C700D5
C700D5
C700D5
Model: C700 D5
Frequency: 50
Fuel Type: Diesel
Standby Standby
Fuel consumption kVA (kW) kVA (kW)
Ratings 706 (565) 640 (512)
Load 1/4 1/2 3/4 Full 1/4 1/2 3/4 Full
gph 10.8 17.6 25.1 33.8 9.5 16.0 22.9 30.8
L/hr 49.00 80.00 114.00 154.00 43.00 73.00 104.00 140.00
Fuel flow
Maximum fuel flow, L/hr 337
Maximum fuel inlet restriction, mm Hg 203
Maximum fuel inlet temperature (°C) 70
©2011 | Cummins Power Generation Inc. | All rights reserved | Specifications subject to change without notice | Cummins Power Generation and Cummins are registered trademarks of Cummins Inc.
PowerCommand and “Our energy working for you.” are trademarks of Cummins Power Generation. Other company, product, or service names may be trademarks or service marks of others.
Document no. DS366-CPGK-RevC - 3/1/2012
Air Standby Rating Standby Rating
Combustion air, m 3/min 52.60 49.50
Maximum air cleaner restriction, kPa 6.2
Exhaust
Exhaust gas flow at set rated load, m3/min 122.8 119.1
Exhaust gas temperature, °C 507.2 493.3
Maximum exhaust back pressure, kPa 10.2
Genset outline
Open set
Enclosed set
Outlines are for illustrative purposes only. Please refer to the genset outline drawing for an exact representation of this model.
©2011 | Cummins Power Generation Inc. | All rights reserved | Specifications subject to change without notice | Cummins Power Generation and Cummins are registered trademarks of Cummins Inc.
PowerCommand and “Our energy working for you.” are trademarks of Cummins Power Generation. Other company, product, or service names may be trademarks or service marks of others.
Document no. DS366-CPGK-RevC - 3/1/2012
Alternator data
Connection 1 Temp rise °C Duty2 Alternator Voltage
Wye, 3 Phase 150/125C S/P HC6G 380-440V
Wye, 3 Phase 150/125C S/P HC5F 380-415V
Ratings definitions
Emergency Standby Limited-Time running Prime Power (PRP) Base Load (Continuous)
Power (ESP) Power (LTP): Power (COP)
Applicable for supplying power to Applicable for supplying power to a Applicable for supplying power to Applicable for supplying power
varying electrical load for the constant electrical load for limited varying electrical load for unlimited continuously to a constant electrical
duration of power interruption of a hours. Limited Time Running Power hours. Prime Power (PRP) is in load for unlimited hours. Continuous
reliable utility source. Emergency (LTP) is in accordance with ISO accordance with ISO 8528. Ten Power (COP) in accordance with ISO
Standby Power (ESP) is in 8528. percent overload capability is 8528, ISO 3046, AS 2789, DIN 6271
accordance with ISO 8528. Fuel available in accordance with ISO and BS 5514.
Stop power in accordance with ISO 3046, AS 2789, DIN 6271 and BS
3046, AS 2789, DIN 6271 and BS 5514.
5514.