Data Alat Proteksi 2023
Data Alat Proteksi 2023
Data Alat Proteksi 2023
General - Values:
TimeTolAbs: 0.04 s VT connection: At protected object
TimeTolRel: 5.00 % CT starpoint connection: To protected object
CurrentTolAbs: 0.05 Iref
CurrentTolRel: 5.00 %
Directional: No
Elements - Phase:
Active Name Tripping characteristic I Pick-up Time Reset Ratio Direction
Yes I #1 Phase IEC Normal Inverse 0.29 Iref 0.24 0.95 Non Directional
Test Module
Name: OMICRON Overcurrent Version: 3.00 SR 2
Test Start: 02-Mar-2023 09:30:17 Test End: 02-Mar-2023 09:30:28
User Name: Manager:
Company:
Test Settings:
Fault Model:
Time reference: Fault inception
Load current: 0.00 A
Load angle: 0.00 °
Prefault time: 0.10 s
Abs. max time: 240.00 s
Post fault time: 0.50 s
Rel. max time: 100.00 %
Enable voltage output: No
Fault voltage LN (for all but two phase faults): 30.00 V
Fault voltage LL (for two phase faults): 51.96 V
Decaying DC active: No
Time constant: 0.05 s
CB char min time: 0.05 s
Thermal reset active: No
Thermal reset method: Manual
Thermal reset message: Please reset the Thermal Memory of the device under
test before continuing.
Shot Test:
Type Relative To Factor Magnitude Angle tnom tmin tmax
L1-L2 I #1 Phase 10.172 2.95 A n/a 707.6 ms 652.7 ms 763.9 ms
L1-L2 I #1 Phase 9.862 2.86 A n/a 717.4 ms 662.1 ms 774.2 ms
L1-L2 I #1 Phase 9.448 2.74 A n/a 731.4 ms 675.5 ms 788.9 ms
L1-L2 I #1 Phase 8.966 2.60 A n/a 749.3 ms 692.6 ms 807.6 ms
L1-L2 I #1 Phase 8.379 2.43 A n/a 773.6 ms 715.9 ms 833.2 ms
Binary Outputs:
Name State
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
Binary Inputs:
Trigger Logic: And
Name Trigger State
Trip 1
Start X
L1-L2 n/a
10000.0
1000.0
100.0
t/s
10.0
1.0
State:
5 out of 5 points tested.
5 points passed.
0 points failed.