Release Notes v5.0.3 and v5.00.03 - EcoStruxure Building Operation 2023 and SpaceLogic, EasyLogic Controller Firmware

Uploaded by

Walter Barba
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 44

[ Release Notes ] EcoStruxure™ Building Operation 2023 v5.0.3 and SpaceLogic, EasyLogic controllers v5.00.

03

Release Notes

EcoStruxure™ Building Operation 2023


v5.0.3

SpaceLogic and EasyLogic


Controller Firmware for MP-C, MP-V, RP-C,
RP-V, IP-IO and CRS Series
v5.00.03

This document is written for and on behalf of Schneider Electric and is supplied on the express terms that it is to be treated as
confidential and that it may not be copied, used, or disclosed to others except as authorized in writing by this Company. This document
is intended for internal use only.

Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.se.com
RN_EBO 2023_v5.0.3 Rev A – June 2023 Page 1 of 44

© 2023 Schneider Electric, all rights reserved

Internal

Internal
[ Release Notes ] EcoStruxure™ Building Operation 2023 v5.0.3 and SpaceLogic, EasyLogic controllers v5.00.03

About This Release


The EcoStruxure™ Building Operation 2023 Release v5.0.3 and SpaceLogic and
EasyLogic Firmware v5.00.03 Release Notes document details changes made since the
release of EBO v5.0.1/ FW 5.00.01 and EBO v5.0.2/ FW 5.00.02. This document should
therefore be read in conjunction with the EBO v5.0.1/ FW 5.00.01 and EBO v5.0.2/ FW
5.00.02 release notes.

This version v5.0.3 of EcoStruxure™ Building Operation 2023 is a maintenance release


that includes new features and enhancements detailed in section 2. It also includes
fixes for several previously reported field defects.

This EBO software release is fully compatible with SpaceLogic and EasyLogic Controller
firmware v5.00.03.

Please note the following:

• This release supersedes the v5.0.1, and v5.0.2 releases and should be used for
all upgrades to 5.0 and new greenfield sites.
• There is a new build of the controller firmware to accompany this release
(v5.00.03).
• It is imperative that any upgrades be accomplished only after reading and
understanding this document and the v5.0.1, v5.0.2 release notes.

Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.se.com
RN_EBO 2023_v5.0.3 Rev A – June 2023 Page 2 of 44

© 2023 Schneider Electric, all rights reserved

Internal

Internal
[ Release Notes ] EcoStruxure™ Building Operation 2023 v5.0.3 and SpaceLogic, EasyLogic controllers v5.00.03

Table of contents
ABOUT THIS RELEASE ......................................................................................................................................................... 2

1. ECOSTRUXURE BUILDING OPERATION 2023 RELEASE V5.0.3 AND SPACELOGIC, EASYLOGIC CONTROLLER
FIRMWARE V5.00.03 AVAILABILITY..................................................................................................................................... 5

1.1 EcoStruxure Building Operation software v5.0.3 ................................................................................. 5

1.2 Upgrade options ...................................................................................................................................... 6

1.3 Firmware Availability and Compatibility ............................................................................................... 6

1.4 Backward compatibility .......................................................................................................................... 9

1.5 Licensing ................................................................................................................................................. 9


1.5.1 Offline / Online definition when activating licenses ............................................................................................. 9

2. NEW FEATURES IN ECOSTRUXURE BUILDING OPERATION V5.0.3 RELEASE .................................................... 10

2.1 Workstation Enhancements ................................................................................................................. 10


2.1.1 Protecting IP in EBO - Securing Script Code.................................................................................................... 10
2.1.2 Workstation SDK ............................................................................................................................................. 11
2.1.3 Graphics Editor – updated library of the NAM Standards Team components ................................................... 11

2.2 WebStation Enhancements .................................................................................................................. 12


2.2.1 Browse and restore an "external" Backup ........................................................................................................ 12

2.3 System Enhancements ......................................................................................................................... 12


2.3.1 Script - Access to trend log data from script programs ..................................................................................... 12
2.3.2 Script Data Files - Generic tables that can interact with script .......................................................................... 13
2.3.3 External Log Storage support for AVEVA PI System ........................................................................................ 16

2.4 Licensing Enhancements ..................................................................................................................... 20


2.4.1 Improved performance (speed) of license activation ........................................................................................ 20
2.4.2 Additional licensing Enhancements.................................................................................................................. 21

2.5 Dali Enhancements ............................................................................................................................... 21


2.5.1 Relay Terminal discovery ................................................................................................................................. 21
2.5.2 Simplified DALI Commissioning ....................................................................................................................... 23
2.5.3 Energy Saving ................................................................................................................................................. 24
2.5.4 DALI On/Off on unused channel ...................................................................................................................... 25

2.6 Insight Sensor – Mask Editor Improvements ...................................................................................... 26

3. FIELD REPORTED DEFECTS FIXED IN ECOSTRUXURE BUILDING OPERATION V5.0.3 RELEASE ..................... 27

4. KNOWN DEFECTS IN ECOSTRUXURE BUILDING OPERATION AND SPACELOGIC AND EASYLOGIC


CONTROLLERS ................................................................................................................................................................... 30

4.1 Known Defects in EcoStruxure Building Operation Release v5.0.3 ................................................. 30

4.2 Known Defects in SpaceLogic and EasyLogic Controllers .............................................................. 33

5. CYBERSECURITY VULNERABILITY DISCLOSURES ................................................................................................ 34

6. IMPORTANT ENGINEERING INFORMATION ............................................................................................................. 35

Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.se.com
RN_EBO 2023_v5.0.3 Rev A – June 2023 Page 3 of 44

© 2023 Schneider Electric, all rights reserved

Internal

Internal
[ Release Notes ] EcoStruxure™ Building Operation 2023 v5.0.3 and SpaceLogic, EasyLogic controllers v5.00.03

6.1 Builder for Function Block ................................................................................................................... 35

6.2 Builder View........................................................................................................................................... 35

6.3 SpaceLogic Series (MP-C/V, IP-IO, and RP-C) Factory Firmware ..................................................... 35

6.4 Restoring Optional Properties ............................................................................................................. 35

6.5 DALI Energy Saving .............................................................................................................................. 36

APPENDIX A – PROCEDURES ............................................................................................................................................ 38

A1. Installing EcoStruxure Building Operation .............................................................................................. 38

A2. Upgrading EcoStruxure Building Operation (From previous major releases) ...................................... 38
A2.1 System Upgrade Overview........................................................................................................................................ 38
A2.1.1 Upgrade Enterprise Server and Enterprise Central................................................................................................. 38
A2.1.2 Upgrading Automation Servers .............................................................................................................................. 38
A2.1.3 Upgrading WorkStation and Client Tools Installation .............................................................................................. 39

A3 Upgrading EcoStruxure Building Operation v5.0.x.x to v5.0.3 ................................................................ 39


A3.1 Automation Server .................................................................................................................................................... 39
A3.2 Device Administrator Installation ............................................................................................................................... 39
A3.3 Enterprise Server ...................................................................................................................................................... 39
A3.4 Enterprise Central ..................................................................................................................................................... 39
A3.5 WorkStation .............................................................................................................................................................. 39
A3.6 License Administrator ................................................................................................................................................ 39

A4 Extended Log Storage Schema .................................................................................................................. 40


A4.1 PostgreSQL/TimescaleDB database schema ............................................................................................................ 40
A4.2 MSSQL database schema ........................................................................................................................................ 40

APPENDIX B – SPACELOGIC, EASYLOGIC CONTROLLER UPGRADE PROCEDURES ................................................. 41

B1 Upgrading Controller Firmware.................................................................................................................. 41

B2 Upgrading CRS Module Firmware.............................................................................................................. 41

B3 Upgrading SpaceLogic Sensor Firmware.................................................................................................. 42

B4 Upgrading Remote-Control Firmware ........................................................................................................ 42

B5 Verifying All Firmware Versions................................................................................................................. 42

Change History.................................................................................................................................................. 44

Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.se.com
RN_EBO 2023_v5.0.3 Rev A – June 2023 Page 4 of 44

© 2023 Schneider Electric, all rights reserved

Internal

Internal
[ Release Notes ] EcoStruxure™ Building Operation 2023 v5.0.3 and SpaceLogic, EasyLogic controllers v5.00.03

1. EcoStruxure Building Operation 2023 Release v5.0.3


and SpaceLogic, EasyLogic Controller Firmware v5.00.03
Availability

1.1 EcoStruxure Building Operation software v5.0.3


The software and firmware included in the EcoStruxure Building Operation v5.0.3
Release deliverable are available for download on Schneider Electric EcoXpert Extranet.

EcoStruxure Building Operation Edge Server is published here.

The EcoStruxure Building Operation Release 5.0.3 deliverable includes the following
software and firmware.

Product Version Build


EcoStruxure Building Operation Device Administrator software * 5.0.3 117
EcoStruxure Building Operation Enterprise Server software 5.0.3 117
EcoStruxure Building Operation Enterprise Central software 5.0.3 117
EcoStruxure Building Operation WorkStation software 5.0.3 117
EcoStruxure Building Operation SpaceLogic Server Hotfix 5.0.3 117
software*
EcoStruxure Building Operation WorkStation Hotfix software 5.0.3 117
EcoStruxure Building Operation License Administrator software 5.0.3 117

* This release is NOT supported on the original AS’s often referred to as AS classic (part
number - SXWAUTSVR10001).

This release is compatible with the following auxiliary tools:


EcoStruxure Building Operation Project Configuration template to support v5.0.3 will
be made available for download from Exchange.
The current version of the EcoStruxure Building Operation Vista transition tool also
supports v5.0.3.
The existing versions of the Automated Engineering Tool (v 5.0.1.261) and Export Tool
(v 5.0.1.119) also support EcoStruxure Building Operation 5.0.3.
EcoStruxure Building Commission mobile application to support the new features of
v5.0.3 is available to download from the appropriate store.

Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.se.com
RN_EBO 2023_v5.0.3 Rev A – June 2023 Page 5 of 44

© 2023 Schneider Electric, all rights reserved

Internal

Internal
[ Release Notes ] EcoStruxure™ Building Operation 2023 v5.0.3 and SpaceLogic, EasyLogic controllers v5.00.03

1.2 Upgrade options


Release v5.0.3 offers the possibility to upgrade a system in a non-sequential way. Any
EcoStruxure solution that is currently at v3.2 or higher can be upgraded directly to v5.0.3. If
you are upgrading from a version that is older than v3.2, it is important for you to read the
earlier Release Notes which can be found on EcoXpert Extranet.

BMS Software Support Policy establishes a clear expectation for product support timelines.
There are two main levels of software support, Full support when the software is in its
active phase and Limited support for a period of two years after the active phase. For more
information, refer to the software support policy document on EcoXpert Extranet.

Supported upgrade paths:

Ending Version
Upgrade Path
3.2 4.0 5.0
1.8 Via 3.1 Via 3.1 Via 3.1
Out of Support
1.9 Direct Via 3.2 Via 4.0
Starting Version

2.0 Direct Direct Via 4.0


Limited Support 3.0 Direct Direct Via 4.0
3.1 Direct Direct Via 4.0
Full Support 3.2 X Direct Direct
Limited Support 3.3L X Direct Via 4.0
Full Support 4.0 X X Direct

Current
Full Support
Version

* Versions 1.9 and earlier are not supported and should be upgraded to a fully supported
version. For details on older versions, see earlier versions' release notes

** Multi-version support is supported from EBO 3.0 onwards however excluding v3.3L. See
section 6.1 in Release Notes v5.0.1 for more details.

1.3 Firmware Availability and Compatibility


The firmware included in this release is available for download on EcoXpert Extranet.
The firmware is delivered in a universal package file that contains all firmware files for
all SpaceLogic IP Controller products.

Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.se.com
RN_EBO 2023_v5.0.3 Rev A – June 2023 Page 6 of 44

© 2023 Schneider Electric, all rights reserved

Internal

Internal
[ Release Notes ] EcoStruxure™ Building Operation 2023 v5.0.3 and SpaceLogic, EasyLogic controllers v5.00.03

SpaceLogic and EasyLogic Controllers v5.00.03.00030 - Firmware Package


File
Product Version
SpaceLogic and EasyLogic Controller – MP-C 5.00.03.00022
SpaceLogic and EasyLogic Controller – MP-V 5.00.03.00022
SpaceLogic and EasyLogic Controller – IP-IO 5.00.03.00022
SpaceLogic and EasyLogic Controller – RP-C 5.00.03.00022
SpaceLogic and EasyLogic Controller – RP-V 5.00.03.00022
EasyLogic Controller – RP-IO 5.00.03.00022

SpaceLogic Living Space Sensor Application 1.11.35


SpaceLogic Living Space Sensor Bootloader 0.03.05
SpaceLogic Living Space Sensor Display 1.02.84
MP-C Main Board1 5.00.03.00002
MP-V Main Board1 5.00.03.00002
RP-C Main Board1 5.00.03.00002
RP-C EFR32 5.00.03.00001
RP-V Main Board1 5.00.03.00002
RP-V EFR32 5.00.03.00001
CRS – Blind LV 1.9.20.9
CRS – Blind HV 1.9.20.9
CRS – Light 0 to 10V 1.9.20.9
CRS – Light 0 to 10V PD 1.9.20.9
CRS – Light DALI 1.9.20.9
CRS – Blind SMI LV 1.9.20.9
CRS – Blind SMI HV 1.9.20.9
CRS – Relay 1.9.20.9
CRS – Sensor expansion module 1.9.20.9
CRS – Insight Sensor module 1.9.20.9
Zigbee Adapter Firmware 1.30.0

1
Due to a defect, this will show as 5.03.00002 in the Device Report

Important Note: The SpaceLogic or EasyLogic Controllers shipped from the factory may not
have the latest firmware installed. It is essential to verify that the controller has the latest
firmware build loaded for the EcoStruxure Building Operation version build being used
before programming the controller.

Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.se.com
RN_EBO 2023_v5.0.3 Rev A – June 2023 Page 7 of 44

© 2023 Schneider Electric, all rights reserved

Internal

Internal
[ Release Notes ] EcoStruxure™ Building Operation 2023 v5.0.3 and SpaceLogic, EasyLogic controllers v5.00.03

Supported EBO releases and SpaceLogic, EasyLogic Firmware

SpaceLogic and EasyLogic MP/RP and IP-IO Series Controller Versions

EBO
v2.00.0x v3.01.0x v3.02.0x v3.03.01 v4.00.0x v5.00.0x
Versions

V3.2.x Supported Supported Supported Supported Supported Supported

V4.0.x Supported Supported Supported Supported Supported Supported

Not
v5.0.x Supported Supported Supported Supported Supported
Supported

*Versions not mentioned in the table above are out of full support. Refer to earlier versions'
release notes for the older versions' compatibility matrix

SpaceLogic/EasyLogic Controller Versions


Commercial References v2.00.0x v3.01.0x v3.02.0x v4.00.01 v4.00.02 v4.00.03/04 v5.00.0x
SXWMPV7AX1001 - MP-V-7A
Supported Supported Supported Supported Supported Supported Supported
BACnet/IP Controller
SXWMPV9AX1001 - MP-V-9A
Supported Supported Supported Supported Supported Supported Supported
BACnet/IP Controller
SXWMPV7AX1002 - MP-V-7A Not Not Not
Supported* Supported Supported Supported
BACnet/IP/MSTP Controller supported supported supported
SXWMPV9AX1002 - MP-V-9A Not Not Not
Supported* Supported Supported Supported
BACnet/IP/MSTP Controller supported supported supported
SXWRPV4A10001 -
Not Not Not Not
RP-V-4A Advanced Supported Supported Supported
supported supported supported supported
BACnet/IP/MSTP Controller
SXWRPV5A10001 -
Not Not Not Not
RP-V-5A Advanced Supported Supported Supported
supported supported supported supported
BACnet/IP/MSTP Controller
SXWRPV5CM10001 -
Not Not Not Not Not
EasyLogic RP-V-5C. BACnet MS/TP Supported Supported
supported supported supported supported supported
only
SXWRCF12AM10001 - EasyLogic Not Not Not Not Not Not Supported
RP-C-12A-M. BACnet MS/TP only supported supported supported supported supported supported
SXWRCF12BM10001 - EasyLogic Not Not Not Not Not Not Supported
RP-C-12B-M. BACnet MS/TP only supported supported supported supported supported supported
SXWRCF16AM10001 - EasyLogic Not Not Not Not Not Not Supported
RP-C-16A-M. BACnet MS/TP only supported supported supported supported supported supported
SXWMPC24AM10001 - EasyLogic Not Not Not Not Not Not Supported
MP-C-24A-M. BACnet MS/TP only supported supported supported supported supported supported
SXWMPC36AM10001 - EasyLogic Not Not Not Not Not Not Supported
MP-C-36A-M. BACnet MS/TP only supported supported supported supported supported supported
SXWRIOF12AM10001 - EasyLogic Not Not Not Not Not Not Supported
RP-IO-12A-M. BACnet MS/TP only supported supported supported supported supported supported
SXWRIOF16EM10001 - EasyLogic Not Not Not Not Not Not Supported
RP-IO-16E-M. BACnet MS/TP only supported supported supported supported supported supported

Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.se.com
RN_EBO 2023_v5.0.3 Rev A – June 2023 Page 8 of 44

© 2023 Schneider Electric, all rights reserved

Internal

Internal
[ Release Notes ] EcoStruxure™ Building Operation 2023 v5.0.3 and SpaceLogic, EasyLogic controllers v5.00.03

Supported* means it will work with BACnet IP but there is no support for configurability to
BACnet MSTP Northbound.

1.4 Backward compatibility

In cases where the compatibility matrix states “Not Supported” for a given pairing, there
remains limited support to allow that unsupported pairing to discover, host, and down-rev
from factory-installed firmware to ensure a compatible pairing is achieved.

Down-Rev from a factory installed 4.0 or 5.0 firmware IP Controller to “earlier” versions
It is important to note that any Down-Rev should be undertaken after hosting and prior to
connecting any external equipment (beyond power and Ethernet connection) and prior to
downloading any application or undertaking any other configuration of the controller.

Warning: Down-Rev is NOT supported between versions once the application is loaded onto
the controller. On controllers loaded with a database, an Erase Database or Factory Reset
command should be issued (and allowed to complete) before a downrev of the controller is
attempted. Once the downrev is completed, the database can be downloaded from the
server, assuming that the server and controller versions are compatible.

1.5 Licensing
EcoStruxure Building Operation 2023 (EBO) v5.0.3 requires either EBO 2022 licenses or EBO
2023 licenses to run.
If your system is currently based on EBO 2022 licenses, there is no need to upgrade your
existing licenses to EBO 2023 in order to operate with EBO 2023 (5.0.3).
1.5.1 Offline / Online definition when activating licenses
When activating embedded licenses EBO users need to consider if Online or Offline
activation methods should be used. From EBO release 5.0.3 the definition of Off-line/On-line
has changed.

On-line = Automation Server (AS) has an internet connection or Device Administrator (PC
running Windows) has an internet connection.

Off-line = No internet connection is available either on Automation Server (AS) or Device


Administrator (PC running Windows).

OR Internet = On-Line
Internet

AND Internet = Off-Line


Internet

Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.se.com
RN_EBO 2023_v5.0.3 Rev A – June 2023 Page 9 of 44

© 2023 Schneider Electric, all rights reserved

Internal

Internal
[ Release Notes ] EcoStruxure™ Building Operation 2023 v5.0.3 and SpaceLogic, EasyLogic controllers v5.00.03

2. New Features in EcoStruxure Building Operation v5.0.3


Release
2.1 Workstation Enhancements
2.1.1 Protecting IP in EBO - Securing Script Code
You can protect a Script program code to safeguard your proprietary algorithms as follows.

1. In Script Editor, right-click in the Code pane and select Protect. A password entry
dialog appears.

2. Enter and confirm a password of 4-25 characters. The password used to protect a
Script program is independent of your Workstation user account and the rules
associated with Workstation passwords do not apply.

IMPORTANT: There is no password recovery function. Verify your password before


saving and retain an unprotected copy of the script program in case of a forgotten
password.

3. Click OK to save and protect the code.

The Protect operation encrypts the Script source code and saves the Script program, even
if the code contains errors. Once protected, the Script program’s code is displayed as
encrypted text and can no longer be legibly viewed or edited in Workstation or Script
Editor until you unprotect the program.

You can protect all types of Script programs, except for programs in i2 and b3 controllers.

Protecting a Script program does not prevent the script from running, being copied,
exported for reuse, or being deleted. When you paste or import a protected program, the
pasted or imported program remains protected with the same password as used to
originally protect it. In Workstation, you can modify the bindings associated with the
protected Script program.

Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.se.com
RN_EBO 2023_v5.0.3 Rev A – June 2023 Page 10 of 44

© 2023 Schneider Electric, all rights reserved

Internal

Internal
[ Release Notes ] EcoStruxure™ Building Operation 2023 v5.0.3 and SpaceLogic, EasyLogic controllers v5.00.03

IMPORTANT: Script program code protection is not supported in EBO versions prior to
5.0.3. In multi-version systems, when logged onto ES or EC version 5.0.3 or later, do not
protect Script program code residing in servers running an earlier version. Doing so can
result in the loss of data if another user inadvertently saves a protected program while
logged on directly to the server running the earlier version.

Perform the following steps to unprotect a script program.


1. Right-click in the Code pane and select Unprotect. A password entry dialog
appears.

2. Enter the password used to protect the Script program.


3. Click OK to unprotect the code.

You have now unprotected your Script program. The Script Editor displays the original
source code.

NOTE: After unprotecting a Script program in Script Editor, the program will remain
protected on the EBO server until you save the program in Script Editor. If you unprotect a
program in Script Editor and close the program without saving it, you will need to re-enter
the password to view the program contents the next time you open the program in Script
Editor.

2.1.2 Workstation SDK


ITrendLog - The interface has been updated with methods that pertain to creating the
most common trend logs: CreateChangeOfValueTrendLog, CreateExtendedTrendLog,
CreateIntervalTrendLog, CreateManualTrendLog, CreateVariableTriggeredTrendLog, and
CreateLogProcessingTrendLog.
This means that there is support for setting meter log properties.

2.1.3 Graphics Editor – updated library of the NAM Standards Team


components
An updated library of the NAM Standard Team Components has been included as part of
the Workstation installation (where the Graphics Editor is included). Full details on all
changes to these components can be found on the Exchange Community.

Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.se.com
RN_EBO 2023_v5.0.3 Rev A – June 2023 Page 11 of 44

© 2023 Schneider Electric, all rights reserved

Internal

Internal
[ Release Notes ] EcoStruxure™ Building Operation 2023 v5.0.3 and SpaceLogic, EasyLogic controllers v5.00.03

2.2 WebStation Enhancements


2.2.1 Browse and restore an "external" Backup
The Upload function (browse and add a backup set) is now available in the default view for
Backup and Restore (/ServerName/System/Backup and Restore).

2.3 System Enhancements


2.3.1 Script - Access to trend log data from script programs
In Script Programs, you can read trend log values and time stamps into corresponding
numeric and datetime Program Arrays. After trend log data is read into arrays, you can use
script programming to perform operations and analysis on the information.

Note: This functionality is supported in Script programs only in Enterprise Server and
Enterprise Central version 5.0.3 and later. This functionality is not supported in Script
Functions or Script Event Programs, nor in devices other than Enterprise Server or
Enterprise Central.

In script programs, you use a new Trendlog binding variable type to configure access to a
trend log and a new system function called Read to read records from the trend log as
follows.

Trendlog
• Trendlog assigns the name that follows it as a binding variable, which you bind to a
trend log object.
• Syntax: Trendlog namelist
o namelist is a list of one or more user-defined script binding variable names
separated by commas.
• You bind Trendlog binding variables to the trends you wish to access in the script
program. The trend logs you bind to must be in the same server as the Script
program.

Read
• Read is a Script program system function that reads trend records from a trend log
into a script program.
• Syntax: variablename.Read (start_time, end_time, requested_number, value_array,
timestamp_array, received_number)
o variablename is a script binding variable of type Trendlog.
o start_time, end_time are datetime values that specify the range of time within
the bound trend log to read trend records. Datetime values must be in server
local time.
o requested_number is a numeric value that specifies the maximum number of
records to read from the trend log.

Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.se.com
RN_EBO 2023_v5.0.3 Rev A – June 2023 Page 12 of 44

© 2023 Schneider Electric, all rights reserved

Internal

Internal
[ Release Notes ] EcoStruxure™ Building Operation 2023 v5.0.3 and SpaceLogic, EasyLogic controllers v5.00.03

o Value_array is a numeric array that receives the Value from each trend record
read.
o timestamp_array is a datetime array that receives the Time stamp from each
trend record read.
o received_number is a numeric value that indicates the actual number of trend
records read.
• The sizes of value_array and timestamp_array are automatically adjusted to match
the number of trend points read from the trend log.

See WebHelp topic Script Program Access to Trend Logs for an example.
2.3.2 Script Data Files - Generic tables that can interact with script
A Script data file is an object that represents a two-dimensional table consisting of columns
and rows. Cells within the data file are defined by column and row indices. Each cell can
contain a string, numeric, or datetime value that can be written to and read by a Script
program using a set of new Script functions.

When you view a Script data file in WorkStation, you see a table that displays the contents
of the data file arranged in rows and columns with column headers that you can edit in
WorkStation

Note: This functionality is supported in Script programs only in Enterprise Server and
Enterprise Central version 5.0.3 and later. This functionality is not supported in Script
Functions or Script Event Programs, nor in devices other than Enterprise Server or
Enterprise Central.

Note: It's not possible to modify the contents of the data file in Data File tab. The contents
of the data file can only be modified by a Script program.

Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.se.com
RN_EBO 2023_v5.0.3 Rev A – June 2023 Page 13 of 44

© 2023 Schneider Electric, all rights reserved

Internal

Internal
[ Release Notes ] EcoStruxure™ Building Operation 2023 v5.0.3 and SpaceLogic, EasyLogic controllers v5.00.03

When creating a Script data file, you enter the number of columns and rows in the object
creation wizard.

Warning: If you later need to adjust the number of rows or columns in the data file, you
can change the data file's Number of rows or Number of columns properties. However,
doing so causes the data in the file to be cleared. So, when creating a data file, be sure to
allow extra rows and columns to anticipate the maximum needs of your application.

In script programs you use a new Datafile binding variable type to configure access to
datafiles and several new system functions to interact with datafiles as follows.

Datafile
• Datafile is a new Script program keyword that assigns the name that follows it as a
binding variable, which you bind to a datafile object.
• Syntax: Datafile namelist
o namelist is a list of one or more user-defined script binding variable names
separated by commas.
• You bind Datafile binding variables to the datafiles you wish to access in the script
program. The datafiles you bind to must be in the same server as the Script
program.

Open
• Open prepares a Script program to access a datafile. You must open a data file
before performing any other operations on the data file.
• Syntax: variablename.Open()
o variablename is a script binding variable of type Datafile.
o Open is an asynchronous operation, so Open must be on its own labeled line in
the Script program.

Write
• Write writes data to a data file.
• Syntax: variablename.Write(row_number, column_number, source_value)
o variablename is a script binding variable of type Datafile.
o row_number and column_number are numeric values that specify the row and
column of the cell to be written.
o source_value is a numeric, string, or datetime value to be written to the cell.

Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.se.com
RN_EBO 2023_v5.0.3 Rev A – June 2023 Page 14 of 44

© 2023 Schneider Electric, all rights reserved

Internal

Internal
[ Release Notes ] EcoStruxure™ Building Operation 2023 v5.0.3 and SpaceLogic, EasyLogic controllers v5.00.03

• Up to 1000 characters can be written to a cell of a data file.


• A data file is limited to a size of 10,000 Kbytes total.

Read
• Read reads a cell from a data file.
• Syntax: variablename.Read(row_number, column_number, return_value)
o variablename is a script binding variable of type Datafile.
o row_number and column_number are numeric values that specify the row and
column of the cell to be read.
o return_value is a numeric, string, or datetime value to receive the data from
the file.
• Read accesses the referenced data file, reads data from the cell specified by
row_number and column_number, and assigns the result to return_value. The data
type of return_value must match the type of data present in the specified cell.

Clear
• Clears the contents of a data file.
• Syntax: variablename.Clear()
o variablename is a script binding variable of type Datafile.

Save
• SAVE saves the contents of a datafile to the server's database.
• Syntax: variablename.Save()
o variablename is a script binding variable of type Datafile.
• Save is an asynchronous operation, so Save must be on its own labeled line in the
Script program.
• Save holds the program at its current line for 10 seconds to mitigate the risk of too
frequent save operations blocking access to the server database for other processes.
• Save updates the Size in Kbytes property of the datafile.

Close
• Close terminates access to the referenced datafile.
• Syntax: variablename.Close()
o variablename is a script binding variable of type Datafile.
• Close is an asynchronous operation, so Close must be on its own labeled line in the
Script program.

Rows
• Rows returns the number of rows in a datafile.
• Syntax: numericvalue = variablename.Rows()
o numericvalue is a variable of type numeric.
o variablename is a script binding variable of type Datafile.

Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.se.com
RN_EBO 2023_v5.0.3 Rev A – June 2023 Page 15 of 44

© 2023 Schneider Electric, all rights reserved

Internal

Internal
[ Release Notes ] EcoStruxure™ Building Operation 2023 v5.0.3 and SpaceLogic, EasyLogic controllers v5.00.03

Columns
• Columns returns the number of columns in a datafile.
• Syntax: numericvalue = variablename.Columns()
o numericvalue is a variable of type numeric.
o variablename is a script binding variable of type Datafile.

2.3.3 External Log Storage support for AVEVA PI System


Note: This feature requires a license.

It is now possible to send historical data to AVEVA PI System. The historical data can only
be written to PI System (I.e. it cannot be read back). For more information about PI
Historian and how to set up the database, please go to AVEVA home page.

We have tested with Pi Web API 2021 SP3. We have not tested older versions, but
according to AVEVA, 2018 should work as well.

After setting up the PI System, go to Control Panel and choose PI Historian under External
Log Storage:

Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.se.com
RN_EBO 2023_v5.0.3 Rev A – June 2023 Page 16 of 44

© 2023 Schneider Electric, all rights reserved

Internal

Internal
[ Release Notes ] EcoStruxure™ Building Operation 2023 v5.0.3 and SpaceLogic, EasyLogic controllers v5.00.03

In the editor, configure the address and other settings:

Configure Host address, Asset server, Database name and credentials. Configure a Point
source to categorize the data for easier access and search. Compression is possible, but
only for new points. If the point already has written data in PI Historian, the data cannot be
compressed afterward. Either remove the tag and set a new one or enable compression
manually in PI System. Enumeration tables can also be written to PI System, i.e. units,
alarm states, etc.
Trend logs
By default, no trend logs are writing data to PI System. The trend log must be configured
with a tag name (PITagName=) in the Note 2 property to write data. Note 2 can still be
used for other purposes.

Supported values for PITagName:

• @(Path) – Will add the log-object path to the tag-name. Initial / is removed.
• @(Name) – Will add the log-object-name to the tag-name.
• @(MonitoredPath) - Will use the source log path if source log use @(Path). Can be
used to merge Extended trend logs with source log.

Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.se.com
RN_EBO 2023_v5.0.3 Rev A – June 2023 Page 17 of 44

© 2023 Schneider Electric, all rights reserved

Internal

Internal
[ Release Notes ] EcoStruxure™ Building Operation 2023 v5.0.3 and SpaceLogic, EasyLogic controllers v5.00.03

• Manual text – Supports manual text.

Examples:
PITagName=@(Path)
PITagName=EBO_@(Name)
PITagName=@(MonitoredPath)
PITagName=MyTempLog1 or Building1_Floor2_Room3_TempSensor
Events
Event can have its own tag name. A few columns are default configured, so select columns
to the right and drag and drop them to the editor to get more. Column data will be stored
with delimiter |.

General behavior
• No trend logs are written by default, only after adding PITagName to the Note2 will
the log start transferring.
• You can change the tag-name and it will start writing to the new one right away, the
old one will not be deleted in PI.
• Deleting PITagName from Note2 will stop that log from transferring, nothing will be
deleted from PI.
• Moving/Renaming a log will not change the tag-names in PI until disable/enable has
been performed for trends. Applicable when using @(Path), @(Name) and
@(MonitoredPath) as tag name.
• If you want to change the tag-name/columns for events then you need to
disable/enable for events before it applies.

PI System Explorer
Data can be viewed in PI System Explorer. Choose the database:

Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.se.com
RN_EBO 2023_v5.0.3 Rev A – June 2023 Page 18 of 44

© 2023 Schneider Electric, all rights reserved

Internal

Internal
[ Release Notes ] EcoStruxure™ Building Operation 2023 v5.0.3 and SpaceLogic, EasyLogic controllers v5.00.03

Example how to view data. Search for the tag name and drag item to the area. Right-click
and select Time Series Data:

Event data is presented in similar way, with | as delimiter between the columns:

Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.se.com
RN_EBO 2023_v5.0.3 Rev A – June 2023 Page 19 of 44

© 2023 Schneider Electric, all rights reserved

Internal

Internal
[ Release Notes ] EcoStruxure™ Building Operation 2023 v5.0.3 and SpaceLogic, EasyLogic controllers v5.00.03

2.4 Licensing Enhancements


2.4.1 Improved performance (speed) of license activation

When performing Online activation on multiple selected Automation Servers the process
has been improved. Previously the activation was made one server at a time. From EBO 5.0.3
the Device Administrator simultaneously works on activation of 20 Automation Servers. This
improves the overall activation fundamentally. A simultaneous license activation test made
on 20 various models of servers showed that the overall time to activate all 20 servers was
24 minutes. With the improvement in EBO 5.0.3, the time was reduced to 2 minutes. The
improvement was also made robust with 3 automatic retrials on Servers that fails to activate.
The retrials eliminate the effect of temporary bad connections or other not foreseen glitches
in the system.

Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.se.com
RN_EBO 2023_v5.0.3 Rev A – June 2023 Page 20 of 44

© 2023 Schneider Electric, all rights reserved

Internal

Internal
[ Release Notes ] EcoStruxure™ Building Operation 2023 v5.0.3 and SpaceLogic, EasyLogic controllers v5.00.03

2.4.2 Additional licensing Enhancements

In EBO 5.0.3 the Device Administrator connectivity has improved. Now the existing
operational feature can use Device Administrator (DA) to communicate with the FNO (cloud
license server). Previously the below features needed an internet connected Automation
Server to communicate with FNO. From EBO 5.0.3 the below features can be used when only
DA is internet connected.

• Online license activation when only DA has an internet connection.


• Reclaim licenses when only DA has an internet connection.
• Return licenses when only DA has an internet connection.

2.5 Dali Enhancements


The following DALI enhancements only apply to DALI Light module with Power Delivery.
2.5.1 Relay Terminal discovery
“Discover new lights” and “Discover all lights” commands have been updated to detect to
which terminal each DALI light is connected.

Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.se.com
RN_EBO 2023_v5.0.3 Rev A – June 2023 Page 21 of 44

© 2023 Schneider Electric, all rights reserved

Internal

Internal
[ Release Notes ] EcoStruxure™ Building Operation 2023 v5.0.3 and SpaceLogic, EasyLogic controllers v5.00.03

During the discovery process, the Power Delivery relays will be switched off and on in
order to identify the terminals.

A new command “Discover Terminals only” has been introduced to discover on which terminal
each DALI light is connected to without impacting the current DALI address and association.
This command must be executed after upgrading an installation to 5.0.3 to allow to use of the
Energy Saving feature.

The Device Discovery UI has been updated to display the terminal information and group the Lights
based on that terminal information.

Note that if the terminal has not yet been discovered (for instance, after upgrading to 5.0.3) or
can’t be discovered (light with external power supply or terminal associated to a relay), the light
terminal will be displayed as “unknown terminal”.

Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.se.com
RN_EBO 2023_v5.0.3 Rev A – June 2023 Page 22 of 44

© 2023 Schneider Electric, all rights reserved

Internal

Internal
[ Release Notes ] EcoStruxure™ Building Operation 2023 v5.0.3 and SpaceLogic, EasyLogic controllers v5.00.03

2.5.2 Simplified DALI Commissioning


This release introduces the support of “DALI Group channel” that can be created on a CRS DALI
Light module with Power Delivery:

A DALI Channel Group allow to control all the lights connected to a terminal as one light, there is no
association to perform (simplified commissioning), the DALI Channel Group must be associated to
one of the 4 terminals (that terminal must not be already associated to another Group Channel or
to a Relay) and a group address must be set.

Note: The Group address shares the same address space as the regular DALI light group.

To control and configure the lights on that Group channel, the same properties as a DALI Light are
available and will be applied to each light on that terminal (if these lights were powered by the
module during discovery process).

Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.se.com
RN_EBO 2023_v5.0.3 Rev A – June 2023 Page 23 of 44

© 2023 Schneider Electric, all rights reserved

Internal

Internal
[ Release Notes ] EcoStruxure™ Building Operation 2023 v5.0.3 and SpaceLogic, EasyLogic controllers v5.00.03

The Device Discovery UI is updated once a Channel group is created to highlight that it is associated
to that terminal.

Note that the lights connected to that terminal cannot be associated to a DALI light/group if a
Channel Group is associated to that terminal (these lights can only be controlled using the Channel
Group), but they can be winked from the Device discovery view.

2.5.3 Energy Saving


The DALI Energy Saving allows opening the Power Delivery Relay of a terminal if all lights connected
to that terminal are currently off.
2 new properties have been introduced in the module properties tab:
• Energy saving: to enable/disable the energy saving
• Reay delay (s): to define how long the DALI power distribution module should wait before
opening the relay when all lights are off

When the Terminal Relay is open (Energy saving is active), then it can take about 200ms to send a
command to a light (close relay, wait that lights power up, and send command).

Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.se.com
RN_EBO 2023_v5.0.3 Rev A – June 2023 Page 24 of 44

© 2023 Schneider Electric, all rights reserved

Internal

Internal
[ Release Notes ] EcoStruxure™ Building Operation 2023 v5.0.3 and SpaceLogic, EasyLogic controllers v5.00.03

There are 2 prerequisites to Energy Saving:


• The light’s terminal must be discovered (done during a Discovery New/All command or using
Discover Terminals only command)
• The Power On level of the light or Group Channel must be set to 0% (to avoid change of light
level when operating the relays)
2.5.4 DALI On/Off on unused channel
This release introduces the support of “DALI Relay” that can be created on a CRS DALI Light module
with Power Delivery:

A DALI Relay allow to control for instance a 230 VAC light on a terminal on which there is no DALI
light connected. The DALI Relay object is similar to the Relay object of the Relay 10 module. It must
be associated to one of the 4 terminals (that terminal must not be already associated to another
Relay or to a Group channel).

Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.se.com
RN_EBO 2023_v5.0.3 Rev A – June 2023 Page 25 of 44

© 2023 Schneider Electric, all rights reserved

Internal

Internal
[ Release Notes ] EcoStruxure™ Building Operation 2023 v5.0.3 and SpaceLogic, EasyLogic controllers v5.00.03

Note that no DALI Light can be controlled if they are connected to the terminal associated to the
Relay.
If any lights is connected and discovered before creating the relay or if the relay was closed during
the discovery, then these lights will be listed in the Device Discovery page but cannot be controlled.

2.6 Insight Sensor – Mask Editor Improvements


The Insight Sensor Mask editor is redesigned to be more intuitive and better represent the physical
space in which the Insight Sensor is installed. There is now a single detection area, while multiple
exclusion areas can still be defined. For more information, see the See WebHelp topic Insight-
Sensor Masks.

Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.se.com
RN_EBO 2023_v5.0.3 Rev A – June 2023 Page 26 of 44

© 2023 Schneider Electric, all rights reserved

Internal

Internal
[ Release Notes ] EcoStruxure™ Building Operation 2023 v5.0.3 and SpaceLogic, EasyLogic controllers v5.00.03

3. Field Reported Defects Fixed in EcoStruxure Building


Operation v5.0.3 Release
These tables list all field reported defects fixed in 5.0.3
Note: a PSS Ticket ID of 99 = Alpha / Beta; 0, 97 = Bench testers

Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.se.com
RN_EBO 2023_v5.0.3 Rev A – June 2023 Page 27 of 44

© 2023 Schneider Electric, all rights reserved

Internal

Internal
[ Release Notes ] EcoStruxure™ Building Operation 2023 v5.0.3 and SpaceLogic, EasyLogic controllers v5.00.03

Ecostruxure Building Operation Defect ID PSS Ticket ID


Summary
Lamp failure alarm is not cleared in alarm list DBSQA-54867 91645418
Webstation: Xenta Central Schedule: Cannot add or edit time
at midnight DBSQA-57208 98497762
Type permissions are not working since we upgraded from
3.2.3 to 4.0.3 DBSQA-57210 96980347
Webstation does not provide the log-in page with the
customer’s ES database. DBSQA-57211 97786742
Minor error creating trend log in Webstation DBSQA-57219 99476984
Semantics - When exporting ExtendedTrendLog there is error
reported as warning. DBSQA-57313 97
Unable to export records or manipulate multi-trend log list in 95863664,
Webstation DBSQA-57320 98718565
Set permissions for AD user DBSQA-57324 97794230
ERROR: invalid regular expression: parentheses () not
balanced seen in PostgreSQL logs DBSQA-57325 97461077
Paths are not sorted in the Software Permission tab DBSQA-57333 99115128
WebStation: No error received when the user doesn't have
permission and tries to create alarm or trend DBSQA-57764 99854931
100201744,
WebStation: Fullscreen button is not working DBSQA-57767 99859657
Notification error after Upgrade from 3.2 to 5.0.1.128 DBSQA-57826 98997170
ModProg: Enter Key to open and exit Component does not 99,
always work in Builder for FB. DBSQA-57909 99790421
92303072,
92530491,
97311189,
Multiversion: ES license violation and AS goes offline DBSQA-57947 99313264
License Administrator crashes when copying diagnostics DBSQA-57957 98421534
When the object DateTime Value is saved with a date that is
not in the same Daylight-saving time as the server, an offset
in the time is introduced in the value of the time saved. DBSQA-57958 95083808
EBO server (AS/ES) allows unrestricted backup initiated from
BACnet client DBSQA-57961 97918541
TH907 Zigbee link break and never reconnect after a power-
cycle DBSQA-57967 0
License Administrator: Installer hangs when trying to install
in directory where path contains special character DBSQA-57969 99586453
Modbus embedded license is not shown in device
administrator DBSQA-57970 99632725
Memory usage in AS-P goes up to 85-90% DBSQA-57974 99788756
"Show real values" property is not working as expected DBSQA-57991 100020875

Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.se.com
RN_EBO 2023_v5.0.3 Rev A – June 2023 Page 28 of 44

© 2023 Schneider Electric, all rights reserved

Internal

Internal
[ Release Notes ] EcoStruxure™ Building Operation 2023 v5.0.3 and SpaceLogic, EasyLogic controllers v5.00.03

Graphic containing script module CSS does not adjust


properly in WebStation when resizing the window DBSQA-57992 99941683
Builder save and deploy crashed workstation and edit option 100129755,
greyed out DBSQA-58071 100213586
AS-B/P Flush buffer. Protocol error on valid Modbus frame -
Shift in data DBSQA-58252 99503394
EBO 5.0.2.109 fail to download i1 controllers 101220299
DBSQA-58257 99782224
BACnet binary inputs stay in alarm state after upgrade to
EBO 2023 DBSQA-58262 100047035
Advance Display does not open beyond Schneider Electric
Splash window DBSQA-58265 99897057
New variables added after changing SpaceLogic FB program 100199698,
custom type version will have value zero DBSQA-58281 100204215
In multi-version system ZigBee device discovery is not shown
devices in ES DBSQA-58310 100096418
Webstation - Timed Force: Error message saving "Forced
until" more than 25 days from today DBSQA-58311 100285738
Webstation: Trend Chart with calculation method "Meter
consumption" is just black DBSQA-58315 100306513
Builder save and deploy doesn’t update RP-C bound object DBSQA-58316 100226041
TAC Vista Conversion Tool doesn't match this specific SCPT
correctly. DBSQA-58415 100418617
Webstation: Right click menu item "Open log" missing DBSQA-58696 100598259
Notification Reports: Corrupt Excel report output DBSQA-58705 100534367
Binding window loses focus causing filtering and selecting of
objects to be inconsistent DBSQA-58741 100700349
User cannot login despite having the IP address added to
allow list after upgrading from 5.0.1 to 5.0.2 DBSQA-58742 100734884
EBO: Webstation operation with NW8K APT results in "Not a
valid cast from String to Double" DBSQA-58747 100325048
Modernized Programming - Digital Point Line Representation
Not Changing DBSQA-58768 100845593
ADv3 changed AS-P gateway setting when plugged in DBSQA-58770 100047740
Webstation: Menu built in Graphics Editor stopped working 100832938,
in 5.0 DBSQA-58789 101050768
AS-P ver 5.0.2 does not show up as Remote interface in LPA DBSQA-58795 0
DA: New database fails in DFU mode if default SSH port is
disabled DBSQA-58836 100107108

Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.se.com
RN_EBO 2023_v5.0.3 Rev A – June 2023 Page 29 of 44

© 2023 Schneider Electric, all rights reserved

Internal

Internal
[ Release Notes ] EcoStruxure™ Building Operation 2023 v5.0.3 and SpaceLogic, EasyLogic controllers v5.00.03

4. Known Defects in EcoStruxure Building Operation and


SpaceLogic and EasyLogic Controllers

4.1 Known Defects in EcoStruxure Building Operation Release


v5.0.3

The table below lists new known defects since 5.0.2 release. For the known issues list up
until EBO v5.0.2, refer to previous version’s release note here.

Jira Key ID Functionality Summary Workaround

Binding b3 BACnet Bind a digital value object


Continuum Alarm’s Event state to a between the Alarm object's
DBSQA-57282
transition script program results in a Event state property and the
compilation error. Script program's input.
Log out of the ES and log back
On ES, i2s are not visible in after a learn operation.
Continuum
DBSQA-58266 under an AS-P after Learn Alternatively, log directly into
transition
operation the AS-P to perform i2
operations.
Unable to configure i2
Continuum devices after import if Export and import i2 devices
DBSQA-58773
transition import file contains more one at a time.
than one device
Create Script Data Files with
Script Data File data is not extra rows and columns to
DBSQA-58283 Script preserved when the Data anticipate the needs of the
File is resized. application. Do not resize a
Script Data File.
The contents of a Script
Data File are not Use export import to
DBSQA-58388 Script
preserved through copy / duplicate a Script Data File.
paste.
Right clicks the desired entry
Unable to paste in Script
DBSQA-58695 Script in the Script Editor clipboard
Editor
list and select Paste.
Script program read Be aware that the returned
requests from trend logs data is stale for example
return stale data when during daylight savings time
DBSQA-58792 Script there is a time change change over. After the time
event in time range change event rolls out of the
requested from the trend requested time window,
log. operation returns to normal.

Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.se.com
RN_EBO 2023_v5.0.3 Rev A – June 2023 Page 30 of 44

© 2023 Schneider Electric, all rights reserved

Internal

Internal
[ Release Notes ] EcoStruxure™ Building Operation 2023 v5.0.3 and SpaceLogic, EasyLogic controllers v5.00.03

Jira Key ID Functionality Summary Workaround

Using a Wait statement in


a Script program
Don’t use a Wait statement
immediately before a
immediately preceding a Data
DBSQA-58896 Script Data File system function
File system function
statement interferes with
statement.
the operation of the
system function.
Validation error occurs
Remove the binding, rename
when renaming a Script
DBSQA-58971 Script the Script program, and
program that is bound to
recreate the binding.
a data file.
Find and Replace does not
Use another "Within" setting
Builder for rename Component/HFB
or replace the text in the
DBSQA-58955 Function labels when using the
Component/HFB label
Block search setting “Within:
manually.
selected objects”.
Using Builder View on the
root of an EcoStruxure Selecting the targeted folder
Building Server (Central, or area in the system tree that
Enterprise, Automation, you wish to evaluate, instead
DBSQA-58874 Builder View
Edge) or a of the root, can avoid longer
SpaceLogic/EasyLogic load times.
device can cause long
loading times.
If a 5.00.03 RP controller is first
configured/engineering in an
EBO 5.0.3 system to contain
Simplified DALI features
(including the Relay object), and
the controller is then removed
Simplified DALI: Relay from the EBO 5.03 system and
object is present and later hosted under an EBO
DBSQA-58875 BACnet
usable in versions that do server at 4.0.3 (without first
not support simplified DALI factory resetting or erasing the
controller's database), and the
user then performs and Upload
All, the Relay object will appear
in the 4.0.3 RP application. This
is because the Relay object was
included in EBO 4.0.3

Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.se.com
RN_EBO 2023_v5.0.3 Rev A – June 2023 Page 31 of 44

© 2023 Schneider Electric, all rights reserved

Internal

Internal
[ Release Notes ] EcoStruxure™ Building Operation 2023 v5.0.3 and SpaceLogic, EasyLogic controllers v5.00.03

Jira Key ID Functionality Summary Workaround

Simplified DALI: When


assigning a terminal, it Click 2x on the terminal to
DBSQA-58876 BACnet
does not take on the first select it
click
CRS devices show Error
indication in the Enhanced Do not add the Error
firmware upgrade view indication column in the
DBSQA-58985 BACnet
even though they are Enhanced firmware upgrade
online and work as view
expected
The enhanced firmware
upgrade can take several
minutes to fully populate, Use the traditional Firmware
DBSQA-58978 BACnet
in cases where child upgrade view, if desired
Automation Servers have a
version < 4.2.
If the save button is used
instead of the X, the changes
Device Admin: Prompt to are saved to the correct server
DBSQA-58945 Device Save changes for the list.
Administrator wrong server list when If yes is selected in the dialog
exiting the application after pressing X, the changes
are saved to the correct server
list.
DBSQA-58910 Dev Admin - AS running
Device SE2 Linux added using USB,
Use correct password
Administrator does not indicate that
password is required
DBSQA-58876 Simplified DALI: When
assigning a terminal, it
DALI Try Again
does not take on the first
click
DBSQA-58898 DALI: Inconsistency of the
DALI object statuses after their None
creation
DBSQA-58875 Simplified DALI: Relay
object is present and
DALI None
usable in versions that do
not support simplified DALI

Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.se.com
RN_EBO 2023_v5.0.3 Rev A – June 2023 Page 32 of 44

© 2023 Schneider Electric, all rights reserved

Internal

Internal
[ Release Notes ] EcoStruxure™ Building Operation 2023 v5.0.3 and SpaceLogic, EasyLogic controllers v5.00.03

4.2 Known Defects in SpaceLogic and EasyLogic Controllers

The table below lists all known defects that affect the IP Controller firmware (MP-C, MP-V,
RP-C, or IP-IO controllers, CRS Modules, SpaceLogic sensors and Remote Control) since
5.00.02 release. For the known issues list up until EBO v5.00.02, refer to previous version’s
release note here.

Jira Key ID Functionality Description Workaround/Solution

DALI module shows 'Lamp failure'


Run a new discovery without
when a Relay on a terminal,
DBSQA -58860 DALI the DALI light or while the
where a lamp is connected and
Relay is OFF
discovered, is OFF
After assigning a terminal to a
Run a “Download All” on RP-C
DBSQA-58887 DALI channel group, the object goes
or restart the DALi module
offline

Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.se.com
RN_EBO 2023_v5.0.3 Rev A – June 2023 Page 33 of 44

© 2023 Schneider Electric, all rights reserved

Internal

Internal
[ Release Notes ] EcoStruxure™ Building Operation 2023 v5.0.3 and SpaceLogic, EasyLogic controllers v5.00.03

5. Cybersecurity Vulnerability Disclosures


For information on security notifications refer to the link
https://www.se.com/ww/en/work/support/cybersecurity/security-notifications.jsp

For more information refer to the Schneider Electric Recommended Cybersecurity Best
Practices document https://www.se.com/us/en/download/document/7EN52-0390/.

Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.se.com
RN_EBO 2023_v5.0.3 Rev A – June 2023 Page 34 of 44

© 2023 Schneider Electric, all rights reserved

Internal

Internal
[ Release Notes ] EcoStruxure™ Building Operation 2023 v5.0.3 and SpaceLogic, EasyLogic controllers v5.00.03

6. Important Engineering Information


Important engineering information regarding EcoStruxure Building Operation v5.0.3 is listed
below. Please refer to the EBO v5.0.1, v5.0.2 release note section 6 for details of existing
engineering information.

Important engineering information with regard to the SpaceLogic Controller (MP-C/V, IP-
IO, and RP-C) is also listed below.

6.1 Builder for Function Block


With the introduction of the “Block style changes” and “Snap shapes to grid” in 5.0.2, a
slight adjustment to the cell grid system had to be made. This means that it is possible that
a few objects in existing programs can “jump” one cell, compared from their original
position in previous version of Builder for Function Block.

6.2 Builder View


Using Builder View on the root of an EcoStruxure Building Server (Central, Enterprise,
Automation, Edge) or a SpaceLogic/EasyLogic device can cause long loading times. This is
because Builder View must analyze all objects and bindings before it can render the view.
This analysis can take a long time, especially if there are a lot of objects and bindings.

Selecting the targeted folder or area in the system tree that you wish to evaluate, instead
of the root, can avoid longer load times.

6.3 SpaceLogic Series (MP-C/V, IP-IO, and RP-C) Factory Firmware


When first powering up a new SpaceLogic IP Series Controller it is important to verify that
the controller has the latest firmware build loaded for the version of EcoStruxure Building
Operation build being used. Please see the compatibility matrix in section 1 and section
appendix B for details on applying the latest firmware.

6.4 Restoring Optional Properties


This function has now been moved to the IP Controller level so optional properties that are
not available after upgrade can be restored. In particular for this release are the Bluetooth
settings, occupant App white list for the RP-C and the Sensor expansion module, and Room
unit properties.
Please note that if the object is a custom type it will need to be checked out before running
this command.

Any new object created with this release will contain the new properties, this command is
only applicable when upgrading from an earlier release.

Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.se.com
RN_EBO 2023_v5.0.3 Rev A – June 2023 Page 35 of 44

© 2023 Schneider Electric, all rights reserved

Internal

Internal
[ Release Notes ] EcoStruxure™ Building Operation 2023 v5.0.3 and SpaceLogic, EasyLogic controllers v5.00.03

6.5 DALI Energy Saving


With the introduction of the “Energy Saving” on DALI CRS module with Power Delivery in EBO 5.0.3,
a specific Discovery command must be executed on every module to allow the Energy saving to be
functional after upgrading an installation EBO to 5.0.3 version.
Indeed, in order to automatically open the Power Delivery relay of a terminal, the module must
first discover on which terminal each DALI light is connected to and thus the discovery command:
“Discover terminal only” must be executed in addition to enabling the new module property:
“Energy Saving”

Device Discovery view right after upgrading to 5.0.3:

Use the ‘Discover Terminals only’ command:

Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.se.com
RN_EBO 2023_v5.0.3 Rev A – June 2023 Page 36 of 44

© 2023 Schneider Electric, all rights reserved

Internal

Internal
[ Release Notes ] EcoStruxure™ Building Operation 2023 v5.0.3 and SpaceLogic, EasyLogic controllers v5.00.03

Device Discovery view updated with terminal information (and ready to support Power Saving):

Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.se.com
RN_EBO 2023_v5.0.3 Rev A – June 2023 Page 37 of 44

© 2023 Schneider Electric, all rights reserved

Internal

Internal
[ Release Notes ] EcoStruxure™ Building Operation 2023 v5.0.3 and SpaceLogic, EasyLogic controllers v5.00.03

APPENDIX A – Procedures
A1. Installing EcoStruxure Building Operation
For installation of EcoStruxure Building Operation v5.0.3 WorkStation, Enterprise Server,
Enterprise Central, please reference the Web Help for that topic.

A2. Upgrading EcoStruxure Building Operation (From previous


major releases)
Note1: This release is NOT supported on the original AS’s often referred to as AS classic.

Note2: If upgrading from v5.0.x to this release v5.0.3, please refer to section A3 below.
Warning: Upgrading from the pre-release (v5.0.1) bench tester build is not supported.

A2.1 System Upgrade Overview

A system upgrade can include an Enterprise Server Enterprise Central, one or more
automation servers and Workstations, and the supporting administrator software, such as
Device Administrator. For more information, see System Upgrade Overview

A2.1.1 Upgrade Enterprise Server and Enterprise Central


If your EcoStruxure BMS contains an Enterprise Server, use the Enterprise Server Upgrade
Workflow.

If your EcoStruxure BMS contains an Enterprise Central, use the Enterprise Central Upgrade
Workflow.

Note1:
Depending upon the size of the system and the quantity of trends, it is possible that the
database on the Enterprise Server/ could be quite large. When upgrading, always make
certain that you have at least twice as much disk space available as the size of your database.
It should also be expected that the Enterprise Server may appear to “hang” for as much as
20 to 30 minutes upon the first initial start-up after the upgrade, but only on the first start.

A2.1.2 Upgrading Automation Servers

To upgrade a single automation server or a series of standalone automation servers, use the
Automation Server System Upgrade Workflow.

You use Device Administrator to upgrade the automation server. You must upgrade Device
Administrator before you upgrade the automation server.

Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.se.com
RN_EBO 2023_v5.0.3 Rev A – June 2023 Page 38 of 44

© 2023 Schneider Electric, all rights reserved

Internal

Internal
[ Release Notes ] EcoStruxure™ Building Operation 2023 v5.0.3 and SpaceLogic, EasyLogic controllers v5.00.03

A2.1.3 Upgrading WorkStation and Client Tools Installation


To upgrade WorkStation, select editor tools and language packs, and use the Upgrading
WorkStation and Client Tools Installation.

Note:
In case of issues compiling or saving applications in WorkPlace Tech Editor, update Visio with
the latest Microsoft Office updates.
A3 Upgrading EcoStruxure Building Operation v5.0.x.x to v5.0.3
Warning: Ensure a backup is available for all servers to be upgraded before proceeding.
A3.1 Automation Server
Applying Hotfix on an AS-P/AS-B is performed using the Device Administrator (DA).

A3.2 Device Administrator Installation

The new v5.0.3 Device Administrator should be used by running the installer “Device
Administrator v5.0.3.117 - EcoStruxure Building – Software”

To apply a Hotfix on AS-P/AS-B, See Applying a Hotfix on an Automation Server

Warning: If the PC does not have access to the internet please refer to this topic in the
online help using another PC with internet access.
https://ecostruxure-building-help.se.com/bms/Topics/show.castle?id=13241&locale=en-
US&productversion=2023&a=1

A3.3 Enterprise Server


To apply the v5.0.3 maintenance release to an existing v5.0.x.x Enterprise Server (ES)
− Run the executable: Enterprise Server v5.0.3.117 - EcoStruxure Building - Software
A3.4 Enterprise Central
To apply the v5.0.3 maintenance release to an existing v5.0.x.x Enterprise Central (EC)
− Run the executable: Enterprise Central v5.0.3.117 - EcoStruxure Building - Software
A3.5 WorkStation
To apply the v5.0.3 maintenance release to an existing v5.0.x.x Workstation

− Stop the Workstation.


− Run the executable: WorkStation Hotfix v5.0.3.117- EcoStruxure Building –
Software
A3.6 License Administrator
To apply the v5.0.3 release to an existing v5.0.x License Administrator installation

Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.se.com
RN_EBO 2023_v5.0.3 Rev A – June 2023 Page 39 of 44

© 2023 Schneider Electric, all rights reserved

Internal

Internal
[ Release Notes ] EcoStruxure™ Building Operation 2023 v5.0.3 and SpaceLogic, EasyLogic controllers v5.00.03

− Run the installer License Administrator v5.0.3.117 - EcoStruxure Building - Software


(note; there is no hotfix installer).
A4 Extended Log Storage Schema
A4.1 PostgreSQL/TimescaleDB database schema

If you use External Log Storage, new scripts must be run in the PostgreSQL/TimescaleDB
database for EBO 5.0. The script “pg_install_db.sql” can handle schema upgrades from 3.0
and forward.

For more info, read WebHelp Topic: “Setting up a Database Schema in the PostgreSQL
Database”.
A4.2 MSSQL database schema
Use the workflow described here to install and configure the EcoStruxure BMS External Log
Storage feature using Microsoft SQL Server.

Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.se.com
RN_EBO 2023_v5.0.3 Rev A – June 2023 Page 40 of 44

© 2023 Schneider Electric, all rights reserved

Internal

Internal
[ Release Notes ] EcoStruxure™ Building Operation 2023 v5.0.3 and SpaceLogic, EasyLogic controllers v5.00.03

APPENDIX B – SpaceLogic, EasyLogic Controller Upgrade


Procedures

B1 Upgrading Controller Firmware


Warning for MP controllers and IP-IO: If upgrading from an IP controller that is currently at
v1.00.xx.xxxx the upgrade might fail the first time, if it does wait until the controller has
restarted and repeat the upgrade a second time.

Down-Rev from a factory installed 4.0 or 5.0 firmware IP Controller to “earlier” versions
It is important to note that any Down-Rev should be undertaken after hosting and prior to
connecting any external equipment ( beyond power and Ethernet connection) and prior to
downloading any application or undertaking any other configuration of the controller.

Warning for IP controllers: Down-Rev is NOT supported between versions once the
application is loaded onto the controller.

Using WorkStation, you can update the firmware of multiple BACnet/IP devices and their
attached SpaceLogic Sensor devices, RP controller expansion modules, and multi-sensors at
the same time with minimum downtime. In particular, the universal upgrade package
simplifies the update process and requires minimal user involvement and coordination. See
BACnet/IP Device Firmware Management for more information.

For more information on updating firmware, see Updating Firmware in BACnet/IP


Controllers.

B2 Upgrading CRS Module Firmware


The firmware for the CRS modules is contained within the RP-C firmware package. Online
CRS modules will be updated automatically once the RP-C firmware has been applied.
To view the upgrade status/progress, select the Room Bus folder and add properties as
below:

The upgrade is complete once the Firmware upgrade status returns to Normal, when it is
queued for upgrading the status shows ready and when downloading a percentage is
shown. Should the upgrade fail a warm start of the RP-C should be performed.

Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.se.com
RN_EBO 2023_v5.0.3 Rev A – June 2023 Page 41 of 44

© 2023 Schneider Electric, all rights reserved

Internal

Internal
[ Release Notes ] EcoStruxure™ Building Operation 2023 v5.0.3 and SpaceLogic, EasyLogic controllers v5.00.03

B3 Upgrading SpaceLogic Sensor Firmware


The SpaceLogic Sensor firmware is upgraded automatically as needed after the host
controller firmware is upgraded. There is new SpaceLogic Sensor firmware for this release
as shown below. It can be verified in the properties of the Room unit device or in the
Device Report.

WARNING: SpaceLogic and EasyLogic controllers update the SpaceLogic Sensor firmware in
the background after the upgrade process seems to be complete as viewed in the
Firmware Upgrade Viewer. It can take several minutes per SpaceLogic Sensor to transfer
files and restart them. During this time, SpaceLogic Sensor may appear offline and sensor
data will be unavailable.

Once the upgrade is complete, please refer to section 6.3 above regarding restoring
optional properties.

B4 Upgrading Remote-Control Firmware


The Remote Control will automatically update its firmware when paired to the Multi
Sensor and any key is pressed, after the Multi Sensor has finished upgrading.

B5 Verifying All Firmware Versions


If there is any question about what individual firmware versions are installed in a given
controller, the version information in the firmware package metadata file can be verified
against information in the controller’s device report.

Device Report for FW Controller Package 5.00.03.00030 in an RP-C:

Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.se.com
RN_EBO 2023_v5.0.3 Rev A – June 2023 Page 42 of 44

© 2023 Schneider Electric, all rights reserved

Internal

Internal
[ Release Notes ] EcoStruxure™ Building Operation 2023 v5.0.3 and SpaceLogic, EasyLogic controllers v5.00.03

NOTE: The BootApplet version is only upgraded if the current boot BootApplet doesn’t exceed the
minimum Boot Applet required to support the incoming firmware, consequently the BootApplet
version might not match to what is shown in the package metadata file.

To see all the versions in a package, select the following in the Firmware File Manager list and
navigate to Actions Tab and click on Open metadata file to view the Meta Data File:

Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.se.com
RN_EBO 2023_v5.0.3 Rev A – June 2023 Page 43 of 44

© 2023 Schneider Electric, all rights reserved

Internal

Internal
[ Release Notes ] EcoStruxure™ Building Operation 2023 v5.0.3 and SpaceLogic, EasyLogic controllers v5.00.03

Change History
Revision Date Revision Description/Change