Modbus Addresses

The document discusses the Modbus protocol and its use for interfacing with easYgen controllers. It describes Modbus as a serial communications standard used with PLCs and provides recommendations for Modbus master software. It also outlines the settings and wiring required to configure the Modbus interface on easYgen controllers and how to read register values at specific Modbus addresses, including techniques for reading 32-bit values. Finally, it discusses using Modbus to remotely control functions of easYgen such as start/stop in auto mode.

Uploaded by

joseph.i
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
17 views

Modbus Addresses

The document discusses the Modbus protocol and its use for interfacing with easYgen controllers. It describes Modbus as a serial communications standard used with PLCs and provides recommendations for Modbus master software. It also outlines the settings and wiring required to configure the Modbus interface on easYgen controllers and how to read register values at specific Modbus addresses, including techniques for reading 32-bit values. Finally, it discusses using Modbus to remotely control functions of easYgen such as start/stop in auto mode.

Uploaded by

joseph.i
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 25

KG-1500

Interface-Modbus

PROPRIETARY INFORMATION - © 2017 WOODWARD, INC. PAGE 1


Interface Modbus
Modbus Protocol

Modbus is a serial communications protocol published by Modicon in 1979 for use with its
programmable logic controllers (PLCs). It has become a de facto standard communications
protocol in industry, and is now the most commonly available means of connecting
industrial electronic devices.

There are also various tools available on the internet. We recommend using ModScan32
which is a Windows application designed to operate as a Modbus Master device for
accessing data points in a connected Modbus Slave device. It is designed primarily as a
testing device for verification of correct protocol operation in new or existing systems.

A trial version download is available from the following website:


http://www.win-tech.com/html/modscan32.htm

PROPRIETARY INFORMATION - © 2017 WOODWARD, INC. PAGE 2


Interface Modbus
Modbus interface setting in easYgen for BMS/SCADA or PLC.

You can change this


parameter as per the
requirement

Settings in these
three screens are
related to setting of
Modbus

PROPRIETARY INFORMATION - © 2017 WOODWARD, INC. PAGE 3


Interface Modbus
Modbus interface setting in easYgen for BMS/SCADA or PLC.
Slave ID is must and is required to
identify this device on Modbus
communication, so it has to be unique
and can in range of 1-255

Reply delay time needs to be set. We


have seen that many a times this
value is “0” and so the customer is
not able to receive any value on the
Modbus.

PROPRIETARY INFORMATION - © 2017 WOODWARD, INC. PAGE 4


Interface Modbus
Modbus interface – Wiring on easYgen (half duplex / full duplex)

120 ohms
terminating register
is must

PROPRIETARY INFORMATION - © 2017 WOODWARD, INC. PAGE 5


Interface Modbus
Modbus Protocol number

Every protocol number has different Modbus addresses, so


when you are entering the Modbus register address in
easYgen model Protocol Number SCADA/BMS, first please refer to the data protocol in the
egY 2000 Sr. 5100 manual and then refer to the corresponding Modbus address
for these protocol. Example shown below.

PROPRIETARY INFORMATION - © 2017 WOODWARD, INC. PAGE 6


Interface Modbus
Reading Modbus address Description against each address

Multiplier against each


This is Modbus address
addresses is used to
to be used for getting
multiple the values that
the values. The first digit
is read in Modbus to get
i.e. 4 is not to be used for
address it is indicating the correct value.
function code (4=holding
register) so the address
starts from 50001

Unit of the Modbus value

Here it shows
whether it is
16bit/2byte register
or 32bit/4byte
register

PROPRIETARY INFORMATION - © 2017 WOODWARD, INC. PAGE 7


Interface Modbus
Reading Modbus address with Multiplier as Mask
How to read the mask value against Modbus address

Mask 000F hex means, we have to make a logical AND


combination

for e.g. I am in STOP mode, and I got this binary information.


Result: 0000 0000 0000 0010

If we now look, at which bit position we get a TRUE value,


when we make a AND equation.
Here the second digit on the right would become TRUE.

In decimal this is = 2. And 2 = STOP as shown in the table.

Similarly if result is
Result: 0000 0000 0000 0001

In decimal this is = 1. And 1 = AUTO as shown in the table

PROPRIETARY INFORMATION - © 2017 WOODWARD, INC. PAGE 8


Interface Modbus
Reading 16 bit and 32 bit Modbus values

For 16 bit Modbus values there is no problem and it can be directly read from easYgen. But for 32 bit you have to
add to Modbus addresses and then you will get the correct value.

See below example for reading 32 bit value on Modbus:


Reading the value of genset hours of operation on Modbus

Starting at Modicon start address 450026 (Av. Gen.


Current).You can see that the next address shown
is 450028. This means the value for “Av. Gen.
Current” consist of two addresses i.e. 450026 and
450027 (1 addr. = 2 bytes so 4 Bytes is total). Keep
an eye on the order of the addresses when looking
for certain value, so you know how many registers
you need to read.

PROPRIETARY INFORMATION - © 2017 WOODWARD, INC. PAGE 9


Interface Modbus
Reading 16 bit and 32 bit Modbus values
Below screen shows 10 address read in one step on Modbus Software

Now to get the “Gen. hours of operation” value correctly


which has 4 byte value, put the first 2-byte and the second
2-byte together i.e. here = 0001 41A9 (hex format) =
82345 (decimal format) * 0.01 (multiplier) = 823.45 hrs.

Similarly here if we want the value of another 32 bit


register like “Active Power setpoint”. The address for this is
450131 and 450132, so here = 0000 03E8 (hex format)=
1000 (decimal format) * 0.1 (multiplier) = 100 kW.

PROPRIETARY INFORMATION - © 2017 WOODWARD, INC. PAGE 10


Interface Modbus
Remote control of easYgen – via Modbus

The Woodward controller can be configured to perform start/stop/acknowledgement functions


remotely through the Modbus protocol and you can even control the Voltage/PF/Frequency and
Power(kW) remotely via Modbus. Refer below for few examples.
Example: Remote Start / Stop in Auto mode via control bit (Modbus)

In LogicsManager of Start req. in Auto configure 3rd


variable as “04.13 Remote request” as shown in the
picture

PROPRIETARY INFORMATION - © 2017 WOODWARD, INC. PAGE 11


Interface Modbus
Remote control of easYgen – via Modbus

In order to issue a command, the respective bit of object 21F7


(hex), i.e. parameter 503, must be enabled. The following bits are
used for this:

 Bit 0 Start bit: This bit activates the LogicsManager command


variable “04.13 Remote request" and enables a remote
request command.
 Bit 1 Stop bit: This bit deactivates the LogicsManager
command variable “04.13 Remote request" and disables a
remote request command.

PROPRIETARY INFORMATION - © 2017 WOODWARD, INC. PAGE 12


Interface Modbus
Remote control of easYgen – via Modbus
The following Modscan32 screenshot shows the
configurations made to remote control
parameter 503. It is possible to set the format to
binary to view single bits using the "display
options".

PROPRIETARY INFORMATION - © 2017 WOODWARD, INC. PAGE 13


Interface Modbus
Remote control of easYgen – via Modbus

Example 1: Start Request Auto Mode


By double-clicking the address, a Write Register command may be
issued.
shows how bit 0 is set using the ModScan32 Software.

Example 2: Stop Request Auto Mode


By double-clicking the address, a Write Register command may be
issued.
shows how bit 1 is set using the ModScan32 Software.

PROPRIETARY INFORMATION - © 2017 WOODWARD, INC. PAGE 14


Interface Modbus
Remote control of easYgen – via Modbus

Assignment of respective bit of object 21F7


(hex), i.e. parameter 503.

PROPRIETARY INFORMATION - © 2017 WOODWARD, INC. PAGE 15


Interface Modbus
Remote control of easYgen – via Modbus
Example: Remote Start / Stop in manual mode via control bit (Modbus)

In LogicsManager of MAN engine start configure


1st variable as “04.44 RemoteControl Bit 1” as
shown in the picture

In LogicsManager of MAN engine stop configure


1st variable as “04.45 RemoteControl Bit 2” as
shown in the picture

PROPRIETARY INFORMATION - © 2017 WOODWARD, INC. PAGE 16


Interface Modbus
Remote control of easYgen – via Modbus

In order to issue a command, the respective bit of object


21F9 (hex), i.e. parameter 505, must be enabled

Example 1: Start in Manual mode


By double-clicking the address, a Write Register command may be
issued.
shows how bit 0 is set using the ModScan32 Software.

Example 2: Stop in Manual mode


By double-clicking the address, a Write Register command may be
issued.
shows how bit 1 is set using the ModScan32 Software.

PROPRIETARY INFORMATION - © 2017 WOODWARD, INC. PAGE 17


Interface Modbus
Remote control of easYgen – via Modbus
Example: Remote GCB Open / Close in manual mode via control bit (Modbus)

In LogicsManager of GCB open in MAN configure


1st variable as “04.46 RemoteControl Bit 3” as
shown in the picture

In LogicsManager of GCB close in MAN configure


1st variable as “04.47 RemoteControl Bit 4” as
shown in the picture

PROPRIETARY INFORMATION - © 2017 WOODWARD, INC. PAGE 18


Interface Modbus
Remote control of easYgen – via Modbus

In order to issue a command, the respective bit of object


21F9 (hex), i.e. parameter 505, must be enabled

Example 1: GCB open in Manual mode


By double-clicking the address, a Write Register command may be
issued.
shows how bit 2 is set using the ModScan32 Software.

Example 2: GCB close in Manual mode


By double-clicking the address, a Write Register command may be
issued.
shows how bit 3 is set using the ModScan32 Software.

PROPRIETARY INFORMATION - © 2017 WOODWARD, INC. PAGE 19


Interface Modbus
Remote control of easYgen – via Modbus

Example: Active Power setpoint


For a remote setting of the control setpoints,
it is necessary to use the interface setpoints
instead of the internal setpoints. For
example, use data source "05.06 Interface
pwr. setp." in parameter 5540 (Load setpoint
2 source) to transmit load setpoint via
interface. No password is required to write
this value. shows an exemplary configuration
of the load setpoint 1 source. All other
setpoint sources are configured accordingly.

Note: The interface setpoints may be set using the objects 21F8 and 21FB (hex) i.e. parameter 504 and 507 respectively
for active power.
PROPRIETARY INFORMATION - © 2017 WOODWARD, INC. PAGE 20
Interface Modbus
Remote control of easYgen – via Modbus

The active power setpoint value must be written to object 21FB(hex), i.e. parameter 507.

PROPRIETARY INFORMATION - © 2017 WOODWARD, INC. PAGE 21


Interface Modbus
Remote control of easYgen – via Modbus
The following Modscan32 screenshot shows the
configurations made to remote control parameter
507. The format used here is hex.

1. Open the "Preset Multiple Registers" dialog by


selecting “Setup -> Extended -> Preset Regs” from
the menu.
2. Select “OK” and enter the desired values.

PROPRIETARY INFORMATION - © 2017 WOODWARD, INC. PAGE 22


Interface Modbus
Remote control of easYgen – via Modbus

The dialog closes and the values are changed.

Select “Update” to confirm the entered values.

PROPRIETARY INFORMATION - © 2017 WOODWARD, INC. PAGE 23


Interface Modbus
Remote control of easYgen – via Modbus
In object 21F8(hex), i.e. parameter
504 each bit represents activation
of different setpoints .
In order to activate the setpoint, the respective bit of
object 21F8 (hex), i.e. parameter 508, must be
enabled. The following bits are used for:

 Bit 4 for Voltage (V).


 Bit 5 for Frequency (Hz).
 Bit 6 for Power Factor (PF).
 Bit 7 for Active power (kW).

PROPRIETARY INFORMATION - © 2017 WOODWARD, INC. PAGE 24