Lenze AC Tech SMV Quick Start Guide

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

SMV Quick Set-Up Card

Input Voltage Selection


Always check this parameter at first power up, set to a value based on mains voltage
P107 = “0” for mains voltage = 120,200,400,480 (VAC)
P107 = “1” (Default) for mains voltage = 120,240,480,600 (VAC)

Frequency Control Wiring


Internal Voltage Control Com A in +10v
2 5 6
P100 = 0, 1, 2, 4 or 5
P101 = 1
2k – 10k

External Voltage Control Com A in


2 5
P100 = 0, 1, 2, 4 or 5
P101 = 1 for 0 -10V input External Speed
Ref Common
External Speed
Ref Voltage

Current Source Speed Control


Com A in
P100 = 0, 1, 2, 4 or 5
P101 = 2 for 4-20mA input 2 25
P163 (TB-25 current loss action) External External
0 = No action Current Current
Ref (-ve) Ref (+ve)
1 = “F.FoL” fault message when input is less than 2mA
2 = Go to Preset Speed

Digital Input Logic Control Wiring


The digital inputs can be configured for positive logic or negative logic,
by setting switch (ALsw) (see picture opposite)
P120 must also be set to match the configuration.
P120 = “1” (Negative logic/Active low/NPN)
P120 = “2” (Positive logic/Active High/PNP) (Default)
(Incorrect setting will result in “F.AL” fault message)

TB-1 = Drive Start/Stop (note that P100 must be set to 1,4 or 5)


TB-13A = Configured using P121 (Default = 0 : No function)
Start +15V/0V* D1 D2 D3
TB-13B = Configured using P122 (Default = 0 : No function)
1 4 13A 13B 13C
TB-13C = Configured using P123 (Default = 0 : No function)
10 = Rev rotation 11 = Start fwd 12 = Start rev
13 = Run fwd 14 = Run rev 15 = Jog fwd
16 = Jog rev 17 = Accel/Decel 2 18 = DC brake *Dependant on logic selected - Negative/Positive
19 = Aux ramp to stop 20 = Clear fault 21 = Ext fault
22 = Inverse Ext fault (0 to 9-Please refer to operating instructions)

Relay Terminal Wiring


Relay contact state when :
P140 = 0 (Always Open)
P140 = 1 (Closed = drive running) Internal Drive Relay
P140 = 2 (Closed = drive running in reverse) Contacts
P140 = 3 (Open = drive tripped)
P140 = 4 (Closed = drive tripped)
P140 = 5 (Open = restart attempts failed if P110 =3 to 6)
P140 = 6 (Closed = output frequency =commanded frequency) 16 17
P140 = 7 (Closed = output frequency is >P136)
P140 = 8 (Closed = motor current = P171)
To External
P140 = 9 (Closed = 4-20mA signal is below 2mA) Device
P140 = 10 (Closed = motor load is below P145)
P140 = 11 through to 22 (Please refer to operating instructions)

UK
SMV Quick Set-Up Card
Parameter Settings:
P100: Start Control Source (Default = ‘0’)
0 = Local keypad : Run button on front of drive
1 = Terminal strip : Terminal strip start/stop circuit

P101: Standard reference source (Default = ‘0’)


0 = Keypad (local or remote) : Speed/torque reference from keypad buttons
1 or 2 : See “Frequency Control Wiring” section.
3 = Preset #1 : Speed/torque reference = Preset #1*
4 = Preset #2 : Speed/torque reference = Preset #2*
5 = Preset #3 : Speed/torque reference = Preset #3*
6 = Network : Speed/torque reference from network*
*Only if no Auto reference is selected using digital inputs

P102 : Minimum Output Frequency (Default = ‘0Hz’)


Set to minimum Frequency for Application

P103 : Maximum Output Frequency (Default = ‘60Hz’) P103


Set to Maximum Frequency for Application
Hz P104 P105
P104 : Acceleration Time (Default = ‘20s’)
Set to required Acceleration Time P102 P102

P105 : Deceleration Time (Default = ‘20s’)


Set to required Deceleration Time t

P108 : Motor overload protection (Default ‘100%’)


Calculate P108 = (motor rated current / SMV output current rating) x 100

P300: Operating Mode (Default = ‘0’)


0 = Constant V/Hz Constant torque V/Hz, for general applications
1 = Variable V/Hz Variable torque V/Hz, for centrifugal fan and pump applications
2 = Enhanced Constant V/Hz-

For single or multiple motor applications that require better


performance than settings 0 or 1 but cannot use vector
mode as no motor data is available or vector mode causing
motor instability.

3 = Enhanced Variable V/Hz-


4 = Vector Speed Single motor applications requiring high starting torque and speed
regulation
5 – Vector Torque Single motor applications requiring torque control independent
of speed

Vector speed and torque control setup (P300 = 4 or 5)

If P300 = 4 or 5, a motor auto-calibration must be carried out, ensure motor nameplate data is programmed
first (detailed below), failure to do so will result in a F.n ld fault message.

P302 = Motor rated voltage


P303 = Motor rated current
P304 = Motor rated frequency
P305 = Motor rated speed
P306 = Motor Cosine Phi
Set P399 to 1 to start the motor auto-calibration, the display will show “CAL” for a short period of time and
then “StoP” once completed. rev A