Hussein Farhat - Lab 6

This document summarizes an experiment analyzing an air conditioning unit. Raw data from 4 points was collected measuring temperature, relative humidity, enthalpy, and dew point. Psychrometric charts were created for each point and connecting the process. The expected processes were heating and humidification from 1-2, cooling and dehumidification from 2-3, and heating and humidification from 3-4. However, dehumidification was not observed from 2-3 as the temperature increased instead of decreasing below the dew point.

Uploaded by

husseinfarhatm
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
404 views7 pages

Hussein Farhat - Lab 6

This document summarizes an experiment analyzing an air conditioning unit. Raw data from 4 points was collected measuring temperature, relative humidity, enthalpy, and dew point. Psychrometric charts were created for each point and connecting the process. The expected processes were heating and humidification from 1-2, cooling and dehumidification from 2-3, and heating and humidification from 3-4. However, dehumidification was not observed from 2-3 as the temperature increased instead of decreasing below the dew point.

Uploaded by

husseinfarhatm
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 7

California State University Long Beach

Mechanical Engineering Department


Fall 2020

Hussein Farhat
Run #4

Experiment #6:
Analysis of Air Conditioning Unit
Instructor: Asieh Jalali-Farahani

Course: MAE 337-Thermal Engineering Lab

Section #5
Date of Experiment: November 9, 2020
Date Report Submitted: December 3, 2020

Group #2
Raw Data:

RH SH (X) h V
Tdry Twet TDew
(%) gram moisture/kg (kJ/kg) 3
o o o (m /kg)
( C) ( C) air ( C)

21.9 53.9 15.8 8.9 44.7 NR NR


Point 1

33.5 35.0 21.5 11.5 62.6 15.9 NR


Point 2

16.0 74.1 13.8 8.4 37.4 NR NR


Point 3

18.0 71.5 14.7 9.3 41.3 NR 0.837


Point 4

Psychrometric Chart for Point 1:


Psychrometric Chart for Point 2:

Psychrometric Chart for Point 3:


Psychrometric Chart for Point 4:

Psychrometric Chart for all points in process connecting (to show process):
Note:
Black = Point 1
Blue = Point 2
Green = Point 3
Purple = Point 4

Calculations:
Discussion:
Process 1-2: Heating and humidification process
Process 2-3: Cooling and dehumidification process
Process 3-4: Heating and humidification process

The process 1-2 was expected to be only heating and no adding of moisture and
humidification. As for process 2-3, it was expected to have cooling and dehumidification
since some of the moisture was removed. Finally, in process 3-4, the expected result was
humidification and heating because the air is pushed out towards point 4 so moisture will be
added in.

In terms of relative humidity changing with temperature, as the temperature decreases


the relative humidity is expected to increase, they have an indirectly proportional
relationship.

For the changes of relative humidity in process 1-2, it was expected to see relative
humidity drop because the temperature increased due to the preheating process. For process
2-3 the expected result was to see relative humidity rise, because the temperature decreased
due to the cooling process. Finally, for process 3-4, the expected result was to see relative
humidity drop since the temperature here increased because of the reheating process.

At process 2-3. Dehumidification was not expected because the temperature at point 3
increases when compared to the dewpoint temperature at point 2.