Abstract The purpose of this paper is to highlight the in order to extend their useful life or to be able to be reused
advantages of applying a preventive and corrective maintenance [7-12].
method in relation to the life of the insulation system of the
transformers in operation. This paper proposes a maintenance Insulating oils in operating equipment undergo a slow but
method based on the revitalization of the insulation of power constant degradation process. Progressive degradation and
transformers, in order to extend their life. Two case studies are premature aging result from various phenomena that occur
presented, and the results of the measurements made before and during the operation of electrical equipment.
after the revitalization process support the requirements of a Dissolved and suspended metal and cellulosic particles
preventive and corrective maintenance method.
along with other polar degradation products are impurities
Keywords: transformer, insulation, oil, revitalisation, that increase the rate of degradation and shorten the useful
mentenance life of electrical equipment. Therefore, the failure potential of
electrical equipment is directly related to the liquid insulating
I. INTRODUCTION
material.
Extending the life of electrical equipment has become a Treating the insulating liquid can extend the lifetime of the
primary condition in ensuring energy efficiency at the SEN transformer and ensure its optimal operation. Oil treatment
(National Energy System) level. methods are presented in specialized literature and applied by
Transformers are essential elements in electrical power the companies that deal with the maintenance of transformers
distribution systems, thus in the last decades, there has been a in operation, this work presents two case studies, which prove
shift from time-based maintenance strategy to condition- the effectiveness of the application of treatment processes in
based and risk-based maintenance. In this context, asset the case of transformers in operation to ensure a maintenance
managers are constantly looking to optimize their use. As efficient.
transformer diagnostic techniques have improved in recent The treatment process whose results are presented was
years, operators have sought techniques, measures and carried out with an installation based on synthetic adsorbents
methods to extend the life of transformers installed in the that uses the principle of adsorption to remove water and
system. polar elements from oil and solid insulation, applying the
From these considerations, the margin is currently applied percolation method under pressure.
to the application of predictive and corrective maintenance in The work supports a maintenance based on the
order to extend their life and ensure an acceptable level of revitalization of the insulation of power transformers, in order
reliability of the transformer in particular [1-7]. to extend their life. The installation used to remove water and
The life of power transformers is generally determined by polar elements from the transformer insulation uses synthetic
the life of the paper-oil insulation system, if the mechanical adsorbents [13-14].
stability of the electrical insulating paper is lost, there is a risk Transformer oil regeneration is an important preventive
of dielectric defects and total shutdowns of the transformer. maintenance tool, and therefore transformer oil must be
The aging of solid insulation must be monitored treated before it reaches levels of deterioration known to
continuously or at least periodically because its degradation cause transformer insulation failure [15-19].
process is final compared to the degradation of oils. The purpose of this work is to highlight the advantages of
Preventive and corrective maintenance is encouraged in order applying a preventive and corrective maintenance in terms of
to extend its life. the lifetime of the insulation system of the transformers in
Insulating oil is of essential importance in ensuring the operation.
efficient operation of the transformer, which due to the The application of reconditioning/regeneration/revitaliza-
specific production technology has high costs. tion processes to extend the lifetime of transformers has a
The primary resources from which these oils are derived major economic impact, and by reusing used oil, primary
are limited and thus, in order to save them, it is necessary to natural resources are preserved and environmental
carry out reconditioning/regeneration/revitalization processes contamination with such residual waste is avoided.
According to the DGA, the CO2/CO ratio has a value that IV. CONCLUSIONS
indicates a moderate state of paper degradation. This
indicates a moderate aging of the solid insulation system, the Whether the treatment of the transformer oil is done inside
causes of which, high humidity and the oxidative process, are or outside the tank, and on-line or off-line, depends mainly on
determined by the analysis of furan compounds. economic and production considerations.
The results of the electrical and physicochemical Regenerating transformer oil in the transformer tank should
measurements presented in table II indicate that the be at least 30% - 60% cheaper than the alternative of
transformer has a high humidity level, which requires the draining, washing and refilling the transformer with
treatment of the insulation system. regenerated oil. By following an oil maintenance program,
Before carrying out the treatment process, the necessary the accumulation of moisture and sludge in the solid
repairs were made to the OLTC to eliminate the leakage insulation of the transformer can be prevented.
problems of its tank relative to the main tank of the It has been shown that the regeneration process is less
transformer. demanding on the insulation of the transformer than the
The applied treatment brings an important contribution to alternative process of draining, washing and refilling the
the improvement of the physico-chemical/electrical transformer with new oil, thus avoiding long periods of
parameters of the insulation system (see tables II and III). interruption and consequently loss of profit.
Extending the life of a transformer, by implementing a transformers,” Proceedingss of the Sixty-sixth Annual International
Conferince of Doble Clients, 1999.
preventive transformer maintenance strategy from the ouset is [10] D. O Adekoya and I. A. Adejumobi, “Analysis of acidic properties of
the most cost-effective approach. distribution transformer oil insulation: a case study of jericho (nigeria)
The results obtained in the case of the two studies distribution network,” Nigerian Journal of Technology (NIJOTECH),
Vol. 36, No. 2, April 2017, pp. 563 – 570,
presented in this paper support the implementation of http://dx.doi.org/10.4314/njt.v36i2.32.
predictive and corrective maintenance to extend the life of the [11] A.-M. Aciu, M. -C. Nițu and D. Ștefan, "Extending the Life of
insulation system. Transformer Units Through Maintenance Based on Insulation
Revitalization," 2022 International Conference and Exposition on
If the transformer oil is regenerated/revitalized as soon as Electrical And Power Engineering (EPE), Iasi, Romania, 2022, pp. 37-
the acidity level exceeds the minimum permissible limits set 42, doi: 10.1109/EPE56121.2022.9959783.
by the standards, the degradation of the transformer oil, the [12] Aciu A-M, Nicola C-I, Nicola M, Nițu M-C. Complementary Analysis
for DGA Based on Duval Methods and Furan Compounds Using
wet condition of the core, the formation of sludge and the Artificial Neural Networks. Energies. 2021; 14(3):588.
subsequent breakdown of the transformer insulation can be https://doi.org/10.3390/en14030588
prevented and the life of the transformer can be extended. [13] J. S. N'cho, I. Fofana, A. Beroual, T. Aka-Ngnui and J. Sabau, “Aged
oils reclamation: Facts and arguments based on laboratory studies,” in
ACKNOWLEDGMENT IEEE Transactions on Dielectrics and Electrical Insulation, vol. 19, no.
5, pp. 1583-1592, October 2012, doi: 10.1109/TDEI.2012. 6311504.
This work was carried out through the Core Program [14] L. Safiddine, A.H.-Z. Zafour, I. Fofana, A. Skender, F. Guerbas, A.
Boucherit, “Transformer oil reclamation by combining several
within the National Research Development and Innovation strategies enhanced by the use of four adsorbents.” The Institution of
Plan 2022-2027, carried out with the support of MCID, Engineering and Technology, IET Generation, Transmission &
project no. PN 23 33 02 03. Distribution, 2017, ISSN 1751-8687, pp.1-9, doi: 10.1049/iet
gtd.2016.1995.
REFERENCES [15] CEI/IEC 60296:2020 - Fluids for electrotechnical applications –
Mineral insulating oils for electrical equipment. Publication date:
[1] CIGRÉ Brochure 227 - Life Management Techniques For Power 26.06.2020, Edition 5, pages 82.
Transformers, WG A2.18, January 2003, pages 125. [16] L. Safiddine, H.-Z. Zafour, U.M. Rao, I. Fofana, “Regeneration of
[2] CIGRÉ Brochure 445 - Guide for Transformer Maintenance, W.G. Transformer Insulating Fluids Using Membrane Separation
A2.34, February 2011, ISBN: 978-2-85873-134-3. Technology.” MDPI - Energies 12, no. 3: 368, pp.1-13,
[3] CIGRÉ Brochure 526 - Oxidation Stability of Insulating Fluids, W.G. doi:10.3390/en12030368.
D1.30, February 2013, ISBN: 978-2-85873-219-7. [17] P. Przybylek, K. Walczak, W. Sikorski, H. Moscicka-Grzesiak, H.
[4] CEI/IEC 60422:2013 - Mineral insulating oils in electrical equipment - Moranda and M. Cybulski, “Experimental Validation of a Method of
Supervision and maintenance guidance. Publication date: 10.01.2013, Drying Cellulose Insulation in Distribution Transformers Using
Edition 4, pages 93. Circulating Synthetic Ester.” In IEEE Access, vol. 9, pp. 150322-
[5] M.Duval and A. DePablo, "Interpretation of Gas-In-Oil Analysis using 150329, 2021, doi: 10.1109/ACCESS.2021.3125840.
New IEC pubication 60599 and IEC TC 10 Databases", IEEE Electrical [18] A. I. Hafez, A. M. el Deeb, M. H. el Behairy, E. M. Khalil and M. S.
Insulation Magazine, Vol.17, No.2, pp.31-41,2001. Abd el Fattah, “Study on the Treatment of High Voltage Used
[6] IEEE Std C57.140-2017 - Guide for Evaluation and Reconditioning of Transformer Oil by Using Natural Material,” IOSR Journal of Applied
Liquid Immersed Power Transformers, 31 Octomber 2017, Electronic Chemistry (IOSR-JAC) e-ISSN: 2278-5736.Volume 12, Issue 10 Ser. I
ISBN: 978-1-5044-4149-0. (October. 2019), PP 19-36.
[7] IEEE Std C57.637-2015 - Guide for the Reclamation of Mineral [19] M.E. Soares, A.J. Araujo, F.S. Silva, R.A. Silva, N.V. Barbosa,
Insulating Oil and Criteria for Its Use. Date of Publication: 26 October “Regeneration of transformer oil using a microemulsion with Triton
2015; Electronic ISBN: 978-1-5044-0062-6. X‑100,” Brazilian Journal of Chemical Engineering, Published online:
[8] Ivanka ATANASOVA-HÖHLEIN, "IEC 60296 (Ed. 5) – a standard for 02 June 2021: https://doi.org/10.1007/s43153-021-00113-6.
classification of mineral insulating oil on performance and not on the
origin", TRANSFORMERS MAGAZINE | Volume 8, Issue 1 | 2021.