SM6
QM, QMC , PM Cubicles
Fuse-Load Break Switch Combination Unit up to 24 kV
QM QMC
Introduction Basic Equipment SM6 units meet all the following
standards and specifications:
- IEC standards
QM, QMC and PM are part of SM6 product range. * SF6 Functional load break switch
- UTE standards for SM6-24
and earthing switch
- EDF specifications for SM6-24
This SM6 range is made up of modular units * Three phase busbar 630 A
- SEISMIC standards for 24 kV
and used for the MV/LV substation in * CI1 operating mechanism (QM & QMC)
secondary distribution system up to 24 kV * CIT operation mechanism (PM) IEC standards
* Three fuses (PM) 62271-200 ,62271-1, 62271-103, 62271-
* Three striker fuses (QM & QMC) 105, 62271-100, 62271-102, 61869-2,
* Mechanical indication for blown fuses (QM 61869-3, 60044-8, 62271-206, 62271-304
Application & QMC)
* Voltage presence indicators SEISMIC standards for 24kV
QM is a fuse load break switch combination unit with * Downstream earthing switch - IEEE-693 2005
striker fuses mechanism (a blown fuse the switch to * Heater 50 W, 220V - EN600068-3-3 1993
open). It can be used for transformer protection, cable - Three current transformers (QMC)
protection, etc. UTE standards for 24 kV
Condition Monitoring NFC 13.100
NFC 13.200
QMC is similar to QM but equipped with three CT’s for * Basic : thermal sensors (TH110)
NFC 64.130
metering or protection purposes. * Option : humidity sensors (CL110)
NFC 64.160
PM is a fuse load break switch without striker fuses Option EDF specifications for 24 kV
Mechanism.
HN 64-S-41
This QM, QMC or PM is normally together in the system * Motor for operating mechanism * visibility of main contacts
HN 64-S-43
with other parts of SM6 product range such as IM, IMC, * key-type interlocks * pressure indicator device
CM, DM1, DM2, etc., in accordance with the design * auxiliary contacts * digital ammeter
Colour
of a distribution system * auxiliary contact for blown fuses * arc detection
White RAL 9003
* release units (coil)
MV prefabricated equipment
SM6
QM, QMC, PM Cubicles
Electrical characteristics
MV prefabricated equipment
SM6
QM, QMC, PM Cubicles
Normal operating conditions Protection index:
• Ambient air temperature: • Classes: PI (insulating partition)
1) less than or equal to 40°C • Loss of service continuity classes: LSC2A (LSC1 for metering GAM/GBM functions)
2) less than or equal to 35°C on average over 24 hours • Units in switchboard: IP3X
3) greater or equal to –5°C. • Between compartments: IP2X for SM6-24, IP2XC for SM6-36
• Altitude • Cubicle: IK08 for SM6-24, IK07 for SM6-36.
1) less than or equal to 1000 m
2) above 1000 m, a derating coefficient is applied (please consult us). Electro-magnetic compatibility:
• Solar radiation • Relays: 4 kV withstand capacity, as per recommendation IEC 60801.4
1) no solar radiation influence is permitted. • Compartments:
• Ambient air pollution electrical field:
1) no significant pollution by dust, smoke, corrosive and/or flammable gases, -- 40 dB attenuation at 100 MHz
vapours or salt. -- 20 dB attenuation at 200 MHz
• Humidity magnetic field: 20 dB attenuation below 30 MHz.
1) average relative humidity over a 24 hour period, less than or equal to 95% • According to standards IEEE-693/2005 and EN 60068-3/1993
2) average relative humidity over a 1 month period, less than or equal to 90% for 36 kV (please contact us).
3) average vapor pressure over a 24 hour period, less than or equal to 2.2 kPa
4) average vapor pressure over a 1 month period, less than or equal to 1.8 kPa. Temperatures:
For these conditions, condensation may occasionally occur. Condensation can be The cubicles must be stored and installed in a dry area
expected where sudden temperature changes occur in periods of high humidity. free from dust and with limited temperature variations.
To withstand the effects of high humidity and condensation, such as breakdown of • For stocking: from -40°C to +70°C
insulation, please pay attention on Civil Engineering recommendations for design • For working: from -5°C to +40°C
of the building or housing, by suitable ventilation and installation. • Other temperatures, consult us.
• Seismic (for 24 Kv and 36 kV): • Seismic:
1) Up to 0.5 g (horizontal) and 0.4 g (vertical) for 24 kV (option):
2) Class 2 for 24 kV and Class 1 for 36kV 1) Up to 0.5 g (horizontal) and 0.4 g (vertical)
3) According to standards IEEE-693/2005 and EN 60068-3/1993 for the 24 kV and 2) Class 2
36 kV
MV prefabricated equipment
SM6
QM, QMC, PM Cubicles
Safety of people
By internal arc protection
Standard IEC 62271-200 appendix
A indicates a method for testing
switchgear in metal enclosures
under internal arc conditions. The
aim of this test is to show that
an operator situated in front of a
switchboard would be protected
against the effects of an internal
fault.