CSC 18 JKV
CSC 18 JKV
PHAAM0810027C2
Air Conditioner
Indoor Unit Outdoor Unit
CS-C18JKV CU-C18JKV
CS-C24JKV CU-C24JKV
TABLE OF CONTENTS
PAGE PAGE
1 Safety Precautions----------------------------------------------- 3 10.5. High Voltage Power Supply Printed Circuit
2 Specifications ----------------------------------------------------- 5 Board-------------------------------------------------------- 18
3 Features ------------------------------------------------------------- 7 11 Installation Instruction ---------------------------------------- 19
4 Location of Controls and Components ------------------- 8 11.1. Select the Best Location ------------------------------- 19
4.1. Product Overview------------------------------------------ 8 11.2. Indoor Unit ------------------------------------------------- 20
5 Dimensions--------------------------------------------------------- 9 11.3. Outdoor Unit----------------------------------------------- 24
5.1. Indoor Unit & Remote Control -------------------------- 9 12 Operation Control----------------------------------------------- 28
5.2. Outdoor Unit -----------------------------------------------10 12.1. Cooling Operation---------------------------------------- 28
6 Refrigeration Cycle Diagram --------------------------------11 12.2. Soft Dry Operation --------------------------------------- 29
7 Block Diagram----------------------------------------------------12 12.3. Automatic Operation ------------------------------------ 30
8 Wiring Connection Diagram ---------------------------------13 12.4. Indoor Fan Speed Control ----------------------------- 31
8.1. CS-C18JKV CU-C18JKV ------------------------------13 12.5. Outdoor Fan Speed Control --------------------------- 32
8.2. CS-C24JKV CU-C24JKV ------------------------------14 12.6. Vertical Airflow Direction Control --------------------- 33
9 Electronic Circuit Diagram -----------------------------------15 12.7. Horizontal Airflow Direction Control ----------------- 33
10 Printed Circuit Board-------------------------------------------16 12.8. Powerful Operation -------------------------------------- 34
10.1. Main Printed Circuit Board -----------------------------16 12.9. Quiet Operation------------------------------------------- 34
10.2. Power Printed Circuit Board ---------------------------17 12.10. Timer Control---------------------------------------------- 35
10.3. Indicator Printed Circuit Board ------------------------18 12.11. Random Auto Restart Control ------------------------ 35
10.4. Receiver Printed Circuit Board ------------------------18 12.12. Remote Control Signal Receiving Sound ---------- 35
12.13. Patrol Operation ------------------------------------------ 36
2
1 Safety Precautions
• Read the following “SAFETY PRECAUTIONS” carefully before perform any servicing.
• Electrical work must be installed or serviced by a licensed electrician. Be sure to use the correct rating of the power plug and
main circuit for the model installed.
• The caution items stated here must be followed because these important contents are related to safety. The meaning of each
indication used is as below. Incorrect installation or servicing due to ignoring of the instruction will cause harm or damage, and
the seriousness is classified by the following indications.
• Carry out test run to confirm that no abnormality occurs after the servicing. Then, explain to user the operation, care and
maintenance as stated in instructions. Please remind the customer to keep the operating instructions for future reference.
15. Keep away from small children, the thin film may cling to nose and mouth and prevent breathing.
16. Do not use unspecified cord, modified cord, joint cord or extension cord for power supply cord. Do not share the single outlet with
other electrical appliances. Poor contact, poor insulation or over current will cause electrical shock or fire.
17. Tighten the flare nut with torque wrench according to specified method. If the flare nut is over-tightened, after a long period, the flare
may break and cause refrigerant gas leakage.
3
18. During pump down operation, stop the compressor before remove the refrigeration piping. (Removal of compressor while compressor
is operating and valves are opened will cause suck-in of air, abnormal high pressure in refrigeration cycle and result in explosion,
injury etc.)
19. During installation, install the refrigerant piping properly before run the compressor. (Operation of compressor without fixing
refrigeration piping and valves at opened condition will caused suck-in of air, abnormal high pressure in refrigeration cycle and result
in explosion, injury etc).
20. After completion of installation or service, confirm there is no leakage or refrigerant gas. It may generate toxic gas when the
refrigerant contacts with fire.
21. Ventilate if there is refrigerant gas leakage during operation. It may cause toxic gas when the refrigerant contacts with fire.
22. Do not insert your fingers or other objects into the unit, high speed rotating fan may cause injury.
23. Must not use other parts except original parts described in catalog and manual.
1. Do not install the unit at place where leakage of flammable gas may occur. In case gas leaks and accumulates at surrounding of the
unit, it may cause fire.
2. Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and damage
the furniture.
3. Tighten the flare nut with torque wrench according to specified method. If the flare nut is over-tightened, after a long period, the flare
may break and cause refrigerant gas leakage.
4. Do not touch outdoor unit air inlet and aluminium fin. It may cause injury.
9. Installation or servicing work. It may need two people to carry out the installation or servicing work.
10. Do not install this appliance in a laundry room or other location where water may drip from the ceiling, etc.
11. Do not sit or step on the unit, you may fall down accidentally.
12. Do not touch the sharp aluminum fin, sharp parts may cause injury.
4
2 Specifications
MODEL INDOOR CS-C18JKV CS-C24JKV
OUTDOOR CU-C18JKV CU-C24JKV
Performance Test Condition NEW JIS NEW JIS
Phase, Hz Single, 60 Single, 60
Power Supply
V 220 220
kW 5.30 7.03
Capacity BTU/h 18100 24000
kJ/h 19100 25300
Running Current A 8.0 12.0
Cooling
Output Power W 40 40
QLo rpm 670 750
Lo rpm 1020 1110
Speed Me rpm 1110 1230
Hi rpm 1200 1350
SHi rpm 1370 1500
Type Propeller Fan Propeller Fan
Material PP Resin PP Resin
Outdoor Fan
5
MODEL INDOOR CS-C18JKV CS-C24JKV
OUTDOOR CU-C18JKV CU-C24JKV
Pipe Diameter (Liquid / Gas) mm (inch) 6.35 (1/4) / 12.70 (1/2) 6.35 (1/4) / 15.88 (5/8)
Standard Length m (ft) 5.0 (16.4) 5.0 (16.4)
Piping
1. Cooling capacities are based on indoor temperature of 27°C Dry Bulb (80.6°F Dry Bulb), 19.0°C Wet Bulb (66.2°F Wet Bulb)
and outdoor air temperature of 35°C Dry Bulb (95°F Dry Bulb), 24°C Wet Bulb (75.2°F Wet Bulb)
2. Specifications are subjected to change without prior notice for further improvement.
6
3 Features
• E-ion Air Purifying System with Patrol Sensor
- Active e-ions are released to catch dust particles and bring them back the large positively charged filter
- Patrol Sensor color changes to indicate the dirt level in the air
• Quality Improvement
- Random auto restart after power failure for safety restart operation
- Gas leakage protection
- Prevent compressor reverse cycle
- Inner protector to protect compressor
- Noise prevention during soft dry operation
- Blue coated condenser for high resistance to corrosion
• Operation Improvement
- Quiet mode to reduce the indoor unit operating sound
- Powerful mode to reach the desired room temperature quickly
- 24-hour timer setting
7
4 Location of Controls and Components
4.1. Product Overview
4.1.1. Indoor Unit
8
5 Dimensions
5.1. Indoor Unit & Remote Control
5.1.1. CS-C18JKV CS-C24JKV
9
5.2. Outdoor Unit
5.2.1. CU-C18JKV CU-C24JKV
10
6 Refrigeration Cycle Diagram
11
7 Block Diagram
12
8 Wiring Connection Diagram
8.1. CS-C18JKV CU-C18JKV
Note: Resistance at 20°C of ambient temperature. Note: Resistance at 20°C of ambient temperature.
13
8.2. CS-C24JKV CU-C24JKV
14
9 Electronic Circuit Diagram
15
10 Printed Circuit Board
10.1. Main Printed Circuit Board
16
10.2. Power Printed Circuit Board
17
10.3. Indicator Printed Circuit Board
18
11 Installation Instruction
11.1. Select the Best Location 11.1.3. Indoor/Outdoor Unit Installation
Diagram
11.1.1. Indoor Unit
• Do not install the unit in excessive oil fume area such as
kitchen, workshop and etc.
• There should not be any heat source or steam near the unit.
• There should not be any obstacles blocking the air
circulation.
• A place where air circulation in the room is good.
• A place where drainage can be easily done.
• A place where noise prevention is taken into consideration.
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from the wall, ceiling,
fence or other obstacles.
• Recommended installation height for indoor unit shall be at
least 2.5 m.
19
11.2. Indoor Unit
11.2.1. How to Fix Installation Plate 11.2.2. To Drill a Hole in the Wall and Install
The mounting wall shall be strong and solid enough to prevent a Sleeve of Piping
it from the vibration. 1. Insert the piping sleeve to the hole.
2. Fix the bushing to the sleeve.
3. Cut the sleeve until it extrudes about 15 mm from the
wall.
Caution
When the wall is hollow, please be sure to use the sleeve
for tube ass’y to prevent dangers caused by mice biting
the connecting cable.
Model Dimension
C7***, C9***,
C12***,
RS-C7**, 485 mm 82 mm 165 mm 158 mm 43 mm 95 mm
RS-C9**,
RS-C12**
C18***, C24***,
C28***,
585 mm 82 mm 165 mm 158 mm 169 mm 219 mm
RS-C18**,
RS-C24**
20
1. For the right rear piping
21
(This can be used for left rear piping and bottom piping also.)
22
b) OUTDOOR POWER SUPPLY MODEL (3.0HP)
Connecting cable between indoor unit and outdoor
unit shall be approved polychloroprene sheathed 4 x
1.5 mm2 (3/4 ~ 3.0HP) flexible cord, type designation
245 IEC 57 or heavier cord.
• Ensure the colour of wires of outdoor unit and the terminal Nos. are the same to the indoor’s respectively.
• Earth wire shall be Yellow/Green (Y/G) in colour and longer than other AC wires for safety reason.
23
11.3. Outdoor Unit
11.3.1. Install the Outdoor Unit
• After selecting the best location, start installation according to Indoor/Outdoor Unit Installation Diagram.
1. Fix the unit on concrete or rigid frame firmly and horizontally by bolt nut (ø10 mm).
2. When installing at roof, please consider strong wind and earthquake. Please fasten the installation stand firmly with bolt or
nails.
Model A B C D
C7***, RU-C7** 474 mm 87 mm 18.5 mm 261 mm
C9***, RU-C9**
C12***, RU-C12** 570 mm 105 mm 18.5 mm 320 mm
C18***, RU-C18** 612.5 mm 131 mm 19 mm 383 mm
C24***, RU-C24**
C28***
24
4(A). Checking gas leakage for left piping
1) a. Connect the manifold gauge to the service port of 3-way valve.
b. Measure the pressure.
2) a. Keep it for 5-10 minutes.
b. Ensure that the pressure indicated on the gauge is the same as that of measured during the first time.
Evacuation (vacuum method) is recommended, for model 2.0 HP ~ 3.0 HP with the piping length more than 5 meter.
1. Connect a charging hose with a push pin to the Low side of a charging set and the service port of the 3-way valve.
• Be sure to connect the end of the charging hose with the push pin to the service port.
2. Connect the center hose of the charging set to a vacuum pump.
3. Turn on the power switch of the vacuum pump and make sure that the needle in the gauge moves from 0 cmHg (0 MPa) to
-76 cmHg (-0.1 MPa). Then evacuate the air approximately ten minutes.
4. Close the Low side valve of the charging set and turn off the vacuum pump. Make sure that the needle in the gauge does not
move after approximately five minutes.
Note: BE SURE TO TAKE THIS PROCEDURE IN ORDER TO AVOID REFRIGERANT GAS LEAKAGE.
5. Disconnect the charging hose from the vacuum pump and from the service port of the 3-way valve.
6. Tighten the service port caps of the 3-way valve at a torque of 18 N•m with a torque wrench.
7. Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to “OPEN” using a hexagonal
wrench (4 mm).
8. Mount valve caps onto the 2-way valve and the 3-way valve.
• Be sure to check for gas leakage.
25
• If gauge needle does not move from 0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa), in step above take the following measure:
- If the leak stops when the piping connections are tightened further, continue working from step .
- If the leak does not stop when the connections are retightened, repair the location of leak.
- Do not release refrigerant during piping work for installation and reinstallation.
- Take care of the liquid refrigerant, it may cause frostbite.
3. Secure the cable onto the control board with the holder.
4. Attach the control board cover back to the original
position with screw.
5. For wire stripping and connection requirement, refer to
instruction of indoor unit.
26
5. Secure the power supply cord and connecting cable onto the control board with the holder.
6. Attach the control board cover back to the original position with screw.
7. For wire stripping and connection requirement, refer to instruction of indoor unit.
• Note: Isolating Devices (Disconnecting means) should have minimum 3.0 mm contact gap.
• Earth wire shall be Yellow/Green (Y/G) in colour and longer than other AC wires for safety reason.
27
12 Operation Control
12.1. Cooling Operation
• Cooling operation can be set using remote control.
• This operation is applied to cool down the room temperature reaches the setting temperature set on the remote control.
• The remote control setting temperature, which takes the reading of intake air temperature sensor, can be adjusted from 16°C to
30°C.
• During cooling operation, the compressor will stop running and restart as shown in figure below.
28
12.2. Soft Dry Operation
• Soft Dry operation can be set using remote control.
• Soft Dry operation is applied to dehumidify and to perform a gentle cooling to the room.
• This operation starts when the intake air temperature sensor reaches the setting temperature on the remote control.
• When operation begins, Soft Dry will be switched “ON” for a maximum 10 minutes, then Soft Dry operation will be turned “OFF”
for a minimum 6 minutes. After that, the Soft Dry operation will be “ON” and “OFF” based on the setting temperature as shown in
figure below.
• However after 3 minutes of compressor off, during Soft Dry “OFF” (within 6 minutes Soft Dry restart control), the indoor unit will
start to operate at normal Cooling mode if the intake temperature is higher than Cooling “ON” point.
29
12.3. Automatic Operation
• Automatic operation can be set using remote control.
• This operation starts to operate with indoor fan at SLo speed for 20 seconds to judge the intake air temperature.
• After judged the temperature, the operation mode is determined by referring to the below standard.
• Then, the unit start to operate at determined operation mode, until it is switched off using remote control, with the setting
temperature as shown in below table.
• The setting temperature for all the operations can be changed one level up or one level down from the standard temperature as
shown in below table by pressing on the temperature up or temperature down button at remote control.
• The operation mode judging temperature and standard setting temperature can be increased by 2°C permanently, by open the
circuit of JX03 at printed circuit board indoor unit.
30
12.4. Indoor Fan Speed Control
• Indoor Fan Speed can be set using remote control.
31
• Auto Fan Speed during Soft Dry operation:
1. Indoor fan will rotate alternately between off and Lo-.
2. At the beginning of each compressor start operation, indoor fan will increase fan speed gradually for deodorizing purpose.
3. When compressor at turn off condition for 6 minutes, indoor fan will start fan speed at Lo- to circulate the air in the room.
This is to obtain the actual reading of intake air temperature.
32
12.6. Vertical Airflow Direction Control
12.6.1. Auto Control
• When the vertical airflow direction is set to Auto using the
remote control, the louver swings up and down as shown in
the diagram.
• When stopped with remote control, the discharge vent is
reset, and stop at the closing position.
• During Cooling operation or Soft Dry operation, indoor fan
motor may stop to rotate at certain periods. At that condition,
the louver will stop swinging and rest at the upper limit.
33
12.8. Powerful Operation
• To achieve the setting temperature quickly.
• When Powerful operation is set, the setting temperature will be automatically decreased 3°C internally against the present
setting temperature (Lower temperature limit: 16°C).
• This operation automatically will be running under SHi Fan Speed (Cooling).
• Vertical Airflow Direction:-
- In “Manual” setting, the vane will automatically shift down 10° lower than previous setting.
- In “Auto” setting, the vane will automatically swing up and down. However the lower limit will be shifted 10° downward.
• Powerful operation stops when:-
- Powerful operation has operate for 15 minutes.
- Powerful mode button is pressed again.
- Stopped by OFF/ON operation button
- Timer OFF activates.
- Quiet mode button is pressed.
- Operation mode is changed.
34
12.10. Timer Control
12.10.1. ON Timer
• When the ON Timer is set by using the remote control, the unit will start to operate slightly before the set time, so that the room
will reach nearly to the set temperature by the set time.
• For Cooling and Soft Dry operation, the operation will start 15 minutes before the set time.
• For Automatic operation, the indoor fan will operate at SLo speed for 20 seconds, 15 minutes before the set time to detect the
intake air temperature to determine the operation mode. The operation indication lamp will blink at this time.
35
12.13. Patrol Operation
• To monitor air dirtiness level by using Patrol sensor and to maintain air freshness by activates e-ion operation.
• Patrol operation stop condition (when any of the following condition is fulfilled):
- When “OFF/ON” button is pressed.
- During any operation with Patrol, “Patrol” button is pressed again.
- When “e-ion” button is pressed.
- When OFF Timer activates.
36
• Dirtiness level sensitivity adjustment.
It is possible to change the Patrol sensor sensitivity, where the Threshold value (G1 ~ G4) will be shifted accordingly:
1. Press and release “SET” button.
2. Press “Timer ” / “Timer ” button to select sensitivity.
(Air 1“Low Sensitivity” <–> Air 2 “Standard” (Default) <–> Air 3 “High Sensitivity”)
3. Confirm setting by pressing “Timer Set” button. LCD returned to original display after 2 seconds.
4. LCD returned to original display if remote control does not operate for 30 seconds.
• e-ion Control
- e-ion operation starts condition
- When dirtiness at level 2 (Patrol LED turns red).
- 2 minutes after stabilization time (Patrol LED turns red).
- 4 hours at level 0 (Patrol LED turns red).
- e-ion operation time
- If dirtiness level improves from level 2 to level 1 (Patrol LED from red to orange), the unit carries out level change after 60
seconds.
- When dirtiness level returns to level 0 (Patrol LED turns blue) continuously for 11 minutes or more, e-ion operation stops.
- Indicator
- When Patrol operation starts, Patrol LED is ON with 3 different colors:
37
- Remote Control Receiving Sound
- Timer Control
- When ON timer activates when unit stops, previous operation resumes and restored last saved patrol operation status.
- When ON timer activates during any operation, no change and carry on current operation.
- When OFF timer activates during any operation, all operation stops and the latest patrol operation status is saved.
- During demo, all operation stops, remote control buttons and auto OFF/ON button are ignored.
- Patrol Operation Demo Mode stop condition.
• Press “Patrol” button for 5 seconds and release.
• Power supply reset.
38
12.14. e-ion Operation
• This operation provides clean air by producing negative ions to attract dust captured at the positively charged e-ion filters.
• Timer control
- When ON timer activates when unit stops, previous operation resumes and restored last saved e-ion operation status.
- When ON timer activates during any operation, no change and carry on current operation.
- When OFF timer activates during any operation, all operation stops and the latest e-ion operation status is saved.
• Indicator
- When e-ion operation starts, e-ion indicator ON.
39
• Power failure
- During e-ion individual operation, if power failure occurs, after power resumes, e-ion individual operation resumes
immediately.
- During combination operation, if power failure occurs, after power resumes, combination operation resume immediately.
- e-ion operation status is not memorized after OFF the unit. After OFF, when the operation is ON again, air conditioner
operates without e-ion operation.
• Troubleshooting Methods
- Connect the connector or stop operation (include during Patrol operation) to cancel the blinking.
• Troubleshooting Method
- Press “e-ion” button or “OFF/ON” button to stop the operation and check the e-ion AIR PURIFYING SYSTEM main
connector to PCB.
- After that, press “e-ion” button again to confirm the e-ion indicator not blinking.
- The 24 times counter will be clear after 10 minutes of normal operation or when operation stops.
• Troubleshooting Method
- Press “e-ion” button or “OFF/ON” button to stop the operation.
- Change main circuit board or filter's high voltage power supply.
- When lo-feedback voltage supplied to e-ion AIR PURIFYING SYSTEM during e-ion operation, e-ion indicator and Timer
indicator stop blinking.
40
13 Protection Control
13.1. Restart Control (Time Delay Safety Control)
• When the thermo-off temperature (temperature which compressor stops to operate) is reached during:-
- Cooling operation - the compressor stops for 3 minutes (minimum) before resume operation.
- Soft Dry operation - the compressor stops for 6 minutes (minimum) before resume operation.
• If the operation is stopped by the remote control, the compressor will not turn on within 3 minutes from the moment operation
stop, although the unit is turn on again within the period.
• This phenomenon is to balance the pressure inside the refrigerant cycle.
41
• This is to prevent compressor from rotate reversely when there is an instantaneous power failure.
• If this condition happens continuously for 5 times within 50 minutes, unit will turn OFF with TIMER LED blinks.
• The 5 times counter can be reset when either one of the following condition happen:
- Unit is OFF by remote control or AUTO OFF/ON button.
- Indoor intake temperature - Indoor piping temperature > 5°C for 1 minute or more.
- Operation mode change.
• The unit could be ON by pressing OFF/ON button at remote control but the TIMER LED will continue blinking.
• TIMER LED blinking will be reset if:
- Indoor intake temperature - indoor pipe temperature > 5°C for 1 minute or more
- Power supply reset.
42
14 Servicing Mode
14.1. Auto OFF/ON Button
After Auto OFF/ON Button is pressed, the 20 seconds counter for Remote Control Receiving Sound OFF/ON Mode is
restarted.
• Under various setting mode, after select the transmission code combination of remote control, press any button of remote
control to transmit a signal to indoor unit. The transmission code will be stored in EEPROM.
• After signal is received, the various setting mode is cancelled and return to normal operation.
• If there is no code is transmitted or AUTO OFF/ON button is not pressed within 20 seconds, the Various Setting mode will
be cancelled.
43
14.2. Remote Control Button
14.2.1. SET BUTTON
• To check current remote control transmission code and store the transmission code to EEPROM.
- Press “SET” button for more than 10 seconds.
- Press “TIMER SET” button until a “beep” sound is heard as confirmation of transmission code change.
14.2.4. TIMER
• To change indoor unit indicator’s LED intensity.
- Press continuously for 5 seconds.
14.2.5. TIMER
• To change remote control display from Degree Celsius to Degree Fahrenheit.
- Press continuously for 10 seconds.
44
15 Troubleshooting Guide
15.1. Refrigeration cycle system
In order to diagnose malfunctions, make sure that there are no
electrical problems before inspecting the refrigeration cycle.
Such problems include insufficient insulation, problem with the
power source, malfunction of a compressor and a fan.
The normal outlet air temperature and pressure of the
refrigeration cycle depends on various conditions, the standard
values for them are shown in the table to the right.
45
15.1.1. Relationship between the condition of the air conditioner and pressure and electric
current
Cooling Mode
Condition of the air
conditioner Low Pressure High Pressure Electric current during operation
Insufficient refrigerant
(gas leakage)
Inefficient compression
• Carry out the measurements of pressure, electric current, and temperature fifteen minutes after an operation is started.
• Electric current during operation becomes approximately 20% lower than the normal value.
Insufficient compressing of a compressor • The discharge tube of the compressor becomes abnormally hot (normally 70 to 90°C).
• The difference between high pressure and low pressure becomes almost zero.
• Electric current reaches a high level abnormally, and the value exceeds the limit of an
ammeter. In some cases, a breaker turns off.
Locked compressor
• The compressor has a humming sound.
46
16 Disassembly and Assembly Instructions
WARNING
High voltages are generated in the electrical parts area by the capacitor. Ensure that the capacitor has discharged sufficiently before proceeding
with repair work. Failure to heed this caution may result in electric shocks.
16.1. Indoor Electronic Controllers, Cross Flow Fan and Indoor Fan Motor
Removal Procedures
16.1.1. To remove front grille
47
16.1.3. To remove electronic controller
48
16.1.4. To remove discharge grille
49
16.1.6. To remove cross flow fan and indoor fan motor
50
16.1.7. To align cross flow fan
51
17 Technical Data
17.1. Thermostat Characteristics
Cooling
Soft Dry
52
17.2. Operation Characteristics
17.2.1. CS-C18JKV CU-C18JKV
53
54
17.2.2. CS-C24JKV CU-C24JKV
55
56
18 Exploded View and Replacement Parts List
18.1. Indoor Unit
Note
The above exploded view is for the purpose of parts disassembly and replacement.
The non-numbered parts are not kept as standard service parts.
57
REF. NO. PART NAME & DESCRIPTION QTY. CS-C18JKV CS-C24JKV
1 CHASSY COMPLETE 1 CWD50C1623 ←
2 FAN MOTOR 1 L6CBYYYL0037 ARW7614AC
3 CROSS FLOW FAN COMPLETE 1 CWH02C1077 ←
4 BEARING ASS’Y 1 CWH64K007 ←
5 SCREW - CROSS FLOW FAN 1 CWH551146 ←
6 ION GENERATOR 1 CWH94C0028 ←
7 EVAPORATOR CO. 1 CWB30C2772 CWB30C2774
8 FLARE NUT (LIQUID) 1 CWT251026 ←
9 FLARE NUT(GAS) 1 CWT251035 CWT251036
10 E-ION AIR PURIFYING SYSTEM 1 CWD93C1090 ←
11 CLIP FOR SENSOR 1 CWH32143 ←
12 CONTROL BOARD CASING 1 CWH102370 ←
13 TERMINAL BOARD COMPLETE 1 CWA28C2356 ←
14 ELECTRONIC CONTROLLER - MAIN 1 CWA73C3742 CWA73C3737
15 ELECTRONIC CONTROLLER - POWER 1 CWA745303 CWA745620
16 ELECTRONIC CONTROLLER - HVU 1 CWA745348 ←
17 ELECTRONIC CONTROLLER - INDICATOR 1 CWA745299 ←
18 ELECTRONIC CONTROLLER - RECEIVER 1 CWA745288 ←
19 SENSOR COMPLETE 1 CWA50C2401 ←
20 CONTROL BOARD TOP COVER 1 CWH131350 ←
21 INDICATOR HOLDER 1 CWD933021 ←
22 CONTROL BOARD FRONT COVER 1 CWH13C1183 ←
23 DISCHARGE GRILLE COMPLETE 1 CWE20C3007 ←
24 FULCRUM 2 CWH621103 ←
25 VERTICAL VANE 15 CWE241289 ←
26 CONNECTING BAR 1 CWE261156 ←
27 CONNECTING BAR 1 CWE261158 ←
28 CONNECTING BAR 1 CWE261157 ←
29 CONNECTING BAR 1 CWE261159 ←
30 CONNECTING BAR 1 CWE261160 ←
31 A.S.MOTOR, DC SINGLE 12V300 OHM 1 CWA98K1014 ←
32 A.S.MOTOR, DC SINGLE 12V300 OHM 1 CWA981154J ←
33 LEAD WIRE - COMPLETE (AIR SWING MOTOR) 1 CWA67C8221 ←
34 CAP - DRAIN TRAY 1 CWH521096 ←
35 HORIZONTAL VANE COMPLETE 1 CWE24C1295 ←
36 BACK COVER CHASSIS 1 CWD933031 ←
37 REMOTE CONTROL COMPLETE 1 CWA75C3155 ←
38 FRONT GRILLE COMPLETE 1 CWE11C4256 ←
39 INTAKE GRILLE COMPLETE 1 CWE22C1483 ←
40 GRILLE DOOR COMPLETE 1 CWE14C1029 ←
41 E-ION FILTER 2 CWD00K1015 ←
42 SCREW - FRONT GRILLE 4 XTT4+16CFJ ←
43 CAP - FRONT GRILLE 3 CWH521194 ←
44 DRAIN HOSE 1 CWH851063 ←
45 INSTALLATION PLATE 1 CWH361098 ←
46 BAG COMPLETE - INSTALLATION SCREW 1 CWH82C067 ←
47 OPERATING INSTRUCTION 1 CWF566341 ←
48 INSTALLATION INSTRUCTION 1 CWF613788 ←
49 INSTALLATION INSTRUCTION 1 CWF613772 ←
50 INSTALLATION INSTRUCTION 1 CWF613790 ←
51 P.S.CORD 1 CWA20C2829 CWA20C2836
(NOTE)
• All parts are supplied from PHAAM, Malaysia (Vendor Code: 00029488).
• “O” marked parts are recommended to be kept in stock.
58
18.2. Outdoor Unit
Note:
The above exploded view is for the purpose of parts disassembly and replacement.
The non-numbered parts are not kept as standard service parts.
59
REF. NO. PART NAME & DESCRIPTION QTY. CU-C18JKV CU-C24JKV
1 CHASSY ASS’Y 1 CWD50K2115 CWD50K2100
2 COMPRESSOR 1 2K25S236F6A 2J39S236A1A
3 ANTI - VIBRATION BUSHING 3 CWH50055 ←
4 NUT - COMPRESSOR MOUNT 3 CWH561049 ←
5 PACKING 3 CWB81043 ←
6 CONDENSER 1 CWB32C2691 CWB32C2692
7 SOUND PROOF BOARD 1 CWH151051 ←
8 FAN MOTOR BRACKET 1 CWD541065 ←
9 SCREW - FAN MOTOR BRACKET 2 CWH551217 ←
10 FAN MOTOR 1 CWA951401J CWA951399J
11 SCREW - FAN MOTOR MOUNT 3 CWH55252J ←
12 PROPELLER FAN ASS’Y 1 CWH03K1017 ←
13 NUT - PROPELLER FAN 1 CWH561038J ←
14 HOLDER COUPLING 1 CWH351036 ←
15 2-WAY VALVE (LIQUID) 1 CWB021484 ←
16 CAPILLARY TUBE ASS’Y 1 CWB15K1252 CWB15K1282
17 3-WAY VALVE (GAS) 1 CWB011483 CWB011484
18 TERMINAL COVER 1 CWH171011 CWH171012
19 NUT - TERMINAL COVER 1 CWH7080300J ←
20 CAPACITOR - F.M 1 DS441355NPQA ←
21 CAPACITOR - COM. 1 CWA312078 CWA312088
22 HOLDER CAPACITOR 1 CWH30060 CWH30071
23 TERMINAL BOARD ASS’Y 1 CWA28K1064J ←
24 CABINET SIDE PLATE 1 CWE041255A ←
25 HANDLE 1 CWE161010 ←
26 CABINET SIDE PLATE COMPLETE 1 CWE04C1123 ←
27 HANDLE 2 CWE16000E ←
28 CABINET FRONT PLATE ASS’Y 1 CWE06K1043 ←
29 CABINET TOP PLATE ASS’Y 1 CWE03K1009A ←
30 CONTROL BOARD COVER (RIGHT-TOP) 1 CWH131169A ←
31 CONTROL BOARD COVER COMPLETE 1 CWH131168 ←
32 STRAINER 1 CWB11025 ←
33 THERMOSTAT 1 — CWA151061
34 SOUND PROOF MATERIAL 1 CWG302278 ←
35 OVERLOAD PROTECTOR WITH WIRE 1 CWA67C7546 —
36 WIRE NET 1 CWD041041A ←
37 HOLDER - O.L.P. 1 CWH7041200 —
(NOTE)
• All parts are supplied from PHAAM, Malaysia (Vendor Code: 00029488).
• “O” marked parts are recommended to be kept in stock.