Modbus Addresses
Modbus Addresses
Interface-Modbus
Modbus is a serial communications protocol published by Modicon in 1979 for use with its
programmable logic controllers (PLCs). It has become a de facto standard communications
protocol in industry, and is now the most commonly available means of connecting
industrial electronic devices.
There are also various tools available on the internet. We recommend using ModScan32
which is a Windows application designed to operate as a Modbus Master device for
accessing data points in a connected Modbus Slave device. It is designed primarily as a
testing device for verification of correct protocol operation in new or existing systems.
Settings in these
three screens are
related to setting of
Modbus
120 ohms
terminating register
is must
Here it shows
whether it is
16bit/2byte register
or 32bit/4byte
register
Similarly if result is
Result: 0000 0000 0000 0001
For 16 bit Modbus values there is no problem and it can be directly read from easYgen. But for 32 bit you have to
add to Modbus addresses and then you will get the correct value.
Note: The interface setpoints may be set using the objects 21F8 and 21FB (hex) i.e. parameter 504 and 507 respectively
for active power.
PROPRIETARY INFORMATION - © 2017 WOODWARD, INC. PAGE 20
Interface Modbus
Remote control of easYgen – via Modbus
The active power setpoint value must be written to object 21FB(hex), i.e. parameter 507.