7SR11 and 7SR12 Argus Catalogue Sheet
7SR11 and 7SR12 Argus Catalogue Sheet
7SR11 and 7SR12 Argus Catalogue Sheet
Protection
Devices
Energy Management
7SR11 and 7SR12 Argus
Overcurrent Relays
Supervision
60CTS CT Supervision
74T/CCS Trip & Close Circuit Supervision
60VTS VT Supervision
Control
79 Auto Reclose
86 Lockout
CB Control
Features
Cold Load Settings
Four Settings Groups
Password Protection – 2 levels
User Programmable Logic
Self Monitoring
Description Circuit Breaker Trip and Maintenance Counter
Trip Timers
The 7SR11 & 7SR12 are overcurrent protection relays
developed to enhance the Argus family of products by
providing a familiar product using the latest generation of
User Interface
hardware technology.
The 7SR11provides overcurrent and earth fault protection, 20 Character x 4 Line Backlit LCD
the 7SR12 comes with additional voltage inputs providing Menu Navigation Keys
directional protection. Both relays are available in single and 9 User Programmable Tri-colour LEDs
four pole variants. User Language Configuration
Housed in a 4U high, size E4 or E6 (Optional IEC61850 mod-
el) cases, these relays provide protection, monitoring, in-
strumentation and metering with integrated input and out- Monitoring Functions
put logic, data logging & fault reports. Communication ac-
cess to the relay functionality is via a front USB port for local
PC connection, a rear electrical RS485 port for remote con- Primary/Secondary Current Phases and Earth
Direction
nection & optional IEC61850 communication through two
Primary/Secondary Line and Phase Voltages
rear Ethernet ports (Electrical or Optical).
Apparent Power and Power Factor
Real and Reactive Power
Function Overview W Hr & VAr Hr Forward and Reverse
Historical Demand Record
Positive Phase Sequence (PPS) Voltage & Current
Protection Negative Phase Sequence (NPS) Voltage & Current
37 Undercurrent Zero Phase Sequence (ZPS) Voltage
46BC Broken Conductor / Load Unbalance Frequency
46NPS Negative Phase Sequence Overcurrent Direction
49 Thermal Overload Binary Input/Output status
50 Instantaneous Overcurrent Trip circuit healthy/failure
50G/N/SEF Instantaneous Earth Fault Time and date
50AFD Arc Flash Detection (6 zones) Starters
50BF Circuit Breaker Fail Fault records
51 Time Delayed Overcurrent Event records
51G/N/SEF Time Delayed Measured/Derived/Sensitive EF Energy
64H High Impedance REF Circuit breaker trip counters
27/59 Under/Over Voltage I2t summation for contact wear
47 Negative Phase Sequence Voltage
51V Voltage Controlled Overcurrent
59N Neutral Voltage Displacement Hardware
67/50 Directional Instantaneous Overcurrent
67/50G/N Directional Instantaneous Earth Fault 1 CT 3 Binary Inputs 5 Binary Outputs
67/51 Directional Time Delayed Overcurrent 4 CT 3 Binary Inputs 5 Binary Outputs
67/51G/N Directional Time Delayed Earth Fault 4 CT 6 Binary Inputs 8 Binary Outputs
32 Directional Power 4 CT 4 Bin.In. 8 Bin.Out. (segregated rear terminals)
32S Directional Sensitive Power 1 CT 3 VT 3 Binary Inputs 5 Binary Outputs
55 Power Factor 4 CT 3 VT 3 Binary Inputs 5 Binary Outputs
81HBL2 Inrush Detector 4 CT 3 VT 6 Binary Inputs 8 Binary Outputs
81 Under/Over Frequency 4 CT 3 VT 4 Bin. In. 8 Bin.Out. (segregated rear terminals)
Line Check/Switch onto Fault
FUNCTIONAL REQUIREMENT
Standard Communication Ports
7SR1102-1*A**-*[C/D]A0
7SR1102-1*A12-*AA0
7SR1101-1*A**-**A0
7SR1101-3*A**-**A0
7SR1102-3*A**-**A0
7SR1204-2*A**-**A0
7SR1204-4*A**-**A0
7SR1205-2*A**-**A0
7SR1205-4*A**-**A0
Front USB port + Rear RS485 port
FUNCTION
2x Electrical RJ45 Ethernet ports
2x LC Fibre Optic Ethernet ports
27 Undervoltage ■ ■ ■ ■
Standard Protocols
32 Directional Power ■ ■
IEC60870-5-103, DNP3.0 or Modbus RTU 32S Directional Sensitive Power ■
User Selectable with programmable data points 37 Undercurrent ■ ■ ■ ■ ■ ■ ■ ■
46BC Broken Conductor / Load Unbalance ■ ■ ■ ■ ■
Optional Protocols Negative Phase Sequence
46NPS ■ ■ ■ ■
IEC61850 (E6 Case) Overcurrent
47 Negative Phase Sequence Voltage ■ ■
Measurands 51SEF
Measured Time Delayed Sensitive
■ ■ ■ ■
Earth Fault
Commands 51N Derived Time Delayed Earth Fault ■ ■ ■ ■ ■
Time Synchronism 55 Power Factor ■ ■
59 Overvoltage
Viewing and Changing Settings ■ ■ ■ ■
59N Neutral Voltage Displacement ■ ■ ■ ■
High Impedance Restricted Earth
64H ■ ■ ■ ■ ■ ■ ■ ■ ■
Application 67
Fault
Directional Overcurrent ■ ■
67G Directional Measured Earth Fault ■ ■
67SEF Directional Sensitive Earth Fault ■ ■
The Argus is a numerical overcurrent protection relay 67N Directional Derived Earth Fault ■ ■
intended for use on distribution and industrial networks. It 81HBL Inrush Detector ■ ■ ■ ■ ■ ■
provides a highly comprehensive functional software 81 Under/Over Frequency ■ ■ ■ ■
package with a range of integral application functions aimed CONTROL / MONITOR
at reducing installation, wiring and engineering time. 51c Cold Load - Phase Only ■ ■ ■ ■
An extensive range of metered values can be viewed on the 60CTS CT Supervision ■ ■ ■ ■ ■
front LCD or at a remote point via the communication 60VTS VT Supervision ■ ■ ■ ■
channel. 74T/CC
Trip & Close Circuit Supervision ■ ■ ■ ■ ■ ■ ■ ■ ■
S
The integrated control feature allows operation of a single
79 Autoreclose □ □ □ □
circuit breaker and monitoring of its trip and close circuits
86 Lockout ■ ■ ■ ■ ■ ■ ■ ■ ■
(except 7SR1102-1*A12-*AA0 models).
Line Check/SOTF ■ ■ ■ ■ ■ ■ ■ ■
Notes
1. Items shown dotted are only available in some
models; please refer to the Ordering Information
Section.
2. The use of some functions are mutually exclusive
49 Thermal Overload
The thermal algorithm calculates the thermal states from the Time
(sec)
measured currents and can be applied to lines, cables and
transformers. Alarm outputs are given for thermal overload
and thermal capacity. 10
Long Time Inverse
60VTS VT Supervision
100
The VT supervision uses a combination of negative phase
sequence voltage and negative phase sequence current to
detect a VT fuse failure. This condition may be alarmed or
Time used to inhibit voltage dependent functions. Element has
(sec)
user operate and delay settings.
RS485 Screened
Ext Wire loop to
twisted pair
To Control System Include line
terminating Res
14 14
16 16
18 18
20
Screens connected
Fig 8. Example of Control Function View RS485 Screened
externally to de vice
Re ar terminals
twisted pair
Communications Editor
To facilitate easier interfacing to a substation the relays
default Protocol configuration may be modified using the
communication editor software tool.
The communication editor is a PC based software package
provided within the Reydisp software suite which allows
modification of the IEC60870-5-103, DNP 3.0 and MODBUS
Fig 10. Typical Reydisp Evolution Screenshot Protocols.
Fig 15. Front view of relay (E4 Case with push buttons)
User
Function
Label
Large LCD
Multi-
coloured
Programmable
LED’s
from fascia
LCD
A 4 line by 20 character liquid crystal display with power
save operation indicates the relay identifier, settings,
instrumentation, fault data and control commands.
Up to 6 user programmable general alarms can be
configured to display your own indications on the LCD.
LEDs
A green steadily illuminated LED indicates the ‘Protection
Healthy’ condition.
9 user programmable LEDs are available eliminating the
need for expensive panel mounted pilot lights and
associated wiring. Each LED is tri-color (red, green, yellow)
allowing for clear indication of the associated function’s
state and has a label insert for identification.
Relay Information
The device is identified by the rating label on the fascia. The
user can also give the device its own identity by editing the
‘Relay Identifier’ displayed on the LCD or space is provided to
place a slip in label giving the relays function.
Auxiliary Supply
Unit Design
Rated DC Voltage 24-250V DC
Operating Range 19.2 to 275V Housing E4 or E6(see dimension
Allowable superimposed 12% of DC voltage drawing)
ac component Indication 20 Character 4 line Display
Relay Healthy LED
Rated AC Voltage 100-230 VAC 50/60Hz
9 Tri Coloured User
Range 80 to 253 V rms AC
Programmable Self or Hand
50/60Hz ±5%
Reset LED’s
Power Consumption: Min (DC) 3.6W(6.1W with
With-drawable Element Yes
IEC61850)
Max (DC) 8.4W (11W with User Interface 5 Navigation Keys
IEC61850) Weight Typical 3.1Kg
Min (AC) 9VA (14.5VA with IP Rating installed with IP 51 from front
Max (AC) IEC61850) cover
17VA (23VA with IP Rating installed without IP 20 from front
IEC61850) cover
Allowable breaks/dips in DC 50ms
supply (collapse to zero) AC 2.5/3 cycles
@50/60Hz
Seismic
IEC 60255-27 & IEC 60255-21-3 Class I
EN100 Fibre Optic Data Communication Interface
(IEC 61850 Option) Type Level Variation
X-plane -
Physical layer Fibre-optic 3.5mm
displacement
Connectors Duplex LC 100BaseF in acc. below crossover
With IEEE802.3 freq (8-9Hz) 1gn
and above
Recommended fibre 62.5/125 m glass fibre with Seismic response 5%
Y-plane –
Duplex-LC connector
1.5mm
Transmission Speed 100 MBits/s
displacement
Optical Wavelength 1300 nm below crossover
Bridgeable distance freq (8-9Hz)
2 km
0.5gn above
Data Storage
Operation – 7SR12 only Non directional, Forward or 50AFD Arc Flash Detector
reverse
Elements Phase, Derived Earth, Measured Number of Zones 6, segregated outputs with and
Earth & SEF without current supervision.
Number of Elements 2/4 x OC Setting Range Is 1,2…10 x In
2 x 7SR11 2/4 x Derived EF ‘N’ Operate Level Iop 100% Is, ±5% or ±1%xIn
4 x 7SR12 2/4 x Measured EF ‘G’ where Reset level 95 % Iop
fitted
Operate time: 50AFD Overcurrent
2/4 x SEF where fitted
<16ms
AFD Zone Operate Time
Setting Range Is 0.05,0.06…50 x In
<25ms
SEF 0.005…5 x In
Time Delay 0.00…14400s
Operate Level Iop 100% Is, ±5% or ±1%xIn
50BF Circuit Breaker Fail
Reset level 95 % Iop
Operate time: Operation Current check - Phase and
50 0 to 2xIs – 35ms, ±10ms, Measured Earth with
0 to 5xIs – 25ms, ±10ms independent settings
50N 0 to 2xIs – 40ms, ±10ms, Mechanical Trip
0 to 5xIs – 30ms, ±10ms CB Faulty Monitor
Operate time following Tbasic +td , ±1% or ±10ms Setting Range Is 0.05,0.055…2.0 x In
delay 2 Stage Time Delays Timer 1 20…60000ms
Inhibited by Binary or Virtual Input Timer 2 20…60000ms
Inrush detector Operate Level 100% Is, ±5% or ±1%xIn
VT Supervision Disengaging time < 20ms
Operate time following Tcbf ±1% or ±2ms
51(67) Time Delayed OC&EF (Directional) delay
Triggered by Any function mapped as trip
Operation – 7SR12 only Non directional, Forward or contact.
reverse Inhibited by Binary/Virtual Input
Elements Phase, Derived Earth, Measured Timer By pass Yes, 50BF CB Faulty Input
Earth & SEF
Number of Elements 2/4 x OC
2 x 7SR11 2/4 x Derived EF ‘N’ 55 Power factor (7SR12)
4 x 7SR12 2/4 x Measured EF ‘G’
2/4 x SEF where fitted Number of Elements 2
Characteristic IEC NI,VI,EI,LTI ANSI MI,VI,EI & Operation Under or Over,
DTL Lead or Lag
Setting Range Is 0.05,0.06…2.5 x In U/C Guard 0.05 to 1.0
SEF 0.005…0.5 x In
Setting Range PFs 0.05 to 0.99
Time Multiplier 0.025,0.030…1.6,1.7…5,6...100 Time Delays 0 to 14400s
Time Delay 0,0.01… 20s
Operate Level ± 0.05
Operate Level 105% Is, ±4% or ±1%xIn
Basic Operate time ≤ 70ms
Minimum Operate time
Operate time following tbasic +td ± 1% or ± 10ms
IEC top
K
Tm delay
IsI 1 Inhibited by Undercurrent Guard, VTS
ANSI A
top P B Tm
Is 1
I
5 % absolute or 30 ms
16 Siemens Protection Devices Limited
59N Neutral Voltage Displacement 81 Under/Over Frequency
79 AutoReclose
Typical
FRONT
when SIDE VIEW
VIEW
fitted
98.5
Diameter 3.6 - 4 holes (see note)
NOTE:
THE 3.6 HOLES ARE FOR M4 THREAD FORMING (TRILOBULAR) SCREWS.
THESE ARE SUPPLIED AS STANDARD AND ARE SUITABLE FOR USE IN
FERROUS / ALUMINIUM PANELS 1.6mm THICK AND ABOVE. FOR OTHER E4
PANELS, HOLES TO BE M4 CLEARANCE (TYPICALLY 4.5 DIAMETER) AND PANEL CUT-
RELAYS MOUNTED USING M4 MACHINE SCREWS, NUTS AND OUT
LOCKWASHERS (SUPPLIED IN PANEL FIXING KIT).
10.25 78
Fig 18. E4 Case Dimensions
Alternative 4BI+8BO
2
+ve B +ve
3 without common terminals
-ve BI 1 BI 4 -ve +ve
4 1 3
+ve +ve BI 4 -ve
6 5 1
BI 2 BI 5
-ve
8 5
+ve +ve
10 7 BO 6 7
-ve BI 3 BI 6
12 9
9 BO 7 11
14 A
BO 6 11 13
16 Screen
BO 7 13 BO 8 15
18 B
BO 8 15
20 Term. B
+ve
22
-ve
24
1 2 1 2
28 GND.
IEC61850
Data B A
1A Comms
13
A 3
(Optional)
14 BO 1 1
5A IL1
15 2
16 4 27 28 27 28
1A
17 BO 2 6
Rear View
18 5 Arrangement of terminals and modules
5A IL2
19
20
8
1A BO 3 NOTES
21
7
22 BI = Binary Input
5A IL3 10 BO = Binary Output
23 BO 4
9
24
1A 12
25 BO 5
11 Shows contacts internal to relay
26
IL4
case assembly.
5A
27 Contacts close when the relay
28 chassis is withdrawn from case
Fig20. Diagram showing 7SR11 relay with 4 CT inputs, up to 6 binary inputs and 8 binary outputs.
RS485
Fig21. Diagram showing 7SR12 relay with 4 CT inputs, 3 VT inputs, up to 6 binary inputs and 8 binary outputs.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Measuring Input
1/5 A, 50/60Hz1) 1 A/C/D
1/5 A, 50/60Hz with SEF Input 2) 3 C/D
Auxiliary voltage
PSU Rated: 24-250V DC / 100-230V AC. BI threshold 19V DC (Rated: 24-250V DC) M
PSU Rated: 24-250V DC / 100-230V AC. BI threshold 88V DC (Rated: 110-250V DC) N
Communication Interface
Standard version – included in all models, USB front port, RS485 rear port (E4 Case) 1 2
Standard version – plus additional rear electrical Ethernet RJ45 (x2), E6 Case 6) 7 7 C/D
Standard version – plus additional rear optical Ethernet duplex (x2), E6 Case 6 ) 8 7 C/D
Protocol
IEC 60870-5-103 Modbus RTU and DNP3 (user selectable) 2
IEC 60870-5-103 Modbus RTU, DNP3 and IEC 61850 (user selectable settings) 6) 7
Relay Cover
Standard Version – No Push Buttons 1
Push Buttons – Down and Right Arrows 2
Standard version C
37 Undercurrent
46BC3) Broken conductor/load unbalance
46NPS3) Negative phase sequence overcurrent
493) Thermal overload
503) Instantaneous phase fault overcurrent
50AFD Arc Flash Detection
50BF3) Circuit breaker fail
50G/50N Instantaneous earth fault
50SEF2) Instantaneous sensitive earth fault
513) Time delayed phase fault overcurrent
51G/51N Time delayed earth fault
51SEF2) Time delayed sensitive earth fault
60CT3) CT Supervision
64H High Impedance REF
74T/CC Trip and Close circuit supervision
81HBL2 4) 2nd harmonic block/inrush restraint
51C3) Cold load pickup
86 Hand reset contacts
Programmable logic
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Additional Functionality
No Additional Functionality A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Directional O/C 7 S R 1 2 0 - A - A 0
Relay (Argus)
Directional
overcurrent
and earth fault Protection Product
protection relay Overcurrent – Directional 2
Measuring Input
1/5 A, 40 to 160 V, 50/60Hz1) 2
1/5 A, 40 to 160 V, 50/60Hz with SEF Input2) 4
Auxiliary voltage
PSU Rated: 24-250V DC / 100-230V AC. BI threshold 19V DC (Rated: 24-250V DC) M
PSU Rated: 24-250V DC / 100-230V AC. BI threshold 88V DC (Rated: 110-250V DC) N
Communication Interface
Standard version – included in all models, USB front port, RS485 rear port (E4 Case) 1 2
Standard version – plus additional rear electrical Ethernet RJ45 (x2), E6 Case 5) 7 7
Standard version – plus additional rear optical Ethernet duplex (x2), E6 Case 5 ) 8 7
Protocol
IEC 60870-5-103, Modbus RTU and DNP3 (user selectable) 2
IEC 60870-5-103 Modbus RTU, DNP3 and IEC 61850 (user selectable settings) 5) 7
Relay Cover
Standard Version – No Push Buttons 1
Push Buttons – Down and Right Arrows 2
Additional Functionality
No Additional Functionality A
EMEA-C10028-00-76GB
Sept 2022