Simex Pressure Readout

Download as pdf or txt
Download as pdf or txt
You are on page 1of 56

Assisting the automation

industry since 1986

User manual
METER
SRP-73
• Firmware: v.5.21 or higher
• Input type: 0/4-20 mA, 0/1-5V, 0/2-10V
• Two-colour display

Read the user's manual carefully before starting to use the unit or software.
Producer reserves the right to implement changes without prior notice.

2014.12.17 SRP-73_INSSXEN_v.2.10.002
User manual - METER SRP-73

CONTENTS
1. BASIC REQUIREMENTS AND USER SAFETY........................................................................................3
2. GENERAL CHARACTERISTICS................................................................................................................4
3. TECHNICAL DATA......................................................................................................................................4
4. DEVICE INSTALLATION............................................................................................................................6
4.1. UNPACKING.......................................................................................................................................6
4.2. ASSEMBLY........................................................................................................................................7
4.3. CONNECTION METHOD...................................................................................................................9
4.4. MAINTENANCE................................................................................................................................13
5. FRONT PANEL DESCRIPTION................................................................................................................14
6. PRINCIPLE OF OPERATION...................................................................................................................14
6.1. MEASUREMENT MODE..................................................................................................................14
6.2. DETECTION OF THE PEAK VALUES............................................................................................16
6.3. CONTROL OF THE RELAY OUTPUTS..........................................................................................16
6.3.1. One threshold mode................................................................................................................18
6.3.2. Two thresholds mode..............................................................................................................19
7. DEVICE PROGRAMMING.........................................................................................................................20
7.1. PROGRAMMING MENU..................................................................................................................20
7.2. PARAMETERS EDITION.................................................................................................................21
7.2.1. Numeric parameters (digit change mode)...............................................................................21
7.2.2. Numeric parameters (slide change mode)..............................................................................21
7.2.3. Switch parameters (“LIST” type).............................................................................................22
7.3. MENU DESCRIPTION.....................................................................................................................22
7.3.1. “rEL1” menu.............................................................................................................................23
7.3.2. “inPt” menu..............................................................................................................................25
7.3.3. ”bri” parameter.........................................................................................................................30
7.3.4. ”CoL” menu..............................................................................................................................30
7.3.5. ”HOLd” menu...........................................................................................................................31
7.3.6. ”SECu” menu...........................................................................................................................32
7.3.7. ”rS” menu.................................................................................................................................32
7.3.8. ”Edit” parameter......................................................................................................................33
7.3.9. ”dEFS” parameter....................................................................................................................33
7.3.10. ”SErv” menu..........................................................................................................................33
7.4. MENU STRUCTURE........................................................................................................................34
8. THE ALARM LED......................................................................................................................................36
9. OVER-CURRENT PROTECTION.............................................................................................................36
10. DISPLAYED VALUES CALCULATION..................................................................................................36
10.1. ADDITIONAL CALCULATIONS (USED CONVERSION CHARACTERISTIC).............................36
10.1.1. Linear characteristic..............................................................................................................37
10.1.2. Square characteristic............................................................................................................37
10.1.3. Square root characteristic.....................................................................................................38
10.1.4. User defined characteristic...................................................................................................38
10.1.5. Volume characteristics of a cylindrical tank..........................................................................39
10.2. EXAMPLES OF CALCULATIONS.................................................................................................40
11. THE MODBUS PROTOCOL HANDLING...............................................................................................44
11.1. LIST OF REGISTERS....................................................................................................................45
11.2. TRANSMISSION ERRORS DESCRIPTION..................................................................................48
11.3. EXAMPLES OF QUERY/ANSWER FRAMES...............................................................................48
12. DEFAULT AND USER'S SETTINGS LIST.............................................................................................51

2
User manual - METER SRP-73

Explanation of symbols used in the manual:

!
- This symbol denotes especially important guidelines concerning the installation and
operation of the device. Not complying with the guidelines denoted by this symbol
may cause an accident, damage or equipment destruction.

IF THE DEVICE IS NOT USED ACCORDING TO THE MANUAL THE USER IS


RESPONSIBLE FOR POSSIBLE DAMAGES.

i
- This symbol denotes especially important characteristics of the unit.
Read any information regarding this symbol carefully

1. BASIC REQUIREMENTS AND USER SAFETY

! - The manufacturer is not responsible for any damages caused by


inappropriate installation, not maintaining the proper environmental
conditions and using the unit contrary to its assignment.
- Installation should be conducted by qualified personnel . During installation all
available safety requirements should be considered. The fitter is responsible for
executing the installation according to this manual, local safety and EMC
regulations.
- GND input of device should be connected to PE wire;
- The unit must be properly set-up, according to the application. Incorrect
configuration can cause defective operation, which can lead to unit damage or
an accident.
- If in the case of a unit malfunction there is a risk of a serious threat to the
safety of people or property additional, independent systems and
solutions to prevent such a threat must be used.

- The unit uses dangerous voltage that can cause a lethal accident. The unit
must be switched off and disconnected from the power supply prior to
starting installation of troubleshooting (in the case of malfunction).

- Neighbouring and connected equipment must meet the appropriate standards


and regulations concerning safety and be equipped with adequate overvoltage
and interference filters.
- Do not attempt to disassemble, repair or modify the unit yourself. The unit
has no user serviceable parts. Defective units must be disconnected and
submitted for repairs at an authorized service centre.

3
User manual - METER SRP-73

! - In order to minimize fire or electric shock hazard, the unit must be protected
against atmospheric precipitation and excessive humidity.
- Do not use the unit in areas threatened with excessive shocks, vibrations, dust,
humidity, corrosive gasses and oils.
- Do not use the unit in areas where there is risk of explosions.
- Do not use the unit in areas with significant temperature variations, exposure to
condensation or ice.
- Do not use the unit in areas exposed to direct sunlight.
- Make sure that the ambient temperature (e.g. inside the control box) does not
exceed the recommended values. In such cases forced cooling of the unit must
be considered (e.g. by using a ventilator).

! The unit is designed for operation in an industrial environment and must


not be used in a household environment or similar.

2. GENERAL CHARACTERISTICS
The SRP-73 meter is equipped with one current input 0-20 / 4-20mA and one voltage
input 0-5 / 1-5 / 0-10 / 2-10V. Current input has additionally overcurrent protection circuit,
which protects standard resistor. The selection of active input is realised by software, and
selected input can be changed at any time. Additionally the SRP-73 allows user to select a
conversion characteristic of several kinds: linear, square, square root, user defined (max.20
points length) and volume characteristics of a cylindrical tank in the vertical and horizontal
position. Result is showed on 4-digit LED display. Displayed values range can be selected by
user, from -999 to 9999, plus decimal point.
The device can be equipped with one or two relay (or OC type) outputs. Device SRP-73
is equipped with RS-485 / Modbus RTU communication interface and sensor supply output.
The meter can be ordered in two power supply versions.

SRP-73 can be used for controlling and regulation of processes need proportional and
threshold control like: temperature processes (heating or cooling), valves controlling or other.

3. TECHNICAL DATA
Power supply voltage 85...230...260V AC/DC; 50 ÷ 60 Hz (separated)
(depending on version) or 19...24...50V DC and 16...24...35V AC (separated)
External fuse (required) T - type, max. 2 A
Power consumption max. 4.5 VA @ 85 ÷ 260V AC/DC
max. 4.5 VA @ 16V ÷ 35V AC
max. 4.5 W @ 19V ÷ 50V DC
Current input 0÷20 mA, 4÷20 mA overload protected,
maximum input current about 40 mA
Current measurement accuracy ± 0,1% @ 25°C; ± one digit (for 0÷20 mA range)

4
User manual - METER SRP-73

Current input resistance < 65 Ω (typical 55 Ω)


Voltage input 0÷5 V, 1÷5 V, 0÷10 V, 2÷10 V
Voltage measurement accuracy ± 0,1% @ 25°C; ± one digit (for 0÷10 V range)
Voltage input resistance > 50 kΩ
Temperature stability 50 ppm / °C
Display range -999 ÷ 9999, plus decimal point
Accepted prolonged input overload: 20%
Outputs
relay: 0, 1 or 2 NO, 1A/250V AC (cos ϕ = 1)
or OC-type: 0, 1 or 2; 30mA / 30VDC / 100mW
sensor power supply: 24V +5%, -10% / max. 100 mA, stabilized
Communication interface RS 485, 8N1 and 8N2, Modbus RTU, not separated
Baud rate 1200 bit/s ÷ 115200 bit/s
Display LED, 4 digit, 13mm height, two-colour (red and green)
(depending on version) or (for IP 65 version) 5 digit, 9mm height, red
Data memory non-volatile memory, EEPROM type
Protection level (depending on
display size)
5 x 9mm version: IP 65 (from front), optional version with panel cut-out
sealing available
IP 20 (housing and connection clips)
4 x 13mm version: IP 40 (from front)
IP 20 (housing and connection clips)
Housing type panel
Housing material NORYL - GFN2S E1
Housing dimensions 72 x 36 x 97 mm
Mounting hole 66.5 x 32.5 mm
Assembly depth min. 102 mm
Panel thickness max. 5 mm
Operating temperature 0°C to +50°C
(depending on version) or -20°C to +50°C
Storage temperature -10°C to +70°C
(depending on version) or -20°C to +70°C
Humidity 5 to 90% no condensation
Altitude up to 2000 meters above sea level
Screws tightening max. torque 0,5 Nm
Max. connection leads diameter 2,5 mm2

5
User manual - METER SRP-73

Safety requirements according to: PN-EN 61010-1


installation category: II
pollution degree: 2
voltage in relation to ground: 300V AC
insulation resistance: >20MΩ
insulation strength between power supply and
input/output terminal: 1min. @ 2300V
insulation strength between relays terminal:
1min. @ 1350V
EMC according to: PN-EN 61326-1

! This is a class A unit. In a residential or a similar area it can cause radio


frequency interference. In such cases the user can be requested to use
appropriate preventive measures.

4. DEVICE INSTALLATION
The unit has been designed and manufactured in a way assuring a high level of user
safety and resistance to interference occurring in a typical industrial environment. In order to
take full advantage of these characteristics installation of the unit must be conducted correctly
and according to the local regulations.

! - Read the basic safety requirements on page 3 prior to starting the installation.
- Ensure that the power supply network voltage corresponds to the nominal
voltage stated on the unit’s identification label.
- The load must correspond to the requirements listed in the technical data.
- All installation works must be conducted with a disconnected power supply.
- Protecting the power supply connections against unauthorized persons must be
taken into consideration.

4.1. UNPACKING
After removing the unit from the protective packaging, check for transportation damage. Any
transportation damage must be immediately reported to the carrier. Also, write down the unit
serial number located on the housing and report the damage to the manufacturer.

Attached with the unit please find:


- user’s manual,
- warranty,
- assembly brackets - 2 pieces.

6
User manual - METER SRP-73

4.2. ASSEMBLY

! - The unit is designed for mounting inside housings (control panel, switchboard)
insuring appropriate protection against surges and interference. Metal housings
must be connected to ground in a way that complies with the governing
regulations.
- Disconnect the power supply prior to starting assembly.
- Check the connections are wired correctly prior to switching the unit on.

!
In order to install the unit, a 66.5 x 32.5 mm mounting hole (Figure 4.1) must be
prepared. The thickness of the material of which the panel is made must not exceed
5mm. When preparing the mounting hole take the grooves for catches located on
both sides of the housing into consideration (Figure 4.1). Place the unit in the
mounting hole inserting it from the front side of the panel, and then fix it using the
brackets (Figure 4.2). The minimum distances between the centre points of multiple
units - due to the thermal and mechanical conditions of operation - are 91 mm x
57mm (Figure 4.3).

a) 66,5 mm

8 mm
8 mm
32,5 mm

8 mm
8 mm

max. 5 mm
1 mm 1 mm

b) 68 mm
32,5 mm

max. 5 mm
Figure 4.1. Mounting hole dimensions: a) recommended b) allowable

7
User manual - METER SRP-73

92 mm

16 mm
8,5 mm
5 mm
12 mm 10 mm

Figure 4.2. Installing of brackets, and dimensions of connectors.

91 mm

57 mm

Figure 4.3. Minimum distances when assembly of a number of units

8
User manual - METER SRP-73

4.3. CONNECTION METHOD


Caution

! - Installation should be conducted by qualified personnel . During installation all


available safety requirements should be considered. The fitter is responsible for
executing the installation according to this manual, local safety and EMC
regulations.
- The unit is not equipped with an internal fuse or power supply circuit breaker.
Because of this an external time-delay cut-out fuse with a small nominal current
value must be used (recommended bipolar, max. 2A) and a power supply circuit-
breaker located near the unit. In the case of using a monopolar fuse it must be
mounted on the phase cable (L).
- The power supply network cable diameter must be selected in such a way that in
the case of a short circuit of the cable from the side of the unit the cable shall be
protected against destruction with an electrical installation fuse.

- Wiring must meet appropriate standards and local regulations and laws.
- In order to secure against accidental short circuit the connection cables must be
terminated with appropriate insulated cable tips.
- Tighten the clamping screws. The recommended tightening torque is 0.5 Nm.
Loose screws can cause fire or defective operation. Over tightening can lead to
damaging the connections inside the units and breaking the thread.
- In the case of the unit being fitted with separable clamps they should be inserted
into appropriate connectors in the unit, even if they are not used for any
connections.
- Unused terminals (marked as n.c.) must not be used for connecting any
connecting cables (e.g. as bridges), because this can cause damage to the
equipment or electric shock.
- If the unit is equipped with housing, covers and sealing to, protecting against
water intrusion, pay special attention to their correct tightening or clamping. In the
case of any doubt consider using additional preventive measures (covers, roofing,
seals, etc.). Carelessly executed assembly can increase the risk of electric shock.
- After the installation is completed do not touch the unit’s connections when it is
switched on, because it carries the risk of electrical shock.

Due to possible significant interference in industrial installations appropriate measures


assuring correct operation of the unit must be applied. To avoid the unit of improper
indications keep recommendations listed below.

– Avoid running signal cables and transmission cables together with power supply cables
and cables controlling inductive loads (e.g. contactors). Such cables should cross at
a right angle.

– Contactor coils and inductive loads should be equipped with interference protection
systems, e.g. RC-type.

9
User manual - METER SRP-73

– Use of screened signal cables is recommended. Signal cable screens should be


connected to the earthing only at one of the ends of the screened cable.

– In the case of magnetically induced interference the use of twisted pair of signal cables is
recommended. Twisted pair (best if shielded) must be used with RS-485 serial
transmission connections.

– In the case of measurement or control signals are longer than 30m or go outside of the
building then additional safety circuits are required.

– In the case of interference from the power supply side the use of appropriate interference
filters is recommended. Bear in mind that the connection between the filter and the unit
should be as short as possible and the metal housing of the filter must be connected to
the earth with the largest possible surface. The cables connected to the filter output must
not be run with cables with interference (e.g. circuits controlling relays or contactors).

Connections of power supply voltage and measurement signals are executed using the
screw connections on the back of the unit’s housing.

6-7 mm
max. 2 mm

Figure 4.4. Method of cable insulation replacing and cable terminals

+24V +5%, -10% RS - 485


Power R2
Imax = 100mA
supply (optional)
+ Uo - GND DATA+
DATA-
(depending on version)

1 2 13 14 16 17 18 19 20
3 4 6 7 8 9 10
n.c. + + n.c.
0/4-20mA
GND
R1
(optional) 0/1 - 5V, 0/2 - 10V

Figure 4.5. Terminals description (relay outputs)

10
User manual - METER SRP-73

+24V +5%, -10% RS - 485


Power Imax = 100mA
supply (optional)
+ Uo - GND DATA+
(depending on version) OC2 DATA-
- +
1 2 13 14 16 17 18 19 20
3 4 6 7 8 9 10
- + n.c. + + n.c.
OC1, OC2: OC1
(optional) 0/4-20mA
Umax = 30V DC GND
Imax = 30mA
Pmax = 100mW 0/1 - 5V, 0/2 - 10V

Figure 4.6. Terminals description (OC-type outputs)

! All connections must be made while power supply is disconnected !

internally connected
+ -
24V DC
16 17
- +
6 7 8 9 10 6 7 8 9 10

+ -
- +

Figure 4.7. Connection of 2-wire current converters

internally connected
+ -
24V DC
16 17
- +
6 7 8 9 10 6 7 8 9 10
+

+ -
-

Figure 4.8. Connection of 3-wire current converters

11
User manual - METER SRP-73

- + internally connected

16 17 24V DC
- +
6 7 8 9 10 6 7 8 9 10

+
+
+ -
-

Figure 4.9. Connection of voltage converters

R2

R1
L N 13 14
1 2 3 4

FUSE
FUSE

Depending on version:
85...230...260V AC/DC or
19...24...50V DC; 16...24...35V AC

L N
Figure 4.10. Connection of power supply and relays

!
Contacts of relay outputs are not equipped with spark suppressors. While use
the relay outputs for switching of inductive loads (coils, contactors, power
relays, electromagnets, motors etc.) it is required to use additional
suppression circuit (typically capacitor 47nF/ min. 250VAC in series with
100R/5W resistor), connected in parallel to relay terminals or (better) directly
on the load. In consequence of using the suppression circuit, the level of
generated electromagnetic disturbances is lower, and the life of relay contacts
rises.

12
User manual - METER SRP-73

a) L b) L

3 4 3 4 !
!
N N
Figure 4.11. Examples of suppression circuit connection:
a) to relay terminals; b) to the inductive load

Uo Uo
OC1
16 17 OC1 16 17
3 4
+ - + -
- + 3 4
- + R
Logic controller 2k2
+ LED 10 mA
voltage input
24 V
-

Figure 4.12. Example of OC-type outputs connection

4.4. MAINTENANCE
The unit does not have any internal replaceable or adjustable components available to
the user. Pay attention to the ambient temperature in the room where the unit is operating.
Excessively high temperatures cause faster ageing of the internal components and shorten the
fault-free time of the unit's operation.
In cases where the unit gets dirty do not clean with solvents. For cleaning use warm water with
small amount of detergent or in the case of more significant contamination ethyl or isopropyl
alcohol.

! Using any other agents can cause permanent damage to the housing.

Product marked with this symbol should not be placed in municipal waste. Please
check local regulations for disposal of electronic products.

13
User manual - METER SRP-73

5. FRONT PANEL DESCRIPTION

alarm LED indicator (AL)


display
AL
R1
R2
Thresholds exceeding ESC
ENTER
LED indicators (R) MENU

programming pushbuttons

Symbols and functions of push-buttons:


ESC Symbol used in the manual: [ESC/MENU]
MENU Functions:
• Enter to main menu ( press and hold by at least 2 sec.)
• Exit the current level and Enter to previous menu (or measure mode)
• Cancel the changes made in parameter being edited

Symbol used in the manual: [ENTER]


ENTER
Functions:
• Start to edit the parameter
• Enter to the sub-menu,
• Confirmation of changes made in parameter being edited

Symbol used in the manual: [^] [v]


Functions:
• Change of the present menu,
• Modification of the parameter value,
• Change of the display mode.

6. PRINCIPLE OF OPERATION
After turning the power supply on, device ID and software version are showed on the
display, next the controller goes to the measurement mode.

6.1. MEASUREMENT MODE


In the measure mode, the measurement results, converted over selected characteristic,
are displayed on the LED display. The measurement range equal to the nominal range is
called: nominal measurement range, and the measurement range equal to the extended
nominal range is called: permissible measurement range (Figure 6.1, 6.2).

14
User manual - METER SRP-73

”Lo r” parameter ”Hi r” parameter

nominal measurement range

4 mA 20 mA

permissible measurement range

Figure 6.1. Definitions of measurement ranges in mode 4 ÷ 20mA

If the result of measurement exceeds the permissible measurement range, warning ”-Hi-” or
”-Lo-” is displayed rather than input signal, depends on exceeded value (see description of
“Lo r” i “Hi r” parameters, paragraph ”inPt” menu).
”Hi r” parameter

nominal measurement range

0 mA 20 mA

permissible measurement range

Figure 6.2. Definitions of measurement ranges in mode 0 ÷ 20mA

If the measurement value do not exceeds permissible measurement range but


i displayed value exceeds range -999 ÷ 9999, the warning ”-Ov-” is displayed rather
than the calculated result.

In the measurement mode user can check main thresholds values. After pressing [^] or
[v] button, name of the threshold (e.g. ”rEL1”) and his value will be displayed on the display
in alternating mode. If [^] or [v] will be pressed in 5 sec again, the next threshold will be
displayed, else the device comes back to the measurement mode. If a free access is enabled
(see description of ”SECu” menu), user can change the value of particular threshold pressing
button [ENTER] (see: PARAMETERS EDITION).

Input type, range of displaying values, characteristic of conversion, decimal point


position and measure filtering ratio, are user configurable parameters. All accessible
parameters can be changed by entering the menu (see: DEVICE PROGRAMMING). Use the
local keyboard or the remote controller to do it. (Note: all parameters can be remote changed
via RS-485 interface).

i Configuration of the device (via menu or RS-485 interface) do not stops measures.

15
User manual - METER SRP-73

6.2. DETECTION OF THE PEAK VALUES


The SRP-73 controller is equipped with peaks detection function. It can detect a peaks of
the input signal and display their values. Presets connected with this function are placed in
”HOLd” menu (see description of ”HOLd” menu). The detection of the peak can be done if
the measured signal raises and drops of value at least equal to parameter ”PEA”. Detected
peaks are displayed during the time defined by parameter ”timE”. If a new peak will be
detected while one is displayed, this new peak will be displayed and display time counter will
be cleared (Figure 6.3). If no peaks are detected while time ”timE” elapses, device starts to
show the current value of input signal again. If „HdiS”=”HOLD” then setting parameter
"timE"=0.0 causes holding peak value until [ESC] button is pressed. If „HdiS”=”rEAL” then
value "timE"=0.0 means no holding. Displaying peak value is signalized by flashing most right
decimal point.
The relays/LEDs can be controlled depend on the current value of input signal or the
peak value (see ”HOLd” menu).

measure

”timE”
”timE”

”PEA”

”PEA”

real measurement result time


display value

Figure 6.3. Process of peaks detection

6.3. CONTROL OF THE RELAY OUTPUTS


The control of the object (measured signal) is realized via relay outputs. Front panel
LEDs named „R” indicates the state of particular relay output.

If device is not equipped with one or more relay outputs, menus refer to this relays
i are available, but apply to LED indicators only. In such case LEDs indicates
exceeding of particular thresholds.

Modes of the control can be changed depend on the values of parameters “SEtP”, “SEt2”,
“HYSt”, “modE”, “t on”, “toFF”, “unit” and “AL”. Depend on “modE” parameter, relays
can be not used or controlled over one or two thresholds values.
If one threshold is used (Figure 6.4) the relay can be turned on (“modE” = ”on”) or off
(“modE” = ”oFF”) when the input signal value is contained in zone A. If two thresholds are
used (Figure 6.5) the relay will be turned on when value of input signal is contained in zone A
(“modE” = ”in”) or zone B (“modE” = ”out”) and turned off if the signal is contained in the
second one.
16
User manual - METER SRP-73

state of
relay/LED
”SEtP” parameter

zone B zone A

measure
”HYSt” parameter

Figure 6.4. One threshold control of the relay/LED outputs

state of
relay/LED
”SEtP” or ”SEt2” parameter

zone B zone A zone B

measure
”HYSt” parameter

Figure 6.5. Two threshold control of the relay/LED outputs

i The relay outputs and LEDs (named R) can be controlled depend on both - the
current value and the peak value (when peak detection is active) of the input signal.

17
User manual - METER SRP-73

6.3.1. One threshold mode


Figure 6.6 presents the principle of relay outputs operation for one threshold mode, and
an example values of other parameters.
measured
displayed value tA tB tC signal tD “SEtP” parameter
(expected signal value)
BOFF B
a) zone A ON
A B

“HYSt” parameter
C D DOFF
zone B (allowed signal
DON deviation)
time
b) relay state
(modE = on
t on = 0 closed
toFF = 0) open
time
c) relay state
(modE = oFF
closed
t on = 0
open
toFF = 0)
time
relay state
d) (modE = on
closed
t on > 0
open
toFF > 0)
time
relay state “t on” “toFF”
e) (modE = oFF parameter parameter
closed
t on > 0 open
toFF > 0)
time
“toFF” “t on”
parameter parameter
Description:
A, B, C, D - points where measured signal exceeds border values (expected value ± allowed deviation)
BON ,BOFF ,DON ,DOFF - relays state changes moments: (for “t on” > 0, “toFF” > 0)
tA , tB , tC , tD - time periods while input signal is in zone A or zone B

Figure 6.6. Principle of LED/relay output operation for one threshold mode

Parameter “SEtP” sets a threshold of the relay, and parameter “HYSt” sets a
hysteresis of the relay (Figure 6.6 a). The relay can change his state only when input value
exceeds (over or under) border value and tA ,tB ,tC ,tD times (Figure 6.6) are bigger than the
time defined by parameters “t on”, “toFF” and “unit”. Border values means values equal
threshold+hysteresis and threshold-hysteresis respectively.
If “t on” and “toFF” parameters are set to “0”, then the relay state will be changed
as soon as input value exceeds any of the border values (see points A and C, Figure 6.6 a,
b, c).
If values of “t on” or/and “toFF” are positive, then relay state will be turned on if the
input value exceeds the border values and stay bigger (or lower) during at least
“t on” (see points BON, DON, Figure 6.6 a, d, e). Similarly, the relay will be turned off if time
“toFF” elapse since the input signal value exceeds any of the border values (see points
BOFF, DOFF, Figure 6.6 a, d, e).

18
User manual - METER SRP-73

If tA ,tB ,tC or tD (when input signal stay in zone A or zone B) are lower than parameters
“t on” or “toFF”, the relay will not change his state (see points A and C, Figure 6.6 a, d, e).
The state of relay output while the input value exceeds the border values (points A, B, C,
D) is described by parameter “modE”. The relay can be turned on (“modE” = ”on”), or
turned off (“modE” = ”oFF”) when input signal value is contained in zone A (Figure 6.6 a).
The parameter “AL” allow user to set the relay output behaviour in critical situations (e.
g. Input values exceeds permissible measurement range). User can select that the relays
will be turned on, turned off,or not changed in critical situations.

All parameters connected with relay outputs are described in paragraph ”rEL1” menu.

6.3.2. Two thresholds mode


displayed value tA tB tC tD tE
measure
zone B COFF CON
d signal
“HYSt” parameter
C

BON
BOFF
D E
EOFF “SEtP” or “SEt2”
a) zone A
EON parameter
A B

“HYSt” parameter
zone B

time
b) relay state
(modE = in
t on = 0 closed
toFF = 0) open
time
c) relay state
(modE = out
closed
t on = 0
open
toFF = 0)
time
relay state
d) (modE = in
t on > 0 closed
toFF > 0) open
time
relay state “t on” parameter “toFF” parameter “t on” parameter
e) (modE = out
closed
t on > 0 open
toFF > 0)
time
“toFF” parameter “t on” parameter “toFF” parameter

Objaśnienie:
A, B, C, D, E - points where measured signal exceeds border values (expected value ± allowed deviation)
BON ,BOFF ,CON ,COFF ,EON ,EOFF - relays state changes moments: (for “t on” > 0, “toFF” > 0)
tA , tB , tC , tD , tE - time periods while input signal is in zone A or zone B

Figure 6.7. Principle of LED/relay output operation for two thresholds mode

19
User manual - METER SRP-73

Figure 6.7 presents the principle of relay outputs operation for two thresholds mode, and
an example values of other parameters. In this mode parameter “SEt2” is accessible in
common with “SEtP”, this parameter describes a second threshold of the relay output. The
parameters “HYSt”, “modE”, “t on”, “toFF”, “unit” and “AL” are connected with both
“SEtP” and “SEt2” thresholds. While the controlling process, the relay output changes his
state depends of both “SEtP” and “SEt2” thresholds in similar way as it was described in one
threshold mode.
If two threshold mode is used, “modE” parameter defines state of the relay output when
the input value occurs in a particular zone defined by border values of both thresholds. The
relay can be turned on if the input value is contained in zone A (“modE” = ”in”) or zone B
(“modE” = ”out”) and turned off if it is contained in the second one (Figure 6.7).

The sequence of thresholds “SEtP” and “SEt2” can be set in any order, due to the
i control of relay outputs is done depend on difference between thresholds values
(zone A ) and outside of threshold values (zone B).

7. DEVICE PROGRAMMING
The device menu allow user to set all parameters connected to operation of
measurement input, control modes, critical situations behaviour, communication via RS-485
and access settings. The meaning of the particular parameters is described in paragraph
MENU DESCRIPTION.
Some of the parameters can be accessed without menu entering (quick view mode).
After pressing [^] or [v] button, name of the threshold (e.g.”rEL1”) and his value will be
displayed on the display in alternating mode. If [^] or [v] will be pressed in 5 sec again, the
next threshold will be displayed, else the device comes back to the measurement mode. If a
free access is enabled (see description of ”SECu” menu), user can change the value of
particular threshold pressing button [ENTER] (see: PARAMETERS EDITION).

If particular parameter has been changed and confirmed in quick view mode, its
i new value is displayed in alternating mode with parameter name by few seconds.
Confirmed changes may be checked or user can switch viewed parameter pressing
[^] or [v] button.

7.1. PROGRAMMING MENU

To enter main menu (being in the measurement mode) operator must to press and hold
at least 2 sec. [ESC/MENU] button.
If the user password is defined (see parameter “Scod“, menu ”SECU”), operator have
to enter correct one before proceeding to menu options . Entering of the passwords is similar
to the edition of numeric parameters (see: PARAMETERS EDITION ), however presently editing
digit is showed only on the display, other digits are replaced by “-” sign.

After entering of last digit of the password first menu position will be displayed (if the password
is correct) or warning ”Err” in other case.

! Pay attention when device parameters are being changed. If it is possible, turn off
controlled installation (machine).

20
User manual - METER SRP-73

Functions of the buttons while sub-menu and parameters choice:

Selection of sub-menu or parameter for editing. Name of selected item (sub-


menu or parameter) is displayed.

Operation of [ENTER] button depend on present menu position:


ENTER
• if the name of some sub-menu is displayed - enter this sub-menu; name
of the first parameter (or next level sub-menu) is displayed,
• if the name of some parameter is displayed - enter the edition of this
parameter; present value of the parameter is displayed,

ESC [ESC/MENU] button allow user to exit present menu level and goes to upper
MENU level menu (or measurement mode).

i After about 1 min. since last use of the buttons, device exits the menu mode and
returns to the measurement mode (only if no parameters are in editing mode).

7.2. PARAMETERS EDITION


To start edition of any parameter user should select name of desired one using [^] [v]
buttons and then press [ENTER].

7.2.1. Numeric parameters (digit change mode)


Numerical parameters are displayed as decimal numbers. The mode of its new value
entering depends on chosen edit method ( see parameter „Edit”).
In mode “by digit” („Edit”=”dig”) pressing one of the keys [^] or [v] causes change of
current position (flashing digit) or the sign (+/-). Short pressing of the [ENTER] button causes
change of the position (digit).
Press [ENTER] at least 2 seconds to accept the changes, after that question ”SEt?” is
displayed, and user must to confirm (or cancel) the changes. To conform changes (and story it
in EEPROM) press [ENTER] button shortly after ”SEt?” is displayed. To cancel the changes
press [ESC] button shortly after ”SEt?” is displayed. After that device returns to the menu.

7.2.2. Numeric parameters (slide change mode)


In “slide change” mode („Edit”=”Slid”), buttons [^] and [v] has different functions.
To increase edited value press (or press and hold) [^] button only, the increasing
became quickest as long as button [^] is pressed. To slow down the increasing, button [v] can
be used. If [v] is pressed shortly (and button [^] is still pressed), increasing slow down for
a moment only, if [v] is pressed and held while button [^] is still pressed the increasing slow
down and will be kept on lower speed.
To decrease edited value press (or press and hold ) [v] button only. The decreasing
became quickest as long as button [v] is pressed. To slow down the decreasing, button [^]
can be used. If [^] is pressed shortly (and button [v] is still pressed), decreasing slow down for
a moment only, if [^] is pressed and held while button [v] is still pressed the decreasing slow
down and will be kept on lower speed.
21
User manual - METER SRP-73

Press [ENTER] at least 2 seconds to accept the changes, after that question ”Set?” is
displayed, and user must to confirm (or cancel) the changes. To conform changes (and story it
in EEPROM) press [ENTER] button shortly after ”SEt?” is displayed. To cancel the changes
press [ESC] button shortly after ”SEt?” is displayed. After that device returns to the menu.

7.2.3. Switch parameters (“LIST” type)


Switch parameters can be described as a sets of values (a lists) out of which only one of
the options available on the list can be selected for the given parameter. Options of switching
parameter are selected using [^], [v] keys.

Short pressing of [ENTER] causes in displaying of the acknowledge question (”SEt?”). If


key [ENTER] is pressed again, the changes are accepted, stored in EEPROM end the edition
process finished. Pressing the key [ESC] after ”SEt?” causes in cancelling of made changes
and returning to menu.

Functions of buttons when editing numeric and switching parameters:

While editing numeric parameter:


• change of current (flashing) digit
• slide change of value (acceleration, deceleration, direction change)
While editing switch parameter - selection of switch parameter.

If numerical parameter is being edited, a short press of [ENTER] button


ENTER
change edited position. A long press of [ENTER] button (at lest 2 sec.)
causes of display a ”SEt?” ask, which allow user to make sure if change of
the parameter value is correct. If switch parameter is being edited, a short
press of [ENTER] button causes of display a ”SEt?” ask. When [ENTER]
button is pressed again (while ”SEt?” is displayed) the new value of the
parameter is stored in EEPROM memory.

ESC Pressing this button operator can cancel the changes done up to now (if they
MENU were not approved by [ENTER] button after the ”SEt?” ask) and come back
to menu

7.3. MENU DESCRIPTION


“- - - -” - password checking. If some password different from „0000” is set, then every
enter to main menu follows the entering of password. If entered password is
correct then first menu position will be displayed else warning ”Err”, and unit
returns to measurement mode.

Due to problem with direct displaying of “m” and “K” letters, they are exchanged
i with special signs “ “ for “m” and “ “ for K respectively. However, in user manual
letters „m” and “K” are used to make it more readable (example: “modE”, “tc K”).

22
User manual - METER SRP-73

7.3.1. “rEL1” menu

This menu allows to configure the operation mode of relays and LEDs marked „R” (e.g. „R1”).
If there are few relay outputs available, then every output has its own configuration menu
(e.g. menu „rEL2” for relay (LED) „R2”). Principle of the relays operation is described in
paragraph CONTROL OF THE RELAY OUTPUTS.

• The relay outputs and LEDs (named R) can be controlled depend on both - the
i current value and the peak value (when peak detection is active) of the input
signal.
• If device is not equipped with one or more relay outputs, menus refer to this
relays are available, but apply to LED indicators only. In such case LEDs
indicates exceeding of particular thresholds.

“SEtP” - first threshold of the relay (range -999 ÷ 9999). Negative values can be input by
selecting a “-” sign on first digit (to change value use [^] and [v] buttons).
Threshold is the medium value of relay hysteresis.

“SEt2” - second threshold of the relay (range -999 ÷ 9999). Negative values can be input
by selecting a “-” sign on first digit ( to change value use [^] and [v] buttons). This
threshold is accessible when ”modE” parameter is set to „in” or „out” value.
Threshold is the medium value of relay hysteresis.

“HYSt” - hysteresis of relay (range 0 ÷ 999). Full hysteresis of the relay is equal to 2x
“HYSt” parameter. The relay state can change when an input signal is out of
threshold-hysteresis to threshold+hysteresis zone.

Presented parameters should be set to ensure that ”SEtP” + ”HYSt”,


i ”SEt2” + ”HYSt”, ”SEtP” - ”HYSt” or ”SEt2” - ”HYSt” do not exceeds the
measure range. Additionally, in two threshold mode (“modE”= „in” or „out”), the
hysteresis for both thresholds must not cover each other (in other case relay can't
change his state).

“modE” - relay operation mode:

“noAC” - the relay is not active (permanent turned off)


“on” - one threshold mode, the relay is turned ON when input signal exceeds
SEtP + HYSt value, and is turned off back when the input signal became
lower than SEtP – HYSt,

“oFF” - one threshold mode, the relay is turned OFF when input signal exceeds
SEtP + HYSt value, and is turned on back when the input signal became
lower than SEtP – HYSt,

“in” - two threshold mode, the relay is turned ON when the input signal is
bigger than “lower threshold + HYSt” and lower than “bigger
threshold – HYSt”, and turned off when the input signal is contained in
the second zone. The bigger threshold means bigger one of “SEtP”
and “SEt2” thresholds, the lower threshold” means lower one of
“SEtP” and “SEt2” thresholds.
23
User manual - METER SRP-73

“out” - two threshold mode, relay is turned ON when the input value is bigger
than “bigger threshold + HYSt” and lower than “lower threshold –
HYSt”, and turned on when the input signal is contained in the second
zone. The bigger threshold means bigger one of “SEtP” and “SEt2”
thresholds, the lower threshold” means lower one of “SEtP” and
“SEt2” thresholds.

“modb” - the relay is controlled via RS-485 interface, independently on the input
signal.
• LEDs light when relays are closed, independently of relays' mode.
i • When power supply fail, unit do not store relays state selected by RS-485
interface.
“t on” - turn on delay time, the relay is turned on with delay equal “t on” if the input value
exceeds appropriate border value (defined with threshold and hysteresis), at
least “t on” time. “t on” range 0 ÷ 99.9, defined with 0.1 sec. resolution. Unit of
this parameter is set by “unit” parameter.

“toFF” - turn off delay time, the relay is turned off with delay equal “toFF” if the input value
exceeds appropriate border value (defined with threshold and hysteresis), at
least “toFF” time. “toFF” range 0 ÷ 99.9, defined with 0.1 sec. resolution. Unit of
this parameter is set by “unit” parameter.

If time when the input signal exceeds some border value is shorter than “t on” or
i “toFF” time, the relay do not change his state (see paragraph: CONTROL OF
THE RELAY OUTPUTS).

“unit” - unit of time for “t on” i “toFF” parameters. Can be set on one of two values:

“min” - minutes,
“SEC” - seconds.

“AL” - this parameter defines the relay reaction when some critical situations occurs:

“noCH” - relay do not change his state,


“on” - relay will be turned on,
“oFF” - relay will be turned off.

If parameter “modE” is set to “on” , “oFF”, “in” or “Out” the “critical situation”
means that allowable measurement range is exceeded.
If parameter “modE” is set to “modb”, the “critical situation” means
communication delay (when no data is received) longer than “mbtO” parameter
(see description: “rS” menu).

• If option “noCH” is selected for “AL” parameter, behaviour of the relay may
i depend on “FiLt” parameter in some cases. If “FiLt” is set to big value and the
input signal drops, result value of the measure will change slow, causes of
turning on or off relay due to thresholds values. The critical situation is slowly
detected, so it is impossible to predict the relay state in that situations.
24
User manual - METER SRP-73

• If parameter „AL” = „on”, the relay will be turned on in the critical situations,
even if his parameter “modE” = ”noAC”.

7.3.2. “inPt” menu


This menu presets the measurement input:

“tYPE" - type of the input / sensor. This parameter can be set to values:
”0-20”, “4-20” - current inputs.
”0-10”, “2-10”, ”0-5”, “1-5” - voltage inputs.
Displayed values are defined by parameters “Lo C”,”Hi C” (or by user defined
characteristic points) and parameter ”Pnt”.

”CHAr” - this option presets type of the conversion characteristic, and can be set to:
”Lin” - linear
“Sqr” - square When one of those characteristics is chosen display
“Sqrt” - square root range is defined by “Lo C” and “Hi C”.

“USEr” - user defined characteristic. Maximal length 20 points. Every point is


defined by user. Adding, Editing and Deleting of points is done by options
„AddP”, „EdtP”, „dELP” („InPt” menu) respectively.
“tn v” - volume characteristics of a cylindrical tank in the vertical position,
determined by parameters: „t h1”, ”t h2”, „t h3”, „t d”, „t Sn”, „t Sh” in „InPt”
menu (see below for details of the parameters),
“n h” - volume characteristics of a cylindrical tank in the horizontal position,
determined by parameters: „t h1”, ”t h2”, „t h3”, „t d”, „t Sn”, „t Sh” in „InPt”
menu (see below for details of the parameters).

i If user defined characteristic is selected, and if number of defined points is lower


than 2 then warning ”Errc” is displayed in measurement mode.

The process of displayed result calculation is described in details in DISPLAY VALUES


CALCULATION paragraph.
”FiLt” - this parameter sets filtration rate. It can be set to values from 0 (no filtration ) to 5
(strongest filtration – time window about 2 sec).

”Pnt” - decimal point position. It can be set to one of:


“ 0”, “ 0.0”, “ 0.00”, “0.000”
Decimal point position is changed by [^], [v] buttons.

“Lo C” These parameters describe the values displayed for minimum and maximum input
“Hi C” current. For example, if input type is set to 4-20 mA “Lo C” parameter defines the
value displayed when input current is equal 4 mA, and “Hi C” parameter defines
the value displayed for 20 mA of input current. Available range for these
parameters: -999 ÷ 9999. Negative values can be set by entering '-' sign on the first
position (by use of [^], [v] buttons).

If volume characteristics of a cylindrical tank is selected (parameter “CHAr” = ”tn


i v” or “CHAr” = ”tn h”) the parameters „Lo C” and „Hi C” are not available.

25
User manual - METER SRP-73

„t h1”, „t h2”, „t h3”, „t d” - the parameters defining shape of cylindrical tank


(Figure 7.1 and Figure 7.2).

a) for the cylindrical tank in the vertical position:

„t h1” - the height of the bottom part of a tank (in the elliptic paraboloid shape), this
parameter has the fixed precision - 2-decimal point,
„t h2” - the height of the middle part of a tank in the cylindrical shape, this parameter has
the fixed precision - 2-decimal point,

„t h3” - the height of the top part of a tank (in the elliptic paraboloid shape), this
parameter has the fixed precision - 2-decimal point,

„t d” - the diameter of the middle part of a tank, this parameter has the fixed precision -
- 2-decimal point,

b) for the cylindrical tank in the horizontal position:

„t h1” - the length of the left bottom of a tank (in the elliptic paraboloid shape), this
parameter has the fixed precision - 2-decimal point,

„t h2” - the length of the middle part of a tank in the cylindrical shape, this parameter has
the fixed precision - 2-decimal point,

„t h3” - the length of the right bottom of a tank (in the elliptic paraboloid shape), this
parameter has the fixed precision - 2-decimal point,

„t d” - the diameter of the middle part of a tank, this parameter has the fixed precision -
- 2-decimal point,

„t Sn”, „t Sh” - parameters defining the length and position of the sensor used to measure
level of liquids, gases or solids in the tank (Figure 7.1, 7.2).

„t Sn” - distance between end of the sensor and bottom of the tank, this parameter has
the fixed precision 2-decimal point but the unit is 100 times smaller than “t Sh”
(see Info below),

„t Sh” - the measuring range, this parameter has the fixed precision - 2-decimal point.

• The unit value of “t Sn” parameter is 100-fold less than the unit value of
i other parameters defining cylindrical tank, i.e. if we set value 10.00 in
“t Sh” parameter and set value 08.00 in "t Sn" parameter this mean that
value of “t Sn” parameter is real has 00.08 value in preserved unit of the
“t Sh” parameter.
• If we set parameters of tank in [m] unit (“t Sn” parameter takes [cm] unit
respectively, see above), than displays the result the volume of the tank in
[m3] unit, if we set parameters of tank in [cm] unit (“t Sn” parameter takes
[mm] unit respectively, see above), than displays the result the volume of
the tank in [cm3] unit.
26
User manual - METER SRP-73

• "t Sh" parameter may be greater than height (for vertical position) or
diameter (for horizontal position) of the tank, which means that the total
volume of the tank can be achieved by eg. such middle-current range,
• If the measurement value do not exceeds permissible measurement range
but displayed value exceeds range of 9999 than you can move to the right
position of the decimal point if it is still possible (see parameter Menu-
>”inPt”->”Pnt”).
• If in the volume characteristics of a cylindrical tank is exceeded the value
of the volume of the tank sets by parameters available in menu "inPt"
instead of the calculated result will be display warning “-Hi-”.

t h3

t Sh
t h2

td

h~I[mA]

t Sn
t h1

Figure 7.1 Parameters of cylindrical tank in vertical position.

27
User manual - METER SRP-73

t h1 t h2 t h3
t Sh

td

h~I[mA]
t Sn

Figure 7.2 Parameters of cylindrical tank in horizontal position.

If user defined characteristic is selected (parameter “CHAr” = ”USEr”) the


i parameters „Lo C” and „Hi C” are not available for modification, due to their values
are calculated from defined characteristic.

“AddP” - this menu allow user to add single point to the user defined characteristic.
After selection of this option device waits for „X” and „Y” coordinates of new point.
Modification of the coordinates is done accordingly to numerical parameters edition.
Coordinate „X” defines the percentage ratio of input current to selected current
range. The „X” range: -99,9 ÷ 199,9. Coordinate „Y” defines displayed value for
particular „X” value. The „Y” value can be changed in range: -999 ÷ 9999, decimal
point position depend on „Pnt” parameter (menu ”inPt ”).

• User can not enter two points with the same value of „X” coordinate. If user trays
i to do it, ”Err” warning is displayed. To modify any defined point use ”EdtP”
option.
• To distinguish „X” and „Y” coordinates, if „X” coordinate is displayed an
additional decimal point on utmost right position is displayed.
• If user defined characteristic is selected, and if number of defined points is lower
than 2 then warning ”Errc” is displayed in measurement mode.

“dELP” - this option allows user to delete any of the points of the user defined
characteristic. After selection current number of points of the user defined
characteristic is displayed for about approx. 1.5 sec. After that device waits for
selection of point being deleted (by [^], [v] buttons). The short pressing of [ENTER]
button causes by switching between X and Y value of the displayed point. The long
press (press and hold at least 2 sec) of [ENTER] button causes by displaying
„dEL?” ask. If [ENTER] button is pressed again, current point is deleted and new
updated number of points of the user defined characteristic is displayed.

28
User manual - METER SRP-73

“EdtP” - this option allows user to modify of particular point of the user defined
characteristic. After selection current number of points of the user defined
characteristic is displayed for about approx. 1.5 sec. After that device waits for
selection of point being edited (by [^], [v] buttons). The short pressing of [ENTER]
button causes by switching between X and Y value of the displayed point. The long
press (press and hold at least 2 sec) of [ENTER] button causes by entering to edit
the selected coordinate of the point. Modification of the coordinates is done
accordingly to numerical parameters edition.

“AddP”, ”dELP” and “EdtP” options are available only if the user defined
i characteristic is used (it means when parameter “CHAr” = ”USEr”).

“Lo r”, ”Hi r” - these parameters define the expansion of nominal range in percent. They
determine the permissible range of input signal (Figure 7.3).

The permissible range allow user to exceed the nominal range of input signal.
If input value is contained in the permissible range a proper result is displayed.
If input signal exceeds this range (defined by “Lo r” and “Hi r”), “-Lo-” or “-
Hi-” warning is displayed depend on input signal value.

”Lo r” = 75,0% (3 mA) ”Hi r” = 5,0 % (1 mA)

nominal measurement range (4-20mA)


Imin Imax

[mA]
0 1 4 20 21 22

permissible measurement range

measurement result is displayed


display regardless on nominal range exceeding display
message ”-Lo-” message ”-Hi-”

Figure 7.3 Example of definition of permissible range of input signal -


“Lo r” and “Hi r” parameters (“4-20” mode)

The “Lo r” parameter is important if input is set to “4-20”, “1-5” or “2-10” mode
only, and determines lower border of the permissible range. If input is set to
“0-20”, “0-5” or “0-10” mode then lower border of the permissible range is
always 0.
For example if input is set to “4-20” mode, then lower border is calculated due to
expression: Imin = 4 mA - 4 mA × “Lo r” %.
The “Lo r” value can be set from 0 to 99.9%.
Parameter “Hi r” determines the upper border of the permissible range accordingly
to the expression (for all modes).
For example if input is set to “4-20” mode, then upper border is calculated due to
expression: Imax = 20 mA + 20 mA × “Hi r” %.
The value of “Hi r” can be set from 0 to 19.9%

29
User manual - METER SRP-73

In example no 1 of the DISPLAY VALUES CALCULATION paragraph the


procedure of the permissible input range determining is presented in details.

If the measurement value do not exceeds permissible measurement range but


i displayed value exceeds range -999 ÷ 9999, the warning ”-Ov-” is displayed rather
than the calculated result.

7.3.3. ”bri” parameter


This parameter allows user to set bright of the LED display, bright can be set to
conventional values from 1 to 8.

7.3.4. ”CoL” menu


This menu contains settings related to signalisation via display colour. This kind of
signalisation consist in change of display colour (from basic colour to „active” colour) in defined
situations, for example after change of R1 state.
“SCoL” - basic colour ( the second one becomes „active” colour):

”grEE” - main colour is green,


”rEd” - main colour is red.

“C r1”,“C r2” - control the display colour according to relay (R1, R2 separate )state :

”oFF” - control for particular relay is off,


”on” - control for selected relay is on, the display will change its colour after
selected relay becomes active.

“C AL” - control the display colour according to alarm situations :

”oFF” - control is off,


”on” - control is on, the display will change its colour after alarm situation occurs.

“C Pr” - this setting enables additional threshold for display colour controlling, detailed
conditions of this control are defined by „dir”, „SEtP” and „HySt” parameters of
„CoL” submenu.

”oFF” - no additional threshold.


”on” - additional threshold enabled, the display will change its colour after result
satisfy conditions defined by „dir”, „SEtP” and „HySt” parameters of „CoL”
submenu.

“dir” - this parameter defines the direction of result changes activating change of display
colour:

”morE” - display will change its colour after the result is higher than
threshold +hysteresis
”LESS” - display will change its colour after the result is lower than
threshold + hysteresis

30
User manual - METER SRP-73

“SEtP” - additional threshold value (range -999 ÷ 9999 ). Negative values can be input by
selecting a “-” sign on first digit ( to change value use [^] and [v] buttons).
Threshold is the medium value of relay hysteresis.

“HYSt” - Hysteresis of colour indication (range 0 ÷ 999). Full hysteresis is equal to 2x


“HYSt” parameter. The display colour can change when an input signal is out of
threshold-hysteresis to threshold+hysteresis zone.

i
Presented parameters should be set to ensure that ”SEtP” + ”HYSt” and
”SEtP” - ”HYSt” do not exceeds the measure range.

“CrES” - permission to use any local key to acknowledgement of display colour change.
Acknowledgement causes clear of all events generating display colour changes (to
active colour), and restores basic colour of the display.

”oFF” - acknowledgement disabled,


”on” - acknowledgement enabled.

7.3.5. ”HOLd” menu


This menu contains parameters connected with peak detection function. See also full
description of the peak detection function in paragraph: DETECTION OF THE PEAK VALUES
“modE” - the type of detected changes of the input signal, can be set to values:

”norm” - peaks, peak and next drop of the input signal of value equal at least “PEA”,
”inv” - drops, drop and next peak of the input signal of value equal at least “PEA”,

“PEA” - minimal detected signal change classified as peak or drop (see Figure 6.3)

“timE” - maximum time of displaying of the peak (drop) value, can be set from 0.0 to 19.9
sec, with 0.1 sec. resolution. If „HdiS”=”HOLD” then setting parameter "timE"=0.0
causes holding peak value until [ESC] button is pressed. If „HdiS”=”rEAL” then
value "timE"=0.0 means no holding.

“HdiS” - type of displayed values:

”rEAL” - current value is displayed,


”HOLd” - peak (drop) value is displayed,

“H r1”, “H r2” - relay/LED outputs (R1, R2) operation mode:

”rEAL” - relay/LED operates depend on the current value,


”HOLd” - relay/LED operates depend on the peak (drop) value.

31
User manual - METER SRP-73

7.3.6. ”SECu” menu


This menu contains presets connected with availability of other parameters:

“Scod” - user password (4-digits number). If this parameter is set at value “0000”, user
password is turned off.

If the user do not remember his password, the access to the menu is possible
by the “one-use password”. To get this password please contact with
Marketing Division. “Single use password” can be used only one time, after
that it is destroyed. Entering this password causes in clearing of user
password, it means sets the user password to „0000”.

i The “one-use password” can be used ONE TIME ONLY, it is impossible to use it
again! The “one-use password” can be restored by Service Division only.

“A r1, A r2” - this option permits user (”on”) or prohibits (”oFF”) to modify the thresholds of
the relays/LEDs R1, R2 without knowledge about user password.

7.3.7. ”rS” menu

This menu is connected with RS-485 interface, and sets his properties:

”Addr” - this parameter defines the address of the device, accordingly to Modbus protocol.
It can be set in range from 0 to 199. If the value 0 is set then device, responds to
frames with address 255 (FFh).

”bAud” - this parameter determines RS-485 interface baud rate. It can be set to one of 8
possible values: ”1.2”, ”2.4”, ”4.8”, ”9.6”, ”19.2”, ”38.4”,”57.6”,”115.2”, which
respond to the baud rates of 1200, 2400, 4800, 9600, 19200, 38400, 57600 and
115200 bit/s respectively.
”mbAc” - this parameter sets the access to the configuration registers of the device.
Possible values:
”on” - configuration registers can be set via RS-485 interface,
”oFF” - configuration registers can not be set via RS-485 interface.

The access to registers no 04h i 05h cant be denied by ”mbAc” parameter (see:
i LIST OF REGISTERS).

”mbtO” - this parameter defines maximal time (sec) between following frames received by
the device. If the delay will be greater than the value of ”mbtO” parameter, the
relays which are controlled via RS-485 interface, will set to alert state (see “rEL1”
menu description). Parameter “mbtO” can be set to values from 0 to 99 seconds.
The value 0 means that the time will be not controlled.
”rESP” - this parameter defines minimal (additional) delay between the Modbus message
and the answer of the device (received and sent via RS-485 interface). This
additional delay allows the device to work with poor RS-converters which do not
works properly on baud rates higher than 19200. This parameter can be set to one
of values:
32
User manual - METER SRP-73

”Std” - answer as quick as possible, no additional delay


” 10c”
” 20c”
- answer delayed of 10, 20, 50, 100 of 200 chars respectively, where
” 50c”
one character time depends on selected baud rate
”100c”
”200c”

In the most cases parameter ”rESP” should be set to ”Std” (no additional delay).
i Unfortunately for some third party RS-converters ”rESP” should be adjusted
experimentally. Table 7.1 contains most frequently used values.

”bAud” parameter “38.4” “57.6” “115.2”


”rESP” parameter “ 10c” “ 20c” “ 50c”

Tab.7.1. Settings of ”rESP” parameter


7.3.8. ”Edit” parameter
This parameter allows to change the edition mode of numerical parameters:
”dig” - the change to “by digit” mode,
”Slid” - slide change mode.

7.3.9. ”dEFS” parameter


This setting allows to restore the factory settings of the device. To get the access to this
option special password is required: „5465”, next the device displays acknowledge question
„SEt?”. Press [ENTER] to acknowledge the restoring of factory settings or [ESC] to cancel.

7.3.10. ”SErv” menu


This menu contains the parameters for authorized service only. To enter this menu
proper service password must be entered. Improper settings can causes of damage of the
device.

33
User manual - METER SRP-73

7.4. MENU STRUCTURE


Measurement mode
ESC
MENU
Press and hold at least 2 seconds
ESC
MENU

0___ 4-digit user password entering (if it is different from „0000”)


ENTER

ESC ENTER ENTER


MENU

rEL1 SEtP Parameter


ENTER
ESC edition
MENU

SEt2

HYSt
ESC ENTER
MENU
Options similar
rEL2
modE
ESC
ESC to „rEL1” menu MENU
MENU

t on

toFF

unit
ENTER ENTER
ESC
MENU
tYPE Parameter
inPt
ENTER
ESC edition
MENU

AL
CHAr

FiLt
ESC
MENU

Pnt

Lo C

Hi C

t h1

t h2

t h3

td

t Sn

t Sh
ESC ENTER
MENU
Parameter
bri AddP
ENTER
ESC edition
MENU

dELP

EdtP

Lo r

See next page Hi r

34
User manual - METER SRP-73

See previous page

ENTER ENTER
ESC
MENU
SCoL Parameter
CoL
ENTER
ESC edition
MENU

C r1

C r2

C AL
ESC
MENU

ESC ENTER ENTER


MENU

modE Parameter
HOLd
ENTER
ESC edition C Pr
MENU

PEA
dir

timE Visible only if


SEtP
„C Pr” = „on”
Hdis
ESC
MENU

HYSt

H r1
CrES

H r2

ESC ENTER ENTER


MENU

SECu Scod Parameter


ENTER
ESC edition
MENU

ESC A r1
MENU

A r2

ENTER ENTER
ESC
MENU
Addr Parameter
rS
ENTER
ESC edition
MENU

bAud

ESC
MENU mbAc

mbtO
ESC ENTER
MENU Parameter
Edit edition
ESC
MENU
rESP

4-digit special
password entering
ESC ENTER ENTER ENTER
MENU

dEFS 0___ SEt? Default settings


ESC restoring
MENU
ESC
MENU

ESC
MENU

SErv

35
User manual - METER SRP-73

8. THE ALARM LED


The ALARM LED (AL) is turned on when input signal is out of the permissible input
range. See parameters: “tyPE”, “Lo r” and “Hi r” in paragraph „InPt” menu.

9. OVER-CURRENT PROTECTION
The current input of the device is equipped with over-current protection circuit. This circuit
protects the standard resistor against damage. Maximum input current is set to 40mA (typical).
When temperature of the standard resistor falls, the protection circuit will turn on automatically,
and the device will measure the input current again. Due to thermal phenomenon in the
standard resistor, precision of the measurement may be lower until to the standard resistor
temperature will falls to the environment temperature.

10. DISPLAYED VALUES CALCULATION


For simplicity of examples it's assumed that current input is selected, and all calculations
are related to this input. When voltage input is selected calculations are similar (be sure of
particular ranges and units).
The first step to compute the result of measure is the calculation of the normalized result
(it means result of 0-1 range). To do it, the begin of the input range (0 mA for 0-20mA range,
and 4mA for 4-20mA range) must be subtracted from measured value. Next, received result
must be divided by the width of the input range ( it means 20mA for 0-20mA range, and 16mA
for 4-20mA range). So normalized result can be expressed by expressions:

I inp. −4
I n= for 4 ÷ 20 mA range
16
I inp.
I n= for 0 ÷ 20 mA range
20

where Iinp. Means input current (in mA), and In – normalized result.

If measured value exceeds the nominal input range (0-20mA or 4-20mA), and do
i not exceed the permissible input range, then received normalized In result exceeds
0-1 range, e.g. input range 4-20 mA, input current = 3 mA – the normalized result is
equal -0,0625, and for input current = 22 mA, the normalized result is equal 1,125.
In such cases presented expressions are still correct.

10.1. ADDITIONAL CALCULATIONS (USED CONVERSION CHARACTERISTIC)


The manner of the additional computation of the displayed result depends on selected
conversion characteristic. All presented charts are connected with the input range 4 - 20 mA.

36
User manual - METER SRP-73

10.1.1. Linear characteristic


The normalized result is converted by fixed coefficients determined by “Lo C” and “Hi C”
parameters (when the normalized results is equal 0, then value “Lo C” is displayed, and when
the normalized results is equal 1, then value “Hi C” is displayed). Expression presented below
shows the manner of result calculation:

W =I n × "Hi C" −"Lo C"   "Lo C" ,

where W means the displayed value.

The value of the “Lo C” parameter can be higher than the value of “Hi C”
i parameter. In such a case, for an increasing value of input current the displayed
value decreases.

Hi C Lo C
Displayed

Displayed
value
value

Lo C Hi C

0 4 8 12 16 20 0 4 8 12 16 20
Input current [mA] Input current [mA]

Figure. 10.1 Normal („Lo C” < ”Hi C) and inverted („Lo C” > ”Hi C) characteristic

10.1.2. Square characteristic


The normalized result is squared and further conversion is done as for linear characteristic.
Conversion is made accordingly with the expression:
2
W =I n × "Hi C" −"Lo C"   "Lo C" ,

where W means the displayed value.

Hi C Lo C
Displayed

Displayed
value

value

Lo C Hi C
0 4 8 12 16 20 0 4 8 12 16 20
Input current [mA] Input current [mA]

Figure. 10.2 Normal („Lo C” < ”Hi C) and inverted („Lo C” > ”Hi C) characteristic

37
User manual - METER SRP-73

10.1.3. Square root characteristic


The normalized result is rooted and further conversion is done as for linear characteristic.
Conversion is made accordingly with the expression:

W = I n × "Hi C" −"Lo C"   "Lo C" ,

where W means the displayed value.

Showed above expression is not valid when normalized result is negative. It is


i possible for 4-20 mode only. In this case (I n<0) the displayed result is equal “Lo C”
(see graphs below).

Hi C Lo C
Displayed

Displayed
value

value
Lo C Hi C
0 4 8 12 16 20 0 4 8 12 16 20
Input current [mA] Input current [mA]

Figure. 10.3 Normal („Lo C” < ”Hi C) and inverted („Lo C” > ”Hi C) characteristic

10.1.4. User defined characteristic


User defined characteristic is defined as set of X-Y points. Number of the points is variable and
may be set from 2 to 20 points which make linear segments (see graph and see Menu ”inPt”).
Due to the normalized result I n , the device computes specific segment, e.g. for characteristic
from figure below, and In = 0,65 the segment between points X = ”50.0.” and X = ”70.0.” will
be chosen.
Let's mark those points as PL (point low) i PH (point high) - in this example PL= “50.0,” and
PH = “70.0.”, and the normalized result I n for the point PL as I p (in this example Ip = In(PL) =
0,5). The displayed result is calculated accordingly to the expression:

[Y PH −Y  PL]


W = I n − I p  × × 100  Y  PL
[ X PH − X  PL]

where Y(PH), X(PH), Y(PL), X(PL) mean values of X and Y coordinates of PH i PL points.

If the normalized result exceeds the user defined characteristic values, then specific
i utmost segment, defined by two next points, is used for calculations. If characteristic
from figure below is used, and if In>1 then segment defined by points
X(PL) = “90.0.”, X(PH) = “100.0.” will be used.

38
User manual - METER SRP-73

Normalized measurement In (for 0-20 mA range)


0 0,2 0,35 0,5 0,7 0,9 1

5-elements characteristic

X (PH) = „70.0.”
Y (PH)
Displayed value

X = „35.0.”
Y (PL)
X (PL) = „50.0.”

X = „20.0.”

Prąd wejściowy [mA]


X = „90.0.”

X = „100.0.”

0 4 8 12 16 20
Input current [mA]

Figure. 10.4 Example of user defined characteristic

10.1.5. Volume characteristics of a cylindrical tank


Volume characteristics of a cylindrical tank is defined by parameters of tank (see menu
”inPt”). Normalized input is proportional to level 'h' and linear scaling by parameters: "t Sn", "t
Sh" (for normalized input value equal 0, displays value "t Sn" and for normalized input value
equal 1, displays value "t Sh"+"t Sn" (Figure 10.5).
The linear scaling can be expressed as follow:

h=In·"t Sh"+"t Sn"

where 'h' is level of liquids, gases or solids in the tank, see Figure 7.1, 7.2.

”t Sh”+”t Sn”
Level 'h'

”t Sn”

0 4 8 12 16 20
Input current [mA]

Figure 10.5 The characteristic of level of liquids, gases or solids in tank depending on input
current in 4÷20mA range.

39
User manual - METER SRP-73

Volume of tank can be write by general formula:

V =∫ P p⋅dh
Possible combination of tank shape for calculation the volume:

cylindrical
tank in
vertical
position

cylindrical
tank in
horizontal
position

parameter t h2=0 t h3=0 t h2=0 t h1=0 - t h1=0 t h1=0


s setting
(for vertical t h3=0 t h3=0 t h2=0
and
horizontal
position of
tank)

10.2. EXAMPLES OF CALCULATIONS

Example 1: Selection of the permissible input range (“4-20” mode)

If in “4-20” mode the user sets “Lo r” = 20,0% and “Hi r” = 10,0%, then permissible
input currents range will be equal: 3,2 mA ÷ 22 mA. Lower border of the range is the result of
calculations: 4 mA - 4 mA × 20%, and the higher : 20 mA + 20 mA × 10%.

Example 2: The normalized In result calculation

Let the input mode = 4-20 mA. The normalized I n result is calculated accordingly to the
expression on page 36, so if Iin = 10 mA then 10 mA - 4 mA = 6 mA, and this result should be
divided by the width of input range (16 mA). Finally the normalized result: I n = 6/16 = 0,375.

In case when input current exceeds nominal measurement range, calculations are similar. For
example if input current is equal 2,5 mA then In = (2,5 - 4)/16 ≅ -0,0938, and if input current is
equal 20,5 mA then In = (20,5 - 4)/16 ≅ 1,0313.

40
User manual - METER SRP-73

Example 3: The linear characteristic

Let the input mode = 4-20 mA, and parameters “Lo C” and “Hi C” equal to -300 and 1200
respectively. The calculations will be done for three different input currents from example 2.

a) Iin =10 mA and In = 0,375


Accordingly to expression on page 37 for linear characteristic:
0,375 × [1200 -(- 300)] ≅ 562 and next, the “Lo C” value is added to the result , so the
displayed value:
W ≅ 562 + (-300) = 262

b) Iin = 2,5 mA and In = -0,0938.


W ≅ -441.

c) Iin = 20,5 mA and In = 1,0313.


W ≅ 1247.

Example 4: The square characteristic

Let the input mode = 4-20 mA, and parameters “Lo C” and “Hi C” equal to -300 and 1200
respectively. The calculations will be done for there different input currents from example 2.

a) Iin =10 mA and In = 0,375


Accordingly to expression on page 37 for square characteristic: (0,375) 2 × [1200 -(- 300)] ≅
211.
and next, the “Lo C” value is added to the result , so the displayed value:
W ≅ 211 + (-300) = -89

b) Iin = 2,5 mA and In = -0,0938.


W ≅ -287.

c) Iin = 20,5 mA and In = 1,0313.


W ≅ 1295.

Example 5: The square root characteristic

Let the input mode = 4-20 mA, and parameters “Lo C” and “Hi C” equal to -300 and 1200
respectively. The calculations will be done for there different input currents from example 2.

a) Iin =10 mA and In = 0,375


Accordingly to expression on page 38 for square root characteristic:
 0,375 × [1200 -(- 300)] ≅ 919.
and next, the “Lo C” value is added to the result , so the displayed value:
W ≅ 919 + (-300) = 619

b) Iin = 2,5 mA and In = -0,0938 , normalized result is negative , so the displayed value is equal
to “Lo C” parameter: W ≅ “Lo C” = -300.

c) Iin = 20,5 mA and In = 1,0313.


W ≅ 1223.

41
User manual - METER SRP-73

Example 6: The user defined characteristic

Let the input mode = 4-20 mA, and the user selected the 10 segment characteristic. To do this
it is necessary to enter X and Y coordinates of 11 points (see Menu ”inPt”).
The calculations will be done for three different input currents from example 2, so in
calculations some of the segments will be used only.

Let the following points will be given:


X1 = “00.0.”, Y1 = “-50.0”,
X2= “10.0.”, Y2 = “-30.0”,
....
X6 = “30.0.”, Y6 = “30.0”,
X7 = “40.0.”, Y7 = “80.0”,
....
X10 = “90.0.”, Y10 = “900.0”,
X11 = “100.0.”, Y11 = “820.0”,

Additionally all other points must to be defined and stored in the device memory.

a) Iin =10 mA and In = 0,375

The segment defined by X6 = “30.0.” and X7 = “40.0.” for this In will be selected. Accordingly
to expressions given for user defined characteristic (see page 38) X6(PL) = 30, Y6(PL) = 30,
X7(PH) = 40, Y7(PH) = 80 and Ip = 0,3 , the displayed value :

[Y  PH −Y PL ]
W = I n − I p  × × 100  Y  PL =
[ X  PH − X  PL]

[80−30]
=0,375−0,3 × × 100  30 ≃ 67
[ 40−30 ]

b) Iin = 2,5 mA and In = -0,0938, because of the normalized I n value is lower than 0, the
segment defined by X1 and X2 will be selected. X1(PL) = 0, Y1(PL) = -50, X2(PH) = 10,
Y2(PH) = -30 and Ip = 0. For these values the displayed value W ≅ -69.

c) Iin = 20,5 mA and In = 1,0313. , because of the normalized In value is higher than 1, the
segment defined by X10 and X11 will be selected, and X10(PL) = 90, Y10(PL) = 900,
X11(PH) = 100, Y11(PH) = 820 and Ip = 0,9 for these values the displayed value W ≅ 795.

Example 7: Volume characteristics of a cylindrical tank in the vertical position

We assume that the user has oil tank in the shape of the cylinder located in vertical position.
The tank has dimmention: height 10m, diameter 4m and length of the sensor 10m. The output
of signal of the sensor has 4÷20mA range.
In first step, we set type of input range 4÷20mA (see parameter MENU->"InPt"->"tYPE").
Next we defined the parameters of tank dimension and location of sensor:

42
User manual - METER SRP-73

„t Sn”=00,00
„t Sh”=10,00

„t h1”=00,00
„t h2”=10,00
„t h3”=00,00
„t d”=04,00

140
120

100

80
V [m3]

60

40

20

0
2 4 6 8 10 12 14 16 18 20 22
Input current [mA]

Figure 10.6 The volume characteristic of tank depending on input current in 4÷20mA range.

Example 8: Volume characteristics of a cylindrical tank in the horizontal position


We assume that the user has tank for wheat in the shape of the cylinder located in horizontal
position. The tank has dimension: height in first part is 2m, height in second part is 8.05m,
diameter 3.26m and length of the sensor 10m. The output of signal of the sensor has 4÷20mA
range.
In first step, we set type of input range 4÷20mA (see parameter MENU->”InPt”->”tYPE”).
Next we defined the parameters of tank dimension and location of sensor:

„t Sn”=00,00
„t Sh”=10,00

„t h1”=02,00
„t h2”=08,05
„t h3”=00,00
„t d”=03,26

43
User manual - METER SRP-73

80
70
60
50
V [m3]

40
30
20
10
0
3 4 5 6 7 8 9 10
I [mA]

Figure 10.7 The volume characteristic of tank depending on input current in 4÷20mA range.

11. THE MODBUS PROTOCOL HANDLING


Transmission parameters: 1 start bit, 8 data bits, 1 or 2 stop bit (2 bits are send, 1 and 2 bits
are accepted when receive), no parity control
Baud rate: selectable from: 1200 to 115200 bits/second
Transmission protocol: MODBUS RTU compatible

The device parameters and display value are available via RS-485 interface, as HOLDING-
type registers (numeric values are given in U2 code) of Modbus RTU protocol. The registers
(or groups of the registers) can be read by 03h function, and wrote by 06h (single registers) or
10h (group of the registers) accordingly to Modbus RTU specification. Maximum group size for
03h and 10h functions can not exceeds 16 registers (for single frame).

i The device interprets the broadcast messages, but then do not sends the answers.

44
User manual - METER SRP-73

11.1. LIST OF REGISTERS

Register Write Range Register description


01h No -999 ÷ 9999 Measurement value (no decimal point)
The status of the current measurement; 0h - data valid; A0h - top
02h No 0h, A0h, 60h border of the measurement range is exceeded; 60h - bottom border
of the measurement range is exceeded;
“Pnt ” parameter in “InPt” menu (decimal point position)
03h Yes 0÷3
0 - “ 0”; 1 - “ 0.0”; 2 - “ 0.00”; 3 - “0.000”
State of the relays and alarm LED (binary format)
(1 - on, 0 - off): 00000000 000e00ba
04h Yes see descr. a - relay R1; b - relay R2; e - alarm LED;
If written, only a, b bits are important (others are ignored) these
bits allows user to control the relays via RS-485 interface
06h No -999 ÷ 9999 Peak (drop) value (no decimal point)
“tyPE” parameter in “InPt” menu (nominal input range).
10h Yes 0÷5 0 - 0-20 mA range; 1 - 4-20 mA range; 2 - 0-10 V range;
3 - 2-10 V range; 4 - 0-5 V range; 5 - 1-5 V range
“CHAr” parameter in “InPt” menu (characteristic type)
0 - linear ; 1 - square; 2 - square root; 3 - user defined; 4 - volume
11h Yes 0÷5
characteristics of a cylindrical tank in the vertical position; 5 -
volume characteristics of a cylindrical tank in the horizontal position
12h Yes 0÷5 “FiLt” parameter in “InPt” menu (measurement filtering rate)
“Pnt ”parameter in “InPt” menu (the copy of 03h register, decimal
13h Yes 0÷3
point position) 0 - “ 0”; 1 - “ 0.0”; 2 - “ 0.00”; 3 - “0.000”
14h Yes -999 ÷ 9999 “Lo C” parameter in “InPt” menu, no decimal point included
15h Yes -999 ÷ 9999 “Hi C” parameter in “InPt” menu, no decimal point included
16h Yes 0 ÷ 999 “Lo r” parameter in “InPt” menu, in 0.1%
17h Yes 0 ÷ 199 “Hi r” parameter in “InPt” menu, in 0.1%
18h Yes 0 ÷ 9999 “t h1” parameter in “InPt” menu, no decimal point included
19h Yes 0 ÷ 9999 “t h2” parameter in “InPt” menu, no decimal point included
1Ah Yes 0 ÷ 9999 “t h3” parameter in “InPt” menu, no decimal point included
1Bh Yes 0 ÷ 9999 “t d” parameter in “InPt” menu, no decimal point included
1Ch Yes 0 ÷ 9999 “t Sn” parameter in “InPt” menu, no decimal point included
1Dh Yes 0 ÷ 9999 “t Sh” parameter in “InPt” menu, no decimal point included
20h2 Yes 0 ÷ 199 Device address
20F7h Device identification code (ID)
21h No
20F3h Device identification code (IP65 version)
“bAud” parameter in “rS” menu (baud rate);
22h3 Yes 0÷7 0 - 1200 baud; 1 - 2400 baud; 2 - 4800 baud; 3 - 9600 baud;
4 - 19200 baud; 5 - 38400 baud; 6 - 57600 baud; 7 - 115200 baud

45
User manual - METER SRP-73

Register Write Range Register description


“mbAc” parameter in “rS” menu (permission to write registers via
23h4 Yes 0÷1
RS-485 interface); 0 - write denied ; 1 - write allowed
Parameters of “SECU” menu (binary format (0 - „oFF”, 1 - „on”):
24h Yes see descr. bit 0 - “A r1” parameter; bit 1 - “A r2” parameter
bit 2 - “A r3” parameter; bit 3 - “A r4” parameter
“rESP” parameter in “rS” menu (additional response delay);
25h Yes 0÷5 0 - no additional delay; 1 - ”10c” option; 2 - ”20c” option;
3 - ”50c” option; 4 - ”100c” option; 5 - ”200c” option;
“mbtO” parameter in “rS” menu (maximum delay between
27h Yes 0 ÷ 99 received frames); 0 - no delay checking;
1 ÷ 99 - maximum delay expressed in seconds
“bri” parameter (display brightness);
2Dh Yes 1÷8
1 - the lowest brightness; 8 - the highest brightness
“SCoL” parameter in “CoL” menu (main colour of display);
2Eh Yes 0÷1
0 - green; 1 - red
“Edit” parameter (numerical parameters edit mode);
2Fh Yes 0÷1
0 - „dig” mode; 1 - „SLid” mode
30h Yes -999 ÷ 9999 “SEtP” parameter in “rEL1” menu, no decimal point included
31h Yes -999 ÷ 999 “HySt” parameter in “rEL1” menu, no decimal point included
“modE” parameter in “rEL1” menu:
32h Yes 0÷5 0 - “noAC” mode; 1 - “on” mode; 2 - “oFF” mode; 3 - “in” mode;
4 - “out” mode; 5 - “modb” mode
“t on” parameter in “rEL1” menu, expressed in tenth of seconds or
33h Yes 0 ÷ 999
tenth of minutes depend on “unit” parameter - register no. 35h)
“toFF” parameter in “rEL1” menu, expressed in tenth of seconds
34h Yes 0 ÷ 999
or tenth of minutes depend on “unit” parameter - register no. 35h)
“unit” parameter in “rEL1” menu:
35h Yes 0÷1
0 - seconds; 1 - minutes
36h Yes 0÷2 “AL” parameter in “rEL1” menu: 0 - no changes; 1 - on; 2 - off
37h Yes -999 ÷ 9999 “SEt2” parameter in “rEL1” menu, no decimal point included
38h Yes -999 ÷ 9999 “SEtP” parameter in “rEL2” menu, no decimal point included
39h Yes -999 ÷ 999 “HySt” parameter in “rEL2” menu, no decimal point included
“modE” parameter in “rEL2” menu:
3Ah Yes 0÷5 0 - “noAC” mode; 1 - “on” mode; 2 - “oFF” mode; 3 - “in” mode;
4 - “out” mode; 5 - “modb” mode
“t on” parameter in “rEL2” menu, expressed in tenth of seconds or
3Bh Yes 0 ÷ 999
tenth of minutes depend on “unit” parameter - register no. 3Dh)
“toFF” parameter in “rEL2” menu, expressed in tenth of seconds
3Ch Yes 0 ÷ 999
or tenth of minutes depend on “unit” parameter - register no. 3Dh)
“unit” parameter in “rEL2” menu:
3Dh Yes 0÷1
0 - seconds; 1 - minutes

46
User manual - METER SRP-73

Register Write Range Register description


3Eh Yes 0÷2 “AL” parameter in “rEL2” menu: 0 - no changes; 1 - on; 2 - off
3Fh Yes -999 ÷ 9999 “SEt2” parameter in “rEL2” menu, no decimal point included
“modE” parameter in “HOLd” menu (type of detected changes):
50h Yes 0÷1
0 - peaks; 1 - drops
“PEA” parameter in “HOLd” menu (minimum detectable change, no
51h Yes 0 ÷ 9999
decimal point included)
“timE” parameter in “HOLd” menu, maximum peaks' (or drops')
52h Yes 0 ÷ 199
display time expressed in seconds
“HdiS” parameter in “HOLd” menu:
53h Yes 0÷1
0 - “rEAL” mode ; 1 - “HOLd” mode
“H r1” parameter in “HOLd” menu :
54h Yes 0÷1
0 - “rEAL” mode ; 1 - “HOLd” mode
“H r2” parameter in “HOLd” menu:
55h Yes 0÷1
0 - “rEAL” mode ; 1 - “HOLd” mode
Parameters of “CoL” menu (binary format, 0 - „oFF”, 1 - „on”):
bit 7 - “C AL” parameter;
60h Yes see descr. bit 6 - “C Pr” parameter;
bit 1 - “C r2” parameter;
bit 0 - “C r1” parameter.
“CrES” parameter in “CoL” menu (reset of colour indication):
61h Yes 0÷1
0 - „oFF”; 1 - „on”
“dir” parameter in “CoL” menu (direction of value changes):
62h Yes 0÷1
0 - „morE”; 1 - „LESS”
63h Yes -999 ÷ 9999 “SEtP” parameter in “CoL” menu, no decimal point included
64h Yes -999 ÷ 999 “HySt” parameter in “CoL” menu, no decimal point included
The value of „X” coordinate of point no. 1 of the user defined
70h5 Yes -999 ÷ 1999
characteristic, expressed in 0.1%
The value of „Y” coordinate of point no. 1 of the user defined
71h5 Yes -999 ÷ 9999
characteristic, no decimal point included
Further pairs of „X” - „Y” coordinates of points no. 2 ÷ 19 of the
72h5 ÷ 95h5
user defined characteristic
The value of „X” coordinate of point no. 20 of the user defined
96h5 Yes -999 ÷ 1999
characteristic, expressed in 0.1%
The value of „Y” coordinate of point no. 20 of the user defined
97h5 Yes -999 ÷ 9999
characteristic, no decimal point included

2 - after writing to register no 20h the device responds with an “old” address in the message.
3 - after writing to register no 22h the device responds with the new baud rate.
4 - the value of the “mbAc” parameter is also connected to write to this register, so it is possible to block a writes, but
impossible to unblock writes via RS-485 interface, The unblocking of the writes is possible from menu level only.
5 - the pairs of „X -Y” coordinates may be defined for any free point. The pair is “free” (it means that particular point is
not defined) if „X” coordinate of this point is equal 8000h. After writing both X and Y coordinate the point is defined
and used in calculation of result. The coordinates of any point can be changed at any time.

47
User manual - METER SRP-73

11.2. TRANSMISSION ERRORS DESCRIPTION


If an error occurs while write or read of single register, then the device sends an error
code according to Modbus RTU specifications (example message no 1).

Error codes:
01h - illegal function (only functions 03h, 06h and 10h are available),
02h - illegal register address
03h - illegal data value
08h - no write permission ( see: “mbAc” parameter)
A0h - exceed of upper border of input range
60h - exceed of lower border of input range

A0h and 60h codes can appear only during reg. 01h is reading by 03h function (read of
a single register).

11.3. EXAMPLES OF QUERY/ANSWER FRAMES

Examples apply for device with address 1. All values are represent hexadecimal.

Field description:
ADDR Device address on modbus network
FUNC Function code
REG H,L Starting address (address of first register to read/write, Hi and Lo byte)
COUNT H,L No. of registers to read/write (Hi and Lo byte)
BYTE C Data byte count in answer frame
DATA H,L Data byte (Hi and Lo byte)
CRC L,H CRC error check (Hi and Lo byte)

1. Read of the displayed value (measurement), SRP-73 device address = 01h:

ADDR FUNC REG H,L COUNT H,L CRC L,H


01 03 00 01 00 01 D5 CA

a) The answer (we assume that the measure result is not out of range):

ADDR FUNC BYTE C DATA H,L CRC L,H


01 03 02 00 FF F8 04

DATA H, L - displayed value = 255, no decimal point.


Decimal point position can be read from reg. 03h.

48
User manual - METER SRP-73

b) The answer (if an error occur):

ADDR FUNC ERROR CRC L,H


01 83 60 41 18

ERROR - error code = 60h, bottom border of the measurement range is exceeded

2. Read of device ID code

ADDR FUNC REG H,L COUNT H,L CRC L,H


01 03 00 21 00 01 D4 00

The answer:

ADDR FUNC BYTE C DATA H,L CRC L,H


01 03 02 20 F7 E0 02

DATA - identification code (20F7h)


3. Change of the device address from 1 to 2 (write to reg. 20h)

ADDR FUNC REG H,L DATA H,L CRC L,H


01 06 00 20 00 02 09 C1

DATA H - 0
DATA L - new device address (2)

The answer (the same as the message):

ADDR FUNC REG H,L DATA H,L CRC L,H


01 06 00 20 00 02 09 C1

4. Change of baud rate of all devices connected to the net (BROADCAST message).

ADDR FUNC REG H,L COUNT H,L CRC L,H


00 06 00 22 00 04 29 D2

DATA H - 0
DATA L - 4, new baud rate 19200 baud

i Device do not reply to BROADCAST-type messages.

49
User manual - METER SRP-73

5. Read of the registers 1, 2 and 3 in one message (example of reading a number of


registries in one frame):

ADDR FUNC REG H,L COUNT H,L CRC L,H


01 03 00 01 00 03 54 0B

COUNT L - the count of being read registers (max.16)

The answer:

ADDR FUNC BYTE C DATA H1,L1 DATA H2,L2 DATA H3,L3 CRC L,H
01 03 06 00 0A 00 00 00 01 78 B4

DATA H1, L1 - reg. 01h (10 - displayed value ”1.0”),


DATA H2, L2 - reg. 02h (0 - no errors),,
DATA H3, L3 - reg. 03h (1 - decimal point position ” 0.0”).

i There is no full implementation of the Modbus Protocol in the device. The


functions presented above are available only.

50
User manual - METER SRP-73

12. DEFAULT AND USER'S SETTINGS LIST

Desc.
Parameter Description Default value User's value
page

Parameters of relay R1 operation (“rEL1” menu)


SEtP Relay R1 threshold 20.0 23
SEt2 Relay R1 second threshold 40.0 23
HYSt Hysteresis of relay R1 0.0 23
modE Operation mode of relay R1 on 23
t on Turn on delay of relay R1 0.0 24
toFF Turn off delay of relay R1 0.0 24
unit Unit of “t on”, “toFF” parameters of relay R1 SEC 24
AL Reaction for critical situation of relay R1 oFF 24
Parameters of relay R2 operation (“rEL2” menu)
SEtP Relay R2 threshold 40.0 23
SEt2 Relay R2 second threshold 60.0 23
HYSt Hysteresis of relay R2 0.0 23
modE Operation mode of relay R2 on 23
t on Turn on delay of relay R2 0.0 24
toFF Turn off delay of relay R2 0.0 24
unit Unit of “t on”, “toFF” parameters of relay R2 SEC 24
AL Reaction for critical situation of relay R2 oFF 24
Configuration of measurement input (“inPt” menu)
tYPE Input mode „4-20” 25
CHAr Conversion characteristic mode Lin 25
FiLt Filtering ratio 0 25
Pnt Decimal point position 0.0 25
Lo C Minimum displayed value (for nominal range) 000.0 25
Hi C Maximum displayed value (for nominal range) 100.0 25
t h1 Height (length) first part of the tank 00.00 26
t h2 Height (length) second part of the tank 00.00 26
t h3 Height (length) third part of the tank 00.00 26
td Tank diameter 00.01 26
t Sn Distance between sensor and bottom of the tank 00.00 26
t Sh Height of the sensor 20.00 26
Lo r Extension of the bottom of the nominal input range 5.0 (%) 29

51
User manual - METER SRP-73

Desc.
Parameter Description Default value User's value
page

Hi r Extension of the top of the nominal input range 5.0 (%) 29


Display parameters
bri Display brightness bri6 30
Signalization via colour of the display (“CoL” menu )
SCoL Basic colour of the display grEE 30
C r1 Change display colour after R1 is activated oFF 30
C r2 Change display colour after R2 is activated oFF 30
C AL Change display colour after alarm occurs oFF 30
Enable additional threshold while signalisation via 30
C Pr oFF
colour
The direction of result changes activating change of 30
dir morE
display colour
SEtP Threshold of display colour control 500 31
HySt Hysteresis of display colour control 0 31
Enable the use of local keyboard for 31
CrES oFF
acknowledgement of display colour signalisation.
Configuration of peaks detection function (“HOLd” menu)
modE Kind of detected changes norm 31
PEA Minimum detected change 0.0 31
timE Maximum time of peak displaying 0.0 31
HdiS The type of displayed value HOLd 31
H r1 Source of relay R1, and LED R1 control rEAL 31
H r2 Source of relay R2, and LED R2 control rEAL 31
Settings of access to the configuration parameters (“SECu” menu)
Permission to changes of relay R1 threshold 32
A r1 on
without of the user password knowledge
Permission to changes of relay R2 threshold 32
A r2 on
without of the user password knowledge
RS 485 interface configuration (menu “rS”)
Addr Device address 0 32
bAud Baud rate 9.6 32
mbAc Permission to changes of configuration registers on 32
mbtO Maximum delay between received messages 0 32
rESP Additional delay of answer transmission Std 32
Configuration of numerical parameters edition
Edit Numerical parameters edit mode dig 33

52
User manual - METER SRP-73

53
User manual - METER SRP-73

54
User manual - METER SRP-73

55
SIMEX Sp. z o.o.
ul. Wielopole 11
80-556 Gdańsk
Poland

tel.: (+48 58) 762-07-77


fax: (+48 58) 762-07-70

http://www.simex.pl
e-mail: [email protected]

You might also like