Three Phase Transformer - Tutorial - 15.09.2023
Three Phase Transformer - Tutorial - 15.09.2023
Tutorial
By
Dr. Krishna Roy
Assistant Professor
Electrical Engineering Department
NITR
Example1: A three phase step-down transformer is energized from 11kV, 50
Hz source. If it takes a line current of 20 A from the supply mains then
calculate the output voltage, output current and output kVA for each of the
following connections:
Star/star (b) star/delta (c) delta/star (d) delta/delta.
The magnetizing current and losses are ignored. Per phase turns ratio is 44.
(a) Star/star
11000
Per phase primary voltage V 6351 V
3
Per phase secondary voltage 6351 V 144.34 V
44
Therefore, secondary line voltage 144.34 3 V 250 V output voltage
(b) Star/delta
11000
Per phase primary voltage V 6351 V
3
Per phase secondary voltage 6351 V 144.34 V output voltage
44
Primary phase current 20A
Secondary phase current 20 44 A 880 A
Therefore, secondary line current 880 3 A 1524.16 A output current
3
Example1: A three phase step-down transformer is energized from 11kV, 50
Hz source. If it takes a line current of 20 A from the supply mains then
calculate the output voltage, output current and output kVA for each of the
following connections:
Star/star (b) star/delta (c) delta/star (d) delta/delta.
The magnetizing current and losses are ignored. Per phase turns ratio is 44.
(c) Delta/star
Per phase primary voltage 11000 V
4
Example1: A three phase step-down transformer is energized from 11kV, 50
Hz source. If it takes a line current of 20 A from the supply mains then
calculate the output voltage, output current and output kVA for each of the
following connections:
Star/star (b) star/delta (c) delta/star (d) delta/delta.
The magnetizing current and losses are ignored. Per phase turns ratio is 44.
(d) Delta/delta
Per phase primary voltage 11000 V
5
Example2: Three single phase transformers, connected in delta/delta supply
a balanced three phase load of 150 kW at 440 volt at 0.8 pf lagging. The
transformers are supplied from three phase mains at 11 kV. Find the currents
in the windings of each of the transformers. If one transformer is found
faulty and is removed and the supply is maintained in V-V connection,
determine the currents in the windings and power supplied by each of the
transformers.
Delta/delta
Secondary load P 150 kW pf cos 0.8 lag
Secondary voltage VLS 440 V primary voltage VLP 11000 V
P 150 1000
I
Secondary line current, LS A
3 VLS cos 3 440 0.8
246 A
VLS 440
Primary line current I LP I LS 246 A 9.84 A
VLP 11000
I 9.84
Primary phase current I phP LP A 5.68 A
3 3
I 246
Secondary phase current I phS LS A 142.03 A
3 3
6
Example2: Three single phase transformers, connected in delta/delta supply
a balanced three phase load of 150 kW at 440 volt at 0.8 pf lagging. The
transformers are supplied from three phase mains at 11 kV. Find the currents
in the windings of each of the transformers. If one transformer is found
faulty and is removed and the supply is maintained in V-V connection,
determine the currents in the windings and power supplied by each of the
transformers.
Open delta
Secondary load P 150 kW pf cos 0.8 lag
Secondary voltage VLS 440 V primary voltage VLP 11000 V
Secondary line current, I LS 246 A
Secondary phase current = Secondary line current I phS 246 A
440
Primary phase current I phP I LS turns ratio 246 A 9.84 A
11000
7
Example2: Three single phase transformers, connected in delta/delta supply
a balanced three phase load of 150 kW at 440 volt at 0.8 pf lagging. The
transformers are supplied from three phase mains at 11 kV. Find the currents
in the windings of each of the transformers. If one transformer is found
faulty and is removed and the supply is maintained in V-V connection,
determine the currents in the windings and power supplied by each of the
transformers.
Open delta
Secondary load P 150 kW pf cos 0.8 lag
Secondary voltage VLS 440 V primary voltage VLP 11000 V
Power delivered by the 1st transformer, P1 440 246 cos 30 36.87 W
42.52 kW
Power delivered by the 2nd transformer, P2 440 246 cos 30 36.87 W
107.47 kW
8
Example3: Resistive loads of 5Ω and 10Ω are connected respectively across
the teaser and main transformer secondaries of a Scott-connected
arrangement of transformers, fed from 3-phase, 230V supply mains. If the
main transformers primary to secondary turns ratio is 2, then determine the
supply line currents. The magnetizing currents and the internal impedance
drops are neglected.
9
Example3: Resistive loads of 5Ω and 10Ω are connected respectively across
the teaser and main transformer secondaries of a Scott-connected
arrangement of transformers, fed from 3-phase, 230V supply mains. If the
main transformers primary to secondary turns ratio is 2, then determine the
supply line currents. The magnetizing currents and the internal impedance
drops are neglected.
= 8.784 A = IC
10