every communication port is monitored selectively.
• Failures are detected and indicated via the operational log. The device remains in operation!
• Each port additionally is equipped with a separate communication log, with which details of the failures
(for example, error rate) are displayed.
• GOOSE signals can automatically be set to defined values in case of disturbed IEC 61850 communication.
• Disturbed protection interfaces set phasor values, analog measured values, and binary information to
invalid, for example for the differential protection. Binary signal traces can be set to defined values in
cases of failures.
• Disturbed time-synchronization signals can lead to an automatic change of the source of time synchroni-
zation.
You can correct communication failures by checking the external connections or by replacing the affected
communication modules.
For further information on failures responses, refer to 8.8.2 Defect Severity 1 to 8.8.4 Defect Severity 3. The
corresponding corrective measures are described there.
[sc_dbbp_proj_17_notifi, 1, en_US]
Figure 8-51 Indications in the 7SS85CU for Monitoring the Busbar-Protection Internal Communication to a
Merging Unit
If the 7SS85CU central unit does not receive any data from the 6MU85 merging unit, for example, because the
merging unit is switched off or the entire bay including the merging unit is not present, this is signaled in the
7SS85CU by sending the communication failure indications Failure and Communication failure.
The indication Failure is a group indication that includes, among others, the indication Communication
failure. It is sent when no more data is received from a merging unit or the indications Group alarm or
Group warning have been sent in the associated merging unit.
In addition, the indication Compatibility state with the value unknown is sent, because no compati-
bility data is received from the merging unit.
NOTE
i If these communication failure indications are unwanted in the 7SS85CU, you can suppress the communi-
cation failure indications by switching off the representative of the corresponding bay in the 7SS85CU
device. For this, refer to 5.2.7 Operating State: Bay Off.
If the indications Failure and Communication failure were sent in the 7SS85CU, these indications drop
out in the 7SS85CU after the representative of the bay is switched off.
The value of the indication Compatibility state changes to the value ignored.
Alternatively, you can use an IEC 61850 control command to set the controllable Mod of the representative of
the bay in the 7SS85CU to off.
[sc_dbbp_proj_18_contr, 1, en_US]
Figure 8-52 Controllable Mod of the Representative for the Bay Bay1 in the 7SS85CU
[sc_dbbp_proj_19_contr_comm, 1, en_US]
If a merging unit does not receive data from the 7SS85CU central unit, this is signaled in the merging unit by
issuing the communication failure indications Failure and Communication failure.
In addition, the indication Compatibility state with the value unknown is issued, because no compati-
bility data is received from the central unit.
NOTE
i The communication failure indications Failure and Communication failure cannot be suppressed in
a merging unit.
8.8.1 Overview
When device errors occur and the corresponding supervision functions pick up, this is displayed on the device
and also indicated. Device errors can lead to corruption of data and signals. These data and signals are marked
and tagged as invalid, so that affected functions automatically go into a secure state. If the supervision func-
tions pick up, this will lead to defined error responses.
• Defect severity 1:
Internal or external device error that is reported. The device remains in operation.
• Defect severity 2:
Severe device failure, the device restarts (reset) to correct the cause for defect.
• Defect severity 3:
Severe device failure, the device goes to a safe condition (fallback mode), as the
correction of defects cannot be implemented by a restart. In fallback mode, the
protection and automated functions are inactive. The device is out of operation.
• Defect severity 4:
Severe device-external failure, the device switches the protection and automatic
functions to inactive for safety, but remains in operation. Normally, the user can
correct the fault by himself.
Step 2: For every defect severity, you will find detailed tables with information about causes
for defects, error responses, and corrective measures in the following chapters.
Device-Diagnosis Log
Indication of the
Operational Log
Group Warning
Fallback Mode
Device restart
Indication in
Indication in
Life Contact
are inactive
(Reset)
Defect Severity 1 x x x – – – –
Defect Severity 2 – – x x During the x –
starting time of
the device
Defect Severity 3 – – x x x – x
Defect Severity 4 – x – x x – –
Defect severity 1 faults allow the continued safe operation of the device. Defect severity 1 faults are indicated.
The device remains in operation.
When the supervision functions pick up, corrupted data and signals are marked as invalid. In this way, the
affected functions can go into a secure state. Whether functions are blocked is decided in the appropriate
function itself. For more detailed information, refer to the function descriptions.
Life contact Remains activated
Red error LED Is not activated
Log
For every device fault, a corresponding supervision indication is generated. The device records these indica-
tions with a real-time stamp in the operational log. In this way, they are available for further analyses. If super-
visions in the communication interfaces area of the device pick up, there is a separate communication log
available for each port. Extended diagnostic indications and measured values are available there. The device-
diagnosis log contains expanded fault descriptions. There you also receive recommendations of corresponding
corrective measures for each detected device error.
[lo_warning_indication, 1, en_US]
Overview of Errors
Faults of defect severity 2 are fatal device faults that lead to an immediate restart of the device (reset).
This occurs when the device data is corrupted (for example, RAM memory), if a restart prevents restoration of
data consistency. The device goes briefly out of operation, a failure is avoided.
Life contact Is terminated during the restart
Red error LED Is activated during the restart
NOTE
i If the fault of defect severity 2 has not been removed after 3 unsuccessful restarts (reset), the fault is auto-
matically assigned to defect severity 3. The device will automatically turn to the fallback mode.
Log
For every device error with a subsequent restart (reset), only the restart can be detected in the operational log.
The actual supervision indication is entered in the device-diagnosis log at the point in time of the fault detec-
tion and before the restart. These indications are recorded with a real-time stamp and are thus available for
later analyses. The device-diagnosis log contains expanded fault descriptions. There, you also receive recom-
mendations of corresponding corrective measures for each detected device error.
29 The indications are not pre-routed in the logic block chart. The indications must be added to by the user in the logic block chart!
Overview of Errors
Faults of defect severity 3 are fatal device faults that lead to device immediately going into the fallback mode.
The signal (_:301) Device status goes to the Alarm state. The Warning state is not supported for this
signal.
Fatal device errors are errors that cannot be resolved by a restart of the device. In this case, contact the
Customer Support Center. The device goes permanently out of operation, a failure is avoided. In the fallback
mode, minimal operation of the device via the on-site operation panel and DIGSI is possible. In this way, for
example, you can still read out information from the device-diagnosis log.
Life contact Is terminated in the fallback mode
Red error LED Is activated in the fallback mode
Log
For every device error that immediately leads to entry into the fallback mode, entries from supervision
messages and from the signal (_:301) Device status into the operational log are not possible. The
actual supervision indication is entered in the device-diagnosis log at the point in time of the fault detection,
that is, before entry into the fallback mode. These indications are recorded with a real-time stamp and are thus
available for later analyses. The device-diagnosis log contains expanded fault descriptions. There, you are
offered recommendations of corresponding corrective measures for each detected device error.
You can find further information on handling the logs in chapter 3.
Overview of Errors
Further information:
Number Device-Diagnosis Log
6232, 6236, 6362, Internal firmware error:
6367, 6368, 6327, Contact the Customer Support Center.
6384
Errors of defect severity 4 are not device failures in the classical meaning. These errors do not affect the device
hardware and are not detected or reported by internal device supervision functions. The condition of the
defect severity 4 – the group alarm – is set user-specifically by the binary input signal (_:503) >Group
alarm. If the binary input signal is reset, the device is no longer in the Group alarm condition and all func-
tions return to the normal operating state.
If the group alarm is generated, the device reacts as follows:
• The group indication (_:300) Group alarm is generated and recorded in the operational log.
• The device remains in operation, does not carry out any restart (reset), and does not switch to the safe
condition (Fallback mode).
• The signals managed internally are marked with the invalid quality attribute. Signals managed inter-
nally are, for example, measured values, binary input and output signals, GOOSE and CFC signals.
In the delivery condition, every device has the CFC chart Process mode inactive, that initiates the Group
alarm (see chapter 8.9 Group Indications).
Life contact Is terminated in case of Group alarm
Red error LED Is initiated in case of Group alarm
Log
The group indication (_:300) Group alarm is recorded in the operational log. Depending on the cause of
the initiation, further information can be found in the operational log.
You can find further information on handling the logs in chapter 3.
[sc_grwarn, 1, en_US]
Figure 8-55 Group Monitoring Indication in the DIGSI 5 Information Routing Matrix
You can adapt the CFC chart as needed. You can find the CFC chart in the DIGSI 5 project tree under Name of
the device → Charts.
The group-warning indication (_:301) Group warning is prerouted to an LED of the base module.
Group Indication
If the binary input signal (_:505) >Group indication is set, the indication (_:302) Group indica-
tion becomes active and is recorded in the operational log. This warning indication does not result in
blocking a protection function. If the binary input signal is reset, the signal (_:302) Group indication
drops out. Using a CFC chart, you can define when the binary input signal (_:505) >Group indication is
to be set.
[sc_bbp-message, 1, en_US]
Figure 8-56 Group Indications Specific to the Busbar Protection in the DIGSI 5 Information Routing Matrix
[dw_om_verf, 1, en_US]
For the display, the measured values of a SIPROTEC 5 device are summed up in the following groups:
• Statistical values
[dw_om_vls1, 1, en_US]
Fundamental Components
Symmetrical Components
• Symmetrical components
Through the settings, you can set how and when the average values are formed. The settings describe:
• Synchronization time for establishing the date of commencement updating information, for example, at
the top of the hour (hh:00) or at one of the other times (hh:15, hh:30, hh:45).
(Parameter: Average synchroniz. time )
Average values are formed through the following measurands:
• DIGSI
The average value formation functionality is not preconfigured with the devices in the function group. If you
use the functionality, you must load it from the library into the respective function group.
The following settings listed for the calculation of the average values can be set with DIGSI and at the device.
You find the setting parameters in DIGSI in the project tree under Settings > Device settings.
NOTE
The following examples explain how to set parameters and to make a change.
A new average value is formed every 30 min, at hh:15 (15 min after the top of the hour) and hh:45 (15 min
before the top of the hour). All measured values obtained during the last 60 min are used for average value
formation.
If these settings are changed to 11:03:25, for instance, the average values are first reset and "---" appears in
the display. The 1st average value is then formed at 12:15:00.
In this example, the Average synchroniz. time = hh:45 acts as described above for = hh:15.
A new average value is formed every 60 min at hh:15 (15 min after the top of the hour). All measured values
obtained during the last 60 min are used for average value formation.
If these settings are changed to 11:03:25, for instance, the average values are first reset and "---" appears in
the display. The 1st average value is then formed at 12:15:00.
A new average value is formed every 10 min at hh:00, hh:10, hh:20, hh:30, hh:40, hh:50. All measured
values obtained during the last 5 min are used to form the average value.
If these settings are changed to 11:03:25, for instance, the average values are first reset and "---" appears in
the display. The 1st average value is then formed at 11:10:00.
Minimum and maximum values can be formed based on different measured or calculated measurands:
• Symmetrical components
• Selected values
You can set which measurand will be used. The measurands for the minimum/maximum formation are loaded
from DIGSI.
Calculation and resetting of the minimum and maximum values are controlled through settings. The settings
describe the following points:
• Point in time when the memories of the minimum/maximum values are reset to 0.
(Setting Min/Max reset each and setting Min/Max reset minute )
• Point in time at which the cyclical reset procedure of the minimum/maximum values begins (after the
parameterization)
(Setting Min/Max days until start )
The following figure shows the effect of the settings.
[dw_min_max, 1, en_US]
• Average values
The minimum and maximum values are reset on a regular basis or via the
• DIGSI
The minimum/maximum values functionality is not preconfigured. If you want to use the functionality, you
must load it from the library into the respective function group.
The following settings listed for the calculation of the minimum/maximum values can be set with DIGSI or at
the device. You find the setting parameters in DIGSI in the project tree under Settings > Device settings.
NOTE
i You can define additional metered values through DIGSI for user-specific applications.
Use pulse meters; then you can define the respective metered values through DIGSI and set parameters for
them analogously to the energy values. You can read out the metered values on the display of the device or
via DIGSI.
Through settings, you can individually set how each pulse-metered value is processed:
[sc_omvimp, 2, en_US]
The functionality Pulse-metered values is not preconfigured. If you want to use the functionality, you must
load it from the library into the respective function group.
The parameters can be set individually for every pulse counter. You will find the setting parameters in DIGSI in
the project tree under Parameter > Function group. The maximum repetition rate when detecting the pulse-
metered values is 50 Hz.
For pulse-metered values, the following described settings and binary inputs are available.
Note: If the parameter is activated through a time setting, the parameter Restore interval is not in effect
and will be deactivated automatically.
Note: If the parameter is activated through a time setting, the parameter Restore time is not in effect and
will be deactivated automatically.
• Number of trippings of the circuit breaker initiated by the device, separately for each circuit breaker pole
(if 1-pole tripping is possible)
• Sum of the primary breaking currents, separately for each breaker pole
• Total number of switching operations of the disconnector switch initiated by the device
• Number of switching operations of the disconnector switch initiated by the device, separately for each
switch pole (if 1-pole switching is possible)
A Phasor Measurement Unit (PMU) measures the phasor values of current and voltage. These values get a high
precision time stamp and together with the values of power frequency, power frequency change rate and
optional binary data that are also time stamped are transmitted to a central analysis station. The standardized
transmission protocol IEEEC 37.118 is used to do this.
The PMU function group is activated by selecting the protocol IEEE C37.118PMU on an Ethernet module
(electrical or optical). The PMU obtains the measured values from the measuring points and the precise time
from time synchronization. The time-stamped synchrophasors for current and voltage are formed from this
and transferred together with additional values via the communication module to a server (PDC, Phasor Data
Concentrator).
[dw_strpmu, 2, en_US]
The synchrophasors, sent from the PMU in a continuous data stream to a PDC, are provided with time stamps
and thus are comparable with the measured values of other PMUs. The power frequency, the power frequency
change rate and optional binary information are also transmitted as time-stamped measured values. There-
fore, you receive an overview of the transient processes in a distributed energy transfer system, for example
network fluctuations and compensating processes.
The following table shows the differences between the PMU measured values and the remaining measured
values of the device.
The following figure shows the structure of such a Wide Area Monitoring System. The data delivered from the
PMUs on the PDC are transmitted via the Inter-Control Center Communications Protocol (ICCP) according to
DIN EN 60870-6 to the network control center.
[dw_strwam, 1, en_US]
Figure 9-5 Structure of a Wide-Area Monitoring System with Phasor Measurement Units
The phasor measurement units each have 2 communication interfaces: an Ethernet module for synchrophasor
communication via IEEE C37.118 and another module for communication with the substation automation
technology, for example, through the IEC 61850 protocol. If you use an ETH-BD-2FO communication module,
you can activate IEEE C37.118 and IEC 61850-8-1 on the same module.
The central evaluation system, for example SIGUARD PDP Phasor Data Processor, receives the data, files,
archives them and graphically displays them on a User Interface. In this system, a self-checking function may
also be performed, for example, on undamped power swings. The further distribution of information to other
PDCs or to a control center is done here.
To maintain the required maximum errors (TVE) required in the standard IEEE C37.118, the time tolerance
relative to the UTC time reference (UTC = Universal Time Coordinated) may be maximum 10 μs. Therefore, the
device must be directly synchronized with a GPS precise time signal for the correct function of the PMU.
Phasors
A phasor u(t) = Uejωt can be displayed as a phasor that moves counterclockwise in the complex plane at the
angular frequency ω. Therefore, the voltage function u(t) = Re{u(t)} is obtained as a projection of the phasor
u(t) on the real axis.
[dw_geopdc, 1, en_US]
[dw_utcphi, 1, en_US]
Figure 9-7 Determination of Phase Angle ρ of Measuring Signal Xm Relative to the Cosine Function
The number of phasors that are transmitted per second is configurable. The transmission rate is defined
according to IEEE C37.118 as the reporting rate. The reporting rate defines the number of phasors that are
transmitted per second. Extremely precise time synchronization is essential so that phasor measurement can
be carried out to enable phasors from different sites to be compared via GPS.
Reporting Rate
You use the configurable reporting rate (parameter (_:10621:102) Reporting rate) to specify the
number of telegrams that are generated and sent to the PDC per second. It is adjustable, depending on the
rated frequency, and applies to all currents and voltages of the relevant PMU function group. If several PMU
function groups are created on the device, these can work with different reporting rates.
• Signal magnitude (relative to 100 % nominal magnitude) for voltage and current
[dw_klatve, 1, en_US]
[fo_utcphi_new, 1, en_US]
Where:
• Amplitude errors
• Phase errors
• Frequency
• Binary information
The current and voltage channels transferred from a PMU function group are selected through the Function
group connections editor in DIGSI 5. The frequency and frequency change rate are determined once per
PMU. In this case, only the current and voltage channels selected via the Function group connections editor
for this PMU are taken into consideration. You may route the binary information in the information routing
matrix of DIGSI 5. You can instantiate the analog-channel data from the Global DIGSI 5 library in the PMU
function group.
The channel used for specifying the frequency is selected dynamically during the device runtime. Each
channel is checked for the presence of a signal in the following order:
1. 3-phase voltage measuring points
2nd 1-phase voltage measuring points
3rd 3-phase current measuring points
4th 1-phase current measuring points
The 1st measuring point found with a valid signal is used for specifying the frequency in the PMU function
group.
In the case of 3-phase measuring points, the positive-sequence system can also be transmitted instead of or in
addition to 3 individual sychrophasors. You can make the selection using the (_:10621:103) Positive
sequence parameter, see 9.9.8 Application and Setting Notes, Parameter: Positive sequence, Page 874.
PMU communication according to standard IEEE C37.118 is a client-server communication format in which the
PDC (Phasor Data Concentrator) functions as both the client and the server.
Once the PDC has been successfully connected to the device PMU and the PMU configuration data has been
queried, the PDC initiates transmission of the synchrophasor data by sending a close command to the PMU. If
you use the method of spontaneous data transmission via UDP, data output starts immediately after the
device boots without a close command to the PMU.
The values and names for the values are transmitted for the phasors, binary information, and analog channels.
The names for the phasors and binary information are automatically generated by the respective PMU function
groups. You must enter the analog-channel names yourself.
If necessary, you can edit the names for the phasors, binary information, and analog-channel data and assign
your own designations for them. For more information, see chapter 9.9.6 Parameterizing the PMU with DIGSI.
As an example, the names (generated) for measuring points or binary information may be as follows:
Name Displayed in the DIGSI Function Depending on the Connection Type, Name Transferred to the
Group Connections PDC (in case it cannot be assigned automatically)
Measuring point V-3ph 1[ID 1] MP-V3ph VAB ID01
MP-V3ph VBC ID01
MP-V3ph VCA ID01
MP-V3ph VA ID01
MP-V3ph VB ID01
MP-V3ph VC ID01
MP-V3ph V1 ID01
MP-V3ph VN ID01
Measuring point I-3ph 1[ID 2] MP-I3ph IA ID02
MP-I3ph IB ID02
MP-I3ph IC ID02
MP-I3ph I1 ID02
MP-I3ph IN ID02
Measuring point I-1ph 1[ID 3] MP-I1ph ID03
Measuring point V-1ph 1[ID 4] MP-V1ph ID04
Data is transmitted continuously from the PMU to the PDC at the configured reporting rate. The transmission is
terminated by a corresponding trip command from the PDC or when the connection between the PDC and the
PMU is interrupted.
Communication between the PMU and the PDC can be passed via TCP or UDP protocols.
The following ports are used for data transmission by default:
NOTE
i When configuring the ports, do not set any ports already being used by other communication protocols.
Configuring ports used elsewhere prevents communication with the PMU. In this case, data packets from
the PDC cannot be received, and inquiries from the PMU cannot be transmitted.
If you are using the UDP protocol for communication between the PMU and the PDC, you can set either
command mode or asynchronous response mode as the communication mode. In asynchronous
response mode, data can be transmitted continuously to preset PDC destination addresses in IEEE C37.118
format without a PDC having to request transmission of the synchrophasor data via a close command to the
PMU.
Up to 4 different PDCs can be connected to one device PMU at the same time. The IP addresses of the
maximum 4 PDCs are set in the PMU function group. If 4 device PMUs are configured, this enables support for
up to 16 PDCs.
You configure and parameterize the Phasor Measurement Unit with DIGSI. After a device has been added in a
DIGSI project, one or more communication modules that support synchrophasors can be configured as PMUs.
The device module supports a maximum of 2 communication modules that can be configured as PMUs. If
more than 2 PMUs are needed, the device must be expanded with a CB202 plug-in module assembly (expan-
sion module), which can accommodate 2 more communication modules.
The following communication modules support synchrophasors:
[sc_commod, 1, en_US]
NOTE
i Port M of the CB202 plug-in module assembly is used to accommodate measuring-transducer modules and
cannot be used for the installation of communication modules.
Addressing
You must configure the respective Ethernet address (IP address, subnet mask, etc.) for each communication
module in DIGSI. This is done in the DIGSI General settings properties dialog of the communication module in
item Ethernet addresses and so forms the IP address for the respective PMU.
[sc_ethern, 2, en_US]
In the Protocols – Communication menu, select the synchrophasor protocol; see the following figure.
[sc_protoc, 2, en_US]
After you have selected the synchrophasor protocol for the communication module, a settings dialog for PMU-
specific configuration opens in Settings; see the following figure.
[sc_wildcard, 3, en_US]
You configure the specific settings for the communication protocol in the top section of this settings dialog. In
the bottom section, you specify the corresponding PMU-specific settings.
In order to permit a better configuration of larger wide-area supervision systems, changes have been imple-
mented in the IEEE C37.118 communication configuration that permit a flexible IP configuration without the
loss of safety aspects in the networks administered.
Configurable placeholders are allowed for every PDC/IP address with the TCP PMU transmission protocol in
general and with UDP in the Communication mode Commanded operation. These placeholders allow you
to define a range of IP addresses where they are accepted within these accesses. The purpose of this is to
permit each individual device or system access within the respective network without limits with regard to
their hierarchy level. Therefore, with regard to security aspects, the limitation to individual IP addresses is
eliminated. You are thus allowed to configure complete sections of IP addresses in each PMU and, as a result,
very flexible when making changes to the configuration of the entire network, for example. The placeholder
character must follow consecutively at the bit level, starting with the bit with the lowest value.
• Placeholder: 0.0.0.127
The device accepts requests within the IP address range of 192.172.16.1 to 192.172.16.127.
Example 3:
• Placeholder: 0.0.0.3
The device accepts requests within the IP address range of 192.172.16.100 to 192.172.16.103.
If a PDC attempts to establish a connection to the device, the PDC IP addresses and corresponding place-
holders are checked in the same order as they had been configured (IP address PDC1, IP address PDC2,
IP address PDC3). Running through the list is stopped with the first match of the IP address, placeholder, and
requested IP-address range and the connection is built-up. If there are no matches, the attempt to connect is
rejected.
If you have configured the IP address 0.0.0.0 and the placeholder 255.255.255.255, every IP address received
is accepted as valid. This could be of use in the course of commissioning measures.
NOTE
i You must have configured at least one IP address to establish a connection between the device and the
PDC.
If you set UDP as the transmission protocol, you can transmit PMU data to groups of PDCs using IP multicast.
Using multicast, considerably more PDCs can be reached via one communication module than when every
PDC connects in unicast mode. Usually, the address range from 224.0.0.0 to 239.255.255.255 is used.
NOTE
i The router used must support the IGMP (Internet Group Management Protocol) V3 protocol.
[sc_PMU_multicast01, 1, en_US]
Make a checkmark at the Use multicast parameter. If Use multicast is checked, you can set up to
2 multicast IP addresses. If you do not put the checkmark in place, the settings for the multicast IP addresses
are not displayed.
[sc_PMU_multicast03, 1, en_US]
NOTE
i DIGSI does not check the validity of the set multicast IP address. A multicast IP address of 0.0.0.0 is ignored.
You can set the settings for the multicast IP addresses and the PDC IP addresses in the Access Control List. If
Use multicast is active, all data packages of the PMU are transmitted to the parameterized multicast
IP addresses, but not to the PDC IP addresses. Commands from PDCs in the Access Control List are processed as
if operating without multicast. Responses are only transmitted by way of the multicast IP addresses. In the
Command mode UDP communication mode, you need at least one additional PDC IP address in the Access
Control List to start PMU data transmission (see Figure 9-13).
[sc_PMU_Multicast_Access, 1, en_US]
EXAMPLE
Multicast Operation
[dw_PMU_multicast_config_with_whitellist_PDC, 1, en_US]
Select the communication module in the Hardware and protocols menu in DIGSI. Set the IP address of the
PMU (192.168.100.1) under Properties → Ethernet addresses.
[sc_IP_comm-mode_de, 1, en_US]
After you have selected the synchrophasor protocol for the communication module, a settings dialog for PMU-
specific configuration opens in Settings; see the following figure. Set the communication mode to Asyn-
chronous response mode.
[sc_general_spon_mode, 2, en_US]
In the following dialog, you set the IP addresses of the multicast routers:
[sc_PMU_multicast03, 1, en_US]
Figure 9-16 Additional Multicast IP Addresses During PMU Transport: UDP and Multicast
If you are using the asynchronous data transmission method, set the PMU transport parameter to UDP
and the Communication mode parameter to Spontaneous operation. The PMU data are then sent cycli-
cally via UDP to every PDC/IP address permanently configured in DIGSI. You may not configure placeholders for
PDC/IP address ranges in this communication mode.
Data output starts immediately after the device has booted. In this way, a starting signal from the PDC is not
necessary to start data transmission.
[sc_spontan, 2, en_US]
The configuration dataset is transmitted 1x per minute. With the Spont. mode config type parameter,
you select the type for the configuration data record. With the Reporting rate parameter, you configure
the number of cyclic repetitions of the data packages. As UDP is a connectionless protocol, a preconfigured
destination device with its PDC/IP address is not required to be physically present and/or connected. This
allows uninterrupted provision of the data without bidirectional communication.
NOTE
i If you have not configured valid PDC/IP addresses and still activate option for spontaneous data transmis-
sion, no cyclic data telegrams are sent.
NOTE
i It is possible to configure IP addresses for various PDCs that are not present in the same subnetwork as the
COM module. Such configurations are considered valid and can be loaded into the device. However, if the
device transmits spontaneous data and configuration packages to these IP addresses, the PDC cannot be
reached with the deviating subnetwork destination addresses.
NOTE
EXAMPLE
COM-Module Address Configuration
• IP address: 192.168.100.1
Measuring-Point Assignment
After adding measuring points to the device, you can assign these measuring points to each configured PMU.
Figure 9-18 shows an example of how the device configuration can be supplemented with 2 additional input/
output modules. You connect the current and voltage inputs of these I/O modules to measuring points via the
DIGSI routing matrix, see example in Figure 9-19.
[sc_addios, 1, en_US]
[sc_routin, 1, en_US]
Figure 9-19 Assignment of the Current and Voltage Inputs of the Added Input/Output Modules on Meas-
uring Points
NOTE
i Consider that the maximum amount of measuring points that can be routed is limited by the device.
The maximum numbers of measuring points that can be routed for one PMU are:
phasors) must not exceed 80 per PMU. The limitation of the load model must also be considered, depending
on the device configuration.
[sc_fgconn, 1, en_US]
Figure 9-20 Connecting Measuring Points to the Configured PMU Function Groups
When these setting steps have been completed, the PMUs are fully configured. The PMU is a function group
that functions independently of all the other function groups instantiated in the device.
[sc_phasor_edit, 1, en_US]
Figure 9-21 Options for Editing the Names of the Individual Phasors
NOTE
i You can only rename each individual phasor when you set the parameter Positive sequence to no or
additionally in the function settings. Otherwise you will only be offered one single phasor for each 3-
phase measuring point for renaming.
[sc_PMU_bin_info_edit, 1, en_US]
Figure 9-22 Options for Editing the Names of the Individual Binary Channels
[sc_pmu_bif, 1, en_US]
[sc_analog_channel, 1, en_US]
Routing Indications
The routable indication ChannelLive of the PMU log
[sc_parami, 1, en_US]
You can also change the PMU settings directly on the device. To do this, select the desired PMU instance on
the device display. By selecting menu item Settings you then access the editable setting values (see
Figure 9-26). Note that the parameter Port cannot be changed, because this corresponds to the physical slot
position of the communication module in question.
[sc_devpmu, 2, en_US]
Figure 9-26 Changing the PMU Setting Values via the Device Display
You can also change the communication settings in the same way. To do this, select the corresponding
communication port in the Communication menu on the device display. From the Channel 1 menu item, you
can then access the detailed setting options for the IP or PMU communication settings (see Figure 9-27).
[sc_compmu, 2, en_US]
Figure 9-27 Changing the Communication Setting Values via the Device Display
Time Synchronization
In order to ensure the time accuracy of the PMU, you must select IRIG-B as the protocol for the GPS clock
(Figure 9-28) or, if an ETH-BD-2FO communication module is present, IEEE 1588 (Figure 9-29). With other
settings, the PMU function function group indicates that it is not time synchronized.
To detect a lack of synchronization quickly, also set the waiting time for the failure indication of the loss of
time synchronization to the smallest possible value, thus to 1 s.
NOTE
i For PMU applications, use the IEEE 1588 protocol on the ETH-BD-2FO communication module, because the
IEEE 1588 protocol that can be activated on the ETH-BA-2EL and ETH-BB-2FO modules does not deliver the
required accuracy.
[sc_activate_ieee_1588, 1, en_US]
Ensure that the domain number in the IEEE 1588 settings matches that of the switch used.
[sc_para_ieee_1588, 1, en_US]
[sc_choose_of_time, 1, en_US]
When selecting the switch used, make sure it supports the PTP standard IEEE 1588. Siemens recommends the
RUGGEDCOM RSG2488.
Parameter: Mode
NOTE
i Different setting values are shown or hidden, depending on the rated frequency set. You can set a
reporting rate of 200 frames/s (50 Hz) or 240 frames/s (60 Hz) only when using an ETH-BD-2FO module.
The setting you make here is then valid for all PMUs with 3-phase measuring points.
Parameter: Class
Parameter: Port
This parameter cannot be set, because the Port results from the physical position where the corresponding
communication module is inserted.
9.9.9 Settings
Measuring transducers with an input rated at 20 mA can be used in the devices. 4 such inputs are available as
module ANAI-CA-4EL, which can be plugged into a communication module slot (for instance, port E or F). Up
to 4 such modules can be plugged in. Typically, slowly changing process variable such as temperature or gas
pressure are recorded with such 20-mA measured values and reported to the substation automation tech-
nology.
The measuring-transducer blocks are embedded in the Analog units function group and contain input and
output channels that are configurable independently of each other.
[dw_strumu, 1, en_US]
The 20-mA inputs typically transmit a value which represents a physical quantity such as a temperature or a
pressure. Therefore, the device must contain a characteristic curve that assigns the physical quantity to the
20-mA value. If the parameter Range active is not activated (no x in the check box), the function operates
over the range -25.6 mA to +25.6 mA. The setting of the range for the scaled value goes from a usable range
of -25.6 mA to +25.6 mA. The following figure shows an example.
[dw_klbsp_1, 3, en_US]
In this example, the measured value 0 mA means a temperature of 0 degrees Celsius and the measured value
20 mA means a temperature of 100 degrees Celsius. Thus, Unit = °C and Conversion factor = 100 are
entered. The resolution (decimal place) of the temperature value can be selected; for one decimal place, select
Resolution = 0.1.
[sc_transd, 1, en_US]
If a value smaller than -25.6 mA or larger than +25.6 mA is applied to the measuring-transducer input, the
measured value is marked as outside the range of values. If the parameter Range active is activated, the 2
additional parameters Upper limit and Lower limit appear. Both limiting values indicate the input
currents in mA, for which the value set by the Conversion factor (Upper limit) and the value 0
(Lower limit) of the calculated measurand are valid (see following figure).
[dw_kl_example_2, 1, en_US]
In this example, Range active is selected. The Upper limit is at 15 mA, the Lower limit is at 5 mA
and the Conversion factor remains at 100. Overall, this results in a characteristic curve as shown in the
following figure, taking into account all possible valid measured values from -25.6 mA to +25.6 mA. The
parameter Upper limit - Sensor is the calculated measured value if the input current corresponds to the
value in the Upper limit setting. The parameter Lower limit - Sensor is the calculated measured
value if the input current corresponds to the value in the Lower limit setting.
[dw_klges_2, 3, en_US]
[sc_trans2, 2, en_US]
Each measuring-transducer input provides the scaled measured value (these are the temperature values in the
examples) and the original current measured value in mA in the information routing for further processing.
The measuring-transducer values can be displayed in the display image and processed with CFC charts.
Parameter: Unit
Parameter: Resolution
Parameter: Upper limitLower limitUpper limit - Sensor and Lower limit - Sensor
9.10.5 Settings
• Allows an adaptation of maintenance intervals for switching contacts of the circuit breakers according to
the real abrasion
• Sends a warning signal when the abrasion of the circuit breaker reaches a certain degree
The function Circuit-breaker monitoring can be used in the function group Circuit-breaker.
The function offers 5 independent operating methods with different measuring methods:
• ΣIx-method
Sum of the breaking-current potentials
• 2P-method
2 points method for calculating the remaining switching cycles
• I2t-method
Sum of all breaking-current square integrals
• Make time
Monitoring of the circuit-breaker make time
• Break time
Monitoring of the circuit-breaker break time
9.11.3.1 Description
• The binary input signal >Start calc. for open is initiated, for example, via an external signal.
• The signal for the closed position of the circuit breaker is going. This signal is built via the circuit-breaker
auxiliary contacts. Thus, a manual opening of the circuit breaker is detected.
The method Make time is started if one of the following criteria is met:
• The binary input signal >Start calc. for close is initiated, for example, via an external signal.
The method Break time is started if one of the following criteria is met:
• The binary input signal >Start calc. for open is initiated, for example, via an external signal.
Definition of the Times when Opening and Closing the Circuit Breaker
With the paramter Make time, you define the point in time when the circuit-breaker poles are closed and the
current has reached a constant value.
[dw_maketime, 1, en_US]
With the parameter Opening time, you define the point in time when the circuit-breaker poles begin to
open. With the parameter Break time, you define the point in time when the circuit-breaker poles are sepa-
rated and the arc is extinct. The following graphic shows the relation between these 2 points in time of the
circuit breaker.
[dw_breaktime, 1, en_US]
NOTE
i The following parameters apply to one phase. The descriptions apply similarly to the parameters of the
remaining phases.
9.11.3.3 Settings
9.11.4.1 Description
[lo_Ix-calc, 1, en_US]
[lo_cb_wixf, 2, en_US]
[fo_CB-WI-xA, 1, en_US]
Where:
x Parameter exponent
q No. of circuit-breaker switching cycle
Tripping/opening current of phase A to the power of x in the qth circuit-breaker operation
The phase-selective ΣIx value is available as statistical value. You can reset or preset the statistics according to
the specific application.
To simplify the interpretation of the sum of the tripping current powers, the values are set in relation to the
exponentiated rated normal current Irated of the circuit-breaker (see also Setting notes).
NOTE
i The following parameters apply to one phase. The descriptions apply similarly to the parameters of the
remaining phases.
Parameter: Active
Parameter: Exponent
You use the Exponent parameter to specify the exponent for the ΣIx method.
A typical value is the default setting of 2. However, due to practical experiences with individual circuit
breakers, slightly different values may be requested.
Parameter: Threshold
9.11.4.3 Settings
9.11.5 2P Method
9.11.5.1 Description
[lo_2P-calc, 1, en_US]
2 points and their connecting line determine the relationship of switching cycles and tripping current. Point P1
is determined by the number of permitted switching cycles at rated normal current Irated. Point P2 is deter-
mined by the maximum number of switching cycles at rated short-circuit breaking current Isc. The 4 associated
values can be configured with the parameters Rated normal current, Switching cycles at Ir,
Rated short-circ.cur. Isc, and Switching cycles at Isc.
[dw_CB_WOpC, 1, en_US]
As shown in the preceding figure, a double-logarithmic diagram, the straight line between P1 and P2 can be
expressed by the following exponential function:
[fo_CB-W2-P1, 1, en_US]
Where:
Itrip Tripping/opening current
Irated Rated normal current
m Slope coefficient
b Switching cycles at rated normal current
n Number of switching cycles
The general line equation for the double-logarithmic representation can be derived from the exponential func-
tion and leads to the coefficients b and m.
NOTE
i Since a slope coefficient of m < -4 is technically irrelevant, but could theoretically be the result of incorrect
settings, the slope coefficient is limited to -4. If a coefficient is smaller than -4, the exponential function in
the switching-cycles diagram is deactivated. The maximum number of switching cycles with Isc is used
instead as the calculation result for the current number of switching cycles, as the dashed line with m =
-4.48 shows in following figure.
[dw_CB_WSlo, 1, en_US]
If the 2P-method stage receives the logic release signal, the current number of used up switching cycles (in
relation to the number of switching cycles at rated normal current) is calculated based on the determined trip-
ping current. This value is subtracted from the the remaining lifetime (switching cycles). The remaining life-
time is available as statistic value. For better understanding, refer to the example below.
You can reset or preset the statistical values according to the specific application. The reset operation changes
the statistic values to 0, and not to their default values of 10 000.
The statistic value of the residual switching cycles is calculated according to the following formula:
[fo_CB-2P-wear-rest_01, 1, en_US]
Where:
i No. of latest circuit-breaker switching cycle
2p wear resti Residual switching cycles with rated normal current, after the ith switching cycle
nrated Overall permissible switching cycles at rated normal current
ntrip Overall permissible switching cycles at tripping current Itrip
nrated/ntrip Lost switching cycles referring to rated normal current
EXAMPLE
For calculating the residual switching cycles of a circuit breaker, the following is assumed:
P1 (2.5 kA, 10 000)
P2 (50.0 kA, 50)
The circuit breaker has made 100 opening operations with rated normal current, 2 tripping operations with
rated short-circuit breaking current, and 3 tripping operations with 10 kA tripping current. Then, the residual
switching cycles with rated normal current are:
[fo_CB-2P-wear-rest_02, 1, en_US]
There are still 9465 possible break operations at rated normal current.
NOTE
i The following parameters apply to one phase. The descriptions apply similarly to the parameters of the
remaining phases.
Parameter: Active
Example
Here is an example that shows you how to set the threshold parameters. Assuming a circuit breaker with the
same technical data as provided in the example for residual switching cycles, 50 breaking operations with
rated short-circuit breaking current are permitted.
A warning signal should be issued when the number of possible breaking operations with rated short-circuit
breaking current is less than 3. For that condition, you set the threshold value based on the following calcula-
tion:
[fo_CB-W2-P4, 1, en_US]
9.11.5.3 Settings
9.11.6.1 Description
[lo_I2t-calc, 1, en_US]
[fo_CB-WI-2T, 1, en_US]
Where:
Irated Rated normal current
iA(t) Sampled measured current value of phase A
The calculated squared tripping current integrals are added to the existing statistic values.You can reset or
preset the statistic value according to the specific application.
Parameter: Active
Parameter: Threshold
9.11.6.3 Settings
9.11.7.1 Description
[lo_LS-Überwachung_Einschaltzeit, 1, en_US]
Operating Mode
The stage for the monitoring of the circuit-breaker make time calculates phase-selectively the time between
the circuit-breaker closing command and the point in time when the current exceeds the Oper.current
threshold. If this threshold has not been exceeded after 2.5 times the value of the parameter Make time,
the measurement is canceled and the output value Make time is set to 0 and marked with the quality invalid.
If one phase of the current has exceeded the parameter Oper.current threshold or the parameter
Current thresh. CB open at the time of the circuit-breaker closing command, the measurement is
canceled and the output value Make time is marked with the quality invalid.
You can define 2 independent thresholds for the monitoring of the measured make time. When these thresh-
olds are exceeded or undershot, the corresponding outputs Make-time warning and Make-time alarm
are activated for 100 ms. These can be routed in the log.
NOTE
i The following parameters apply to one phase. The descriptions apply similarly to the parameters of the
remaining phases.
Parameter: Active
9.11.7.3 Settings
9.11.8.1 Description
[lo_LS-Überwachung_Ausschaltzeit, 1, en_US]
Operating Mode
The stage for the monitoring of the circuit-breaker break time calculates phase-selective the time between the
circuit-breaker opening command and the point to which no load current flows. In the event of a restrike after
the current was lost, the measurement of the break time is extended accordingly. If a current is still measured
after 2.5 times of the value parameter Break time, the measurement is canceled and the output value
Break time is set to 0 and marked with the quality invalid.
If no load current is measured at the time of the break time command, the measurement for the relevant
phase is canceled and the output value Break time is marked with the quality invalid.
You can define 2 independent thresholds for the monitoring of the measured break time. When these thresh-
olds are exceeded or undershot, the corresponding outputs Break-time warning and Break-time
alarm are activated for 100 ms. These can be routed in the log.
NOTE
i The following parameters apply to one phase. The descriptions apply similarly to the parameters of the
remaining phases.
Parameter: Active
9.11.8.3 Settings
Display
After starting system visualization, you can see the current switchgear diagram in the application window. You
cannot change the structure of the switchgear diagram here. However, you can edit it using the Single-line
Editor and transfer it to the device again.
[sc_bbp_sle_online, 2, en_US]
• Topological coloring of busbars, lines, disconnectors, and circuit breakers. In overlapping sections of the
protection zones in the bus coupler, the lines are displayed in alternating colors (protection view).
The up-to-date phase currents of the current transformers and measuring systems are displayed in measured-
value boxes. The 1st row of each measured-value box shows the designation of the measuring system or of
the bay and of the current transformer. Measured-value boxes for transformers display the transformer
current, optionally the primary, secondary, or in percent.
NOTE
i The percentage values of the differential and restraint currents refer to the normalization currents. The
percentage values of the feeder currents refer to the transformer rated current of the corresponding
feeder.
NOTE
i If the check zone is disabled, no measured values are displayed in the measured-value box of the check
zone.
NOTE
i For an easier analysis of the protection response, the current values are displayed in the fault record from
the view of the protection, thus following algorithmic processing. That is, for example, the stabilization
factor k is taken into account in the restraint current. The restraint currents of the check zone must be
mentioned as a special feature: In an extreme case (bus fault with all currents directed to the busbar), the
resulting restraint current of the check zone is 0 because the outgoing current is 0.
NOTE
i The filtered differential and restraint currents are displayed in the measured-value boxes of the bus
sections.
NOTE
i If 2 busbars are connected to one another with a busbar shunt by disconnectors, then only the measured-
value boxes of the busbar with the higher priority (with the lower instance number such as BB1) are visible.
The measured-value box for a transformer shows the up-to-date feeder currents assigned to the transformer.
You can show/hide the measured-value boxes.
²
In the toolbar, click . The configuration of the measured-value boxes is displayed just like you speci-
fied in the Single-line Editor.
with the higher priority are displayed. You can specify the colors used in the display during engineering in the
Single-line Editor with the selected object using the right mouse button via the Object properties menu.
² Check the display and change it if necessary in the Single-line Editor.
• There may be hazardous voltages in all switching components connected to the power supply and to
measurands or test quantities.
• Hazardous voltage may be present in the device even after the supply voltage has been removed (capaci-
tors can still be charged).
• Never exceed the limiting values indicated in chapter Technical Data, even during testing and commis-
sioning.
• The measuring accuracy to be attained depends on the electrical data of the test sources. Due to the
phase-selective measuring principle, two 1-phase current sources that can be controlled separately are
sufficient for the tests.
! WARNING
Warning of danger from secondary tests
Noncompliance with safety notes means that death, serious injuries, or significant material damage
can occur.
² Secondary tests may be done only by qualified electrical engineering personnel who are familiar with
the commissioning of protection systems, with the operation of the system and with safety regula-
tions and provisions (switching, grounding, etc.).
² Make sure that there are no connections to the primary system during the secondary test.
! DANGER
Danger due to hazardous voltages during the operation of electric devices
Noncompliance with the safety notes will result death or severe injuries.
² Before disconnecting the power supply to the equipment, short circuit the secondary connections of
the current transformer.
² If a test switch is installed that automatically short circuits the secondary wires of the current trans-
former, check the short-circuiting device and turn the test switch to its Test position.
NOTE
i Observe the information regarding testing with secondary quantities in chapter Commissioning in the
manual SIPROTEC 5 Operating.
10.5.1 Overview
The test setup for the busbar-selective protection is shown in Figure 10-2. The trip command of the feeders
switches off the test equipment.
The test setup for the check zone is shown in Figure 10-4. In order to test the busbar selectivity, at least one
bay must be switched to a second busbar (applies also to disconnector-position simulation).
² Connect the test currents directly to the measuring inputs of the bay currents.
Depending on the setting, the rated current of the bays is 1 A or 5 A.
Test Setup
² For the test, use 2 bays with the same normalization factor (transformer ratio). Do not use a busbar
section disconnection bay or bus coupler bay.
² Connect both bays to the same busbar.
[dw_prkess, 1, en_US]
Figure 10-2 Test Setup for Recording the Characteristic Curve of the Busbar-Selective Measuring System
Test Items
² Switch off the differential current supervision function. This prevents blocking the protection during the
test (parameter (_:12031:1) Mode).
² Set the differential current limit and the restraint factor for the busbar-selective protection (parameter
(_:12091:100) Threshold Idiff and (_:12091:104) Stabilization factor k) and for
the check zone (parameter Threshold Idiff and Stabilization factor k) as desired.
² Test currents I1 and I2 must have a phase displacement of 180°. Use the same current to check bay 1 and
bay 2 (1 x IN) in order to determine the phase position.
If the connection is correct, the differential current must be close to 0 and the restraint current should be
equal to twice the input current.
² Set current I1 and I2 = 0. Increase the current I1 until a trip command is generated.
The current in the bay must be identical to the differential current limit set in parameter (_:12091:100)
Threshold Idiff.
² Supply a constant current to bay 1 and bay 2 of the test equipment.
(Idiff =0, Irest = I1 + I2, I1 = I2). The current must exceed the set differential current limit.
[dw_char_ss, 2, en_US]
The following history shown in Figure 6-9 applies to the sensitive characteristic curve.
² Repeat the test by using different constant currents.
² After the test, switch on the differential current supervision function with parameter (_:12031:1)
Mode.
The trip decision of the check zone can be queried phase-selectively. This allows a test that is independent
from the busbar-selective protection.
Test Setup
² For the test, use 3 bays with the same normalization factor (transformer ratio). Do not use a bus section
bay or bus coupler bay.
² Connect bay 1 and bay 2 to the same busbar.
² Switch the current inputs of bay 1 and bay 2 against each other.
² Connect bay 3 to another busbar.
[dw_prkecz, 1, en_US]
Figure 10-4 Test Setup for the Characteristic Curve Support of the Check Zone
Test Items
² Switch off the differential current supervision function. This prevents blocking the protection during the
test (parameter (_:12031:1) Mode).
² Set the differential current limit and the restraint factor:
Busbar-selective protection (parameters (_:12091:100) Threshold Idiff and (_:12091:104)
Stabilization factor k) and
check zone (parameters (_:11911:100) Threshold Idiff and (_:11911:104) Stabiliza-
tion factor k).
² Test current I1 must have a phase displacement of 180° in bay 1 and bay 2
(Idiff = 0, Irestr = 2 x I1 of the assigned busbar).
If the connection is correct, the differential current must be close to 0 and the restraint current should be
equal to twice the input current.
² Set the current I1 = 0. Increase current I2 until the phase-specific indication Operate diff. prot. is
issued for the check zone.
The current I2 must correspond with the differential current limit set in parameter (_:11911:100)
Threshold Idiff for the check zone.
² Supply a constant current I1 to bay 1 and bay 2 of the test equipment.
Subsequently, the differential current is I2 and the restraint current is I1. Therefore, it follows that the stabiliza-
tion factor k of the check zone is equal the ratio I2 to I1
² Repeat the test by using various restraint currents I1. The characteristic curve is shown in Figure 6-8.
In order to check the busbar-selective protection, the busbar-selective protection must be set to a more sensi-
tive level than the check zone. This ensures that the supervision function of the differential current of the
check zone picks up later.
Test Setup
² Refer to chapter 10.5.2 Busbar-Selective Protection to assemble the test setup.
Test Items
² Set the differential current limit (_:12031:100) Thresh. Id superv. BZ and the time delay
(_:12031:102) Id superv. t. delay as desired.
If the parameter (_:12031:103) Id superv. reaction BZ is set to Blocking until dropout or
Blocking until release, follow the next steps:
² Connect bay 1 and bay 2 to separate busbars.
² Slowly increase current I1 in bay 1 until the indication of the differential current supervision function is
issued. The current must match the pickup threshold set in parameter (_:12031:100) Thresh. Id
superv. BZ.
This blocks this busbar. Even increasing current I1 again does not initiate tripping.
² Switch the current in bay 2 to 4 times the rated current Irated.
This trips the busbar section. Subsequently, the protection system initiates the trip command for the circuit
breaker in bay 2.
The last 2 test items ensure that differential current supervision is busbar-selective.
If the parameter (_:12031:103) Id superv. reaction BZ is set to Alarm only or , follow the next
steps:
² Connect bay 1 and bay 2 to the same busbar.
² Slowly increase current I1 in bay 1 until the indication of the differential current supervision function is
issued. The current must match the pickup threshold set in parameter (_:12031:100) Thresh. Id
superv. BZ .
² Continue increasing the current until the busbar section trips.
Subsequently, the protection system switches off the current in bay 1 and bay 2.
In order to verify the check zone, the sensitivity of the check zone must be set higher than the busbar-selective
protection function. This ensures that the supervision of the check zone picks up earlier.
Test Setup
² Refer to chapter 10.5.2 Busbar-Selective Protection to assemble the test setup.
Test Items
Checking the pickup threshold and time delay:
² Slowly increase the current in bay 1 until the supervision function of the check zone trips. The measured
current must be identical to the set current (_:12031:101) Thresh. Id superv. CZ.
² Follow chapter 10.6.3 Time Delay to perform the time measurement.
Conventional test equipment for protection equipment can be used for measuring the time.
² Use the test equipment to start a current in bay 1 that is twice as high as the set differential current limit
(_:12031:100) Thresh. Id superv. BZ.
The message of the differential current supervision function terminates the test equipment. The measured
time corresponds to the set time delay in parameter (_:12031:102) Id superv. t. delay.
10.7.1 General
NOTE
i Also observe the information regarding testing with primary quantities in chapter Commissioning in the
SIPROTEC 5 Operation manual.
The test procedure of the system with primary quantities depends on whether the system is being commis-
sioned for the first time or if the system has been operated before.
² Use a test current to check the system.
- or -
² Use the operating current to check the system.
When performing a primary test with a test current, check the correct parameterization of the current trans-
former for the following settings:
• Polarity
• Transformer ratio
[dw_fctpan, 1, en_US]
² In the reference bay, connect the phase to be tested to the current generator by way of the closed line
grounding switch.
² Open the solid connection to the ground.
If the system is already in operation, it is often not possible to use a test generator. In this case, the operating
current is used for testing the correct parameterization of the current transformer for the following settings.
• Polarity
• Transformer ratio
10.8.1 General
NOTE
i Always keep in mind the local conditions, the station plans, and protection plans.
NOTE
i Siemens recommends isolating the circuit breakers of the tested feeders at both ends before starting the
tests.
General Precautions
! CAUTION
Tests on the local circuit breaker of the feeder cause a trip command to the output to the adjacent (busbar)
circuit breakers.
Noncompliance with the following measure can result in minor personal injury or material damage.
² In a first step, interrupt the trip commands to the adjacent (busbar) circuit breakers, for example, by
disconnection of the corresponding control voltages.
For testing the circuit-breaker failure protection, it must be ensured that the protection (external protection
device or device-internal protection functions) cannot operate the circuit breaker. The corresponding trip
command must be interrupted.
Although the following list does not claim to be complete, it can also contain points, which have to be ignored
in the current application.
Test Modes
The device and the function can be switched to test mode. These test modes support the test of the function
in different ways:
NOTE
i When the function or device is in test mode, all indications are given a test bit.
Start Caused by a Trip Command of an External Protection Device without Current Flow
² If it is possible to start without current flow, for example, pickup by routing the CB auxiliary contacts,
proceed as described before.
Termination
² All temporary measures taken for testing must be undone, such as special switch positions, interrupted
trip commands, changes to setting values, or individually switched off protection functions.
Test Setup
[dw_pr_svsv, 1, en_US]
Figure 10-6 Test Setup for Recording the Characteristic Curve of the Circuit-Breaker Failure Protection
Test Items
² Block the differential current supervision function to prevent the protection to initialize blocking during
the test.
² Set the parameter of the circuit-breaker failure protection to (_:102) Threshold phase current
the desired value.
² Use the busbar disconnector to connect bays 1 and 2 to the same busbar.
² Test currents I1 and I2 must have a phase displacement of 180°. Use the same current to check bay 1 and
bay 2 (0.5 x IN) in order to determine the phase position. If the connection is correct, the differential
current must be close to 0 and the restraint current should be equal to twice the input current.
² Supply bay 1 and bay 2 with constant current I (I1 = I2) from the test equipment. The test current must lie
below the threshold for the phase current
² After triggering the feeder protection, instead of using the 1-channel or 2-channel binary input, for
example, using the definite time-overcurrent protection, increase the current in the bays, until it exceeds
the set threshold.
The protection is tripped (circuit-breaker failure protection trip).
Test Setup
The test setup for measuring the time delay is shown in Figure 10-6.
Test Items
² Ensure the bays are supplied with a current that is equal to twice the value of the parameter (_:102)
Threshold phase current of the CBFP in the bay. This current matches an external error. The differ-
ential current should be approximately 0.
² Simulate the trip command from the feeder protection for bay 2 and start measuring the time.
² Use the trip command of the busbar protection to stop the time measurement.
The displayed time is equal to the preset time delay, plus the tripping time of the protection.
[dw_cbch01, 1, en_US]
[dw_zecbc1p2, 2, en_US]
Test Procedure
The following conditions must be satisfied before the circuit-breaker test can start:
² If a circuit-breaker auxiliary contact reports the position of the breaker pole to the device via the binary
inputs of the signal Position, the test cycle is not initiated unless the circuit breaker is closed.
² If the circuit-breaker auxiliary contact has not been routed, you must ensure that the circuit breaker is
closed.
² The circuit breaker must be ready for an open-closed cycle or an open-only cycle (indication >Ready).
² A protection function must not have been picked up in the circuit-breaker protection function group
responsible for the circuit breaker.
[sc_cbtest3p, 1, en_US]
Figure 10-10 shows the chronological sequence of an open-closed cycle as an example. If you have activated
the Open only option, the close command is not executed and the dead time not taken into consideration.
If a circuit-breaker auxiliary contact is connected, the function waits for the indication circuit breaker Posi-
tion = open after the trip command is generated. When the indication Position = open is received, the
close command is transmitted during an open-closed cycle after a dead time (parameter (_:6151:101)
Dead time). If the feedback from the circuit-breaker positions is not received within the maximum transmis-
sion time (Dead time + 2 · Output time + 5 s), the circuit-breaker test is aborted and considered to be
failed. The proper functioning of the circuit breaker is monitored via the feedback on the circuit-breaker posi-
tions.
[dw_cbch03, 1, en_US]
With the Use current-flow criterion parameter, you can also specify that a circuit-breaker test is only
executed if the current flowing through the circuit breaker does not exceed a specific current threshold
(Current threshold parameter). Otherwise, the circuit-breaker test is not started.
² If the current-flow criterion is disabled, the current threshold is not evaluated. Then, the circuit-breaker
test is performed independent of the magnitude of current flowing through the circuit breaker.
You can start the test program as follows:
• Via DIGSI
• Via control commands, which you can also connect in the CFC
The following figure illustrates operation of the circuit-breaker test in DIGSI.
[sc_cb_1-3pol, 1, en_US]
² Select the function in the project tree on the left in the online access.
² Start the desired test program in the upper portion of the working area.
² The corresponding feedback is displayed in the bottom portion of the working area. Additional informa-
tion about the behavior of other functions while the circuit-breaker test is being performed can be read in
the operational log.
2 Binary Inputs
² Make sure that the binary inputs used are isolated.
1 Binary Input
² Make sure that, in the circuit of the 2nd circuit-breaker auxiliary contact, an equivalent resistance R is
connected.
² Observe the dimensioning notes under the section Equivalent resistance R.
If the devices are connected to one another via the protection interface and switched on, they contact each
other automatically. If, for example, device 1 recognizes device 2, the successful connection is indicated (see
next figure). Accordingly, each device signals to all devices that a communication is available.
The following information is provided via the protection interfaces by the devices in the device combination:
• Signal-transit time in the transmission and reception direction of the telegrams between the local device
and the neighboring device
You can find this diagnostic data in DIGSI under the following menu structure:
[sc_protec, 1, en_US]
NOTE
i To reset the measured values for the protection interface directly in the device, proceed as follows:
Device functions > x Device protection comm. > Protection interface y > Release measured values.
Proper communication of the devices among each other can be supervised during operation.
² Check the connections for each protection interface in DIGSI 5.
If a connection is successfully established, the Status of topo recog. field shows the indication valid in DIGSI
5 (see Figure 10-12).
If 2 devices are parameterized incorrectly, the Status of topo recog. field shows the indication invalid (see
Figure 10-12).
In Figure 10-13 there is no communication between device 1 and device 2, that is, the protection interfaces 1
and 2 of device 1 do not receive data. One reason for this can be a remote control with DIGSI via the protec-
tion interface. In this case, the protection connection is interrupted and the connection is used exclusively for
DIGSI.
[sc_protcocol, 1, en_US]
Harmonic Analysis
² Superimpose on the fundamental-component current a test current of double frequency (2nd harmonic)
and test the pickup behavior with this.
² Cause a threshold value excess (internal pickup) for one of the protection functions that you want to
block.
- or -
² Apply a test current with a load current as lead (current step).
The inrush current detection creates a blocking signal.
CWA Process
² Create a test current that has flat ranges of a minimum width of 3 ms simultaneously in all 3 phase
currents.
The inrush current detection creates a blocking signal.
Current Inputs
All current, voltage, and power data are specified as RMS values.
Rated frequency frated 50 Hz, 60 Hz
Protection-class current trans- Rated current Irated Measuring range
formers
5A 0 A to 500 A
1A 0 A to 100 A
Consumption per current input at Approx. 0.1 VA
rated current
Thermal rating 500 A for 1 s
(protection-class current trans- 150 A for 10 s
formers) 20 A continuously
25 A for 3 min
30 A for 2 min
Dynamic load-carrying capacity 1250 A one half wave
All current, voltage, and power data are specified as RMS values.
Rated frequency frated 50 Hz, 60 Hz
GIS-LPCT input Primary rated current Irated Measuring range
Kr ⋅ GIS-LPCT secondary rated value Kpcr = 50 (protection channel)
Kr = Transformation ratio of the Kpcr = 1.6 (measuring channel)
GIS-LPCT (DIGSI setting)
Refer to the GIS manual for the GIS-
LPCT secondary rated value.
Power consumption per current Max. 40 mVA
circuit at rated current Burden = 9.5 kΩ
Thermal rating Max. input voltage = 20 V
Accuracy Class 5TPE (protection channel)
Class 0.2S (measuring channel)
Voltage Input
All current, voltage, and power data are specified as RMS values.
Rated frequency frated 50 Hz, 60 Hz
Input and output modules IO102, IO202, IO208, IO211, IO215
IO214
Measuring range 0 V to 200 V 0 V to 7.07 V
Burden < 0.1 VA < 0.01 VA
Thermal rating 230 V continuously 20 V continuously
All current, voltage, and power data are specified as RMS values.
Rated frequency frated 50 Hz, 60 Hz
Insulation class PELV (Protective Extra Low Voltage) (according to IEC 60255-27)
Connector type 8-pin terminal spring
Input channels 4 differential current inputs
Measuring range DC -20 mA to +20 mA
Tolerance 0.5 % of the measuring range
Maximum measuring range DC -25.6 mA to +25.6 mA
Input impedance 140 Ω
ADC type 16-Bit Delta-Sigma
Permissible potential difference DC 20 V
between channels
Galvanic separation from ground/ AC 500 V, DC 700 V
housing
Permissible overload DC 100 mA continuously
Sampling rate 5 Hz
Insulation class HLV (Hazardous Live Voltage) (in accordance with IEC 60255-27)
Connector type 8-pin terminal spring
Input channels 1 DC voltage input, channel 2 (CH2)
Measuring range DC 0 V to + 300 V
Tolerance 0.2 % of measuring range
Input impedance 260 kΩ
Galvanic separation against DC 4.6 kV
ground/housing
Max. permissible voltage against DC 300 V
ground on the measuring inputs
Sampling rate 16 kHz
Inputs for Optical Sensors for Arc Protection (via Module ARC-CD-3FO)
Attenuation In the case of plastic optical fibers, you can expect a path attenuation of
0.2 dB/m. Additional attenuation comes from the plug and sensor head.
Optical budget30 Minimal 25 dB
Analog sampling rate 16 kHz
ADC type 10-bit successive approximation
Transmitter
Type LED
Wavelength λ = 650 nm
Transmitter power Minimum 0 dBm
Maximum 2 dBm
Numerical aperture 0.5 31
Signal rate connection test 1 pulse per second
Pulse duration connection test 11 μs
NOTE
i Current and voltage must not be connected at the same time to one measuring transducer input. Instead,
only connect either current or voltage. For EMC reasons, do not connect a line to an unused input (current
or voltage).
Use shielded cables.
Table 11-3 Combined Data for Fast Measuring Transducer Voltage/Current Inputs
Temperature Inputs
Settings Value
Sensor Type PT100 (Class F 0.3 EN 60751)
4-wire shielded cable connection
Measurement range -50 °C to +180 °C
Accuracy ±1 °C
36 For time-critical applications with low-active signals, consider the specified dropout times. If necessary, provide for active discharge
of the binary input (for example, a resistor in parallel to the binary input or using a change-over contact).
Control voltage for all modules Adapt the binary-input threshold to be set in the device to the control
with binary inputs, except voltage.
module IO233 Range 1 for 24 V, 48 V, and 60 V Vlow ≤ DC 10 V
Control voltage Vhigh ≥ DC 19 V
Range 2 for 110 V and 125 V Vlow ≤ DC 44 V
Control voltage Vhigh ≥ DC 88 V
Range 3 for 220 V and 250 V Vlow ≤ DC 88 V
Control voltage Vhigh ≥ DC 176 V
Control voltage for binary inputs of Range for 125 V Vlow ≤ DC 85 V
the IO233 module Control voltage Vhigh ≥ DC 105 V
Maximum permitted voltage DC 300 V
The binary inputs contain interference suppression capacitors. To ensure EMC immunity, use the terminals
shown in the terminal diagrams/connection diagrams to connect the binary inputs to the common potential.
Special Binary Input with Maximized Robustness against Electrical Disturbances and Failures (IO216)
37 For time-critical applications with low-active signals, consider the specified dropout times. If necessary, provide for active discharge
of the binary input (for example, a resistor in parallel to the binary input or using a change-over contact).
Permissible current per contact (switching on and 30 A for 1 s (make contact only)
holding)
Short-time current across closed contact 250 A for 30 ms
Breaking capacity Max. 30 W (L/R = 40 ms)
Max. 360 VA (power factor ≥ 0.35, 50 Hz to 60 Hz)
Switching time OOT (Output Operating Time) Make time: typical: 8 ms; maximum: 10 ms
Additional delay of the output medium used Break time: typical: 2 ms; maximum: 5 ms
Max. rated data of the output contacts in accordance DC 24 V, 5 A, general purpose
with UL certification DC 48 V, 0.8 A, general purpose
DC 240 V, 0.1 A, general purpose
AC 240 V, 5 A, general purpose
AC 120 V, 1/6 hp
AC 250 V, 1/2 hp
B300
R300
Interference suppression capacitors across the 4.7 nF, ± 20 %, AC 250 V
contacts
Safety/monitoring 2-channel activation
11.1.5 ETH-BD-2FO
NOTE
i The firmware must be updated to version ≥ V7.90 if using the ETH-BD-2FO module. If the module is
connected to a device with a previous version, a hardware failure is reported that disappears with an FW
update to V7.90. As this is not an actual hardware failure, there is no need to send in the device.
The ETH-BD-2FO module offers the possibility of replacing the SFPs (Small Form-Factor Pluggable) delivered by
default for a communication route of up to 2 km by SFPs that can be ordered separately in order to adapt the
interface to different transmission media and longer routes.
Distance 24 km
Laser class 1 as per EN 60825-1/-2 With the use of 9 µm/125 µm optical fibers
Description SFP with RJ45 connector, for Ethernet protocols via an electrical inter-
face
Product code P1Z3201
Connector type RJ45
Baud rate 100 Mbit/s
Protocol
Max. line length 20 m with Ethernet patch cable CAT 6 S/FTP, F/FTP, or SF/FTP
Interface design Corresponds to IEEE 802.3, 100BaseTX
! CAUTION
Risk of burns due to high temperatures of the SFP pluggable transceivers
Noncompliance with the safety notes may result in medium or light injuries.
² The SFP pluggable transceivers can be disconnected and plugged in while in operation. Siemens
recommends switching off the device.
² Allow the SFP pluggable transceiver to cool as much as possible.
✧ Remove the connecting cables or the dust protection cap that was plugged on in the delivery state from
the SFP pluggable transceiver.
✧ In order to release the interlocking, open the bracket on the SFP pluggable transceiver.
✧ Pull on the bracket in order to pull the SFP pluggable transceiver out of the slot. The removal must be
possible with free movement and without great exertion of force.
✧ Provide the SFP pluggable transceiver with the dust protection cap so that the optics are protected from
contamination.
NOTE
i Check for secure positioning of the transceiver in the slot and whether it is locked in place in order to avoid
unintentional removal by pulling on the connection line.
Masses
Device Size
Weight of the Modular Devices
Type of construction 1/3 1/2 2/3 5/6 1/1
Flush-mounting device 4.4 kg 7.2 kg 9.9 kg 12.7 kg 15.5 kg
Surface-mounted device with inte- 7.4 kg 11.7 kg 15.9 kg 20.2 kg 24.5 kg
grated on-site operation panel
Surface-mounted device with 4.7 kg 7.8 kg 10.8 kg 13.9 kg 17.0 kg
detached on-site operation panel
Type of Max. Total wWidth x Max. Total Height x Max. Total Depth40, Rounded to full mm (in
Construction Inches)
Device width 1/3 1/2 2/3 5/6 1/1
Flush-mounting 150 mm x 225 mm x 300 mm x 375 mm x 450 mm x
device 266 mm x 266 mm x 266 mm x 266 mm x 266 mm x
231 mm 231 mm 231 mm 231 mm 231 mm
(5.91 x 10.47 x (8.86 x 10.47 x (11.81 x 10.47 x (14.76 x 10.47 x (17.72 x 10.47 x
9.09) 9.09) 9.09) 9.09) 9.09)
Flush-mounting 150 mm x 225 mm x 300 mm x 375 mm x 450 mm x
device with 266 mm x 266 mm x 266 mm x 266 mm x 266 mm x
IO240 277 mm 277 mm 277 mm 277 mm 277 mm
(5.91 x 10.47 x (8.86 x 10.47 x (11.81 x 10.47 x (14.76 x 10.47 x (17.72 x 10.47 x
10.91) 10.91) 10.91) 10.91) 10.91)
Type of Max. Total wWidth x Max. Total Height x Max. Total Depth40, Rounded to full mm (in
Construction Inches)
Flush-mounting 150 mm x 225 mm x 300 mm x 375 mm x 450 mm x
device with 266 mm x 266 mm x 266 mm x 266 mm x 266 mm x
IO111 243 mm 243 mm 243 mm 243 mm 243 mm
(5.91 x 10.47 x (8.86 x 10.47 x (11.81 x 10.47 x (14.76 x 10.47 x (17.72 x 10.47 x
9.57) 9.57) 9.57) 9.57) 9.57)
Surface- 150 mm x 225 mm x 300 mm x 375 mm x 450 mm x
mounted device 315 mm x 315 mm x 315 mm x 315 mm x 315 mm x
with integrated 341 mm 343 mm41 343 mm41 343 mm41 343 mm41
on-site operation (5.91 x 12.4 x (8.86 x 12.4 x (11.81 x 12.4 x (14.76 x 12.4 x (17.72 x 12.4 x
panel 13.43) 13.43) 13.43) 13.43) 13.43)
Surface- 150 mm x 225 mm x 300 mm x 375 mm x 450 mm x
mounted device 315 mm x 315 mm x 315 mm x 315 mm x 315 mm x
with detached 231 mm 231 mm 231 mm 231 mm 231 mm
on-site operation (5.91 x 12.4 x (8.86 x 12.4 x (11.81 x 12.4 x (14.76 x 12.4 x (17.72 x 12.4 x
panel 9.09) 9.09) 9.09) 9.09) 9.09)
Surface- 150 mm x 225 mm x 300 mm x 375 mm x 450 mm x
mounted device 315 mm x 315 mm x 315 mm x 315 mm x 315 mm x
with detached 277 mm 277 mm 277 mm 277 mm 277 mm
on-site operation (5.91 x 12.4 x (8.86 x 12.4 x (11.81 x 12.4 x (14.76 x 12.4 x (17.72 x 12.4 x
panel with 10.91) 10.91) 10.91) 10.91) 10.91)
IO240
Surface- 150 mm x 225 mm x 300 mm x 375 mm x 450 mm x
mounted device 315 mm x 315 mm x 315 mm x 315 mm x 315 mm x
with detached 243 mm 243 mm 243 mm 243 mm 243 mm
on-site operation (5.91 x 12.4 x (8.86 x 12.4 x (11.81 x 12.4 x (14.76 x 12.4 x (17.72 x 12.4 x
panel with 9.57) 9.57) 9.57) 9.57) 9.57)
IO111
Type of Construction Max. Width x Max. Height x Max. Depth (in Inches)
USART-Ax-xEL, ETH-Bx-xEL 61 mm x 45 mm x 121 mm (2.4 x 1.77 x 4.76)
USART-Ax-xFO, ETH-Bx-xFO (without protective cover) 61 mm x 45 mm x 133 mm (2.4 x 1.77 x 5.24)
ANAI-CA-4EL, ANAI-CE-2EL 61 mm x 45 mm x 120 mm (2.4 x 1.77 x 4.72)
ARC-CD-3FO 61 mm x 45 mm x 121 mm (2.4 x 1.77 x 4.76)
Minimum Bending Radii of the Connecting Cables Between the On-Site Operation Panel and the Base Module
Fiber-optic cable R = 50 mm
Pay attention to the length of the cable protection
sleeve, which you must also include in calculations.
D-Sub cable R = 50 mm (minimum bending radius)
For operator protection (back side) IP2x for current terminal (installed)
IP2x for voltage terminal (installed)
Degree of pollution, IEC 60255-27 2
Maximum operating altitude above sea level 2000 m (6561.68 ft)
UL Note
Type of Line Current Terminal Voltage Terminal with Voltage Terminal with
Spring-Loaded Terminals Screw Connection
Stranded wires with ring- 2.7 Nm No ring-type lug No ring-type lug
type lug
Stranded wires with boot- 2.7 Nm 1.0 Nm 0.6 Nm
lace ferrules or pin-type
lugs
Solid conductor, bare 2.0 Nm 1.0 Nm –
(2 mm2)
Blank stranded wire Not permitted 1 Nm 0.6 Nm
NOTE
i For current and voltage terminals, the maximum speed of the tool must not exceed 640 rpm.
NOTE
43 if provided
Operate Time
Frequency
Frequency range 50 Hz or 60 Hz
Tolerances
Setting Values
Dropout
The larger dropout differential (= | pickup threshold – dropout threshold |) of the following 2
criteria is used:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies to the current threshold values.
Minimum absolute dropout differential
Protection-class current transformers 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument transformers 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)
Circuit-Breaker Supervision
NOTE
i The circuit-breaker failure protection can also work without the circuit-breaker auxiliary contacts stated.
Auxiliary contacts are required for circuit-breaker failure protection in cases where the current flow is
absent or too low for tripping (for example with a transformer or a Buchholz protection).
Times
NOTE
i If you use the setting Direct release for the parameters 3I0 criterion or I2 criterion, this can
result in extended dropout times.
Tolerances
Threshold values, dropout thresholds 2 % of the setting value or 1 % of the rated current
Times 1 % of the setting value or 10 ms
Setting Values
Setting Values
Dropout
The greater dropout differential (= | pickup threshold – dropout threshold |) of the following
2 criteria applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies to the current threshold values.
Minimum absolute dropout differential
Protection-class current transformers 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument transformers 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)
Circuit-Breaker Supervision
NOTE
i The circuit-breaker failure protection can also work without the circuit-breaker auxiliary contacts stated.
Auxiliary contacts are required for circuit-breaker failure protection in cases where the current flow is
absent or too low for tripping (for example with a transformer or a Buchholz protection).
Times
NOTE
i Using the setting Direct release with the parameters 3I0 criterion or I2 criterion can result
in extended dropout times.
Tolerances
Threshold values, dropout thresholds 2 % of the setting value or 1 % of the rated current
Times 1 % of the setting value or 10 ms
Dropout
The larger dropout differential (= | pickup threshold – dropout threshold |) of the following 2
criteria is used:
Dropout differential 95 % of the pickup value
Minimum absolute dropout differential
Protection-class current transformers 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument transformers 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)
Tolerances
Times
If the end-fault protection is active, the current for the busbar differential protection is immediately set to 0 in
case of a trigger (irrespective of the tripping delay and of the threshold values for the end-fault protection).
This tripping delay corresponds to the minimum operate time for the busbar differential protection, see also
Operate Time, Page 952.
Dropout
The larger dropout differential (= | pickup threshold – dropout threshold |) of the following
2 criteria is used:
Dropout differential 95 % of the pickup value
Minimum absolute dropout differential
Protection-class current transformers 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument transformers 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)
Tolerances
Threshold values, dropout thresholds 2 % of the setting value or 1 % of the rated current
Times 1 % of the setting value or 10 ms
Operate Time
Tolerance
Operate Time
Tolerances
Setting Values
Setting Values
Setting Values
Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-
rent functionality.
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)
Times
47 If you have selected the method of measurement = RMS value, do not set the threshold value under 0.1 lrated,sec.
48 OOT (Output Operating Time): additional delay of the output medium used, for example 5 ms with fast relays
Tolerances
Setting Values
Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout 95 % of 1.1 ⋅ threshold value
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)
[dw_ocp_ki1, 1, en_US]
Figure 11-1 Operate Curves and Dropout-Time Characteristic Curves According to IEC
[dw_ocp_ki2, 1, en_US]
Figure 11-2 Operate Curves and Dropout-Time Characteristic Curves According to IEC
[dw_iec-short-inverse, 1, en_US]
Figure 11-3 Operate Curves and Dropout-Time Characteristic Curves According to IEC (Advanced Stage)
[dw_ocp_ka1, 2, en_US]
Figure 11-4 Operate Curves and Dropout-Time Characteristic Curves According to ANSI/IEEE
[dw_ocp_ka2, 2, en_US]
Figure 11-5 Operate Curves and Dropout-Time Characteristic Curves According to ANSI/IEEE
[dw_ocp_ka3, 2, en_US]
Figure 11-6 Operate Curves and Dropout-Time Characteristic Curves According to ANSI/IEEE
[dw_ocp_ka4, 2, en_US]
Figure 11-7 Operate Curves and Dropout-Time Characteristic Curves According to ANSI/IEEE
NOTE
i In the preceding operate curves according to IEC and ANSI/IEEE, the inverse-time delays for I/Threshold
value I > 20 are identical to the inverse-time delay for I/Threshold value I = 20.
Tolerances
Operate time for 2 ≤ I/I threshold value ≤ 20 5 % of the reference (calculated) value
+2 % current tolerance or 30 ms
Dropout time for I/I threshold value ≤ 0.90 5 % of the reference (calculated) value
+2 % current tolerance or 30 ms
Setting Values
Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-
rent functionality.
Minimum absolute dropout differential
Protection-class current transformer 5 mA sec. (Irated = 1 A) or
25 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)
Times
49 If you have selected the method of measurement = RMS value, do not set the threshold value under 0.1 lrated,sec.
50 OOT (Output Operating Time): additional delay of the output medium used, see 11.1.4 Relay Outputs
Tolerances
3I0 measured via I451, method of measurement = 1 % of the setting value or 5 mA (Irated = 1 A)
fundamental component or 25 mA (Irated = 5 A)
3I0 measured via I452, method of measurement = RMS value
(33 % harmonics, in relation to fundamental component)
Up to 30th harmonic 1 % of the setting value or 5 mA (Irated = 1 A)
or 25 mA (Irated = 5 A)
Up to 50th harmonic, frated = 50 Hz 3 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A)
Up to 50th harmonic, frated = 60 Hz 4 % of the setting value or 20 mA (Irated = 1 A)
or 100 mA (Irated = 5 A)
Pickup delay 1 % of the setting value or 10 ms
Dropout delay 1 % of the setting value or 10 ms
Operate delay for the basic stage 1 % of the setting value or 10 ms
Operate delay for the Operate delay mode = 1 % of the setting value or 10 ms
advanced stage Running dur. DO-delay
Operate delay mode = 1 % of the reference value or 10 ms
Frozen dur. DO-delay (Reference value = Setting value + Frozen time)
Setting Values
Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
51 Slightly expanded tolerances will occur during the calculation of 3I0, maximum factor of 2
52 Slightly expanded tolerances will occur during the calculation of 3I0, maximum factor of 2
53 If you have selected the method of measurement = RMS value, do not set the threshold value under 0.1 l
rated,sec.
Normal inverse: type A See Figure 11-1 in chapter 11.15.2 Stage with
Very inverse: type B Inverse-Time Characteristic Curve
Extremely inverse: type C See Figure 11-2 in chapter 11.15.2 Stage with
Long-time inverse: type B Inverse-Time Characteristic Curve
Short-time inverse See Figure 11-3 in chapter 11.15.2 Stage with
(Only in the advanced stage) Inverse-Time Characteristic Curve
Tolerances
3I0 measured via I454, method of measurement = 1 % of the setting value or 5 mA (Irated = 1 A)
fundamental component or 25 mA (Irated = 5 A)
3I0 measured via I455, method of measurement = RMS value
(33 % harmonics, in relation to fundamental component)
Up to 30th harmonic 1 % of the setting value or 5 mA (Irated = 1 A)
or 25 mA (Irated = 5 A)
54 Insignificantly increased tolerances will occur during the calculation of 3I0, maximum factor of 2
55 Insignificantly increased tolerances will occur during the calculation of 3I0, maximum factor of 2
Setting Values
Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-
rent functionality.
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)
Direction Determination
Times
56 If you have selected the method of measurement = RMS value, do not set the threshold value under 0.1 lrated,sec.
57 OOT (Output Operating Time): additional delay of the output medium used, for example 5 ms with fast relays
Tolerances
Setting Values
58 If you have selected the method of measurement = RMS value, do not set the threshold value under 0.1 lrated,sec.
Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout 95 % of 1.1 ⋅ threshold value
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)
Normal inverse: type A See Figure 11-1 in chapter 11.15.2 Stage with
Very inverse: type B Inverse-Time Characteristic Curve
Extremely inverse: type C See Figure 11-2 in chapter 11.15.2 Stage with
Long-time inverse: type B Inverse-Time Characteristic Curve
Short-time inverse See Figure 11-3 in chapter 11.15.2 Stage with
(Only in the advanced stage) Inverse-Time Characteristic Curve
Direction Determination
Times
Tolerances
59 OOT (Output Operating Time): additional delay of the output medium used, for example 5 ms with fast relays
Setting Values
Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-
rent functionality.
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)
Times
Tolerances
Setting Values
Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout 95 % of 1.1 ⋅ threshold value
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument current transformer 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)
Normal inverse: type A See Figure 11-1 in chapter 11.15.2 Stage with
Very inverse: type B Inverse-Time Characteristic Curve
Extremely inverse: type C See Figure 11-2 in chapter 11.15.2 Stage with
Long-time inverse: type B Inverse-Time Characteristic Curve
Short-time inverse See Figure 11-3 in chapter 11.15.2 Stage with
(Only in the advanced stage) Inverse-Time Characteristic Curve
Times
Tolerances
Where
Top Operate delay
Tinv Inverse-time delay
Tadd Additional time delay (parameter Additional time delay)
60 If you have selected the method of measurement = RMS value, do not set the threshold value under 10 V.
Where
Tinv Inverse-time delay
Tp Time multiplier (parameter Time dial)
V Measured voltage
Vthresh Threshold value (parameter Threshold)
k Curve constant k (parameter Charact. constant k)
α Curve constant α (parameter Charact. constant α)
c Curve constant c (parameter Charact. constant c)
Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for the overvoltage and of 105 % for the
undervoltage functionality.
Minimum absolute dropout differential 150 mV sec.
Times
61 OOT (Output Operating Time): additional delay of the output medium used, see chapter 11.1.4 Relay Outputs
Setting Values
Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for the overvoltage and of 105 % for the
undervoltage functionality.
Minimum absolute dropout differential 150 mV sec.
Times
Tolerances
62 OOT (Output Operating Time): additional delay of the output medium used, see chapter 11.1.4 Relay Outputs
Setting Values
Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for the overvoltage and of 105 % for the
undervoltage functionality.
Minimum absolute dropout differential 150 mV sec.
Times
Tolerances
Setting Values
63 OOT (Output Operating Time): additional delay of the output medium used, for example 5 ms with fast relays
64 If you have selected the method of measurement = RMS value, do not set the threshold value under 10 V.
Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for the overvoltage and of 105 % for the
undervoltage functionality.
Minimum absolute dropout differential 150 mV sec.
Times
Tolerances
65 OOT (Output Operating Time) additional delay of the output medium used, see chapter 11.1.4 Relay Outputs
Setting Values
Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for the overvoltage and of 105 % for the
undervoltage functionality.
Minimum absolute dropout differential 150 mV sec.
Times
66 If you have selected the method of measurement = RMS value, do not set the threshold value under 10 V.
67 OOT (Output Operating Time): additional delay of the output medium used, see chapter 11.1.4 Relay Outputs
Tolerances
Operate Curve
Top=TInv+ Tadd
Where:
Top Operate delay
TInv Inverse-time delay
Tadd Additional time delay (Parameter Additional time delay)
[fo_uvp_3ph_1_3pol_inverse, 2, en_US]
68 If you have selected the Method of measurement = RMS value, do not set the threshold value to less than 10 V.
Where
TInv Inverse-time delay
Tp Time multiplier (Parameter Time dial)
V Measured undervoltage
Vthresh Threshold value (Parameter Threshold)
k Curve constant k (Parameter Charact. constant k)
α Curve constant α (Parameter Charact. constant α)
c Curve constant c (Parameter Charact. constant c)
Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for the overvoltage and of 105 % for the
undervoltage functionality.
Minimum absolute dropout differential 150 mV sec.
Times
Setting Values
69 OOT (Output Operating Time) additional delay of the output medium used, see chapter 11.1.4 Relay Outputs
Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for the overvoltage and of 105 % for the
undervoltage functionality.
Minimum absolute dropout differential 150 mV sec.
Times
Tolerances
70 OOT (Output Operating Time): additional delay of the output medium used, see chapter 11.1.4 Relay Outputs
Setting Values
Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for the overvoltage and of 105 % for the
undervoltage functionality.
Minimum absolute dropout differential 150 mV sec.
Times
71 If you have selected the method of measurement = RMS value, do not set the threshold value under 10 V.
72 OOT (Output Operating Time): additional delay of the output medium used, see chapter 11.1.4 Relay Outputs
Tolerances
Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for the overvoltage and of 105 % for the
undervoltage functionality.
Minimum absolute dropout differential 150 mV sec.
Times
Tolerances
73 OOT (Output Operating Time): additional delay of the output medium used, for example 5 ms with fast relays
Setting Values
Times
Dropout
The larger dropout differential (= | pickup value – dropout threshold |) of the following 2 criteria
is used:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not present, a dropout ratio of 99.97 % applies to the overfrequency protection.
Minimum absolute dropout differential 5 mHz
Operating Ranges
Tolerances
Frequency f>
frated - 0.20 Hz < f < frated + 0.20 Hz ± 5 mHz at V = Vrated
frated - 3.0 Hz < f < frated + 3.0 Hz ± 10 mHz at V = Vrated
Time delay T(f>) 1 % of the setting value or 10 ms
Minimum voltage 1 % of the setting value or 0.5 V
74 OOT (Output Operating Time): Additional delay of the output medium used, for example, 5 ms with fast relays, see chapter
11.1.4 Relay Outputs
Setting Values
Times
Dropout
The larger dropout differential (= | pickup value – dropout threshold |) of the following 2 criteria
is used:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not present, a dropout ratio of 100.03 % applies to the underfrequency protection.
Minimum absolute dropout differential 5 mHz
Operating Ranges
Tolerances
Frequency f<
frated - 0.20 Hz < f < frated + 0.20 Hz ± 5 mHz at V = Vrated
frated - 3.0 Hz < f < frated + 3.0 Hz ± 10 mHz at V = Vrated
Time delay T(f<) 1 % of the setting value or 10 ms
Minimum voltage 1 % of the setting value or 0.5 V
75 OOT (Output Operating Time): Additional delay of the output medium used, for example, 5 ms with fast relays, see chapter
11.1.4 Relay Outputs
Dropout
Times
Tolerances
Value Description
df/dt Calculated rate of frequency change
76 OOT (Output Operating Time): Additional delay of the output medium used, for example, 5 ms with fast relays, see chapter
11.1.4 Relay Outputs
Tolerances
77 OOT (Output Operating Time) additional delay of the output medium used, for example 5 ms with fast relays
Dropout
The larger dropout differential (= | pickup value – dropout threshold |) of the following 2 criteria
is used:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies to the current threshold value and a dropout
ratio of 105 % applies to the voltage threshold value.
Minimum absolute dropout differential 150 mV sec.
Times
Times
78 OOT (Output Operating Time) Additional delay of the output medium used, see chapter 11.1.4 Relay Outputs
79 OOT (Output Operating Time) Additional delay of the output medium used, for example 5 ms with fast relays, see chapter
11.1.4 Relay Outputs
80 OOT (Output Operating Time) Additional delay of the output medium used, for example 5 ms with fast relays, see chapter
11.1.4 Relay Outputs
Tolerances
Dropout Ratio
Times
Dropout Ratio
Times
Times
Dropout Ratios
Times
Tolerances
81 OOT (Output Operating Time) additional delay of the used output medium, such as 5 ms with quick-acting relay
Dropout
The larger dropout differential (= | pickup threshold – dropout threshold |) of the following 2
criteria is used:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 90 % applies to the current threshold values.
Minimum absolute dropout differential
Protection-class current transformers 15 mA sec. (Irated = 1 A) or
75 mA sec. (Irated = 5 A)
Instrument transformers 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)
Times
82 OOT (Output Operating Time): Additional delay of the output medium used, for example, 5 ms with fast relay, see chapter
11.1.4 Relay Outputs
Times
Pickup
Dropout
The greater dropout differential (= | pickup threshold – dropout threshold |) of the following
criteria is used:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for the overcurrent protection and a dropout
ratio of 105 % applies for the undercurrent protection.
Minimum absolute dropout differential
Protection-class current transformers 5 mA sec. (Irated = 1 A) or
25 mA sec. (Irated = 5 A)
Instrument transformers 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)
Harmonic: I2nd harm/I1st harm 0.75
Protection-class current transformers I2nd harm = 5 mA sec. (Irated = 1 A) or
I2nd harm = 25 mA sec. (Irated = 5 A)
Instrument transformers I2nd harm = 0.5 mA sec. (Irated = 1 A) or
I2nd harm = 2.5 mA sec. (Irated = 5 A)
Tolerances
Times
Pickup
Dropout
The greater dropout differential (= | pickup threshold – dropout threshold |) of the following
2 criteria applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for the overcurrent protection and a dropout
ratio of 105 % applies for the undercurrent protection.
Minimum absolute dropout differential
Protection-class current transformers 5 mA sec. (Irated = 1 A) or
25 mA sec. (Irated = 5 A)
Instrument transformers 0.5 mA sec. (Irated = 1 A) or
2.5 mA sec. (Irated = 5 A)
Harmonics: I2nd harm/I1st harm 0.75 or
Protection-class current transformers I2nd harm = 5 mA sec. (Irated = 1 A) or
I2nd harm = 25 mA sec. (Irated = 5 A)
Instrument transformers I2nd harm = 0.5 mA sec. (Irated = 1 A) or
I2nd harm = 2.5 mA sec. (Irated = 5 A)
Tolerances
Times
Blockings
Blocked protection functions Busbar differential protection, busbar tripping by the circuit-breaker
failure protection
• The values apply both to the RMS values and the absolute value and phase angle of the fundamental
components.
• These values were determined for pure sinusoidal signals – without harmonics.
Voltages
Power Factor
Frequency
Frequency f Hz
Range frated - 0.20 Hz ≤ f ≤ frated + 0.20 Hz
Tolerance ± 2 mHz at V = Vrated or at I = Irated
Range frated - 3.00 Hz ≤ f < frated + 3.00 Hz
Tolerance ± 5 mHz at V = Vrated or at I = Irated
Range 25 Hz to 80 Hz; operational measured values
10 Hz to 90 Hz; functional measured values, system
frequency
Tolerance ± 10 mHz at V = Vrated or at I = Irated
Range 0 to 9.2e+15
Operating hours h
Range 0 to 9999999 h
Tolerance 1h
Circuit breaker open hours h
Range 0 to 9999999 h
Tolerance 1h
Dropout
Dropout differential 3 °C or 6 °F
Tolerances
Mode On
Off
Synchronization External synchron. off
Telegr. and ext. synch.
Telegr. or ext. synch.
External synch. only
Blocking of the unbalanced Yes
runtimes No
Maximum signal runtime threshold 0.1 ms to 30.0 ms Increments of 0.1 ms
Maximum runtime difference 0.000 ms to 3.000 ms Increments of 0.001 ms
Failure indication after 0.05 s to 2.00 s Increments of 0.01 s
Transm. fail. alarm after 0.0 s to 6.0 s Increments of 0.1 s
Max. error rate/h 0.000 % to 100.000 % Increments of 0.001 %
Max. error rate/min 0.000 % to 100.000 % Increments of 0.001 %
PPS failure indication after 0.5 s to 60.0 s Increments of 0.1 s
Transmission Rate
Direct connection:
Transmission rate 2048 kbit/s
Connection via communication networks:
Supported network interfaces IP protection communication
C37.94 with 64 kBit/s or 128 kBit/s or 512 kBit/s
G703.1 with 64 kBit/s
G703-T1 with 1.455 MBit/s
G703-E1 with 2.048 MBit/s
X.21 with 64 kBit/s or 128 kBit/s or 512 kBit/s
Pilot wires with 128 kbit/s
Transmission Rate Transmission rate 64 kBit/s at G703.1
1.455 MBit/s at G703-T1
2.048 MBit/s at G703-E1
512 kBit/s or 128 kBit/s or 64 kBit/s at X.21
128 kBit/s for pilot wires
Transmission Times
NOTE
i The times apply to devices without line differential protection for fiber-optic connections with 2 Mbit/s.
Priority 1
Response time, total approx. Minimum 5 ms
Typical 10 ms
Priority 2
Response time, total approx. Minimum 5 ms
Typical 12 ms
Priority 383
Response time, total approx. Typical 18 ms
Data Transfer
IEEE Standard for Synchrophasor
Data transfer
IEEE Std C37.118.2TM-2011
Tolerances
11.40 CFC
Typical response times and maximum number of ticks of the CFC task levels:
Task Level Time (in ms) Ticks CP300
High priority Event-trig- <1 1000
gered
Event-triggered <10 15 359
Low priority Event-trig- <10 149 603 in total
gered
Measurement 250
The times describe the response time of a typical CFC chart at the respective task level. The maximum number
of ticks applies to a typical load for the device based on the application template Basics.
The task level Measurement runs in cycles every 500 ms. All other task levels are event-triggered.
In order to estimate the tick consumption of a CFC chart, you can use the following formula:
TChart = 5 ∙ nInp + 5 ∙ nOutp + TTLev + ∑i Tint + ∑j TBlock
Where:
nInp Number of indications routed as input in the CFC chart
nOutp Number of indications routed as output in the CFC chart
TTLev 101 Ticks in the High priority Event-triggered level
104 Ticks in the Event-triggered level
54 Ticks in Measurement level
74 Ticks in the Low priority Event-triggered level
Tint Number of internal connections between 2 CFC blocks in one chart
TBlock Used ticks per CFC block (see Table 11-4)
Element Ticks
ABS_D 2.3
ABS_R 1.5
ACOS_R 6.9
ADD_D4 3.4
ADD_R4 3.3
ADD_XMV 6.4
ALARM 1.8
AND_SPS 1.1
AND10 2.9
APC_DEF 1.2
APC_EXE 1.0
APC_INFO 3.9
ASIN_R 1.3
ATAN_R 1.2
BLINK 1.3
BOOL_CNT 2.0
BOOL_INT 1.5
BSC_DEF 1.3
BSC_EXE 1.1
Element Ticks
BSC_INFO 2.7
BUILD_ACD 2.9
BUILD_ACT 2.2
BUILD_BSC 1.2
BUILD_CMV 2.3
BUILD_DEL 2.1
BUILD_DPS 1.4
BUILD_ENS 1.3
BUILD_INS 0.5
BUILD_Q 0.8
BUILD_SPS 0.6
BUILD_WYE 3.2
BUILD_XMV 2.9
BUILDC_Q 3.0
CHART_STATE 5.9
CMP_DPS 1.5
CON_ACD 0.7
CON_ACT 0.5
CONNECT 0.4
COS_R 2.5
CTD 1.8
CTU 1.6
CTUD 2.3
DINT_REAL 3.0
DINT_UINT 3.0
DIV_D 2.9
DIV_R 1.6
DIV_XMV 2.2
DPC_DEF 0.4
DPC_EXE 0.4
DPC_INFO 1.1
DPC_OUT 1.3
DPS_SPS 1.0
DRAGI_R 1.7
ENC_DEF 3.6
ENC_EXE 3.8
EQ_D 1.0
EQ_R 1.9
EXP_R 1.5
EXPT_R 2.7
F_TRGM 0.3
F_TRIG 0.3
FF_D 0.9
FF_D_MEM 1.4
FF_RS 0.7
FF_RS_MEM 1.2
FF_SR 0.8
Element Ticks
FF_SR_MEM 1.1
GE_D 0.9
GE_R 1.1
GT_D 0.9
GT_R 1.2
HOLD_D 1.1
HOLD_R 1.0
INC_INFO 0.9
LE_D 1.1
LE_R 1.1
LIML_R 1.5
LIMU_R 1.5
LN_R 3.3
LOG_R 1.2
LOOP 1.5
LT_D 0.9
LT_R 0.9
MAX_D 0.9
MAX_R 1.4
MEMORY_D 0.9
MEMORY_R 1.1
MIN_D 0.7
MIN_R 1.3
MOD_D 1.5
MUL_D4 2.5
MUL_R4 2.7
MUL_XMV 2.8
MUX_D 1.2
MUX_R 0.9
NAND10 3.5
NE_D 0.9
NE_R 0.9
NEG 1.2
NEG_SPS 0.8
NL_LZ 3.8
NL_MV 5.6
NL_ZP 2.7
NOR10 3.2
OR_DYN 1.1
OR_SPS 1.3
OR10 2.6
R_TRGM 0.4
R_TRIG 0.4
REAL_DINT 3.0
REAL_SXMV 3.0
SIN_R 0.8
SPC_DEF 0.4
Element Ticks
SPC_EXE 0.4
SPC_INFO 0.4
SPC_OUT 0.4
SPLIT_ACD 3.4
SPLIT_ACT 1.0
SPLIT_BSC 1.3
SPLIT_CMV 2.2
SPLIT_DEL 2.0
SPLIT_DPS 1.0
SPLIT_INS 0.5
SPLIT_Q 0.7
SPLIT_SPS 0.8
SPLIT_WYE 2.6
SPLIT_XMV 2.1
SQRT_R 0.6
SUB_D 1.3
SUB_R 1.6
SUB_XMV 2.4
SUBST_B 1.0
SUBST_BQ 1.5
SUBST_D 1.0
SUBST_R 1.0
SUBST_XQ 1.4
SXMV_REAL 3.0
TAN_R 1.1
TLONG 2.2
TOF 1.0
TON 1.1
TP 2.5
TSHORT 1.9
UINT_DINT 3.0
XOR2 2.6
Ordering Options
The following ordering options are possible for SIPROTEC 5 products:
• Device
• Single part
• DIGSI 5
• Functional enhancement
NOTE
i To order single parts in the order configurator, use the Single part link.
• Expansion module
• Plug-in module
• Operation panel
• Terminal
• Accessories
NOTE
i To order terminals, terminal accessories, and mechanical accessories in the order configurator, use the
Single part link.
Group Accessories
Terminal Voltage terminal, terminal block, 14-pole
Terminal Voltage terminal (power supply)
Terminal block, 2-pole84
Terminal Type A current terminal, 4 x protection
(for modular devices)
Terminal Type A current terminal, 3 x protection and 1 x measurement
(for modular devices)
Terminal Type A current terminal, 4 x measurement
(for modular devices)
Terminal Type B current terminal, 4 x protection
(for non-modular devices)
Terminal Type B current terminal, 3 x protection and 1 x measurement
(for non-modular devices)
Terminal 2-pole cross connector for current terminal
Terminal Terminals for IO110, IO112, IO11384
Terminal Terminals and shielding for IO11184,85,86
Terminal Terminal set only for IO23x84
Terminal 2-pole cross connector for voltage terminal
Terminal Cover for current terminal block
Terminal Cover for voltage terminal block
Terminal Transport safety, current terminal
Terminal Transport safety, voltage terminal
Terminal Terminal set for direct connection to 400 V low voltage
Accessories USB covers (10 each for CP 100, 150, 200, 300)
Accessories Cable, integrated operation panel, 0.43 m
Accessories Cable, detached operation panel, 2.50 m
Accessories Cable, detached operation panel, 5.00 m
Accessories Cable set, COM link cable
Accessories Cover plate for plug-in modules
Accessories Cover panel 1/6, 5 pcs
Accessories Set of angle rails
Accessories 10 x labeling strip, LEDs/function keys
Accessories 5 x labeling strips, push-buttons
Accessories Set of parts, mounting bracket 1/2
Accessories Set of parts, mounting bracket 2/3
84 Recommended tightening torque when screwing down the terminal on the rear plate: 0.3 Nm
85 The set consists of terminals and shielding for the IO111 for the terminal positions M and N.
86 Only for non-modular devices 7xx82
Group Accessories
Accessories Set of parts, mounting bracket 5/6
Accessories Set of parts, mounting bracket 1/1
Accessories 4 x screw cover 1/3, type C11
Accessories 4 x screw cover 1/3, type C22
Accessories 4 x screw cover 1/6, type C21
Accessories 2 x bus termination plate
Accessories Assembly frame for panel surface mounting for non-modular
devices 7xx81 and 7xx82 devices
Accessories SDHC memory card for 7KE85
Accessories 10 x battery holder
Accessories Connecting cable for 2nd row
Accessories DIGSI 5 USB cable 2.0
Accessories SFP RJ45, 10 units
Accessories SFP Single-mode, 24 km, 10 units
Sensors for arc protection Point sensor with line length of 3 m
Sensors for arc protection Point sensor with line length of 4 m
Sensors for arc protection Point sensor with line length of 5 m
Sensors for arc protection Point sensor with line length of 7 m
Sensors for arc protection Point sensor with line length of 10 m
Sensors for arc protection Point sensor with line length of 15 m
Sensors for arc protection Point sensor with line length of 20 m
Sensors for arc protection Point sensor with line length of 35 m
Sensors for arc protection Line sensor, length 3 m
Sensors for arc protection Line sensor, length 10 m
Sensors for arc protection Line sensor, length 20 m
Sensors for arc protection Line sensor, length 30 m
Sensors for arc protection Line sensor, length 40 m
Sensors for arc protection Supply line for line sensors, length 3 m
Sensors for arc protection Supply line for line sensors, length 5 m
Sensors for arc protection Supply line for line sensors, length 10 m
Dynamic settings:
State logic
Icon Description
Binary input signal derived from an external output
signal
AND gate
OR gate
XOR gate
Negation
Comparators
Pickup delay
Dropout delay
Icon Description
Trigger the pulse of duration T with a positive signal
edge
Characteristic curve
[lo_svs_typc1, 1, en_US]
[lo_svs_typc2, 1, en_US]
[lo_svs_typc3, 1, en_US]
[sv_7ss8x_bbp8, 1, en_US]
Current Transformers
Parameter Description
ALF Accuracy limit factor
ALF' Operational accuracy limit factor
The operational accuracy limit factor is derived from the connected burden Rbc:
Protected Object
Parameter Description
ISC Max Max. symmetrical short-circuit current
Burden: Rb ≥ Rbc
Required knee-point voltage Ek
PX, PXR
ANSI class
Required transformer terminal voltage Vtc
C (Isr = 5 A)
NOTE
i Avoid using different classes of transformers at the measuring points. This is particularly the case for
combining P class and TP class transformers, especially TPZ.
In contrast to class P transformers, class TP transformers heavily suppress the direct current component in
the short-circuit current. Additional differential currents will occur when you mix transformer classes.
You can find examples of different classes of current transformer and application examples in the following
sections:
87 The phase displacement is not specified in IEC 61869-2. Classes 10P and 10PR are not recommended for differential protection for
this reason.
Conditions:
Requirement:
The current transformer meets the requirements and the default stabilization factor can be maintained. You
don't have to carry out any additional calculations.
Check each current transformer. A relation between the smallest and largest current transformer ratio needs
not be considered.
NOTE
i If the requirement is not met or just met, you can use the current transformer by increasing the stabiliza-
tion factor.
Extensive calculations are required for determining the stabilization factor. Use the CTDim tool from
Siemens to do this.
Required product:
Current transformer:
Result: 60 > 25
NOTE
i The KSSC factor is determined by the maximum symmetrical short-circuit current. The minimum require-
ment in the example is KSSC = 50 and Ktd = 0.5. As the product is crucial for the design of the current trans-
former, the standard permits KSSC and Ktd values to be freely chosen, subject to certain limits (see
IEC TR 61869-100, Section 11.5.3.3.5 and Section 9.2). The KSSC = 25 and Ktd = 1.0 specification is
permitted.
The required resistive dimensioning burden Rb of the current transformer must be greater than the connected
resistive burden Rbc that was previously calculated.
Requirement: Rb > Rbc
Result: 1 Ω > 0.633 Ω
This class is specified with a maximum secondary terminal voltage Vt. In this example, the current trans-
former uses the following parameters:
Class: C200
Transformer terminal voltage at a rated burden of 2 Ω:
Rated secondary current: Isr = 5 A
The rated secondary current of Isr = 5 A causes the connected burden to change.
[ti_phase_2, 4, en_US]
Figure A-5 Connection to 3 Phase Current Transformers and a Measured Zero-Sequence Current (Current
in Common Return Conductor)
NOTE
i The switchover of the current polarity at the 3-phase current transformer causes a rotation in the direction
of electric current for current input I4 (IN)!
[tvvolta1-260313-01.tif, 1, en_US]
[tvvolta2-260313-01.tif, 1, en_US]
Figure A-7 Connection to 3 Star-Connected Voltage Transformers and to the Broken-Delta Winding
[tvvolta3-260313-01.tif, 1, en_US]
Figure A-8 Connection to 3 Star-Connected Voltage Transformers and to the Broken-Delta Winding of a
Separate Voltage Transformer (for Example Busbar)
[tvvolta4-260313-01.tif, 2, en_US]
Figure A-9 Connection to 3 Star-Connected Voltage Transformers and to the Phase-to-Phase Voltage of a
Busbar Voltage Transformer (for Example for Synchrocheck Applications)
[tvvolta5-260313-01.tif, 1, en_US]
Figure A-10 Connection to V-Connected Voltage Transformer (Delta-Connected Device Input Transformer)
and Connection to the Phase-to-Phase Voltage of a Busbar Voltage Transformer
NOTE
i When using the connection type 3-phase-to-phase voltage, the zero-sequence voltage cannot be detected.
[tvvolta6-260313-01.tif, 1, en_US]
Figure A-11 Connection to V-Connected Voltage Transformer (Delta-Connected Device Input Transformer)
and Connection to the Broken-Delta Winding of a Busbar Voltage Transformer
[tvvol2ll-260313-01.tif, 2, en_US]
[tvl2lluu-260313-01.tif, 2, en_US]
[tvvolta7-260313-01.tif, 1, en_US]
Light-Emitting Diodes
Table A-2 Preset LED Display, for Example Busbar Protection 7SS85
Table A-3 Siemens recommends Routing the Additional Following Bay-Related Indications to LEDs.
/1/ Distance Protection, Line Differential Protection, and Overcurrent Protection for 3-Pole Tripping – 7SA82,
7SD82, 7SL82, 7SA84, 7SD84, 7SA86, 7SD86, 7SL86, 7SJ86
C53000-G5040-C010
/2/ Distance and Line Differential Protection, Breaker Management for 1-Pole and 3-Pole Tripping – 7SA87,
7SD87, 7SL87, 7VK87
C53000-G5040-C011
/3/ Overcurrent Protection – 7SJ82/7SJ85
C53000-G5040-C017
/4/ Overcurrent Protection – 7SJ81
C53000-G5040-C079
/5/ Motor Protection – 7SK82/85
C53000-G5040-C024
/6/ Transformer Differential Protection – 7UT82, 7UT85, 7UT86, 7UT87
C53000-G5040-C016
/7/ Generator Protection – 7UM85
C53000-G5040-C027
/8/ Busbar Protection 7SS85
C53000-G5040-C019
/9/ High-Voltage Bay Controller – 6MD85/86
C53000-G5040-C015
/10/ Paralleling Device – 7VE85
C53000-G5040-C071
/11/ Universal Protection – 7SX82/7SX85
C53000-G5040-C607
/12/ Merging Unit 6MU85
C53000-G5040-C074
/13/ Fault Recorder – 7KE85
C53000-G5040-C018
/14/ Compact Class – 7SX800
C53000-G5040-C003
/15/ Hardware Description
C53000-G5040-C002
/16/ Communication Protocols
C53000-L1840-C055
/17/ Process Bus
C53000-H3040-C054
/18/ DIGSI 5 – Software Description
C53000-D5040-C001
ACD
IEC 61850 data type: Directional protection activation information
ACK
Data transfer acknowledgment
ACT
IEC 61850 data type: Protection-activation information
APC
Controllable analog set point information – information regarding a controllable analog value
ASDU
ASDU stands for Application Service Data Unit. An ASDU can consist of one or more identical information
objects. A sequence of the same information elements, for example measured values, is identified by the
address of the information object. The address of the information object defines the associated address of the
1st information element of the sequence. A consecutive number identifies the subsequent information
elements. The number builds on this address in integral increments (+1).
BAC
Binary controlled analog process value
Back-up battery
The back-up battery ensures that specified data areas, flags, timers, and counters are held as retentive.
Bay controller
Bay controllers are devices with control and supervision functions without protection functions.
BCR
IEC 61850 data type: Binary Counter Reading
Big-endian
The terms big-endian and little-endian are used to describe the arrangement of the bytes when saving. In case
of big-endian, the upper limiting value byte is saved at the lowest address. Little-endian saves the upper
limiting value byte at the highest address.
BMCA
Best Master Clock Algorithm
Boundary clock
The PTP protocol recognizes different types of clock: An Ordinary Clock (OC), Boundary Clock (BC), and Trans-
parent Clock (TC). The boundary clock transmits time information beyond a network limit. For example in a
router which connects different switched networks. As a slave, the clock of the router receives time informa-
tion and passes it on as a master.
BRCB
Buffered Report Control Block
BSC
Binary Controlled Step Position
CB
Circuit breaker
CBFP
Sampled Value Supervision
CDC
Common Data Class
CFC
Continuous Function Chart
Chatter blocking
A rapidly intermittent input (for example, due to a relay contact fault) is disconnected after a configurable
supervision time and can thus not generate any further signal changes. The function prevents overloading of
the system when a fault occurs.
CID
Configured IED Description
CIT
Conventional Instrument Transformer
CMV
Complex measured value
Combination Device
Combination devices are bay units with protection functions and with feeder mimic diagram.
Communication branch
A communication branch corresponds to the configuration of 1 to n participants that communicate via a
common bus.
Control display
The control display becomes visible for devices with a large display after pressing the CTRL key. The diagram
contains the switching devices to be controlled in the feeder, with status representation. The control display
serves for the bushing of the switching operations. Defining this display is part of the project engineering.
Controller
The controller initiates the IO data communication.
COT
Cause of Transmission
CRC
Cyclic redundancy check
DAN
Double Attached Node
DANP
Double Attached Node PRP
Data Type
The data type is a value set of a data object, together with the operations allowed on this value set. A data
type contains a classification of a data element, such as the determination whether it consists of integers,
letters, or suchlike.
Data unit
Information item with a joint transmission source. Abbreviation: DU – Data Unit
Data window
The right section of the project window visualizes the content of the section selected in the navigation
window. The data window contains for example, indications or measured values of the information lists or the
function selection for parameterization of the device.
DCF
Device Configuration File
DCF77
The high-precision official time is determined in Germany by the Physikalisch-Technische Bundesanstalt PTB in
Brunswick. The atomic clock unit of the PTB transmits this time via the long-wave time signal transmitter in
Mainflingen near Frankfurt/Main. The emitted time signal can be received within a radius of approx. 1500 km
from Frankfurt/Main.
DCP
Discovery and Basic Configuration Protocol
DCP Protocol
The DCP protocol is used to detect devices without an IP address and to assign addresses to these devices.
DDD
DIGSI 5 Device Driver – SIPROTEC 5 device driver which must be loaded in DIGSI.
DEL
Phase-to-phase related measurements of a 3-phase system
DEX5
Device 5 Export Format
You can archive the data from an individual SIPROTEC 5 device in DEX5 format.
DHCP
Dynamic Host Configuration Protocol
DIGDNP
DIGSI 5 protocol settings for DNP3
File extension for a file which is generated from DIGSI when the protocol configuration is exported from DIGSI
5.
DIGMOD
DIGSI 5 protocol settings for Modbus TCP
File extension for a file which is generated from DIGSI when the protocol configuration is exported from DIGSI
5.
DIGSI
Configuration software for SIPROTEC
DIGT103
DIGSI 5 protocol settings for IEC 60870-5-103
File extension for a file which is generated from DIGSI when the protocol configuration is exported from DIGSI
5.
DIGT104
DIGSI 5 protocol settings for IEC 60870-5-104
File extension for a file which is generated from DIGSI when the protocol configuration is exported from DIGSI
5.
DNP3
DNP3 is a communication standard for telecontrol engineering. DNP3 is used as a general transmission
protocol between control systems and substations, as well as between bay devices and the systems controls.
Double command
Double commands (DPC – Double Point Control) are process outputs which represent 4 process states at 2
outputs: 2 defined states (for example ON/OFF) and 2 undefined states (for example disturbed positions).
Double-point indication
A double-point indication (DPS – Double Point Status) ia a process information that represents 4 process states
at 2 inputs: 3 defined states (for example, On/Off and disturbed position) and 1 undefined state (00).
DPC
IEC 61850 data type: Double Point Control - double command
DPS
IEC 61850 data type: Double Point Status - double-point indication
DSP5
DIGSI 5 Display Pages
DU
Data Unit
ELCAD
Electrical CAD
Electrical CAD
You can import the topology information contained in an ELCAD file into a project and use it as the basis for a
single-line configuration. The other information contained in the ELCAD file is not included in this process.
Electromagnetic compatibility
Electromagnetic compatibility (EMC) means that an item of electric equipment functions without error in a
specified environment. The environment is not influenced in any impermissible way here.
ENC
Enumerated Status Controllable
ENS
Enumerated Status
ESD protection
The ESD protection is the entirety of all means and measures for the protection of electrostatic-sensitive
devices.
FC
Ferrule Connector
FEFI
Far End Fault Indication
FG
Function group
Fleeting indication
Fleeting indications are single-point indications present for a very short time, in which only the coming of the
process signal is logged and further processed time-correctly.
Floating
Floating means that a free potential of the output voltage that is not connected to ground is generated. There-
fore, no current flows through the body to ground in the event of touching.
Function group
Functions are brought together into function groups (FG). The assignment of functions to current and/or
voltage transformers (assignment of functions to measuring points), the information exchange between the
function groups via interfaces as well as the generation of group indications are important for this bringing
together.
GaAs
Gallium arsenide
General Interrogation
The state of all process inputs, of the status, and of the fault image are scanned on system startup. This infor-
mation is used to update the system-side process image. Likewise, the current process state can be interro-
gated after data loss with a general interrogation (GI).
GI
General Interrogation
GIN
Generic Identification Number
GNSS
Global Navigation Satellite System
GOOSE
Generic Object-Oriented Substation Event
Ground
The conductive ground whose electric potential can be set equal to 0 at every point. In the area of grounding
conductors, the ground can have a potential diverging from 0. The term reference ground is also used for
this situation.
Grounding
The grounding is the entirety of all means and measures for grounding.
GSDML
General Station Description Mark-up Language
Hierarchy level
Within a structure with higher-level and lower-level objects a hierarchy level is a level of equivalent objects.
HMI
Human-Machine Interface (HMI)
HSR
High Availability Seamless Redundancy Protocol
HSR Protocol
Like PRP (Parallel Redundancy Protocol), HSR (High-Availability Seamless Redundancy Protocol) is specified in
IEC 62439-3. Both protocols offer redundancy without switching time.
The principal function can be found in the definition of PRP. With PRP, the same indication is sent via 2 sepa-
rated networks. In contrast to this, in the case of HSR the indication is sent twice in the 2 directions of the ring.
The recipient receives it correspondingly via 2 paths in the ring, takes the 1st indication and discards the 2nd
indication (see PRP protocol).
Whereas NO indications are forwarded in the end device in the case of PRP, a switch function is installed in the
HSR node. Thus, the HSR node forwards indications in the ring that are not directed at it.
In order to avoid circular indications in the ring, corresponding mechanisms are defined in the case of HSR.
SAN (Single Attached Node) end devices can only be connected with the aid of a RedBox in the case of HSR.
PRP systems and HSR systems can be coupled redundantly with 2 RedBoxes.
HV bay description
The HV project description file contains details of bays which exist in a ModPara project. The actual bay infor-
mation of each bay is stored in a HV field description file. Within the HV project description file, each bay
receives an HV field description file through a reference to the file name.
HV project description
If the configuring and parameterization of PCUs and submodules is completed with ModPara, all the data will
be exported. This data is distributed to several files. One file contains details about the fundamental project
structure. This also includes, for example, information detailing which bays exist in this project. This file is
called a HV project description file.
ICD
IED Capability Description
IEC
International Electrotechnical Commission - International Electrotechnical Standardization Body
IEC 60870-5-103
International standard protocol for communication with IEDs (especially protection devices) Many protection
devices, bay units, bay controllers, and measured-value acquisition devices use the IEC 60870-5-103 protocol
to communicate with SICAM PAS.
IEC 60870-5-104
Standard international telecontrol protocol. Transmission protocol based on IEC 60870-5-101 for connecting
the substation control level to the telecontrol center via TCP/IP protocols using a wide area network connec-
tion (WAN).
IEC 60870-5-104 is also used for communicating with IEDs.
IEC 61850
IEC 61850 is an international standard for continuous communication in switchgear. It defines the communi-
cation between devices in a switchgear and the corresponding system requirements. All automation functions
of a switchgear and their engineering are supported this way. IEC 61850 can also be transferred to automa-
tion systems in other applications, for example for controlling and monitoring decentralized power genera-
tion.
IEC address
A unique IEC address must be assigned to each SIPROTEC device within an IEC bus. A total of 254 IEC
addresses per IEC bus are available.
IED
Intelligent Electronic Device
IED stands for a physical part of a device (hardware, etc.)
IEEE
Institute of Electrical and Electronic Engineers
IEEE 1588
Time-synchronization protocol according to the standard IEEE 1588-2008. Precision Clock Synchronization
Protocol for Networked Measurement and Control Systems (IEEE 1588 v2) and the standard IEEE
C37.238-2011: IEEE Standard Profile for Use of IEEE 1588 PTP protocol in Power System Applications (Power
Profile).
IEEE 1588v2/PTP
PTP has many optional features and often offers more than one way of doing things. Meaning that it is not
mandatory for PTP devices to work together. Provided that they are configured with a compatible set of selec-
tion options for IEEE 1588 options and settings. The solution for this is profiles. Profiles are rule sets with
restrictions for PTP that are designed to be used to meet the requirements for specific applications or a set of
similar applications. The IEEE 1588 standard itself only defines 1 profile, which is designated as the Default
profile. 2 profiles are used in the power industry: IEC 61850-9-3 (Power Utility Profile) and C37.238-2017
(Power Profile).
IID
Instantiated IED Description
INC
Controllable Integer Status
INS
Integer Status
Internet Protocol
An Internet protocol (IP) enables the connection of participants which are positioned in different networks.
IO
Input-Output
IO Provider Status
The transmitter (provider) of an IO data element uses this to indicate the state (good/bad, including fault loca-
tion).
IOPS
IO Provider Status
IP
Internet Protocol
IPv4
Internet-Protocol Version 4
ISC
Integer Step Controlled Position Information
LAN
Local Area Network
Link address
The link address indicates the address of a SIPROTEC device.
List view
The right area of the project window displays the names and icons of the objects which are within a container
selected in the tree view. As the visualization is in the form of a list, this area is also referred to as list view.
LLDP
Link Layer Discovery Protocol
LPIT
Low-Power Instrument Transformer –
AKA NCIT – Non Conventional Instrument Transformer. Examples: Low-power current transformer, C dividers,
R dividers, RC dividers, optical sensors
LPVT
Low-Power Voltage Transformer
LSB
Least Significant Bit
MAC address
The MAC address (Media Access Control) is the hardware address of each individual network adaptor. It serves
to identify the devices in the network unambiguously.
Master Clock
The Master Clock (MC) contains a mechanical or electric mechanism and a contact device, which periodically
transmits drive pulses to the slave clocks.
MC
Master Clock
Measured Value
This data type provides a measured value that can be used as a CFC result, for instance.
Merging Unit
The Merging Unit (MU) is used (also for IEC 61850 plant) for the field-signal bus interface. The publisher/
server of the sampled measured values is designated as the merging unit.
Metered value
Metered values are a processing function, used to determine the total number of discrete similar events
(counter pulses), for example, as integral over a time span. In the power utility field, electrical energy is often
recorded as a metered value (energy import/delivery, energy transport).
MIB
Management Information Base
MICS
Model Implementation Conformance Statement
MMS
Manufacturing Message Specification
Modbus
The Modbus protocol is a communication protocol. It is based on a master/slave or client/server architecture.
Module
Unit of a device. This can either be a physical module or a functional unit of a device.
MSB
Most Significant Bit
MU
Merging Unit
MV
Data type Measured Value
NACK
Negative acknowledgment
Navigation window
The left area of the project window displays the names and icons of all containers of a project in the form of a
folder tree structure.
NTP
Network Time Protocol
Object
Each element of a project structure is designated as an object in DIGSI 5.
Object property
Each object has properties. These might be general properties that are common to several objects. Otherwise,
an object can also have object-specific properties.
Offline
If there is no communication connection between a PC program (for example, configuration program) and a
runtime application (for example, a PC application), the PC program is offline. The PC program executes in
Offline mode.
Online
If there is a communication connection between a PC program (for example configuration program) and a
runtime application (for example a PC application), the PC program is online. The PC program executes in
Online mode.
OSM
Optical Switch Module
PRP is based on the following approach: The redundancy procedure is generated in the end device itself. The
principle is simple: The redundant end device has 2 Ethernet interfaces with the same address (DAN, Double
Attached Node). Now the same indication is sent twice, in the case of PRP (parallel) over 2 separate networks,
and unambiguously marks both with a sequence number. The receiver takes the information that it receives
first, stores its ID based on the source address and the sequence number in a duplicate filter and thus recog-
nizes the 2nd, redundant information. This redundant information is then discarded. If the 1st indication is
missing, the 2nd indication with the same content comes via the other network. This redundancy avoids a
switching procedure in the network and is thus interruption-free. The end device relays no indications to the
other network. Since the process is realized in the Ethernet layer (same MAC address), it is transparent and
usable for all Ethernet user data protocols (IEC 61850, DNP, other TCP/IP based protocols). In addition, it is
possible to use one of the 2 networks for the transmission of non-redundant indications.
There are 2 versions of PRP: PRP-0 and its successor PRP-1. Siemens implements PRP-1.
Parameterization
Comprehensive term for all setting work on the device. You can set parameters for the protection functions
with DIGSI 5 or sometimes also directly on the device.
Parameter set
The parameter set is the entirety of all parameters that can be set for a SIPROTEC device.
Participant address
A participant address comprises the name of the participant, the national code, the area index and the partici-
pant-specific phone number.
PB Client
Process-Bus client. The sampled measured values subscriber is designated as a process-bus client.
PICS
Protocol Implementation Conformance Statement
PROFIBUS
PROcess FIeld BUS, German process and fieldbus standard (EN 50170). The standard specifies the functional,
electrical, and mechanical characteristics for a bit-serial fieldbus.
PROFIBUS address
An unambiguous PROFIBUS address must be assigned to each SIPROTEC device within a PROFIBUS network. A
total of 254 PROFIBUS addresses per PROFIBUS network are available.
Profile_ID
Together with an API, the Profile_ID unambiguously defines the access and behavior of an application.
PROFINET IO
PROFINET is the open Industrial Ethernet Standard of PROFIBUS for automation.
Programmable Logic
The programmable logic is a function in Siemens devices or station controllers, enabling user-specific func-
tionality in the form of a program. This logic component can be programmed by various methods: CFC
(Continuous Function Chart) is one of these. SFC (Sequential Function Chart) and ST (Structured Text) are
others.
Project
Content-wise, a project is the image of a real energy supply system. Graphically, a project is represented as a
number of objects which are integrated in a hierarchical structure. Physically, a project consists of a number of
directories and files containing project data.
Project tree
The project tree contains a representation of the data structure. This data structure represents the content of
the project and is created with a generic browser.
Protection communication
Protection communication includes all functionalities necessary for data exchange via the protection interface.
Protection communication is created automatically during configuration of communication channels.
Protection device
A protection device detects erroneous states in distribution networks, taking into consideration various
criteria, such as fault distance, fault direction, or fault duration, triggering a disconnection of the defective
network section.
PRP
Parallel Redundancy Protocol
PTP
Precision-Time Protocol
PTP Protocol
The PTP protocol causes the time settings of several devices in a network to synchronize. PTP is defined in
IEEE 1588. The focus of PTP is on higher accuracy and networks that are locally restricted. PTP can achieve an
accuracy in the range of nanoseconds in a hardware variant, and in the range of a few milliseconds in a soft-
ware variant.
Real Time
Real time
RedBox
Redundancy box
The RedBox is used to connect a device with only one interface redundantly to both PRP networks LAN A and
LAN B. The RedBox is a DAN (Double Attached Node) and functions as a proxy server for the devices (VDANs)
connected to it. The RedBox has its own IP address for configuration, administration, and monitoring.
RIO
Data format Relay Information by OMICRON
RSTP
The Rapid Spanning Tree Protocol (RSTP) is a standardized redundancy process with a short response time. In
the Spanning Tree Protocol (STP protocol), structuring times in the multidigit second range apply in the case of
a reorganization of the network structure. These times are reduced to several 100 milliseconds for RSTP.
RSTP
Rapid-Spanning Tree Protocol
Sampled value
Sampling is the registration of measured values for discrete, mostly equidistant periods of time. This can be
used to extract a discrete time signal from a continuous time signal.
Sampling rate
In signal processing, sampling is reducing a continuous time signal (for example current and voltages) to a
discrete time signal. A common example is converting soundwave (a continuous signal) into a sampling
sequence (a discrete time signal).
SAN
Single Attached Node
An SAN is a non-redundant node in a PRP network. It is connected with a single port to a single network (LAN
A or LAN B). It can only communicate in the connected network via nodes. Devices with only one connection
can be connected to both networks, LAN A and LAN B, redundantly via a RedBox. In order to keep LAN A and
LAN B symmetrical, Siemens recommends avoiding SANs and to connect the devices either via a RedBox or in
a separate network without PRP support.
SBO
Select before operate
SC
Single command
SCD
Substation Configuration Description
SCL
Substation Configuration Description Language
SED
System Exchange Description
SEQ
Data type sequence
SEQ5
DIGSI 5 Test Sequences
Sequence of Events
Acronym: SOE. An ordered, time-stamped log of status changes at binary inputs (also referred to as state
inputs). SOE is used to restore or analyze the behavior, or an electrical power system itself, over a certain
period of time.
Service interface
Device interface for interfacing DIGSI 5 (for example, through a modem)
SFP
Small Form-Factor Pluggable
SICAM SAS
Substation Automation System – Modular substation automation system based on the SICAM SC substation
controller and the HMI system SICAM WinCC.
SICAM WinCC
The operator control and monitoring system SICAM WinCC graphically displays the state of your network.
SICAM WinCC visualizes alarms and indications, archives the network data, provides the option of intervening
manually in the process and manages the system rights of the individual employees.
SIM
Simulation data format for single/multiple devices
Single command
Single commands (SPC – Single Point Control) are process outputs which represent 2 process states (for
instance on/off) at one output.
Single-line diagram
A single-line diagram (SLD) is a simplified electrical overview diagram of the switchgear. Instead of all 3
phases, only a single line is shown, hence the name single-line.
Single-Line Editor
The Single-Line Editor (SLE) contains the catalog with the topological elements of a single-line diagram. Using
the single-line components, the customer can configure the topological part of the plant.
Single-point indication
Single-point indications (SPS) are a type of process information which represents 2 process states (for instance
on/off) at one output.
SIPROTEC
The registered trademark SIPROTEC designates the product family of Siemens protection devices and fault
recorders.
SIPROTEC 5 device
This object type represents a real SIPROTEC device with all the contained setting values and process data.
Slave device
A slave may only exchange data with a master after being prompted to do so by the master. SIPROTEC devices
work as slaves. A master computer controls a slave computer. A master computer can also control a peripheral
device.
SLD
Single-Line Diagram
SLE
Single-Line Editor
SMV
Sampled Measured Value
SNMP
The Simple Network Management Protocol (SNMP) is an Internet standard protocol and serves for the admin-
istration of nodes in an IP network.
SNMP
Single Network Management Protocol
SNTP
The Simple Network Time Protocol (SNTP) is a protocol for the synchronization of clocks via the Internet. With
SNTP, client computers can synchronize their clocks via the Internet with a time server.
SNTP
Single NetworkTime Protocol
SOE
Sequence of Events
SP
Single-point status
SP
Single-Point Indication
SPC
IEC 61850 data type: Single Point Control
SPS
IEC 61850 data type: Single Point Status
SPS
Programmable Logic Controller
SSD
System Specification Description
ST
Structured Text file
SV Stream
Sampled Value Stream
The SV stream is a set of current and voltage values that are transmitted in a fast and cyclical fashion. Informa-
tion exchange is based on a publisher/subscriber mechanism. SV transmission is a continuous stream of
layer-2 Ethernet telegrams in one direction. The content of an SV stream can be configured in anyway you
wish in accordance with IEC 61869-9. IEC 61850-9-2 LE defines a fixed set of 4 voltage and 4 current values
for each SV stream.
TAI
Temps Atomique International - International atomic time
TC
Tap-position command
TCP
Transmission Control Protocol
TEA-X
You can archive the data from individual SIPROTEC 5 devices or whole projects in TEA-X format. This format is
also suitable for data exchange between different applications, such as DIGSI 5 and Engineering Base (EB). The
TEA-X format is based on XML.
Time stamp
A time stamp is a value in a defined format. The time stamp assigns a point in time to an event, for example,
in a log file. Time stamps ensure that events can be found again.
TOCT
Trench Optical Current Transformer – Optical current transformer manufactures by Trench
Topological view
The Topological View is oriented to the objects of a system (for example, switchgear) and their relationship to
one another. The topological view describes the structured layout of the system in hierarchical form. The
Topological View does not assign the objects to the devices.
Transparent clock
The Precision Time Protocol protocol (PTP) recognizes different types of clocks: a standard clock (referred to as
Ordinary Clock, OC for short), a Boundary Clock (BC) and a Transparent Clock (TC). The transparent clock was
integrated in the specification retrospectively in 2008 and serves to improve the transmission of time informa-
tion within a network by receiving PTP messages and modifying (correcting) them before passing them on.
Tree view
The left area of the project window displays the names and icons of all containers of a project in the form of a
folder tree structure. This area is called the tree view.
Tunneling
Technology for connecting two networks via a third network, whereby the through traffic is completely
isolated from the traffic of the third network.
UDP
User Datagram Protocol
URCB
Unbuffered Report Control Block
USART
Universal Synchronous/Asynchronous Receiver/Transmitter
UTC
Universal Time Coordinated
Vendor ID
Manufacturer-specific part of the device labeling for PROFINET.
Virtual device
A virtual device (VD) comprises all communication objects, as well as their properties and states, which a
communication user can utilize in the form of services. A VD can be a physical device, a module of a device or
a software module.
VLAN
Virtual Local Area Network
WYE
Phase-to-ground related measurements of a 3-phase system
A Communication-supervision log 69
Configuring merging units 276
ACD 200 Control functions
Acknowledgment Command logging 740
Spontaneous fault display 73 Controllables 694
Acquisition blocking 207 User-defined objects 196
ACT 199 Control Functions
Advanced protection communication Command Checks 721
Assignment of the protection FG to the FG Protec- Current transformer 264
tion communication 179
Advances protection interface
Indications and measured values of the external
D
synchronization 175
Arc protection 657
Detecting the line disconnector 298
Device-diagnosis log 66
Dimensions 948
B Directional overcurrent protection, phases 523
Disconnector 248, 266
Battery fault 829 Distributed busbar protection 242
Bay proxy DPC 199
Circuit-breaker function group 319 DPS 198
Current-transformer function group 319
Bay type
Bus coupler bay 321
E
Busbar section disconnection bay 321
Feeder bay 321
ENC 201
Bay unit 226
End-fault protection 481
Bus coupler bay 236, 248, 292
Structure of the function 483
Bus coupler differential protection 498
Bus Section without measuring system 295
Bus zone 245
Bus-coupler variants 326 F
Bus-section bays 298
Busbar 246 Fault display
Busbar-section disconnection bay 332 Configuration 72
Spontaneous 72
Fault log 60
Fault record 385
C
Feeder bay 248, 322
Feeder unit 248
Circuit breaker 265
FG Analog units
Trip-circuit supervision 337
Technical data 1021
Circuit-breaker failure protection
Function group
CBFP 427, 451
Bay proxy 319
Client 226
Busbar 314
Combined bus coupler bays 293
Circuit breaker 337
Communication log 67
Current transformer 359
Disconnector 363 N
Switching devices 363
Function group VI 3-phase Negative-sequence protection 552
Overview 370
Structure of the function group 370
O
G Operational log 59
Operational measured values 842
General Functionalities (Undervoltage Check, df/dt Calcu- Optical fiber
lation) 634 Multimode 114
Group Indications Multiplexer 114
Time Overcurrent Protection Functions 550 Repeater 114
Singlemode 114
Order configurator 1034
Ordering
H
Accessories 1035
Individual components 1034
Hardware 240
Other functions
Acquisition blocking 203
Chatter blocking 203
I Manual updating 203
Persistent commands 203
IEC 60529 949 Stored outputs 203
INC 199 Overcurrent protection, ground 514
Indication display Structure of the function 514
Spontaneous 72 Overcurrent protection, phases 504
Indications 52 Structure of the function 504
Displays 55
Read out 52
Reading 52
P
Reading with DIGSI 54
Inherent circuit-breaker failure protection
Power Quality Basics 229
Inherent circuit-breaker failure protection 473
Preference 332
INS 198, 199
Protection communication 112, 150
Constellation measured values 121, 145, 168
Protection interface
L Advanced protection interface, remote data 170,
176
Lockout 75 Checking the protection-data communication 931
Log 57 Indications and measured values in the classic
Configuring 58 protection interface 136
Deleting 70 Indications and measured values of the advanced
Logs 70 protection interface 160
Management 58 Remote data, data bar 141
Setting notes for the classic protection interface 131
Time synchronization 127, 156, 163
M
Manual updating 207
Q
Merging Unit 226
Quality attributes 56
Quality processing for GOOSE Later Binding 88
T
Temperature Monitoring
Technical Data 1022
Topology
Chain topology 112
Ring topology 112
Transfer Busbars 294
Truck-type switchgear 299, 322
U
User log 63
V
Voltage jump detection