CESI A9033826 Blue TR
CESI A9033826 Blue TR
CESI A9033826 Blue TR
A9033826
Tested samples/items Three-pole indoor vacuum contactor set in power-cube frame, equipped
with short-circuit protective device (current-limiting fuses)
Type CEF and CMF
Tests carried out Verification of coordination with short-circuit protection device (SCPDs)
PUBBLICATO A9033826 (PAD - 1278768)
The results reported in this document relate only to the tested samples/items.
Partial reproduction of this document is permitted only with the written permission from CESI.
Any reference to the Accreditation Body shall include name, registration number and scope.
Prepared
Prepared QED - Beccarini Pierangelo
Unit LABORATORIES
A9033826 2925 AUT - P. Beccarini
Verified
Verified QED - Arneodo Giorgio,-PPR
Unit LABORATORIES
A9033826 503478 VER
- Ghezzi Giuseppe
G. Ghezzi A9033826 2992 VER
Approved
Approved LAP - Il Responsabile - Nicolini
Unit LABORATORIES
A9033826 821814 APP
Roberto
- R. Nicolini
D1265IG
CESI Via R. Rubattino 54 Capitale sociale 8 550 000 Euro Registro Imprese di Milano
Centro Elettrotecnico 20134 Milano - Italia interamente versato Sezione Ordinaria
Sperimentale Italiano Telefono +39 022125.1 Codice fiscale e numero N. R.E.A. 429222
Giacinto Motta spa Fax +39 0221255440 iscrizione CCIAA 00793580150 P.I. IT00793580150
http://www.cesi.it
CESI
A9033826
Tests witnessed by
Only for laboratory requirement, in order to reproduce the test conditions, all the laboratory data are contained in the
document marked: A9009134
The measurement uncertainties of the test results reported in the document are the following:
voltage: ± 5 % ; current: ± 5 % ; time: ± 5 % ; temperature: ± 2 °C
The measurement uncertainties are estimated at the level of twice the standard deviation (corresponding, in the case of
normal distribution, to a confidence level of about 95 %) and have to be considered as maximum values.
D1001IG
D1002IG
A9033826
Test Report CESI Approved Page 3
CESI
A9033826
Power-cube frame
Manufacturer ABB
Type PB1/F
Serial number 1VC1AM00009255
Voltage 12 kV
Insulation level
Lightning impulse withstand voltage
To earth and between phases 75 kV
Power frequency withstand voltage
To earth and between phases 28 kV
Frequency 50/60 Hz
Normal current 400 A
Short-time withstand current
Main circuit 31,5 kA
Peak withstand current
Main circuit 79,0 kA
Short-circuit duration 3s
Cont’d
D1008IG
CESI
A9033826
Cont’d
Cont’d
D1180IG
CESI
A9033826
Cont’d
Cont’d
D1089IG
CESI
A9033826
Cont’d
- Fuse base
Voltage 7,20 kV
Current 200 A
Lightning impulse withstand voltage 60 kV
Power frequency withstand voltage 20 kV
- Fuse link
Type CEF 3,6/7,2-200
Voltage 3,6-7,2 kV
Current 200 A
Frequency 50 Hz
Maximum breaking current 50 kA
Minimum breaking current (at 7,2 kV) 650 A
Cont’d
D1004IG
CESI
A9033826
Cont’d
- Fuse base
Voltage 7,2 kV
Current 315 A
Lightning impulse withstand voltage 60 kV
Power frequency withstand voltage 20 kV
- Fuse link
Type CMF 7,2-315
Voltage 7,2 kV
Current 315 A
Frequency 50 Hz
Maximum breaking current 50 kA
Minimum breaking current (at 7,2 kV) 950 A
Cont’d
D1089IG
CESI
A9033826
Cont’d
- Fuse base
Voltage 3,6 kV
Current 315 A
Lightning impulse withstand voltage 30 kV
Power frequency withstand voltage 10 kV
- Fuse link
Type CMF 3,6-315
Voltage 3,6 kV
Current 315 A
Frequency 50 Hz
Maximum breaking current 50 kA
Minimum breaking current (at 3,6 kV) 900 A
Cont’d
D1089IG
CESI
A9033826
Cont’d
- Fuse base
Voltage 12 kV
Current 200 A
Lightning impulse withstand voltage 75 kV
Power frequency withstand voltage 28 kV
- Fuse link
Type CEF 12-200
Voltage 12 kV
Current 200 A
Frequency 50 Hz
Maximum breaking current 50 kA
Minimum breaking current (at 12 kV) 650 A
Cont’d
D1089IG
CESI
A9033826
Cont’d
- Fuse base
Voltage 12 kV
Current 200 A
Lightning impulse withstand voltage 75 kV
Power frequency withstand voltage 28 kV
- Fuse link
Type CMF 12-200
Voltage 12 kV
Current 200 A
Frequency 50 Hz
Maximum breaking current 50 kA
Minimum breaking current (at 12 kV) 560 A
D1089IG
D1015IG
A9033826
Test Report CESI Approved Page 12
D1232IG
Three-phase making and breaking tests at the rated short-circuit current; test duty A and B with 51,7 kA at 7,40 kV
Test circuit : See D0051 Power factor : <0,15 Frequency : 50 Hz
Condition of the CONTACTOR before the tests: new (VSC 7/P DC0) - 1VC1AM00008017
Condition of the FUSE before the tests: new (CEF 3,6-7,2-200)
Condition of the apparatus after the tests: no remarks; during the tests No.1 and 2 the contactor operated properly.
A9033826
Test Report CESI Approved Page 13
D1245IG
Three-phase making and breaking tests at the rated short-circuit current; test duty A and B with 51,7 kA at 7,40 kV
Test circuit : See D0051 Power factor : <0,15 Frequency : 50 Hz
Condition of the CONTACTOR before the tests: as after the test No.2 (VSC 7/P DC0) -1VC1AM00008017
Condition of the FUSE before the tests: new (CMF 7,2-315)
Condition of the apparatus after the tests: no remarks; during the tests No.3 and 4 the contactor operated properly.
A9033826
Test Report CESI Approved Page 14
D1232IG
Three-phase making and breaking tests at the rated short-circuit current; test duty A and B with 50,1 kA at 3,90 kV
Test circuit : See D0051 Power factor : <0,15 Frequency : 50 Hz
Condition of the CONTACTOR before the tests: as after the test No.4 (VSC 7/P DC0) - 1VC1AM00008017
Condition of the FUSE before the tests: new (CMF 3,6-315 )
Condition of the apparatus after the tests: no remarks; during the tests No.5 and 6 the contactor operated properly.
A9033826
Test Report CESI Approved Page 15
D1232IG
Three-phase making and breaking tests at the rated short-circuit current; test duty A and B with 50,9 kA at 12,1 kV
Test circuit : See D0051 Power factor : <0,15 Frequency : 50 Hz
Condition of the CONTACTOR before the tests: new (VSC 12/P DC0) -1VC1AL00031865
Condition of the FUSE before the tests: new (CEF 12-200)
Condition of the apparatus after the tests: no remarks; during the tests No.7 and 8 the contactor operated properly.
A9033826
Test Report CESI Approved Page 16
D1232IG
Three-phase making and breaking tests at the rated short-circuit current; test duty A and B with 50,9 kA at 12,1 kV
Test circuit : See D0051 Power factor : <0,15 Frequency : 50 Hz
Condition of the CONTACTOR before the tests: as after the test No.8 (VSC 12/P DC0) -1VC1AL00031865
Condition of the FUSE before the tests: new (CMF 12-200)
Condition of the apparatus after the tests: no remarks; during the tests No.9 and 10 the contactor operated properly.
A9033826
Test Report CESI Approved Page 17
D1248IG
Condition of the apparatus before the tests: as after the test No.6 (VSC 7/P DC0) - 1VC1AM00008017
Condition of the apparatus after the tests: during each test the contactor operated properly.
A9033826
Test Report CESI Approved Page 18
D1232IG
Condition of the apparatus before the tests: as after the test No.10 (VSC 12/P DC0) - 1VC1AL00031865
Condition of the apparatus after the tests: during each test the contactor operated properly.
A9033826
Test Report CESI Approved Page 19
CESI
A9033826
Symbols used in this diagram are the same as those on the oscillograms.
D0051IG
CESI
A9033826
Symbols used in this diagram are the same as those on the oscillograms.
D0061IG
CESI
A9033826
Photo No.1
(VSC 7/P DC0) - 1VC1AM00008017
Photo No.2
(VSC 7/P DC0) - 1VC1AM00008017
D1091IG
CESI
A9033826
Photo No.3
(VSC 12/P DC0) - 1VC1AL00031865
Photo No.4
(VSC 12/P DC0) - 1VC1AL00031865
D1091IG
CESI
A9033826
Photo No.5
CEF 3,6/7,2-200
Photo No.6
CEF 3,6/7,2-200
D1091IG
CESI
A9033826
Photo No.7
CMF 7,2-315
Photo No.8
CMF 7,2-315
D1091IG
CESI
A9033826
Photo No.9
CMF 3,6-315
Photo No.10
CMF 3,6-315
D1091IG
CESI
A9033826
Photo No.11
CEF 12-200
Photo No.12
CEF 12-200
D1091IG
CESI
A9033826
Photo No.13
CMF 12-200
Photo No.14
CMF 12-200
D1091IG