Product Selection Guide
Product Selection Guide
Selection Guide
EcoStruxure™ Building
Integrated building management system
se.com/ecostruxure-building
I2 se.com/ecostruxure-building
Unlock building value, unleash productivity
Next generation EcoStruxure™ Building from Schneider Electric is The Open Innovation Platform of
Buildings – a collaborative Internet of Things (IoT) solution that features a scalable, secure and global
architecture to create future-ready smart buildings.
Our EcoXpert partners are the implementation arms of EcoStruxure in Homes and Buildings
I4 se.com/ecostruxure-building
Table of Contents
EcoStruxureTM Solution
Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E2
User Interfaces. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E4
Automation Server Family of Modules . . . . . . . . . . . . . . . . . . . . . . . . . E6
SpaceLogic Edge Server – AS-P. . . . . . . . . . . . . . . . . . . . . . . . . . . . . E6
Power Supply and Module Terminal Bases . . . . . . . . . . . . . . . . . . . . . E7
Power Supply Selection Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E7
I/O Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E8
I/O Modules - Inputs and Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . E12
SpaceLogic Edge Server – AS-B. . . . . . . . . . . . . . . . . . . . . . . . . . . . E14
SpaceLogic Edge Server – AS-B – Inputs and Outputs . . . . . . . . . . E15
Edge Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E16
SpaceLogic Advanced Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E16
Reference Architecture . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E17
SpaceLogic IP Controllers
SpaceLogic IP Controller – MP Series. . . . . . . . . . . . . . . . . . . . . . . . . S9
SpaceLogic IP Controller – IP-IO Series . . . . . . . . . . . . . . . . . . . . . . S14
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . S15
BACnet® Controllers
BACnet b3 Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B2
b3 Series Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B3
b3 Series xP Expansion I/O Modules. . . . . . . . . . . . . . . . . . . . . . . . . . B9
b3 Series Controllers – Inputs and Outputs. . . . . . . . . . . . . . . . . . . . B11
b3 Series xP Expansion I/O Modules – Inputs and Outputs . . . . . . . B14
MNB Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B15
MNB Series Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B16
MNB Series Controllers – Inputs and Outputs . . . . . . . . . . . . . . . . . B18
LonWorks® Controllers
Xenta™ Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . L2
Xenta Series Controllers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . L3
Xenta Series I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . L5
Xenta Series Controllers – Inputs and Outputs . . . . . . . . . . . . . . . . . . L7
Xenta Series I/O Modules – Inputs and Outputs . . . . . . . . . . . . . . . . . L8
MNL Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . L9
MNL Series Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . L10
MNL Series Controllers – Inputs and Outputs . . . . . . . . . . . . . . . . . . L14
Disclaimers
• Not all products in the guide may be available in every country, please check availability with the local Schneider Electric office.
• Some product images are not images of the exact model, but are represented by a “series” image.
• Information within this guide is subject to change without notice.
• Schneider Electric is not responsible for inadvertent typographical errors or omissions.
E1 se.com/ecostruxure-building
Software
SXWSWESXX00010 Enterprise Server - 10 The Enterprise Server is the Windows® application that aggregates and archives data from up to 10 Servers
SXWSWESXX00050 Enterprise Server - 50 The Enterprise Server is the Windows® application that aggregates and archives data from up to 50 Servers
SXWSWESXX00100 Enterprise Server - 100 The Enterprise Server is the Windows® application that aggregates and archives data from up to 100 Servers
SXWSWESXX00250 Enterprise Server - 250 The Enterprise Server is the Windows® application that aggregates and archives data from up to 250 Servers
SXWSWASES00001 ES Hosting AS Pack -1 Allows the addition of one more Servers than were supported by the original Enterprise Server purchased
SXWSWNDES00010 ES Hosting AS Pack - 10 Allows the addition of 10 more Servers than were supported by the original Enterprise Server purchased
SXWSWNDES00005 ES Hosted Node Pack - 5 Allow the addition of 5 servers or controllers to any of the interfaces supported by the Enterprise Server
SXWSWNDES00010 ES Hosted Node Pack - 10 Allow the addition of 10 servers or controllers to any of the interfaces supported by the Enterprise Server
SXWSWNDES00025 ES Hosted Node Pack - 25 Allow the addition of 25 servers or controllers to any of the interfaces supported by the Enterprise Server
SXWSWNDES00050 ES Hosted Node Pack - 50 Allow the addition of 50 servers or controllers to any of the interfaces supported by the Enterprise Server
SXWSWNDES00100 ES Hosted Node Pack - 100 Allow the addition of 100 servers or controllers to any of the interfaces supported by the Enterprise Server
SXWSWNDES00300 ES Hosted Node Pack - 300 Allow the addition of 300 servers or controllers to any of the interfaces supported by the Enterprise Server
SXWSWNDES00600 ES Hosted Node Pack - 600 Allow the addition of 600 servers or controllers to any of the interfaces supported by the Enterprise Server
* The Enterprise Server is BACnet B-OWS and B-BC certified; the testing for this certification included the use of EcoStruxure Building Operation WorkStation as the HMI.
SXWSWCLIENT0001 Building Operation Client - 1 Fully featured environment for operating and administering all aspects of the system – 1 seat
SXWSWCLIENT0005 Building Operation Client - 5 Fully featured environment for operating and administering all aspects of the system – 5 seats
SXWSWCLIENT0010 Building Operation Client - 10 Fully featured environment for operating and administering all aspects of the system – 10 seats
SXWSWCLIENT0025 Building Operation Client - 25 Fully featured environment for operating and administering all aspects of the system – 25 seats
SXWSWCLIENT0999 Building Operation Client - unl Fully featured environment for operating and administering all aspects of the system – Unlimited seats
Integration
SXWSWSDRV00001 Smart Driver License Allow "drivers" to be deployed, loaded and run on the Enterprise Server and the SpaceLogic Controller - AS-P
Smart Connector Deployment
SXWSWSCDL100001 Allows the Smart Connector application to be deployed to a single server
License
Engineering Tools
SXWSWWORK00002 WorkStation Professional A full environment for operating and engineering all aspects of EcoStruxure Building Operation
SXWSWEDIT00001 Editors An environment that provides the ability to edit graphics, script programs and function block programs.
Add-On Features
SXWSWSNMP00001 SNMP Alarming This option provides support for SNMP alarm traps v3.0 notifications on any EcoStruxure Building server.
SXWSWEWSX00001 EWS 1 A common integration method to other Schneider Electric systems and services. Consume
SXWSWEWSX00002 EWS 2 A common integration method to other Schneider Electric systems and services. Consume and serve
A common integration method to other Schneider Electric systems and services. Consume, serve and
SXWSWEWSX00003 EWS 3
gather history
SXWSWGWSX00001 GWS An integration method to other systems and services
SXWSWDASH00001 Personal Dashboards license Enables Personal Dashboard feature on one Enterprise Server or Enterprise Central
SXWSWECDBTS001 TimescaleDB connection license Enables high capacity historical storage in TimescaleDB on one Enterprise Central
SXWSWESDBTS001 TimescaleDB connection license Enables high capacity historical storage in TimescaleDB on one Enterprise Server
Regulated-industry Compliance
SXWSWCMPLPK001 Set of features to assist in validation in a regulated environment
Pack
SXWSWECPDFSS01 Building Operation PDF Sign EC Enables PDF documents to be digitally signed at time of generation - EC
SXWSWESPDFSS01 Building Operation PDF Sign ES Enables PDF documents to be digitally signed at time of generation - ES
SXWSWSTDBAC002 Semantic DB - Plus CPU Cores - 2 Extends semantic graph database capacity with 2 additional CPU cores
SXWSWSTDBAC006 Semantic DB - Plus CPU Cores - 6 Extends semantic graph database capacity with 6 additional CPU cores
Semantic DB - External Use Plus Enables programmatic queries from external tools to semantic graph database and extends capacity with 2
SXWSWSTDBEUAC2
Cores - 2 additional CPU cores
Semantic DB - External Use Plus Enables programmatic queries from external tools to semantic graph database and extends capacity with 6
SXWSWSTDBEUAC6
Cores - 6 additional CPU cores
SXWSWECSAML001 SAML Authentication - EC Enables SAML 2.0 authentication on Enterprise Central
SXWSWESSAML001 SAML Authentication - ES Enables SAML 2.0 authentication on Enterprise Server and connected SpaceLogic Edge Servers
E3 se.com/ecostruxure-building
User Interface
Functionality matrix
WorkStation Standard - WorkStation software without graphics editor, script and function block programming editors.
WorkStation Pro - WorkStation software including graphics editor, script and function block programming editors.
WebStation - Direct access to an Automation Server and/or Enterprise Server using a web browser.
WebReports - Direct access to the Reports Server using a web browser.
Semantics
Navigate, Search, Filter, View semantic
Yes Yes Yes
descriptions
Create and edit semantic descriptions Yes Yes
Dashboards
View dashboards Yes
Create and edit public dashboards Yes3 Yes3 Yes
Create and edit personal dashboards Yes
View slide shows Yes
Create and edit slide shows Yes Yes Yes
Develop custom dashboard components Yes
Zoning
Graphical management Yes 4
Textual management Yes 4 Yes 4 Yes 4
Alarms
View alarms Yes Yes Yes
Manage alarms Yes Yes Yes
Edit alarms Yes Yes Yes5
Create alarms Yes Yes
Support for flashing and audible alarms Yes Yes Yes
Create and edit alarm filters Yes Yes Yes
View events Yes Yes Yes
BACnetTM
View priority array Yes Yes Yes
Edit priority array Yes Yes Yes
Create devices (includes device discovery) Yes Yes
Manage BACnet backup and restore Yes Yes
Graphics
View graphics Yes Yes Yes
Create and edit graphics Yes
View graphics that use client API Yes
Create graphics that use client API Yes
Trend Logs and Extended Trend Logs
View trend logs Yes Yes Yes
Edit trend logs Yes Yes Yes6
Create trend logs Yes Yes Yes7
View multi trend log lists Yes Yes Yes
Create and edit multi trend log lists Yes Yes Yes
Export multi trend log lists Yes8 Yes8 Yes9
View extended trend logs Yes Yes Yes
Edit extended trend logs Yes Yes Yes
Create extended trend logs Yes Yes
LonWorks
Create devices (includes device discovery) Yes Yes
Manage devices Yes Yes
View Network Variables (NVs) and
Yes Yes Yes
Configuration Parameters (CPs)
Edit NVs and CPs Yes Yes Yes
Modbus ®
Create devices Yes Yes
Manage devices Yes Yes
View values Yes Yes Yes
Edit values Yes Yes Yes
1. WorkStation software without Graphics Editor, Script Editor, and Function Block Editor.
2. WorkStation software including Graphics Editor, Script Editor, and Function Block Editor.
3. Non-visual editing only.
4. Requires add-on license
5. Can edit alarm ranges, text, delay times, shunt variables, assignments, and deadband.
6. Can only change parameters, for example, interval time.
7. Can only create interval trend log type.
8. Export to XML, CSV, and XLSX supported.
9. Export to XML and XLSX supported.
Point Values
View values Yes Yes Yes
Edit values (for example, change a setpoint) Yes Yes Yes
Programs
Create and edit customised programs Yes
View graphical function block viewer Yes Yes
Notification Reports
Create and edit reports Yes Yes
Schedules and Calendars
View schedules and calendars Yes Yes Yes
Edit schedules and calendars Yes Yes Yes11
Create schedules and calendars Yes Yes
Create multi schedule views Yes Yes Yes
Edit and manage schedules in multi
Yes
schedule view
Users and User Groups
Create and edit users Yes Yes Yes12
Create and edit user group membership Yes Yes Yes12
Create and edit user groups Yes Yes
Create and edit permissions Yes Yes
User Experience
View customized workspaces Yes Yes Yes
View customized navigation panes Yes Yes Yes
Log on as Windows Active Directory user Yes Yes Yes
Log on using SAML 2.0 authentication Yes
Automatic guest account log on Yes Yes Yes
Password management Yes Yes Yes
View saved searches Yes Yes Yes
Create saved searches Yes Yes
Edit saved searches Yes Yes Yes
Simple and advanced searches Yes Yes Yes
Kiosk mode Yes
Bookmark views (web page URLs) Yes
Bookmark favorite pages Yes
Support for localization Yes Yes Yes
Support for translation Yes Yes Yes
Ability to change language on the client side Yes Yes Yes
Use personal layout and filter favorites Yes Yes Yes
Create and edit personal layout and filter
Yes Yes Yes
favorites
Support for Dark Mode Yes
Support custom accent color Yes
Other
Configure and edit I/O points, field buses,
Yes Yes
and communication ports
Create and edit logical structure Yes Yes
Create and edit views, panels, workspaces,
Yes Yes
and navigation panes
View and configure Watch pane Yes Yes Yes
Administer backup and restore of database Yes Yes
Manage archiving Yes Yes
1. WorkStation software without Graphics Editor, Script Editor, and Function Block Editor.
2. WorkStation software including Graphics Editor, Script Editor, and Function Block Editor.
10. Can edit some parameters per report, can save changes or make a copy of the report with changes.
11. Can edit only existing schedules and calendars.
12. Cannot assign permissions.
13. Excluding Graphics Editor, Script Editor, and Function Block Editor.
E5 se.com/ecostruxure-building
Automation Server Family of Modules
Power
Power 24 VDC 24 VDC 24 VDC
Consumption 10 W 10 W 10 W
Environmental
The AS-P and
0°C to 50°C (32°F to 122°F) 0°C to 50°C (32°F to 122°F) 0°C to 50°C (32°F to 122°F)
AS-B feature Operating Range 0-95% RH 0-95% RH 0-95% RH
dual Ethernet (non-condensing) (non-condensing) (non-condensing)
ports to elevate CPU Internals
BACnet field bus CPU SPEAr320S, ARM926 core SPEAr320S, ARM926 core SPEAr320S, ARM926 core
communication Memory 4 GB 4 GB 4 GB
to the IP level. Battery No No No
Modernize the Yes -10 days backup/Super Yes -10 days backup/Super Yes -10 days backup/Super
Real time clock
BMS while keeping Capacitor Capacitor Capacitor
in place legacy External Features
field buses and Enclosure rating
Eco Friendly ABS/PC, UL94 5VB, Eco Friendly ABS/PC, UL94 5VB, Eco Friendly ABS/PC, UL94 5VB,
IP 20 (<12.5 mm protection) IP 20 (<12.5 mm protection) IP 20 (<12.5 mm protection)
devices to future-
HOA Switches (DO/AO) N/A N/A N/A
ready current
Manual Override of Outputs N/A N/A N/A
systems and move
Digital Status LEDs Yes Yes Yes
buildings into the
21st century! Service Port Yes Yes Yes
Terminals
Yes - Up to 29 modules/464 Yes - Up to 29 modules/464 Yes - Up to 29 modules/464
I/O Expansion
max I/O max I/O max I/O
External Enclosure/Mounting
Mounting DIN-rail or wall mount DIN-rail or wall mount DIN-rail or wall mount
Certifications
BTL Yes Yes Yes
FCC 47 CFR § 15, Class B (Emission) 47 CFR § 15, Class B (Emission) 47 CFR § 15, Class B (Emission)
Industry Canda (IC) ICES-003 (Emission) ICES-003 (Emission) ICES-003 (Emission)
UL-916 (Energy Management UL-916 (Energy Management UL-916 (Energy Management
UL
Equipment) Equipment) Equipment)
C-UL US Yes Yes Yes
CE - EU Yes Yes Yes
WEEE - Directive of the
Yes Yes Yes
European Union
RoHS Directive Yes Yes Yes
RCM Yes Yes Yes
US Patent 8 207 842, 8 271 102, 7 994 438 8 207 842, 8 271 102, 7 994 438 8 207 842, 8 271 102, 7 994 438
UL-864 No No Yes
*Notes: EcoStruxure solution installations or BMS transitions requiring UL-864 certifications must use the SpaceLogic Controller
AS-P-SMK (listed above).
AS-P and AS-B conform to the BACnet ® Building Controller (B-BC) profile at protocol revision 12 by the BACnet Testing
Laboratories (BTL®). StruxureWare™ Building Operation v1.9 is the certified firmware revision.
SXWTBPSW110001 TB-PS-W1 Terminal Base Power Supply (Terminal Base required for each power supply)
SXWTBASW110002 TB-ASP-W1 Terminal Base AS-P (Terminal base required for each AS-P)
SXWTBIOW110001 TB-IO-W1 Terminal Base I/O (Terminal Base required for each I/O module)
PS-24V
Automation Server Power Supply
NOTE: An appropriate terminal base is required for each module, including the AS-P, Power Supply
and I/O Modules. See the above table for the correct part numbers.
I/O Module
Terminal Base and Module Detail
E7 se.com/ecostruxure-building
Automation Server Family of Modules
I/O Modules
The Automation Server includes support for a broad spectrum of I/O modules. The variety of modules available ensures the right
combination of points for any project, which keeps costs down for our customers. Some modules are available with Hand/Off/Auto
(HOA) switches to provide override control of the outputs.
AO-8,
UI-16 DI-16
AO-8-H
SXWAO8XXX10001,
Part Number SXWUI16XX10001 SXWDI16XX10001
SXWAO8HXX10001
Physical
90 W x 114 H x 64 D mm 90 W x 114 H x 64 D mm 90 W x 114 H x 64 D mm
Dimensions
(3.60 W x 4.50 H x 2.50 D in.) (3.60 W x 4.50 H x 2.50 D in.) (3.60 W x 4.50 H x 2.50 D in.)
Weight (including baseplate) 0.269 kg (0.59 lb.) 0.255 kg (0.56 lb.) 0.279 kg (0.62 lb.)
Power
Environmental
UI-16 0 °C to 50 °C (32 °F to 122 °F) 0 °C to 50 °C (32 °F to 122 °F) 0 °C to 50 °C (32 °F to 122 °F)
16 Channel Universal Input Operating Range
0-95% RH (non-condensing) 0-95% RH (non-condensing) 0-95% RH (non-condensing)
External Features
Eco Friendly ABS/PC, UL94 5VB, Eco Friendly ABS/PC, UL94 5VB, Eco Friendly ABS/PC, UL94 5VB,
Enclosure rating
IP 20 (<12.5 mm protection) IP 20 (<12.5 mm protection) IP 20 (<12.5 mm protection)
HOA Switches (DO/AO) No No Available on -H model
Service Port No No No
Terminals
External Enclosure/Mounting
Mounting DIN-rail or wall mount DIN-rail or wall mount DIN-rail or wall mount
Certifications
FCC 47 CFR § 15, Class B (Emission) 47 CFR § 15, Class B (Emission) 47 CFR § 15, Class B (Emission)
AO-8, AO-8-H
8 Channel Analog Output
Power
Environmental
AO-V-8 , AO-V-8-H 0 °C to 50 °C (32 °F to 122 °F) 0 °C to 50 °C (32 °F to 122 °F) 0 °C to 50 °C (32 °F to 122 °F)
Operating Range
8 Channel Analog Output 0-95% RH (non-condensing) 0-95% RH (non-condensing) 0-95% RH (non-condensing)
Voltage Points
External Features
Eco Friendly ABS/PC, UL94 5VB, Eco Friendly ABS/PC, UL94 5VB, Eco Friendly ABS/PC, UL94 5VB,
Enclosure rating
IP 20 (<12.5 mm protection) IP 20 (<12.5 mm protection) IP 20 (<12.5 mm protection)
HOA Switches (DO/AO) Available on -H model Available on -H model Available on -H model
Service Port No No No
Terminals
External Enclosure/Mounting
Mounting DIN-rail or wall mount DIN-rail or wall mount DIN-rail or wall mount
Certifications
FCC 47 CFR § 15, Class B (Emission) 47 CFR § 15, Class B (Emission) 47 CFR § 15, Class B (Emission)
DO-FC-8, DO-FC-8-H
8 Channel Digital Output,
Form-C
E9 se.com/ecostruxure-building
Automation Server Family of Modules
Power
Environmental
UI-8/AO-4, UI-8/AO-4-H 0 °C to 50 °C (32 °F to 122 °F) 0 °C to 50 °C (32 °F to 122 °F) 0 °C to 50 °C (32 °F to 122 °F)
8 Channel Universal Inputs Operating Range
0-95% RH (non-condensing) 0-95% RH (non-condensing) 0-95% RH (non-condensing)
with 4 Analog Outputs
External Features
Eco Friendly ABS/PC, UL94 5VB, Eco Friendly ABS/PC, UL94 5VB, Eco Friendly ABS/PC, UL94 5VB,
Enclosure rating
IP 20 (<12.5 mm protection) IP 20 (<12.5 mm protection) IP 20 (<12.5 mm protection)
HOA Switches (DO/AO) Available on -H model Available on -H model Available on -H model
Service Port No No No
Terminals
External Enclosure/Mounting
Mounting DIN-rail or wall mount DIN-rail or wall mount DIN-rail or wall mount
Certifications
FCC 47 CFR § 15, Class B (Emission) 47 CFR § 15, Class B (Emission) 47 CFR § 15, Class B (Emission)
UI-8/DO-FC-4, UI-8/DO-FC-4-H
8 Channel Universal Inputs with 4
Channel Digital Outputs, Form-C
RTD-DI-16
Power
Power 24 VDC
Consumption 1.6 W
Environmental
0 °C to 50 °C (32 °F to 122 °F)
Operating Range
0-95% RH (non-condensing)
RTD-DI-16
16 Channel Inputs (RTD and External Features
Digital) Combination Module Eco Friendly ABS/PC, UL94 5VB, IP
Enclosure rating
20 (<12.5 mm protection)
HOA Switches (DO/AO) No
Service Port No
Terminals
External Enclosure/Mounting
Certifications
CE - EU Yes
WEEE - Directive of the European
Yes
Union
RoHS Directive Yes
RCM Yes
E11 se.com/ecostruxure-building
Automation Server Family of Modules
Digital Contact •
Digital Supervised •
Analog Resistance •
Analog Thermistor - 10 k •
Analog Thermistor - 1 k •
Analog Thermistor - 20 k •
Digital Inputs 16
Digital Contact •
Digital Outputs 12 8
Form A, SPST •
Form C, SPDT •
Triac
Analog Outputs 8 8
Voltage - 0-10 V • •
Current - 0-20 mA •
Digital Contact • • • •
Digital Supervised • • •
Analog Resistance • • • •
Analog Thermistor - 10 k • • •
Analog Thermistor - 1 k • • •
Analog Thermistor - 20 k • • •
Digital Inputs
Digital Contact
Digital Outputs 4
Form A, SPST
Form C, SPDT •
Triac
Analog Outputs 4 4
Voltage - 0-10 V • •
Current - 0-20 mA •
E13 se.com/ecostruxure-building
Automation Server Family of Modules
the controller. Spare 0°C to 50°C (32°F to 122°F) 0-95% RH 0°C to 50°C (32°F to 122°F) 0-95% RH
Operating Range
(non-condensing) (non-condensing)
is available. See CPU Internals
accessories section CPU SPEAr320S, ARM926 core SPEAr320S, ARM926 core
on page E16.
Memory 4 GB 4 GB
Battery No No
Real time clock Yes -10 days backup/Super Capacitor Yes -10 days backup/Super Capacitor
External Features
Eco Friendly ABS/PC, UL94 5VB, IP 20 Eco Friendly ABS/PC, UL94 5VB, IP 20
Enclosure rating
(<12.5 mm protection) (<12.5 mm protection)
HOA Switches (DO/AO) N/A N/A
Manual Override of Outputs Yes - On 'H' model Yes - On 'H' model
Digital Status LEDs Yes Yes
Service Port Yes Yes
Terminals
I/O Expansion No No
External Enclosure/Mounting
Mounting DIN-rail or wall mount DIN-rail or wall mount
Certifications
BTL Yes Yes
FCC 47 CFR § 15, Class B (Emission) 47 CFR § 15, Class B (Emission)
Industry Canada (IC) ICES-003 (Emission) ICES-003 (Emission)
UL-916 (Energy Management UL-916 (Energy Management
UL
Equipment) Equipment)
C-UL US Yes Yes
CE - EU Yes Yes
WEEE - Directive of the European Union Yes Yes
RoHS Directive Yes Yes
RCM Yes Yes
8 207 842, 8 271 102, 8 207 842, 8 271 102,
US Patent
7 994 438 7 994 438
*Notes: EcoStruxure Building installations or BMS transitions requiring UL-864 certifications must use the SpaceLogic Server
AS-P-SMK (see page E6).
AS-P and AS-B conform to the BACnet ® Building Controller (B-BC) profile at protocol revision 12 by the BACnet Testing
Laboratories (BTL®). EcoStruxure™ Building Operation v1.9 is the certified firmware revision.
Digital Inputs 4
Digital Contact •
Digital Outputs 4 8
Form A, SPST • 4
Form C, SPDT
PWM • •
Triac 4
Key:
Ua – Universal Type A
Ub – Universal Type B
I – Input
O – Output
E15 se.com/ecostruxure-building
SpaceLogic Edge Server add-on options
Add-on option part numbers are required to activate certain features. SpaceLogic Servers require an embedded license to
activate features. An embedded license is not interchangeable with a Windows license.
* An embedded client license that will be activated on a SpaceLogic Server will always allow for the operation of a WebStation only. In order for
WorkStation to operate it must have access to a Windows license on a PC that is running a Windows OS. Since WorkStation software requires a
Windows operating system, then the license might be installed on the same PC or it might make use of a demo license.
SXWADUSBC10001 USB-C cable, Straight, 2.4m (7.87 ft) - Only for use with Wi-Fi module
Wireless Connectivity
USB-based wireless adapter that enables Zigbee™ wireless connectivity for SpaceLogic Servers and SpaceLogic Controllers.
EcoStruxure Building
TM
Apps,
Analytics
and Services
EcoStruxure Planon
Building Advisor Workplace Insights
IP
IP
IP
IP
Connected
Products
Daisy Chain Topology - Private Daisy Chain Topology - Star Topoology - Hosted under Enterprise Server or Edge/ RSTP Topology (Self healing) - Private Network Hosted under Edge/
Network Hosted directly under Corporate Network hosted under Automation Server (AS-P) Automation Server (AS-P).
Edge/Automation Server (AS-P) Enterprise Server Private network if hosted under an Automation Server 39 RP/MP is supported in an RSTP loop
50 RP/MP in a daisy chain 50 RP/MP in a daisy chain max 200 RP/MP under 1 AS-P. Max 50 RP/MP under 1 AS-B
Building Management
Schneider Electric and Cisco® together have developed, tested and validated this building system
design to provide customers with confidence in knowing that their systems will securely connect to
an end-to-end IP network with a resilient architecture that is easy to manage.
E17 se.com/ecostruxure-building
EcoStruxure
Connected Room Solutions
Create engaging environments with personalized comfort
and increased operational and energy efficiency, which
are essential in today’s connected world. Connected Room
Solutions feature a modular BACnet/IP Controller, the
SpaceLogic Controller RP-C with native web services and
Bluetooth capabilities for control of HVAC, lights and blinds.
Built on a flexible architecture, the RP-C provides a consistent
IP story across the building together with our existing network
and field level controllers. Complementary offers include the
Engage employee mobile app, SpaceLogic Living Space
Sensors, and EcoStruxure eCommission Building Mobile App.
S2 se.com/ecostruxure-building
Connected Room Solutions
All eu.bac certified products are found on the eu.bac web site www.eubaccert.eu
Digital Input Ub Ub Ub Ub
Counter Input Ub Ub Ub Ub
Supervised Input Ub Ub Ub Ub
Resistive Input Ub Ub Ub Ub
Temperature Input Ub Ub Ub Ub
Thermistor Input - 1k Ub Ub Ub Ub
Digital Outputs
Solid-state Relay Output
4 4 4
(MOSFET)
Relay Output (Form A) 3 3 3
SXWRPCCOV10001 RP-C external terminal covers Optional external covers for RP-C HVAC
Wireless Connectivity
USB-based wireless adapter that enables Zigbee™ wireless connectivity for SpaceLogic Servers and Controllers.
SXWZBAUSB10001 ZB-A-USB Zigbee Adapter for the AS-P, AS-B and RP Series controllers
SXWUSBCRA10001 USB-CRA USB adapter plastic mounting cradle and wall plate
SXWUSBCBL10002 USB-CBL-3 Plenum rated USB Extension Cable of Length 3 m (10 ft)
S4 se.com/ecostruxure-building
Connected Room Solutions (continued)
SpaceLogic Sensors
Communicating sensors for SpaceLogic IP Controllers with the EcoStruxure Building Operation user interface.
These sensors use an RJ-45 sensor bus that provides communication and power from the controller. For quick
installation, up to four SpaceLogic sensors may be connected to each IP controller through the RJ-45 sensor
bus using Cat 5/6 cable (22 to 26 AWG). A Bluetooth® adapter is available for commissioning and service. It is
temporarily connected to installed communicating sensors and allows for quick setup and configuration. The
Bluetooth adapter communicates to upload devices (smart phone, laptop, table, etc.) with the Living Space
Sensor EcoStruxure Building Operation app installed via USB or Bluetooth communications. These sensors
support light, blind and scene control when used with Connected Room Solutions.
SpaceLogic Living Space Sensors are modular and ordered in two parts: the sensor base and the cover.
Four SpaceLogic communicating sensor base models are available that can be paired with any SpaceLogic
cover model. CO2, Relative Humidity, and Temperature sensor base options provide an efficient, cost effective
solution for living space air quality and comfort needs. Covers are available with a 61 mm (2.4”) backlit
color touchscreen and a three button non-display version for override and setpoint. Blank covers with no
user interface are also available. All modular cover variants are available with and without passive infrared
occupancy sensors.
Two complete sensor/cover combination model types are available:
• Temperature-only with LCD display. Communicating with three button cover. This is a low cost temperature
sensor with a basic display.
• A two-wire, resistive-only, non-communicating temperature sensor is offered for a low cost conformance part.
This uses an I/O port on the controller.
Combination models come with a sensor base and cover, and are available in White Optimum, Black Optimum
or medium White Matte finishes. Combination units have the same form factor as the modular sensor bases
and covers of the same housing type. (Combination units will not work with other covers.) Sensors measure
the levels of CO2 (if equipped), RH (if equipped), and temperature of air in a living space application. The
CO2 sensor operates within accuracy specifications for an interval of two years and can be field calibrated.
Find more information and part numbers on The EcoXpert Exchange: https://ecobuilding.schneider-electric.
com/field-devices/sensors
Physical
Dimensions 155 W x 44 H x 30 D mm (6.1 W x 1.7 H x 1.2 D in.) 155 W x 44 H x 30 D mm (6.1 W x 1.7 H x 1.2 D in.)
Power
Nominal voltage 220 to 240 VAC 220 to 240 VAC
Environmental
Operating Range -20 °C to +50 °C (-4 °F to +122 °F) -20 °C to +50 °C (-4 °F to +122 °F)
Humidity 85 % RH 85 % RH
Material
Plastic flame rating UL94 V-0 UL94 V-0
IP rating IP 20 IP 20
Connectors No No
Inputs
Digital Inputs No No
Outputs
Type of Output 0-10V DALI
Number of outputs 1 1
Power Distribution Yes Yes
Certifications
FCC No No
UL No No
C UL No No
CE Yes Yes
WEEE- Directive of EU Yes Yes
RoHS Yes Yes
RCM No No
S6 se.com/ecostruxure-building
Connected Room Solutions (continued)
Material
Plastic flame
UL94 V-0 UL94 V-0 UL94 V-0 UL94 V-0
rating
IP rating IP 20 IP 20 IP 20 IP 20
Connectors Yes Yes Yes Yes
Inputs
Digital Inputs 4 4 4 4
Outputs
Type of Output DALI 0-10V 230V 24V
RP-C Controller Light Module - 0-10V
Number of
4 4 4 2
outputs
Power
Yes Yes Yes Yes
Distribution
Certifications
FCC Yes Yes Yes Yes
UL No No No No
C UL No No No No
CE Yes Yes Yes Yes
WEEE-
Yes Yes Yes Yes
Directive of EU
RoHS Yes Yes Yes Yes
RCM Yes Yes Yes Yes
RP-C-EXT-BL-SMI-4-
Product RP-C-EXT-MS-BLE
HV-PD
RP-C-EXT-BL-SMI-2-LV-PD RP-C-EXT-REL-4 CRS-HH-REL-10
Communication
Communication
Room Bus Room Bus Room Bus Room Bus Room Bus
Interface
Physical
97.5 mm (3.84 in.) 198 W x 110 H x 64 D mm 198 W x 110 H x 64 D mm 198 W x 110 H x 64 D mm 198 W x 110H x 64 D mm
Dimensions
overall diameter (7.8 W x 4.3 H x 2.5 D in.) (7.8 W x 4.3 H x 2.5 D in.) (7.8 W x 4.3 H x 2.5 D in.) (7.8 W x 4.3 H x 2.5 D in.)
weight 0.083 kg (0.183 lb) 0.405 kg (0.893 lb) 0.439 kg (0.968 lb) 0.378 kg (0.833 lb) 0.476 kg (1.050 lb)
Power
Nominal
24 VDC 230VAC 230VAC 100 to 277 VAC 24 VDC
voltage
Room bus
power 0.3W 0.3W 0.3W 0.3W 0.3W
consumption
Environmental
Operating
0 to 50 °C (32 to 122 °F) 0 to 50 °C (32 to 122 °F) 0 to 40 °C (32 to 104 °F) 0 to 50 °C (32 to 122 °F) 0 to 50 ˚C (32 to 122 ˚F)
Range
Humidity 20 to 90 % RH 20 to 90 % RH 20 to 90 % RH 20 to 90 % RH 20 to 90 % RH
Material
Plastic flame
UL94 V-0 UL94 V-0 UL94 V-0 UL94 V-0 UL94 V-0
rating
IP rating IP 20 IP 20 IP 20 IP 20 IP 20
10 x 2-pin plus 2 x 9-pin
screw terminal blocks
Connectors No Yes Yes Yes
for relay outputs and
digital inputs respectively
Inputs
Digital Inputs no 4 4 4 12
Outputs
Type of
no 230V SMI 24V SMI Relays Relays
Output
Number of
0 4 2 4 10
outputs
Power
no Yes Yes Yes No
Distribution
Certifications
S8 se.com/ecostruxure-building
Connected Room Solutions (continued)
Power
Nominal voltage 100 to 277 VAC 100 to 277 VAC 24VDC 230VAC 3.0 VDC
Power
0.3W 0.3W <0.24W 0.5W n/a
Consumption
Environmental
-5 °C to +45 °C (23 °F to
Operating Range 0 to 50 °C (32 to 122 °F) 0 to 50 °C (32 to 122 °F) -10 to 50 °C (14 to 122 °F) 0 to 40 °C (32 to 104 °F)
+113 °F)
Humidity 20 to 90 % RH 20 to 90 % RH 5 to 93 % RH n/a 20 to 90 % RH
Material
Plastic flame
UL94 V-0 UL94 V-0 UL94 V-0 n/a n/a
rating
IP rating IP 20 IP 20 IP 20 IP 20 IP 30
Connectors Yes Yes No No No
Inputs
Digital Inputs 4 4 No No No
Outputs
Type of Output 0-10V DALI KNX 230V n/a
Number of
4 4 1 1 0
outputs
Power
no no no Yes No
Distribution
Certifications
FCC Yes Yes no no Yes
UL Yes Yes no no no
C UL Yes Yes no no no
CE Yes Yes Yes Yes Yes
WEEE- Directive
Yes Yes Yes Yes Yes
of EU
RoHS Yes Yes Yes Yes Yes
RCM Yes Yes No No Yes
S10 se.com/ecostruxure-building
SpaceLogic Controllers
SpaceLogic Controllers MP-C and MP-V conform to the BACnet ® Advanced Application Controller (B-AAC) profile at protocol revision 12 by
the BACnet Testing Laboratories (BTL®). EcoStruxure solution installations or BMS transitions requiring UL-864 certifications must use the
SpaceLogic Controller MP-C-xxx-SMK (listed above).
MP-V-7A MP-V-9A
Part Number SXWMPV7AX10001 SXWMPV9AX10001
Other Models MP-V-7A-SMK MP-V-9A-SMK
Part Number
SXWMPV7AX1S001 SXWMPV9AX1S001
(UL-864 Smoke Control)
Communications
Communication Interface BACnet/IP, BTL B-AAC BACnet/IP, BTL B-AAC
Software
Programability Function Block/Script Programmable Function Block/Script Programmable
Physical
Dimensions 161 W x 198 H x 63 D mm (6.3 W x 7.8 H x 2.5 D in.) 161 W x 198 H x 63 D mm (6.3 W x 7.8 H x 2.5 D in.)
Weight (including
1.13 kg (2.5 lb) 1.13 kg (2.5 lb)
baseplate)
Power
Note: Screw terminals
Power 24 VAC 24 VAC
are prepopulated.
Spare is available. Consumption 21 VA 22 VA
SpaceLogic Controllers MP-C and MP-V conform to the BACnet ® Advanced Application Controller (B-AAC) profile at protocol revision 12 by
the BACnet Testing Laboratories (BTL®). EcoStruxure solution installations or BMS transitions requiring UL-864 certifications must use the
SpaceLogic Controller MP-V-xx-SMK (listed above).
S12 se.com/ecostruxure-building
SpaceLogic IP Controllers (continued)
Automation Server Family of Modules
SpaceLogic IP Controllers MP-C – Inputs and Outputs
MP-C-15A MP-C-18A MP-C-18B MP-C-24A MP-C-36A
Part Number SXWMPC15A10001 SXWMPC18A10001 SXWMPC18B10001 SXWMPC24A10001 SXWMPC36A10001
Other Models MP-C-15A-SMK MP-C-18A-SMK MP-C-18B-SMK MP-C-24A-SMK MP-C-36A-SMK
Part Number
SXWMPC15A1S001 SXWMPC18A1S001 SXWMPC18B1S001 SXWMPC24A1S001 SXWMPC36A1S001
(UL-864 Smoke Control)
Universal Inputs/Outputs 8-Ub 10-Ub 10-Ub 16-Ub, 4Uc 20-Ub, 8Uc
Digital Input Ub Ub Ub Ub/Uc Ub/Uc
Counter Input Ub Ub Ub Ub/Uc Ub/Uc
Supervised Input Ub Ub Ub Ub/Uc Ub/Uc
Voltage Input - (0-10V) Ub Ub Ub Ub/Uc Ub/Uc
Resistive Input Ub Ub Ub Ub/Uc Ub/Uc
Thermistor Input - 10k Ub Ub Ub Ub/Uc Ub/Uc
Thermistor Input - 1.8k Ub Ub Ub Ub/Uc Ub/Uc
Thermistor Input - 1k Ub Ub Ub Ub/Uc Ub/Uc
Thermistor Input - 20k Ub Ub Ub Ub/Uc Ub/Uc
Thermistor Input - 2.2k Ub Ub Ub Ub/Uc Ub/Uc
RTD Temp Input - Pt100
RTD Temp Input - Pt1000 Ub Ub Ub Ub/Uc Ub/Uc
RTD Temp Input - Ni1000 Ub Ub Ub Ub/Uc Ub/Uc
RTD Temp Input - LG-Ni1000 Ub Ub Ub Ub/Uc Ub/Uc
Voltage Output (0-10V) Ub Ub Ub Ub/Uc Ub/Uc
Current Output (0-20mA) Uc Uc
Digital Outputs 7 8 8 4 8
Form A Relay, SPST 3 4 8
Form C Relay, SPDT
Triac 6 4 8
Form A High Power Relay, SPST 1 1
SpaceLogic Controllers - IP-IO Series is pending certification of the BACnet Application Specific Controller (B-ASC) profile at protocol revision 14
by the BACnet Testing Laboratories (BTL®).
S14 se.com/ecostruxure-building
SpaceLogic IP Controllers (continued)
Automation Server Family of Modules
SpaceLogic IP Controllers IP-IO – Inputs and Outputs
DIN-RAIL-CLIP SXWMPVCON10001
*Touch Display supports user access to the following settings: HVAC mode (Cooling/Heating/Auto), Setpoint adjust, Override and Fan (On/Off/Auto)
S16 se.com/ecostruxure-building
BACnet controllers
B2 se.com/ecostruxure-building
b3 Series
b3 Series Controllers
B4 se.com/ecostruxure-building
b3 Series
B6 se.com/ecostruxure-building
b3 Series
b3920,
Part Number
b3920-D
Communications
Protocol BACnet Open Protocol
Communication Interface MS/TP, 9600 -76,800 bit/s
Software
Programmability Script Programmable
Physical
270.8 W x 330.2 H x 69.0 D mm
Dimensions
(10.66 W x 13.00 H x 2.72 D in.)
Weight (including baseplate) 1.58 kg (3.50 lb.)
Power
115/230 VAC +10% -15%, 50/60
Power
Hz
45 VA (3 A fuse overload MOV
Consumption
protected)
b3887-L-115-C, b3887-L-
230-C Terminal Controllers Environmental
0 °C to 49 °C (32 °F to 120 °F) 10-
Operating Range
95% RH (non-condensing)
CPU Internals
CPU Motorola Coldfire 32-bit, 10 Mhz
Memory 2 MB flash, 1 MB SRAM
Replaceable, non-rechargeable
lithium battery. Provides 5 years
Battery
typical accumulated power failure
backup of RAM memory.
Real time clock Synchronized via BACnet service
External Features
UL94 5 V (Plenum rated), IP 10
Enclosure rating
(<50 mm protection)
HOA Switches (DO/AO) Yes - (8/8)
Digital Status LEDs Yes
Display Option - xP Display
Intelligent Sensors Smart Sensor
Service Port b3
Terminals
I/O Terminals Two-piece terminal
b3920
I/O Expansion Up to 2 xP expansion modules
System Controller
External Enclosure/Mounting
Open class (separate enclosure
Enclosure class
required)
Mounting Wall mount
Certifications
BTL: BACnet Advanced
BTL Application Controllers (B-AAC)
with trending
FCC 47 CFR § 15, Class A (Emission)
Industry Canada (IC) ICES-003 (Emission)
UL-916 (Energy Management
Equipment), Optional UL-
UL
864 (Smoke Control System
Equipment) UUKL
C-UL US Yes
CE - EU Yes
WEEE - Directive of the
Yes
European Union
RoHS Directive Yes
RCM Yes
B8 se.com/ecostruxure-building
b3 Series
Communications
Physical
180 W x 82 H x 41 D mm 180 W x 82 H x 41 D mm
xPDI8 Dimensions
(7.10 W x 3.21 H x 1.60 D in.) (7.10 W x 3.21 H x 1.60 D in.)
8 Channel Digital Output
Expansion Module Weight (including baseplate) 0.22 kg (0.48 lb.) 0.22 kg (0.48 lb.)
Power
From xP bus with 400 mA power From xP bus with 400 mA power
Power
supply supply
Consumption 25 mA 50 mA
Environmental
External Features
Terminals
External Enclosure/Mounting
Certifications
BTL No No
Communications
Physical
Power
From xP bus with 400 mA From xP bus with 400 mA From xP bus with 400 mA
Power
power supply power supply power supply
Environmental
External Features
Terminals
Certifications
BTL No No No
B10 se.com/ecostruxure-building
b3 Series
Digital Contact • • • • • •
Digital Supervised • • • • • •
Analog Resistance
Analog Thermistor - 10 k • • • • • •
Analog Thermistor - 1 k
Analog Inputs
Voltage - 0-5 V
Voltage - 0-10 V
Velocity Pressure
Analog Thermistor - 10 k
Analog Thermistor - 1 k
Digital Outputs 8 4 8 4
Form A, SPST
Form C, SPDT • • • •
Triac
Analog Outputs 4 4
Voltage - 0-10 V • •
Current - 0-20 mA •
Damper Outputs
Form K, Triac
Voltage
Intelligent Sensors 1 1 1 1 1 1
Universal Inputs 4 4 4 4 4
Digital Contact • • • • •
Digital Supervised • • • • •
Analog Resistance
Analog Thermistor - 10 k • • • • •
Analog Thermistor - 1 k
Analog Inputs 1 2 1
Voltage - 0-5 V
Voltage - 0-10 V
Analog Thermistor - 10 k
Analog Thermistor - 1 k
Digital Outputs 4 4 4 3 5
Form C, SPDT
Analog Outputs 2 2
Voltage - 0-10 V • •
Current - 0-20 mA
Damper Outputs 1
Form K, Triac
Voltage internal
Intelligent Sensors 1 1 1 1 1
B12 se.com/ecostruxure-building
b3 Series
b3920,
Part Number b3885-V b3887
b3920-D
Universal Inputs 2 3 16
Digital Contact • • •
Digital Supervised • • •
Analog Resistance
Analog Thermistor - 10 k • • •
Analog Thermistor - 1 k
Analog Inputs 1
Voltage - 0-5 V
Voltage - 0-10 V
Analog Thermistor - 10 k
Analog Thermistor - 1 k
Digital Outputs 2 5 8
Form C, SPDT •
Triac • 4 channel
Analog Outputs 8
Voltage - 0-10 V •
Current - 0-20 mA •
Damper Outputs 1
Voltage
Intelligent Sensors 1 1 1
Digital Contact •
Digital Supervised •
Analog Resistance
Analog Thermistor - 10 k •
Analog Thermistor - 1 k
Digital Inputs 8
Digital Contact •
Digital Outputs 4
Form A, SPST
Form C, SPDT •
Triac
Analog Outputs 2 4
Voltage - 0-10 V • •
Current - 0-20 mA • •
B14 se.com/ecostruxure-building
MNB Series
Now native in EcoStruxure solution, the MNB series of MicroNet
controllers are designed in accordance with BACnet® standards.
When programmed or loaded with a pre-engineered application, these
controllers provide control for packaged rooftops, heat pumps, fan coils,
unit ventilators, and similar applications.
B16 se.com/ecostruxure-building
MNB Series
B18 se.com/ecostruxure-building
LonWorks Controllers
L2 se.com/ecostruxure-building
Xenta Series
102-ES 102-AX
Software
Physical
127 W x 126 H x 50 D mm 159 W x 197 H x 63 D mm
Dimensions
Xenta 102-ES (5.0 W x 4.9 H x 1.9 D in.) (6.25 W x 7.75 H x 2.50 D in.)
VAV Zone Controller
Weight 0.4 kg (0.88 lb.) 1.04 kg (2.3 lb.)
Power
Enclosure rating UL94 5VB, IP 30 (<2.5 mm protection) NEMA-1, UL94 5VB, IP 10 (<50 mm protection)
Terminals
I/O Expansion No No
External Enclosure/Mounting
Certifications
C-UL US Yes No
CE - EU Yes Yes
WEEE - Directive of the European
Yes Yes
Union
RoHS Directive Yes Yes
122-FC/24,
122-FC/230
007307110,
Part Number
007307120
Communications
Software
Physical
Xenta 122-FC/24, 122-FC/230
Flexible Zone Controllers 112 W x 110 H x 50 D mm
Dimensions
(4.37 W x 4.29 H x 2.00 D in.)
Weight 0.3 kg (0.66 lb.) / 0.6 kg (1.3 lb)
Power
24 VAC ±20%, 50/60 Hz
Power
(230 V AC ±10%, 50–60 Hz)
Controller and OP 4 VA, including digital outputs: FC/24: 84 VA,
Consumption
FC/230: 20 VA
Environmental
0 °C to 50 °C (32 °F to 122 °F)
Operating Range
0-90% RH (non-condensing)
External Features
Terminals
I/O Expansion No
External Enclosure/Mounting
Certifications
C-UL US Yes
CE - EU Yes
WEEE - Directive of the European
Yes
Union
RoHS Directive Yes
RCM Yes
L4 se.com/ecostruxure-building
Xenta Series
411, 421A,
412 422A
007302011, 007302450,
Part Number
007302031 007302460
Communications
Physical
90 W x 110 H x 75 D mm 90 W x 110 H x 75 D mm
Dimensions
(3.55 W x 4.33 H x 3.1 D in.) (3.55 W x 4.33 H x 3.1 D in.)
Weight (including baseplate) 0.595 kg (1.41 lb.) 0.295 kg (0.65 lb.)
Xenta 411/412
10 Channel Digital Input Power
Modules Power 24 VAC ±20%, 50/60 Hz 24 VAC ±20%, 50/60 Hz
Consumption 2 VA 4 W, 8 VA transformer
Environmental
0 °C to 50 °C (32 °F to 122 °F) 0 °C to 50 °C (32 °F to 122 °F)
Operating Range
0-90% RH (non-condensing) 0-90% RH (non-condensing)
External Features
UL94 V-0, IP 20 UL94 V-0, IP 20
Enclosure rating
(<12.5 mm protection) (<12.5 mm protection)
HOA Switches (DO/AO) Available on 412 model Available on 422A model
Terminals
External Enclosure/Mounting
Enclosed class (no separate Open class (separate enclosure
Enclosure class
enclosure required) required)
Mounting DIN-rail or wall mount DIN-rail or wall mount
Certifications
LonMark® certified: Digital Input
LonMark No
20543, Analog Input 0520
FCC 47 CFR § 15, Class A (Emission) 47 CFR § 15, Class B (Emission)
UL-916 (Energy Management
UL-916 (Energy Management
UL Equipment), UL 3111-1 (Electrical
Equipment)
Measuring and Test Equipment)
Xenta 421A/422A
4 Channel Universal Input/5 C-UL US Yes Yes
Channel Digital Output
Modules CE - EU Yes Yes
WEEE - Directive of the European
Yes Yes
Union
RoHS Directive Yes Yes
451A, 491,
471
452A 492
007302850, 007303010,
Part Number 007302910
007302860 007303030
Communications
Protocol LonTalk communication protocol LonTalk communication protocol LonTalk communication protocol
Physical
90 W x 110 H x 75 D mm 90 W x 110 H x 75 D mm 90 W x 110 H x 75 D mm
Dimensions
(3.55 W x 4.33 H x 3.1 D in.) (3.55 W x 4.33 H x 3.1 D in.) (3.55 W x 4.33 H x 3.1 D in.)
Weight (including baseplate) 0.295 kg (0.65 lb.) 0.495 kg (1.09 lb.) 0.495 kg (1.09 lb.)
Environmental
0 °C to 50 °C (32 °F to 122 °F) 0 °C to 50 °C (32 °F to 122 °F) 0 °C to 50 °C (32 °F to 122 °F)
Operating Range
0-90% RH (non-condensing) 0-90% RH (non-condensing) 0-90% RH (non-condensing)
External Features
UL94 V-0, IP 20 UL94 V-0, IP 20 UL94 V-0, IP 20
Enclosure rating
(<12.5 mm protection) (<12.5 mm protection) (<12.5 mm protection)
HOA Switches (DO/AO) Available on 452A model No Available on 492 model
Terminals
External Enclosure/Mounting
Enclosed class (no separate Enclosed class (no separate Enclosed class (no separate
Enclosure class
enclosure required) enclosure required) enclosure required)
Mounting DIN-rail or wall mount DIN-rail or wall mount DIN-rail or wall mount
Certifications
LonMark certified: Analog Input
Xenta 471 LonMark No No
0520, Analog Output 0521
8 Channel Universal Input
Module 47 CFR § 15, Class B 47 CFR § 15, Class A 47 CFR § 15, Class A
FCC
(Emission) (Emission) (Emission)
UL-916 (Energy Management UL-916 (Energy Management
UL-916 (Energy Management
UL Equipment), UL 3111-1 (Electrical Equipment), UL 3111-1 (Electrical
Equipment)
Measuring and Test Equipment) Measuring and Test Equipment)
C-UL US Yes Yes Yes
Xenta 491/492
8 Channel Analog Output
Modules
L6 se.com/ecostruxure-building
Xenta Series
Universal Inputs 4 4
Digital Contact • •
Digital Supervised
Analog Resistance
Analog Thermistor - 10 k •
Analog Thermistor - 1 k
Digital Inputs 2 3
Digital Contact • •
Analog Inputs 3 5 •
Resistor, 10 k •
Analog Thermistor - 10 k
Analog Thermistor - 1 k
Digital Outputs 6 3 8
Form A, SPST 4
Form C, SPDT
Triac • • 4
Analog Outputs 1 3
Voltage - 0-10 V • •
Current - 0-20 mA
Damper Outputs 1
Voltage
Intelligent Sensors 1 1 1
STR (Xenta) • • •
Universal Inputs 4 8 8
Digital Contact • •
Digital Supervised
Analog Resistance • •
Analog Thermistor - 10 k • •
Analog Thermistor - 1 k
Digital Inputs 10
Digital Contact •
Digital Outputs 5
Form A, SPST •
Form C, SPDT
Triac
Analog Outputs 2 8
Voltage - 0-10 V • •
Current - 0-20 mA
Note: 421A, 422A, 451A, and 452A can also be used as distributed I/Os under an automation server.
L8 se.com/ecostruxure-building
MNL Series
The MNL series of controllers are designed in accordance with
LonMark® guidelines. When programmed or loaded with a pre-
engineered application, these controllers provide control for
packaged rooftops, heat pumps, fan coils, unit ventilators,
and similar applications.
L10 se.com/ecostruxure-building
MNL Series
RoHS Directive No No No
RoHS Directive No No No
L12 se.com/ecostruxure-building
MNL Series
MNL-V3RV3
C-UL US Yes
CE - EU Yes
WEEE - Directive of the
No
European Union
RoHS Directive No
RCM Yes
Universal Inputs 1 2 3 3 3
Digital Contact • • • • •
Digital Supervised
Analog Resistance • • • • •
Analog Thermistor - 10 k
Analog Thermistor - 1 k • • • • •
Digital Inputs 1 1
Digital Contact • •
Analog Inputs
Voltage - 0-5 V
Voltage - 0-10 V
Velocity Pressure
Analog Thermistor - 10 k
Analog Thermistor - 1 k
Digital Outputs 3 4 5 7 2
Form C, SPDT
Analog Outputs 2
Voltage - 0-10 V
Current - 0-20 mA •
Damper Outputs
Form K, Triac
Voltage
Intelligent Sensors 1 1 1 1 1
L14 se.com/ecostruxure-building
MNL Series
Universal Inputs 3 8 1 1 1
Digital Contact • • • • •
Digital Supervised
Analog Resistance • • • • •
Analog Thermistor - 10 k
Analog Thermistor - 1 k • • • • •
Digital Inputs 2 5 1 1 1
Digital Contact • • • • •
Analog Inputs 1 1 1
Voltage - 0-5 V
Voltage - 0-10 V
Analog Thermistor - 10 k
Analog Thermistor - 1 k
Digital Outputs 6 8 3 5
Form C, SPDT •
Triac 2 channel
Analog Outputs 2 4 1 1
Voltage - 0-10 V
Current - 0-20 mA • • • •
Damper Outputs 1 1
Voltage
Intelligent Sensors 1 1 1 1 1
A1 A1
Schneiderse.com/ecostruxure-building
Electric EcoStruxure Solution
Modernize your BMS with EcoStruxure Building
Future-ready your customers’ buildings. Minimize the risk, downtime and cost of modernizing
a BMS, and take advantage of new features and benefits, with EcoStruxure Building transition
tools and services.
Customer benefits:
• Update and make your buildings IoT-ready while preserving Tools are available to support transition
existing site investments from any other building management
• Leverage the benefits of Schneider Electric’s preeminent building systems:
management system, including: a new user experience, new
technology and new feature sets TAC I/A Series™ – transitioniaseries
System integrator benefits: TAC I/NET™ – transitioninet
• Protect valued customer relationships with best-in-class solutions TAC Vista™ – transitionvista
and conversion tools to ease customer site transitions Andover Continuum™ – transitioncontinuum
• Save time and labor costs by reusing components (controllers, NETWORK 8000™ – transitionnw8000
sensors, wiring) and system design and configuration
Use the keywords to find all assets on The Exchnage.
Mutual benefits:
• Choose from multiple modernization path options to meet specific
needs, schedules and budgets
• Enable access to connected offers; facilitate predictive and
preventative cloud-enabled connected services
Managed
Plus Prime Ultra
Services
Alarm Monitoring
Monitoring
Condition Monitoring
Cloud Backup
Maintenance
Preventive Checks
A3 se.com/ecostruxure-building
Smart starts at the foundation of the BMS
If connected products are not running at optimal efficiency, neither is the higher level BMS.
Please find all sales, marketing and technical documentation on Connected Devices on The Exchange:
https://ecobuilding.schneider-electric.com/field-devices#tab/documents
A5 se.com/ecostruxure-building
EcoStruxure Security Expert
TM
Available for small, mid and large enterprise environments, this solution provides extensive data handling capabilities
that can store millions of credentials in off-line memory; while functioning independently and maintaining a unique
database. Information is encrypted throughout the architecture, and complies with global agency listings. EcoStruxure
Security Expert will also easily extend to multiple sites and future business expansions.
Security Expert
Building Security & Building
Communication Management
Infrastructure System
Please find all sales, marketing and technical documentation for EcoStruxure Security Expert on
The Exchange:
https://ecobuilding.schneider-electric.com/ecostruxure-security-expert#tab/documents
SE8000 Series
With rich, customizable features, the SE8000 Series enables significant energy
savings with accurate temperature control in any space. The SE8000 room
controllers can be easily integrated into most BMSs as well as to communicate
wirelessly for ease of installation, flexibility and scalability.
SE7000 Series
The SE7000 digital controllers offer easy-to-install, thermostat-like functionality
that sense occupancy and adjust set-point or fan speed control. Easily
integrate into most BMSs. The wireless versions of the SE7000 provide a simple
yet powerful solution which targets retrofit installations where running new communication wiring
is prohibitive.
Please find all sales, marketing and technical documentation for Room Controllers on
The Exchange:
https://ecobuilding.schneider-electric.com/room-controllers#tab/documents
A7 se.com/ecostruxure-building
Quick Links
White Papers
http://www.schneider-electric.com/ww/en/
download/1555889-WhitePaperLanding
Schneider Electric Americas Schneider Electric EMEA Schneider Electric Hong Kong Ltd
December 2021