Building Lighting Protection Calculation (1.1.19)
Building Lighting Protection Calculation (1.1.19)
Calculations:
Collection Area: (Ac) 7794.7104 Meter2
Probable No of Strikes to Building / Structure :(P) 0.001558942 No's/Year
Overall Multiplying Factor : (M) 0.06120
Overall Risk Factor Calculated: (xc) 9.54073E-05
Base Area of Structure:
2
Base Area of Structure: ( Ab) 2622 Meter
Perimeter of Structure: (P) 314 Meter
Base Area (Ab) > 100 Meter2 Yes >
Results:
Calculated Overall Risk Factor Calculated > Maximum Acceptable Overall Risk Factor
Lightning Protection is Required. 1
No's of Down Conductors:
Down Conductors As per Base Area of Structure:(s) 9 No's
Down Conductors As per Perimeter of Structure: (t) 10 No's
Required No's of Down Conductors 9 No's