579-1167 Manual Programmer
579-1167 Manual Programmer
Programmer’s
Manual
579-1167
Rev. A
Copyrights, Trademarks, Cautions, Warnings, and Regulatory Info
Cautions READ AND SAVE THESE INSTRUCTIONS- Follow the instructions in this installation manual. These instructions
and must be followed to avoid damage to this product and associated equipment. Product operation and reliability
Warnings depend upon proper installation.
DO NOT INSTALL ANY SIMPLEX® PRODUCT THAT APPEARS DAMAGED- Upon unpacking your Simplex
product, inspect the contents of the carton for shipping damage. If damage is apparent, immediately file a claim
with the carrier and notify an authorized Simplex product supplier.
ELECTRICAL HAZARD - Disconnect electrical field power when making any internal adjustments or repairs. All
repairs should be performed by a representative or authorized agent of your local Simplex product supplier.
EYE SAFETY HAZARD - Under certain fiber optic application conditions, the optical output of this device may
exceed eye safety limits. Do not use magnification (such as a microscope or other focusing equipment) when
viewing the output of this device.
FCC RULES AND REGULATIONS – PART 15 - This equipment has been tested and found to comply with the limits for a Class A
digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful
interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate
radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to
radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the
user will be required to correct the interference at his own expense.
SYSTEM REACCEPTANCE TEST AFTER SOFTWARE CHANGES - To ensure proper system operation, this product must be
tested in accordance with NFPA-72, after any programming operation or change in site-specific software. Reacceptance testing is
required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system
hardware or wiring.
All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that
other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50
devices, must also be tested and proper system operation verified.
IMPORTANT: Verify FACP System Programmer, Executive, and Slave Software compatibility
when installing, or replacing system components. Refer to the Technical Support
Information and Downloads website for compatibility information.
i
Table of Content
Copyrights, Trademarks, Cautions, Warnings, and Regulatory Info............... i
Copyrights and Trademarks............................................................................. i
Chapter 1 Getting Started ...................................................................... 1-1
Introduction .................................................................................................1-1
Requirements and Compatibility .................................................................1-1
Downloading the Software ..........................................................................1-1
Getting Started .................................................................................................1-2
Installing the Software .................................................................................1-2
Starting the Programmer .............................................................................1-2
Chapter 2 User Interface ........................................................................ 2-1
Introduction .................................................................................................2-1
Menus .........................................................................................................2-1
User Interface ...................................................................................................2-2
Toolbar Icons ..............................................................................................2-4
Tabs and Sub-Tabs .....................................................................................2-5
Status bar ....................................................................................................2-5
Chapter 3 Working with Jobs ................................................................ 3-1
Introduction .................................................................................................3-1
Creating Jobs ..............................................................................................3-1
Working with Jobs ...........................................................................................3-2
Opening Existing Jobs ................................................................................3-2
Setting Job Preferences ..............................................................................3-2
Job Notes ....................................................................................................3-3
Saving Jobs .................................................................................................3-3
Building a Job ..............................................................................................3-3
System Requirements .....................................................................................3-4
Archiving a Job ............................................................................................3-4
Backing Up a Job ........................................................................................3-4
Chapter 4 Panel Information and Configuration ................................. 4-1
Introduction .................................................................................................4-1
Notice to users, Installers, Authorities Having Jurisdiction, and other Involved
Parties ..........................................................................................................................4-1
Panel Information ........................................................................................4-1
System Options ...........................................................................................4-2
Panel Information and Configuration ............................................................4-2
User Access Level Configuration ................................................................4-7
Passcode Configuration ..............................................................................4-8
Features Configuration ................................................................................4-8
Chapter 5 Specifying Hardware Components ..................................... 5-1
Introduction .................................................................................................5-1
iii
Table of Content
Hardware Tab Overview .............................................................................5-1
Specifying Hardware Components ................................................................5-2
Adding Hardware ........................................................................................5-2
Adding a Zone/Relay Card ..........................................................................5-3
Adding the Additional IDNet Loops .............................................................5-3
Removing Hardware ...................................................................................5-3
Editing Properties ........................................................................................5-3
Annunciator Numbers .................................................................................5-4
Annunciator Number Sharing Rules ............................................................5-4
Editing Basic Card Properties .....................................................................5-5
Chapter 6 Editing Standard Component Properties ........................... 6-1
Introduction .................................................................................................6-1
Accessing Properties ..................................................................................6-1
Editing the Unit Properties ..........................................................................6-1
Editing the CPU ...........................................................................................6-1
Editing the Color User Interface ..................................................................6-3
Editing the IDNAC Power Supply ................................................................6-4
Editing the IDNET Multiloop ........................................................................6-6
Editing the NAC Power Supply ...................................................................6-8
Editing the Zone/Relay Card .....................................................................6-10
Editing the Serial DACT Card Per Point ....................................................6-12
Editing the Event DACT Card ...................................................................6-14
48-LED Module .........................................................................................6-16
Chapter 7 Editing Standard Component Properties ........................... 7-1
Introduction .................................................................................................7-1
Point Editing for TrueAlert Device .................................................................7-2
TrueAlert ES AO Appliance Point Editing ...................................................7-2
TrueAlert ES VO Appliances Point Editing ..................................................7-3
TrueAlert ES AV Appliance Point Editing ....................................................7-4
ISO Options .................................................................................................7-6
Repeater Options ........................................................................................7-6
DCAI Options ..............................................................................................7-7
TrueAlert STRB Appliances Point Editing ...................................................7-7
TrueAlert Horn Appliance Point Editing .......................................................7-8
TrueAlert AV Appliances Point Editing ........................................................7-9
TrueAlert ASTRB Appliances Point Editing ...............................................7-10
Copy and Pasting Properties ....................................................................7-11
Chapter 8 Viewing, Adding, and Editing Lists ..................................... 8-1
Introduction .................................................................................................8-1
Viewing, Adding, and Editing Lists ................................................................8-2
List Tab .......................................................................................................8-2
iv
Table of Content
Sort Function ...............................................................................................8-2
Custom Label Spell Check ..........................................................................8-2
Managing Points .........................................................................................8-3
Turning Autogen Off and On from the General List Tab .............................8-3
Basic Operations .........................................................................................8-4
Adding a User-Defined List .........................................................................8-4
Editing an Existing User-Defined List ..........................................................8-4
Latching Supv Verification ...........................................................................8-5
WalkTest .....................................................................................................8-6
Elevator Recall List .....................................................................................8-9
Zone Lists ..................................................................................................8-10
Chapter 9 Custom Control .................................................................... 9-1
Introduction .................................................................................................9-1
Custom Control Overview ...........................................................................9-1
Custom Control ...............................................................................................9-2
Role of Lists and Pseudo Points .................................................................9-2
Anatomy of a Custom Control Equation ......................................................9-2
Using a Ladder Logic Diagram to Evaluate an Equation ............................9-3
Custom Control Window .............................................................................9-5
Step 1. Select User Program ......................................................................9-6
Step 2. Add Input Statements .....................................................................9-7
Step 3. Add Output Statements ..................................................................9-8
Floor Above/Floor Below Wizard .................................................................9-8
Step 1. Select Floor Tab .............................................................................9-9
Step 2. General Information ......................................................................9-10
Step 3. Specify Floor Names ....................................................................9-11
Step 4. Specify Input and Static Points. ....................................................9-11
Using the Selective Signaling Wizard .......................................................9-12
Step 1. Select Selective Signaling Wizard Tab .........................................9-12
Step 2. Set General Options .....................................................................9-13
Step 3. Set Zone Names ...........................................................................9-13
Step 4. Link Initiating and Notification Points ............................................9-14
Using the Sounder/Relay Base Wizard .....................................................9-15
Activate Base on Alarm .............................................................................9-15
Alert—Activate Base Prior to Alarm ..........................................................9-17
Chapter 10 File Transfer ...................................................................... 10-1
Introduction ...............................................................................................10-1
USB File Transfer ......................................................................................10-1
IP File Transfer ...............................................................................................10-2
IP File Transfer ..........................................................................................10-2
File Transfer Connection to the PC ...........................................................10-2
Starting the IP File Transfer Utility ............................................................10-2
v
Table of Content
IP File Transfer ...............................................................................................10-3
IP Communication Parameter Settings .....................................................10-3
Downloadable Files ...................................................................................10-3
Download Tab ...........................................................................................10-4
Upload/Reports Tab ..................................................................................10-6
Type of Transfer ........................................................................................10-7
Mass Storage Tab .....................................................................................10-8
History/Undo Tab ......................................................................................10-9
Chapter 11 Port Vectoring ................................................................... 11-1
Introduction ...............................................................................................11-1
Choosing Event Groups to Route .............................................................11-1
Chapter 12 AMON Point Type ............................................................. 12-1
Introduction ...............................................................................................12-1
AMON Pt Type Tab ...................................................................................12-1
AMON Point Type ..........................................................................................12-2
Adding a Point Type ..................................................................................12-2
Editing a Point ...........................................................................................12-4
Deleting a Point .........................................................................................12-4
vi
Chapter 1.
Getting Started
Introduction The 4007ES Panel Programmer is a software program designed to create “jobs” that are used
to configure and program the 4007ES and 4007ES Hybrid Fire Alarm Control Panel (FACP).
The 4007ES Panel Programmer must be installed on a computer that can be either physically
or remotely connected to the panel.
In this chapter Requirements and Compatibility .....1-1 Installing the Software .....................1-2
Downloading the Software ..............1-1 Starting the Programmer ..................1-2
Programmer Requirements:
To install and open the Programmer, the user must have the following:
• Internet access in order to download the software.
1-1
4007ES Panel Programmer Manual (579-1167)
Getting Started
1-2
Chapter 2.
User Interface
Introduction The user interface is made up of menus, icon, tabs, sub-tabs, and a status bar that help the user
navigate through the programmer and create jobs.
The following sections will detail the user interface and the options associated with each item.
Menus
Toolbar
Icons
Tabs
Sub-Tabs
Status Bar
Figure 2-1. 4007ES Programmer Interface
Menus The menus are located at the top of the ES Panel Programmer:
Consult the following tables for the description of the menu items.
Table 2-1. File Menu
Close Closes the current job. Restore Restore the previous saved version of
the job.
Save Saves the current job. Export Allows the user to:
• Export data to service sales tools
Save as Allows you to copy or rename the • Export user points to text file
current job. • Export XLG point data
Reports Generates a digital job report. Import Allow the importation of user points
from another file.
View report Brings up the latest report. DB Compare Compare the job to previous revisions
of itself.
Print set up Configures the hard copy print Current Job The name of the current job.
specifications.
Print Label Prints labels for the FACP cards. Exit Exits the current job.
2-1
4007ES Panel Programmer Manual (579-1167)
User Interface
Paste Inserts the previously cut or copied material into the selected area.
*Tab List* Click on the option to open the corresponding tab. The choices are:
• Panel
• Hardware
• Point
• List
• Custom Control
• TrueAlert Zone
• Port Vectoring
• AMON Pt Type
• Zone Lists
Checklist Displays a mandatory and an optional checklist that lets the user know which steps
have been completed in the programming process.
Toolbar Click in the checkbox to make the tool bar icons visible.
Status Bar Click in the checkbox to make the status bar visible.
Notes Click to open a note pad where the user can type in notes on the job.
View Build Log Click to view the log of previous builds for this job.
2-2
4007ES Panel Programmer Manual (579-1167)
USB Transfer the job data from the computer to the USB key
Serial Click to enable a connection between the computer and the FACP through the
computer’s serial port.
Network Click to enable a network connection between the computer and the panel
About Programmer Click to access basic information, copyrights of the programmer software, and the
revision of the programmer being used.
2-3
4007ES Panel Programmer Manual (579-1167)
Toolbar Icons The toolbar icons are shortcuts to popular programmer commands.
Table 2-9 explains each icon and the command it is attached to.
Table 2-9 Icons and Commands
Copy Click to copy the selected information and delete it from its current location.
About Click to access basic information and copyrights of the programmer software.
2-4
4007ES Panel Programmer Manual (579-1167)
Tabs and Sub- Each tab represents a specific component or feature of the job that must be configured. The
Tabs tabs are placed in sequential order and should be completed in that order. Certain tabs are made
up of multiple sub-tabs that are found at the bottom of the page. All sub-tabs must be opened
and configured to complete the job.
Table 2-10. Tab list
Panel • General Info Enter the general panel and branch information.
• Access Levels View the default user levels for specific tasks. Right
click on the user level to view and edit its properties.
Point -NA- Display the list of all the points in the FACP.
Double click on any of the points to view and edit
their properties.
• Alarm Verification View and edit the items on Alarm Verification list.
• Elevator Recall View and edit the items on the Elevator Recall list.
• Floor Above/Floor Control the areas in which the NACs are activated.
Below Wizard
AMON Point Type -NA- View the analog monitor (AMON) points.
Status bar The Status bar is found at the bottom of the Programmer window and indicates the:
• Programmer status
• Time
2-5
Chapter 3.
Working with Jobs
Introduction A job is a file that contains specific programming and configuration information for the FACP.
This chapter explains the basics surrounding creating and saving jobs, however, it is important
to consult the following chapter in this document, Panel Information and Configuration, for
crucial information on how to configure and program the job.
Creating Jobs When the programmer is opened on a computer for the first time, a prompt window will
appear automatically requesting that the user create a job. If a job has been previously saved
on the programmer it will automatically open when the programmer is started.
To create a new job:
1. Start the ES Panel Programmer:
• If this is the first job saved for the FACP, the New Job window will open automatically.
• If a previous job opens, click on the New icon or select New from the File menu to
open the New Job window.
2. In the New Job window, select the job type: 4007, Small Panel.
3. Enter the job number. The job name should be 8 characters long and start with a number.
• Year. This is a two-digit field. Use the last two digits of the current year to indicate the year
in which the job was programmed.
• Month. This is a single character field. Use the numbers and letters shown in the example
below to indicate the month in which the job was programmed. See Table 3-1.
• File Type. This field is a single letter, used to indicate the panel type. There is currently
only a single supported type.
• Number. This is a three-digit field used to track how many of a specific job type have been
programmed during the month. For example, if the File type is 4100ES, enter the number
of 4100ES jobs programmed during the month.
• Job Version. When archiving a job, you can use letters to differentiate the jobs once they
have been archived. For example, once job 103E123A is archived, new edits should be
saved to 103E123B.
3-1
4007ES Panel Programmer Manual (579-1167)
4. Select the path to the file in which the job will be stored.
Note: It is preferable that the default folder C:\4100UJOBS be used for job storage.
3-2
4007ES Panel Programmer Manual (579-1167)
Saving Jobs There are two saving options in the programmer, Save and Save As. The Save option is used to
save the job in progress, the Save As option is used to save the job with a new name.
To save a job with Save:
• Click on the Save icon.
• Open the Edit menu and click on the Save option.
Note: When you click on the save option, the programmer overwrites the previous information and there is
no way to backtrack to the previous job.
To save a job with Save As:
1. Open the Edit menu and click on the Save As option.
2. Select either the Copy option or the Rename option:
• Copy: This option saves a copy of the currently open job under a new name in a new
directory. This option allows you to open and reuse the previous version.
• Rename: This option saves the job under a new name and deletes the content of the
previous job folder. For example, if a user renames job 333 as job 444, a new job
folder named 444 will appear and the job folder 333 will be empty.
Note: Conventionally, performing a Save As > Copy will be the first action a technician will take when
opening an existing job to create a new revision. This way if complications arise, the technician can
always return to the previously saved revision.
Building a Job A job needs to be “built” before it can be downloaded. This process transforms the .SDB file
into a CFIG file that is compatible with the FACP.
Note: All configuration options and panel information must be complete before building the job. Any errors
detected during the build will abort the process.
To build a job:
1. Open the job.
2. Start the build by either clicking on the Build icon or by selecting the Build item from the
Build menu.
3. The Revision History window appears and the user must enter:
• Their name.
• A brief description of the edits that were made to the current revision.
Once the information has been entered click on OK.
4. The Job Builder window then appears and displays all the elements in the job and their build
status. Once the compilation is complete, the final dialogue in the window will read either:
• Build Complete: This means the build has been successful and the job is ready to be
downloaded to the FACP.
• Build Aborted: This means that errors were found while the job was being built and
that the job build was aborted. The errors that caused the job to abort are listed in the
Job Builder window.
3-3
4007ES Panel Programmer Manual (579-1167)
System Requirements
Archiving a Job Once a job is archived, it is saved as a read-only .SDA4100U file that can no longer be opened
for editing.
To archive a job:
1. Save the job.
2. Open the Edit menu and click on the Archive menu item.
3. The Programmer Archive Utility window opens and requests that the user name the file and
select the directory to which the file will be saved.
4. Click on Archive. A progress meter appears, showing the progress of the operation. When
this bar disappears, the archive operation is complete. The archived file is saved as
.SDA4100U.
To open an archived file:
1. Open the File menu and click on the Restore menu item.
2. The Programmer Restore Utility window opens. Use the Look In search box to locate the
archived file.
3. Once the file is located, click on it so that its name appears in the File Name box.
4. Click on Continue.
5. The Browse for Folder window appears and requires that the user select the directory and
file to which the file will be restored. It is recommended to use the 4100UJOB Folder.
6. If a file with that name already exists, the user will be prompted to:
• Overwrite the existing file
• Rename the file
• Cancel the operation: This will result in an error file and the programmer will return to
the last saved job.
7. The archived file will then open as a read-only job. To save the job as different version in
the 4100U folder, the user must use the Save As function.
Backing Up a Job Backing up a job creates a compressed version of the job and stores it as a read/writable
.SDC4100U file on either a removable storage medium or a remote disk.
To back up a job:
1. Open the File menu and select the Backup menu item.
2. The Programmer Backup Utility window opens and requests that the user name the file and
select the directory to which the file will be saved.
3. Click on Backup. A progress meter appears, showing the progress of the operation. When
this bar disappears, the backup is complete.
To restore a Backup file:
1. Open the File menu and click on the Restore menu item.
2. The Programmer Restore Utility window opens. Use the Look In search box to locate the
backup file.
3. Once the file is located, click on it so that its name appears in the File Name box.
4. Click on Continue.
5. The Browse for Folder window appears and requires that the user select the directory and
file to which the file will be restored.
6. If a file with that name already exists, the user will be prompted to:
• Overwrite the existing file
• Rename the file
• Cancel the operation
7. The backup file will then open as normal job.
3-4
Chapter 4.
Panel Information and Configuration
Introduction This section focuses on items found in the Panel tab. Information in this section must be
completed and the options must be configured before the job is successfully built.
Notice to users, This product incorporates field programmable software. In order for the product to comply
Installers, with the Standard for Control Units and Accessories for Fire alarm systems, UL864, certain
Authorities programming features or options must be limited to specific values or not used at all as
Having indicated in Table 4-1.
Jurisdiction, and Table 4-1. Programming Features and Options
other Involved
Program Feature Permitted in Settings Permitted
Parties Possible Settings
or Option UL864? (Y/N) by UL
Editing group ON until completion
properties DC group tab Yes ON until RESET
ON until SILENCE ON until completion
3.1
Editing Custom Control
2.6
equations that change 3.1
2.2
sensitivity levels (set Alarm Yes 2.6
1.8
Thresholds) for ISN- 550 2.2
1.4
Photo smoke detectors
1.0
LVSUPV - Latching Verified
No
Supervisory Smoke Detector
LVSDUCT - Latching
Verified Supervisory Duct No
Smoke Detector
MACOFIRE - Carbon
COFIRE, COPRI2 COSUPV
Monoxide Fire Yes
COSUPV, UTILITY UTILITY
Algorithm
Panel Information Panel information provides identification reference for the technicians who created the jobs.
To enter the panel information:
1. Click on the Panel tab and select the General Information sub-tab.
2. Fill out the information requested on the page:
• Panel Information: This section requests information about the panel itself.
• Branch Information: This section requests information on the branch of the company
and other useful information.
• Programmed by: This section requests information on the people who programmed
the FACP.
• Hardware Edit Lock: When this option is checked, the user cannot add or remove any
hardware.
• Comment: Enter any comments about this specific FACP.
4-1
579-1167
System Options ES Panel System Options are global attributes that allow the user to configure specific
application options as well as configure certain elements of the panel's display.
To access the System Options screen:
1. Click on the Panel tab and select the System Options sub-tab.
2. Configure the options that appear on the page. The following tables list and define the
different options.
Table 4-2. General System Options
Description
Option
(“dflt” indicates the default setting)
Date Format • Select MM-DD-YY dflt for the panel to display the date by month, day, and
year (example: January 4th 2013 = 01-04-13).
• Select DD-MM-YY for the panel to display the date by day, month, and year
(example: January 4th 2001 = 04-01-13).
Time Format • Select 12 Hour dflt for the panel to display the time as “a.m.” and “p.m.”
(example: 6:00 a.m., 6:00 p.m.)
• Select 24 Hour for the panel to display the time on a 24h clock (example:
6:00, 18h00.)
Unit Format • Select Fahrenheit dflt for the panel to display Imperial units.
(example: 96 oF, 6 ft)
• Select Centigrade for the panel to display Metric units.
(example: 36 oC, 1.83 m)
Acknowledge • Select Global acknowledgedfl to allow every point reporting the same alarm
Option state (alarm, trouble, priority 2, or supervisory condition) to be
acknowledged at once by pressing the according Acknowledge button.
(Example: If 5 Trouble conditions are present on the system and global
acknowledge is enabled, one press of the Trouble Ack button
acknowledges all five Troubles at the same time.)
• Select Individual Acknowledge to ensure that each point reporting an
alarm state must be acknowledged individually. (example: If five Trouble
conditions are present, you will have to acknowledge each one individually.)
Service Select Service Reset to allow an operator to reset the system even though
Reset the device causing the alarm has not restored to normal.
The typical application for this would be when a malfunctioning initiating
device (detector or sensor consisting of a base and removable head) causes
an alarm, but will not reset even though the off-normal condition is no longer
present. With this option enabled, the head can be removed and the system
(including the local energy masterbox, if provided) can be reset. Without this
option enabled, removing the head will cause the system to abort the reset
because it will not have seen the alarmed point/zone having restored to a
normal state, and it will not be possible to reset the local energy masterbox.
The default setting for this option is disabled.
4-2
579-1167
Description
Option
(“dflt” indicates the default setting)
Combined If checked, pressing the Reset button performs an alarm reset followed by a
Alarm and hardware reset. If this option is not selected, an alarm reset is performed if
Hardware there are fire alarms or supervisories in the system. Otherwise, a hardware
Reset reset is performed.
Display First When this option is selected, the display alternates between the summary
Alarm screen (with the number of active alarms, troubles, etc.) and the screen
showing detailed information on the first alarm received by the system.
If this option is not selected, the screen indicating the number of alarm
conditions on the system is displayed.
Language of The pull down list contains two options, Primary and Alternate. Use Alternate
Use only when you download an alternate msglib file, containing alternate
language text, to the panel. If no alternate msglib file is downloaded, you must
use the English option.
Non Steady When enabled, this option allows you to select the type of operation for Non
Audible Evac Steady Audible Evacuation Signals. The term Non Steady Audible Evacuation
Signal refers to any Notification Appliance capable of sounding a coded
signal. The default setting for this option is not enabled. Choices are:
• California Code 1. A coding pattern consisting of 12 beats within a
10 seconds span of time, followed by a 2 and ½ second pause. This
sequence repeats four times (four rounds) and then terminates (i.e., the total
coding pattern lasts approximately one minute).
• California Code 3. Same coding pattern as California Code 1, however the
sequence repeats 12 times (12 rounds) and then terminates (i.e., the total
coding pattern lasts approximately three minutes).
• Fast March Time. A coded signal that uses 120 beats per minute. Each
beat consists of ¼ second pulse on, ¼ second off. Pattern repeats until
alarm silence.
• March Time. A coded signal that uses 60 beats per minute. Each beat
consists of ½ second pulse on, ½ second off. Pattern repeats until alarm
silence.
• Slow March Time. A coded signal that uses 20 beats per minute. Each beat
consists of 1.5 second pulse on, 1.5 second off. Pattern repeats until alarm
silence.
• Temporal 4. A CO gas warning that is a repeated sequence of four
cycles of 100 msec on with 100 msec off, followed by 5 seconds off.
• Temporal. A three-pulse coding pattern consisting of three ½ second
pulses, each separated by a ½ second silence. Each three pulse group is
separated by 1 ½ seconds of silence. Pattern repeats until alarm silence.
• On Steady.
Note: If the coding pattern selected here is not supported by the notification appliance,
it will be replaced by a default one.
4-3
579-1167
Description
Option
(“dflt” indicates the default setting)
Non Steady When enabled, this option allows you to select the flash pattern output by Non
Visual Evac Steady Visual Signals. The term Non Steady Visual Signal refers to any Visual
Notification Appliance capable of emitting a pattern of flashes (such as
incandescent visuals). The default setting for this option is not enabled.
Choices are:
• March Time. A coded signal that uses 120 beats per minute. Each beat
consists of ¼ second pulse on, ¼ second off.
• Slow March Time. A coded signal that uses 20 beats per minute. Each beat
consists of 1.5 second pulse on, 1.5 second off.
• Temporal. A three-pulse coding pattern consisting of three ½ second
pulses, each separated by a ½ second silence. Each three pulse group is
separated by 1 ½ seconds of silence.
Note: This option cannot be used for public mode signaling as defined in Section 4-4 of
NFPA 72-99.
Alarm Cutout This option allows you to set a duration (up to 60 minutes) that specifies how
Timer long signals sound following an alarm. For example, with this option set at
2 minutes, building signals sound for two minutes and then automatically stop.
After the signals stop, the alarm condition remains active at the panel.
If Alarm Silence/Reset Inhibit option is active, it takes precedence over this
option. See description of Alarm Silence/Reset Inhibit below for more
information
The range for this option is 60-3600 seconds. The default setting for this
option is not enabled. Set the point type for visual NACS to SVISUAL to have
them turn off at the same time as the audible signals.
This option disables the Alarm Silence and System Reset buttons for a user-
definable duration that ranges from 1 to 60 minutes. The timer is activated
only by the first alarm (i.e., subsequent alarms do not reset the timer).
Alarm If this option and the Alarm Cutout Timer are both enabled, this option takes
Silence/ precedence. For example, if the Alarm Cutout Timer is set to one minute and
Reset Inhibit this option is set to 2 minutes, signals continue to sound after one minute.
The default setting is not enabled.
Note: This option must be enabled for Canadian jobs.
AC Failure Specifies the time delay (HH:MM) in reporting an AC failure trouble to the city
Delay circuit (if AC fail is the only trouble) or Central Station if an SDACT is installed.
The time and date that appeared on the panel before the CFIG DOWNLOAD
Auto Set
are automatically set after download is complete. This option will not work if
Panel Time
the time/date was not set prior to the download (i.e. system time/date invalid
and Date
trouble at the panel).
4-4
579-1167
System Options
Table 4-3. Active Status Reminder System Options
Option Description
Fire The Fire Reminder option programs the system to periodically sound the
Reminder piezo if an uncleared Alarm condition exists at the panel, thereby reminding
system operators about the uncleared condition.
By default, this option is enabled and the Resound Time is set to 8:00.
To modify the Active Status Reminder settings, do the following:
1. Make sure the box labeled Enabled is checked.
2. Set the interval at which the piezo should sound. The range is from 0 to
18 hours. The default is 8 hours.
Pri2 The Pri2 Reminder option programs the system to periodically sound the
Reminder piezo if an uncleared Priority 2 Alarm (security) condition exists at the panel,
thereby reminding system operators about the uncleared condition.
By default, this option is enabled and the Resound Time is set to 8:00.
To modify the Active Status Reminder settings, do the following:
1. Make sure the box labeled Enabled is checked.
2. Set the interval at which the piezo should sound. The range is from 0 to
18 hours. The default is 8 hours.
Supv. The Supv Reminder option programs the system to periodically sound the
Reminder piezo if an uncleared supervisory condition exists at the panel, thereby
reminding system operators about the uncleared condition.
By default, this option is enabled and the Resound Time is set to 8:00.
To modify the Active Status Reminder settings, do the following:
1. Make sure the box labeled Enabled is checked.
2. Set the interval at which the piezo should sound. The range is from 0 to
18 hours. The default is 8 hours.
Trbl. The Trbl Reminder option programs the system to periodically sound the piezo
Reminder if an uncleared trouble condition exists at the panel, thereby reminding system
operators about the uncleared condition.
By default, this option is enabled and the Resound Time is set to 8:00.
To modify the Active Status Reminder settings, do the following:
1. Make sure the box labeled Enabled is checked.
2. Set the interval at which the piezo should sound. The range is from 0 to
18 hours. The default is 8 hours.
Local If there is a per point serial DACT in the system, this setting specifies whether
Annunciation the piezo on the local panel will sound. This option is useful in situations
where the panel is located in a public area (such as a lobby) and the occupant
does not want the piezo repeatedly sounding.
4-5
579-1167
General Description: These options will stop a recurring trouble event from continuously
dialing the central station or from generating SafeLINC email events if the programmed criteria
are met (number of occurrences of that point in the trouble log within the specified elapsed
time frame).
Option Description
Occurrences Number of times the point is found in the trouble log (0=no filtering; default for
pre-existing jobs upgraded to 12.06). Value is selectable from 0 and 2 to 10.
By default, it is set to 3.
Elapsed Time Number of minutes in which the troubles must be found. Value is selectable
from 1 to 1440 minutes. By default, it is set to 60.
General Description: This option allows TrueAlert ES appliances that can be configured
identically or independently through the ES Programmer software.
To use the System Options to configure TrueAlert ES appliances:
• The appliance's jumpers and configuration switches must be set to the correct setting. For
example, if a specific candela value is selected in the system options, the device should be
set to FACP. On the other hand, if system option is set to “Hardware”, the candela flag at the
device should be set to any other position than FACP.
• The appliance's candela and coding type in the power supply's Point Editing tab in the
programmer must be set to "System Default".
When a specific candela value is selected, that value will be applied to all compatible
appliances that have their configuration switches set to FACP*.
When Hardware Specified is selected, it is the appliance's locally configured candela value that
will be used.
*Note: When a specific candela value is selected, a warning window will appear to notify the user that in
the event that an appliance cannot be set to the selected Preferred Default System Option, a
compatible default value will be assigned to the device by the programmer.
For example: If the System Option is set to 20 cd and there is a UL Weatherproof device (that has
no 20 cd setting), the Programmer will assign a value of WP75 cd to the UL weatherproof device.
4-6
579-1167
System Options Table 4-5. Addressable Appliances Preferred Default System Options (Continued)
Value for
Assigned Candela Value for Indoor Value for Weatherproof,
Weatherproof,
Value Appliances UL
ULC
15 cd 15 cd 15 cd 20 cd
20 cd 30 cd WP75 cd 20 cd
30 cd 30 cd WP75 cd 30 cd
75 cd 75 cd 75 cd 75 cd
WP75 cd 75 cd WP75 cd 75 cd
User Access Level User access levels can be configured on the programmer for display functions to determine
Configuration their access level.
Each access level automatically has access to the level below it. For example, if a technician is
authorized for level 1, he will only be able to access functions that are tagged as level 1. A
technician with a level 3 authorization level however, will have access to functions tagged as
levels 1, 2 and 3.
Note: Passcodes can be attributed to user levels 2, 3, and 4 to restrict the access to certain functions. For
more information consult the Passcode Configuration section.
To associate user levels with a display function:
1. Click on the Panel tab and select the Access Levels sub-tab.
2. Double-click on the table entry to open its Object Properties window.
3. Select one of four user levels for the display function. Basic display functions, such as
System Reset and Change Time and Date, are usually assigned to user level 1. More
sensitive display functions, such as Remote Download, are typically assigned to user level 2,
3, or 4.
4. Click on OK to confirm the selection.
4-7
579-1167
Passcode Numeric passcodes can be created to grant specific access level to up to 20 different operators.
Configuration Each access level automatically has access to the level below it. For example, if a technician is
authorized for level 1, he will only be able to access functions that are tagged as level 1. A
technician with a level 3 authorization level however, will have access to functions tagged as
levels 1, 2, and 3.
To create a passcode:
1. Click on the Panel tab and select the Passcode Assignments sub-tab.
2. Double-click on a table entry to open Object Properties window.
3. Enter a passcode, composed of up to ten numbers.
4. Assign the access level to the passcode.
5. Click on OK to confirm the selection.
Features The Features sub-tab provides information on the functionalities of the ES Panel Programmer
Configuration which can be used with the software key currently plugged into the Programmer PC.
To configure the functionalities:
1. Click on the Panel tab and select the Features sub-tab.The usable features are listed in the
Programmer/Runtime Features window.
2. To enable the options under Programmer and Runtime on the left panel, enter the software
key provided by an authorized Simplex representative with the appropriate access codes.
3. Click on Update Access Codes to complete the action.
Note: This sub-tab also prompts the user to enter the CPU Number. To get the CPU number, from the
panel, press on Menu > System info > Panel Serial Number. Enter the number in the designated box.
4-8
Chapter 5.
Specifying Hardware Components
Introduction The hardware components that are part of the FACP must be entered into the programmer so
that the user can configure their properties according to the job requirements.
This chapter explains how to add and remove the hardware elements that are entered into the
programmer.
Hardware Tab The Hardware Tab Window uses a drag and drop interface, consisting of a palette of available
Overview icons on the right hand side of the screen and a work area on the left hand side of the screen.
There are two available views:
• Tree View: This view displays the hardware in a branch structure. The hardware
appears linked to the bay into which it is installed.
• Grid View: This view displays the hardware in a grid structure and groups the
hardware by type. This view also features search and sorting options for elements
already added to the FACP.
5-1
Chapter 5 Specifying Hardware Components
Icon Meaning
Panel Icon This is a non-editable icon that permanently resides in the top left corner of the
work area. The panel icon represents all of the non-networked, RUI-linked
components controlled by a single CPU. A single panel may, for example,
actually be multiple boxes, some residing at one location and some at another
location.
Highlighting this icon and hitting Shift-Right Arrow at the same time expands
the entire hardware tree.
Unit Icon The unit icon does not actually represent equipment. It corresponds to a
location at which the box resides.
Click on the + sign to expand the contents of a unit and see the box.
Box Icon The box icon typically represents a standard bay box. There is also an option
that represents a custom box.
Click on the + sign to expand the contents of the box.
Logical Card Logical cards are not hardware; instead they represent all of the analog pseudo
Icon points, digital pseudo points, or lists used on the system.
Double-click on the card to access its properties.
Physical Physical cards are actual hardware, including: monitor, signal, relay,
Card Icon annunciator, display, interface, audio, and power cards.
Double-click on the card to access its properties.
Slot Card This icon represents a legacy-style card that extends perpendicular from the
Icon back plane in the panel called <slots>. These cards mount into a card edge
connector.
Double-click on the card to access its properties.
LED Module This icon represents the fixed-48 LED Module. The module is installed directly
Icon in a recess of the dress panel.
Double-click on the card to access its properties.
Adding Hardware There are two ways to add a hardware component to the programmer:
• Drag and drop
• Right-click + add
To add a hardware component to the programmer using drag and drop:
1. Locate the hardware component that you want to add from the Available Hardware window
on the right of the programmer screen.
2. Click on the hardware and drag it into the Hardware Configuration window on the left of the
programmer screen, into the proper directory:
• Units must be placed in panel icons.
• Boxes must be placed in units
• Cards must be placed in boxes.
3. When the component is in the proper place, release the mouse. If the component was
successfully added, it will appear in the Hardware Configuration menu. If the component
cannot be added to the configuration, an error message will appear with the problem
diagnosis.
5-2
Chapter 5 Specifying Hardware Components
Adding Hardware To add a hardware component to the programmer using click + add:
1. Right-click in the Hardware component window. An action list appears.
2. Select the type of hardware you want to add to the programmer from the action list:
• Add Unit: The Unit Properties box automatically opens.
• Add Box: The Add Box window opens and displays the available boxes.
• Add Card: The Add Card window opens. Use the drop-down menus to select the card
you want to add. If the card cannot be added to the configuration, an error message will
appear with the problem diagnosis.
To add multiple boxes or cards at one time, use the right-click method. Specify the number of
boxes/cards to add in the Quantity field.
Adding the To add a the addition loops in the IDNet expansion loop card:
Additional IDNet 1. In the Hardware Configuration window, double-click on IDNAC power supply, then click on
Loops IDNet+ Multiloop.
2. Click on the Loop Editing tab.
3. Select the first unused card 2: loop B isolator.
4. Change the device type to Isolator/Expanded point capacity.
5. Repeat steps 3 and 4 with the second unused card 2: loop C isolator.
5-3
Chapter 5 Specifying Hardware Components
Annunciator Every card in a 4007ES Panel job must have an associated annunciator number, whether it is an
Numbers annunciator or not. Annunciator numbers are assigned in the following manner. When a new
unit is added to a job, the unit is assigned the next available annunciator number.
When the first annunciator card is added to such a unit, it also assumes the unit's annunciator
number.
As additional annunciators are added to the unit, there are several cases where the annunciators
will share their annunciator numbers. Any additional annunciator cards of the same type added
to the same unit also share this number.
When an additional annunciator card of a different type is added to the unit, that annunciator
card is given an annunciator number distinct from the number assigned to the earlier
annunciator type.
A card’s annunciator number is important for a correct LED Switch operation. For example, a
lamp test switch will only light lamps/LED on cards with the same annunciator number.
Exception to the rules above:
• Internal and external LCD Annunciators require their own annunciator number and
will not share numbers even with their own kind.
5-4
Chapter 5 Specifying Hardware Components
Editing Basic All cards, regardless of whether they are the standard system cards (such as the system power
Card Properties supply) or an option card - include the basic properties. The basic card properties are listed
below.
• Card Address. A unique number used to identify the card within the system. This
number must correspond to the card address dip switch settings on the card.
- Address 001 IDNAC/NAC power supply
- Address 002 IDNet and multiloop
- Address 003 Color user interface
Note: It is usually easier to first add the card to the job with the programmer and then set the dip switches
with the address automatically assigned by the programmer.
• Card Custom Label. This field describes the card's function, location, or some other
descriptive text.
• Card Alternate Custom Label. This label will be displayed when the alternate
language is displayed.
• Unit, Box, Bay, and Slot (location). The values shown in the fields reflect the location
in which the card icon was placed when you added it with the programmer. It is
possible to change these values; however, the new values must reflect the new physical
location of the card.
To gain access to the Card Properties dialog, do either of the following:
• Double-click on any card icon in the work area.
• Right-click on any card in the work area. When the list of choices appears, click on
Properties.
A window similar to Figure 5-2 appears.
Figure 5-2. Card Properties Window - Color User Interface shown as example
5-5
Chapter 6.
Editing Standard Component Properties
Introduction 4007ES panels come equipped with a standard set of hardware components. This chapter
details the programming for those cards.
In this chapter Accessing Properties..............................6-1 Editing the Unit Properties ................... 6-1
Editing the CPU.....................................6-1 Editing the Color User Interface........... 6-3
Editing the IDNAC Power Supply ........6-4 Editing the IDNET Multiloop............... 6-6
Editing the NAC Power Supply.............6-8 Editing the Zone/Relay Card .............. 6-10
Editing the Serial DACT Card Per Point6-12 Editing the Event DACT Card............ 6-14
48-LED Module...................................6-16
Accessing b
Properties 1. Open the Hardware tab.
2. Select the hardware component from the Hardware Configuration window and double-click
on it to open the editing window.
Editing the Unit Each 4007ES panel set-up automatically requires a unit in the programmer.
Properties To edit the unit:
The Unit Window requests that the user enters the following information:
• Description: Enter a description that identifies the particular FACP.
• AC Breaker Location: Enter the location of the breaker that powers the unit’s power
supply.
Editing the CPU The 4007 CPU window has three main tabs to edit. The Card Properties tab, the Service Port
tab, and the Ethernet tab.
To edit the Card Properties tab (Figure 6-1):
Enter the card’s custom label. This label should make the card easily identifiable.
The following fields in the tab are filled by the programmer and cannot be edited:
• Card address
• Card description
• Card default label
• Annunciator address
• Unit number
• Box number
• Bay number
• Location
To edit the Service Port tab:
1. Configure the communication settings by selecting the Baud Rate, Parity, Data Bits, and
Stop Bits fields to the values required by the attached device. It is recommended that you
use the following default settings whenever possible.
• Baud Rate: 115,200
• Data Bits: 8
• Stop Bits: 1
• Parity: None
2. Click on the Port Data button. The RS323 Port Data Entry window opens (Figure 6-1).
Continued on next page
6-1
4007ES Panel Programmer Manual (579-1167)
Editing the CPU 3. Click the Gen. Info tab. Enter the
information requested. Click on
Apply and then OK to confirm the
selection (Figure 6-1).
• Device Type: For a CPU card
service port, this field is
permanently set to
COMMAND.
• Header Label: This field
specifies the first line of banner
text that appears at the top of the
CRT screen.
• Port ID Label: This field
specifies the second line of
banner text that appears at the
top of the CRT screen. It is
typically used to designate the
port connection. For example,
“Port 2, Command Center.”
Figure 6-1 4007 CPU - Gen Info Tab
• Port Default SET Priority CPU Card Only: This is the system priority level assigned to
commands issued from the service port. The range is 2 to 15 and the default is 9.
4. Click on the Access Level tab
in the RS232 Port Data Entry
window (Figure 6-2). This tab
allows you to set the access
level for the various system
operations that can be carried
out via the service port.To set
an access level for one of the
service port operations, scroll
through the list of functions
and highlight the function. Use
this control to associate an
access level with the function.
Click on Apply and then OK
to confirm the selection.
Figure 6-2. 4007 CPU Access Levels and Port Options
Note: These access levels apply only to actions performed through the service port, not for operations
made at the panel display.
5. Click on the Port Options tab in the RS232 Port Data Entry window. This tab contains
options that apply to the way data appears on the display connected to the service port.
These are read-only fields. Click OK to return to the Service Port tab.
6. Click in the TrueInsight Remote Service Gateway box to enable the use of the Remote
Service Gateway.
6-2
4007ES Panel Programmer Manual (579-1167)
6-3
4007ES Panel Programmer Manual (579-1167)
Editing the Color To edit the Display Options tab (Figure 6-4): If
User Interface needed, check the Reverse Display of custom label and
status line. To use custom external files for the primary
and/or the alternate MsgLib:
1. Click on Import.
2. Browse to import the appropriate MsgLib.
3. Click on Open.
4. Edit the Name and Date fields.
By default, the System is Normal image is displayed. To
edit this image:
1. Check the Enable Custom Image check box.
2. Click on Import Image...
3. Browse to select the appropriate image.
4. Click on Open > Apply.
Figure 6-4. Color User Interface - Display Options
To edit the Access Levels tab:
Editing the IDNAC The IDNAC Power Supply is part of the 4007ES Hardware Configuration. It has five main tabs
Power Supply to edit. The Card Properties tab, the Data Entry tab, the AuxNAC tab, the Aux Relay tab, and
the Point Editing tab. For more information on the 4007ES Hybrid power supply, refer to the
Editing the NAC Power Supply section.
To edit the Card Properties tab:
1. Enter the card’s custom label. This label should make the card easily identifiable.
The following fields in the tab are filled by the programmer and cannot be edited:
• Card address
• Card description
• Card default label
• Annunciator address
• Unit number
• Box number
• Bay number
• Location
6-4
4007ES Panel Programmer Manual (579-1167)
Editing the IDNAC To edit the Data Entry tab (Figure 6-6):
Power Supply 1. Configure the Depleted Battery Cutout
option. If selected, the power supply card
will shut itself off after detecting a
depleted battery condition when no AC
power is present. If this option is selected,
a jumper must be installed on the power
supply (on S527), for Canadian operation.
It is unselected by default.
2. Select the optional cards that are
connected to the power supply card. The
choices are:
• None
• City Connect; OR
• Relay
Figure 6-6. IDNAC - Data Entry Tab
3. Click in the 25V Regulator box if a 25V regulator card, 4007-9802, will be used with the
FACP.
4. Click OK to confirm the selection.
6-5
4007ES Panel Programmer Manual (579-1167)
Editing the IDNET The IDNet Multiloop can contain up to 250 points. The card has three main tabs to edit. The
Multiloop Card Properties tab, the Point Editing tab, and the Loop Editing tab.
To edit the Card Properties tab:
1. Enter the card’s custom label. This label should make the card easily identifiable.
2. Click in the box beside the following functions to activate them:
• Only activate TrueAlarm device LEDs
• Activate Signal IAM LEDs
The following fields in the tab are filled by the programmer and cannot be edited:
• Card address
• Card description
• Card default label
• Annunciator address
• Unit number
• Box number
• Bay number
• Location
• Total of configured points
• Total of available points
6-6
4007ES Panel Programmer Manual (579-1167)
6-7
4007ES Panel Programmer Manual (579-1167)
Editing the NAC The NAC Power Supply is part of the 4007ES Hybrid Hardware Configuration. The card has
Power Supply four main tabs to edit. The Card Properties tab, the Data Entry tab, the Nacs tab, and the
AuxNAC tab.
To edit the Card Properties tab:
1. Enter the card’s custom label. This label should make the card easily identifiable.
The following fields in the tab are filled by the programmer and cannot be edited:
• Card address
• Card description
• Card default label
• Annunciator address
• Unit number
• Box number
• Bay number
• Location
To edit the Data Entry tab (Figure 6-13):
1. Configure the Depleted Battery Cutout option. If selected, the power supply card will shut
itself off after detecting a depleted battery condition when no AC power is present. If this
option is selected, a jumper must be installed on the power supply (on S527), for Canadian
operation. It is unselected by default.
2. Select the optional cards that are connected to the power supply card. The choices are:
• None
• City Connect
• Relay
3. Select the NAC options for the wiring. The choices are:
• 4 Class B
• 4 Class A
4. Click in the Wheelock Devices (Code 3) box if a Wheelock device will be used with the
FACP.
5. Click in the 25V Regulator box if a 25V regulator card will be used with the FACP.
6. Click Apply > OK to confirm the edits.
.
6-8
4007ES Panel Programmer Manual (579-1167)
6-9
4007ES Panel Programmer Manual (579-1167)
• MONB Class B
Monitoring Device
• Relay device
2. Select the point type.
3. Enter the card’s custom
label. This label should
make the card easily
identifiable.
4. Select the EOL resistance
from the EOL Resistance
drop-down list.
5. Click Apply > OK to
confirm the edits.
6-10
4007ES Panel Programmer Manual (579-1167)
6-11
4007ES Panel Programmer Manual (579-1167)
Editing the Serial The 4007-9806 serial DACT interface card can be programmed per point or by event.
DACT Card Per The 4007-9806 serial DACT per point has six main tabs to edit. The Card Properties tab, the
Point Basics tab, the Event Codes tab, the Local Points tab, the Point Types tab, and the Points tab.
To edit the Card Properties tab per point:
1. The panel assigns an address when a DACT card is added. Set the card address to math the
programmer assigned address.
2. Enter the card’s custom label. This label should make the card easily identifiable.
3. Select a card address, from 0 to 31.
The following fields in the tab are filled by the programmer and cannot be edited:
• Card description
• Card default label
• Annunciator address
• Box number
• Bay number
• Location
To edit the Basics tab (Figure 6-18):
The Basics tab can be used to set up the basic communication information of the DACT to
DACR link. The following fields in the tab can be edited:
• Phone and Account Numbers
- Primary (1)#:
- Secondary (2)#:
- Account (1)#:
- Account (2)#:
• Central Station Line #
• Dial Mode
- Tone
- Pulse
- Tone else Pulse
• Miscellaneous
- Report AC Failure Delay
- Test Report Time:
- Send Unmapped Points
- IP Communicator
Figure 6-18. DACT Card - Basics Tab
• Central Station Email Address. Check the box to enter an email address and the .CSV
file will automatically be sent to Central Station. Only for Per Point DACTs and needs
to be set up with Central Station.
To edit the Event Codes tab (Figure 6-19):
The Event Codes tab allows to edit the event
codes associated with each of the 4007ES
Panel point types.
1. Click on the Point Types drop-down list box
and select the point type whose event codes
needs to be changed. (The Next and
Previous buttons allow to scroll through the
list without clicking on the drop-down list
box.)
2. Click on the Enable Edit checkbox at the
top left of the window.
3. A warning window appears. Click on Yes.
Figure 6-19. DACT - Event Codes Tab
Note: Do not edit event codes without prior authorization and direction from the central station.
4. The non-edible fields remain grayed out. Define the appropriate event codes for both the
Event and the Restoral columns.
5. Click Apply > OK to confirm the edits.
6-12
4007ES Panel Programmer Manual (579-1167)
Editing the Serial To edit the Local Points tab (Figure 6-20):
DACT Card The Local Points tab allows to edit the local points associated with each of the 4007ES Panel
point types.
1. Click on the Enable Edit checkbox at the
top right of the window.
2. A warning window appears. Click on Yes.
Note: Do not edit local points without prior
authorization and direction from the central
station.
3. The non-edible fields remain grayed out.
Define the appropriate local points for
both the Event and the Restoral columns.
4. Click Apply > OK to confirm the edits.
6-13
4007ES Panel Programmer Manual (579-1167)
Editing the Event The 4007-9806 DACT “per event” has five main tabs. To edit the Card Properties tab, the
DACT Card Basics tab, the Event Codes tab, the Local Points tab, and the Points tab.
To edit the Card Properties tab per event:
1. The panel assigns an address when a DACT card is added. Set the card address to math the
programmer assigned address.
2. Enter the card’s custom label. This label should make the card easily identifiable.
3. Select a card address, from 0 to 31.
The following fields in the tab are filled by the programmer and cannot be edited:
• Card description
• Card default label
• Annunciator address
• Box number
• Bay number
• Location
6-14
4007ES Panel Programmer Manual (579-1167)
6-15
4007ES Panel Programmer Manual (579-1167)
Editing the Event The Local Points tab allows the editing for the local points associated with each of the 4007ES
DACT Card Panel point types.
To edit the Local Points tab (Figure 6-20):
1. Select the Enable Edit checkbox at the top right of the window.
2. A warning window appears. Click on Yes.
Note: Do not edit local points without prior authorization and direction from the central station.
3. Define the appropriate local points for both the Event and the Restoral columns.
4. Click Apply > OK to confirm the edits.
48-LED Module The 48-LED Module has two main tabs to configure. The Card Properties tab and the Point
Editing tab.
To edit the Card Properties tab:
1. Enter a card address for the 48-LED Module.
2. Enter the card’s custom label. This label should make the card easily identifiable.
The following fields in the tab are filled by the programmer and cannot be edited:
• Card description
• Card default label
• Annunciator address
• Unit number
• Box number
• Bay number
• Location
6-16
4007ES Panel Programmer Manual (579-1167)
6-17
4007ES Panel Programmer Manual (579-1167)
6-18
Chapter 7.
Editing Standard Component Properties
Introduction TrueAlert devices are edited through the Point Editing tab on the IDNAC Power Supply.
To access this tab:
1. Go to the Hardware Configuration window.
2. Double-click on the IDNAC Power Supply icon.
3. Click on the Point Editing tab.
In this chapter TrueAlert ES AO Appliance Point Editing ...... 7-2 TrueAlert ES VO Appliances Point Editing .... 7-3
TrueAlert ES AV Appliance Point Editing....... 7-4 ISO Options ..................................................... 7-6
Repeater Options.............................................. 7-6 DCAI Options .................................................. 7-7
TrueAlert STRB Appliances Point Editing ...... 7-7 TrueAlert Horn Appliance Point Editing ......... 7-8
TrueAlert AV Appliances Point Editing........... 7-9 TrueAlert ASTRB Appliances Point Editing. 7-10
Copy and Pasting Properties .......................... 7-11
7-1
4007ES Panel Programmer Manual (579-1167)
TrueAlert ES AO Use this device type to edit TrueAlert ES Audible (AO) appliances.
Appliance Point The following editing options are available for this appliance:
Editing Table 7-1. TrueAlert ES AO Point Editing Options
Option Description
Custom Label This field can be used to describe the appliance's function, location, or other
descriptive information.
Style Select the Style that corresponds to the appliance or device you are programming.
Available • Indoor
settings: • Weatherproof UL
• Weatherproof ULC
Coding Type Select the Coding Type that will determine the cadence of the audible signal.
System This will set the coding to the value determined in the System
Default Option tab.
March 20 A coded signal that uses 20 beats per minute. Each beat consists of
1.5 second pulse on, 1.5 second off. Pattern repeats until alarm
silence.
March 60 A coded signal that uses 60 beats per minute. Each beat consists of
½ second pulse on, ½ second off. Pattern repeats until alarm
silence.
March 120 A coded signal that uses 120 beats per minute. Each beat consists
of ¼ second pulse on, ¼ second off. Pattern repeats until alarm
silence.
On Steady On steadily.
High To use this option the appliance's configuration control must be set
to Panel.
Low To use this option the appliance's configuration control must be set
to Panel.
Hardware Selecting this option will set the appliance to the setting indicated
on the appliance's configuration switch or jumper.
Note: The "Copy/Paste/ Special Paste" feature can be used to configure multiple devices
identically.
7-2
4007ES Panel Programmer Manual (579-1167)
TrueAlert ES VO Use this device type to edit TrueAlert ES Visual (VO) appliances.
Appliances Point The following editing options are available for this appliance:
Editing Table 7-2. TrueAlert ES VO Point Editing Options
Option Description
Custom Label This field can be used to describe the appliance's function, location, or other
descriptive information.
Current Draw This information is not available.
(Amps)
Style Select the Style that corresponds to the appliance or device you are programming.
• Indoor. System Default. Sets the candela value to the one selected in
Available candela the System Option tab.
options:
15 candela
30 candela
75 candela
110 candela
135 candela
185 candela
Hardware. Selecting this option will set the appliance to the
setting indicated on the appliance's configuration switch or
jumper.
• Weatherproof UL. System Default. Sets the candela value to the one selected in
Available candela the System Option tab.
options: 15 candela
75 candela
WP 75 candela
WP 185 candela
Hardware. Selecting this option will set the appliance to the
setting indicated on the appliance's configuration switch or
jumper.
• Weatherproof ULC. System Default. Sets the candela value to the one selected in
Available candela the System Option tab.
options:
20 candela
30 candela
75 candela
Hardware. Selecting this option will set the appliance to the
setting indicated on the appliance's configuration switch or
jumper.
Operation Select the type of operation the appliance will signal.
General Evac. The strobe will be automatically associated with the “ALL
VISUAL” VNAC by default. The “alarm/alert” switch on the
device must be set to "Alarm".
Alert The strobe will be automatically associated with the “ALL
ALERT” VNAC by default. The user must select this option to
configure the strobe as a “Mass notification” device. The
“alarm/alert” switch on the device must be set to "Alert".
Other When this mode is selected the user is confirming that the
strobe will not have a default assignation to a particular VNAC
and that the VNAC must be specified by the user.
Candela Select the candela output of the appliance. The selection varies according to the
appliance style.
Note: The "Copy/Paste/ Special Paste" feature can be used to configure multiple devices identically.
7-3
4007ES Panel Programmer Manual (579-1167)
TrueAlert ES AV Use this device type to edit TrueAlert ES Audible/Visual (AV) appliances.
Appliance Point The following editing options are available for this appliance:
Editing
Option Description
Custom Label This field can be used to describe the appliance's function, location, or other
descriptive information.
Style Select the Style that corresponds to the appliance or device you are programming.
15 candela
30 candela
• Indoor. 75 candela
• Available candela 110 candela
options:
135 candela
185 candela
15 candela
20 candela
• Weatherproof
ULC. 30 candela
• Available candela
options: 75 candela
7-4
Table 7-3.TrueAlert ES AV Point Editing Options (Continued)
Option Description
General Evac. The strobe will be automatically associated with the “ALL
VISUAL” VNAC by default. The “alarm/alert” switch on the
device must be set to "Alarm".
Other When this mode is selected the user is confirming that the
strobe will not have a default assignation to a particular VNAC
and that the VNAC must be specified by the user.
Candela Select the candela output of the appliance. The selection varies according to the
appliance style.
Coding Type Select the Coding Type that will determine the cadence of the audible signal.
System Default This will set the coding to the value determined in the System
Option tab.
March 60 A coded signal that uses 60 beats per minute. Each beat
consists of ½ second pulse on, ½ second off. Pattern repeats
until alarm silence.
March 120 A coded signal that uses 120 beats per minute. Each beat
consists of ¼ second pulse on, ¼ second off. Pattern repeats
until alarm silence.
On Steady On steadily.
7-5
4007ES Panel Programmer Manual (579-1167)
Option Description
Custom Label This field can be used to describe the appliance's function, location, or other
descriptive information.
Option Description
Custom Label This field can be used to describe the appliance's function, location, or other
descriptive information.
Depleted Battery When this option is selected the Repeater will shut itself off after detecting a depleted
Cutout battery condition when no AC power is present. This option is de-selected by default.
Repeater Select the option that corresponds to the Repeater’s wiring style.
Operation
• For local Class B Wiring select "Class B Spur"
7-6
4007ES Panel Programmer Manual (579-1167)
Option Description
Custom Label This field can be used to describe the appliance's function, location, or other
descriptive information.
Loop 2 Address When the second loop is used, the programmer will assign it a virtual address. This
virtual address does not need to be adjacent to the loop 1 hardware address.
TrueAlert STRB Use this device type to edit TrueAlert Strobe (STRB) appliances.
Appliances Point The following editing options are available for this appliance:
Editing
Table 7-7. TrueAlert STRB Point Editing Options
Option Description
Custom Label This field can be used to describe the appliance's function, location, or other
descriptive information.
Style Select the Style that corresponds to the appliance or device you are programming.
• Indoor. System Default. Sets the candela value to the one selected in
Available candela the System Option tab.
options:
15 candela
30 candela
75 candela
110 candela
General Evac. The strobe will be automatically associated with the “ALL
VISUAL” VNAC by default.
Note: The "Copy/Paste/Special Paste" feature can be used to configure multiple devices identically.
7-7
4007ES Panel Programmer Manual (579-1167)
TrueAlert Horn Use this device type to edit TrueAlert Horn appliances.
Appliance Point The following editing options are available for this appliance:
Editing
Table 7-8. TrueAlert Horn Point Editing Options
Option Description
Custom Label This field can be used to describe the appliance's function, location, or other
descriptive information.
Coding Type Select the Coding Type that will determine the cadence of the audible signal.
System This will set the coding to the value determined in the System Option
Default tab.
March 60 A coded signal that uses 60 beats per minute. Each beat consists of ½
second pulse on, ½ second off. Pattern repeats until alarm silence.
March 120 A coded signal that uses 120 beats per minute. Each beat consists of
¼ second pulse on, ¼ second off. Pattern repeats until alarm silence.
On Steady On steadily.
High To use this option the appliance's configuration control must be set to
Panel.
Low To use this option the appliance's configuration control must be set to
Panel.
Note: The "Copy/Paste/Special Paste" feature can be used to configure multiple devices identically.
7-8
4007ES Panel Programmer Manual (579-1167)
TrueAlert AV Use this device type to edit TrueAlert Strobe Audible/Visual (AV) appliances.
Appliances Point The following editing options are available for this appliance:
Editing
Point Editing for TrueAlert Device
Table 7-9. TrueAlert AV Point Editing Options
Option Description
Custom Label This field can be used to describe the appliance's function, location, or other
descriptive information.
Alternate Label This label is displayed when the alternate language is used.
Style Select the Style that corresponds to the appliance or device you are programming.
Indoor. System Default. Sets the candela value to the one selected in
Available candela the System Option tab.
options:
15 candela
30 candela
75 candela
110 candela
Operation The strobe and horn appliances will be automatically associated respectively with the
“ALL VISUAL” and "ALL AUDIBLE" VNAC by default.
Coding Type Select the Coding Type that will determine the cadence of the audible signal.
System Default This will set the coding to the value determined in the System
Option tab.
March 60 A coded signal that uses 60 beats per minute. Each beat
consists of ½ second pulse on, ½ second off. Pattern repeats
until alarm silence.
March 120 A coded signal that uses 120 beats per minute. Each beat
consists of ¼ second pulse on, ¼ second off. Pattern repeats
until alarm silence.
On Steady On steadily.
Note: The "Copy/Paste/Special Paste" feature can be used to configure multiple devices identically.
7-9
4007ES Panel Programmer Manual (579-1167)
TrueAlert ASTRB Use this device type to edit TrueAlert Alert Strobe (ASTRB) appliances.
Appliances Point The following editing options are available for this appliance:
Editing
Option Description
Custom Label This field can be used to describe the appliance's function, location, or other
descriptive information.
Style Select the Style that corresponds to the appliance or device you are programming.
Indoor. System Default. Sets the candela value to the one selected in
Available candela the System Option tab.
options:
15 candela
30 candela
75 candela
110 candela
Operation Alert. The strobe will be automatically associated with the “ALL ALERT” VNAC by
default. The user must select this option to configure the strobe as a “Mass
notification” device.
Note: The "Copy/Paste/Special Paste" feature can be used to configure multiple devices identically.
7-10
4007ES Panel Programmer Manual (579-1167)
Copy and Pasting The standard copy and paste as well as the special paste, allow you to copy the properties of a
Properties device and paste them into the properties of a similar device by using the "Copy" and "Paste"
buttons.
Standard Copy and Paste:
There are two ways to perform a Copy and Paste.
• Device by device:
1. Select the point to be copied.
2. Select the device type
3. Enter the required information in the Properties section (the options differ depending on
the selected device).
4. Click on the "Copy" button located above the properties window.
5. Select the next point to be programmed and click on the "Paste" or "Paste Special" button.
Special Paste:
The Special paste essentially works like the regular paste but gives you more options
and more control over the content you paste. The special paste gives you four advanced
paste options:
• Auto Increment last number in labels: Selecting this options will automatically
increase the existing number on the label by 1. For example: Label DEVICE1 would
be pasted as label DEVICE2. This option can be added to the "Paste All Properties"
option and the "Paste Label Only" option.
• Paste All Properties: This option pastes all properties of the copied device, including
labels.
• Paste Labels Only: This option only pastes the copied labels.
6. Paste Exclude Labels: Pastes all copied properties of the device except the labels.
7. All of the properties from the first device will now be copied into the new device's
properties.
8. Make any editing adjustments required and repeat if necessary.
• By multiple selection:
1. Select the point to be copied.
2. Select the device type.
3. Enter the required information in the Properties section (the options differ depending on
the selected device).
4. Click on the "Copy" button located above the properties window.
5. Go to the Point Editing spreadsheet and select all the points you want filled with the
pasted properties.
6. Once all the points are selected, click on the "Paste" button.
7. All of the properties from the first device will now be copied into the properties of all the
selected devices.
7-11
Chapter 8.
Viewing, Adding, and Editing Lists
Introduction A list is a group of similar points, sharing a common name, that can be monitored or
controlled as if they were a single point. For example, when you use a switch to turn on a list
populated with control points, all of the points in the list turn on.
The 4007ES FACP includes the following types of lists.
• Automatically Generated, Read-Only System Lists. These lists are created based
on the point type assigned to the point. Points cannot be manually added or deleted
from these lists.
• Automatically Generated, Editable System Lists. These are lists created based on
the point types you assign to the point. These lists are only editable after the automatic
list generation property is turned off for the list.
• User-Defined Lists. Switches, LEDs, and Custom Control equations all make use of
these types of lists. Switches typically control lists made up of control points (relays),
audio NACs, or standard NACs (horns/strobes). LEDs can be programmed to monitor
a list and turn ON when any point in the list activates. Custom Control equations
typically use lists of monitor points to indicate when a specific output action should
occur, and the points affected by the output action are typically specified in a user-
defined list of control points.
• Zone Lists. This option allows you to create up to 512 lists grouping together points
in one defined zone.
This chapter describes the programming of the four list categories, General Lists, WalkTest
Lists, Latching Supv Verification Lists, and Elevator Recall Lists, used by the Panel FACP.
Note: The Alarm Verification Tab can still be accessed through the List Tab, but it cannot be used.
For information on using lists for the Install Mode feature, consult the 4007ES Operator’s
Manual (579-1165).
8-1
4007ES Panel Programmer Manual (579-1167)
List Tab Select the List Tab to display the List Tab window. By default when you select the List Tab, the
General List subtab, located on the bottom left of the window, is selected. This window
contains an entry for every list in the system.
The subtabs running across the bottom of the window allow you to display only the lists
associated with a specific system category. For example, clicking on the alarm verification
subtab displays only the lists associated with alarm verification.
Sort Function The Sort function allows you to sort and display lists in ascending or descending order based
on list-specific criteria (the criteria shown in the Sort Dialog is different for each type of list).
To sort lists, do one of the following:
Custom Label Spell Check allows you to validate the spelling of custom labels. Using Spell Check,
Spell Check incorrectly spelled words can then be automatically corrected or suggested alternatives can be
substituted.
1. Position the pointer in the point list and press the F7 button. (Alternatively, you can right-
click in the List window and select Spell Check when the list of options appears.)
2. Correct the misspelled word in any of the following ways. (Use the Ignore and Ignore All
buttons to ignore the misspelled word.)
• Click on the Change or Change All button to accept the suggested spelling in the
“Change to” field.
• Type the correct spelling in the “Change to” field and press the Change or Change All
button.
• Scroll through the Suggestions drop-down list, click on one of the entries, and then
click on the Change or Change All field.
The Search and Find functions allow you to specify a specific search criteria (such as a specific
custom label) and then search the List Window for the selected data.
1. Position the pointer in the List Window and press the CTRL + F key combination.
(Alternatively, you can right click in the List Window and select Search or Find from the list
that appears.)
2. Enter the Search text in the Search What field. Click on the Search in Column field and
select the column in which to search. Click on Search Next to start the search.
3. Press the F3 key to continue searching the List Window for another occurrence of the item
you are searching.
8-2
4007ES Panel Programmer Manual (579-1167)
Managing Points Default custom control programming within the system automatically adds points to system
lists based on their point type, a process known as auto list generation, or autogen. For
example, adding a signal point with the SSIGNAL point type automatically adds the point to
system list L8, Fire Alarm Points Off on Silence.
In some applications, however, you need to turn a system list's autogen property off, so that you
can manually move points into or out of the system list. This is particularly true when editing
WalkTest, Latching Supv Verification, and Elevator Recall groups.
Be aware that when working with the system lists, four icons are used to indicate the status of
the system list.
This symbol represents an auto-generated list with the autogen property turned on. When
autogen is turned on, points cannot be manually moved into or out of the list.
This symbol represents an auto-generated list whose autogen property cannot be altered.
The list is permanently set to autogen on and cannot be edited.
This symbol represents an auto-generated list with the autogen property turned off.
A system list's autogen property can be turned on and off in one of two places:
• General List Tab. Clicking on the General List tab displays all lists (system and user)
currently defined on the panel. Refer to “Turning Autogen Off and On from the
General List Tab” for specific information on doing this.
• WalkTest, Latching Supv Verification, Elevator Recall Tabs. Each of these tabs
displays a window that allows you to move points into the appropriate lists. Within
each window, you can toggle the autogen property to allow points to be moved into
and out of the lists. Refer to the specific section for information on turning off autogen
for Latching Supv Verification, WalkTest, or elevator recall.
Turning Autogen 1. Click on the List tab at the top of the programmer.
Off and On from 2. Click on the General List subtab at the bottom of the window.
the General List 3. Right-click on the list whose autogen property you want to change. Select Properties from
Tab the list that appears. A dialog similar to Figure 8-2 appears.
8-3
4007ES Panel Programmer Manual (579-1167)
Basic Operations User-defined lists allow a range of points to be controlled (turned on or off, for example) by
turning a switch on, or via a Custom Control command. Lists associated with LEDs allow the
status of system attributes or components to be monitored.
Editing an To edit an existing list (i.e., add additional points or delete points from the list):
Existing User- 1. Open the list's Tag List by either right-clicking on the list and selecting Tag List from the
Defined List menu that appears, or click on the list and press the F9 key.
2. When the tag list appears, click on the point you want to add or delete. Press the spacebar to
toggle whether the point is tagged (included in the list) or not. Tagged points are identified
by the “>>” to the left of the point name.
8-4
4007ES Panel Programmer Manual (579-1167)
Type Operation
Retard Stage. If a point specified within one of the alarm verification lists
enters an alarm state, the system delays the annunciation of the alarm for 15
seconds
Reset Stage. When the 15 second timer expires, the system attempts to reset
Canadian
the initiating device for five seconds.
Operation
Confirmation Stage. After the five second timer expires, the system
evaluates the state of the initiating device for 10 additional seconds. After 10
seconds, if the device is still in alarm, the system immediately annunciates the
alarm.
Retard Stage. If a point specified within one of the alarm verification lists
enters an alarm state, the system delays the annunciation of the alarm for 30
seconds
Domestic
Reset Stage. When the timer expires, the system attempts to reset the
(US)
initiating device for five seconds.
Operation
Confirmation Stage. After the timer expires, the system evaluates the state
of the initiating device for up to 120 additional seconds. After this duration, if
the device is still in alarm, the system immediately annunciates the alarm.
To select Canadian or Domestic (US) operation, follow these steps.
1. Right click on one of the groups and select
Properties. The Alarm Verification Properties
dialog shown below appears.
2. Click on the Alarm Verification tab.
3. Click on the drop-down list box and select
Canadian or Domestic operation.
Note: You only need to set the Verification Timer field
for one of the alarm verification groups. The
programmer sets this field to the same value for
all other groups.
8-5
4007ES Panel Programmer Manual (579-1167)
WalkTest WalkTest allows the function of the system's initiating devices and signals to be tested by a
single person. Conducting a WalkTest requires you to perform the following general steps.
• Step 1. Create WalkTest Groups. The ES Panel supports up to eight WalkTest™
groups. This allows the building to be divided into small portions for the WalkTest™,
and allows the rest of the building to be protected by the fire alarm panel. Each group
has a list of monitor points (initiating devices) and a list of the signal circuits that
activate when one of the monitor points within the group activates.
• Step 2. Enable WalkTest Options from Front Panel. These options include the
following. Refer to the 4007ES Operator's Manual (579-1165) for information on
setting these options.
- Which WalkTest Group is enabled.
- Whether the group's signals turn on when a monitor point in the same group
activates. Turn this option off to perform a silent WalkTest on the system.
- Whether logging of WalkTest information is enabled or not. (Enable this option to
perform a silent WalkTest.)
• Step 3. Manually Activate Initiating Devices in Each Group and Interpret Signals.
Individually activate each initiating device in the group, using the manufacturer’s
recommended test equipment. Make sure to proceed in a logical manner (i.e., start with
the lowest IDNet address and work toward the highest). Each time you activate an
initiating device, the system’s signals pulse a code that allows you to verify exactly
which initiating device triggered the signals. For hardwired monitor zones, the signal
code corresponds to the number of the zone. (For example, if the zone number is eight,
the signals pulse eight times to indicate zone eight.) For IDNet devices, the first set of
pulses from the signals correspond to the channel. The signals then pause momentarily
and the next set of pulses corresponds to the number of the device on the channel. For
example, if you activate an IDNet smoke detector with an address of M1-25, the
signals would sound once to indicate channel one, pause for a short duration, and then
sound two pulses followed by a pause and then five pulses to indicate device 25. In
some cases, immediately after verifying the function of an initiating device, you may
also want to verify its ability to generate a trouble condition. To do this, cause a trouble
on the device and then listen to the signals. The signals sound steady for 4 seconds to
indicate trouble conditions, and then reset.
8-6
4007ES Panel Programmer Manual (579-1167)
8-7
4007ES Panel Programmer Manual (579-1167)
Tab Properties
Setting the properties in this tab affects all WalkTest groups.
Monitor. A check in this box means monitor points are automatically inserted in
Group 1 - Monitor Zones. If you uncheck this box, you can move points from
one group to another. However, at a later point, if you recheck this box, the
points you previously moved to other groups will be moved back to Group 1.
WalkTest Control. A check in this box means control points (signals/relays) are
automatically inserted in Group 0 - Signals/Relays. If you uncheck this box, you
can move points from one group to another. However, at a later point, if you
recheck this box, the points you previously moved to other groups will be
moved back to Group 1.
On. Allows you to set the duration of each tone within the PNIS code.
Off. Allows you to set the duration of silence between tones of the PNIS code.
Setting the properties in this tab affects only the selected group.
Monitor. A counter that tracks the number of devices in the group.
Group Control. A counter that tracks the number of devices in the group.
Reset Delay. Allows you to shorten or lengthen the reset time used by the
monitor device. For example, increase the delay in cases where canned smoke
does not clear from a smoke detector quickly enough.
Description. Allows you to change the description of the group’s monitor or
List control lists. For example, you can change the name of the WalkTest Group 0 -
Signals/Relays to a more descriptive name, if necessary.
4. After making changes to the WalkTest Group properties, click on the Apply button to apply
the changes and then click on OK to close the window.
8-8
4007ES Panel Programmer Manual (579-1167)
Elevator Recall The Elevator Recall list is made up of five groups, each corresponding to an elevator shaft
List numbered from one to five. Each shaft group contains three lists - one for the primary recall
points, one for the alternate recall points, and one for the shutdown points.
The Elevator Shaft 1 group initially contains all of the system's monitor points and all relays
with the following point types - PRIMARY, ALTERN, and SHAFT (shutdown).
8-9
4007ES Panel Programmer Manual (579-1167)
Zone Lists The Zone List tab provides a way to group alarm conditions into zones (up to 512 zones).
When grouped into zone, when an alarm occurs, a list of affected zones is be displayed on the
panel's touchscreen. It is then possible to touch the zone in alarm to display all the points that
are in alarm in that particular zone.
8-10
Chapter 9.
Custom Control
Introduction Custom control allows the components of the ES Panel FACP—hardware points, pseudo
points, and lists—to be controlled with user-definable custom control “equations.”
This chapter describes using Custom Control to create custom programming applications for
the ES Panel FACP.
In this chapter Custom Control Overview........................9-1 Role of Lists and Pseudo Points .............. 9-2
Using a Ladder Logic Diagram to Evaluate an
Anatomy of a Custom Control Equation ..9-2
Equation ................................................... 9-3
Custom Control Window..........................9-5 Step 1. Select User Program .................... 9-6
Step 2. Add Input Statements ...................9-7 Step 3. Add Output Statements................ 9-8
Floor Above/Floor Below Wizard ............9-8 Step 1. Select Floor Tab ........................... 9-9
Step 2. General Information ...................9-10 Step 3. Specify Floor Names ................. 9-11
Step 4. Specify Input and Static Points...9-11 Using the Selective Signaling Wizard ... 9-12
Step 1. Select Selective Signaling Wizard
Step 2. Set General Options................... 9-13
Tab ..........................................................9-12
Step 4. Link Initiating and Notification
Step 3. Set Zone Names..........................9-13
Points ..................................................... 9-14
Using the Sounder/Relay Base Wizard...9-15 Activate Base on Alarm......................... 9-15
Alert—Activate Base Prior to Alarm .....9-17
Custom Control ES Panel Custom Control —which is a wizard-based application used to create Custom
Overview Control Equations -- provides a way to override the ES Panel’s default operation and allows
the ES Panel to function in a facility-specific way. Each Custom Control equation has a
similar form: one half of the equation, called the input side, is used to monitor the state of
specific system inputs (initiating devices, for example). The other half of the equation, called
the output side, is used to control specific system outputs (relays, notification appliances, etc.).
The output side executes only when the state of the input side is true. Another way to think
about Custom Control equations is to consider them as If/Then commands. If the input side of
the equation is true, then execute the output side.
The following examples help explain the way custom control is typically used with a ES Panel
FACP.
• Selective Signaling. Selective signaling replaces the system's general alarm NAC
operation - which activates all NACs in response to any alarm condition -- with
selective NAC control. This type of control allows you to program the system so that
only specific NACs respond to specific initiating devices.
• Fan and Damper Control following an Alarm. Controlling a building's HVAC
system following an alarm condition prevents supply fans from feeding a potential
fire and also allows the HVAC system to exhaust smoke from the area in alarm. In this
case, custom control equations are used to monitor the initiating devices in a given
area and control the HVAC system’s dampers and air handling units to provide the
correct supply and exhaust pressurization.
9-1
4007ES Panel Programmer Manual (579-1167)
Custom Control
Role of Lists and Using lists and pseudo points (both user-defined and system) improves the efficiency of
Pseudo Points Custom Control equations and allows a range of facility-specific operations to be programmed.
Anatomy of a As mentioned above, every Custom Control equation has an input side, consisting of input
Custom Control statements, and an output side, consisting of output statements.
Equation
Input Statements are typically used to monitor the status of a point or list, or perform an
action such as delay, cycle, compare two values, or save/recall values. Every input statement
begins with an Opcode, which is the action that the input is performing (for example, monitor
point status, recall memory register, etc.). The Custom Control wizard then displays a series of
opcode-specific dialogs. For example if the Opcode is Point Status, the dialogs prompt the user
for Qualifier about the condition (alarm, trouble, etc.) and point being monitored.
Output Statements are the actions that occur only when the input side of the equation is true.
Every output statement begins with an Opcode, which is the general action that occurs when
the input side is true. The opcode is followed by a series of opcode-specific dialogs, which
allow you to specify exactly how the selected opcode functions. For example, if you are using
the Set Opcode, the wizard displays a series of dialogs that allow you to specify a qualifier (on,
off, etc.) and the point (a signal, for example) on which you want the output action to execute.
9-2
4007ES Panel Programmer Manual (579-1167)
Anatomy of a Logical Operators (AND, OR, NOT) allow you to link multiple input statements to form
Custom Control logical expressions. Logical operators are only used with input statements and are not used
Equation with Output statements. ES Panel Custom Control uses the following logical operators.
• AND Operator. The AND logical operator allows you to put a group of points in series
so that only the activation of all points at the same time causes the Output side of the
equation to occur. In the following example, Zone1 and Zone2 must both be in alarm
(FIRE) before the output (Hold ON SIG3) executes.
• OR Operator. The OR operator allows you to put a group of points in parallel, meaning
the activation of any one of the points causes the output side of the equation to execute.
In the following example, if either Zone1 or Zone2 enters an alarm state, the output
(Hold ON SIG3) executes.
• NOT Operator. Use the NOT Operator to specify that a condition must not be true in
order for the output to execute. In the following example, the output side of the
equation (print message “Smoke not dirty” executes only if the condition of M1-1 is
NOT dirty.
Using a Ladder A ladder logic diagram is a “sketch” of the equation used to evaluate (predict the outcome) of a
Logic Diagram to custom control equation before it is entered into the programmer. Use the following
Evaluate an conventions when creating ladder logic diagrams.
Equation
• Draw a solid, vertical line on the left side of the sketch to represent the starting point
for the equation. Use a vertical dashed line to divide the sketch into an input side and
an output side.
• Use two vertical, parallel lines to represent each input statement. Add text between the
lines to describe the input statement.
9-3
4007ES Panel Programmer Manual (579-1167)
Using a Ladder • Use a circle to represent each output statement. Add text within or beside the circle to
Logic Diagram to describe the output statement. In the following example, the output side of the equation
Evaluate an contains a single output statement, HOLD ON SIG 1. This action only occurs if the
Equation input side of the equation, which monitors point M 2-1 for the presence of a fire
condition, is true.
• Represent the OR logical operator by positioning inputs on top of one another as
shown in the example below. Represent the AND logical operator by positioning the
inputs beside one another.
Point Status
Position the M 2-1 for TBL
inputs on Point Status Point Status Relay
top of one M 2-2 for TBL M 2-4 for TBL
another to
Point Status
represent M 2-3 for TBL
the OR
Position the iputs beside
logical operator
one another to represent AND
logical operator
The example shown above can be interpreted as: If point M2-1 or M2-2 or M2-3 and M2-4 are
in a trouble state, hold on Relay 1. M2-4 is the key here. At least one of the three on the left
(M2-1, M2-2, and M2-3) must be in a trouble state AND M2-4 must also be in a trouble state.
9-4
4007ES Panel Programmer Manual (579-1167)
Custom Control Selecting the Custom Control tab from the main programmer window displays the Custom
Window Control Window shown in Figure 9-1. This window contains two halves.
• The left half lists user-defined and system-only (non-editable) programs. Click on the
+ sign to the left of an entry to expand the contents of that entry.
• The right half of the window is used for creating user-defined Custom Control
equations. The Equation Comment text entry box allows you to enter descriptive text
explaining the operation of the equation. The Equations Area contains a text entry box
for creating and editing an equation’s input and output statements. The Add button
starts the Custom Control Wizard and is used to create new equations. The Edit button
is used to edit existing equations. The Taglist button starts a taglist that can be used for
selecting/deselecting points in an existing equation.
9-5
4007ES Panel Programmer Manual (579-1167)
Step 1. Select Note: You cannot write custom control on InfoAlarm switches and LEDs.
User Program
The first step in defining a new custom control equation is to add the equation to the User
Programs 3.
To add a new custom control equation:
1. Right-click on one of the user programs (Program 3 through Program 55), located at the
bottom of the program list, and select Add Equation from the list of options.
The Equations section of the Custom Control window updates to include the [INPUTS], [END
INPUTS], etc. entries.
9-6
4007ES Panel Programmer Manual (579-1167)
Step 2. Add Input The second step in creating a new Custom Control equation is to add input statements to the
Statements equation. Repeat the steps in this section until all input statements in the equation have been
defined.
1. In the Equations box, position the cursor just to the right of [INPUTS].
9-7
4007ES Panel Programmer Manual (579-1167)
Step 3. Add The third step in creating a new Custom Control equation is to add output statements to the new
Output equation. Repeat the steps in this section until all output statements in the equation have been
Statements defined.
1. In the Equations box, position the cursor just to the right of [OUTPUTS].
2. Click on the Add button. The dialog shown in Figure 9-5 appears.
3. Click on the drop-down list box, select one of the output Opcodes, and click the Next button.
4. The next dialogs displayed by the wizard depend on the Opcode you selected in Step 3.
Follow the Wizard’s windows to create the output for the equation.
5. The Finish button becomes available when all dialogs related to the output Opcode have
appeared. Click it to finish defining the output statement.
Floor Above/Floor This application limits the activation of NACs to the floor on which the activated initiating
Below Wizard device is located, referred to as the fire floor, and the floors immediately above and below the
fire floor.
In Figure 9-6, an activated smoke detector or pull station on Floor 3 activates the NACs on
Floors 2, 3, and 4.
9-8
4007ES Panel Programmer Manual (579-1167)
Step 1. Select 1. Start the Floor Above/Below Wizard by clicking on the Floor Above/Floor Below Wizard
Floor Tab tab, which is located along the bottom left part of the Custom Control window.
2. Right-click in the blank area above the tab. When the list of options appears, select Create
Floor Group. (The ES Panel refers to each set of floor above/below equations as a Floor
Group. This is the name of the group or area that the floor above/below program has control
over.) Enter a name for the Floor Group in the dialog that appears.
9-9
4007ES Panel Programmer Manual (579-1167)
Step 2. General After you enter a name for the floor group, click the Next button. A dialog appears, allowing
Information you to specify general information about the application.
9-10
4007ES Panel Programmer Manual (579-1167)
Step 3. Specify The Floor drop-down list box contains an entry for all floors (i.e., if you set number of floors to
Floor Names 10 in the previous screen, there are 10 entries). To enter a floor's name, first click on the drop-
down list box to select the floor and then enter a descriptive label in the Floor Label text box.
Enter any comments in the Comment box at the bottom of the dialog.
Step 4. Specify Enter information for the other fields in this screen as follows:
Input and Static
Points. • Alarm Points. Identifies the floor's input points (detectors, pull stations, etc.).
• Audio Points. Identifies the floor's audio speaker points.
• Non-Audio Points. Identifies the floor's non-audio (horns, strobes) notification points.
• Air ON Points. Identifies the pressurization fan and damper ON points.
• Exhaust ON Points. Identifies the exhaust fan and damper ON points.
• Air OFF Points. Identifies the pressurization fan and damper OFF points.
• Exhaust OFF Points. Identifies the exhaust fan and damper OFF points.
For each of these selections, when you click on the button, a taglist appears, allowing you to
select specific points. Press the space bar to select a point. A “>>” symbol appears to the left of
the point to indicate that it is selected.
9-11
4007ES Panel Programmer Manual (579-1167)
Using the Selective Signaling is typically used to limit the activation of NACs to the area or floor on
Selective which an activated initiating device(s) is located. In the following example, an activated
Signaling Wizard initiating device on Floor 2 triggers only the NACs located on Floor 2.
Step 1. Select Start the Selective Signaling Wizard by clicking on the Selective Signaling Wizard tab, which
Selective is located along the bottom left part of the Custom Control window.
Signaling Wizard Right-click in the blank area above the tabs. When the list of options appears, select Create
Tab Group. (See Figure 9-13.)
9-12
4007ES Panel Programmer Manual (579-1167)
Step 2. Set After you enter a name for the group, click the Next button. A dialog appears, allowing you to
General Options specify general information about the application.
Step 3. Set Zone Click on the Zone drop-down list box and select the zone number. Enter a label for the zone in
Names the Signal Zone Label box. Click on Next to continue.
9-13
4007ES Panel Programmer Manual (579-1167)
Step 4. Link The screen shown below allows you to link initiating and notification points to one another. If
Initiating and one of the specified initiating devices activates, only the notification appliances linked to the
Notification initiating device will activate.
Points
1. Click on the button labeled Alarm Points. A tag list appears. Use the up and down arrow
keys to move through the list. Use the spacebar to tag (select) a point. A “>>” symbol
appears to the left of the point when it is selected. Click OK to continue. The previous
screen appears.
2. In the “Notification Points in this Signal Zone” area of the screen, click on the button
corresponding to the type of notification appliance you want to turn on when the tagged
initiating devices activate. The choices are: Visual Points, Audible Points, Speaker Points,
TrueAlert Zones (Addressable), and TrueAlert Zones (Non-Addressable). A tag list appears.
Use the up and down arrow keys to move through the list. Use the spacebar to tag (select) a
point. A“>>” symbol appears to the left of the point when it is selected. Click OK to
continue. The previous screen appears.
3. You can also activate other notification signal zones when a tagged initiating device
activates. To do this, click on the Notification Zones button to the right of the “Other Signal
Zones Notified” label. A tag list appears. Use the up and down arrow keys to move through
the list. Use the spacebar to tag (select) a point. A “>>” symbol appears to the left of the
point when it is selected. Click OK to continue. The previous screen appears.
4. Click Next to continue. A screen showing the equations created by the wizard appears. Click
Finish.
9-14
4007ES Panel Programmer Manual (579-1167)
Using the The Sounder/Relay Base Wizard allows you to change the default operation of single station
Sounder/Relay smoke detectors. Note that the default operation—sounder activates when the alarm threshold
Base Wizard is passed and deactivates when the smoke level drops back below the threshold—is
programmed using the TPHOTO device type. To use the wizard to change the default
operation, you must assign a device type of SPHOTO or RPHOTO to the device.
The wizard allows two types of custom operations—Activate the Base on Alarm and Activate
the Base Prior to Alarm (Alert).
1. Start the Sounder/Relay Base Wizard by clicking on the Sounder/Relay Base Operation Wiz-
ard tab, which is located along the bottom left part of the Custom Control window.
2. Right-click in the blank area above the tabs. When the list of options appears, select Create
Point Group. A figure similar to Figure 9-18 appears.
Activate Base on Activate base on Alarm configures the single station detectors to activate when the alarm
Alarm threshold is reached and to turn off on either reset or silence.
1. To select this option, select the radio button labeled “Alarm—Activate Base on Alarm.”
2. If necessary, you can select a different Custom Control user program. To do this, click on the
control to the right of Program # and select the appropriate program number. Click Next to
continue.
9-15
4007ES Panel Programmer Manual (579-1167)
Activate Base on 3. A dialog similar to the following appears. Select the operation for the device as either “Hold
Alarm Device ON until Reset” (sounder or relay remains activated until reset) or “Hold Device on
until Silence” (sounder or relay remains activated until signal silence).
9-16
4007ES Panel Programmer Manual (579-1167)
Alert—Activate If you select the radio button labeled “Activate base prior to alarm,” the sounder or relay on
Base Prior to the single station detector activates when the detector passes a threshold below the alarm level.
Alarm 1. To select this option, select the radio button labeled “Alert—Activate Base Prior to
Alarm.”
2. If necessary, you can select a different Custom Control user program.To do this, click on the
control to the right of Program # and select the appropriate program number.
3. Press Next to continue.
9-17
4007ES Panel Programmer Manual (579-1167)
9-18
Chapter 10.
File Transfer
Introduction This chapter describes features associated with IP and USB File Transfer.
10-1
4007ES Panel Programmer Manual (579-1167)
IP File Transfer
IP File Transfer The IP file transfer operates exclusively over the Ethernet service port and provides a faster and
more fully featured file transfer. The files are directly copied to the file system and activated.
New Slave Exec data is then downloaded by the master once it is running.
File Transfer The Ethernet service port connects to the front panel Ethernet connection through a standard
Connection to the straight (non-crossover) Ethernet Patch Cable. The service technician should connect his PC to
PC the CPU card through this front panel connection with a standard straight Ethernet cable (see
Figure 10-2). If this connection is not available, you may plug directly into the CPU Card
connector J1 to the PC with a standard straight Ethernet cable.
Starting the IP This feature enables a user to download all Fire Alarm Control Panel (FACP) software features
File Transfer (Panel Exec, Slave Exec, etc.). All files are first downloaded to the Compact Flash Memory
Utility card on the Master Controller card before being activated. This provides a means for
recovering previous configurations (via the File Transfer “History/Undo” tab). It also allows
the FACP to continue operating during file download operation. FACP down-time is minimal.
This feature allows for file transfers speeds between 60 kbps and 100 kbps. Job configuration
files are typically between 1 MB and 2 MBs.
The ES Panel IP File Transfer utility can be started from within the ES Panel Programmer or
from the Windows Start menu. To start the File Transfer:
• From within the Programmer. While the programmer is already running, click on the
Transfer icon, located along the menu bar at the top of the programmer window. When
the options appear, click on Local Panel.
When either one of the start-up procedures has been completed, the File Transfer Utility
appears.
10-2
4007ES Panel Programmer Manual (579-1167)
IP File Transfer
IP Communication Click on the Settings button near the top of the IP File Transfer Window to access the Settings
Parameter Window. The settings window shows you the IP address the program is currently using and
Settings allows you to change it if necessary.
Downloadable The following types of files can be downloaded to the ES Panel FACP through its file transfer
Files utility.
• CFIG File. This is the built job file, consisting of all programming definitions in a
binary format, that the panel's CPU can execute.
• Slave Exec. Module-specific slave Exec files execute on intelligent slave modules
(listed below) and define the way in which the slave module operates. Occasionally,
changes to the functionality of a slave module may require you to download a new
slave Exec file. (For example, a change to the IDNet Slave Exec file may be necessary
to provide support for new, additional device types.) The following 4007ES modules
are “intelligent” slave devices that use a module-specific Slave Exec file.
- CFIG Text File. A panel with a missing or corrupt CFIG file can be restored to
proper operation by downloading a CFIG text file to the panel. The CFIG text file is
automatically built and placed in the same job directory as the “executable” CFIG
file (file ending in .CFG extension).
- Panel Exec (Master). The Panel Exec file is the “operating system” that runs on
the panel’s CPU module. It manages interactions between system components.
Occasionally, changes to the functionality of the operating system may require that a
new Panel Exec file be downloaded.
10-3
4007ES Panel Programmer Manual (579-1167)
Download Tab By default, the IP File Transfer window will open to the Download tab.
10-4
4007ES Panel Programmer Manual (579-1167)
Download Tab 1. To download a software feature, make sure the Service Mode (Jumper 7) is enabled and
select the type of file you want to download by clicking on the radio button next to the file
you want to download. The options are:
• CFIG and all Execs
• CFIG
• Slave Exec
• Panel Exec
• CPU Bootloader
• Primary Msglib
• Alternate Msglib
2. Once the selection has been made, use the checkboxes to select the download options:
• Download to a running panel: Select this option to download the file to a running
panel. Once this option is selected, there are 3 ways in which the changes can be
applied:
- Automatically after the download. Select the "Apply download changes after
download" box to have the downloaded changes applied immediately after the
download. This is the program’s default setting.
- When the system reboots: If the "Apply download changes after download"
button is not selected, the downloaded changes will be saved and applied once the
system is rebooted.
- When you click on the "activate changes on all network nodes" button. To use
this function, leave "Apply download changes after download" box unselected and
click on the button when you are ready to apply the changes. It is not necessary to
reboot when using this option. See the "Additional Download Tab Functions" sec-
tion below.
• Exclude the recovery file. This box option can be used when downloading a CFIG, it
will result in a faster download.
IMPORTANT: Checking this box will render job recovery impossible and will
create a trouble on the panel.
• Preserve current Install mode list: Select this box to keep all the points you have
placed in install mode in install mode once downloaded changes have been applied.
This is highly recommended.
3. Use the File name box to select the file you want to download to the panel.
4. Click on the Download button to start the process.
The following are additional functions accessible from the Download tab:
• View Final Status of Last Panel Update: Click on this button to bring up the final status of
the last panel update.
• Activate changes on all Network Nodes: Click on this button at any point to apply all
previously downloaded files.
Note: All inactive files, including job configuration files download via IP File Transfer and/or the serial file
transfer utility, will be applied when the button is clicked and the user confirms the activation.
10-5
4007ES Panel Programmer Manual (579-1167)
Upload/Reports The default option for this feature is to upload the job that is currently running in the FACP.
Tab The file that is uploaded is a compressed image of the programmer job file. Therefore, there is
no need for an “unbuild.” The file is uploaded to its default location.
(C:\4100UJOBS\JobName). This tab also has options for uploading all FACP reports. The
reports are uploaded to the “reports” subdirectory of the current job directory. The report file is
given a descriptive name, appended with the current date (e.g., AlarmLog_2010_3_11.txt).
10-6
4007ES Panel Programmer Manual (579-1167)
Type of Transfer In addition to the upload of the CFIG file, other types of information from the Panel can also be
uploaded to the ES Panel Programmer.
• TrueAlert Report: It is a report generated by the panel. It provides information such
as Point ID, Device Type, and Candela rating for all TrueAlert devices.
• TrueNAC Report: It is a report generated by the panel following the completion of a
TrueNAC diagnostic test. The report indicates all devices’ pass or fail status along
with nominal current, predicted worst case current and predicted worst case voltage
threshold at the minimum TPS operating voltage. Selecting this option allows one to
choose between downloading the report for All TrueAlert devices on all TPSs or only
for the Last TrueNAC diagnostics performed on a specific TPS and SLC.
• Panel Logs: It is a selection which allows one to select between uploading an Alarm
Log or the Trouble Log, produced as a result of Alarm or Trouble conditions reported
to the Control Panel, onto the ES Panel Programmer.
• TrueAlarm Status Report: A report providing the following information for each
point:
- Device Number
- Custom Label
- Current Sensitivity of the Point
- Point Status: Normal, Trouble, Alarm
- Almost Dirty Status: Points that are almost dirty have an asterisk in this field to
denote this status.
• TrueAlarm Service Report: A report providing the following information for each
point:
- Device Number
- Custom Label
- Alarm Level (sensitivity level of the device)
- Average Value
- Current Value
- Percent of Alarm: Shows the current value for the sensor. Value is shown as a
percentage of 100 percent (alarm). For example, if the value shown is 9%, it means
that the sensor is currently at 9% of the value required to trigger an alarm.
- Peak Value: Shows the highest value that the sensor has reached. Value is shown
as a percentage of 100 percent (alarm). For example, if the value shown is 9%, it
means that the peak value experienced by the sensor was 9% of the value required to
trigger an alarm.
- Current State: Possible values include Normal, Trouble, Dirty, Excessively Dirty,
and Almost Dirty.
• TrueAlarm CO Service Report: This report provides the following information
regarding the CO devices:
- Device Number (on the network)
- Custom Label (custom description of device)
- Current Device Value (PPM)
- End-of-Life Date
• Device Status (Normal, Trouble)
10-7
4007ES Panel Programmer Manual (579-1167)
Mass Storage Tab This feature allows a user to copy job related files to the 4100ES Master Controller Card’s
Compact Flash Memory. It also allows the user to copy files from the Panel to the PC and from
the PC to the Panel easily.
To use the Mass Storage:
1. Open the ES Programmer and perform a File Backup – creating an .SDC file. The .SDC file
is then stored in the Jobs folder.
2. Open File Transfer software and click the Mass Storage.
3. Browse the PC files or the panel files and select the appropriate .SDC file:
• The upper portion of the window displays the Panel files.
• The lower portion of the window displays the PC files.
4. Click the Copy FROM PC to copy a selected file from the PC to the Panel or click on Copy
TO PC to copy a selected file from the Panel to the PC.
5. Follow District Procedures for storing backup copies of job(s).
10-8
4007ES Panel Programmer Manual (579-1167)
History/Undo Tab Each time an FACP initializes, it checks versions of any active software (e.g., Panel Exec,
Slave Exec, CFIG). If a new software version is detected, a snapshot of the current configura-
tion is taken. File Transfer software retrieves the FACP snapshots and displays a list of the
configuration snapshots within the History/Undo tab. You can manage the number of snapshots
– with a limit of 1 GB available memory.
By selecting a snapshot from the list, the user is shown an overview of the differences from the
active configuration. For a detailed description of job configuration changes, the user has the
option of uploading the job configurations and automatically running the Compare utility. An
option also exists to restore the FACP to any of the listed snapshots.
10-9
Chapter 11.
Port Vectoring
Introduction The term port vectoring refers to the way in which certain cards can be programmed to output
only specific groups of events. This section describes programming the ES Panel's port
vectoring option.
Note: User editing of the DACT port vectoring is not permitted in UL 864.
11-1
Chapter 12.
AMON Point Type
Introduction This chapter describes creating custom point types (referred to as AMON point types) for use
with analog monitor ZAMs. These point types allow descriptive text and device-specific
settings to be associated with a point name.
AMON Pt Type The AMON Pt Type tab (Figure 12-1) is for use only with IDNET analog monitor ZAMs. It
Tab allows you to create a custom point type that specifies how the ES Panel system should
interpret (i.e., react to) incoming analog data from the device attached to the ZAM. This point
type can then be assigned to the ZAM using the IDNET point editing screen, which is
accessible through either the Hardware or Point tab. For example, if you have an analog
device that measures the amount of liquid within a tank, you can use this tab to create a point
type that specifies what the unit of measurement is (gallons, for example) and what the
threshold value(s) for an alarm should be (generate an alarm when the tank is half empty, for
example).
12-1
4007ES Panel Programmer Manual (579-1167)
Adding a Point The AMON Point Type Tab uses a wizard-style interface that guides you through the process
Type of creating an AMON point type.
1. To start this wizard, right-click in the blank space just below the Point. When the menu
appears, click on Add. A dialog similar to the one shown in Figure 12-3 appears.
FIRE Causes the system to generate a fire alarm when the device crosses the
threshold.
Creates a latching supervisory condition when the device crosses the
LATSUPV threshold. This means that the supervisory condition on the panel does
not clear until the point restores to normal and a system reset is
performed.
MPR12 Generates a priority 2 alarm when the device crosses the threshold.
12-2
4007ES Panel Programmer Manual (579-1167)
Adding a Point 3. Click the Next button to view the dialog shown in Figure 12-3.
Type
Field Description
The “unit” (ppm, gal, psi, etc.) text that appears on the front panel display
Eng Unit Text when you display the current value of the device via the front panel. For
example, if a monitor device with a monitoring capability of parts per
million is attached to the ZAM, you might put ppm in this field.
4mA Value This is the lowest value that the device reports. When the device is at this
value, it draws 4mA of current from the ZAM.
20mA Value This is the highest value that the device reports. When the device is at
this value, it draws 20mA of current from the ZAM.
5. Click the Next button. A dialog similar to the one shown in Figure 12-4 appears.
12-3
4007ES Panel Programmer Manual (579-1167)
12-4
579-1167
Rev. A
© 2014 Tyco Fire Protection Products. Specifications and other information were current as of publication and are subject to change without notice.