TeSys Deca Contactors - LC1D09BD

Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

Product data sheet

Specifications

IEC contactor, TeSys Deca,


nonreversing, 9A, 5HP at 480VAC,
up to 100kA SCCR, 3 phase, 3 NO,
24VDC coil, open style
LC1D09BD

Product availability : Stock - Normally stocked in distribution


facility

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Price* : 119.00 USD

Main
Range of Product TeSys Deca

Product or Component Type Contactor

Device short name LC1D

Contactor application Motor control


Resistive load

Utilisation category AC-4


AC-1
AC-3
AC-3e

Poles description 3P

[Ue] rated operational voltage Power circuit <= 690 V AC 25...400 Hz


Power circuit <= 300 V DC

[Ie] rated operational current 9 A 140 °F (60 °C)) <= 440 V AC AC-3 power circuit
25 A 140 °F (60 °C)) <= 440 V AC AC-1 power circuit
9 A 140 °F (60 °C)) <= 440 V AC AC-3e power circuit

[Uc] control circuit voltage 24 V DC

Complementary
Motor power kW 2.2 kW 220...230 V AC 50/60 Hz AC-3)
4 kW 380...400 V AC 50/60 Hz AC-3)
4 kW 415...440 V AC 50/60 Hz AC-3)
5.5 kW 500 V AC 50/60 Hz AC-3)
5.5 kW 660...690 V AC 50/60 Hz AC-3)
2.2 kW 400 V AC 50/60 Hz AC-4)
2.2 kW 220...230 V AC 50/60 Hz AC-3e)
4 kW 380...400 V AC 50/60 Hz AC-3e)
4 kW 415...440 V AC 50/60 Hz AC-3e)
5.5 kW 500 V AC 50/60 Hz AC-3e)
5.5 kW 660...690 V AC 50/60 Hz AC-3e)

Maximum Horse Power Rating 1 hp 230/240 V at AC 50/60 Hz for 1 phase


2 hp 200/208 V at AC 50/60 Hz for 3 phase
2 hp 230/240 V at AC 50/60 Hz for 3 phase
5 hp 460/480 V at AC 50/60 Hz for 3 phase
7.5 hp 575/600 V at AC 50/60 Hz for 3 phase
0.33 hp 115 V at AC 50/60 Hz for 1 phase

Compatibility code LC1D

Pole contact composition 3 NO

Contact compatibility M4

Protective cover With

* Price is “List Price” and may be subject to a trade discount – check with your local distributor or retailer for actual price.

Oct 12, 2023 1


[Ith] conventional free air 25 A 140 °F (60 °C) power circuit
thermal current 10 A 140 °F (60 °C) signalling circuit

Irms rated making capacity 250 A 440 V power circuit IEC 60947
140 A AC signalling circuit IEC 60947-5-1
250 A DC signalling circuit IEC 60947-5-1

Rated breaking capacity 250 A 440 V power circuit IEC 60947

[Icw] rated short-time withstand 105 A 104 °F (40 °C) - 10 s power circuit
current 210 A 104 °F (40 °C) - 1 s power circuit
30 A 104 °F (40 °C) - 10 min power circuit
61 A 104 °F (40 °C) - 1 min power circuit
100 A - 1 s signalling circuit
120 A - 500 ms signalling circuit
140 A - 100 ms signalling circuit

Associated fuse rating 10 A gG signalling circuit IEC 60947-5-1


25 A gG <= 690 V type 1 power circuit
20 A gG <= 690 V type 2 power circuit

Average impedance 2.5 mOhm - Ith 25 A 50 Hz power circuit

Power dissipation per pole 1.56 W AC-1


0.2 W AC-3
0.2 W AC-3e

[Ui] rated insulation voltage Power circuit 690 V IEC 60947-4-1


Power circuit 600 V CSA
Power circuit 600 V UL
Signalling circuit 690 V IEC 60947-1
Signalling circuit 600 V CSA
Signalling circuit 600 V UL

Overvoltage category III

Pollution degree 3

[Uimp] rated impulse withstand 6 kV IEC 60947


voltage

Safety reliability level B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1

Mechanical durability 30 Mcycles

Electrical durability 0.6 Mcycles 25 A AC-1 <= 440 V


2 Mcycles 9 A AC-3 <= 440 V
2 Mcycles 9 A AC-3e <= 440 V

Control circuit type DC standard

Coil technology Built-in bidirectional peak limiting diode suppressor

Control circuit voltage limits 0.1...0.25 Uc -40…158 °F (-40…70 °C) drop-out DC


0.7...1.25 Uc -40…140 °F (-40…60 °C) operational DC
1...1.25 Uc 140…158 °F (60…70 °C) operational DC

Inrush power in W 5.4 W 68 °F (20 °C))

Hold-in power consumption in 5.4 W 68 °F (20 °C)


W

Operating time 53.55...72.45 ms closing


16...24 ms opening

Time constant 28 ms

Maximum operating rate 3600 cyc/h 140 °F (60 °C)

Connections - terminals Power circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²) flexible without cable end
Power circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²) flexible without cable end
Power circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²) flexible with cable end
Power circuit screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²) flexible with cable end
Power circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²) solid without cable end
Power circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²) solid without cable end
Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²) flexible without cable end
Control circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²) flexible without cable end
Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²) flexible with cable end
Control circuit screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²) flexible with cable end
Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²) solid without cable end
Control circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²) solid without cable end

Tightening torque Power circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm
Power circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2
Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm
Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2
Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals pozidriv No 2
Power circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals pozidriv No 2

2
Oct 12, 2023
Auxiliary contact composition 1 NO + 1 NC

Auxiliary contacts type Mechanically linked 1 NO + 1 NC IEC 60947-5-1


Mirror contact 1 NC IEC 60947-4-1

Signalling circuit frequency 25...400 Hz

Minimum switching voltage 17 V signalling circuit

Minimum switching current 5 mA signalling circuit

Insulation resistance > 10 MOhm signalling circuit

Non-overlap time 1.5 ms on de-energisation between NC and NO contact


1.5 ms on energisation between NC and NO contact

Mounting Support Plate


Rail

Environment
Standards CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
IEC 60335-1

Product Certifications LROS (Lloyds register of shipping)


CSA
UL
GOST
DNV
CCC
GL
BV
RINA
UKCA

IP degree of protection IP20 front face IEC 60529

Protective treatment THIEC 60068-2-30

Climatic withstand IACS E10 exposure to damp heat


IEC 60947-1 Annex Q category D exposure to damp heat

Permissible ambient air -40…140 °F (-40…60 °C)


temperature around the device 140…158 °F (60…70 °C) with derating

Operating altitude 0...9842.52 ft (0...3000 m)

Fire resistance 1562 °F (850 °C) IEC 60695-2-1

Flame retardance V1 conforming to UL 94

Mechanical robustness Vibrations contactor open 2 Gn, 5...300 Hz)


Vibrations contactor closed 4 Gn, 5...300 Hz)
Shocks contactor open 10 Gn for 11 ms)
Shocks contactor closed 15 Gn for 11 ms)

Height 3.03 in (77 mm)

Width 1.77 in (45 mm)

Depth 3.74 in (95 mm)

Net Weight 1.06 lb(US) (0.48 kg)

Ordering and shipping details


Category 22355-CTR,TESYS D,OPEN,9-38A DC

Discount Schedule I12

GTIN 3389110353075

Returnability Yes

Country of origin ID

Oct 12, 2023 3


Packing Units
Unit Type of Package 1 PCE

Number of Units in Package 1 1

Package 1 Height 1.97 in (5.000 cm)

Package 1 Width 3.62 in (9.200 cm)

Package 1 Length 4.37 in (11.100 cm)

Package 1 Weight 18.41 oz (522.000 g)

Unit Type of Package 2 S02

Number of Units in Package 2 15

Package 2 Height 5.91 in (15.000 cm)

Package 2 Width 11.81 in (30.000 cm)

Package 2 Length 15.75 in (40.000 cm)

Package 2 Weight 17.99 lb(US) (8.160 kg)

Unit Type of Package 3 P06

Number of Units in Package 3 240

Package 3 Height 29.53 in (75.000 cm)

Package 3 Width 23.62 in (60.000 cm)

Package 3 Length 31.50 in (80.000 cm)

Package 3 Weight 302.65 lb(US) (137.280 kg)

Offer Sustainability
Sustainable offer status Green Premium product

California proposition 65 WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony
trioxide, which is known to the State of California to cause cancer. For more information go to
www.P65Warnings.ca.gov

REACh Regulation REACh Declaration

EU RoHS Directive Compliant


EU RoHS Declaration

Mercury free Yes

China RoHS Regulation China RoHS declaration


Product out of China RoHS scope. Substance declaration for your information.

RoHS exemption information Yes

Environmental Disclosure Product Environmental Profile

Circularity Profile End of Life Information

PVC free Yes

Contractual warranty
Warranty 18 months

4
Oct 12, 2023
Product data sheet LC1D09BD
Dimensions Drawings

Dimensions

(1) Minimum electrical clearance

LC1 D09…D18 D093…D123 D099…D129

b 77 99 80

c without cover or add-on blocks 93 93 93

with cover, without add-on blocks 95 95 95

c1 with LAD N or C (2 or 4 contacts) 126 126 126

c2 with LA6 DK10 138 138 138

c3 with LAD T, R, S 146 146 146

with LAD T, R, S and sealing cover 150 150 150

Oct 12, 2023 5


Product data sheet LC1D09BD
Connections and Schema

Wiring

6
Oct 12, 2023
Product data sheet LC1D09BD
Technical Illustration

Dimensions

CONTACTOR WITH AC COIL

CONTACTOR WITH DC COIL

Recommended replacement(s)

Oct 12, 2023 7

You might also like