Genset Model:P200P

DIESEL GENERATOR SET 220V-380V 3P4W

The picture only for reference.

Generator Specification
Performance Data
Service PRP (1) ESP (2)
Model P200P
Power (kVA) 200 220
Engine brand Perkins
Power (kW) 160 176
Engine model 1106A-70TAG4
Rated speed ( r.p.m) 1500
Speed control type Electronic
Standard voltage (V) 400/230V
Phase 3
Rated at power factor(cos phi) 0.8
Control system Digital
Star ter motor voltage 12V
Frequency 50HZ
Superwatt Power gensets are compliant with ISO 9001 and CE standard, which include the
following directives:
Engine speed (RPM) 1500
·2006/42/EC Machinery safety.
100% standby power 49.4
·2006/95/EC Low voltage
Fuel
·EN 60204-1: 2006+A1: 2009, EN ISO 12100: 2010, EN ISO 13849-1: 2008, EN 100% prime power 45.8
12601 : 2010 Consumption
75% prime power 34.7
(L/H)
50% prime power 23.1
(1) PRP (Prime Power):
According to ISO8528-1, prime power is the maximum power available during a variable
power sequence, which may be run for an unlimited number of hours per year, between Standard reference Conditions
stated maintenance intervals. The permissible average power output during at 24 hours Note: Standard reference condition 25℃ (77℉) air inlet temp, 100m(328ft) A.S.L 30%
period shall not exceed 80% of the prime power. 10% overload available for governing relative humidity. Fuel consumption dat with diesel fuel with specific gravity of 0.85 and
purposes only. conforming to BS 2869: 1998, Class A2

(2) ESP (Standby Power):


L L
According to ISO 8528-1, It is defined as the maximum power available, under the
agreed operating conditions, for which the generating set is capable of delivering for up
to 500 hours of operation per year (of which no more than 300 hours for continuative H
H
use) with the maintenance intervals and procedures being carried out as prescribed by W
W
the manufacturers. No overload capability is available.

Dimension and Weight


Dimension Open Silent
Powers ESP PRP Standby
Length (L) 2763mm 3600mm
Voltage (V) KVA KW KVA KW Amps
Width (W) 890mm 1100mm
415/240 220 176 200 160 306.1
Height (H) 1375mm 2170mm
400/230 220 176 200 160 317.6 Net Weight 1560KG 2399KG
380/220 220 176 200 160 334.3 Fuel Tank (L) - 220L
Note: This parameters allows for some acceptable deviations.
Engine Specification: 1106A-70TAG4

Basic technical data Induction system

No. of cylinders 6 Clean filter 2kpa

Cylinder arrangement In-line Dir ty filter 3kpa

Cycle 4 stroke Air filter type paper element

Induction system Turbocharged

and air charge cooled

Compression ratio 16:1

Bore 105mm
Lubrication system
Stroke 135mm
Total lub capacity 16.5L
Displacement 7.01L
Sump minimum 12.4L
All ratings cer tified to within ± 3%
Sump maximum 14.9L
Estimated total weight 788kg
Maximum engine operating angles

-front up, front down, right side

or left side 25°

Lubricating oil pressure


Cooling system -Relief valve opens 430kPa

Total coolant capacity - at maximum no-load speed 340kPa

-with radiator 21L Oil consumption at full load


-without radiator TBD as a % of fuel consumption <0.1

Maximum top tank temp 110℃


Thermostat operation range 85-95℃
Radiator face area 0.351 m²
Rows and material 4 rows, aluminium
Pressure cap setting 100 kPa Electrical system

Fan diameter 610 mm Type A115i

Drive ratio 1.2 : 1 Alternator voltage 12 volts

Number of blades 7 Alternator output 85 amps

Star ter motor voltage 12 volts

Star ter motor power 4.0 kw

Fuel system

Injection system Mechanical

Fuel injection pump DP210G General installation Prime power

Manual Gross engine power 178.9kW


Priming pump type
90 seconds Brake mean effective pressure 2041.8kPa
Maximum priming time
Electronic Combustion air flow 12.6m³/min
Fuel lift pump type
TBD Exhaust gas temperature outlet 580°C
- flow/hour
TBD Energy to charge coolers 32.8kW
- pressure
Power to exhaust 148.1kW
Maximum suction head:

-1500 rev/min 10 kPa


Alternator Specification Stamford UCI274H
Emergency voltage curve

Sudden increase warp


Alternator Sudden voltage warp Sudden decrease warp
520
Number of phase 3
464
Power factor (Cos Phi) 0.8
+ 1%
408 +380
1%
Poles 4 380
- 1%

Winding Connections (standard) Star-serie 352

Terminals 12 296

Insulation type H class 240


0 1 2 3 4 5 6 7 8 9 10 11 12
δu%: -18.18 Benchmark phase: A Min. voltage: 310.9V Recovery time: 1.95s
Winding Pitch 2/3 δu%: 8.89 Benchmark phase: A Max. voltage: 413.8V Recovery time: 0..12ss

IP rating IP23

Excitation system Self-excited

Bearing Single bearing

Coating Vacuum impregnation


Emergency frequency curve
Voltage regulator A.V.R
Sudden increase warp
Sudden voltage warp Sudden decrease warp
Couping Flexible disc
70

62

54 +1%%
+-1150
%
50
- 1%
46

38

30
0 1 2 3 4 5 6 7 8 9 10 11 12
δf%:
%: -10.64 Benchmark phase: A Min. frequency: 44.68Hz Recovery time: 1..95s
Three phase Reliable Single phase
δf%:
%: 7.74 Benchmark phase: A Max. frequency: 53.87Hz Recovery time: 0..54s

Options

Engine Alternator Generator Sets Fuel System

· Water Jacket · Winding Temp measuring · Tools with the machine · Low fuel level alarm
Pre-heater Instrument · Extended range fuel tank · Automatic fuel
· Fuel heater · Alternator Pre-heater · Bunded fuel tank feeding system
· PMG · Fuel T-valves
· Anti-damp and anti-corrosion
treatment
· Anti-condensation heater
· Winding and bearing RTD

Canopy Lub oil system Cooling System Control Panel

· Rental type · Oil Pre-heater · Front heat protection · Remote control panel
Canopy · Oil temp sensor · ATS
· Trailer · Synchronizing controller
· Adjustable ear th leakage
relay
Control Panel Deepsea DSE4520

Configuration Benefits

· Emergency stop button · Less wiring and components


· Integrated solution
· Protection MCB
· Less engineering and programming
· Battery charger · User friendly set-up and button layout
· Integrated aviation plug · Module can be configured to suit individual applications
· ATS connection · PC software for simplified configuration
· Digital control module · Wide range of communication capabilities

Features Operation conditions

· 3 phase generator set monitoring · Operation temp: -20 ˚C to + 70 ˚C


· S uppor t of engines equipped with electronic control · Storage temp: -30 ˚C to + 80 ˚C
unit · Operating humidity: 95% w/o condensation
· Comprehensive diagnostic message · Vibration: 5-25Hz, ±1.6 mm
· A utomatic or manual star t / stop of the gensets 5-1 00 Hz , a=4g
· Push buttons for simple control , lamp test · Shocks: a= 500m/s²

· G raphic back - lit LCD display


· Parameters adjustable via keyboard or PC
· Mains measurements ( 50HZ / 60HZ ): Options
U1 - U3, Hz
· Generator measurements ( 50HZ / 60HZ ): · Ethernet interface (Remote monitoring and control)
U1 - U3, I1 - I3, Hz, kW, kVAr, kWh · GSM modem/wireless internet (Remote monitoring and control)
· Comprehensive shutdown or warning on fault condition · RS232-RS485 Dual por t interface
· 3 Phasa Generator Protections · Synchronizing control panel
· Distribution board with sockets kit and power busbar
- Over - / under voltage
· Battery trickle charge ammeter
- Over - / under frequency
· Ear th leakage protection
- Current / voltage asymmetry · Ear th fault protection
- Over current / overload · Low fuel level alarm
· 3 phase AMF function · Low fuel level shutdown
- Over-/under frequency · High fuel level alarm
- Over-/under voltage · Fuel transfer system control
- Voltage asymmetry · Low coolant level shutdown
· Configurable analog inputs · High lube oil temp shutdown
· Battery voltage, engine speed (pick-up) measurement · Overload via alarm switch on breaker
· Configurable programmable binary inputs and outputs · Engine coolant heater controls
· Warm-up and cooling functions · Control panel heater
· Generator C.B. and Mains C.B. control with feedback · S peed adjust switch
and return timer
· Oil temp displayed on LCD screen
· RS232 interface
· Additional 8 inputs and outputs
· Modem communication suppor t
· Hours counter
· Sealed to Ip65
· Event log