IOM Magnum SDM W Orifice
IOM Magnum SDM W Orifice
IOM Magnum SDM W Orifice
for:
Shipment/Storage of Equipment
• Upon delivery, check equipment for structural damage during shipment. Damages must be
reported to EDI within 10 days of delivery.
• All aeration system piping and diffusers must be stored in such a manner as to prevent any
deformation resulting from flexing, cracking or softening. Contractor shall insure that the
stored equipment is properly stacked to avoid warpage, has adequate cover and ventilation
to avoid exposure to the heat of the day or direct sunlight. EDI recommends utilizing the
original unopened shipping cartons.
Installation Instructions for FlexAir® SDM Diffuser Units with locking rib on
wedge.
Each duplex diffuser assembly consists of:
• One "Male" diffuser that has protruding alignment pins, a red “TOP” sticker applied near the wedge
ramp, and wedge retaining ribs at small end of ramp.
• One "Female" diffuser that has alignment slots, a red “TOP” sticker applied near the wedge ramp, and
wedge retaining ribs at small end of ramp.
• Two wedges with locking rib.
• Two o-rings.
• One alignment plug
Locking Rib
Interlocking Ribs
Note: The lateral will have two different sized holes. The smaller hole is the air flow orifice for one side
of the duplex diffuser and the larger hole is for the alignment plug.
3) Tap the plug into the lateral using a soft blow hammer and a short piece of 1.0 inch diameter dowel
(provided by EDI).
4) Ensure that the plug is correctly seated and was not damaged during the installation. Replace any plug
if damage occurred.
Installing of diffusers on air lateral piping:
5) Install O-ring immediately before saddle is to be installed on lateral. The o-ring is placed in the
internal groove. DO NOT USE ANY MASTIC OR OTHER ADHESIVE.
6) There are retaining bumps to hold the o-ring in place during installation. Note: The o-ring must be
able to move to seal when pressure is applied. Note: During cold weather installation, below 40°F
(4°C), it is advisable to keep the o-rings warm. One method is to place the o-rings in a bucket of
warm water.
7) Position the diffuser unit in the proper orientation (see table below) while positioning the alignment
plug to the center hole in the saddle. The plug fits into the saddle.
RED
Ear of “TOP”
Unit Type Perforation Clamp Sticker
MiniPanel On Top On Top On Top
Magnum On Sides On Top On Top
8) Note: Ensure that the saddles’ alignment pins mate properly when installing the opposing saddle
before sliding on the wedges. The red “TOP” stickers should face up.
10) Install the bottom wedge hand tight-approximately 3/4 inch (19mm) from being flush with the saddle.
11) Ensure that the diffuser assembly is in the correct location, level, and that each diffuser arm is in line
with the rest of the diffusers on the shared lateral.
12) Tighten the top wedge and bottom wedge EQUALLY with a non-metallic mallet or rubber faced
hammer. When properly tightened, each diffuser should be level and resist rotation. Note: Metal
mallets or hammers may crack or shatter the wedge assembly or damage the unit. Do not use metal
hammers directly. Note: Extra care is needed during cold weather installation, below 40°F (4°C).
Plastic components become brittle and may fracture with excessive impact force.
13) Ensure that wedges are driven on as equally as possible while maintaining level on the diffusers. The
wedges should be flush with that saddle when complete. Over-tightening wedges can cause
irreversible damage to the diffuser saddle.
NOTE: Diffusers must be protected from the sun. Long term exposure to direct summer sunlight
can cause failure. Diffusers need to either be protected from the sun or heat by covering them with
clean water or shade over the basin.
(OPTIONAL) Water Flush and Air Purge Cleaning of
Piping
These instructions cover the general procedure, which may be utilized to clean the piping in a
fine or medium bubble diffuser system. Special pipe cleaning requirements outlined in the
Engineer’s specifications, contract documents, or instructions offered by EDI shall be
supplementary to or take precedent over the general instructions outlined below.
Water Flush Cleaning
• Water flush cleaning is the recommended method to clean assembled piping systems where
pipe segments are too long for manual cleaning. This procedure can be used in conjunction
with air purge cleaning and is recommended when fine debris is not removed prior to
assembly of piping. When both water flush and air purge are used, the water flush
procedure should be implemented first.
• To water flush the system, connect a water supply to the air header or make individual
connections to each lateral. If flush water is piped to the header, it is imperative that the
header be throttled or stubbed such that water does not flood the blowers.
• Clean water must be used. It is not necessary to use potable water but the flush water must
be free of silt or debris.
• Flush header assembly prior to water flushing the laterals. To flush the header, fill it with
water and open the end lateral to create a flush velocity in the header of at least two feet per
second (if possible).
• Next, the laterals are to be individually flushed at a recommended velocity of five to six feet
per second. Opening one isolation valve will produce a significant flushing action in the
lateral as water is pumped through the header. The lateral end cap or one or two drilled air
outlet holes should be uncapped to allow water and debris to be flushed out of the piping.
• The cleaning procedure in the previous step should be completed for each of the laterals.
This is done by sequentially opening and closing the isolation valves on the individual
laterals.
• As an alternate to using the main header/lateral flush procedure, the individual laterals may
be cleaned independent of the main header. For this operation, the individual laterals are
disconnected from the main header and cleaned individually.
Trouble Shooting
The FlexAir aeration system requires very little maintenance for long term operation. Periodic
visual inspection of the system should allow the Operator to determine if the system is
performing at optimum levels. For example, diffuser unit elevation variations greater than the
design tolerance, typically ± 1", will reduce the uniformity of air distribution in the system. In
addition, operating airflows below the design condition will also reduce the uniformity of air
distribution. If operating conditions warrant airflow rates below the design condition, contact EDI
for additional operational guidelines.
Below are symptoms and procedures to follow if inspection of the aeration system reveals
abnormal operating characteristics:
1. Large volume of air in localized area
Possible Cause: a. Air leak in aeration piping.
b. Diffuser sleeve damaged or missing.
Shutdown Conditions
If an interruption in air service is experienced at any time, restoration of air service should be
instituted as soon as possible. When restarting positive displacement blower units, the start-up
pressure surge should be reduced by down-weighting the pressure relief valve (PRV) or
operating the blow-off valve. Once the blower is operational, reset the PRV or slowly close the
blow-off valve over a five to ten minute period. The PRV must be set properly to prevent
overloading of the blower system. Operate water purge devices if provided. If the PRV
releases air for an extended period of time, the relief setting should be checked.
• If the basin is to be idle for a prolonged time period, the basin should be drained and
cleaned. NOTE: Maintain the minimum airflow to the system during the drain down
procedure. For maximum protection of the aeration system, refill the basin to completely
submerge the aeration system. This provides thermal protection in the event of severe cold
or hot weather conditions.
• Contact EDI for additional operation and maintenance information if it is necessary to
decrease the system airflow during cold weather.
Operation of the FlexAir Diffuser
The FlexAir unit has no moving parts and requires very little maintenance for long term
operation. EDI recommends that the air supply to the diffusers be maintained at all times for
optimum performance. The airflow to the FlexAir units must be kept within the ranges
summarized in Table 2 to maintain the structural and operating characteristics of the diffuser
membrane. Continuous application of high airflows, greater than denoted for normal operation
may result in physical damage to the diffuser membrane. Under no circumstances should the
airflows indicated as maximum be exceeded. NOTE: Use caution when adjusting several
lateral throttling valves in the same piping system. This procedure can result in elevated
airflows in sections of the basin, exceeding the maximum allowable airflow to each FlexAir unit.