Kidde Fire Systems is very pleased to introduce a group of new products to meet the need to monitor the
placement of electric actuators on discharge control heads and directional valves, as required by NFPA 2001-
1 2 3 4
2012 , UL 2166 , UL 2127 and FM 5600 . These requirements are effective as of January 1, 2016. All systems
installed on and after this date must be able to monitor these electrical actuators to be compliant with code and
agency requirements.
At your next service interval the CHM can be added and wired to your existing control unit. There is no longer
the need to worry that an electric actuator may have been accidentally left off a discharge control head.
Our CHM is truly a supervised solution. It comes standard with 4 wires to ensure that not only are you
supervising the placement of the electric actuator but that you are also supervising the complete circuit from
panel to CHM to junction box for continuity (in accordance with UL 864 Standard for Control Units and
th
Accessories for Fire Alarm Systems 9 Edition).
3M™ and Novec™ are trademarks of 3M © 2015 Kidde-Fenwal, Inc. All Rights Reserved
Bulletin #15-50K
The CHM is also universal in use. It fits on all clean agent storage cylinder valves (1.5, 2.0 and 3.0 inch) the
Advanced Delivery System (ADS) Nitrogen Drivers and the Nitrogen Pilot Cylinders for both HFC-227ea and 3M™
Novec™ 1230 Fire protection Fluid platforms. It comes standard for use in hazardous locations Class I groups C &
D, Class II groups E, F & G and Class III and will be identified as such.
In order to maintain the cULus Listing and FM Approval of Clean Agent Suppression Systems starting January 1,
2016, all electric actuators must be installed with a placement monitor. To this end Kidde Fire Systems is offering
Actuation Kits (see table 1) that will include the electric actuator along with the CHM.
Table 1
New P/N Description Old P/N Old P/N Status
85-486500-010 Control Head Monitor - New
Stackable Explosion proof 82-486500-010 Discontinued
(1.5 and 2 inch valves only)
Lever Operated Control Head WK-870652-000 Spare
(required per NFPA 2001)
85-890181-000 Control Head Monitor - New
Electric Control Head WK-890181-000 Discontinued*
85-897494-000 Control Head Monitor - New
Electric Control Head Explosion Proof WK-897494-000 Discontinued*
85-895630-000 Control Head Monitor - New
Electric Control Head with 81-895630-000 Discontinued*
Cable operated control head
* The discontinuance of these products is effective for new Clean Agent platforms only. Electric Actuators used
on our CO2 platform with the same part numbers will not be discontinued and can be purchased as normal or as
spare parts.
Table 2
New P/N Description Old P/N Old P/N Status
The CHM is placed between the valve and electric actuator. See figure 1. The actuator is installed in the same
manner as normal and there is no interference with the CHM. When installed, it does not sit completely snug
against the valve. This play allows for easier attachment of a conduit.
Electric Actuator
CHM
Figure 1
2
Bulletin #15-50K
New part numbers for directional valves with placement monitor are shown in table 3:
Table 3
Old P/N
New P/N Description Old P/N
Status
Clean Agent
85-220030-001 3 Way Selector Valve 1/2" 90-220030-001 Discontinued
85-220030-100 3 Way Selector Valve 1/2" Explosion-Proof 90-220030-001 Discontinued
85-220030-002 3 Way Selector Valve 3/4" 90-220030-002 Discontinued
85-220030-200 3 Way Selector Valve 3/4" Explosion-Proof 90-220030-002 Discontinued
85-220030-003 3 Way Selector Valve 1" 90-220030-003 Discontinued
85-220030-300 3 Way Selector Valve 1" Explosion-Proof 90-220030-003 Discontinued
85-220031-001 3 Way Selector Valve 1 1/4" 90-220031-001 Discontinued
85-220031-100 3 Way Selector Valve 1 1/4" Explosion-Proof 90-220031-001 Discontinued
85-220031-002 3 Way Selector Valve 1 1/2" 90-220031-002 Discontinued
85-220031-200 3 Way Selector Valve 1 1/2" Explosion-Proof 90-220031-002 Discontinued
85-220031-003 3 Way Selector Valve 2" 90-220031-003 Discontinued
85-220031-300 3 Way Selector Valve 2" Explosion-Proof 90-220031-003 Discontinued
85-220032-001 3 Way Selector Valve 3" 90-220032-001 Discontinued
85-220032-100 3 Way Selector Valve 3" Explosion-Proof 90-220032-001 Discontinued
85-220032-002 3 Way Selector Valve 4" 90-220032-002 Discontinued
85-220032-200 3 Way Selector Valve 4" Explosion-Proof 90-220032-002 Discontinued
Inert Gas
85-609800-001 2 Way Selector Valve 1/2" 38-609800-001 Discontinued
85-609800-002 2 Way Selector Valve 3/4" 38-609800-002 Discontinued
85-609800-003 2 Way Selector Valve 1" 38-609800-003 Discontinued
85-609800-004 2 Way Selector Valve 1 1/4" 38-609800-004 Discontinued
85-609800-005 2 Way Selector Valve 1 1/2" 38-609800-005 Discontinued
85-609800-006 2 Way Selector Valve 2" 38-609800-006 Discontinued
To retrofit installed directional valves, use the appropriate bracket/switch assembly shown in table 4:
Table 4
New P/N Description Old P/N Old P/N Status
85-220000-001 Retrofit Kit - Clean Agent Selector Valves, - New
Standard switch
85-220000-100 Retrofit Kit - Clean Agent Selector Valves, - New
Explosion proof switch
3
Bulletin #15-50K
Product Availability
The new directional valve part numbers and retrofit kits referenced in tables 3 and 4 are in the price list
effective January 4, 2016.
Orders placed prior to January 1, 2016 but which will be shipping after this date, must include the Control Head
Monitor p/n 85-100000-100. A Customer Service Representative will contact you to add this item to your order.
Table 5
Price List Update
New P/N Description & Order
Acceptance
85-486500-010 Stackable Explosion proof with Control Head Monitor (1.5 & 2 in. valves only) Jan. 4, 2016
85-890181-000 Electric Control Head with Cable operated control head and Control Head Monitor Jan. 4, 2016
85-897494-000 Electric Control Head Explosion Proof with Control Head Monitor Jan. 4, 2016
85-895630-000 Electric Control Head with Cable operated control head and Control Head Monitor Jan. 4, 2016
To retrofit existing electric control heads the CHM retrofit kit will be available as follows:
Table 6
Price List Update
Ne w P/N De scription & Orde r
Acce ptance
85-100000-100 Control Head Monitor Jan. 4, 2016
Legacy Brands
Chemetron Fire Systems Chemical Clean Agent Systems can only be used to replace legacy systems installed prior
to January 1, 2016. New installations will not comply with the placement monitor requirement.
Fenwal Protection Systems series 9300 Top Discharge Cylinders fall under the same design requirements as the
Kidde cylinders and therefore retrofits can be accomplished in the same manner. New installations will not
comply with the placement monitor requirement. Fenwal Sphere and Bottom Discharge platforms use electro-
explosive actuators which, given that they can be tested without physical removal of the squib from the valve,
5
are not required to be monitored for placement as per NFPA 2001-2012 .
Tools
The installation of the CHM and DVCHM on electric actuators and directional valves is simple. Nevertheless, we
have created a slide show to serve as a guide to aid better understanding of the process before the next
Technical Training school. The guide can be downloaded from the Distributor Extranet.
New and revised datasheets for the CHM, DVCHM, Control Heads and Directional Valves are on the Extranet.
The following 2016 price lists have been revised and can be obtained from the extranet:
4
Bulletin #15-50K
We are also in the process of revising the Kidde QuickCalc BOM-Generator Tool such that the Agent Wizard
appropriately selects the CHM and DVCHM for Clean Agent Systems and expect to make this revised tool
available in January 2016.
With over half-million Clean Agent systems in the installed base, this ability to retrofit provides you
a significant revenue opportunity as you help safeguard existing service customers and a new
opening with which to approach previous service customers.
In Summary:
The Kidde Fire Systems Chemical Clean Agent CHM is a stand-alone unit which is:
• Easy to install
• Easy to retrofit (new revenue from existing, ability to approach previous customers)
• Universal in use (can be used on all KFS electric actuated systems)
• True supervision (four wire)
• Extremely robust (explosion proof rating)
The Kidde Fire Systems Clean Agent DVCHM is a stand-alone unit which is:
• Already installed on new units
• Easy to retrofit (new revenue from existing, ability to approach previous customers)
• True supervision (four wire)
• Extremely robust (optional explosion proof rating for chemical clean agents)
As always, we appreciate your business and should you have any questions please contact us at:
1
NPFA 2001-2012 Standard on Clean Agent Fire Extinguishing Systems Sections 4.3.4.1 to 4.3.4.2
2
UL 2166-29 May 2015 Standard for Halocarbon Clean Agent Extinguishing System Units Section 9.6, 9.7, 61.2k, 61.3
3
UL 2127-30 Sept. 2014 Standard for Inert Gas Clean Agent Extinguishing System Units Section 9.6, 9.7, 59.2j, 59.3
4
FM 5600- April 2013 Approval Standard for Clean Agent Extinguishing Systems Section 3.2.14.4
5
NFPA 2001-2012 Standard on Clean Agent Fire Extinguishing Systems Annex A.4.3.4.1