Building Lighting Protection Calculation (1.1.19)

This document contains calculations to determine if lightning protection is required for a building and how many down conductors would be needed. It provides details on the building dimensions and factors like flash density and risk. The results show the calculated overall risk factor is higher than the maximum acceptable level, so lightning protection is required. Based on the base area and perimeter of the structure, 9 down conductors would be needed.

Uploaded by

mohammed ali
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
52 views1 page

Building Lighting Protection Calculation (1.1.19)

This document contains calculations to determine if lightning protection is required for a building and how many down conductors would be needed. It provides details on the building dimensions and factors like flash density and risk. The results show the calculated overall risk factor is higher than the maximum acceptable level, so lightning protection is required. Based on the base area and perimeter of the structure, 9 down conductors would be needed.

Uploaded by

mohammed ali
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Building / Structure Lighting Protection Calculations

Calculations As per IS-2309 Jignesh.N.Parmar, www.electricalnotes.wordpress.com


Area of Building / Structure:
Length of the Building : (L) 138.00 Meter
Width of the Building :(W) 19.00 Meter
Height of the Building: (H) 14.40 Meter

Lightning Flash Density:


Number of Thunderstorm: (N) 5.00 Days/Year
Lightning Flash Density : (Ng) 0.2 km2/Year
Application of Structure :(A) Houses & Buildings 0.3
Type of Constructions :(B) Reinforced concrete without Metal Roof 0.4
Conteats or Consequential Effects: (C) Schools / hoapitals / Childern Homes 1.7
Degree of Isolations: (D) Structure located in a area of the same height 1
Type of Country: (E) Flat country at any level 0.3
Maximum Acceptable Overall Risk Factor 0.000001 >

Calculations:
Collection Area: (Ac) 7794.7104 Meter2
Probable No of Strikes to Building / Structure :(P) 0.001558942 No's/Year
Overall Multiplying Factor : (M) 0.06120
Overall Risk Factor Calculated: (xc) 9.54073E-05
Base Area of Structure:
2
Base Area of Structure: ( Ab) 2622 Meter
Perimeter of Structure: (P) 314 Meter
Base Area (Ab) > 100 Meter2 Yes >

Results:
Calculated Overall Risk Factor Calculated > Maximum Acceptable Overall Risk Factor
Lightning Protection is Required. 1
No's of Down Conductors:
Down Conductors As per Base Area of Structure:(s) 9 No's
Down Conductors As per Perimeter of Structure: (t) 10 No's
Required No's of Down Conductors 9 No's