Topic 7 Load Estimation
Topic 7 Load Estimation
Maximum Demand
Maximum Demand
• Special Equipment
Electrical Terms
They are:
1. Connected Load
2. Maximum Demand
3. Diversity Factor
Connected Load
Connected Load (CL) – The sum of kW rating of all equipment connected
to the electrical supply.
Example
A small shop is provided with the single-phase loads listed in the table
below. Determine the total connected load in watts and in amperes for the
small shop.
Loads Quantity
Filament lamps each rated at 100W 10
Fluorescent lamps each rated at 40W 24
13A Switch Socket Outlets (SSO)
(assume 300W per SSO) 30
Single-phase air-conditioner rated at 2.5 kW 5
Water heater rated at 1.5kW 2
Single phase motor rated at 2kW 3
Connected Load
Example (Solution)
This means that the maximum demand will be less than the sum of the
load of all the connected equipment depending on the Diversity Factor
applied.
- Ten types of final circuit fed from wiring to which diversity applies
The tables for allowances of diversity are shown in the next 2 slides.
Diversity Factor
Diversity Factor
Maximum Demand and Diversity Factor
Example
A small shop is provided with the single-phase loads listed in the table
below. Applying the diversity factor for each load, determine the maximum
demand (in kW) of the small shop.
Loads Quantity
Filament lamps each rated at 100W 10
Fluorescent lamps each rated at 40W 24
13A Switch Socket Outlets (SSO)
(assume 300W per SSO) 30
Single-phase air-conditioner rated at 2.5 kW 5
Water heater rated at 1.5kW
(Instantaneous) 2
Single phase motor rated at 2kW 3
Maximum Demand and Diversity Factor
Maximum Demand and Diversity Factor
Loads Qty DF MD
10 90% 100W x 10 x 0.9
Filament lamps each rated at 100W
= 0.9kW
24 90% 40W x 24 x 0.9
Fluorescent lamps each rated at 40W
= 0.864kW
Maximum Demand and Diversity Factor
Loads Qty DF MD
10 90% 100W x 10 x 0.9
Filament lamps each rated at 100W
= 0.9kW
24 90% 40W x 24 x 0.9
Fluorescent lamps each rated at 40W
= 0.864kW
13A Switch Socket Outlets 1 100% 300W x 1.0 +
(assume 300W per SSO) 29 75% 300W x 29 x 0.75
= 6.825kW
Maximum Demand and Diversity Factor
Loads Qty DF MD
10 90% 100W x 10 x 0.9
Filament lamps each rated at 100W
= 0.9kW
24 90% 40W x 24 x 0.9
Fluorescent lamps each rated at 40W
= 0.864kW
13A Switch Socket Outlets 1 100% 300W x 1.0 +
(assume 300W per SSO) 29 75% 300W x 29 x 0.75
= 6.825kW
Single-phase air-conditioner 1 100% 2.5kW x 1.0 +
rated at 2.5 kW 4 75% 2.5kW x 4 x 0.75
= 10kW
Maximum Demand and Diversity Factor
Loads Qty DF MD
10 90% 100W x 10 x 0.9
Filament lamps each rated at 100W
= 0.9kW
24 90% 40W x 24 x 0.9
Fluorescent lamps each rated at 40W
= 0.864kW
13A Switch Socket Outlets 1 100% 300W x 1.0 +
(assume 300W per SSO) 29 75% 300W x 29 x 0.75
= 6.825kW
Single-phase air-conditioner 1 100% 2.5kW +
rated at 2.5 kW 4 75% 2.5kW x 4 x 0.75
= 10kW
Water heater rated at 1.5kW 1 100% 1.5kW x 1.0 +
(Instantaneous) 1 100% 1.5kW x 1.0
= 3kW
Maximum Demand and Diversity Factor
Example (Solution)
Loads Qty DF MD
10 90% 100W x 10 x 0.9
Filament lamps each rated at 100W = 0.9kW
24 90% 40W x 24 x 0.9
Fluorescent lamps each rated at 40W = 0.864kW
13A Switch Socket Outlets 1 100% 300W x 1.0 +
(assume 300W per SSO) 29 75% 300W x 29 x 0.75
= 6.825kW
1 100% 2.5kW +
Single-phase air-conditioner
4 75% 2.5kW x 4 x 0.75
rated at 2.5 kW
= 10kW
1 100% 1.5kW x 1.0 +
Water heater rated at 1.5kW
1 100% 1.5kW x 1.0
(Instantaneous)
= 3kW
1 100% (2kW x 1.0) +
Single phase motor rated at 2kW 1 80% (2kW x 0.8) +
1 60% (2kW x 0.6)
= 4.8kW
Maximum Demand and Diversity Factor
Example (Solution)
Loads Qty DF MD
10 90% 100W x 10 x 0.9
Filament lamps each rated at 100W
= 0.9kW
24 90% 40W x 24 x 0.9
Fluorescent lamps each rated at 40W
= 0.864kW
13A Switch Socket Outlets 1 100% 300W x 1.0 +
(assume 300W per SSO) 29 75% 300W x 29 x 0.75
= 6.825kW
Single-phase air-conditioner 1 100% 2.5kW +
rated at 2.5 kW 4 75% 2.5kW x 4 x 0.75
= 10kW
Water heater rated at 1.5kW 1 100% 1.5kW x 1.0 +
(Instantaneous) 1 100% 1.5kW x 1.0
= 3kW
1 100% (2kW x 1.0) +
Single phase motor rated at 2kW 1 80% (2kW x 0.8) +
1 60% (2kW x 0.6)
= 4.8kW
Maximum Demand = 0.9 + 0.864 + 6.825 + 10 + 3 + 4.8 = 26.389kW
Load Estimation
What is load estimation?
• Computation of expected maximum electrical demand of a building
• Determining the capacities of the switchgears required
• Used for the application of electricity supply to the local supply
authority
• Take into consideration the maximum electrical demand of all the
facilities to be installed in the building and the possibility of future
load extension
• So that the capacities of the major equipment such as the
transformers, standby generators, etc. are sufficiently sized
Load Estimation
Two methods:
Initial planning stage, the detail design of the lighting system, general
power and air-conditioning system are not known.
Exact load requirement based on the actual design could not be made.
Based on past experience of electrical load per unit area in similar type
of development.
Other electrical loads which are not proportional to the area usage.
Escalators 4 20 0.85
Fire sprinkler pump 1 30 1.0
Basement 30 - 50 15 -
Halls, corridors 5 - - Main floor 25 - 45 10 50 - 70
Upper floor 20 - 40 5 -
Dwelling (not hotel):
Storage spaces 2.5 - - 0-300m2 30 5 -
300-12000m2 20 2.5 -
Above 12000m2 10 1.5 -
Car park (commercial) 5 1.5 -
Hospital 20 - 30 10 50 - 70
Hotel:
Lighting Power Air-conditioning Lobby 10 - 30 5 50 - 80
Type of occupancy Rooms (no 10 - 25 5 30 - 50
(W/m2) (W/m2) (W/m2) cooking)
Industrial building 10 - 20 10 -
Laboratories 30 - 40 50 - 200 60 - 100
Library 15 - 35 5 50 - 70
Office Building 15 - 35 15 40 - 70 Office Building 15 - 35 15 40 - 70
Restaurant 15 - 25 2.5 60 - 100
Shops 20 - 50 5 -10 40 - 90
School 15 - 35 15 35 - 50
Warehouse (storage) 2.5 - 10 2.5 -
General building:
Halls, corridors 5 - -
Storage spaces 2.5 - -
Example (Solution)
(commercial)
Example (Solution – con’t)
Therefore,
Maximum Demand of the building = 2131.86 + 406 = 2537.86kW
End of Topic 7