Power System Protection
Power System Protection
net/publication/372476944
Power System Protection: -Protective Devices Fuses and Circuit Breakers. FUSES
AND CIRCUIT BREAKERS. FUSES
CITATIONS READS
0 673
1 author:
Enyutu Elia
Mbarara University of Science & Technology (MUST)
4 PUBLICATIONS 0 CITATIONS
SEE PROFILE
All content following this page was uploaded by Enyutu Elia on 20 July 2023.
The fusing current for this type of fuse may vary considerably. Circulating air can cool the wire, thereby
increasing the fusing current. Air will also oxidize the wire in time, and this will cause a reduction of
the fusing current. If discrimination is required, or accuracy in the value of the fusing current is
necessary, then the wire fuse is most unreliable. The wires deteriorate and are subject to misuse, since
it is easy for the wrong size of wire to be fitted. In circuits where the energy level is high, the wire fuse
can be a source of danger, as it may not be adequate in extinguishing the arc.
protected so that the wrong size of fuse cannot be fitted. The fuse wire does not deteriorate and is more
reliable in operation (Fig. 2).
For large currents and where the energy level is high, the high-breaking- capacity (h.b.c.) fuse is
used. This is a cartridge-type fuse in which a silver fuse element is connected between two end-
contacts of a ceramic tube filled with a special quartz powder. When the fuse blows there is a fusion
of the silver vapor produced with the filling powder, so that globules of high-resistance material are
formed in the path of the arc, causing it to be extinguished.
This type of fuse is very reliable in performance and can be used when discrimination is required. It
does not deteriorate and has a high speed of operation (Fig. 3).
The relationship between the rated minimum fusing current and the current rating is called the fusing
factor:
.
Fusing factor = rated minimum fusing current / current rating
Classification of LV fuses.
In British standard, there are four classes of fuses, depending upon their fusing factors. These are as
follows:
Class P fuses:These having a fusing factor of 1.25 or less and provide protection for circuits that cannot
withstand even small sustained overloads.
Class Q fuses:These fuses are for circuits that can withstand small overcurrents but give protection
against higher values of overload. There are two types:
Class Q1—fusing factor between 1.25 and 1.5
Class Q2—fusing factor between 1.5 and 1.75
Class R fuses: These fuses have a fusing factor between 1.75 and 2.5 and will protect a circuit against
relatively large over- currents only. Their main use is as back-up protection where the normal
protection is provided by some other device such as a circuit breaker or a motor overload trip.
According to IEC standard, two classes of LV cartridge fuse are very widely used:
• for domestic and similar installation ,type gG
• for industrial installations type gG, gM or aM .
Class gG for protection of lighting circuit .While gM and aM for motor protection.
class aM fuses protect agains short-circuit currents only, and must t always be associated with another
device which protects against overload.
As we did with melting time, we can draw a curve to represent the total clearing
time as a function of the current.
Following are the main characteristics of a fuse:
• The minimum melting time curve
• The total clearing time curve
• The fuse minimum melting current
• The fuse rating (nominal current) which should not be confused with the minimum melting current.
If the pre-arcing I2t is not exceeded then there will be no deterioration of the fuse performance. This is
taken into account when discrimination is required between fuses. If the total I 2t of the smaller fuse is
less than the pre-arcing I2t of the larger fuse then the smaller fuse would operate without causing any
deterioration of the larger fuse.
Example: It is proposed to use a No.30 AWG copper wire as a fuse element. If its initial temperature
is 50 C⁰, calculate the following:
(a) Tha I2t needed to melt the wire (copper melt at1083 C⁰ ).
(b) The time needed to melt the wire if the short circuit curreny is 30A.
These types of fuses are shown in Fig.6 ,and are used for voltages up to 33kV.The time current
characteristics are shown in Fig.7.
Power System Protection: - Protective Devices Fuses and Circuit Breakers.
The
Circuit Breakers
1.Low Voltage Circuit breakers
.
A circuit breaker is an automatically-operated electrical switch designed to
protect an electrical circuit from damage caused by overload or short circuit. Unlike a fuse, which
operates once and then has to be replaced, a circuit breaker can be reset (either manually or
automatically) to resume normal operation. Circuit breakers are made in varying sizes, from small
devices that protect an individual household appliance up to large switchgear designed to protect high
voltage circuits feeding an entire city.
Operation
Magnetic circuit breakers are implemented using a solenoid (electromagnet) whose pulling force
increases with the current. The circuit breaker's contacts are held closed by a latch and, as the current
in the solenoid increases beyond the rating of the circuit breaker, the solenoid's pull releases the latch
which then allows the contacts to open by spring action. Thermal breakers use a bimetallic strip, which
heats and bends with increased current, and is similarly arranged to release the latch. This type is
commonly used with motor control circuits. Thermal breakers often have a compensation element to
reduce the effect of ambient temperature on the device rating.
Thermomagnetic circuit breakers, which are the type found in most distribution boards, incorporate
both techniques with the electromagnet responding instantaneously to large surges in current (short
circuits) and the bimetallic strip responding to less extreme but longer-term overcurrent conditions.
There are many different technologies used in circuit breakers and they do not always fall into distinct
categories. Types that are common in domestic, commercial and light industrial applications at low
voltage (less than 1000 V) include:
• MCB (Miniature Circuit Breaker)—rated current not more than 100 A. Trip characteristics
normally not adjustable. Thermal or thermal-magnetic operation. Breakers illustrated above are
in this category.
• MCCB (Moulded Case Circuit Breaker)—rated current up to 1000 A. Thermal or thermal-
magnetic operation. Trip current may be adjustable.
Power System Protection: - Protective Devices Fuses and Circuit Breakers.
• ACB (Air circuit breaker) – rated current up to 4000 A. Thermal and magnetic operation . Trip
current adjustaible.
1. Actuator lever - used to manually trip and reset the circuit breaker. Also
indicates the status of the circuit breaker (On or Off/tripped). Most breakers
are designed so they can still trip even if the lever is held or locked in the
on position. This is sometimes referred to as "free trip" or "positive trip"
operation.
2. Actuator mechanism - forces the contacts together or apart.
3. Contacts - Allow current to flow when touching and break the flow of
current when moved apart.
4. Terminals
5. Bimetallic strip
6. Calibration screw - allows the manufacturer to precisely adjust the trip
current of the device after assembly.
7. Solenoid
8. Arc divider / extinguisher.
• Rated current.
International Standard IEC 60898-1 defines the rated current In of a circuit breaker for household
applications as the current that the breaker is designed to carry continuously (at an ambient air
temperature of 30 °C). The commonly-available preferred values for the rated current are 6 A, 10 A,
13 A, 16 A, 20 A, 25 A, 32 A, 40 A, 50 A, 63 A, 80 A and 100 A .The circuit breaker is labeled with
the rated current in ampere, but without the unit symbol "A". Instead, the ampere figure is preceded by
a letter "B", "C" , "D" "K" or "Z" that indicates the instantaneous tripping current, that is the minimum
value of current that causes the circuit-breaker to trip without intentional time delay (i.e., in less than
100 ms)
These circuit breakers are mainly used for 3-phase circuits and for currents larger than 100A and up to
1600A. Types of these C.Bs are shown below:
Power System Protection: - Protective Devices Fuses and Circuit Breakers.
These breakers are used mainly in industrial applications to protect cables and equipment.
C1, C2 to close. As soon as they close, the tripping coil is energized by an auxiliary dc source. This
causes the three main line contacts to open, thus interrupting the circuit.
• Bulk oil circuit breakers are composed of a steel tank filled with insulating oil. In one version
(Fig.2), three porcelain bushings channel the 3-phase line currents to a set of fixed contacts. Three
movable contacts, actuated simultaneously by an insulated rod, open and close the circuit. When
the circuit breaker is closed, the line current for each phase penetrates the tank by way of one
porcelain bushing, flows through the first fixed contact, the movable contact, the second fixed
contact, and then on out by a second bushing.
If an overload occurs, the tripping coil releases a powerful spring that pulls on the insulated rod, causing
the contacts to open. As soon as the contacts separate, a violent arc is created, which volatilizes the
surrounding oil. The pressure of the hot gases creates turbulence around the contacts. This causes cool
oil to swirl around the arc, thus extinguishing it.
These circuit breakers contain minimum quantity of oil. The three phases are separated into three
chambers as shown in Fig.3. Unlike bulk oil circuit breaker, the insulating oil is available only in
interrupting chamber.
Power System Protection: - Protective Devices Fuses and Circuit Breakers.
The reduction in the number of interrupting chambers per pole has led to a considerable simplification
of circuit breakers as well as the number of parts and seals required. As a direct consequence, the
reliability of circuit breakers improved.
Power System Protection: - Protective Devices Fuses and Circuit Breakers.
Disadvantages
The main disadvantages of SF6 circuit breakers are :
1. SF6 breakers are costly due to the high cost of SF6.
2. Since SF6 gas has to be reconditioned after every operation of the breaker, additional equipment is
required for this purpose.
Applications.
A typical SF6 circuit breaker consists of interrupter units each capable of dealing
with currents up to 60 kA and voltages in the range of 50—80 kV. A number of units are connected in
series according to the system voltage. SF6circuit breakers have been
developed for voltages 115 kV to 230 kV, power ratings 10 MVA to 20 MVA and interrupting time
less than 3 cycles.
Fig.8 shows a typical 3-phase air-blast circuit breaker. Each phase is composed of three contact
modules connected in series.
Power System Protection: - Protective Devices Fuses and Circuit Breakers.