SH 09 BPH

This document is a manual for room air conditioner models SH09BPH, SH12BPH, SH09BPHX, and SH12BPHX. It includes sections on product specifications, operating instructions, disassembly/reassembly, refrigerating cycle diagrams, setup options, troubleshooting, exploded views/parts lists, and wiring diagrams. The specifications section provides technical details on the models such as power requirements, cooling/heating capacities, dimensions, weights, compressor/fan motor parts, and refrigerant amounts. It also includes cooling/heating pressure graphs.

Uploaded by

jacs50
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
172 views52 pages

SH 09 BPH

This document is a manual for room air conditioner models SH09BPH, SH12BPH, SH09BPHX, and SH12BPHX. It includes sections on product specifications, operating instructions, disassembly/reassembly, refrigerating cycle diagrams, setup options, troubleshooting, exploded views/parts lists, and wiring diagrams. The specifications section provides technical details on the models such as power requirements, cooling/heating capacities, dimensions, weights, compressor/fan motor parts, and refrigerant amounts. It also includes cooling/heating pressure graphs.

Uploaded by

jacs50
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 52

ROOM AIR CONDITIONER

INDOOR UNIT OUTDOOR UNIT


SH09BPH SH09BPHX
SH12BPH SH12BPHX

Manual
SERVICE
AIR CONDITIONER CONTENTS

1. Product Specifications

2. Operating Instructions

3. Disassembly and Reassembly

4. Refrigerating Cycle Diagram

5. Set Up the Model Option

6. Troubleshooting

7. Exploded Views and Parts List

8. PCB Diagram

9. Wiring Diagram

Downloaded from www.Manualslib.com manuals search engine


1. Product Specifications

1-1 Table

Model SH09BPH SH12BPH


Item SH09BPHX SH12BPHX

Power Source ø-V-Hz 1-220/240-50 1-220/240-50


W 2,800(1,500~3,400) 3,500(1,500~4,000)
Capacity
BTU/h 9,500(5,100~11,600) 11,900(5,100~13,600)
Energy Efficiency Ratio BTU/wh 11.8(10.0~13.8) 10.9(10.2~13.8)
Cooling Air Flow m3/min 5.5 6.5
Moisture Removal \/h 1.5 1.6
Noise Level Indoor 34 39
Perfor- dBA
Noise Level Outdoor 53 53
mance
W 3,200(1,500~4,500) 4,000(1,500~5,000)
Capacity
BTU/h 10,900(5,100~15,300) 13,600(5,100~17,000)
Energy Efficiency Ratio BTU/wh 13.6(10.2~14.6) 11.6(10.0~14.6)
Heating
Air Flow m3/min 7.5 8.3
Noise Level Indoor 39 42
dBA
Noise Level Outdoor 53 53
Available Voltage Range V 187~264 187~264
Running Amperes A 3.6(2.0~4.9) 4.8(2.0~5.9)
Cooling Power Input W 800(370~1,150) 1,090(370~1,330)
Power Factor % 96.6(84.5~97.6) 98.0(82.3~98.7)
Running Amperes A 4.0(1.8~6.5) 5.5(1.8~7.2)
Electrical
Heating Power Input W 880(350~1,500) 1,170(350~1,700)
Rating
Power Factor % 95.6(81.8~98.6) 97.8(81.8~98.4)
Starting Current A 10↓ 10↓
Fuse Capacity AxV 3.15 x 250 / 20 x 250 3.15 x 250 / 20 x 250
Power Cord AxV 15 x 250 15 x 250
Cable-Connector mm x G
3
1.5 x 4 1.5 x 4
Type - Single Rotary Single Rotary
Com-
Model Name - G4C090LU1ER G4C090LU1ER
pressor
Safety Devices - 204CT 204CT
Model Name - YDK-204F8C-1 YDK-204F8C-1
Indoor
Fan Running Capacitor µF x VAC 1.2µF / 450V 1.2µF / 450V
Motor Model Name - AMASS-020WTVB SIC-52FV-D828-1
Outdoor
Running Capacitor µF x VAC 1.7µF / 450V -
Refrigerant Tube EEV UKV-18D11 UKV-18D11
Refrigerant to Charge (R410A) g 1000 1000
Indoor unit : W x H x D mm 890 x 285 x 180 890 x 285 x 180
Dimension
Outdoor unit : W x H x D mm 720 x 548 x 265 720 x 548 x 265
Indoor unit kg 9 9
Weigth
Outdoor unit kg 33.8 33.8

Remark : Text condition Indoor room Outdoor room


Cooling test DB27˚C / WB19˚C DB35˚C / WB24˚C
Heating test DB20˚C / WB15˚C DB 7˚C / WB 6˚C

Samsung Electronics 1

Downloaded from www.Manualslib.com manuals search engine


1-2 Pressure Graph

■ SH09BPH

10.5

10.0

9.5
Pressure (kgf/cm2g)

9.0

8.5

8.0

7.5

7.0

6.5
20 25 30 35 40 45

Outdoor Temp. (ßC)

■ SH12BPH

10.5

10.0

9.5
Pressure (kgf/cm2g)

9.0

8.5

8.0

7.5

7.0

6.5
20 25 30 35 40 45

Outdoor Temp. (ßC)

2 Samsung Electronics

Downloaded from www.Manualslib.com manuals search engine


2. Operating Instructions

2-1 The Feature of Key in remote control

No NAMED OF KEY FUNCTION OF KEY

1 On/Off button.
(On/Off)
Press the button to stop or run the air conditioner.

Temperature adjustment button(UP).


(UP)
To increase the temperature by the pressing the temperature button.

Temperature adjustment button(DOWN).


(DOWN)
To decrease the temperature by the pressing the temperature button.

Mode selection button.


Each time you press this button : Auto Mode : Fan Only
Mode is changed in the following order
3
: Cool Mode : Heat Mode

: Dry Mode

Fan speed adjustment button.


Each time you press this button, FAN SPEED is changed in the following order.

4 Low Medium High

Automatic(rotated : )

Swing button.
5
It adjusts the airflow to upward and downward.

Turbo button.
6 The air conditioner cools or heats the room as quickly as possible.
After 30 minutes, the air conditioner is reset automatically to the previous mode.

Sleep button.
7 The sleep timer can be used when you are cooling or heating your room to switch the
air conditioner off automatically after a period of 6 hours.

Anion button.
8
Press the button to generate ion from the air conditioner.

Samsung Electronics 3

Downloaded from www.Manualslib.com manuals search engine


Operating Instructions

No NAMED OF KEY FUNCTION OF KEY

On Timer button.
The On Timer enables you to switch on the air conditioner automatically after
9 a given period of time that is from 30 minutes to 24 hours.
To set the operating time, press the button one or more times until the required
time display.

Off Timer button.


The Off Timer enables you to switch off the air conditioner automatically after
10 a given period of time that is from 30 minutes to 24 hours.
To set the operating time, press the button one or more times until the required
time display.

Timer Set/Cancel button.


11 After setting On Timer or Off Timer, press the button to set it completely.
And press the button again to cancel On Timer or Off Timer set.

Digital On/Off button.


12
If you want to turn off the display during operation press the button.

4 Samsung Electronics

Downloaded from www.Manualslib.com manuals search engine


Operating Instructions

2-1-1 Name & Function of Key in remote control

1. AUTO MODE : In this mode, operation mode(COOL, 4. DRY MODE : Has 3 states, each determined by room
HEAT) is selected automatically by the room temperature temperature.
of initial operation. The unit operates in DRY mode.
*Compressor ON/OFF Time is controlled compulsorily
Room Temp Operation Type
(can not set up the fan speed, always breeze).
Tr≥ 21°C+∆T Cool Operation (Set Temp:24˚C+∆T)
*Protective function : Low temperature release.
21°C +∆T>Tr Heat Operation (Set Temp:22˚C+∆T) (Prevention against freeze)

∆T= -1°C, -2°C, 0°C, +1°C, +2°C 5. TURBO MODE : This mode is available in AUTO, COOL,
∆T is controlled by setting temperature up/down key of HEAT, DRY, FAN MODE.
remote control When this button is pressed at first, the air conditioner is
operated "powerful" state for 30 minutes regardless of the
2. COOL MODE : The unit operates according to the set temperature, room temperature.
difference between the setting and room temperature. When this button is pressed again, or when the operating
(18°C~30°C) time is 30 minutes, turbo operation mode is canceled and
returned to the previous mode.
3. HEAT MODE : The unit operates according to the *But, if you press the TURBO button in DRY or FAN
difference between the setting and room tempera- mode that is changed with AUTO mode automatically.
ture.(16°C~30°C)
*Prevention against cold wind : In order to prevent the 6. SLEEP MODE : Sleep mode is available only in COOL or
cool air from flowing out at the heat mode, the indoor fan HEAT mode.
does not operate or operates very slowly in the The operation will stop after 6 hours.
following cases. At this time, the indoor heat exchanger *In COOL mode : The setting temperature is automatical-
will be preheating. ly raised by 1°C each 1hour When the temperature has
- For 3~5 minutes after the initial operation been raised by total of 2°C, that temperature is
- For deicing operation maintained.
- The operation of an indoor fan in accordance with *In HEAT mode : The setting temperature is automatically
the temperature of an indoor heat exchanger dropped by 1°C each 1hour.
When the temperature has been dropped by total of
The temperature of
Indoor fan speed 2°C, that temperature is maintained.
indoor heat exchanger

below 28˚C off


7. FAN SPEED : Manual (3 step), Auto (4 step)
28˚C~below 34˚C LL Speed Fan speed automatically varies depending on both the
34˚C~below 40˚C L Speed difference between setting and the room temperature.
above 40˚C Setting Speed
8. COMPULSORY OPERATION :
*High temperature release function : It is a function to For operating the air conditioner without the remote
detect an outdoor overload by the sensor of an indoor control.
heat exchanger and to turn the outdoor fan or the *The air conditioner starts up in the most suitable mode
compressor ON/OFF for safety. for the room temperature:
*Deice : Deicing operation is controlled by indoor unit's
Room Temperature Operating Mode Temperature Setting
heat exchanger temperature and accumulating time of
Less than 21˚C Heat 22˚C approx.
compressor's operation.
21˚C or above Cool 24˚C approx.
Deice ends by sensing of the processing time by deice
condition.

Samsung Electronics 5

Downloaded from www.Manualslib.com manuals search engine


Operating Instructions

9. SWING : BLADE-H is rotated vertically by the stepping 12. SELF DIAGNOSIS


motor.
DISPLAY 7-SEGMENT
*Swing Set : Press the button under the remote Error Mode Remark
Operation Off Operation On
control is displayed on LCD the and the blades
move up and down. If the one more time press the Indoor unit room temperature sensor
OFF E1
error (open or short)
button, blades location is stop.
Indoor unit heat exchanger
OFF E5
10. SETTING THE ON/OFF TIMER. : temperature sensor error(open or short)
*ON TIMER : The On Timer enables you to switch on the
Indoor FAN MOTOR error :
air conditioner automatically after a given period of time. Keep the RPM value 100 below for OFF E3_01
You can set the period of time from 30 minutes to 24 15 seconds
hours.
*OFF TIMER : The Off Timer enables you to switch off EEPROM error OFF 06
the air conditioner automatically after a given period of
time. You can set the period of time from 30 minutes to Error in option
24 hours. In case of No option set-up OFF 09
In case of option data error

11. GENERATING ANION :


Communication error EA_01 EA_01
The air conditioner can generate anion with an ionizer in
the indoor unit.

13. BUZZER SOUND : Whenever the On/Off button is


pressed or whenever change occurs to the condition
which is set up or select, the compulsory operation mode,
buzzer is sounded "beep".

6 Samsung Electronics

Downloaded from www.Manualslib.com manuals search engine


2-2 Replace PCB Model option

2-2-1 Replace PCB model option

Remove power cord

Replace the PCB module

Check the connection and plug in

No
Does all display lamp blink? Replace another PCB

Yes

Refer to set up the Model option(15~17page)

Samsung Electronics 7

Downloaded from www.Manualslib.com manuals search engine


3. Disassembly and Reassembly
Stop operation of the air conditioner and remove the power cord before repairing the unit.

3-1 Indoor Unit

No Parts Procedure Remark

1 Front Panel 1) Stop the air conditioner operation and block


the main power.
2) Detach tape of Front Panel upper.

3) Slide the lower Front Grille down, then


disassemble it by pulling it forwards.
4) Open the upper Front Grille by pulling right
and left sides of the Grille.
5) Take the left and right Filter out.
6) Loosen one of the right screw and detach
the Terminal Cover.
7) Detach the thermistor from the Front Grille.

8) Loosen 5 fixing screws of Front Grille.

9) Pull the lower left and right of discharge


softly for the outside cover to be pulled out.

8 Samsung Electronics

Downloaded from www.Manualslib.com manuals search engine


Disassembly and Reassembly

No Parts Procedure Remark

10) At first, press the left and center hook of


the back side of the Panel Grille with the
thumb to remove the hook. And press the
right of the upper side of the Panel Grille
with the fingers. And then disassemble the
Panel Grille.

2 Electrical Parts 1) Take all the connector of PCB upper side


(Main PCB) out.(Including Power Cord)
2) Detach the outdoor unit connection wire
from the Terminal Block.
3) If pulling the main PCB up, it will be taken
out.

3 Tray Drain 1) Pull Tray Drain out from the Back Body.

Samsung Electronics 9

Downloaded from www.Manualslib.com manuals search engine


Disassembly and Reassembly

No Parts Procedure Remark

4 Heat Exchanger 1) Loosen 2 fixing earth screws of right side.


2) Detach the Connection Pipe.
3) Detach the Holder Pipe at the rear side.
4) Loosen 3 fixing screws of right and left
side.

5) Detach the Heat Exchanger from the


indoor unit.

5 Fan Motor 1) Loosen 2 fixing screws and separate the


& Motor Holder.
Cross Fan 2) Loosen 1 fixing screw of Fan Motor.
(with a M3 wrench)
3) Detach the Fan Motor from the Fan.

4) Detach the Fan from the left Holder


Bearing.

10 Samsung Electronics

Downloaded from www.Manualslib.com manuals search engine


3-2 Outdoor Unit

No Parts Procedure Remark

1 Common Work 1) Loosen each 3 fixing screws on both right


and left Cabinet-Side edge and a fixing
screw on the Cabinet-Front lower to detach
the Cabinet-Front.

2) Loosen 1 fixing screws of the


Cover-Valve.

3) Loosen 6 fixing screws of the Cabinet-Side


RH.

4) Loosen 2 fixing screws of the Cabinet-Side


LF.

Samsung Electronics 11

Downloaded from www.Manualslib.com manuals search engine


Disassembly and Reassembly

No Parts Procedure Remark

2 Fan & Motor 1) Detach the Nut Flange.(Turn counterclock-


wise because the screw is right-handed)
2) Detach the Fan.
3) Loosen 4 fixing screws to detach
the Motor.

3 Heat Exchanger 1) Loosen 2 fixing screws on both sides.


2) Disassemble the pipe in both inlet and
outlet with welding torch.
3) Detach the Heat Exchanger.

4 Compressor 1) Loosen the Terminal Cover nut to open the


Terminal Cover.
2) Disassemble the cloth sound felt.
3) Disassemble the pipe in both inlet and
outlet of the Compressor with welding
torch.
4) Disassemble the pipe in both inlet and
outlet of the Condenser with welding torch.
5) Loosen the 3 bolts at the bottom.
6) Detach the Compressor.

12 Samsung Electronics

Downloaded from www.Manualslib.com manuals search engine


4. Refrigerating Cycle Diagram

Indoor Unit Outdoor Unit

Capillary tube

T1 2-Way valve

Liquid side EEV

Propeller fan
Cross fan

Heat Heat
Exchanger Exchanger
(Evaporator) (Evaporator)

T2
Gas side

3-Way valve 4-Way valve


Cooling

Heating
Compressor
Gas leak check point

Samsung Electronics 13

Downloaded from www.Manualslib.com manuals search engine


5. Set Up the Model Option

5-1 Setting Option Setup Method

ex) Option No. :

Step 1 : Enter the Option Setup mode.

1st Take out the batteries of remote control.

2nd Press the temperature button simultaneously and


insert the battery again.

3rd Make sure the remocon display shown as .

Step 2 : Enter the Option Setup mode and select your option according to the following procedure.

1
The default value is .
Otherwise, push the button to .
Every time you push the button, the display panel reads or
repeatedly.

2
Push the button to set the display panel to .
Every time you push the button, the display panel reads
3 2
... repeatedly.

1 3
Push the button to set the display panel to .
4 Every time you push the button, the display panel reads
... repeatedly.
5 6
4
Push the button to set the display panel to .
Every time you push the button, the display panel reads
... repeatedly.

5
Push the button to set the display panel to .
Every time you push the button, the display panel reads
... repeatedly.

6
✳ Setting is not required if you must Push the button to set the display panel to .
a value which has a default. Every time you push the button, the display panel reads
... repeatedly.

14 Samsung Electronics

Downloaded from www.Manualslib.com manuals search engine


Set Up the Model Option

7
Press button, then the default value is .

8
Push the button to set the display panel to .
Every time you push the button, the display panel reads
... repeatedly.
9 8
9
Push the button to set the display panel to .
7 Every time you push the button, the display panel reads
... repeatedly.
10

10
11 12 Push the button to set the display panel to .
Every time you push the button, the display panel reads
... repeatedly.

11
Push the button to set the display panel to .
Every time you push the button, the display panel reads
... repeatedly.

12
Push the button to set the display panel to .
✳ Setting is not required if you must
Every time you push the button, the display panel reads
a value which has a default. ... repeatedly.

Step 3 : Upon completion of the selection, check you made right selections.
Press the Mode Selection key, to set the display part to and check the display part.
The display part shows .

Press the Mode Selection key, to set the display part to and check the display part.
The display part shows .

Step 4 : Pressing the ON/OFF button ( )


When pressing the operation ON/OFF key with the direction of remote controller for unit, the sound ''Ding'' or ''Diriring'' is
heard and the OPERATION ICON( ) lamp of the display is flickering at the same time, then the input of option is com-
pleted. (If the diriring sound isn't heard, try again pressing the ON/OFF button.)

Step 5 : Unit operation test-run


First, Remove the battery from the remote controller.
Second, Re-insert the battery into the remote controller.
Third, Press ON/OFF key with the direction of remote controller for set.

• Error Mode
1st If all lamps of indoor unit are flickering, Plug out, plug in battery again and press ON/OFF key to retry.
2nd If the unit is not working properly or all lamps are continuously flickering after setting the option code, see if the correct option code is
set up for its model.

Samsung Electronics 15

Downloaded from www.Manualslib.com manuals search engine


Set up the Model Option

■ OPTION ITEMS

REMOCON
SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
MODEL

SH09BPH 0 0 9 0 A 0 1 0 0 2 2 E

SH12BPH 0 0 7 0 9 0 1 1 0 3 6 2

16 Samsung Electronics

Downloaded from www.Manualslib.com manuals search engine


6. Troubleshooting
Since the inverter air conditioner is equipped with Electrical control circuits at both Indoor & outdoor unit, the trouble shooting shall
be performed according to the error mode.
Inside the controller of the outdoor unit (inverter), the large capacity of electrolytic condenser so that it takes the time to discharge
after the power off since the electrical charge remains(the charging voltage DC 340V).
Take care of the electrical shock by contact on the charging part before the discharge after the power off. (It takes approximately
2 minutes to discharge).

6-1 Basic items for trouble shooting


1. Is the power source proper?
The power source shall be in the range of the rated voltage ±10%. If it is out of this range, it may cause the abnormal operation.
2. Is the connection made between the indoor and outdoor unit?
The connection between indoor and outdoor unit shall be performed with 4 wire. (connection cable of indoor and outdoor unit +
ground wire).
3. The phenomena as follows are not out of order.

No Phenomena Cause and reason

1 The operation is not done. • Is the power off or the power unplugged?
• Does it stop because it is the completion time?
• Unplug and plug again the power source for 2 minutes.

2 The wind comes out but the • Is the filter clogged with dust or dirty?
heating/cooling is not performed. • Is there any direct light on the outdoor unit or any obstacle against it?
• Is the selected temperature too high?
Lower the selected temperature lower than the current one (during cooling).
• Is the selected temperature too low?
Raise the desired temperature than the current one? (during heating)
• Is the "Fan only Mode" operation?

3 The remote controller does not • Is the battery run out?


operate. • Is the battery inserted in the wrong way(+, -)?
• Is the detection part of the indoor unit blocked?
• Does it interfered with the radio of neon sign?

4 The wind volume is not adjusted. • Is the operation selected among one of Auto / Dry / Turbo / Sleeping?
• The temperature setting is not required since the wind volume set automatically.
• Check again at the state of Cooling / Fan only / Heating.

5 The temperature is not set. • Is the operation selected among the Dry / Turbo / Sleeping / Fan only Mode.
Since the temperature is automatically set, the temperature setting is not required.
• Check again at the cooling / heating state.
• The standard temperature ±2˚C during the automatic operation.

6 The operation lamp continues to be • Push the Operation / Stop button.


flickering. • Unplug and plug the power source.

7 The immediate operation starts • It is the case that the auto restart function works.
without control of remote controller ✳Auto restart function is the convenient function where the operation state is
when plugged memorized in the Memory IC during the blackout and the operation restarts when
the power comes back.

Samsung Electronics 17

Downloaded from www.Manualslib.com manuals search engine


6-2 The first determination method of troubled part

6-2-1 Error mode display of indoor unit

TEMPERATURE / ERROR CODE

ERROR CODE Check point


Discription
DISPLAY INDOOR OUTDOOR
Indoor Unit
Indoor unit room temperature sensor error (open / short) Temp-Sensor
Indoor unit heat exchanger out temperature sensor error(open / short) Temp-Sensor
Indoor unit heat exchanger in temperature sensor error(open / short) Temp-Sensor
EEPROM error PCB
Option code setting error Option Code
Indoor fan motor malfunction Fan and cable
Communication error or miss-wiring error

PCB, Cable between


Communication error between the indoor unit and outdoor unit
Indoor and outdoor unit

Compressor protection error


Abnormal increase of operation current
Abnormal increase of OLP temperature
Abnormal increase of discharge temperature
Over current of IPM circuit Comp. Fan
Abnormal increase of heatsink temperature Fan
BLCD compressor starting error Comp. PCB,Comp wire
Outdoor unit sensor error (open / short)
deice temp-sensor Temp-Sensor
outdoor temp-sensor Temp-Sensor
discharge temp-sensor Temp-Sensor
OLP temp-sensor Temp-Sensor
Outdoor control PCB error
Communication error between 2 micom on the outdoor PCB PCB
current sensor error PCB
heatsink temp-sensor error PCB
Voltage sensor error PCB, Outlet voltage
✳Error display : / / and 2-digit-number are displayed alternately

18 Samsung Electronics

Downloaded from www.Manualslib.com manuals search engine


Troubleshooting

6-2-2 Error mode display of outdoor unit board

RED
GRN
YEL ULN2003

LAMP of Display Monitor Description


YELLOW GREEN RED : Lamp on : Lamp flickering X : Lamp off

X X X Power Off / VDD NG


X X Comp. Peak Current (O.C.)
X X Communication NG
X X Comp. Starting error
X Heatsink sensor error
X Normal Operation
X DC-Iink overvoltage error
X 4-Way valve error
X X Heatsink Temp. trip
X Outdoor Sensor error(Open/Short)
X Discharge sensor temp. trip
X Discharge sensor error(Open/Short)
OLP sensor error(Open/Short)
CT sensor error
X Unit Over Current protection
Deice sensor error(Open/Short)
OLP sensor temp. trip
X OPTION error (EEPROM)
X Compressor rotation error
X DC fan error (SH12BWHX only)
DC-Link voltage sensor error
PFC OC error
X NO GAS error
AC Line zero-crossing error

Samsung Electronics 19

Downloaded from www.Manualslib.com manuals search engine


6-3 Sequence of trouble shooting for inverter aircon

OPERATION START

• The indoor unit does not work even


though the power is plugged.
Check the indoor unit control board. (A)
• There is no sound "DING"
• The lamp is not on the display.

The indoor unit does not work when


Checking the Remocon.(B)
operated by the remocon.

Check the control board and display board


of indoor unit.(C)

The 2 digit part of indoor LED


display shows Error Code and the Check the error code on the LED
unit stops several minutes after the display(A), (D)-(O)
indoor uint starts.

In case of Error Code : Er/E1(D), Er/E5(D), Er/05(D), Er/06(A), E3/01(E) Check the indoor unit

See section 5. Setup the


In case of Error Code : Er/09
model option

In case of Error Code : E3/01 → (F) Check the communication line

In case of Error Code : E3/E6(H), Er/17(K),


In case of Error Code : Er/31(H), Er/32(G), Er/33(G), Er/36(K), Check the outdoor unit
In case of Error Code : Er/37(I), Er/38(K)

In case of Error Code : Er/11(J), Er/12(M), Er/13(M), Er/14(L), Check the outdoor unit and
In case of Error Code : Er/15(N), Er/18(O) outdoor unit installation

20 Samsung Electronics

Downloaded from www.Manualslib.com manuals search engine


Troubleshooting

6-3-1 (A) Check of indoor unit control board

√ Unplug the power cord and plug it after 5 seconds.


√ Press the on/off switch located indoor unit inside to operate the air conditioner.
◆ • If the air conditioner operates, check the remocon and indoor unit display board.
◆ • If the air conditioner does not operates, check according to the sequence of the followings:
√ Check sequence of indoor unit control board
◆ Step 1 : Check whether two wires of power cord (Sky-blue, brown) are connected correctly to the terminal block and
Relay on the control board.
◆ Step 1 : • Sky -blue : connected to "N1" of Terminal block
◆ Step 1 : • Brown : connected to RY71 Tab terminal (control board outer side)
◆ Step 2 : Check whether the wire connected to the terminal block is connected to th control board.

(Control board) (Terminal block)


SKY-BLU (N1)
CN71
BRN 1
RY71
BLK 2
CN71

◆ Step 3 : Check whether the fuse (F701)(F702) on the control board is normal. (3.15[A]/250[V]:F701) (1[A]/250[V]:F702)
◆ Step 1 : • If the fuse is broken, replace it with new one.
◆ Step 4 : Check the output voltage of SMPS on the control board.
◆ Step 1 : • Input power AC178 ~ AC 264V— • CN22 1-3pin : DC12V
◆ Step 1 : - Input power AC178 ~ AC 264V— • CN22 2-3pin : DC5V
◆ Step 1 : - ✳CN22 : As socket not mounted measure at the solder points
◆ Step 5 : Check whether the control board gets wet with dew
◆ Step 1 : • Dry the control board.
◆ Step 6 : Check whether tiny metal objects make a short fircuit on the PCB, especially between pins of the surface mount IC.
◆ Step 1 : • remove the objects. Do not use splay solvent or some components may get damage by solvent.

6-3-2 (B)(C) Display board and remocon check of indoor unit

√ Check whether the connection wire of Display board is correctly connected to CN53 connector.
√ Check the voltage of remocon battery. - the voltage of one battery shall be higher than about 1.4V, and then the remocon
operates normally.
√ Check whether the neon sign is on and the 3 wave long fluorescent lamp is on around the indoor unit. - After putting all lamps of
the indoor out and then operate it by remocon. If it operates with the remocon, it is the abnormality due to the interference from
the light of lamps. (Aircon unit is normal).

6-3-3 (D) Check the indoor temperature sensor and indoor heat exchanger temperature sensor.

Take out the thermistor connected to the connector (CN41,CN42) of control board of indoor unit and measure the resistance
between two wires and if it is same as follows: it is normal but if not, replace it.

Ambient temperature
15°C 20°C 25°C 30°C 35°C 40°C
(°C)
Resistance of
14.68 12.09 10 8.31 6.94 5.83
thermistor [KΩ]

Samsung Electronics 21

Downloaded from www.Manualslib.com manuals search engine


Troubleshooting

6-3-4 (E) Check of indoor unit fan motor

■ 1. √ Check whether the wires are connected surely between control board(CN72) and running capacitor(Tab).
■ 1. √ Check whether the wire of fan motor is connected to the control board (CN73,CN74) of indoor unit.
■ 1. √ Check whether the error mode displays after the strong rotation for approximately 15 seconds since air conditioner turned on.
■ 1. √ • In case the error code displays after the fan motor is rotating for 15 seconds. → Defect of HALL IC of fan motor and/or control
board.
■ 1. √ • In case that error code displays without fan motor rotating after 15 seconds. → Operate with making short circuit of AC side
pins of SSR(SS71) of indoor unit control board. And then if the fan motor does not operate, it is the fan motor defect.
If it rotates, it is the defect of control board(SS71,IC05,IC04).

6-3-5 (F) Check of communication line between the indoor unit and outdoor unit
■ Communication error mode
■ 1. Check of connection
■ 1. √ Check whether the cable wire connecting the indoor unit with outdoor unit is correctly connected to the (N1), 1, 2 terminal. (If
the wire is connected reversely, the communication error occurs)
■ 1. √ If the cable connecting the indoor unit and outdoor unit is longer than 20m, error mode may occur (shorten the cable length).
■ Check of indoor unit
■ √ Check whether the connection wire of the terminal block and control board of indoor unit is correct.
(Control board) (Terminal block)
SKY-BLU (N1)
CN71
BRN 1
RY71
BLK 2
CN71

■ Check of outdoor unit


■ √ Check whether the connection wire of the terminal block and control board of outdoor unit is correct.
(Control board) (Terminal block)
SKY-BLU (N1)
TB-N
BRN 1
TB-L
BLK 2
CN04

■ 2. Check of power supply to the outdoor unit


■ 2. After operation of aircon, select the turbo mode and approximately 3minutes later, check whether the red color lamp of control
board (to be seen if the top cover of outdoor unit) is on.
■ 2. → If the red lamp (LED 3) is not on, check the power part of control board of outdoor unit.
■ 2. • Check the connection of reactor.
■ 2. • → If the red lamp (LED 3) is on and green lamp is flickering, it is normal.

6-3-6 (G) Check of discharge temperature sensor and comp top OLP temperature sensor.
√ Connector of outdoor unit control board
(PIN#3,4 of CN51 - discharge temperature sensor), (PIN#1,2 of CN52-OLP Temperature sensor)
Measure the resistance between two wires and if it is same as follows, it is normal but if not, replace.
Ambient temperature
0°C 10°C 20°C 30°C 40°C 50°C
(°C)
Resistance of
553 362 242 166 165 82
thermistor [KΩ]

22 Samsung Electronics

Downloaded from www.Manualslib.com manuals search engine


Troubleshooting

6-3-7 (H) Check the defrost temperature sensor and outdoor temperature sensor.
√ Connector of outdoor unit control board
(PIN#1,2 of CN51 - outdoor temperature sensor),(PIN#3,4 of CN52-deice Temperature sensor)
Measure the resistance between two wires and if it is same as follows, it is normal but if not, replace it.
Ambient temperature
15°C 20°C 25°C 30°C 35°C 40°C
(°C)
Resistance of
14.68 12.09 10 8.31 6.94 5.83
thermistor [KΩ]

6-3-8 (I) Check the heatsink temperature sensor of IPM


√ This sensor is inside of the IPM module and PIN#24,25 of IPM module are the sensor terminal.
Usually PIN solder crack or short circuit with small metal object cause sensor error.
Check the object to make short circuit and solder condition of these pins.
Ambient temperature
15°C 20°C 25°C 30°C 35°C 40°C
(°C)
Resistance of
77.4 61.4 49.1 39.5 31.9 26
thermistor [KΩ]

6-3-9 (J) Check of operation current abnormal increase mode


√ The operation abnormal current mode is the protection control for the safe operation by detecting the operation current of
inverter aircon by the current sensor on the control board.
√ If the operation current abnormal increase occurs,
√ • The ventilation is not good because the outdoor unit is installed wrong (the ambient temperature is higher than 50 °C)
√ • → Reinstall the outdoor unit so that the good ventilation can be made.
å If the Refrigerant is overcharged.
√• → Check the amount of Refrigerant.
√ • If the comp is locked.
√• → Replace the comp.
√ • If the comp is operating without the revolution of fan motor.
√ • → Check the fan motor connector, replace the fan motor.
√ • If the protection cover is operating with bending to the outdoor.
√ • → Take out the protection cover.
å If two outdoor units are operating face to face. (the bad ventilation is made)
√• → Reinstall the outdoor unit for the good ventilation.
å The air circulation is bad due to the attachment of falling leaves
√• → Take away the leaves for the good ventilation.
√ Check and clean the dirt of current sensor block of outdoor control board.
√ especially • IC83 pin solder • C437 47uF • R459 33K • R461 4.7K

6-3-10 (K) Check of Current sensor, Voltage sensor and Communication between 2 micom on the
board.
√ These errors are from component trouble on the outdoor control board.
√ → Replace the outdoor control board

Samsung Electronics 23

Downloaded from www.Manualslib.com manuals search engine


Troubleshooting

6-3-11 (L) Check of instantaneous over-current protection of IPM circuit.


√ Inverter instantaneous over-current protection mode is the mode to be actuated in order to prevent the damage of elements from
the peak current of IPM circuit elements.
√ In case that the inverter circuit instantaneous over-current protection mode actuates.

■ condition of installation
■ • The ventilation is not good because the outdoor unit is installed wrong (the ambient temperature is higher than 50 (°C) )
■ • → Reinstall the outdoor unit so that the good ventilation can be made.
■ • In case that the operation is made with the cover bent of the outdoor unit.
■ • → Take out the cover.
■ • If two outdoor units are operating face to face, (the bad ventilation is made)
■ • → Reinstall the outdoor unit for the good ventilation.
■ • The air circulation is bad due to the attachment of falling leaves.
■ • → Take away the leaves for the good ventilation.
■ • If the Refrigerant is overcharged.
■ • → Check the amount of Refrigerant.

■ Unit defect
■ • If the comp is locked.
■ • → Replace the comp.
■ • If the comp is operating without the revolution of fan motor.
■ • → Check the fan motor connector and replace the fan motor.
■ • In case the parts of the control board is damaged.
■ • → Replace the outdoor control board.

6-3-12 (M) Check of the comp discharge gas temperature and OLP temperature abnormal rise.
√ If the comp discharge gas temperature and OLP temperature rises higher than a certain level, it protects the circuit.
√ If the comp discharge gas temperature and OLP temperature rises abnormally,

■ Condition of installation
■ • The ventilation is not good because the outdoor unit is installed wrong (the ambient temperature is higher than 50 (°C) )
■ • → Reinstall the outdoor unit so that the good ventilation can be made.
■ • In case that the operation is made with the cover bent of the outdoor unit.
■ • → Take out the cover.
■ • If two outdoor units are operating face to face, (the bad ventilation is made)
■ • → Reinstall the outdoor unit for the good ventilation.
■ • The air circulation is bad due to the attachment of falling leaves
■ • → Take away the leaves for the good ventilation.
■ • If the refrigerant is insufficient.
■ • → Fill up the amount of refrigerant.

■ Unit defect
■ • If the comp is locked.
■ • → Replace the comp.
■ • If the comp is operating without the revolution of fan motor
■ • → Take out the protection cover.
■ • → Check the fan motor connector and replace the fan motor.

24 Samsung Electronics

Downloaded from www.Manualslib.com manuals search engine


Troubleshooting

6-3-13 (N) Check of the heatsink temperature abnormal rise


√ If the air flow around the heatsink on the control box is not good, heatsink temperature will go up and the control box
will have damage. So controller check the heatsink temperature and protect at the cirtain limit.
Possible troubles are fan motor trouble, fan motor drive circuit trouble and air flow blocking.

■ Condition of installation
■ • The ventilation is not good because the outdoor unit is installed wrong (the ambient temperature is higher than 50(˚C)).
■ • → Reinstall the outdoor unit so that the ventilation can be made.
■ • In case that the operation is made with the cover bent of the outdoor unit.
■ • → Take out the cover.
■ • If two outdoor unit are operatong face to face,(the bad ventilation is made)
■ • → Reinstall the outdoorunit for the good ventilation.
■ • The air circulation is bad due to the attachement of falling leaves.
■ • → Take away the leaves for the good ventilation.
■ • If the refrigerant is insufficient.
■ • → Fill up the amount of refrigerant.

■ Unit defect
■ • If the fan is locked with some object.
■ • → Remove the object.
■ • If the comp is operationg without the revolution of fan motor.
■ • → Take out the protection cover
■ • → Check the fan motor connector(CN54), running capacitor, relay(RY503) and replace the fan motor.

6-3-14 (O) Check BLDC compressor starting error


√ If the compressor have some trouble inside like locking or gas pressure of suction and discharge pipe is not balanced,
Inverter system will give up compressor rotation control to protect itself from overcurrent.
√ In case of compressor rotation starting trouble without overcurrent condition, controller detect the compressor
rotation error and stop.
√ • Compressor wire connection is not good.
√ • → Check Compressor TAB terminal connection of the wire and connector to control box.
√ • Gas pressure balance is not good at stop condition.
√ • → Check service valve open.
√ • → Check EEV motor attachement and connector.
√ • Compressor is locked or have some mechanical damage.
√ • → Replace the compressor.

Samsung Electronics 25

Downloaded from www.Manualslib.com manuals search engine


Troubleshooting

6-3-15 (P) Check no gas error


Charge standard amount of refrigerant.

6-3-16 (Q) Check of 4-Way valve


Check whether the wires of 4-Way valve and control board of outdoor units correct.
If it is normal, replace 4-Way valve.

6-3-17 (R) Check of outdoor unit fan motor (SH12BPHX only)


Check whether the wire of fan motor is connected to the control board (CN01) of outdoor unit.
Check the voltage on the control board of outdoor unit and if it is same as follows, replace fan motor.
Input power AC178V~AC264V.
→ CN01 1-3pin : DC250V±10% ~ DC370V±10%
→ CN01 4-3pin : DC15V

26 Samsung Electronics

Downloaded from www.Manualslib.com manuals search engine


6-4 Fault Diagnosis of Major Parts

Part Diagnosis

• Indoor "Temp.Sensor" Measure resistance with a tester.


• Indoor "Heat ex. Sensor"
• Outdoor "Temp.Sensor" Normal
Ambient temperature 15°C 20°C 25°C 30°C 35°C 40°C
• Outdoor "Deice Temp. Sensor"
Resistance of
14.68 12.09 10 8.31 6.94 5.83
thermistor[KΩ]

Abnormal ∞, OΩ … open or short

• Outdoor "Discharge Normal Ambient temperature 0°C 10°C 20°C 30°C 40°C 50°C
Temp.Sensor"
• Outdoor "OLP Temp.Sensor" Resistance of
553 362 242 166 165 82
thermistor[KΩ]

Abnormal ∞, OΩ … open or short

Indoor Fan Motor Measure the voltage between terminals (CN72) with a tester

Normal At ambient temperature (10°C ~ 30°C)

between Voltage[V]
Red, Blue 410±10% Main
Red, Yellow 325±10% Sub

Abnormal

Measure the voltage between ground and signal wire of the fan motor

Normal between Voltage


Gray, Orange 0.5V~4.5V
Yellow, Orange 5V

Abnormal Abnormal if voltage does not change from 0V to 5V.

Outdoor Fan Motor Normal At ambient temperature (10°C ~ 30°C)

between Resistance[Ω]
Black, Red 275±10% Main
Black, Yellow 350±10% Sub

Abnormal ∞, OΩ … open or short

Stepping Motor Measure resistance between red wire and each terminal.
(UP/DOWN swing motor)
Normal Approx. 290Ω at ambient temperature (20°C ~30°C)

Abnormal ∞, OΩ … open or short

Stepping Motor Measure resistance between red wire and each terminal.
(FRONT GRILLE motor)
Normal Approx. 110Ω at ambient temperature (20°C ~30°C)

Abnormal ∞, OΩ … open or short

Samsung Electronics 27

Downloaded from www.Manualslib.com manuals search engine


DB98_17175A_1 2/6/04 4:14 PM Page 28

7. Exploded Views and Parts List

7-1 Indoor Unit


13

7-1
15

7-5
7-6
16

16-4
8 7-3

7-2 16-1
16-3

7-4

11 16-2
16-5
10
3

1-2 12
1

14

1-1-2
1-1-3
1-1
1-1-4 1-1-1
1-3 1-1-5

1-1-6
1-1-7 2

1-4

4 5
You can search for the updated part code
number through the ITSELF.
URL : http://itself.sec.samsung.co.kr

28 Samsung Electronics

Downloaded from www.Manualslib.com manuals search engine


Exploded Views and Parts List

■ Parts List
Q'TY
No. Code No. Description Specification Remark
SH09BPH SH12BPH

1 DB92-00488C ASS'Y PANEL FRONT-TOTAL ASS'Y 1 1


1-1 DB92-00392F ASS'Y PANEL FRONT-SUB P ASS'Y 1 1
1-1-1 DB92-00346A ASS'Y PANEL FRONT ASS'Y 1 1
1-1-2 DB31-00166A MOTOR STEP - 1 1
1-1-3 DB39-00794A CONNECTOR WIRE-STEP MOTOR - 1 1
1-1-4 DB61-01114A HOLDER-MOTOR DC HIPS 1 1
1-1-5 DB61-01115A HINGE-GRILLE HIPS 1 1
1-1-6 DB61-01116A GUIDE-LINK HIPS 1 1
1-1-7 DB66-00364A LINK-MOTOR ABS 1 1
1-2 DB64-00494B GRILLE-UP ABS 1 1
1-3 DB63-00585C FILTER-PRE LF PP 1 1
1-4 DB63-00586C FILTER-PRE RH PP 1 1
2 DB92-00491B ASS'Y GRILLE-LOW SUB ASS'Y 1 1
3 DB96-04189A ASS'Y EVAP-TOTAL ASS'Y 1 1
4 DB95-00367B ASS'Y-FILTER BIO ASS'Y 1 1
5 DB63-00581A COVER TERMINAL HIPS 1 1
6 DB93-02531N ASS'Y REMOCON ASS'Y 1 1
7 DB94-00304H ASS'Y BACK BODY-SUB ASS'Y 1 1
7-1 DB61-01335A BACK-BODY HIPS 1 1
7-2 DB63-00580A COVER-IONIZER HIPS 1 1
7-3 DB91-00264A ASS'Y ELECTRIC-IONS ASS'Y 1 1
7-4 DB39-01451C ASS'Y CONNECTOR WIRE-ION ASS'Y 1 1
7-5 DB73-00128A RUBBER-BEARING - 1 1
7-6 DB94-40007A ASS'Y BEARING-MOTOR - 1 1
8 DB94-00020E ASS'Y-CROSS FAN ASS'Y 1 1
9 6009-001001 BOLT SPECIAL - 1 1
10 DB31-00152B MOTOR FAN - 1 1
11 DB61-01099A HOLDER-MOTOR PP 1 1
12 DB67-60030A SPRING-SENSOR STS301 2 2
13 DB70-00276A PLATE-HANGER SGCC-M 1 1
14 DB93-02583B ASS'Y CONTROL IN ASS'Y 1 1
15 DB90-00992A ASS'Y HOLDER-PIPE ASS'Y 1 1
16 DB94-00305H ASS'Y TRAY DRAIN ASS'Y 1 1
16-1 DB94-00062E ASS'Y DRAIN-HOSE ASS'Y 1 1
16-2 DB61-01103A BLADE-H HIPS 1 1
16-3 DB61-01104A BLADE-V PP 2 2
16-4 DB63-00587A TRAY DRAIN HIPS 1 1
16-5 DB95-20138A ASS'Y MOTOR-STEPPING ASS'Y 1 1

Samsung Electronics 29

Downloaded from www.Manualslib.com manuals search engine


DB98_19047A(1)_2 4/21/04 2:27 PM Page 32

7-2 Outdoor Unit

22

23
17
16
24

8
10
25

3
9

11
3-2 7
26
13
12 20
6

21

3-1

18

5 19

2 4
14

15

30 Samsung Electronics

Downloaded from www.Manualslib.com manuals search engine


DB98_19047A(1)_2 4/21/04 2:27 PM Page 33

Exploded Views and Parts List

 Parts List
Q'TY
No. Code No. Description Specification
SH09BPHX SH12BPHX

1 DB90-01581A ASS'Y-CABI FRONT ASS'Y 1 1


2 DB63-00847A GUARD FAN PP 1 1
3 DB90-01332A ASS'Y-CABI SIDE LF ASS'Y 1 1
3-1 DB64-01094A CABINET-SIDE LF COATING SC-90073T 1 1

3-2 DB64-00992A HANDLE-LF PP 1 1


4 DB90-01546A ASS'Y-CABI SIDE RH ASS'Y 1 1
5 DB63-00843A COVER-VALVE PP 1 1
6 DB90-01330F ASS'Y BASE-OUTDOOR ASS'Y 1 1

7 DB99-00401B ASS'Y VALVE-BRACKET ASS'Y 1 1

8 DB94-00584B ASS'Y PARTITION ASS'Y 1 1


9 DB61-01644A BRACKET MOTOR SGCC-M 1 1

10 DB97-02225A ASS'Y SUPPORT-PLATE B/M 1 1


11 DB31-00220A MOTOR FAN YDK-020S62213-03 1 -

DB31-00238A MOTOR FAN SIC-52FV-D828-1 - 1


12 DB67-00397A FAN-PROPELLER 1 1

13 DB60-30004A NUT-FLANGE 1 1
14 DB63-00763A GROMMET ISOLATOR NR 3 3

15 DB60-30028A NUT-WASHER 3 3
16 DB96-03602A ASS'Y COND ASS'Y 1 1

17 DB93-02740C ASS'Y CONTROL OUT SH12BPHX - 1


DB93-02740D ASS'Y CONTROL OUT SH09BPHX 1 -

18 DB63-01043A FELT COMP SIDE FELT 1 1


19 G4C090LU1ER COMPRESSOR G4C090LU1ER 1 1
20 DB99-00481B ASS'Y VALVE 4WAY ASS'Y 1 1

21 DB97-02490B ASS'Y VALVE EEV ASS'Y 1 1


22 DB71-00090E BAR-STEEL ASS'Y 1 1
23 DB32-00083C ASS'Y THERMISTOR OUT ASS'Y 1 1

24 DB32-00121A ASS'Y THERMISTOR OLP/SUC ASS'Y 1 1


25 DB33-00021A SOLENOID-REACTOR 12A, 21mH 1 1
26 3301-001738 CORE-FERRITE ASS'Y 0 1

Samsung Electronics 31

Downloaded from www.Manualslib.com manuals search engine


7-3 Ass'y Control In (Indoor Unit)

■ SH09BPH / SH12BPH : DB93-02583A

32 Samsung Electronics

Downloaded from www.Manualslib.com manuals search engine


Exploded Views and Parts List

■ Parts List
No. Code No. Description Specification Q'TY Remark

1 DB61-01631A CASE-CONTROL ABS 1

2 DB93-02584B ASS'Y MAIN PCB ASS'Y 1


3 DB93-01368G ASS'Y S/W & DISPLAY PCB ASS'Y 1
4 DB93-01369A ASS'Y-MODULE PCB ASS'Y 1
5 DB65-00149A ASS'Y TERMINAL BLOCK ASS'Y 1
6 DB70-00289A PLATE TERMINAL LOW SGCC-M,T1.2 1
7 DB61-00171A HOLDER WIRE CLAMP HIPS 1
8 6001-000929 SCREW-MACHINE PH M3xL22 1 SNA
9 6001-000725 SCREW-MACHINE TH M4xL16 2 SNA
10 DB93-01380B C/W MODULE ASS'Y 1
11 DB39-00793A C/W STEP MOTOR UP/DOWN ASS'Y 1 SNA
12 DB62-01368X SEAL 61x40x3,30FOAM-PE,GRAY 1 SNA
13 - SCREW-MACHINE PH M4x10 1
14 DB39-00780B C/W STEPPING MOTOR ASS'Y(AUTO GRILLE) 1
15 DB39-00820A C/W ION-PCB ASS'Y 1

16 DB61-01110A HOLDER-DISPLAY ABS 1


17 DB64-00763A HALF MIRROR 95,T1.5 1
18 2301-001339 FAN CAPACITOR 1.2 µF/450V 1
19 DB72-00126N SEAL T3, FOAM-PE,GRAY 1
20 DB32-00084B THERMISTOR OUT,ø6,220 1
21 DB32-00054B THERMISTOR IN,ø5,200 1
22 DB39-00183A C/W FAN_CAP UL1015 AWG #22 1
23 DB93-01549C POWER CORD 15A 1
24 6001-001054 SCREW-MACHINE TH M4xL10 1

Samsung Electronics 33

Downloaded from www.Manualslib.com manuals search engine


7-4 Ass'y Control Out

■ SH09BPHX : DB93-02740D
■ SH12BPHX : DB93-02740C

34 Samsung Electronics

Downloaded from www.Manualslib.com manuals search engine


Exploded Views and Parts List

■ Parts List
Q'TY
No. Code No. Description Specification
SH09BPHX SH12BPHX

1 DB93-01627A CASE CONTROL BASE ABS 5V 1 1


2 DB62-02749A HEAT SINK MAIN - 1 1
3 DB93-02741C ASS'Y PCB OUT ASS'Y - 1
DB93-02741D ASS'Y PCB OUT ASS'Y 1 -
4 6006-001051 SCREW-MACHINE M4xL16 WSP PH+ 5 5
5 6006-000160 SCREW-MACHINE M3xL16 WSP PH+ 2 2
6 6002-000630 SCREW-TAPPING PH,+,2S,M3,L8 1 1

7 DB61-01628A CASE CONTROL COVER RESIN-ABS 1 1


8 DB39-00608E CONNECTOR WIRE COMP UL1015 AWG#16 1 1
9 DB39-00607B CONNECTOR WIRE REACTOR UL1015 AWG#16 1 1
10 DB39-01003A CONNECTOR WIRE FAN UL1007 AWG#20 1 -
11 - - - - -
12 - - - - -
13 DB93-02775A ASS'Y L/W POWER UL1015 AWG#16 1 1
14 DB39-00649C CONNECTOR WIRE 4 WAY V/V UL1015 AWG#18 1 1
15 - INSULATOR-MICA - 1 1
16 DB65-00086A ASS'Y TERMINAL BLOCK 3P 3P 1 1
17 DB61-00250A HOLDER WIRE PP 1 1
18 DB70-00465A PLATE-CASE CONTROL SGCC-MTO.6 1 1
19 6003-000325 SCREW-TAPPING PH,+,2,M3,L20 1 1
20 6005-000643 SCREW-TAPPING TH,+,1,M4,L10 2 2
21 6002-000171 SCREW-TAPPING PH,+,2S,M4,L10 1 1
22 - FOAMLEX 60x180xT2.0 1 1

23 DB93-00936A RUN CAPACITOR 1.7µF/450V 1 -


24 - SCREW-TAPPING M3x14 WSP PH+ 1 -
25 DB62-02541L SEAL CASE CONTROL BASE 70x15xT10 1 1

Samsung Electronics 35

Downloaded from www.Manualslib.com manuals search engine


8. PCB Diagram

8-1 ASS'Y PCB Indoor Unit : DB93-02584A

■ TOP

36 Samsung Electronics

Downloaded from www.Manualslib.com manuals search engine


PCB Diagram

■ BOTTOM

Samsung Electronics 37

Downloaded from www.Manualslib.com manuals search engine


PCB Diagram

■ Parts List
Location No. Description Specification Q'TY Remark

D101 DIODE-RECTIFIER UG2D,200V,2A,DO-204AC,TP 1


D701,D702,D703 DIODE-RECTIFIER MRA4005,600V,1A,SMA,TP 3
BD71 DIODE-BRIDGE DF06S,600V,1A,SMD-4,TP 1
ZD11 DIODE-ZENER BZX84C3V6,3.6,350mW,SOT-23,TP 1
ZD71 DIODE-ZENER 1N4749A,24V,5%,1W,DO-41,TP 1
ZD12 DIODE-ZENER BZX84-C11,10.4-11.6V,350MW,SOT-23,TP 1
CD11 DIODE-TVS ST02D-200,185/200/215V,200W,DO-214 1
Q201,Q401,Q602 TR-SMALL SIGNAL 2SC2412K,NPN,200mW,SOT-23,TP,1 3
Q603 TR-SMALL SIGNAL MMST2907A,PNP,200mW,SOT-23,TP,100- 1
Q301,Q302,Q601 TR-DIGTAL DTC114EKA,NPN,200mW,10K/A0K,SOT-23,TP 3
IC05,IC06,IC07 TR-ARRAY 2003,NPN,7,1W,SOP-16,ST,1000 3
PC02 PHOTO-COUPLER TR,50-150%,200mW,DIP-4,ST 1
PC01,PC31,PC32 PHOTO-COUPLER TR-100-300,200mW,SOP,TP 3
IC08 IC-SOURCE DRIVER TD62783AFW,SOL,18P,-,8,-500MA,TP 1
IC51 IC-EEPROM 93LC56,128x16Bit,SOP,8P,150MIL,-,2.5V,- 1
IC03 IC-VOLTAGE COMP. 7533,TO-92,3P,-,SINGLE,-,-,PLASTIC 1
IC01 IC-PWM CONTROLLER 255,DIP,8P,300MIL,PLASTIC,-0.3/7 1
VA71,VA72,VA73 VARISTOR INP14D561K 3
R703,R704 R-METAL OXIDE(S) 4.7Kohm,5%,2W,AA,TP,4x12mm 2
R701,R702 R-METAL OXIDE(S) 47Kohm,5%,3W,AA,TP,6x16mm 2
R601,R602 R-CHIP 10Kohm,1%,1/10W,TP,1068 2
R504,R505,R506 R-CHIP 330ohm,5%,1/10W,TP,1068 3
R302,R604,R605 R-CHIP 470ohm,5%,1/10W,TP,1068 1
R201,R207,R208,R301 R-CHIP 1Kohm,5%,1/10W,TP,1068 8
R401,R403,R607,R903
R603,R901 R-CHIP 4.7Kohm,5%,1/10W,TP,1068 2
R206,R902 R-CHIP 10Kohm,5%,1/10W,TP,1068 2
R510,R511 R-CHIP 47Kohm,5%,1/10W,TP,1068 2
R606 R-CHIP 560ohm,5%,1/10W,TP,1068 1
R706 R-CHIP 100Kohm,5%,1/8W,TP,2012 1
R202,R203,R304,R205 R-CHIP 100Kohm,5%,1/4W,TP,3216 4
R707 R-CHIP 1Kohm,5%,1/8W,TP,2012 1
R102,R103,R104 R-CHIP 220Kohm,5%,1/4W,TP,3216 3
R106,R407 R-CHIP 220ohm,5%,1/8W,TP,2012 2
R101 R-CHIP 4.7Kohm,5%,1/8W,TP,2012 1
R105 R-CHIP 470ohm,5%,1/8W,TP,2012 1
R402,R501,R502,R503 R-CHIP 6.8Kohm,1%,1/10W,TP,1068 4
R303 R-CHIP 8.2Kohm,1%,1/10W,TP,1068 1
C104 C-CERAMIC,DISC 2.2NF,20%,400V,Y5U,BK,12.5x6mm,10 1
C103,C107,C110,C112,C201 C-CER,CHIP 100nF,+80-20%,50V,Y5V,TP,2012 11
C202,C500,C501,C502,C503
C901

38 Samsung Electronics

Downloaded from www.Manualslib.com manuals search engine


PCB Diagram

■ Parts List (cont.)


Location No. Description Specification Q'TY Remark

C301,C510,C706,C903 C-CER,CHIP 1nF,10%,50V,X7R,TP,2012,- 4


C203,C204,C302,C303 C-CER,CHIP 10nF,+80-20%,50V,Y5V,TP,2012 6
C401,C705
C702 C-FILM,LEAD-PEF 10nF,10%,630V,TP,16x11x7.5mm,5 1
C703,C704 C-FILM,LEAD-PEF 4.7nF,10%,100V,TP,10x8.5x5.0mm 2
XC71,XC72 C-FILM,MPPF 100nF,10%,275V,BK,18x6x12,15 2
C111 C-AL 470uF,20%,16V,GP,TP,8x11.5,5 1
C106 C-AL 1000uF,20%,25V,GP,TP,13x20,5 1
C701 C-AL 470uF,20%,50V,GP,TP,13x20,5 1
C601 C-AL 47uF,20%,50V,GP,TP,6.3x11,5 1
C101,C102 C-AL 6.8uF,20%,450V,GP,TP,10x16mm,5 2
L101 INDUCTOR-RADIAL 5000uH,10%,8.0x11.0mm 1
X301 RESONATOR-CERAMIC 10MHz,0.5%,TP,10.0x5.0x10.0mm 1
BZ61 BUZZER-PIEZO 70dB,3V,-,2KHz,BK 1
RY71 RELAY-POWER 12VDC,0,9W,20000MA,SPST,20MS,10MS 1
SS71 SSR 12Vdc,-,2A,1mS,1mS 1
F701 FUSE-CARTRIDGE 250V,3.15A,FAST-ACTING,CERAMIC,5.2x20mm 1
F702 FUSE-RADIAL LEAD 250V,1A,TIME-LAG,-,8.5x8mm 1
CN72 CONNECTOR-HEADER 1WALL,2P,1R,7.92mm,STRAIGHT,SN,WH 1
CN73 CONNECTOR-HEADER 1WALL,3P,1R,7.92mm,STRAIGHT,SN,WH 1
CN74 CONNECTOR-HEADER BOX,3P,1R,2.5mm,STRAIGHT,SN,BLU 1
CN62 CONNECTOR-HEADER BOX,5P,1R,2.5mm,STRAIGHT,SN 1
CN71 CONNECTOR-HEADER 1WALL,2P,1R,7.92mm,STRAIGHT,SN,BLU 1
CN42 CONNECTOR-HEADER BOX,2P,1R,2mm,STRAIGHT,SN,WHT 1
CN51 CONNECTOR-HEADER BOX,14P,1R,2mm,STRAIGHT,SN 1
CN53 CONNECTOR-HEADER BOX,3P,1R,2mm,STRAIGHT,SN 1
CN61 CONNECTOR-HEADER PH-5A,BOX,5P,2mm,WHT 1
CN41 CONNECTOR-HEADER BOX,4P,1R,2mm,STRAIGHT,SN,WHT 1
CN81 CONNECTOR-HEADER PH-3A,BOX,3P,1R,2mm,BLU 1
IC02 KA78L05AZTA(0.1A,Positive,Vol,Reg) 1
IC04 IC MICOM MB89538APF-101,MB89538APF-101,64P,+5V,10M 1
ST11 TRANS SWITCHING DC12V,-,-,-,-,-,-,12V,0.01A,-,E119 1
DSA POSISTOR DSA-332MA,2pF MAX,100Mohm,ASM-3 1
JE LEAD-WIRE UL1015 AWG#20 GRN/YEL 1
PCB 1
FT72 LS403110 1
C001 SC102M Y-CAP 7.5mm 1

Samsung Electronics 39

Downloaded from www.Manualslib.com manuals search engine


8-2 Ass'y PCB Outdoor Unit : DB93-02741D(9K) / DB93-02741C(12K)

■ TOP

40 Samsung Electronics

Downloaded from www.Manualslib.com manuals search engine


PCB Diagram

■ Parts List
Location No. Description Specification Q'TY

D102 DIODE 1N4937,600V/1A 1


BD01 DIODE-BRIDGE GSIB2560 1
C011,C010 C-CERAMIC 103,2KV 2
C003,C004 C-CERAMIC 0.33uF,275V 2
C01 C-CERAMIC 684,275V 1
C101,C102,C103 C-AL 560uF,400V 3
C104,C105,C304 C-CERAMIC 222,2KV 3
C123 C-AL 10uF,450V 1
C201,C437,C117,C508 C-AL 47uF,35V 4
C301 C-FILM 10nF,100V 1
C303,C308 C-CER,CHIP 1nF,50V,1608 2
C402,C404,C406,C407 C-CER,CHIP 470pF,1608 4
C409,C410,C411 C-AL 47uF,50V 3
C416,C905 C-AL 220uF,50V 2
C418 C-FILM 100nF,630V 1
C464,C466,C108,C109,C110 C-AL 220uF,25V 5
C509 C-CER,CHIP 47nF,50V,2012 1
C520,C516,C506,C507,C513,C514,C202 C-CER,CHIP 100nF,25V,1608 13
C518,C551,C413,C414,C415,C412
C521,C305,C306,C302,C307 C-CER,CHIP 10nF,50V,1608 5
C653 C-CERAMIC 10nF,25V 1
C702 C-AL 100uF,16V 1
C902 C-AL 10uF,50V 1
CN01 CONNECTOR-HEADER YAW396-07V,WHT 1
CN04 CONNECTOR-HEADER YAW396-03AV,BLU 1
CN52,CN51 CONNECTOR-HEADER SMAW250-04,WHT 2
CN53 CONNECTOR-HEADER SMAW250-06,WHT 1
CN701 CONNECTOR-HEADER SMW200-04,NTR 1
D101 DUAL-DIODE FEP30JP 1
D201 DIODE-RECTIFIER US1G,400V 1
D401,D402,D403 DIODE-RECTIFIER 1N4937,600V,1A 3
DSA SURGE-ABSORBER DSA332M 1
FT01 SS2915044B SS2915044B 1
FT00 SS2915025B SS2915025B 1
FUSE FUSE 65TS-150-H,250V,20A 1
IC01 IC-MICOM ML66Q517 1
IC11 IC-PWM CONTROLLER TOP222P,8P/DIP 1
IC17 IC-POSI.FIXED REG KA7805A,TO-220 1
IC18 IC-POSI.FIXED REG KA7815 1
IC19 IC-POSI.FIXED REG KA7812A,TO-220 1
IC21,IC32 PHOTO-COUPLER TLP181-GRH,150-300% 2
IC701 IC-EEPROM 93LC56,128x16Bit 1
IC73 IC-POSI.ADJUST REG TL431,8P/SMD 1

Samsung Electronics 41

Downloaded from www.Manualslib.com manuals search engine


PCB Diagram

■ Parts List (cont.)


Location No. Description Specification Q'TY

IPM IPM FSAM15SM60A,* 1


LED1 LED 3mm/2.54,RED 1
LED2 LED 3mm/2.54,GRN 1
LED3 LED 3mm/2.54,YEL 1
PT02 PULSE TRANS PT_30AM,* 1
PTC1 PTC PTC,27R 1
Q202,Q302,Q301,Q905,Q907,Q902 TR-DIGITAL KRC102S,* 6
Q803 IGBT-SGL IRG4BC30F,* 1
Q901,Q903,Q904,Q906 TR-DIGITAL KRA102S,SOT-23 4
R001 R-CEMENT 200-J,5W 1
R101 R-METAL OXIDE(S) 47K-J,3W 1
R102 R-CHIP 6.8-F,1/10W,2012 1
R115 R-CHIP 14.3K-F,1/4W,3216 1
R201 R-METAL OXIDE 47K-J,2W 1
R202 R-METAL OXIDE 100K-J,2W 1
R204,R515 R-CHIP 20K-J,1/8W,1608 2
R301,R307 R-METAL OXIDE(S) 4.7K-J,2W 2
R303,R304 R-CHIP 470-J,1/10W,1608 2
R305,R404,R403,R402,R401,R406,R415 R-CHIP 4.7K-J,1/12W,1608 7
R306 R-CHIP 560-J,1/12W,1608 1
R418 R-CHIP 0.02R-J,7W 1
R425,R423,R421 R-CHIP 100-J,1/8W,1608 3
R459 R-CHIP 47K-J,1/8W,2012 1
R460 R-CHIP 20K-J,1/8W,2012 1
R507,R508 R-CHIP 1K-F,1/12W,1608 2
R510,R511,R509 R-CHIP 100K-J,1/12W,1608 3
R512 R-CHIP 5.6K-J,1/12W,1608 1
R513,R514,R529,R528,R527,R526,R530 R-CHIP 10K-F,1/12W,1608 15
R531,R525,R524,R522,R521,R533,R534
R535
R536 R-CHIP 1M-J,1/10W,1608 1
R537,R538 R-CHIP 10K-J,1/10W,1608 2
R801 R-CEMENT 0.045-J,3W 1
R812,R506,R517,R505,R553 R-CHIP 330-J,1/12W,1608 5
RY01 RELAY-POWER UKH-12S,12Vdc/20A 1
RY502,RY501 RELAY-MINIATURE FTR-F3AA012E,12Vdc/5A 2
VA07,VA08,VA09,VA03,VA04 VARISTOR INR14D561K-RS,560V,2500A 5
XTAL01 RESONATOR-CERAMIC 6.25MHz,* 1
ZD21 DIODE-ZENER 1N4749A,24V/1W 1
ZD23,ZD22 DIODE-ZENER MMBZ5232B,* 2
ZD31 DIODE-ZENER 1N4751A,30V/1W 1

42 Samsung Electronics

Downloaded from www.Manualslib.com manuals search engine


PCB Diagram

■ BOTTOM

Samsung Electronics 43

Downloaded from www.Manualslib.com manuals search engine


PCB Diagram

■ Parts List
Location No. Description Specification Q'TY

C111,C801 C-CER,CHIP 1uF,2012 2


C203,C421 C-CER,CHIP 1nF,50V,2012 2
C401,C403,C405,C517 C-CER,CHIP 1.2nF,2012 4
C106,C118,C121,C122,C124,C408 C-CER,CHIP 100nF,50V,2012 11
C417,C423,C519,C802,C803
C451 C-CERAMIC 33pF,25V 1
C452 C-CERAMIC 4.7nF,25V 1
C453,C454,C462 C-CER,CHIP 2.2nF,2012 3
C806 C-CER,CHIP 470pF,50V,2012 1
C900 C-CER,CHIP 1uF,3225 1
C204,C455,C501,C502,C503,C804 C-CER,CHIP 10nF,50V,2012 12
C805,C807,C903,C904,C906,C907
D103,D104,D106 DIODE-RECTIFIER ES1D,200V/1A 3
D202,D451 DUAL-DIODE DCB010,* 2
D301 DIODE ES1D,200V 1
IC02 S80142 S80142ANMC-JC3T2,* 1
IC15 PHOTO-COUPLER TLP181,* 1
IC31 PHOTO-COUPLER TLP181-GRH,150-300% 1
IC451 IC-OP AMP LA6393M,* 1
IC55,IC56 TR-ARRAY ULN2003AFW,1W 2
IC74 IC-LOGIC 74HCT00D,SOP-14 1
IC83 LM324 LM324,* 1
Q201,Q802 TR-DIGITAL KRC102S,* 2
Q801,Q804 TR-SMALL SIGNAL BC847B,* 2
R002,R003 R-CHIP 470K-F,1/2W,5025 2
R105 R-CHIP 6.8K-F,1/8W,2012 1
R110,R111,R451 R-CHIP 180K-F,6432/1W 3
R112,R113,R114 R-CHIP 470K-F,1/4W 3
R203,R405,R461,R804 R-CHIP 4.7K-J,1/8W,2012 4
R407,R408,R409 R-CHIP 33-J,1/10W,2012 3
R104,R106,R413 R-CHIP 3.3K-J,1/8W,2012 3
R414,R523,R532,R808,R810 R-CHIP 10K-F,1/10W,2012 5
R416 R-CHIP 390-J,1/10W,2012 1
R419,R420,R422,R424 R-CHIP 100-J,1/8W,2012 4
R426,R427,R428 R-CHIP 300K-F,1W,6432 3
R429 R-CHIP 1.6K-F,1/8W,2012 1
R430 R-CHIP 51-F,1/8W,2012 1
R452 R-CHIP 150K-F,1W,6432 1

44 Samsung Electronics

Downloaded from www.Manualslib.com manuals search engine


PCB Diagram

■ Parts List (cont.)


Location No. Description Specification Q'TY

R453 R-CHIP 2.7K-F,1/8W,2012 1


R501,R504 R-CHIP 5.1K-F,1/8W,2012 2
R539,R540,R541 R-CHIP 2.2K-J,1/8W,2012 3
R502,R552 R-CHIP 24K-F,1/8W,2012 2
R554 R-CHIP 470-J,1/8W,2012 1
R802 R-CHIP 220-J,1/8W,2012 1
R803 R-CHIP 2.2K-F,6432/1W 1
R805 R-CHIP 3.3K-F,1/8W,2012 1
R302,R807 R-CHIP 1K-J,1/8W,2012 2
R103,R811,R813 R-CHIP 330-J,1/8W,2012 3
R814 R-CHIP 5.1K-J,1/8W,2012 1
R806,R809,R901,R902, R-CHIP 10K-J,1/8W,2012 8
R903,R904,R905,R908
R906 R-CHIP 6.8K-J,1/8W,2012 1
R907 R-CHIP 560-J,1/8W,2012 1

Samsung Electronics 45

Downloaded from www.Manualslib.com manuals search engine


8-3 ASS'Y DISPLAY PCB(9K / 12K) : DB93-01368G

■ Parts List

No Description Specification Q'TY Remark

1 ASS'Y LED MODULE 1 SNA


2 PCB-DISPLAY FR-1 T1.6 1 SNA
3 TACT SWITCH KPT-1105A TSTA-2 1 SNA
4 RESISTOR 200ohm, 2W 2 SNA
5 RESISTOR 100ohm, 2W 3 SNA
6 CONNECTOR WIRE 14P 1 SNA

46 Samsung Electronics

Downloaded from www.Manualslib.com manuals search engine


8-4 ASS'Y MODULE PCB(9K / 12K) : DB93-01369A

■ Parts List

No Description Specification Q'TY Remark

1 PCB-DISPLAY FR-1 T1.6 1 SNA


2 CONNECTOR SMAW200-03P(WHT) 1 SNA
3 C-CERAMIC CA OA 50V 102K 1 SNA
4 DIODE SWITCHING 1N4148 1 SNA
5 C-CERAMIC CA OA 50V 104Z 1 SNA
6 MODULE REMOCON FRP4021-H7(7mm) 1 SNA

Samsung Electronics 47

Downloaded from www.Manualslib.com manuals search engine


DB98_17175A_1 2/6/04 4:14 PM Page 49

9. Wiring Diagram

9-1 Indoor Unit(9K / 12K)

This Document can not be used without Samsung's authorization.

48 Samsung Electronics

Downloaded from www.Manualslib.com manuals search engine


DB98_19047A(1)_2 4/21/04 2:27 PM Page 50

9-2 Outdoor Unit(9K / 12K)

Code No : DB98-17635A

This Document can not be used without Samsung's authorization.

Samsung Electronics 49

Downloaded from www.Manualslib.com manuals search engine


MEMO

50 Samsung Electronics

Downloaded from www.Manualslib.com manuals search engine


ELECTRONICS

This Service Manual is a property of Samsung Electronics Co., Ltd. © Samsung Electronics Co., Ltd.
Any unauthorized use of Manual can be punished under applicable Printed in China.
International and/or domestic law.

Downloaded from www.Manualslib.com manuals search engine