0% found this document useful (0 votes)
30 views2 pages

RRRR

1) The document provides details of a trial and error analysis to design the reinforcement for an electric chiller replacement wall. 2) Key parameters determined include a required reinforcement area of 5.65 cm2 using 12 mm diameter bars spaced at 200 mm. 3) The analysis checked requirements for compression, moment, shear, and minimum reinforcement are satisfied. The design was determined to pass all checks.

Uploaded by

Aek Jan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
30 views2 pages

RRRR

1) The document provides details of a trial and error analysis to design the reinforcement for an electric chiller replacement wall. 2) Key parameters determined include a required reinforcement area of 5.65 cm2 using 12 mm diameter bars spaced at 200 mm. 3) The analysis checked requirements for compression, moment, shear, and minimum reinforcement are satisfied. The design was determined to pass all checks.

Uploaded by

Aek Jan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

PROJECT NAME ; Electric Chiller replacement 8000 RT DESIGN BY ; Aekkachai Jansiriwilaikun WALL NAME / DIRECTION ; VERT I BAR

BUILDING NAME ; PRV pit ( Step down Building ) FLOOR/ LEVEL ; WALL SIDE ; INSIDE & OUTSIDE OF WALL

Trial and error Eccentric Distance " e" find Balance section .

DB 12@200

e= 6.482 cm. covering = 4 cm.


fc' = 280 ksc. Use Re‐bar( DB/RB) = DB 12 mm
cb 6.283 fy = 4000 ksc. 15cm

/* Assume c = 6.283 cm. b = 100 cm.


β1 = 0.8 h = 15 cm. 100 cm
a = β1 c = 5.03 cm. d = 10.390 cm. , plastic centroid = 7.5 cm. [ wall Plan]
εy = 0.002

Es = 2040000 (1) (2) (3) (4) (5)


Concrete xi εsi fs As T Force Dist from Cc =0.85*fc'b β1 c Moment force Ref (1) X (Xi)

Reinforcement Bar (cm) (ksc) (cm²) (kg) Bottom bar (cm) Bottom bar position (kg.‐m)

Concrete 3.77 7.88 119628.3 942288.4 4509.75


Steel Layer 1 5 DB 12 1.673 0.00080 1629.6 5.65 9215 5.780 53263.6 154.17
Steel Layer 2 5 DB 12 ‐4.107 ‐0.00196 ‐4000.0 5.65 ‐22619 0 0 928.98
Steel Layer 6 0 DB 12 0 0.000 0 0.0
Steel Layer 7 0 DB 12 0 0.000 0 0.0
Steel Layer 8 0 DB 12 0 0.000 0 0.0
9.372 0.0527 995551.95 5592.9
Check!! ==> Pne ‐0.85fc'bβ1 c (h/2 ‐1/2β1c)‐ Fscysc ‐FstYst =995552/9.37‐5593/0.053=0 0.06
Trial & Error again No trial = Pass
Pn (kg) = 106224
At Balance section. Pu(kg) = ΦP n = 74356.8
Mu(kg*m) = ΦPnxe = 4820.0
Mode of Failure : = Balance failure
fsi < fy ?? = YES

Determine pure compression load at failure, Po


Po = 0.85fc'(Ag‐Ast) + Astfy = 399547 Kg.
øPo = 279683 Kg.
Determine pure moment at failure, Mo
Mo = AsFyd = 2350 Kg‐m.
øMo = 1645 Kg‐m.
Determine pure tension load at failure, Pt
Pt = Astfy = 45239 Kg.
øPt = 40715 Kg.

øP(Ton)
øPo=279.68

Interaction Diagram
Ultimate strength

øPb=74.36

øPc=1.72
1.62 1.718 øM(Ton‐m)
øMo=1.65 øMb=4.82
øPt=0.57

øPt=40.72
Check case of maximum compression.
moment force of member 0.800 Ton‐m.

Check compression side


Maximum compression force =
= 1.72 Ton <‐‐ 11.45 T/m^2 x1 m x 0.15m
Max bending moment from interaction diagram
Mu = 1.718 Ton‐m. > 0.8 O.K.

Check Shear force [ out plane shear , /wo not provide shear reinforcement]
Vu = 2.26 Ton. <‐‐ 15.09 T/m^2 x1 m x 0.15m
Nu = 1.72 Ton. [ + = comp, ‐ = tension ]
Check maximum shear strength permitted
λs = MIN(1, [ 2/ (1+0.04*d ) ]0.5 )
= 1.0000
ρw = 0.0006 <‐‐ use 50% of minimum long reinf bar ( 0.5x0.0012)
фVc = ɸ [ 2.1 λ λs (ρw)0.33 xfc'0.5 + Nu/(6Ag) ] xb wd ,
= 0.75x[ 2.1 x1x0.0006^0.33 x280^0.5 + 1720/(6*100x15) ]x100x10.39
= 2459.0 kg.
= 2.5 Ton > Vu, OK!!

therefore ‐‐> check spacing as minimum req (0.0012BH for vert, 0.002BH for Hor)
{ minimum rebar } per side wall [ VERT = 1, HOR = 2 ] ‐‐‐> 1
0.5x 0.0012BH = 0.5x 0.0012x 15x100
= 0.90 cm2
spacing = 200 mm.
Area re‐bar = [ 1 / 0.2]x1.13
= 5.65 cm2 >0.9 cm^2 PASS