Load Schedule: Proposed Two-Storey Residence
Load Schedule: Proposed Two-Storey Residence
2-2.0mmØ IN 20mmØ 5 6 5 6
12 C.O. 10 2,000 8.70 20 15A 20A 30A 30A
2-5.5mm² + 1-1.6mmØ 7 8 7 8
13 RANGE 1 3,500 15.22 30 20A 20A 30A 30A
IN 25mmØ
2-5.5mm² + 1-1.6mmØ
9 10 9 10
14 REF 1 1,200 5.21 30 20A 20A 30A 30A
IN 25mmØ
11 12 11 12
30A 30A 30A SPARE
15 SPARE 1 1,000 4.35
13 14 13 14
SPARE SPARE SPACE SPACE
16 SPARE 1 1,000 4.35
15 16 15 16
TO GROUND LINE
TO GROUND LINE
LPP ACCP
TOTAL 33,438
LOAD SCHEDULE
PROTECTOR: 175A, 230V, 100AF, 2-POLE, BOLT-IN TYPE
ACCP BRANCHES: PLUGGED-IN TYPE
SERVICE
NO. OF NO. OF TOTAL CKT. BREAKER FENCE
CKT. DESCRIPTION LTS. OUTLET AMPS VOLTS * WIRE & CONDUIT SIZE (PVC) ENTRANCE
WATTS AT AF P
2-5.5mm² + 1-1.6mmØ
1 ACU - 1 (1.5HP) 1 2,760 12 230 30 50 2P IN 25mmØ
GROUND WIRE
11 HEATER-3 1 3,500 15.22 63 mm² BARE
COPPER WIRE
12 HEATER-4 1 3,500 15.22
15 SPACE
PANEL BOARD SCHEDULE
16 SPACE
TOTAL 40,580
NOTE & SPECIFICATIONS:
I PPAC 1. ALL ELECTRICAL WORK TO BE DONE SHALL CONFORM TO THE PROVISIONS
PROTECTOR: 175A, 230V, 100AF, BOLT-ON CB
OF THE LATEST EDITION OF THE N.E.C. INCLUDING ORDINANCE OF THE CITY
& MERALCO REQUIREMENTS.
USE: 2-60 mm² THHN
1-30 mm² THHN } IN 63mmØ PVC 2. SERVICE ENTRANCE SHALL BE 230V SINGLE PHASE 2 WIRE 60 Hz.
LOAD SCHEDULE 3. SERVICE ENTRANCE SHALL BE IN RIGID STEEL CONDUIT LOCAL BRAND.
4. BRANCH CIRCUIT WIRING SHALL BE ENTIRELY IN PVC CONDUITS EITHER
PROTECTOR:275A, 230V, 300AF, 2-POLE, BOLT-IN TYPE EXPOSED OR CONCEALED AND SHALL NOT BE SMALLER THAN 12" CONDUIT.
MPB BRANCHES: PLUGGED-IN TYPE