Power Capacitors S.A.C.: Seleccion de Celdas de Media Tension Interruptore de Media Tension

Download as pdf or txt
Download as pdf or txt
You are on page 1of 17

POWER CAPACITORS S.A.C.

SELECCION DE CELDAS DE
MEDIA TENSION

INTERRUPTORE DE MEDIA
TENSION
Ingeniería de Aplicaciones – Consorcio Minero Horizonte S.A / Mayo 2015

Power Capacitors SAC August 22, 2015 | Slide 7


Caracteristicas que definen el interruptor
 Available versions
 Fixed and withdrawable with front operating mechanism
 Withdrawable for UniSafe and UniGear type ZS1 switchgears
 Available models (Jan. 2003)
 12 kV, … 2500 A, … 31.5 kA
 17.5 kV, … 2500 A, … 31.5 kA
 24 kV, … 2500 A, … 25 kA

 Compliance to the STDs


 IEC 62271-100 (2001-05)
 Fields of application
 Power distribution
 Cable control and protection
 Overhead control and protection
 Transformation and distribution substations
 Motor and transformer control and protection
 Generator control and protection
 Capacitor bank control and protection
 Vacuum interrupter
(principle structure )
1

2 1 Stem/Terminal
3 2 Twist protection
4 3 Bellow
5 4 Interrupter lid
5 Shield
6

6 Ceramic insulator
7
7 Shield
8
8 Contacts
9
9 Stem/Terminal
1
10 Interrupter lid
0
 Embedded pole
1
(principle structure )

2
1 Upper terminal
3
2 Vacuum interrupter
4 3 Epoxy resin
5 4 Stem
6 5 Lower terminal
7 6 Flexible connection
7 Contact force spring
8
8 Push rod
9
9 Fixing point
1
0
10 Operating mechanism connection
 New VD4: Embedded poles
Pol Rated Rated Rated short-circuit
e current breaking current
voltage
Typ A kA

12
kV 630 20
eP1
12 / 17.5 630 25
P1
12 / 17.5 1250 25
P1
P1 P2 12 / 17.5 1250 31.5
P1
P2 12 / 17.5 2500 (1) 31.5

P4 24 630 16

P4
24 1250 20
P4 24 1250 25

P5 24 2500 (1) 25

P4 P5 (1) 2500 A pole with heat-sink.


 Fixed circuit-
breakers

12 kV, ...1250 A, ...31.5 kA 12 kV, 1600-2500 A, ... 31.5 kA


17.5 kV, ...1250 A, ...31.5 kA 17.5 kV, 1600-2500 A, ...31.5 kA
p H a b c d e p H a b c d e
mm mm mm mm mm mm mm mm mm mm mm mm mm mm
150 205 450 424 433 217.5 475 210 310 570 424 433 237.5 599(1)
210 205 570 424 433 217.5 475 275 310 700 424 433 237.5 599(1)

24 kV, ...1250 A, ...25,kA 24,kV, 1600-2500 A, ...25,kA


p H a b c d e p H a b c d e
mm mm mm mm mm mm mm mm mm mm mm mm mm mm
210 310 570 424 433 282.5 631(1) 275 310 700 424 433 282.5 642(2)
275 310 700 424 433 282.5 631(1)

(1) Measuring point pole part (1) Pole with heat-sink 616 mm
(2) Pole with heat-sink 661 mm
 Circuit-breakers on
withdrawable part

Circuit-breakers on withdrawable
part is obtained starting from
fixed version, adding:
 Withdrawable assembly
 Contact arms with
isolating contacts
 Control wiring with plug
 Features
 Vacuum interruption technique
 Contacts protected against oxidation
and contamination
 Vacuum interrupter embedded in the
resin poles
 Vacuum interrupter protected against
shocks, dust and humidity
 Ensured operation under different
climatic conditions
 Limited switching energy
 High number of operations
 Operating mechanism with high
reliability
 EL type operating mechanism A Open/closed auxiliary contacts
B Auxiliary circuits terminal box
C Charged/discharged closing
springs mechanical indicator
D Closing push button
B E Opening push button
F Auxiliary releases (opening /
closing / undervoltage)
E D
G Electrical accessories plug-
F
G socket connectors
H Closing spring motor geared
A
I Circuit-breaker open/closed
L C
mechanical indicator
I L Built-in closing spring charging
lever
M
H M Mechanical operation counter
Power Capacitors SAC August 22, 2015 | Slide 7