Wall Mounting Single Relay Output Module
The single channel output modules are loop-powered, designed
around a fully digital protocol and provide form C changeover
contacts for activating equipment for DDA compliance such as
vibrating pillows.
The output channel is a normally de-energised relay switched on
by a command from the control panel.
The unit provides a fast and secure response, and incorporates
a bidirectional short circuit isolator.
Connections are made using plug-in terminal blocks which will
accept conductors up to 2.5mm ² .
The unit is supplied fixed to a plate which is suitable for wall
mounting with a choice of standard 25 mm or deep 47 mm
mounting boxes available.
Features
Short circuit isolators in each device to the requirements of
EN54-17
Auto-addressing capability (by the control panel) or manually
using a hand held programmer.
Digital checking of double address
Line quality information
Bicolour (red/green) LED driven by the control panel
Standards and Approvals
EN54-17:2005
EN54-18:2005
Specification
Power supply 15 - 40 Vdc
Maximum alarm current consumption 6 mA
Relay switching 2 A / 30 Vdc
Operating temperature range -30°C to +70°C
Humidity (non condensing) 85% RH
Dimensions H x W x D mm 87 x 87 x 32
Weight 200 g
Version [1.1] Page 1 of 2
www.advancedco.com
IP rating 21C
Order Codes and Options
20-VMC120-ADV: Wall Mounting Single Relay Output Module
Check if this document is up to date | Give us feedback
Advanced, The Bridges, Balliol Business Park, Newcastle upon Tyne, NE12 8EW, UK T: +44 (0)345 894 7000, E: [email protected],
W: www.advancedco.com