Module 4
Module 4
Residential Occupancies
Residential occupancy is defined as an occupancy that provides sleeping accommodations for purposes
other than health care or correctional. This includes four categories: one- or two-family dwellings,
lodging or rooming houses, hotels or motels or dormitories, and apartments. Each category has its own
chapter.
Chapter 24 covers one- or two-family dwellings, including new, existing, and modified buildings.
Smoke alarms are required in all sleeping rooms, outside of each sleeping area, and on each level
including basements. The smoke alarms must be hard wired in new constructions, but may be battery
powered in existing.
Carbon monoxide alarms are required in all new one- and two-family dwellings with an attached garage,
fuel burning appliance, or fuel burning fireplace. CO alarms are required to be positioned in the
immediate vicinity of sleeping rooms and on each occupiable level including basements.
Lodging and rooming occupancies provide sleeping accommodations for <=16 occupants, excluding
residential one- or two-family dwellings. Main difference compared to hotels and to board and care are
in the number of occupants, the nature of personal care provided, and duration of accommodation.
Main differences between lodging and rooming compared to one- and two-family units is requirements
for protecting stairs providing the primary means of escape, through the protection of vertical openings.
Open Stair:
Per Chapter 43 requirement that change of occupancy meets sprinkler and alarm requirements for new
construction, converting a one- or two-family dwelling to a lodging and rooming bed and breakfast
requires adding sprinklers and fire alarms.
Hotels and Dormitories, covered in Ch28/29, address residential occupancies involving transient or short
duration stays, like hotels and motels, as well as dormitories which are typically occupied during the 9-
month academic year.
Means of escape from guest rooms and suites must comply with Section 24.2 for one- and two-family
dwellings, where by analogy guest room:guest suite::dwelling unit:living unit
Travel distance limitations for all sleeping occupancies consist of (1) travel within a room or suite of
rooms to the room door, and (2) travel from the corridor door to the nearest exit
For new and existing hotels: If no automatic sprinklers, travel distance within a guest room must be
<=75ft, and travel distance from corridor door to exit must be <=100 ft. If there are automatic sprinklers,
travel distance within a guest room must be <=125ft, and travel distance from corridor door to exit must
be <=200 ft.
Fire alarm system is required in hotels and dorms and must initiated by each of the following:
Smoke alarms are required in all sleeping/living areas in new and existing buildings.
Carbon monoxide alarms are required where guest rooms or guest suites communicate with attached
garages or contain a permanently installed fuel burning appliance.
All new buildings must have supervised automatic sprinklers throughout. Existing high-rise buildings
must have automatic sprinklers unless each guest room or guest suite has exterior exit access
Doors that open into exit access corridors must be self-closing and self-latching.
Transoms, louvers, transfer grilles are banned in walls or doors of exit access corridors of new buildings.
Apartments
Requirements, outlined Ch30/31, are similar to hotels and dorms, due to shared configuration of interior
corridor connecting various dwelling units.
Requirements for existing apartment buildings vary based on present protection options from among:
(1) no suppression or detection system, (2) complete automatic detection system, (3) automatic
sprinklers in defined areas lie corridors, (4) total automatic sprinkler protection
Apartment buildings have several exceptions permitted a single exit, unlike hotels and dorms.
The living unit has an exit leading directly to the street or yard at ground level
The apartment has direct access to an outside stair serving a maximum of two apartments, both
of which are on the same floor
The single exit is a private stairways serving one apartment only and is separated from all
abutting apartment units, including those on lower floors, by 1 hour rated construction
Exception 2: A single exit is permitted if all these conditions are met:
If fire alarm system is required in apartment building, new or existing, it must notify fire department
using auxiliary, central station, proprietary supervising station, or remote supervising station fire alarm
system. Sprinklers are required for all new apartment buildings.
Detention and correction occupancies are used to house one or more persons under varied degrees of
restraint or security, where such occupants are mostly incapable of self-preservation because of security
measures not under the occupants’ control
Detention and correction occupancies include adult/juvenile substance abuse centers, adult and juvenile
work camps, adult and juvenile community residential centers, adult correctional institutions, adult local
detention facilities, juvenile detention facilities, and juvenile training schools.
No physical restrictions such as locks on means of egress. Occupants are capable of self preservation.
Example is work release center. Exempt from Ch22/23 if meet the requirements of some other
residential occupancy chapter, like Ch28/29 for dorms.
Residents have ability to move freely within the building, such as from their room across smoke barriers
and into separate smoke compartments. Locked doors, that are permitted to be unlocked manually at
the door, impede movement through the exit door on the exterior wall to the outside.
Residents have ability to move outside their rooms but are confined to the smoke compartments that
contain their room. Locked doors within the smoke barrier are equipped with remote control locks to
impede movement to adjoining smoke compartment. Locked doors, that are permitted to be unlocked
manually at the door, impede movement through the exit door on the exterior wall to the outside.
Residents are locked in their sleeping rooms. Locks on sleeping room doors are equipped with remote
control release. Locked doors within the smoke barrier are equipped with remote control locks to
impede movement to adjoining smoke compartment. Locked doors, that are permitted to be unlocked
manually at the door, impede movement through the exit door on the exterior wall to the outside
All locks are manually operated at the individual door. The unlocking process places a heavy demand on
staff to open doors in an emergency, severely restricting the movement of residents, necessitating
stringent life safety requirements.
22/23.2.2.5.2 permit horizontal exits to comprise 100% of the exits from any fire compartment provided
the compartment is not dead ended (i.e. it is not necessary to move through a compartment where fire
could originate to reach a door to the outside). In example below, A and C are compliant with a least
two exits (one outside, one to adjoining compartment), B is compliant with 100% of exits being
horizontal exits to other compartments, but C is not compliant since 100% of exit is a horizontal exit to C
which may be dead ended if fire originates there.
Travel distance in detention occupancies is measured to the closest exit only, along the natural path of
travel. The travel distance between any point in sleeping room to door in that room must be <= 50 ft.
The maximum travel distance limitation, such as from X2 to C2, may be increased to 100 ft in open
dorms provided that the enclosing walls of the dormitory are smoke-tight construction AND also that
>=2 exit access doors remotely located from each other are provided where travel distance to the exit
access from any point within the dorm exceeds 50 ft.
The travel distance between any room door required as an exit access and an exit (C1 -> E1, or C2 -> E2)
must be <=150 ft. The travel distance between any point in a room and an exit (X1 -> E1, or X2 -> E2)
must be <=250 ft.
In occupancies other than detention, up to 50% of required exits in either number or capacity can
discharge through the LED and remaining must discharge directly outside. At detention occupancies, due
to security concerns, up to 100% of exits can discharge through the LED if a minimum 1-hour fire rated
separation that creates at least two fire compartments is provided on the LED. The number or capacity
of exits discharging into any one fire compartment must be <=50% of total number or capacity of exits.
Smoke barrier may be used instead of a fire barrier in an existing facility if the travel route along the LED
is sprinklered and the route is separated from nonsprinklered portions of the LED by fire barriers
meeting the fire resistance rating requirements of exit enclosure.
Doors in a means of egress are permitted to be horizontal sliding type, assuming that the force
necessary to slide the door to its fully open position be <=50 lb applied perpendicular to door.
Any remote-control release used in means of egress must have a reliable means of operation to releasee
locks on all doors and be remotely located from the resident living areas unless otherwise permitted.
Vertical openings must be protected per Section 8.6 Maximum 2-story unprotected conveinience
openings are permitted per 8.6.9.1.
In new residential housing smoke compartments, and existing residential housing smoke compartments
protected by automatic sprinklers, unprotected openings are permitted per 8.6.6. The maximum 3-story
limitation is exempted provided the height between lowest and highest finished floor levels does not
exceed 23 ft.
Multilevel housing: For existing non=sprinklered buildings, the vertical separation from the lowest floor
level and the uppermost floor level may not exceed 13 ft.
Multitiered Open Cell Block: can be considered a single story building in an existing building, assuming
that either the entire building is protected with automatic sprinklers OR smoke control is provided to
maintain the smoke level from potential cell fires >=60 inches above the highest occupied tier within the
cell block.
Subdivision of building spaces: per 22/23.3.7, smoke barriers must be provided to divide every story
used for sleeping by
into at least two compartments. This is exempted where protection si permitted to be accomplished
using horizontal exits, OR where the requirement for subdivision is permitted to be accomplished by
smoke compartments having exit to public way, where exit serves only one area and has no
opening to other areas
building is separated from the resident housing area by 2-hour fire resistance rating or 50 ft of
open space
secured open area having a holding space located 50 ft from housing areda that provides 15 sqft
or more of refuge area for each occupant (staff, resident, visitor)
Based on use category, new or existing, and automatic sprinkler presence, there are requirements for
resident housing space subdivision listed in Table 22/23.3.8