GENERAL SPECIFICATION
Packaged Energy Recovery units with Integrated Heating and Cooling shall be Spinnaker Industries Inc. Model Series
RERVHC . Units shall be factory assembled, wired and tested prior to shipment. Units shall bear a QPS special
inspection label. Field wiring shall require a single point power connection and a numbered terminal strip for low voltage
remote wiring connections.
UNIT CONSTRUCTION
Unit construction to suit outdoor applications. All exterior cabinet screws shall be Clima-seal with bonded washer. Unit
casing shall be minimum 18 gauge satin coat steel with weather resistant powder coat finish ( Sky Grey ). Units with
bear metal or an air dried paint finish will not be accepted. All seams to be sealed with weather resistant caulking. All
interior cabinet surfaces shall be lined with 1” thick, 3 lbs/cu ft density foil faced insulation, with seems foil taped. Access
doors and center partitions to be lined with ¼” thick foil faced polyethylene bubble insulation, with seams foil taped. The
floor shall be double skinned to protect the 2” thick, minimum 1.5 lbs/cu ft density insulation. The base shall be
constructed with heavy gauge galvanized steel with integral supports. Perimeter base frame designed to be such that it
overhangs when mounted on a roof curb. Access doors shall be double wall constructed internally insulated with 1” thick
insulation. A minimum of 2 latch and hinge assemblies shall be provide for each door and shall be rated for ambient
temperatures of.–40 deg. F. Each access door shall be provided with a continuous dual durometer extruded automotive
style flexible seal rated to –40 deg. F. Units with lift off access doors will not be accepted.
The wheel media shall be constructed of a corrugated synthetic fiber-based substrate impregnated with a non-migrating
water selective 4A molecular sieve desiccant uniformly and permanently dispersed throughout the matrix structure. The
wheel media shall be spirally wound to form fluted honeycomb geometry so as to eliminate internal wheel bypass.
Wheel layers that can be separated or spread apart by airflow are unacceptable due to the possibility of channeling and
performance degradation. Face flatness of the wheel shall be maximized (+/- 0.032 inches) in order to minimize wear on
inner seal surfaces and minimize cross leakage. The wheel shall be complete with a purge section, minimizing cross
over of return air into supply air, with a non-contact bulb seal. Wheels with large pore size desiccants like silica gel, that
are coated, bonded, or synthesized onto the media or without a purge section will not be accepted. The wheel shall
consist of evenly spaced galvanized steel spokes, a galvanized steel outer band, and an aluminum center hub.
The standard drive system shall consist of a standard motor, fixed pulley, and link type drive belt constructed from a
high performance polyurethane elastomer reinforced with multiple plies of polyester fabric. The drive pulley and belt
shall drive the wheel from inside the assembly casing. Wheels with drive pulleys and belts that are exposed will not be
accepted. Single phase drive motors shall have integral automatic reset thermal overload protection. Three phase drive
motors shall have a manual reset thermal overload mounted in the unit control enclosure.
Wheel media shall be in accordance with NFPA, and be UL tested and UL recognized as a component for heating and
heating-cooling appliance accessories. Energy recovery wheels shall be rigorously performance tested using the
ASHRAE 84-1991 and ARI 1060 standard method of testing. Recovery wheels shall be ARI certified and must bear the
ARI certification stamp.
FANS
Supply and exhaust fans shall be forward curved double width double inlet with ball bearings. Fan drive shaft shall be
polished with keyways for drive pulley mounting. Unit fans with machined flats on fan shafts for drive pulley mounting will
not be accepted. Fans shall have ball bearings suitable for operation in ambient temperatures of –65 to 250 deg. F with
a minimum L10 life in excess of 100,000 hours at maximum cataloged operating speeds. Fan bearings shall be
permanently lubricated and sealed, mounted in resilient neoprene rings. Fan housings shall have extruded holes for
base side mounting. Fans in units with air flow capacity greater than 2500 CFM shall have welded steel angle frames.
Fans in units with air flow capacity greater than 5000 CFM shall have welded steel angle frames with T bar supports
with cast iron pillow block bearings with grease nipples. Fan motors shall be rated continuous duty, ball bearing
construction, and have class F insulation. Variable pitch v-belt drives, of cast iron construction and adjustable motor
mounts to be provided. Units with fans, motors, and drives that do not meet the above criteria will not be accepted.
FILTERS
The supply entering and exhaust entering sides of the recovery wheel shall be complete with 2" deep MERV 8 pleated
filters. Units without supply and exhaust filters will not be accepted.
Unit controls shall include: fan motor / compressor fuses, contactors, and manual reset thermal overloads, energy
recovery wheel drive motor contactor, control transformer(s) with primary and secondary fusing. Unit wiring shall be
color coded with a numbered terminal strip for low voltage wiring and field connections. Unit shall have single point
power input terminals. Units without separate motor fusing and contactors will not be accepted
ACCEPTANCE
Verify prior to bidding that the units meet the specified construction, and scheduled performance and electrical
characteristics. Units that do not meet the specified construction, accessories, or scheduled performance and electrical
characteristics will not be accepted.
ADDITIONAL ACCESSORIES
ROOF CURBS
Roof curbs shall of knock down constructed with minimum 18 gauge galvanized steel with perimeter wood nailer and
patented Cliplock corner clips to facilitate field assembly without the use of tools. Adhesive backed foam gasket seal
shall be provided loose for field installation to act as a seal between the unit and the roof curb. Bolt together roof curbs
will not be accepted.
OTHER OPTIONS :
D/X cooling system with modulating hot gas by pass for capacity control (410A),internally piped , wired and tested.
Chilled water coils
Hot Water / Steam / Glycol heating coils or Electric heat with SCR control
Modulating Natural gas indirect fired heating with 409 or 304 stainless steel heat exchangers
Desiccant D/X Dehumidification with re heat
1” – 1.5” – 2” thick foam insulation ( R values of 6.2 to 12.4 )
22 gauge inner cabinet liner
Non-fused disconnect switch
Dirty filter pressure differential switches
Recovery wheel rotation sensor
Digital CFM monitor ( read only ) in CFM
Frost control strategies : Exhaust only
Recirculation
Electric pre heat
VFD
EBTRON OAFM ( outdoor air flow monitor ) with ALRT remote audible alarm
Direct drive plenum fans with VFD
4"-6"-12" MERV13 , bag filters or HEPA filters
VFD for supply and exhaust fans
Internal spring Isolators
Dirty filter pressure switches
Energy recovery wheel rotation sensor
Internal spring Isolators
Heat exchanger options : Enthalpy fixed plate
Heat Pipe
150,200
RERVHC-3 3000 ECW 424 94,900
ӿ Above Cooling & Heating capacities are based on following conditions. Contact factory for custom design condition.
Cooling: OAT: 93/79 °F, SAT: 55/54 °F. RAT: 72/54.2 °F
Evaporator T: 45 °F, Condensing T: 120 °F, Liq T: 105, Eva./Comp. Superheat: 20 °F, Subcooling: 15 °F
Heating: OAT: -13/-12 °F, SAT: 80 °F. RAT: 72/54.2 °F
Page 4 of 4 RERVHC REV 0
RERVHC MODEL SERIES
PACKAGED ENERGY RECOVERY
VENTILATOR WITH INTEGRATED
HEATING AND COOLING
A
36
36
20 C
D
RERVHC
APR 25/14. Rev2, 2023-09-11 1171 Gorham Road, Newmarket, ON L3Y 8Y2
Tel: (905) 830-5550 Fax: (905) 830-5507
SPINNAKER RESERVES THE RIGHT TO CHANGE ANY OF THE INFORMATION HEREIN WITHOUT NOTICE.
4846 Jennings Lane, Louisville, Kentucky, USA 40218
Tel: 1-800-932-6210 Fax: 1-800-903-7294
SERVICE CLEARANCES FOR RERVHC
MODEL SERIES UNITS
SERVICE CLEARANCE REQUIREMENTS:-
THE MINIMUM CLEARANCE SHOWN IN FIG.1 MUST BE MAINTAINED FOR
ACCESS AND REMOVAL OF INTERNAL COMPONENTS.
RERVHC-1 A=36" B=37" C=30" RERVHC-9 A=86" B=48" C=32"
RERVHC-2 A=50" B=37" C=30" RERVHC-10A=86" B=48" C=32"
RERVHC-3 A=62" B=48" C=32" RERVHC-11A=86" B=48" C=32"
RERVHC-4 A=62" B=48" C=32" RERVHC-12A=102" B=60" C=48"
RERVHC-5 A=62" B=48" C=32" RERVHC-13A=102" B=60" C=48"
RERVHC-6 A=80" B=48" C=32"
RERVHC-7 A=80" B=48" C=32"
RERVHC-8 A=80" B=48" C=32"
THE FRESH AIR INLET SHOULD BE AWAY FROM SOURCES OF CONTAMINANTS
SUCH AS DISCHARGE AIR FROM OTHER VENTILATION UNITS.
SA FA
RERVHC
(PLAN VIEW)
RA
36" EA B
C
SPINNAKER RESERVES THE RIGHT TO CHANGE ANY OF THE INFORMATION HEREIN WITHOUT NOTICE.
LIMITED WARRANTY
COVERAGE AND TERMS
RERVHC Model Series units, and all related accessories as manufactured by Spinnaker Industries, are warranted to the original buyer to be
free from defects in materials or workmanship provided that these units and accessories have been installed and maintained in accordance with
instructions and operated under normal conditions. Spinnaker Industries sole obligation under this Limited Warranty is to repair or replace, at its
opinion, free of charge to the customer (except as provided below), FOB factory, any part determined by Spinnaker Industries (in its sole
discretion) to be defective. Warranty terms, from original ship date are as follows:
All components ( excluding filters and fan belts ) ……………. I year from date of shipment
Stainless Steel Heat Exchanger (s) ……………………………. 10 years from date of shipment ( pro rated as follows )
Year 1 …………… customer pays 0 % of list price
Year 2 …………… customer pays 10% of list price
Year 3 …………… customer pays 20% of list price
Year 4 …………… customer pays 30% of list price
Year 5 …………… customer pays 40% of list price
Year 6 …………… customer pays 50% of list price
Year 7 …………… customer pays 60% of list price
Year 8 …………… customer pays 70% of list price
Year 9 …………… customer pays 80% of list price
Year 10 ……………customer pays 90% of list price
EXCLUSIONS
Spinnaker Industries Limited Warranty does not cover defects, reduced performance, or failure caused, directly or indirectly, by improper
installation, abuse, misuse, misapplication, improper maintenance, lack of maintenance, negligence, accident, or normal deterioration, including
wear and tear. This Limited Warranty shall not apply to items that require replacement due to normal wear i.e. fan drive belts, filters, etc., or to
failures, defects, or reduced performance resulting, directly or indirectly, from use of its products exposed to corrosive gasses or liquids.
Warranty claims that are not supported with a copy of the original start up report will not be considered.
Spinnaker Industries Limited Warranty does not include costs for transportation (including, without limitation, freight and return freight charges,
costs, and insurance), costs for removal or re-installation of parts or equipment, cranes and hoisting, premiums for overtime, labor for performing
repairs or replacement made in the field, roofing contractors or any other sub trades. Spinnaker Industries is not responsible for damages
occurring during transport of any product to or from its facilities.
RETURN PROCEDURE
To return defective parts under these warranty terms, please contact Spinnaker Industries at 1-800-932-6210 to confirm the ship to
address. The serial number located on the rating label of the unit must be provided so that the original ship date of the unit can be verified. All
defective parts must be authorized for return and shipped pre-paid to Spinnaker Industries for inspection. A purchase order must be received
prior to shipment of repaired or replacement parts. Repaired or replacement parts will be invoiced and shipped collect FOB Factory. A credit will
be issued only if the defective parts are deemed the responsibility of Spinnaker Industries. Spinnaker Industries is not responsible for any
damage or loss occurring during shipment to or from Spinnaker Industries.
THE OBLIGATION AND LIABILITY OF Spinnaker Industries UNDER THIS LIMITED WARRANTY DOES NOT
INCLUDE LOSSES, DIRECT OR INDIRECT, FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES. THIS LIMITED
WARRANTY IS PROVIDED EXCLUSIVELY TO THE ORIGINAL BUYER OF PRODUCTS AND MAY NOT BE
ASSIGNED OR OTHERWISE TRANSFERRED.
THIS LIMITED WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESED OR IMPLIED, INCLUDING WARRANTIES
OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, AND THERE ARE NO WARRANTIES WHICH
EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF.
Spinnaker Industries maintains a continuous product improvement policy , therefore specifications are subject to change without notice