Cooling Only
MFL67986329
2
Single Indoor Unit
1. ABNQ21GM1T6
2. ABNQ28GM1T6
3. ABNQ34GM3T6
4. ABNQ40GM3T6
5. ABNQ55GM3T6
6. ABNQ60GM3T6
7. ABNQ60LM3T6
8. APNQ55GT3E6
9. APNQ55GT3M6
10. ATNQ21GPLT6
11. ATNQ28GPLT6
12. ATNQ34GNLT6
13. ATNQ40GNLT6
14. ATNQ55GMLT6
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
ABNQ21GM1T6
1.
1. ABNQ21GM1T6
1.1 Specifications
Category
Unit Value
Major Minor
Classification Chassis - M1
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
kW 4.74
Cooling Capacity Nominal
Btu/h 16,200
kW -
Heating Capacity Nominal
Btu/h -
Power Input(Indoor) H/M/L W -
Running Current(Indoor) H/M/L A -
Type - Sirocco Fan
Air Flow Rate((SH)/H/M/L) m³/min - / 16.5 / 14.5 / 13.0
Indoor Fan
Air Flow Rate Range(Min~Max) m³/min 10.4~21.5
External Static Pressure_Factory Set Pa 6
Type - BLDC
Drive - -
Indoor Fan Motor
W 136.5
Output
No. 1
Rows x Columns x FPI - 2 x 13 x 18
Heat Exchanger No. - 1
Face Area m² 0.21
Net(W x H x D) mm 900 x 270 x 700
Dimensions
Shipping(W x H x D) mm 1,100 x 338 x 773
Net kg 23.8
Weight
Shipping kg 28.9
Color - Steel Gray
Exterior
RAL (Classic) - -
Air Filter Type - Long Life
Fuse - O
Protection Device
Overload Protector for Fan Motor - -
Type - R410A
Refrigerant
Control Type - EEV
Drain Pipe(Natural Drainage) O.D / I.D mm(inch) 25.4/20.4
Drain Pipe(Drain Pump) O.D / I.D mm(inch) 32/25
Liquid mm(inch) Φ6.35 (1/4)
Gas mm(inch) Φ12.7 (1/2)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Cooling ((SH)/H/M/L) dB(A) - / 34.0 / 32.0 / 30.0
Sound Pressure Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) -
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Cooling ((SH)/H/M/L) dB(A) -
Sound Power Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power and Communication cable(H07RN-F) mm² × cores 0.75 x 4C
Power Supply Type to Indoor - - -
Maximum Fuse Amperes (MFA) A 15
Electrical Characteristic
Indoor Fan Motor_Full Load Amperes (FLA) A 1.6
4
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
1. ABNQ21GM1T6
Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national code. And “Electric characteristics” should be considered for electrical work and design.
■ Especially the power cable and circuit breaker should be selected in accordance with that.
■ Sound Level Values are measured at Noise Measuring chamber accordance with standard. Therefore, these values depend on the ambient conditions and
values are normally higher in actual operation.
5
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
1. ABNQ21GM1T6
Note
■ O : Applied, X : Not applied, Embedded : Included with product.
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.
■ Some functions can be limited by remote controller.
■ Selecting a wireless remote controller in case of ducted type indoor units requires either a connection to the wired remote controller (Standard II)
or an IR receiver accessory to be connected to the duct in order to receive the signal.
■ 'Auto Mode' varies depending on the outdoor unit type.
- Auto Change Over(Single Heat Pump Outdoor Unit)
- Auto Mode Select(Multi Heat Pump Outdoor Unit)
- Auto Intensity Control(Cooling Only Outdoor Unit)
■ * : These functions need to connect the wired remote controller.
■ ** : It is included by default when the product is manufactured.
■ *** : This functions need to connect to the Standard III wired remote controller.
6
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
1. ABNQ21GM1T6
Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant, Embedded : Included with product.
■ If there is a difference in development time between the product and the remote controller, some functions cannot be operated.
■ Selecting a wireless remote controller in case of ducted type indoor units requires either a connection to the wired remote controller (Standard II)
or an IR receiver accessory to be connected to the duct in order to receive the signal.
■ If you need more detail, please refer to the BECON PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
7
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
1. ABNQ21GM1T6
1.4 Dimensions
1.4.1 Product
8
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
1. ABNQ21GM1T6
1.4.2 Install Space
Top view
[Unit: mm(inch)]
Air inlet vents
≥ 1,000 (39-3/8)
≥ 600 x 600 Inspection hole(1)
(23-5/8) (23-5/8)
(23-5/8 x 23-5/8) Air outlet vents 600 x 600
(23-5/8 x 23-5/8)
Front
If distance between false ceiling and actual ceiling is more than 100cm (39-3/8 inch), the number of inspection hole
could be decreased to 1. But if that is less than 20cm (7-7/8 inch), the hole size should be more than size of Indoor Unit.
Front view
[Unit: mm(inch)]
≥ 20 (25/32)
Ceiling
B(Min)
A(Min) Service Space
Note
■ Places where products are installed should not be any obstacles to the air circulation or installation. Ensure the spaces from the wall, ceiling,
or other obstacles.
■ According to type of indoor unit, external appearance or installed structure could be different.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.
9
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
1. ABNQ21GM1T6
Thermistor for
evaporator inlet
temperature
10
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
1. ABNQ21GM1T6
11
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
1. ABNQ21GM1T6
70
Octave Band Sound Pressure Level (0dB = 20μPa)
NC-65
60
NC-60
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
NC-25
20
Approximate
NC-20
Hearing
Threshold
NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)
Note
■ Sound measured at some distance away from the center of the unit.
■ Data is valid at free field condition.
■ Reference accoustic pressure 0dB = 20μPa.
■ Data is valid at nominal operation condition. Refer to the Model Specifications for nominal conditions (Power source and Ambient temperature, etc)
■ Sound levels can be increased in accordance with installation and operating conditions.
(Static pressure mode, used air guide, Room target temperature setting, etc)
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
12
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
1. ABNQ21GM1T6
Note
■ Each dash line represents for each 100 RPM step
■ If operation range is out of auto E.S.P setting range, air flow rate should be adjusted manually by wired remotecontroller. (ESP Set Value = RPM / 10)
For more information, please see the installation manual.
■ The above P-Q Curve shows available E.S.P. range. If the E.S.P value is out of min/max RPM at desired air flow, indoor components could be failed
and performance would be decreased.
■ Automatic constant air volume is a function that controls air volume automatically when installation, and the air volume is not set automatically
during operation.
13
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
ABNQ28GM1T6
2.
2. ABNQ28GM1T6
2.1 Specifications
Category
Unit Value
Major Minor
Classification Chassis - M1
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
kW 6.27
Cooling Capacity Nominal
Btu/h 21,400
kW -
Heating Capacity Nominal
Btu/h -
Power Input(Indoor) H/M/L W -
Running Current(Indoor) H/M/L A -
Type - Sirocco Fan
Air Flow Rate((SH)/H/M/L) m³/min - / 18.0 / 16.5 / 14.5
Indoor Fan
Air Flow Rate Range(Min~Max) m³/min 11.6~23.4
External Static Pressure_Factory Set Pa 6
Type - BLDC
Drive - -
Indoor Fan Motor
W 136.5
Output
No. 1
Rows x Columns x FPI - 3 x 13 x18
Heat Exchanger No. - 1
Face Area m² 0.21
Net(W x H x D) mm 900 x 270 x 700
Dimensions
Shipping(W x H x D) mm 1,100 x 338 x 773
Net kg 25.3
Weight
Shipping kg 30.3
Color - Steel Gray
Exterior
RAL (Classic) - -
Air Filter Type - Long Life
Fuse - O
Protection Device
Overload Protector for Fan Motor - -
Type - R410A
Refrigerant
Control Type - EEV
Drain Pipe(Natural Drainage) O.D / I.D mm(inch) 25.4/20.4
Drain Pipe(Drain Pump) O.D / I.D mm(inch) 32/25
Liquid mm(inch) Φ9.52 (3/8)
Gas mm(inch) Φ15.88 (5/8)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Cooling ((SH)/H/M/L) dB(A) - / 37.0 / 35.0 / 32.0
Sound Pressure Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) -
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Cooling ((SH)/H/M/L) dB(A) -
Sound Power Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power and Communication cable(H07RN-F) mm² × cores 0.75 x 4C
Power Supply Type to Indoor - - -
Maximum Fuse Amperes (MFA) A 25
Electrical Characteristic
Indoor Fan Motor_Full Load Amperes (FLA) A 1.6
14
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
2. ABNQ28GM1T6
Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national code. And “Electric characteristics” should be considered for electrical work and design.
■ Especially the power cable and circuit breaker should be selected in accordance with that.
■ Sound Level Values are measured at Noise Measuring chamber accordance with standard. Therefore, these values depend on the ambient conditions and
values are normally higher in actual operation.
15
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
2. ABNQ28GM1T6
Note
■ O : Applied, X : Not applied, Embedded : Included with product.
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.
■ Some functions can be limited by remote controller.
■ Selecting a wireless remote controller in case of ducted type indoor units requires either a connection to the wired remote controller (Standard II)
or an IR receiver accessory to be connected to the duct in order to receive the signal.
■ 'Auto Mode' varies depending on the outdoor unit type.
- Auto Change Over(Single Heat Pump Outdoor Unit)
- Auto Mode Select(Multi Heat Pump Outdoor Unit)
- Auto Intensity Control(Cooling Only Outdoor Unit)
■ * : These functions need to connect the wired remote controller.
■ ** : It is included by default when the product is manufactured.
■ *** : This functions need to connect to the Standard III wired remote controller.
16
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
2. ABNQ28GM1T6
Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant, Embedded : Included with product.
■ If there is a difference in development time between the product and the remote controller, some functions cannot be operated.
■ Selecting a wireless remote controller in case of ducted type indoor units requires either a connection to the wired remote controller (Standard II)
or an IR receiver accessory to be connected to the duct in order to receive the signal.
■ If you need more detail, please refer to the BECON PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
17
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
2. ABNQ28GM1T6
2.4 Dimensions
2.4.1 Product
18
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
2. ABNQ28GM1T6
2.4.2 Install Space
Top view
[Unit: mm(inch)]
Air inlet vents
≥ 1,000 (39-3/8)
≥ 600 x 600 Inspection hole(1)
(23-5/8) (23-5/8)
(23-5/8 x 23-5/8) Air outlet vents 600 x 600
(23-5/8 x 23-5/8)
Front
If distance between false ceiling and actual ceiling is more than 100cm (39-3/8 inch), the number of inspection hole
could be decreased to 1. But if that is less than 20cm (7-7/8 inch), the hole size should be more than size of Indoor Unit.
Front view
[Unit: mm(inch)]
≥ 20 (25/32)
Ceiling
B(Min)
A(Min) Service Space
Note
■ Places where products are installed should not be any obstacles to the air circulation or installation. Ensure the spaces from the wall, ceiling,
or other obstacles.
■ According to type of indoor unit, external appearance or installed structure could be different.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.
19
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
2. ABNQ28GM1T6
Thermistor for
evaporator inlet
temperature
20
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
2. ABNQ28GM1T6
21
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
2. ABNQ28GM1T6
70
Octave Band Sound Pressure Level (0dB = 20μPa)
NC-65
60
NC-60
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
NC-25
20
Approximate
NC-20
Hearing
Threshold
NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)
Note
■ Sound measured at some distance away from the center of the unit.
■ Data is valid at free field condition.
■ Reference accoustic pressure 0dB = 20μPa.
■ Data is valid at nominal operation condition. Refer to the Model Specifications for nominal conditions (Power source and Ambient temperature, etc)
■ Sound levels can be increased in accordance with installation and operating conditions.
(Static pressure mode, used air guide, Room target temperature setting, etc)
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
22
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
2. ABNQ28GM1T6
Note
■ Each dash line represents for each 100 RPM step
■ If operation range is out of auto E.S.P setting range, air flow rate should be adjusted manually by wired remotecontroller. (ESP Set Value = RPM / 10)
For more information, please see the installation manual.
■ The above P-Q Curve shows available E.S.P. range. If the E.S.P value is out of min/max RPM at desired air flow, indoor components could be failed
and performance would be decreased.
■ Automatic constant air volume is a function that controls air volume automatically when installation, and the air volume is not set automatically
during operation.
23
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
ABNQ34GM3T6
3.
3. ABNQ34GM3T6
3.1 Specifications
Category
Unit Value
Major Minor
Classification Chassis - M3
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
kW 7.75
Cooling Capacity Nominal
Btu/h 26,400
kW -
Heating Capacity Nominal
Btu/h -
Power Input(Indoor) H/M/L W -
Running Current(Indoor) H/M/L A -
Type - Sirocco
Air Flow Rate((SH)/H/M/L) m³/min - / 30.0 / 25.0 / 20.0
Indoor Fan
Air Flow Rate Range(Min~Max) m³/min 16.0~39.0
External Static Pressure_Factory Set Pa 6
Type - BLDC
Drive - -
Indoor Fan Motor
W 154
Output
No. 1
Rows x Columns x FPI - 3x16x18
Heat Exchanger No. - 1
Face Area m² 0.32
Net(W x H x D) mm 1,250 x 360 x 700
Dimensions
Shipping(W x H x D) mm 1,450 x 428 x 773
Net kg 37.1
Weight
Shipping kg 42.8
Color - Steel Gray
Exterior
RAL (Classic) - -
Air Filter Type - Long Life
Fuse - O
Protection Device
Overload Protector for Fan Motor - -
Type - R410A
Refrigerant
Control Type - EEV
Drain Pipe(Natural Drainage) O.D / I.D mm(inch) 25.4/20.4
Drain Pipe(Drain Pump) O.D / I.D mm(inch) 32/25
Liquid mm(inch) Φ9.52 (3/8)
Gas mm(inch) Φ15.88 (5/8)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Cooling ((SH)/H/M/L) dB(A) - / 36.0 / 33.0 / 31.0
Sound Pressure Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) -
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Cooling ((SH)/H/M/L) dB(A) -
Sound Power Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power and Communication cable(H07RN-F) mm² × cores 0.75 x 4
Power Supply Type to Indoor - - -
Maximum Fuse Amperes (MFA) A 25
Electrical Characteristic
Indoor Fan Motor_Full Load Amperes (FLA) A 1.9
24
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
3. ABNQ34GM3T6
Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national code. And “Electric characteristics” should be considered for electrical work and design.
■ Especially the power cable and circuit breaker should be selected in accordance with that.
■ Sound Level Values are measured at Noise Measuring chamber accordance with standard. Therefore, these values depend on the ambient conditions and
values are normally higher in actual operation.
25
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
3. ABNQ34GM3T6
Note
■ O : Applied, X : Not applied, Embedded : Included with product.
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.
■ Some functions can be limited by remote controller.
■ Selecting a wireless remote controller in case of ducted type indoor units requires either a connection to the wired remote controller (Standard II)
or an IR receiver accessory to be connected to the duct in order to receive the signal.
■ 'Auto Mode' varies depending on the outdoor unit type.
- Auto Change Over(Single Heat Pump Outdoor Unit)
- Auto Mode Select(Multi Heat Pump Outdoor Unit)
- Auto Intensity Control(Cooling Only Outdoor Unit)
■ * : These functions need to connect the wired remote controller.
■ ** : It is included by default when the product is manufactured.
■ *** : This functions need to connect to the Standard III wired remote controller.
26
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
3. ABNQ34GM3T6
Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant, Embedded : Included with product.
■ If there is a difference in development time between the product and the remote controller, some functions cannot be operated.
■ Selecting a wireless remote controller in case of ducted type indoor units requires either a connection to the wired remote controller (Standard II)
or an IR receiver accessory to be connected to the duct in order to receive the signal.
■ If you need more detail, please refer to the BECON PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
27
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
3. ABNQ34GM3T6
3.4 Dimensions
3.4.1 Product
DWG No. : TBB36535401_rev01
Chassis Code : M3
28
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
3. ABNQ34GM3T6
3.4.2 Install Space
Top view
[Unit: mm(inch)]
Air inlet vents
≥ 1,000 (39-3/8)
≥ 600 x 600 Inspection hole(1)
(23-5/8) (23-5/8)
(23-5/8 x 23-5/8) Air outlet vents 600 x 600
(23-5/8 x 23-5/8)
Front
If distance between false ceiling and actual ceiling is more than 100cm (39-3/8 inch), the number of inspection hole
could be decreased to 1. But if that is less than 20cm (7-7/8 inch), the hole size should be more than size of Indoor Unit.
Front view
[Unit: mm(inch)]
≥ 20 (25/32)
Ceiling
B(Min)
A(Min) Service Space
Note
■ Places where products are installed should not be any obstacles to the air circulation or installation. Ensure the spaces from the wall, ceiling,
or other obstacles.
■ According to type of indoor unit, external appearance or installed structure could be different.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.
29
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
3. ABNQ34GM3T6
Thermistor for
evaporator inlet
temperature
30
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
3. ABNQ34GM3T6
31
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
3. ABNQ34GM3T6
70
Octave Band Sound Pressure Level (0dB = 20μPa)
NC-65
60
NC-60
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
NC-25
20
Approximate
NC-20
Hearing
Threshold
NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)
Note
■ Sound measured at some distance away from the center of the unit.
■ Data is valid at free field condition.
■ Reference accoustic pressure 0dB = 20μPa.
■ Data is valid at nominal operation condition. Refer to the Model Specifications for nominal conditions (Power source and Ambient temperature, etc)
■ Sound levels can be increased in accordance with installation and operating conditions.
(Static pressure mode, used air guide, Room target temperature setting, etc)
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
32
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
3. ABNQ34GM3T6
Note
■ Each dash line represents for each 100 RPM step
■ If operation range is out of auto E.S.P setting range, air flow rate should be adjusted manually by wired remotecontroller. (ESP Set Value = RPM / 10)
For more information, please see the installation manual.
■ The above P-Q Curve shows available E.S.P. range. If the E.S.P value is out of min/max RPM at desired air flow, indoor components could be failed
and performance would be decreased.
■ Automatic constant air volume is a function that controls air volume automatically when installation, and the air volume is not set automatically
during operation.
33
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
ABNQ40GM3T6
4.
4. ABNQ40GM3T6
4.1 Specifications
Category
Unit Value
Major Minor
Classification Chassis - M3
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
kW 9.95
Cooling Capacity Nominal
Btu/h 34,000
kW -
Heating Capacity Nominal
Btu/h -
Power Input(Indoor) H/M/L W -
Running Current(Indoor) H/M/L A -
Type - Sirocco Fan
Air Flow Rate((SH)/H/M/L) m³/min - / 30.0 / 25.0 / 20.0
Indoor Fan
Air Flow Rate Range(Min~Max) m³/min 16.0~39.0
External Static Pressure_Factory Set Pa 6
Type - BLDC
Drive - -
Indoor Fan Motor
W 154
Output
No. 1
Rows x Columns x FPI - 3 x 16 x 18
Heat Exchanger No. - 1
Face Area m² 0.32
Net(W x H x D) mm 1,250 x 360 x 700
Dimensions
Shipping(W x H x D) mm 1,450 x 428 x 773
Net kg 37.1
Weight
Shipping kg 42.8
Color - Steel Gray
Exterior
RAL (Classic) - -
Air Filter Type - Long Life
Fuse - O
Protection Device
Overload Protector for Fan Motor - -
Type - R410A
Refrigerant
Control Type - EEV
Drain Pipe(Natural Drainage) O.D / I.D mm(inch) 25.4/20.4
Drain Pipe(Drain Pump) O.D / I.D mm(inch) 32/25
Liquid mm(inch) Φ9.52 (3/8)
Gas mm(inch) Φ15.88 (5/8)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Cooling ((SH)/H/M/L) dB(A) - / 36.0 / 33.0 / 31.0
Sound Pressure Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) -
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Cooling ((SH)/H/M/L) dB(A) -
Sound Power Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power and Communication cable(H07RN-F) mm² × cores 0.75 x 4C
Power Supply Type to Indoor - - -
Maximum Fuse Amperes (MFA) A 25
Electrical Characteristic
Indoor Fan Motor_Full Load Amperes (FLA) A 1.9
34
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
4. ABNQ40GM3T6
Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national code. And “Electric characteristics” should be considered for electrical work and design.
■ Especially the power cable and circuit breaker should be selected in accordance with that.
■ Sound Level Values are measured at Noise Measuring chamber accordance with standard. Therefore, these values depend on the ambient conditions and
values are normally higher in actual operation.
35
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
4. ABNQ40GM3T6
Note
■ O : Applied, X : Not applied, Embedded : Included with product.
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.
■ Some functions can be limited by remote controller.
■ Selecting a wireless remote controller in case of ducted type indoor units requires either a connection to the wired remote controller (Standard II)
or an IR receiver accessory to be connected to the duct in order to receive the signal.
■ 'Auto Mode' varies depending on the outdoor unit type.
- Auto Change Over(Single Heat Pump Outdoor Unit)
- Auto Mode Select(Multi Heat Pump Outdoor Unit)
- Auto Intensity Control(Cooling Only Outdoor Unit)
■ * : These functions need to connect the wired remote controller.
■ ** : It is included by default when the product is manufactured.
■ *** : This functions need to connect to the Standard III wired remote controller.
36
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
4. ABNQ40GM3T6
Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant, Embedded : Included with product.
■ If there is a difference in development time between the product and the remote controller, some functions cannot be operated.
■ Selecting a wireless remote controller in case of ducted type indoor units requires either a connection to the wired remote controller (Standard II)
or an IR receiver accessory to be connected to the duct in order to receive the signal.
■ If you need more detail, please refer to the BECON PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
37
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
4. ABNQ40GM3T6
4.4 Dimensions
4.4.1 Product
DWG No. : TBB36535401_rev01
Chassis Code : M3
38
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
4. ABNQ40GM3T6
4.4.2 Install Space
Top view
[Unit: mm(inch)]
Air inlet vents
≥ 1,000 (39-3/8)
≥ 600 x 600 Inspection hole(1)
(23-5/8) (23-5/8)
(23-5/8 x 23-5/8) Air outlet vents 600 x 600
(23-5/8 x 23-5/8)
Front
If distance between false ceiling and actual ceiling is more than 100cm (39-3/8 inch), the number of inspection hole
could be decreased to 1. But if that is less than 20cm (7-7/8 inch), the hole size should be more than size of Indoor Unit.
Front view
[Unit: mm(inch)]
≥ 20 (25/32)
Ceiling
B(Min)
A(Min) Service Space
Note
■ Places where products are installed should not be any obstacles to the air circulation or installation. Ensure the spaces from the wall, ceiling,
or other obstacles.
■ According to type of indoor unit, external appearance or installed structure could be different.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.
39
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
4. ABNQ40GM3T6
Thermistor for
evaporator inlet
temperature
40
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
4. ABNQ40GM3T6
41
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
4. ABNQ40GM3T6
70
Octave Band Sound Pressure Level (0dB = 20μPa)
NC-65
60
NC-60
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
NC-25
20
Approximate
NC-20
Hearing
Threshold
NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)
Note
■ Sound measured at some distance away from the center of the unit.
■ Data is valid at free field condition.
■ Reference accoustic pressure 0dB = 20μPa.
■ Data is valid at nominal operation condition. Refer to the Model Specifications for nominal conditions (Power source and Ambient temperature, etc)
■ Sound levels can be increased in accordance with installation and operating conditions.
(Static pressure mode, used air guide, Room target temperature setting, etc)
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
42
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
4. ABNQ40GM3T6
Note
■ Each dash line represents for each 100 RPM step
■ If operation range is out of auto E.S.P setting range, air flow rate should be adjusted manually by wired remotecontroller. (ESP Set Value = RPM / 10)
For more information, please see the installation manual.
■ The above P-Q Curve shows available E.S.P. range. If the E.S.P value is out of min/max RPM at desired air flow, indoor components could be failed
and performance would be decreased.
■ Automatic constant air volume is a function that controls air volume automatically when installation, and the air volume is not set automatically
during operation.
43
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
ABNQ55GM3T6
5.
5. ABNQ55GM3T6
5.1 Specifications
Category
Unit Value
Major Minor
Classification Chassis - M3
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
kW 13.75
Cooling Capacity Nominal
Btu/h 47,000
kW -
Heating Capacity Nominal
Btu/h -
Power Input(Indoor) H/M/L W -
Running Current(Indoor) H/M/L A -
Type - Sirocco Fan
Air Flow Rate((SH)/H/M/L) m³/min - / 38.0 / 32.0 / 26.0
Indoor Fan
Air Flow Rate Range(Min~Max) m³/min 20.8~49.4
External Static Pressure_Factory Set Pa 6
Type - BLDC
Drive - -
Indoor Fan Motor
W 400
Output
No. 1
Rows x Columns x FPI - 3 x 16 x 18
Heat Exchanger No. - 1
Face Area m² 0.32
Net(W x H x D) mm 1,250 x 360 x 700
Dimensions
Shipping(W x H x D) mm 1,450 x 428 x 773
Net kg 43.0
Weight
Shipping kg 48.3
Color - Steel Gray
Exterior
RAL (Classic) - -
Air Filter Type - Long Life
Fuse - O
Protection Device
Overload Protector for Fan Motor - -
Type - R410A
Refrigerant
Control Type - EEV
Drain Pipe(Natural Drainage) O.D / I.D mm(inch) 25.4/20.4
Drain Pipe(Drain Pump) O.D / I.D mm(inch) 32/25
Liquid mm(inch) Φ9.52 (3/8)
Gas mm(inch) Φ19.05 (3/4)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Cooling ((SH)/H/M/L) dB(A) - / 38.0 / 36.0 / 34.0
Sound Pressure Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) -
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Cooling ((SH)/H/M/L) dB(A) -
Sound Power Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power and Communication cable(H07RN-F) mm² × cores 0.75 x 4C
Power Supply Type to Indoor - - -
Maximum Fuse Amperes (MFA) A 40
Electrical Characteristic
Indoor Fan Motor_Full Load Amperes (FLA) A 2.4
44
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
5. ABNQ55GM3T6
Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national code. And “Electric characteristics” should be considered for electrical work and design.
■ Especially the power cable and circuit breaker should be selected in accordance with that.
■ Sound Level Values are measured at Noise Measuring chamber accordance with standard. Therefore, these values depend on the ambient conditions and
values are normally higher in actual operation.
45
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
5. ABNQ55GM3T6
Note
■ O : Applied, X : Not applied, Embedded : Included with product.
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.
■ Some functions can be limited by remote controller.
■ Selecting a wireless remote controller in case of ducted type indoor units requires either a connection to the wired remote controller (Standard II)
or an IR receiver accessory to be connected to the duct in order to receive the signal.
■ 'Auto Mode' varies depending on the outdoor unit type.
- Auto Change Over(Single Heat Pump Outdoor Unit)
- Auto Mode Select(Multi Heat Pump Outdoor Unit)
- Auto Intensity Control(Cooling Only Outdoor Unit)
■ * : These functions need to connect the wired remote controller.
■ ** : It is included by default when the product is manufactured.
■ *** : This functions need to connect to the Standard III wired remote controller.
46
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
5. ABNQ55GM3T6
Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant, Embedded : Included with product.
■ If there is a difference in development time between the product and the remote controller, some functions cannot be operated.
■ Selecting a wireless remote controller in case of ducted type indoor units requires either a connection to the wired remote controller (Standard II)
or an IR receiver accessory to be connected to the duct in order to receive the signal.
■ If you need more detail, please refer to the BECON PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
47
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
5. ABNQ55GM3T6
5.4 Dimensions
5.4.1 Product
DWG No. : TBB36535401_rev01
Chassis Code : M3
48
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
5. ABNQ55GM3T6
5.4.2 Install Space
Top view
[Unit: mm(inch)]
Air inlet vents
≥ 1,000 (39-3/8)
≥ 600 x 600 Inspection hole(1)
(23-5/8) (23-5/8)
(23-5/8 x 23-5/8) Air outlet vents 600 x 600
(23-5/8 x 23-5/8)
Front
If distance between false ceiling and actual ceiling is more than 100cm (39-3/8 inch), the number of inspection hole
could be decreased to 1. But if that is less than 20cm (7-7/8 inch), the hole size should be more than size of Indoor Unit.
Front view
[Unit: mm(inch)]
≥ 20 (25/32)
Ceiling
B(Min)
A(Min) Service Space
Note
■ Places where products are installed should not be any obstacles to the air circulation or installation. Ensure the spaces from the wall, ceiling,
or other obstacles.
■ According to type of indoor unit, external appearance or installed structure could be different.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.
49
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
5. ABNQ55GM3T6
Thermistor for
evaporator inlet
temperature
50
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
5. ABNQ55GM3T6
51
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
5. ABNQ55GM3T6
70
Octave Band Sound Pressure Level (0dB = 20μPa)
NC-65
60
NC-60
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
NC-25
20
Approximate
NC-20
Hearing
Threshold
NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)
Note
■ Sound measured at some distance away from the center of the unit.
■ Data is valid at free field condition.
■ Reference accoustic pressure 0dB = 20μPa.
■ Data is valid at nominal operation condition. Refer to the Model Specifications for nominal conditions (Power source and Ambient temperature, etc)
■ Sound levels can be increased in accordance with installation and operating conditions.
(Static pressure mode, used air guide, Room target temperature setting, etc)
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
52
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
5. ABNQ55GM3T6
Note
■ Each dash line represents for each 100 RPM step
■ If operation range is out of auto E.S.P setting range, air flow rate should be adjusted manually by wired remotecontroller. (ESP Set Value = RPM / 10)
For more information, please see the installation manual.
■ The above P-Q Curve shows available E.S.P. range. If the E.S.P value is out of min/max RPM at desired air flow, indoor components could be failed
and performance would be decreased.
■ Automatic constant air volume is a function that controls air volume automatically when installation, and the air volume is not set automatically
during operation.
53
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
ABNQ60GM3T6
6.
6. ABNQ60GM3T6
6.1 Specifications
Category
Unit Value
Major Minor
Classification Chassis - M3
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
kW 15.25
Cooling Capacity Nominal
Btu/h 52,000
kW -
Heating Capacity Nominal
Btu/h -
Power Input(Indoor) H/M/L W -
Running Current(Indoor) H/M/L A -
Type - Sirocco
Air Flow Rate((SH)/H/M/L) m³/min - / 48.0 / 43.0 / 38.0
Indoor Fan
Air Flow Rate Range(Min~Max) m³/min 30.4~62.4
External Static Pressure_Factory Set Pa 6
Type - BLDC
Drive - -
Indoor Fan Motor
W 400
Output
No. 1
Rows x Columns x FPI - 3 x 16 x 18
Heat Exchanger No. - 1
Face Area m² 0.32
Net(W x H x D) mm 1,250 x 360 x 700
Dimensions
Shipping(W x H x D) mm 1,450 x 428 x 773
Net kg 43.0
Weight
Shipping kg 48.3
Color - Steel Gray
Exterior
RAL (Classic) - -
Air Filter Type - Long Life
Fuse - O
Protection Device
Overload Protector for Fan Motor - -
Type - R410A
Refrigerant
Control Type - EEV
Drain Pipe(Natural Drainage) O.D / I.D mm(inch) 25.4/20.4
Drain Pipe(Drain Pump) O.D / I.D mm(inch) 32/25
Liquid mm(inch) Φ9.52 (3/8)
Gas mm(inch) Φ19.05 (3/4)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Cooling ((SH)/H/M/L) dB(A) - / 46.0 / 44.0 / 42.0
Sound Pressure Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) -
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Cooling ((SH)/H/M/L) dB(A) -
Sound Power Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power and Communication cable(H07RN-F) mm² × cores 0.75 x 4C
Power Supply Type to Indoor - - -
Maximum Fuse Amperes (MFA) A 40
Electrical Characteristic
Indoor Fan Motor_Full Load Amperes (FLA) A 2.4
54
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
6. ABNQ60GM3T6
Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national code. And “Electric characteristics” should be considered for electrical work and design.
■ Especially the power cable and circuit breaker should be selected in accordance with that.
■ Sound Level Values are measured at Noise Measuring chamber accordance with standard. Therefore, these values depend on the ambient conditions and
values are normally higher in actual operation.
55
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
6. ABNQ60GM3T6
Note
■ O : Applied, X : Not applied, Embedded : Included with product.
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.
■ Some functions can be limited by remote controller.
■ Selecting a wireless remote controller in case of ducted type indoor units requires either a connection to the wired remote controller (Standard II)
or an IR receiver accessory to be connected to the duct in order to receive the signal.
■ 'Auto Mode' varies depending on the outdoor unit type.
- Auto Change Over(Single Heat Pump Outdoor Unit)
- Auto Mode Select(Multi Heat Pump Outdoor Unit)
- Auto Intensity Control(Cooling Only Outdoor Unit)
■ * : These functions need to connect the wired remote controller.
■ ** : It is included by default when the product is manufactured.
■ *** : This functions need to connect to the Standard III wired remote controller.
56
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
6. ABNQ60GM3T6
Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant, Embedded : Included with product.
■ If there is a difference in development time between the product and the remote controller, some functions cannot be operated.
■ Selecting a wireless remote controller in case of ducted type indoor units requires either a connection to the wired remote controller (Standard II)
or an IR receiver accessory to be connected to the duct in order to receive the signal.
■ If you need more detail, please refer to the BECON PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
57
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
6. ABNQ60GM3T6
6.4 Dimensions
6.4.1 Product
DWG No. : TBB36535401_rev01
Chassis Code : M3
58
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
6. ABNQ60GM3T6
6.4.2 Install Space
Top view
[Unit: mm(inch)]
Air inlet vents
≥ 1,000 (39-3/8)
≥ 600 x 600 Inspection hole(1)
(23-5/8) (23-5/8)
(23-5/8 x 23-5/8) Air outlet vents 600 x 600
(23-5/8 x 23-5/8)
Front
If distance between false ceiling and actual ceiling is more than 100cm (39-3/8 inch), the number of inspection hole
could be decreased to 1. But if that is less than 20cm (7-7/8 inch), the hole size should be more than size of Indoor Unit.
Front view
[Unit: mm(inch)]
≥ 20 (25/32)
Ceiling
B(Min)
A(Min) Service Space
Note
■ Places where products are installed should not be any obstacles to the air circulation or installation. Ensure the spaces from the wall, ceiling,
or other obstacles.
■ According to type of indoor unit, external appearance or installed structure could be different.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.
59
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
6. ABNQ60GM3T6
Thermistor for
evaporator inlet
temperature
60
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
6. ABNQ60GM3T6
61
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
6. ABNQ60GM3T6
70
Octave Band Sound Pressure Level (0dB = 20μPa)
NC-65
60
NC-60
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
NC-25
20
Approximate
NC-20
Hearing
Threshold
NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)
Note
■ Sound measured at some distance away from the center of the unit.
■ Data is valid at free field condition.
■ Reference accoustic pressure 0dB = 20μPa.
■ Data is valid at nominal operation condition. Refer to the Model Specifications for nominal conditions (Power source and Ambient temperature, etc)
■ Sound levels can be increased in accordance with installation and operating conditions.
(Static pressure mode, used air guide, Room target temperature setting, etc)
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
62
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
6. ABNQ60GM3T6
Note
■ Each dash line represents for each 100 RPM step
■ If operation range is out of auto E.S.P setting range, air flow rate should be adjusted manually by wired remotecontroller. (ESP Set Value = RPM / 10)
For more information, please see the installation manual.
■ The above P-Q Curve shows available E.S.P. range. If the E.S.P value is out of min/max RPM at desired air flow, indoor components could be failed
and performance would be decreased.
■ Automatic constant air volume is a function that controls air volume automatically when installation, and the air volume is not set automatically
during operation.
63
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
ABNQ60LM3T6
7.
7. ABNQ60LM3T6
7.1 Specifications
Category
Unit Value
Major Minor
Classification Chassis - M3
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
kW 15.25
Cooling Capacity Nominal
Btu/h 52,000
kW -
Heating Capacity Nominal
Btu/h -
Power Input(Indoor) H/M/L W -
Running Current(Indoor) H/M/L A -
Type - Sirocco
Air Flow Rate((SH)/H/M/L) m³/min - / 48.0 / 43.0 / 38.0
Indoor Fan
Air Flow Rate Range(Min~Max) m³/min 30.4~62.4
External Static Pressure_Factory Set Pa 6
Type - BLDC
Drive - -
Indoor Fan Motor
W 400
Output
No. 1
Rows x Columns x FPI - 3 x 16 x 18
Heat Exchanger No. - 1
Face Area m² 0.32
Net(W x H x D) mm 1,250 x 360 x 700
Dimensions
Shipping(W x H x D) mm 1,450 x 428 x 773
Net kg 43.0
Weight
Shipping kg 48.3
Color - Steel Gray
Exterior
RAL (Classic) - -
Air Filter Type - Long Life
Fuse - O
Protection Device
Overload Protector for Fan Motor - -
Type - R410A
Refrigerant
Control Type - EEV
Drain Pipe(Natural Drainage) O.D / I.D mm(inch) 25.4/20.4
Drain Pipe(Drain Pump) O.D / I.D mm(inch) 32/25
Liquid mm(inch) Φ9.52 (3/8)
Gas mm(inch) Φ19.05 (3/4)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Cooling ((SH)/H/M/L) dB(A) - / 46.0 / 44.0 / 42.0
Sound Pressure Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) -
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Cooling ((SH)/H/M/L) dB(A) -
Sound Power Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power and Communication cable(H07RN-F) mm² × cores 0.75 x 4
Power Supply Type to Indoor - - -
Maximum Fuse Amperes (MFA) A 20
Electrical Characteristic
Indoor Fan Motor_Full Load Amperes (FLA) A 2.4
64
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
7. ABNQ60LM3T6
Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national code. And “Electric characteristics” should be considered for electrical work and design.
■ Especially the power cable and circuit breaker should be selected in accordance with that.
■ Sound Level Values are measured at Noise Measuring chamber accordance with standard. Therefore, these values depend on the ambient conditions and
values are normally higher in actual operation.
65
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
7. ABNQ60LM3T6
Note
■ O : Applied, X : Not applied, Embedded : Included with product.
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.
■ Some functions can be limited by remote controller.
■ Selecting a wireless remote controller in case of ducted type indoor units requires either a connection to the wired remote controller (Standard II)
or an IR receiver accessory to be connected to the duct in order to receive the signal.
■ 'Auto Mode' varies depending on the outdoor unit type.
- Auto Change Over(Single Heat Pump Outdoor Unit)
- Auto Mode Select(Multi Heat Pump Outdoor Unit)
- Auto Intensity Control(Cooling Only Outdoor Unit)
■ * : These functions need to connect the wired remote controller.
■ ** : It is included by default when the product is manufactured.
■ *** : This functions need to connect to the Standard III wired remote controller.
66
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
7. ABNQ60LM3T6
Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant, Embedded : Included with product.
■ If there is a difference in development time between the product and the remote controller, some functions cannot be operated.
■ Selecting a wireless remote controller in case of ducted type indoor units requires either a connection to the wired remote controller (Standard II)
or an IR receiver accessory to be connected to the duct in order to receive the signal.
■ If you need more detail, please refer to the BECON PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
67
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
7. ABNQ60LM3T6
7.4 Dimensions
7.4.1 Product
DWG No. : TBB36535401_rev01
Chassis Code : M3
68
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
7. ABNQ60LM3T6
7.4.2 Install Space
Top view
[Unit: mm(inch)]
Air inlet vents
≥ 1,000 (39-3/8)
≥ 600 x 600 Inspection hole(1)
(23-5/8) (23-5/8)
(23-5/8 x 23-5/8) Air outlet vents 600 x 600
(23-5/8 x 23-5/8)
Front
If distance between false ceiling and actual ceiling is more than 100cm (39-3/8 inch), the number of inspection hole
could be decreased to 1. But if that is less than 20cm (7-7/8 inch), the hole size should be more than size of Indoor Unit.
Front view
[Unit: mm(inch)]
≥ 20 (25/32)
Ceiling
B(Min)
A(Min) Service Space
Note
■ Places where products are installed should not be any obstacles to the air circulation or installation. Ensure the spaces from the wall, ceiling,
or other obstacles.
■ According to type of indoor unit, external appearance or installed structure could be different.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.
69
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
7. ABNQ60LM3T6
Thermistor for
evaporator inlet
temperature
70
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
7. ABNQ60LM3T6
71
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
7. ABNQ60LM3T6
70
Octave Band Sound Pressure Level (0dB = 20μPa)
NC-65
60
NC-60
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
NC-25
20
Approximate
NC-20
Hearing
Threshold
NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)
Note
■ Sound measured at some distance away from the center of the unit.
■ Data is valid at free field condition.
■ Reference accoustic pressure 0dB = 20μPa.
■ Data is valid at nominal operation condition. Refer to the Model Specifications for nominal conditions (Power source and Ambient temperature, etc)
■ Sound levels can be increased in accordance with installation and operating conditions.
(Static pressure mode, used air guide, Room target temperature setting, etc)
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
72
Single Indoor Unit Ceiling Concealed Duct - Middle Static Product Data
7. ABNQ60LM3T6
Note
■ Each dash line represents for each 100 RPM step
■ If operation range is out of auto E.S.P setting range, air flow rate should be adjusted manually by wired remotecontroller. (ESP Set Value = RPM / 10)
For more information, please see the installation manual.
■ The above P-Q Curve shows available E.S.P. range. If the E.S.P value is out of min/max RPM at desired air flow, indoor components could be failed
and performance would be decreased.
■ Automatic constant air volume is a function that controls air volume automatically when installation, and the air volume is not set automatically
during operation.
73
Single Indoor Unit Floor standing Product Data
APNQ55GT3E6
8.
8. APNQ55GT3E6
8.1 Specifications
Category
Unit Value
Major Minor
Classification Chassis - PT3
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
kW 14.05
Cooling Capacity Nominal
Btu/h 48,000
kW -
Heating Capacity Nominal
Btu/h -
Power Input(Indoor) H/M/L W -
Running Current(Indoor) H/M/L A -
Type - Sirocco
Air Flow Rate((SH)/H/M/L) m³/min 37.0 / 33.0 / 28.0 / 24.0
Indoor Fan
Air Flow Rate Range(Min~Max) m³/min -
External Static Pressure_Factory Set Pa -
Type - BLDC
Drive - -
Indoor Fan Motor
W 224
Output
No. 1
Rows x Columns x FPI - 3 x 38 x 19
Heat Exchanger No. - 1
Face Area m² 0.39
Net(W x H x D) mm 590 x 1,840 x 440
Dimensions
Shipping(W x H x D) mm 690 x 1,940 x 531
Net kg 49.0
Weight
Shipping kg 57.0
Color - Noble white
Exterior
RAL (Classic) - RAL 9016
Air Filter Type - Long Life
Fuse - O
Protection Device
Overload Protector for Fan Motor - -
Type - R410A
Refrigerant
Control Type - EEV
Drain Pipe(Natural Drainage) O.D / I.D mm(inch) 21.0(13/16) / 17.0(21/32)
Drain Pipe(Drain Pump) O.D / I.D mm(inch) -
Liquid mm(inch) Φ9.52 (3/8)
Gas mm(inch) Φ19.05 (3/4)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Cooling ((SH)/H/M/L) dB(A) 55.0 / 52.0 / 49.0 / 47.0
Sound Pressure Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) -
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Cooling ((SH)/H/M/L) dB(A) -
Sound Power Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power and Communication cable(H07RN-F) mm² × cores 0.75 x 4C
Power Supply Type to Indoor - - -
Maximum Fuse Amperes (MFA) A 40
Electrical Characteristic
Indoor Fan Motor_Full Load Amperes (FLA) A 0.95
74
Single Indoor Unit Floor standing Product Data
8. APNQ55GT3E6
Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national code. And “Electric characteristics” should be considered for electrical work and design.
■ Especially the power cable and circuit breaker should be selected in accordance with that.
■ Sound Level Values are measured at Noise Measuring chamber accordance with standard. Therefore, these values depend on the ambient conditions and
values are normally higher in actual operation.
75
Single Indoor Unit Floor standing Product Data
8. APNQ55GT3E6
Note
■ O : Applied, X : Not Applied, - : Unconfirmed or irrelevant
- Embedded : A kit is provided by default for using this function when the product is manufactured.
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.
■ Some functions can be limited by remote controller.
■ In case of cassette type indoor units, Plasma kit and Auto Elevation Grille functions are not applicable at the same time.
■ 'Auto Mode' varies depending on the outdoor unit type.
- Auto Change Over(Single Heat Pump Outdoor Unit)
- Auto Mode Select(Multi Heat Pump Outdoor Unit)
- Auto Intensity Control(Cooling Only Outdoor Unit)
■ * : These functions need to connect the wired remote controller.
■ ** : This functions need to connect to the Standard III wired remote controller.
76
Single Indoor Unit Floor standing Product Data
8. APNQ55GT3E6
Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant.
■ * : Some advanced functions controlled by individual controller cannot be operated.
■ If there is a difference in development time between the product and the remote controller, some functions cannot be operated.
■ If you need more detail, please refer to the Control(BECON) PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
77
Single Indoor Unit Floor standing Product Data
8. APNQ55GT3E6
8.4 Dimensions
8.4.1 Product
DWG No. : TBE35607201_Rev01
Chassis code : PT3
78
Single Indoor Unit Floor standing Product Data
8. APNQ55GT3E6
8.4.2 Install Space
[Unit : mm(inch)]
300 (11-1
3 /16)
300 (11-1
3/16)
300 (11-13/16)
Note
■ Places where products are installed should not be any obstacles to the air circulation or installation. Ensure the spaces from the wall, ceiling,
or other obstacles.
■ According to type of indoor unit, external appearance or installed structure could be different.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.
79
Single Indoor Unit Floor standing Product Data
8. APNQ55GT3E6
Cooling
Evaporator Out
Temperature
Thermistor
Evaporator In
Temperature
Thermistor
M
(Sirocco Fan)
Indoor Unit
Inlet Air
Temperature
Thermistor
80
Single Indoor Unit Floor standing Product Data
8. APNQ55GT3E6
81
Single Indoor Unit Floor standing Product Data
8. APNQ55GT3E6
S-High
▲ High
70 Mid
Octave Band Sound Pressure Level (0dB = 20μPa)
◆ Low
NC-65
60
NC-60
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
NC-25
20
Approximate
NC-20
Hearing
Threshold
NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)
Note
■ Sound measured at some distance away from the center of the unit.
■ Data is valid at free field condition.
■ Reference accoustic pressure 0dB = 20μPa.
■ Data is valid at nominal operation condition.
Refer to the Model Specifications for nominal conditions(Power source and Ambient temperature, etc)
■ Sound levels can be increased in accordance with installation and operating conditions.
(Static pressure mode, used air guide, Room target temperature setting, etc)
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
82
Single Indoor Unit Floor standing Product Data
8. APNQ55GT3E6
Cooling
Discharge angle: 90°
2m
2.0 2.5 3.0
1.5
1.0 1m
0.5
0.2
0m
10m 8m 6m 4m 2m 0m
Temperature [°C]
2.7m
2m
15 14 13
16
1m
17 18 19
0m
10m 8m 6m 4m 2m 0m
Note
■ These figures are accordance with normal certain condition and environment.
(Airflow step is 'High', Air discharge angle is fixed as indicated angle.)
■ Indoor airflow distribution under actual installation or operating conditions depends on ambient temperature, ceiling height, product installation direction /
location, indoor / Heating load, and other obstacles, etc.
83
Single Indoor Unit Floor standing Product Data
APNQ55GT3M6
9.
9. APNQ55GT3M6
9.1 Specifications
Category
Unit Value
Major Minor
Classification Chassis - PT3
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
kW 14.05
Cooling Capacity Nominal
Btu/h 48,000
kW -
Heating Capacity Nominal
Btu/h -
Power Input(Indoor) H/M/L W -
Running Current(Indoor) H/M/L A -
Type - Sirocco
Air Flow Rate((SH)/H/M/L) m³/min 37.0 / 33.0 / 28.0 / 24.0
Indoor Fan
Air Flow Rate Range(Min~Max) m³/min -
External Static Pressure_Factory Set Pa -
Type - BLDC
Drive - -
Indoor Fan Motor
W 224
Output
No. 1
Rows x Columns x FPI - 3 x 38 x 19
Heat Exchanger No. - 1
Face Area m² 0.39
Net(W x H x D) mm 590 x 1,840 x 440
Dimensions
Shipping(W x H x D) mm 690 x 1,940 x 531
Net kg 49.0
Weight
Shipping kg 57.0
Color - Noble white
Exterior
RAL (Classic) - RAL 9016
Air Filter Type - Long Life
Fuse - O
Protection Device
Overload Protector for Fan Motor - -
Type - R410A
Refrigerant
Control Type - EEV
Drain Pipe(Natural Drainage) O.D / I.D mm(inch) 21.0(13/16) / 17.0(21/32)
Drain Pipe(Drain Pump) O.D / I.D mm(inch) -
Liquid mm(inch) Φ9.52 (3/8)
Gas mm(inch) Φ19.05 (3/4)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Cooling ((SH)/H/M/L) dB(A) 55.0 / 52.0 / 49.0 / 47.0
Sound Pressure Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) -
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Cooling ((SH)/H/M/L) dB(A) -
Sound Power Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power and Communication cable(H07RN-F) mm² × cores 0.75 x 4C
Power Supply Type to Indoor - - -
Maximum Fuse Amperes (MFA) A 40
Electrical Characteristic
Indoor Fan Motor_Full Load Amperes (FLA) A 0.95
84
Single Indoor Unit Floor standing Product Data
9. APNQ55GT3M6
Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national code. And “Electric characteristics” should be considered for electrical work and design.
■ Especially the power cable and circuit breaker should be selected in accordance with that.
■ Sound Level Values are measured at Noise Measuring chamber accordance with standard. Therefore, these values depend on the ambient conditions and
values are normally higher in actual operation.
85
Single Indoor Unit Floor standing Product Data
9. APNQ55GT3M6
Note
■ O : Applied, X : Not Applied, - : Unconfirmed or irrelevant
- Embedded : A kit is provided by default for using this function when the product is manufactured.
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.
■ Some functions can be limited by remote controller.
■ In case of cassette type indoor units, Plasma kit and Auto Elevation Grille functions are not applicable at the same time.
■ 'Auto Mode' varies depending on the outdoor unit type.
- Auto Change Over(Single Heat Pump Outdoor Unit)
- Auto Mode Select(Multi Heat Pump Outdoor Unit)
- Auto Intensity Control(Cooling Only Outdoor Unit)
■ * : These functions need to connect the wired remote controller.
■ ** : This functions need to connect to the Standard III wired remote controller.
86
Single Indoor Unit Floor standing Product Data
9. APNQ55GT3M6
Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant.
■ * : Some advanced functions controlled by individual controller cannot be operated.
■ If there is a difference in development time between the product and the remote controller, some functions cannot be operated.
■ If you need more detail, please refer to the Control(BECON) PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
87
Single Indoor Unit Floor standing Product Data
9. APNQ55GT3M6
9.4 Dimensions
9.4.1 Product
DWG No. : TBE35607201_Rev01
Chassis code : PT3
88
Single Indoor Unit Floor standing Product Data
9. APNQ55GT3M6
9.4.2 Install Space
[Unit : mm(inch)]
300 (11-1
3 /16)
300 (11-1
3/16)
300 (11-13/16)
Note
■ Places where products are installed should not be any obstacles to the air circulation or installation. Ensure the spaces from the wall, ceiling,
or other obstacles.
■ According to type of indoor unit, external appearance or installed structure could be different.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.
89
Single Indoor Unit Floor standing Product Data
9. APNQ55GT3M6
Cooling
Evaporator Out
Temperature
Thermistor
Evaporator In
Temperature
Thermistor
M
(Sirocco Fan)
Indoor Unit
Inlet Air
Temperature
Thermistor
90
Single Indoor Unit Floor standing Product Data
9. APNQ55GT3M6
91
Single Indoor Unit Floor standing Product Data
9. APNQ55GT3M6
S-High
▲ High
70 Mid
Octave Band Sound Pressure Level (0dB = 20μPa)
◆ Low
NC-65
60
NC-60
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
NC-25
20
Approximate
NC-20
Hearing
Threshold
NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)
Note
■ Sound measured at some distance away from the center of the unit.
■ Data is valid at free field condition.
■ Reference accoustic pressure 0dB = 20μPa.
■ Data is valid at nominal operation condition.
Refer to the Model Specifications for nominal conditions(Power source and Ambient temperature, etc)
■ Sound levels can be increased in accordance with installation and operating conditions.
(Static pressure mode, used air guide, Room target temperature setting, etc)
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
92
Single Indoor Unit Floor standing Product Data
9. APNQ55GT3M6
Cooling
Discharge angle: 90°
2m
2.0 2.5 3.0
1.5
1.0 1m
0.5
0.2
0m
10m 8m 6m 4m 2m 0m
Temperature [°C]
2.7m
2m
15 14 13
16
1m
17 18 19
0m
10m 8m 6m 4m 2m 0m
Note
■ These figures are accordance with normal certain condition and environment.
(Airflow step is 'High', Air discharge angle is fixed as indicated angle.)
■ Indoor airflow distribution under actual installation or operating conditions depends on ambient temperature, ceiling height, product installation direction /
location, indoor / Heating load, and other obstacles, etc.
93
Single Indoor Unit Ceiling Cassette 4-Way Product Data
ATNQ21GPLT6
10.
10. ATNQ21GPLT6
10.1 Specifications
Category
Unit Value
Major Minor
Classification Chassis - TP
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
kW 4.98
Cooling Capacity Nominal
Btu/h 17,000
kW -
Heating Capacity Nominal
Btu/h -
Power Input(Indoor) H/M/L W -
Running Current(Indoor) H/M/L A -
Type - 2D Turbo Fan
Air Flow Rate((SH)/H/M/L) m³/min - / 16.5 / 14.5 / 13.0
Indoor Fan
Air Flow Rate Range(Min~Max) m³/min -
External Static Pressure_Factory Set Pa -
Type - BLDC
Drive - -
Indoor Fan Motor
W 50.3
Output
No. 1
Rows x Columns x FPI - 2x8x19
Heat Exchanger No. - 1
Face Area m² 0.35
Net(W x H x D) mm 840 x 204 x 840
Dimensions
Shipping(W x H x D) mm 922 x 276 x 917
Net kg 21.5
Weight
Shipping kg 26.0
Color - Morning Fog
Exterior
RAL (Classic) - RAL 9001
Air Filter Type - Long life
Fuse - O
Protection Device
Overload Protector for Fan Motor - -
Type - R410A
Refrigerant
Control Type - EEV
Drain Pipe(Natural Drainage) O.D / I.D mm(inch) -
Drain Pipe(Drain Pump) O.D / I.D mm(inch) 32/25
Liquid mm(inch) Φ6.35 (1/4)
Gas mm(inch) Φ12.7 (1/2)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Cooling ((SH)/H/M/L) dB(A) - / 36.0 / 34.0 / 32.0
Sound Pressure Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) -
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Cooling ((SH)/H/M/L) dB(A) -
Sound Power Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power and Communication cable(H07RN-F) mm² × cores 0.75 x 4
Power Supply Type to Indoor - - -
Maximum Fuse Amperes (MFA) A 15
Electrical Characteristic
Indoor Fan Motor_Full Load Amperes (FLA) A 0.6
94
Single Indoor Unit Ceiling Cassette 4-Way Product Data
10. ATNQ21GPLT6
Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national code. And “Electric characteristics” should be considered for electrical work and design.
■ Especially the power cable and circuit breaker should be selected in accordance with that.
■ Sound Level Values are measured at Noise Measuring chamber accordance with standard. Therefore, these values depend on the ambient conditions and
values are normally higher in actual operation.
95
Single Indoor Unit Ceiling Cassette 4-Way Product Data
10. ATNQ21GPLT6
Note
■ O : Applied, X : Not Applied, - : Unconfirmed or irrelevant
- Embedded : A kit is provided by default for using this function when the product is manufactured.
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.
■ Some functions can be limited by remote controller.
■ In case of cassette type indoor units, Plasma kit and Auto Elevation Grille functions are not applicable at the same time.
■ 'Auto Mode' varies depending on the outdoor unit type.
- Auto Change Over(Single Heat Pump Outdoor Unit)
- Auto Mode Select(Multi Heat Pump Outdoor Unit)
- Auto Intensity Control(Cooling Only Outdoor Unit)
■ * : These functions need to connect the wired remote controller.
■ ** : This functions need to connect to the Standard III wired remote controller.
96
Single Indoor Unit Ceiling Cassette 4-Way Product Data
10. ATNQ21GPLT6
Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant.
■ * : Some advanced functions controlled by individual controller cannot be operated.
■ If there is a difference in development time between the product and the remote controller, some functions cannot be operated.
■ If you need more detail, please refer to the BECON PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
97
Single Indoor Unit Ceiling Cassette 4-Way Product Data
10. ATNQ21GPLT6
10.4 Dimensions
10.4.1 Product
PT-M*HW0
98
Single Indoor Unit Ceiling Cassette 4-Way Product Data
10. ATNQ21GPLT6
10.4.2 Intallation Space
≥ 10(13/32)
Ceiling Ceiling Board
Ceiling Board
≤ 300 (11-13/16)
≥ 1000(39-3/8) ≥ 500(19-11/16)
≥ 500(19-11/16)
A
1.6 ~ 10.0 kW = 2,000 (78-3/4) ≤ A ≤ 3,600 (141-24/32)
10.0~14.5 kW = 2,500 (98-7/16) ≤ A ≤ 4,200 (165-11/32)
Unit:mm(inch)
Floor
Note
■ Places where products are installed should not be any obstacles to the air circulation or installation. Ensure the spaces from the wall, ceiling,
or other obstacles.
■ According to type of indoor unit, external appearance or installed structure could be different.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.
■ Install certainly the decoration panel. Cool air leakage causes sweating or falling of water-drops.
99
Single Indoor Unit Ceiling Cassette 4-Way Product Data
10. ATNQ21GPLT6
Thermistor for
Evaporator inlet
Humidity sensor
temperature
100
Single Indoor Unit Ceiling Cassette 4-Way Product Data
10. ATNQ21GPLT6
101
Single Indoor Unit Ceiling Cassette 4-Way Product Data
10. ATNQ21GPLT6
High
70
Octave Band Sound Pressure Level (0dB = 20µPa)
NC-65
60
NC-60
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
NC-25
20
Approximate
NC-20
Hearing
Threshold
NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)
Note
■ Sound measured at some distance away from the center of the unit.
■ Data is valid at free field condition.
■ Reference accoustic pressure 0dB = 20μPa.
■ Data is valid at nominal operation condition.
Refer to the Model Specifications for nominal conditions(Power source and Ambient temperature, etc)
■ Sound levels can be increased in accordance with installation and operating conditions.
(Static pressure mode, used air guide, Room target temperature setting, etc)
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
102
Single Indoor Unit Ceiling Cassette 4-Way Product Data
10. ATNQ21GPLT6
2.7m
0.25 1.2
2m
0.5
0m
5m 4m 3m 2m 1m 0m 1m 2m 3m 4m 5m
Temperature [°C]
25 25 2.7m
3.2m
2m
24 24
2m
23 23
1m
22 22 1m
23 23
0m
0m
5m
5m 4m
4m 3m
3m 2m
2m 1m
1m 0m
0m 1m
1m 2m
2m 3m
3m 4m
4m 5m
5m
Note
■ These figures are accordance with normal certain condition and environment.
(Airflow step is 'High', Air discharge angle is fixed as indicated angle.)
■ Indoor airflow distribution under actual installation or operating conditions depends on ambient temperature, ceiling height, product installation direction /
location, indoor / Heating load, and other obstacles, etc.
103
Single Indoor Unit Ceiling Cassette 4-Way Product Data
ATNQ28GPLT6
11.
11. ATNQ28GPLT6
11.1 Specifications
Category
Unit Value
Major Minor
Classification Chassis - TP
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
kW 6.45
Cooling Capacity Nominal
Btu/h 22,000
kW -
Heating Capacity Nominal
Btu/h -
Power Input(Indoor) H/M/L W -
Running Current(Indoor) H/M/L A -
Type - 2D Turbo Fan
Air Flow Rate((SH)/H/M/L) m³/min - / 17.0 / 15.0 / 13.0
Indoor Fan
Air Flow Rate Range(Min~Max) m³/min -
External Static Pressure_Factory Set Pa -
Type - BLDC
Drive - -
Indoor Fan Motor
W 50.3
Output
No. 1
Rows x Columns x FPI - 2x8x19
Heat Exchanger No. - 1
Face Area m² 0.35
Net(W x H x D) mm 840 x 204 x 840
Dimensions
Shipping(W x H x D) mm 922 x 276 x 917
Net kg 21.5
Weight
Shipping kg 26.0
Color - Morning Fog
Exterior
RAL (Classic) - RAL 9001
Air Filter Type - Long Life
Fuse - O
Protection Device
Overload Protector for Fan Motor - -
Type - R410A
Refrigerant
Control Type - EEV
Drain Pipe(Natural Drainage) O.D / I.D mm(inch) -
Drain Pipe(Drain Pump) O.D / I.D mm(inch) 32/25
Liquid mm(inch) Φ9.52 (3/8)
Gas mm(inch) Φ15.88 (5/8)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Cooling ((SH)/H/M/L) dB(A) - / 38.0 / 36.0 / 34.0
Sound Pressure Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) -
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Cooling ((SH)/H/M/L) dB(A) -
Sound Power Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power and Communication cable(H07RN-F) mm² × cores 0.75 x 4
Power Supply Type to Indoor - - -
Maximum Fuse Amperes (MFA) A 25
Electrical Characteristic
Indoor Fan Motor_Full Load Amperes (FLA) A 0.6
104
Single Indoor Unit Ceiling Cassette 4-Way Product Data
11. ATNQ28GPLT6
Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national code. And “Electric characteristics” should be considered for electrical work and design.
■ Especially the power cable and circuit breaker should be selected in accordance with that.
■ Sound Level Values are measured at Noise Measuring chamber accordance with standard. Therefore, these values depend on the ambient conditions and
values are normally higher in actual operation.
105
Single Indoor Unit Ceiling Cassette 4-Way Product Data
11. ATNQ28GPLT6
Note
■ O : Applied, X : Not Applied, - : Unconfirmed or irrelevant
- Embedded : A kit is provided by default for using this function when the product is manufactured.
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.
■ Some functions can be limited by remote controller.
■ In case of cassette type indoor units, Plasma kit and Auto Elevation Grille functions are not applicable at the same time.
■ 'Auto Mode' varies depending on the outdoor unit type.
- Auto Change Over(Single Heat Pump Outdoor Unit)
- Auto Mode Select(Multi Heat Pump Outdoor Unit)
- Auto Intensity Control(Cooling Only Outdoor Unit)
■ * : These functions need to connect the wired remote controller.
■ ** : This functions need to connect to the Standard III wired remote controller.
106
Single Indoor Unit Ceiling Cassette 4-Way Product Data
11. ATNQ28GPLT6
Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant.
■ * : Some advanced functions controlled by individual controller cannot be operated.
■ If there is a difference in development time between the product and the remote controller, some functions cannot be operated.
■ If you need more detail, please refer to the BECON PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
107
Single Indoor Unit Ceiling Cassette 4-Way Product Data
11. ATNQ28GPLT6
11.4 Dimensions
11.4.1 Product
PT-M*HW0
108
Single Indoor Unit Ceiling Cassette 4-Way Product Data
11. ATNQ28GPLT6
11.4.2 Install Space
≥ 10(13/32)
Ceiling Ceiling Board
Ceiling Board
≤ 300 (11-13/16)
≥ 1000(39-3/8) ≥ 500(19-11/16)
≥ 500(19-11/16)
A
1.6 ~ 10.0 kW = 2,000 (78-3/4) ≤ A ≤ 3,600 (141-24/32)
10.0~14.5 kW = 2,500 (98-7/16) ≤ A ≤ 4,200 (165-11/32)
Unit:mm(inch)
Floor
Note
■ Places where products are installed should not be any obstacles to the air circulation or installation. Ensure the spaces from the wall, ceiling,
or other obstacles.
■ According to type of indoor unit, external appearance or installed structure could be different.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.
■ Install certainly the decoration panel. Cool air leakage causes sweating or falling of water-drops.
109
Single Indoor Unit Ceiling Cassette 4-Way Product Data
11. ATNQ28GPLT6
Thermistor for
Evaporator inlet
Humidity sensor
temperature
110
Single Indoor Unit Ceiling Cassette 4-Way Product Data
11. ATNQ28GPLT6
111
Single Indoor Unit Ceiling Cassette 4-Way Product Data
11. ATNQ28GPLT6
70
Octave Band Sound Pressure Level (dB = 20μPa )
65
NC-65
60
NC-60
55
NC-55
50
NC-50
45
NC-45
40
NC-40
35
NC-35
30
NC-30
25
20 NC-25
Approximate
Hearing NC-20
15 Threshold
NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)
Note
■ Sound measured at some distance away from the center of the unit.
■ Data is valid at free field condition.
■ Reference accoustic pressure 0dB = 20μPa.
■ Data is valid at nominal operation condition.
Refer to the Model Specifications for nominal conditions(Power source and Ambient temperature, etc)
■ Sound levels can be increased in accordance with installation and operating conditions.
(Static pressure mode, used air guide, Room target temperature setting, etc)
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
112
Single Indoor Unit Ceiling Cassette 4-Way Product Data
11. ATNQ28GPLT6
0.25
2.7m
3.2m
0.25
0.25 0.25
0.25 2m
2m
2.0 2.0
0.25
0.5 0.25
1m
1m
0.25 0.25
1.0 1.0
0.5 1.5
1.5 0.5
0m
0m
5m
5m 4m
4m 3m
3m 2m
2m 1m
1m 0m
0m 1m
1m 2m
2m 3m
3m 4m
4m 5m
5m
Temperature [°C]
2.7m
3.2m
24 24
21 21 2m
23 23 2m
23
1m
1m
22 22 22
23
23 23
22
0m
0m
5m
5m 4m
4m 3m
3m 2m
2m 1m
1m 0m
0m 1m
1m 2m
2m 3m
3m 4m
4m 5m
5m
Note
■ These figures are accordance with normal certain condition and environment.
(Airflow step is 'High', Air discharge angle is fixed as indicated angle.)
■ Indoor airflow distribution under actual installation or operating conditions depends on ambient temperature, ceiling height, product installation direction /
location, indoor / Heating load, and other obstacles, etc.
113
Single Indoor Unit Ceiling Cassette 4-Way Product Data
ATNQ34GNLT6
12.
12. ATNQ34GNLT6
12.1 Specifications
Category
Unit Value
Major Minor
Classification Chassis - TN
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
kW 7.35
Cooling Capacity Nominal
Btu/h 25,000
kW -
Heating Capacity Nominal
Btu/h -
Power Input(Indoor) H/M/L W -
Running Current(Indoor) H/M/L A -
Type - 2D Turbo Fan
Air Flow Rate((SH)/H/M/L) m³/min - / 23.0 / 21.0 / 19.0
Indoor Fan
Air Flow Rate Range(Min~Max) m³/min -
External Static Pressure_Factory Set Pa -
Type - BLDC
Drive - -
Indoor Fan Motor
W 124
Output
No. 1
Rows x Columns x FPI - 2x10x19
Heat Exchanger No. - 1
Face Area m² 0.43
Net(W x H x D) mm 840 x 246 x 840
Dimensions
Shipping(W x H x D) mm 922 x 318 x 917
Net kg 25.5
Weight
Shipping kg 29.7
Color - Morning Fog
Exterior
RAL (Classic) - RAL 9001
Air Filter Type - Long Life
Fuse - O
Protection Device
Overload Protector for Fan Motor - -
Type - R410A
Refrigerant
Control Type - EEV
Drain Pipe(Natural Drainage) O.D / I.D mm(inch) -
Drain Pipe(Drain Pump) O.D / I.D mm(inch) 32/25
Liquid mm(inch) Φ9.52 (3/8)
Gas mm(inch) Φ15.88 (5/8)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Cooling ((SH)/H/M/L) dB(A) - / 40.0 / 38.0 / 36.0
Sound Pressure Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) -
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Cooling ((SH)/H/M/L) dB(A) -
Sound Power Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power and Communication cable(H07RN-F) mm² × cores 0.75 x 4
Power Supply Type to Indoor - - -
Maximum Fuse Amperes (MFA) A 25
Electrical Characteristic
Indoor Fan Motor_Full Load Amperes (FLA) A 1.28
114
Single Indoor Unit Ceiling Cassette 4-Way Product Data
12. ATNQ34GNLT6
Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national code. And “Electric characteristics” should be considered for electrical work and design.
■ Especially the power cable and circuit breaker should be selected in accordance with that.
■ Sound Level Values are measured at Noise Measuring chamber accordance with standard. Therefore, these values depend on the ambient conditions and
values are normally higher in actual operation.
115
Single Indoor Unit Ceiling Cassette 4-Way Product Data
12. ATNQ34GNLT6
Note
■ O : Applied, X : Not Applied, - : Unconfirmed or irrelevant
- Embedded : A kit is provided by default for using this function when the product is manufactured.
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.
■ Some functions can be limited by remote controller.
■ In case of cassette type indoor units, Plasma kit and Auto Elevation Grille functions are not applicable at the same time.
■ 'Auto Mode' varies depending on the outdoor unit type.
- Auto Change Over(Single Heat Pump Outdoor Unit)
- Auto Mode Select(Multi Heat Pump Outdoor Unit)
- Auto Intensity Control(Cooling Only Outdoor Unit)
■ * : These functions need to connect the wired remote controller.
■ ** : This functions need to connect to the Standard III wired remote controller.
116
Single Indoor Unit Ceiling Cassette 4-Way Product Data
12. ATNQ34GNLT6
Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant.
■ * : Some advanced functions controlled by individual controller cannot be operated.
■ If there is a difference in development time between the product and the remote controller, some functions cannot be operated.
■ If you need more detail, please refer to the BECON PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
117
Single Indoor Unit Ceiling Cassette 4-Way Product Data
12. ATNQ34GNLT6
12.4 Dimensions
12.4.1 Product
118
Single Indoor Unit Ceiling Cassette 4-Way Product Data
12. ATNQ34GNLT6
12.4.2 Install Space
≥ 10(13/32)
Ceiling Ceiling Board
Ceiling Board
≤ 300 (11-13/16)
≥ 1000(39-3/8) ≥ 500(19-11/16)
≥ 500(19-11/16)
A
1.6 ~ 10.0 kW = 2,000 (78-3/4) ≤ A ≤ 3,600 (141-24/32)
10.0~14.5 kW = 2,500 (98-7/16) ≤ A ≤ 4,200 (165-11/32)
Unit:mm(inch)
Floor
Note
■ Places where products are installed should not be any obstacles to the air circulation or installation. Ensure the spaces from the wall, ceiling,
or other obstacles.
■ According to type of indoor unit, external appearance or installed structure could be different.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.
■ Install certainly the decoration panel. Cool air leakage causes sweating or falling of water-drops.
119
Single Indoor Unit Ceiling Cassette 4-Way Product Data
12. ATNQ34GNLT6
Thermistor for
Evaporator inlet
Humidity sensor
temperature
120
Single Indoor Unit Ceiling Cassette 4-Way Product Data
12. ATNQ34GNLT6
121
Single Indoor Unit Ceiling Cassette 4-Way Product Data
12. ATNQ34GNLT6
High
Octave Band Sound Pressure Level (0dB = 20µPa)
70
NC -65
60
NC-60
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
NC-25
20
Approximate
NC-20
Hearing
Threshold
NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)
Note
■ Sound measured at some distance away from the center of the unit.
■ Data is valid at free field condition.
■ Reference accoustic pressure 0dB = 20μPa.
■ Data is valid at nominal operation condition.
Refer to the Model Specifications for nominal conditions(Power source and Ambient temperature, etc)
■ Sound levels can be increased in accordance with installation and operating conditions.
(Static pressure mode, used air guide, Room target temperature setting, etc)
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
122
Single Indoor Unit Ceiling Cassette 4-Way Product Data
12. ATNQ34GNLT6
2.7m
3.2m
0.25 0.25
0.5
2m
2m
Temperature [°C]
23 23 2.7m
3.2m
2m
2m
21 21
22 22
20 20 1m
1m
21
21 21 21
22 22
0m
0m
5m
5m 4m
4m 3m
3m 2m
2m 1m
1m 0m
0m 1m
1m 2m
2m 3m
3m 4m
4m 5m
5m
Note
■ These figures are accordance with normal certain condition and environment.
(Airflow step is 'High', Air discharge angle is fixed as indicated angle.)
■ Indoor airflow distribution under actual installation or operating conditions depends on ambient temperature, ceiling height, product installation direction /
location, indoor / Heating load, and other obstacles, etc.
123
Single Indoor Unit Ceiling Cassette 4-Way Product Data
ATNQ40GNLT6
13.
13. ATNQ40GNLT6
13.1 Specifications
Category
Unit Value
Major Minor
Classification Chassis - TN
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
kW 9.40
Cooling Capacity Nominal
Btu/h 32,000
kW -
Heating Capacity Nominal
Btu/h -
Power Input(Indoor) H/M/L W -
Running Current(Indoor) H/M/L A -
Type - 2D Turbo Fan
Air Flow Rate((SH)/H/M/L) m³/min - / 23.0 / 21.0 / 19.0
Indoor Fan
Air Flow Rate Range(Min~Max) m³/min -
External Static Pressure_Factory Set Pa -
Type - BLDC
Drive - -
Indoor Fan Motor
W 124
Output
No. 1
Rows x Columns x FPI - 2x10x19
Heat Exchanger No. - 1
Face Area m² 0.43
Net(W x H x D) mm 840 x 246 x 840
Dimensions
Shipping(W x H x D) mm 922 x 318 x 917
Net kg 25.5
Weight
Shipping kg 29.7
Color - Morning Fog
Exterior
RAL (Classic) - RAL 9001
Air Filter Type - Long Life
Fuse - O
Protection Device
Overload Protector for Fan Motor - -
Type - R410A
Refrigerant
Control Type - EEV
Drain Pipe(Natural Drainage) O.D / I.D mm(inch) -
Drain Pipe(Drain Pump) O.D / I.D mm(inch) 32/25
Liquid mm(inch) Φ9.52 (3/8)
Gas mm(inch) Φ15.88 (5/8)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Cooling ((SH)/H/M/L) dB(A) - / 40.0 / 38.0 / 36.0
Sound Pressure Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) -
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Cooling ((SH)/H/M/L) dB(A) -
Sound Power Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power and Communication cable(H07RN-F) mm² × cores 0.75 x 4
Power Supply Type to Indoor - - -
Maximum Fuse Amperes (MFA) A 25
Electrical Characteristic
Indoor Fan Motor_Full Load Amperes (FLA) A 1.28
124
Single Indoor Unit Ceiling Cassette 4-Way Product Data
13. ATNQ40GNLT6
Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national code. And “Electric characteristics” should be considered for electrical work and design.
■ Especially the power cable and circuit breaker should be selected in accordance with that.
■ Sound Level Values are measured at Noise Measuring chamber accordance with standard. Therefore, these values depend on the ambient conditions and
values are normally higher in actual operation.
125
Single Indoor Unit Ceiling Cassette 4-Way Product Data
13. ATNQ40GNLT6
Note
■ O : Applied, X : Not Applied, - : Unconfirmed or irrelevant
- Embedded : A kit is provided by default for using this function when the product is manufactured.
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.
■ Some functions can be limited by remote controller.
■ In case of cassette type indoor units, Plasma kit and Auto Elevation Grille functions are not applicable at the same time.
■ 'Auto Mode' varies depending on the outdoor unit type.
- Auto Change Over(Single Heat Pump Outdoor Unit)
- Auto Mode Select(Multi Heat Pump Outdoor Unit)
- Auto Intensity Control(Cooling Only Outdoor Unit)
■ * : These functions need to connect the wired remote controller.
■ ** : This functions need to connect to the Standard III wired remote controller.
126
Single Indoor Unit Ceiling Cassette 4-Way Product Data
13. ATNQ40GNLT6
Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant.
■ * : Some advanced functions controlled by individual controller cannot be operated.
■ If there is a difference in development time between the product and the remote controller, some functions cannot be operated.
■ If you need more detail, please refer to the BECON PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
127
Single Indoor Unit Ceiling Cassette 4-Way Product Data
13. ATNQ40GNLT6
13.4 Dimensions
13.4.1 Product
128
Single Indoor Unit Ceiling Cassette 4-Way Product Data
13. ATNQ40GNLT6
13.4.2 Install Space
≥ 10(13/32)
Ceiling Ceiling Board
Ceiling Board
≤ 300 (11-13/16)
≥ 1000(39-3/8) ≥ 500(19-11/16)
≥ 500(19-11/16)
A
1.6 ~ 10.0 kW = 2,000 (78-3/4) ≤ A ≤ 3,600 (141-24/32)
10.0~14.5 kW = 2,500 (98-7/16) ≤ A ≤ 4,200 (165-11/32)
Unit:mm(inch)
Floor
Note
■ Places where products are installed should not be any obstacles to the air circulation or installation. Ensure the spaces from the wall, ceiling,
or other obstacles.
■ According to type of indoor unit, external appearance or installed structure could be different.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.
■ Install certainly the decoration panel. Cool air leakage causes sweating or falling of water-drops.
129
Single Indoor Unit Ceiling Cassette 4-Way Product Data
13. ATNQ40GNLT6
Thermistor for
Evaporator inlet
Humidity sensor
temperature
130
Single Indoor Unit Ceiling Cassette 4-Way Product Data
13. ATNQ40GNLT6
131
Single Indoor Unit Ceiling Cassette 4-Way Product Data
13. ATNQ40GNLT6
High
Octave Band Sound Pressure Level (0dB = 20µPa)
70
NC -65
60
NC-60
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
NC-25
20
Approximate
NC-20
Hearing
Threshold
NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)
Note
■ Sound measured at some distance away from the center of the unit.
■ Data is valid at free field condition.
■ Reference accoustic pressure 0dB = 20μPa.
■ Data is valid at nominal operation condition.
Refer to the Model Specifications for nominal conditions(Power source and Ambient temperature, etc)
■ Sound levels can be increased in accordance with installation and operating conditions.
(Static pressure mode, used air guide, Room target temperature setting, etc)
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
132
Single Indoor Unit Ceiling Cassette 4-Way Product Data
13. ATNQ40GNLT6
2.7m
3.2m
0.25 0.25
0.5
2m
2m
Temperature [°C]
23 23 2.7m
3.2m
2m
2m
21 21
22 22
20 20 1m
1m
21
21 21 21
22 22
0m
0m
5m
5m 4m
4m 3m
3m 2m
2m 1m
1m 0m
0m 1m
1m 2m
2m 3m
3m 4m
4m 5m
5m
Note
■ These figures are accordance with normal certain condition and environment.
(Airflow step is 'High', Air discharge angle is fixed as indicated angle.)
■ Indoor airflow distribution under actual installation or operating conditions depends on ambient temperature, ceiling height, product installation direction /
location, indoor / Heating load, and other obstacles, etc.
133
Single Indoor Unit Ceiling Cassette 4-Way Product Data
ATNQ55GMLT6
14.
14. ATNQ55GMLT6
14.1 Specifications
Category
Unit Value
Major Minor
Classification Chassis - TM
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
kW 13.50
Cooling Capacity Nominal
Btu/h 46,000
kW -
Heating Capacity Nominal
Btu/h -
Power Input(Indoor) H/M/L W -
Running Current(Indoor) H/M/L A -
Type - 2D Turbo Fan
Air Flow Rate((SH)/H/M/L) m³/min - / 31.0 / 28.0 / 25.0
Indoor Fan
Air Flow Rate Range(Min~Max) m³/min -
External Static Pressure_Factory Set Pa -
Type - BLDC
Drive - -
Indoor Fan Motor
W 124
Output
No. 1
Rows x Columns x FPI - 3x12x19
Heat Exchanger No. - 1
Face Area m² 0.53
Net(W x H x D) mm 840 x 288 x 840
Dimensions
Shipping(W x H x D) mm 922 x 360 x 917
Net kg 28.5
Weight
Shipping kg 33.0
Color - Morning Fog
Exterior
RAL (Classic) - RAL 9001
Air Filter Type - Long Life
Fuse - O
Protection Device
Overload Protector for Fan Motor - -
Type - R410A
Refrigerant
Control Type - EEV
Drain Pipe(Natural Drainage) O.D / I.D mm(inch) -
Drain Pipe(Drain Pump) O.D / I.D mm(inch) 32/25
Liquid mm(inch) Φ9.52 (3/8)
Gas mm(inch) Φ19.05 (3/4)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Cooling ((SH)/H/M/L) dB(A) - / 47.0 / 45.0 / 42.0
Sound Pressure Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) -
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Cooling ((SH)/H/M/L) dB(A) -
Sound Power Level(Indoor Unit)
Heating ((SH)/H/M/L) dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power and Communication cable(H07RN-F) mm² × cores 0.75 x 4
Power Supply Type to Indoor - - -
Maximum Fuse Amperes (MFA) A 40
Electrical Characteristic
Indoor Fan Motor_Full Load Amperes (FLA) A 1.28
134
Single Indoor Unit Ceiling Cassette 4-Way Product Data
14. ATNQ55GMLT6
Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national code. And “Electric characteristics” should be considered for electrical work and design.
■ Especially the power cable and circuit breaker should be selected in accordance with that.
■ Sound Level Values are measured at Noise Measuring chamber accordance with standard. Therefore, these values depend on the ambient conditions and
values are normally higher in actual operation.
135
Single Indoor Unit Ceiling Cassette 4-Way Product Data
14. ATNQ55GMLT6
Note
■ O : Applied, X : Not Applied, - : Unconfirmed or irrelevant
- Embedded : A kit is provided by default for using this function when the product is manufactured.
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.
■ Some functions can be limited by remote controller.
■ In case of cassette type indoor units, Plasma kit and Auto Elevation Grille functions are not applicable at the same time.
■ 'Auto Mode' varies depending on the outdoor unit type.
- Auto Change Over(Single Heat Pump Outdoor Unit)
- Auto Mode Select(Multi Heat Pump Outdoor Unit)
- Auto Intensity Control(Cooling Only Outdoor Unit)
■ * : These functions need to connect the wired remote controller.
■ ** : This functions need to connect to the Standard III wired remote controller.
136
Single Indoor Unit Ceiling Cassette 4-Way Product Data
14. ATNQ55GMLT6
Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant.
■ * : Some advanced functions controlled by individual controller cannot be operated.
■ If there is a difference in development time between the product and the remote controller, some functions cannot be operated.
■ If you need more detail, please refer to the BECON PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
137
Single Indoor Unit Ceiling Cassette 4-Way Product Data
14. ATNQ55GMLT6
14.4 Dimensions
14.4.1 Product
PT-M*HW0
138
Single Indoor Unit Ceiling Cassette 4-Way Product Data
14. ATNQ55GMLT6
14.4.2 Install Space
≥ 10(13/32)
Ceiling Ceiling Board
Ceiling Board
≤ 300 (11-13/16)
≥ 1000(39-3/8) ≥ 500(19-11/16)
≥ 500(19-11/16)
A
1.6 ~ 10.0 kW = 2,000 (78-3/4) ≤ A ≤ 3,600 (141-24/32)
10.0~14.5 kW = 2,500 (98-7/16) ≤ A ≤ 4,200 (165-11/32)
Unit:mm(inch)
Floor
Note
■ Places where products are installed should not be any obstacles to the air circulation or installation. Ensure the spaces from the wall, ceiling,
or other obstacles.
■ According to type of indoor unit, external appearance or installed structure could be different.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.
■ Install certainly the decoration panel. Cool air leakage causes sweating or falling of water-drops.
139
Single Indoor Unit Ceiling Cassette 4-Way Product Data
14. ATNQ55GMLT6
Thermistor for
Evaporator inlet
Humidity sensor
temperature
140
Single Indoor Unit Ceiling Cassette 4-Way Product Data
14. ATNQ55GMLT6
141
Single Indoor Unit Ceiling Cassette 4-Way Product Data
14. ATNQ55GMLT6
70
Sound Pressure Level (dB re 20Pa )
NC-65
60
NC-60
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
20 NC-25
Approximate
NC-20
Hearing
Threshold NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)
Note
■ Sound measured at some distance away from the center of the unit.
■ Data is valid at free field condition.
■ Reference accoustic pressure 0dB = 20μPa.
■ Data is valid at nominal operation condition.
Refer to the Model Specifications for nominal conditions(Power source and Ambient temperature, etc)
■ Sound levels can be increased in accordance with installation and operating conditions.
(Static pressure mode, used air guide, Room target temperature setting, etc)
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
142
Single Indoor Unit Ceiling Cassette 4-Way Product Data
14. ATNQ55GMLT6
0.5 0.5 2m
2m
0.5
Temperature [°C]
23 23 3.2m
3.2m
3m
20 20 2m
22 22 22 22
21 23 23 21 1m
0m
0m
5m
5m 4m
4m 3m
3m 2m
2m 1m
1m 0m
0m 1m
1m 2m 3m
3m 4m 5m
5m
Note
■ These figures are accordance with normal certain condition and environment.
(Airflow step is 'High', Air discharge angle is fixed as indicated angle.)
■ Indoor airflow distribution under actual installation or operating conditions depends on ambient temperature, ceiling height, product installation direction /
location, indoor / Heating load, and other obstacles, etc.
143
Indoor Units
Installation
1.Selection of the best Location
2.Precautions regarding cassette indoor unit installation
3.Connecting pipes
4.Electrical Wiring
5.Drain pipe connection
Indoor Units Installation
Take enough
distance
(Min. 500 mm)
Use the ventilation fan
for smoke-collecting
hood with sufficient
capacity.
Cooking table
2. Avoid installing the unit in such places where cooking oil or iron powder is generated.
3. Avoid places where inflammable gas is generated.
4. Avoid places where noxious gas is generated.
5. Avoid places near high frequency generators.
CAUTION
• If the temperature rise above 30℃ or the humidity rise above RH 80%, additional insulation working is needed
to the unit body for protection of dew formation.
– Use the glass wool material or polyethylene foam and it make sure to be thick of 10mm at least.
2
Indoor Units Installation
■ In case the floor or surfaces is contact with the outdoor air directly
If the floor of air conditioned room contact with the outside air, like the store room or garage, the floor
temperature will be decreased and users can have a cold feeling in the feet.
In such places where the feet comes in direct contact with floors will give a cold feeling to the foot.
• Countermeasure method
Indoor
1.Use the carpet on the floor.
Low temperature
(compared to the tiles the carpet over it will have a 3 degree rise in
of the floor temperature)
2.Insulating the floor.
(50~100mm
3.Floor heating.
Outdoor side
Insulation required)
Outdoor side Garage
Outdoor side
CAUTION
In case there is a cold air intake, the duct surface may have some dew drops.
So a insulation on the duct is a must.(Insulation material: a glass wool of thickness 25 mm will be appropriate.)
Lighting Ceiling
1,500mm or more
1,500mm or more
2,000mm or more
3,000mm or more 2,000mm or more
3,000mm or more
※ According to type of indoor unit, external appearance could be different.
3
Indoor Units Installation
• In case of places having the temperature and humidity of the Psychrometric chart
surrounding water sources(sea, river etc.)
• In case the steam is generated between the false ceiling and Enhance additional
insulation required area
the ceiling slab due to some nearby by steam source.
• In case of temperature of 30 degree and humidity above
80%, the units body as well as the piping insulation should
be strengthened. Refer to the psychrometric chart.
• Countermeasure method
– Indoor unit: Insulate the unit body with some insulation like glass wool at least 10 mm in thickness.
– Refrigerant piping: Increase the piping insulation thickness with thickness above 20 mm.
– Others: Inside the ceiling near th air tight seal places. (No escape of the humidity inside false ceiling)
Note
• According to type of indoor unit, external appearance or installed structure could be different.
• According to product type, model line up, sales region..etc, applicability of each chassis could be different.
4
Indoor Units Installation
3. Connecting pipes
CAUTION
• When mechanical connectors are reused, indoors’ sealing parts shall be renewed. (for R32)
• When flared joints are reused, indoors’ the flare part shall be re-fabricated. (for R32)
Thermal insulation for refrigerant pipe • Heat insulation material : Adiabatic glass wool with
(Local supply) Thermal insulation for thickness of 10~20mm(13/32 ~13/16 inch).
piping(Local supply) • Stick glass wool on all air conditioners that are located
in ceiling atmosphere.
Overlap with
insulation
CAUTION
• Make sure to insulate any field piping all the way to the piping connection inside the unit. Any exposed piping
may cause condensation or burns if touched.
5
Indoor Units Installation
4. Electrical Wiring
• All field supplied parts and materials, electric works must conform to local codes. Use copper wire only.
• Follow the "WIRING DIAGRAM” attached to the unit body to wire the outdoor unit, indoor units and the remote
controller.
• All wiring must be performed by an authorized electrician.
• A circuit breaker capable of shutting down the power supply to the entire system must be installed.
CAUTION
After the confirmation of the above conditions, prepare the wiring as follows:
– Never fail to have separate power specially for the air conditioner.
– Provide a circuit breaker switch between power source and the unit.
– Confirm the Specification of power source.
– Confirm that electrical capacity is sufficient.
– Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the
name plate.
– Confirm that the cable thickness is as specified in the power sources specification.
(Particularly note the relation between cable length and thickness.)
– Do not install the leakage breaker in a place which is wet or moist.
Water or moist may cause short circuit.
– The following troubles would be caused by voltage drop-down.
» Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the
normal function of a overload protection device.
» Proper starting power is not given to the compressor.
■ Wiring Connections
• Connect the wires to the terminals on the control board individually according to the outdoor unit connection.
• Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit
respectively.
• In case of the system with multiple indoor units, mark each indoor unit as unit A, unit B, etc and be sure the
terminal board wiring to the outdoor unit and indoor units are properly matched. If wiring and piping between the
outdoor unit and an indoor unit are mismatched, the system may cause a malfunction.
WARNING
• Make sure that the screws of the terminal are fixed tightly.
• The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to
which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly
fastened. (If they are loose, it could give rise to burn-out of the wires.)
• Make sure to attach the sealing material or (field supplied) to hole of wiring to prevent the infiltration of foreign
particle from outside. Otherwise a short-circuit may occur inside the electric parts box.
• When clamping the wires, be sure no pressure is applied to the wire connections by using the included clamping
material to make appropriate clamps. Also, when wiring, make sure the cover on the electric parts box fits snugly
by arranging the wires neatly and attaching the electric parts box cover firmly. When attaching the electric parts
box cover, make sure no wires get caught in the edges. Pass wiring through the wiring through holes to prevent
damage to them.
• Make sure the remote controller wiring, the wiring between the units, and other electrical wiring do not pass
through the same locations outside of the unit, separating them properly, otherwise electrical noise (external
static) could cause product malfunction.
6
Indoor Units Installation
4. Electrical Wiring
Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average
temperature.
7
Indoor Units Installation
drain head
* height of
clamp
slope (1/50~1/100 )
Flexible drain hose
Thermal Insulation
Drain Pump
※ * : drain head height should be considered by dimensional drawings of each models.
※ According to type of indoor unit, external appearance could be different. ※ According to type of indoor unit, external appearance could be different.
Indoor Unit
Metal clamp
Thermal insulation(bend area)
※ According to type of indoor unit,
Drain pan external appearance could be different.
8
Indoor Units Installation
CAUTION
• The supplied flexible drain hose should not be curved, neither screwed. The curved or screwed hose may cause
a leakage of water.
• It is need to insulate the auxiliary drain hose with thermal insulation material.
– When extending the drain hose, use a commercially Additional extension drain piping
available drain extension hose, and be sure to (Field supply part) Insulating tape
insulate the extended section of the drain hose
which is indoors.
– Make sure the diameter of the extension drain piping
is the same as the indoor unit drain hose size or
bigger. Bigger Ø drain pipes Indoor unit drain hose
Indoor
Unit
Indoor
Unit
Vent pipe
Face the vent pipe opening facing downward to
keep foreign matter from penetrating the system
Note
• According to type of indoor unit, external appearance or installed structure could be different.
• According to product type, model line up, sales region..etc, applicability of each chassis could be different.
9
ACCESSORY
Accessory
1.Air Purification Kit
2.UVnano Filter Box Kit
ACCESSORY
1. Specification
1way Cassette
Specification Unit
TU TT
Air Purification Kit Model - PTAHTP0
Air Purification Panel - PT-UPHG0 PT-TPHG0
Size (W x H x D) mm 59 x 45 x 22
PM1.0 Sensor Supply Voltage V 5
Measure - PM1.0 / PM2.5 / PM10
Size (W x H x D) mm 99 X 50 X 30
Input - DC 12V
HVPS
Output
(Electrification / - -7.7kV / -5.2kV
Dust Collection)
Size (W x H x D) mm 524 x 18 x 141
PM1.0 Filter
Weight g 430
Material - Pulp + Carbon (Corrugate)
Deodorization filter Size (W x H x D) mm 301 x 11 x 100
Weight g 40
Size (W x H x D) mm 71 x 19 x 30
Input - DC 12V
Ionizer Output - -3.2kV
Amount of Ion
emission EA/cc 3,000,000
4way Cassette
Specification Unit
TP / TN / TM TP-B / TM-A
Air Purification Kit Model - PTAHMP0
Air Purification Panel - PT-MPGW0 (U-style) PT-AFGW0 (Dual Vane)
Size (W x H x D) mm 59 x 45 x 22
PM1.0 Sensor Supply Voltage V 5
Measure - PM1.0 / PM2.5 / PM10
Size (W x H x D) mm 99 X 50 X 30
Input - DC 12V
HVPS
Output
(Electrification / - -7.7kV / -5.2kV
Dust Collection)
Size (W x H x D) mm 500 x 38 x 395
PM1.0 Filter
Weight g 2,090
Material - Pulp + Carbon (Corrugate)
Deodorization filter Size (W x H x D) mm 478 x 14 x 138
Weight g 180
Size (W x H x D) mm 71 x 19 x 30
Input - DC 12V
Ionizer Output - -3.2kV
Amount of Ion
EA/cc 3,000,000
emission
2
Air Purification Kit
1. Specification
Round Cassette
Specification Unit
TY
Air Purification Kit Model - PTAHYP0
Air Purification Panel - -
Size (W x H x D) mm 59 x 45 x 16.6
PM1.0 Sensor Supply Voltage V 5
Measure - PM1.0 / PM2.5 / PM10
Size (W x H x D) mm 99 X 50 X 30
Input - DC 12V
HVPS
Output
(Electrification / - -7.7kV / -5.2kV
Dust Collection)
Size (W x H x D) mm 500 x 38 x 395
PM1.0 Filter
Weight g 2,090
Material - Pulp + Carbon (Corrugate)
Deodorization filter Size (W x H x D) mm 478 x 14 x 138
Weight g 180
Size (W x H x D) mm -
Input - -
Ionizer Output - -
Amount of Ion
emission EA/cc -
3
ACCESSORY
1. Specification
Model PBM13M1UA0 PBM13M2UA0 PBM13M3UA0
Unit
Applied Chassis M1 M2 M3
Net Size (W x H x D) mm 900 x 270 x 280 1,250 x 270 x 280 1,250 x 360 x 280
Shipping Size (W x H x D) mm 1,048 x 340 x 377 1,440 x 340 x 377 1,440 x 430 x 377
Net Weight kg 9.1 11.6 12.7
Shipping Weight kg 11.4 14.7 16.2
Size(W x H x D) mm 600 x 251 x 50.8 600 x 251 x 50.8 600 x 341 x 50.8
Quantity EA 1 2 2
Filter (1)
Grade 1 - ePM1 65% ePM1 65% ePM1 65%
Grade 2 - MERV 13 MERV 13 MERV 13
Size(W x H x D) mm 250 x 251 x 50.8 - -
Quantity EA 1 - -
Filter (2)
Grade 1 - ePM1 65% - -
Grade 2 - MERV 13 - -
Size(W x H x D) mm 596 x 247 x 4 596 x 247 x 4 596 x 377 x 4
Mesh - 34 x 39 34 x 39 34 x 39
Pre-Filter (1)
Color - BLACK BLACK BLACK
Quantity - 1 2 2
Size(W x H x D) mm 247 x 247 x 4 - -
Mesh - 34 x 39 - -
Pre-Filter (2)
Color - BLACK - -
Quantity EA 1 - -
LED Quantity EA 8 8 8
UVnano Input V DC 12V DC 12V DC 12V
Wavelength nm 275 275 275
Note
1. Grade 1 : ISO EN 16890
2. Grade 2 : ASHRAE 52.2
2
UVnano Filter Box
2. Dimensions
PBM13M1UA0
3
UVnano Filter Box
2. Dimensions
PBM13M2UA0
4
UVnano Filter Box
2. Dimensions
PBM13M3UA0
5
UVnano Filter Box
140 SV
135 SV
130 SV
125 SV
120 SV
115 SV
110 SV
75 SV 80 SV 85SV 90 SV 95 SV 100 SV 105 SV
"JS'MPX $..
Note
1. SV : Setting Value
2. The available range of External Static Pressure and Setting Value depends on the applied model.
Please check the specifications of the applied model.
3. Auto E.S.P Setting is also available with UVnano Filter Box.
140 SV
135 SV
130 SV
125 SV
95 SV 100 SV 105 SV 110 SV 115 SV 120 SV
"JS'MPX $..
Note
1. SV : Setting Value
2. The available range of External Static Pressure and Setting Value depends on the applied model.
Please check the specifications of the applied model.
3. Auto E.S.P Setting is also available with UVnano Filter Box.
6
UVnano Filter Box
120 SV
115 SV
110 SV
90 SV 95 SV 100 SV 105 SV
"JS'MPX $..
Note
1. SV : Setting Value
2. The available range of External Static Pressure and Setting Value depends on the applied model.
Please check the specifications of the applied model.
3. Auto E.S.P Setting is also available with UVnano Filter Box.
4. This PQ Curve is for ABN*30GM2** only.
&YUFSOBM4UBUJD1SFTTVSF NN"R 1B
150 SV
145 SV
140 SV
105 SV 110 SV 115 SV 120 SV 125 SV 130 SV 135 SV
"JS'MPX $..
Note
1. SV : Setting Value
2. The available range of External Static Pressure and Setting Value depends on the applied model.
Please check the specifications of the applied model.
3. Auto E.S.P Setting is also available with UVnano Filter Box.
7
UVnano Filter Box
125 SV
120 SV
115 SV
110 SV
75 SV 80 SV 85 SV 90 SV 95 SV 100 SV 105 SV
"JS'MPX $..
Note
1. SV : Setting Value
2. The available range of External Static Pressure and Setting Value depends on the applied model.
Please check the specifications of the applied model.
3. Auto E.S.P Setting is also available with UVnano Filter Box.
100 SV
95 SV
90 SV
80 SV 85 SV
70 SV 75 SV
"JS'MPX $..
Note
1. SV : Setting Value
2. The available range of External Static Pressure and Setting Value depends on the applied model.
Please check the specifications of the applied model.
3. Auto E.S.P Setting is also available with UVnano Filter Box.
4. This PQ Curve is for ABN*36GM3** only.
8
Air Solution
LG Electronics Inc, 128, Yeoui-daero,
Yeongdeungpo-gu, Seoul, Korea
(07336)
http://partner.lge.com
http://sedc.lge.com
The air conditioners manufactured by LG have received ISO9001 certificate for quality assurance
and ISO14001 certificate for environmental management system.
The specifications, designs, and information in this brochure are subject to change without notice.