0% found this document useful (0 votes)
521 views28 pages

Class Assignment Powerplant Economics A Batch

This document contains 13 multi-part questions related to power plant engineering. Question 1(a) involves calculating the average heat rate and savings from operating a 10MW power station at full vs. partial capacity. Question 1(b) involves calculating load factors, plant use factors, and capacity factors for base and standby power plants sharing a common load. The remaining questions involve additional calculations related to power plant operation, load curves, energy generation, demand factors, and economic evaluations.

Uploaded by

Abhijith Mohan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
521 views28 pages

Class Assignment Powerplant Economics A Batch

This document contains 13 multi-part questions related to power plant engineering. Question 1(a) involves calculating the average heat rate and savings from operating a 10MW power station at full vs. partial capacity. Question 1(b) involves calculating load factors, plant use factors, and capacity factors for base and standby power plants sharing a common load. The remaining questions involve additional calculations related to power plant operation, load curves, energy generation, demand factors, and economic evaluations.

Uploaded by

Abhijith Mohan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 28

Power Plant Engineering

Assignment
Max Marks 15
A batch
Each student shall answer the question assigned to him.

1(a)
The input output curve of a 10MW power station is expressed
as follows:
i=106(8+L+0.4L2)
where i is in kcal per hour and L is in MW.
Determine the average heat rate of the power station for a day if
it operates at its full capacity for 12 hours and is kept running at
zero load for remaining 12 hours. Also calculate the saving per
kWh of energy produced if the energy is generated at a
constant 24 hours load (100% load factor).

(b)A common load is to be shared by two power plants. One


power plant is a base load plant with 30 MW installed capacity
and other power plant is a standby plant with 20 MW capacity.
The yearly output of the base load plant is 130 x 106 kWh and
that of standby plant is 9 x 10 6 kWh. The peak load taken by the
standb y plant is 15 MW and this plant works for 2800 hours
during the year. The base load plant takes a peak of25 MW.
Determine the following for both plants:
(a) Annual load factor
(b) Plant use factor
(c) Capacity factor.

2(a)
The maximum (peak) load on a thermal power plant of 60 MW
capacity is 50 MW at an annual load factor of 50%. The loads
having maximum demands of25 MW, 20 MW, 8 MW and 5 M
are connected to the power station. Determine : (a) Average
load on power station (b) Energy generated per year (c)
Demand factor (d) Diversity factor.
(b)The capital cost of a power generating equipment in a steam
power plant is Rs 80 *10 6 . The useful life of the plant is 30
years and its salvage value is 5% of the capital cost. Determine
by the sinking-fund method the amount of money to be saved
annually for replacement if the yearly rate of compound interest
is 6%.

3 (A)

A power station supplies the following loads to the consumers:

Time 0-6 6-10 10-12 12-16 16-20 20-22 22-24


(hours)
Load 30 70 90 60 100 80 60
(MW)

(a) Draw the load curve and estimate the load factor of the
plant.
(b) What is the load factor of a standby equipment of 30 MW
capacity if it takes up all loads above 70 MW? What is its use
factor?

(B)A plant costing Rs 125,000 has a useful life of 20 years. Find


the amount which should be saved annually to replace the
equipment at the end of that time (a) by the straight-line
method, and (b) by the sinking-fund method if the annual rate of
compound interest is 7%. Assume that the salvage value of the
equipment is Rs55000.

4.(A)

A power station has to meet the following demand :


Group A : 150 kW between 8 A.M. and 6 P.M.
Group B : 350 kW between 6 A.M. and 10 A.M.
Group C : 350 kW between 6 A.M. and 10 A.M.
Group D : 50 kW between 10 A.M. and 6 P.M. and then between 6 P.M.
and 6 A.M.
Plot the daily load curve and determine (i) diversity factor (ii) units
generated per day (iii) load factor.

(B)A chimney is 29 metres high and the temperature of hot gases


inside the chimney is 320oC. The ternperaiuie of outside air is 27oC
and furnace as supplied with 15 kg of air per kg of coal burnt.
Calculate
(a) Draught in mm of water.
(b) Draught height in metres of hot gases.

5
At the end of a power distribution system, a certain feeder supplies three
distri-
bution transformers, each one supplying a group of customers whose
connected load are listed as
follows :
Transformer 1 Transformer 2 Transformer
3
General power Residence lighting Store lighting and
power
service and lighting

a : 22 H.P., 14kW e : 15 kW i : 25
kW
b : 13 H.P., 14kW f : 12 kW l : 16 kW
c : 14 H.P. g : 6 kW j : 28 kW, 7
H.P.
d : 7 H.P., 12 kW h : 12 kW k : 16 kW,
23 H.P.

Demand factor for all type of load is .62 & Diversity factor as 1.35
Use the factor and predict the maximum demand on the feeder. The
H.P. load
is motor load and assume an efficiency of 75%.

6.(a)
The maximum (peak) load on a thermal power plant of 60 MW
capacity is 50 mW at an annual load factor of 50%. The loads
having maximum demands of 25 MW, 20 MW, 8 MW and, 5 MW
are connected to the power station.
Determine: (a) Average load on power station (b) Energy
generated per year (c) Demand factor (d) Diversity factor.

6(b)
In a steam power plant the capital cost of power generation
equipment is Rs. 25 × 10 . The useful life of the plant is 30 years
and salvage value of the plant to Rs. 1 × 10 5 . Determine by
sinking fund method the amount to be saved annually for
replacement if the rate of annual compound interest is 6%.

7
(a)

Two lamps are to be compared:


(a) Cost of first lamp is Re. 1 and it takes 100 watts.
(b) Cost of second lamp is Rs. 4 and it takes 60 watts.
Both lamps are of equal candle power and each has a useful life of
100 hours. Which lamp will prove economical if the energy is
charged at Rs. 70 per kW of maximum demand per year plus 5
paise per kWh? At what load factor both the lamps will be equally
advantageous?

(b)The input-output curve of a 150 MW station is expressed by the


formula,
I = 106 (250 + 5L + 0.03L3) + L4
where I is in kcal per hour and L is in mega-watts. Find the load at
which minimum heat rate occurs and check with the plot.
8(A)
A power station has to supply load as follows:

Time 0-6 6-12 12-14 14-18 18-24


(hours)
Load (MW) 30 90 60 100 50
(a) Draw the load curve. (b) Draw the load duration curve. (c)
Select suitable generating units to supply the load. (d) Cal
culate the load factor. (e) Calculate the capacity of the plant and
the plant capacity factor.

(B)The capital cost of a power generating equipment in a steam


power plant is Rs 80 *10 6 . The useful life of the plant is 30
years and its salvage value is 7% of the capital cost. Determine
by the sinking-fund method the amount of money to be saved
annually for replacement if the yearly rate of compound interest
is 6.5%.

9 (a)
The incremental fuel costs for two generating units A and B of a
power plant are given by the following relations,
dFa /dPa = 0.065 Pa + 25
dFb /dPb = 0.08 Pa + 20
where F is the fuel cost in rupees per hour and P is the power
output in MW. Estimate
(a) the economic loading of the two units when the total load
supplied by the power plants is 200 MW, (b) the loss in fuel cost
per hour if the load is equally shared by both units.

(b)
In a steam power plant the capital cost of power generation
equipment is Rs. 25 × 10 . The useful life of the plant is 30 years
and salvage value of the plant to Rs. 1 × 10 5 . Determine by
sinking fund method the amount to be saved annually for
replacement if the rate of annual compound interest is 6%.

10 (a)
The following loads are connected to a power plant:

Type of load Max. demand Diversity factor Demand factor


(MW)
Domestic 15 1.25 0.70
Commercial 25 1.20 0.90
Industrial 50 1.30 0.98

If the overall diversity factor is 1.5, determine (a) the maximum


load, and (b) the connected load of each type

(b)The incremental fuel costs for two generating units A and B of a


power plant are given by the following relations,
dFa /dPa = 0.06 Pa + 35
dFb /dPb = 0.09 Pa + 25
where F is the fuel cost in rupees per hour and P is the power
output in MW. Estimate
(a) the economic loading of the two units when the total load supplied by
the power plants is 150 MW, (b) the loss in fuel cost per hour if the load
is equally shared by both units.

11 (a)
A power station has to meet the following demand :
Group A : 200 kW between 8 A.M. and 6 P.M.
Group B : 100 kW between 6 A.M. and 10 A.M.
Group C : 50 kW between 6 A.M. and 10 A.M.
Group D : 100 kW between 10 A.M. and 6 P.M. and then between 6 P.M.
and 6 A.M.
Plot the daily load curve and determine (i) diversity factor (ii) units
generated per day (iii) load factor.

(b)

12
At the end of a power distribution system, a certain feeder supplies three
distri-
bution transformers, each one supplying a group of customers whose
connected load are listed as
follows :
Transformer 1 Transformer 2 Transformer
3
General power Residence lighting Store lighting and
power
service and lighting

a : 10 H.P., 5kW e : 5 kW i : 20 kW
b : 7·5 H.P., 4kW f : 4 kW l : 4 kW
c : 15 H.P. g : 8 kW j : 10 kW, 5
H.P.
d : 5 H.P., 2 kW h : 15 kW k : 8 kW, 25
H.P.

Demand factor for all type of load is .60 & Diversity factor as 1.25
Use the factor and predict the maximum demand on the feeder. The
H.P. load
is motor load and assume an efficiency of 72%.

13 (A)
Example 3.11. A power station has to meet the following demand :
Group A : 450 kW between 8 A.M. and 6 P.M.
Group B : 250 kW between 6 A.M. and 10 A.M.
Group C : 250 kW between 6 A.M. and 10 A.M.
Group D : 100 kW between 10 A.M. and 6 P.M. and then between 6 P.M.
and 6 A.M.
Plot the daily load curve and determine (i) diversity factor (ii) units
generated per day (iii) load factor.
(B)A chimney is 26 metres high and the temperature of hot gases
inside the chimney is 350oC. The ternperaiuie of outside air is 25oC
and furnace as supplied with 13 kg of air per kg of coal burnt.
Calculate
(a) Draught in mm of water.
(b) Draught height in metres of hot gases.

14
At the end of a power distribution system, a certain feeder supplies three
distri-
bution transformers, each one supplying a group of customers whose
connected load are listed as
follows :
Transformer 1 Transformer 2 Transformer
3
General power Residence lighting Store lighting and
power
service and lighting

a : 20 H.P., 15kW e : 12 kW i : 20
kW
b : 13 H.P., 14kW f : 12 kW l : 16 kW
c : 11 H.P. g : 6 kW j : 22 kW, 7
H.P.
d : 7 H.P., 2 kW h : 15 kW k : 6 kW, 23
H.P.

Demand factor for all type of load is .62 & Diversity factor as 1.35
Use the factor and predict the maximum demand on the feeder. The
H.P. load
is motor load and assume an efficiency of 75%.

15.(A)

A power station has to meet the following demand :


Group A : 150 kW between 8 A.M. and 6 P.M.
Group B : 350 kW between 6 A.M. and 10 A.M.
Group C : 350 kW between 6 A.M. and 10 A.M.
Group D : 50 kW between 10 A.M. and 6 P.M. and then between 6 P.M.
and 6 A.M.
Plot the daily load curve and determine (i) diversity factor (ii) units
generated per day (iii) load factor.

(B)A chimney is 29 metres high and the temperature of hot gases


inside the chimney is 320oC. The ternperaiuie of outside air is 27oC
and furnace as supplied with 15 kg of air per kg of coal burnt.
Calculate
(a) Draught in mm of water.
(b) Draught height in metres of hot gases.

16
At the end of a power distribution system, a certain feeder supplies three
distri-
bution transformers, each one supplying a group of customers whose
connected load are listed as
follows :
Transformer 1 Transformer 2 Transformer
3
General power Residence lighting Store lighting and
power
service and lighting

a : 22 H.P., 14kW e : 15 kW i : 25
kW
b : 13 H.P., 14kW f : 12 kW l : 16 kW
c : 14 H.P. g : 6 kW j : 28 kW, 7
H.P.
d : 7 H.P., 12 kW h : 12 kW k : 16 kW,
23 H.P.

Demand factor for all type of load is .62 & Diversity factor as 1.35
Use the factor and predict the maximum demand on the feeder. The
H.P. load
is motor load and assume an efficiency of 75%.

17.(a)
The maximum (peak) load on a thermal power plant of 60 MW
capacity is 50 mW at an annual load factor of 50%. The loads
having maximum demands of 25 MW, 20 MW, 8 MW and, 5 MW
are connected to the power station.
Determine: (a) Average load on power station (b) Energy
generated per year (c) Demand factor (d) Diversity factor.

17(b)
In a steam power plant the capital cost of power generation
equipment is Rs. 25 × 10 . The useful life of the plant is 30 years
and salvage value of the plant to Rs. 1 × 10 5 . Determine by
sinking fund method the amount to be saved annually for
replacement if the rate of annual compound interest is 6%.

18
(a)

Two lamps are to be compared:


(a) Cost of first lamp is Re. 1 and it takes 100 watts.
(b) Cost of second lamp is Rs. 4 and it takes 60 watts.
Both lamps are of equal candle power and each has a useful life of
100 hours. Which lamp will prove economical if the energy is
charged at Rs. 70 per kW of maximum demand per year plus 5
paise per kWh? At what load factor both the lamps will be equally
advantageous?

(b)The input-output curve of a 150 MW station is expressed by the


formula,
I = 106 (250 + 5L + 0.03L3) + L4
where I is in kcal per hour and L is in mega-watts. Find the load at
which minimum heat rate occurs and check with the plot.
19 (A)
A power station has to supply load as follows:

Time 0-6 6-12 12-14 14-18 18-24


(hours)
Load (MW) 30 90 60 100 50
(a) Draw the load curve. (b) Draw the load duration curve. (c)
Select suitable generating units to supply the load. (d) Cal
culate the load factor. (e) Calculate the capacity of the plant and
the plant capacity factor.

(B)The capital cost of a power generating equipment in a steam


power plant is Rs 80 *10 6 . The useful life of the plant is 30
years and its salvage value is 7% of the capital cost. Determine
by the sinking-fund method the amount of money to be saved
annually for replacement if the yearly rate of compound interest
is 6.5%.

20 (a)
The annual peak load on a 30 MW power station is 25 mW. The
power station supplies load having maximum demands of 10 MW,
8.5 MW, 5 MW and 4.5 MW. The annual load factor is 0.45. Find:
(i) Average load
(ii) Energy supplied per year
(iii) Diversity factor
(iv) Demand factor

(b)In a steam power plant the capital cost of power generation


equipment is Rs. 35 × 10 . The useful life of the plant is 25 years and
salvage value of the plant to Rs. 2 × 10 5 . Determine by sinking fund
method the amount to be saved annually for replacement if the rate of
annual compound interest is 5%.

21 (A)
(A power station has a maximum demand of 15 MW, a load factor
of 0.7, a plant capacity factor of 0.525 and a plant use factor of
0.85. Find:
(i) The daily energy produced.
(ii) The reserve capacity of the plant.
(iii) The maximum energy that could be produced daily if the
plant operating schedule is fully loaded when in operation.

(B)The input output curve of a 10MW power station is


expressed as follows:
i=106(8+L+0.4L2)
where i is in kcal per hour and L is in MW.
Determine the average heat rate of the power station for a day if it
operates at its full capacity for 12 hours and is kept running at zero
load for remaining 12 hours.

22
(a)A residential load of a locality is given below:
Time (h) 0-5 5-6 6-9 9-18 18-21 21-24
Load 2 6 18 0 12 8
(kW)
Draw the load curve and find out the load factor and energy
consumed during 24 hr.

(b) A power plant has the following annual factors: Load factor =
70 per cent; capacity factor = 50 per cent. Use factor = 60 per cent.
Maximum demand is 20 MW. Find out the following:
(a) Annual energy production
(b) Reserve capacity over and above peak load
(c) Hours during which the plant is not in service per year

23 (a)
A power station supplies the following loads to the consumers:
Time 0-6 6-10 10-12 12-16 16-20 20-22 22-24
(h)
Load 30 50 60 40 80 70 40
(MW)
Find (a) the load factor of the plant and (b) what is the load factor
of a standby equipment of 30 MW capacity if it takes up all loads
above 60 MW?

(b)In a steam power plant the capital cost of power generation


equipment is Rs. 15 × 10 . The useful life of the plant is 30 years
and salvage value of the plant to Rs. 1.25 × 10 5 . Determine by
sinking fund method the amount to be saved annually for
replacement if the rate of annual compound interest is 4%.

24 (a)
The peak load on a power station is 35 MW. The loads having
maximum demands of 15, 10, 5 and 7 MW are connected to the
power station. The capacity of the power station is 40 MW and
annual load factor is 50 per cent. Find (a) the average load on the
power station, (b) energy supplied per year, (c) demand factor and
(d) diversity factor.

(b)The input-output curve of a 150 MW station is expressed by the


formula,
I = 106 (250 + 5L + 0.03L3) + L4
where I is in kcal per hour and L is in mega-watts. Find the load at
which minimum heat rate occurs .

25 (a)
A power plant supplies the loads having maximum demands of 40,
50 and 30 MW respectively. The load factor of the plant on the
basis of annual load curve is 60 per cent and the diversity factor of
the load is 1.2. Determine (a) the maximum load on the power
plant, (b) the capacity of the power plant required to take the loads
and (c) annual energy supplied by the power plant.

(b)The capital cost of a power generating equipment in a steam power


plant is Rs 70 *10 6 . The useful life of the plant is 20 years and its
salvage value is 8% of the capital cost. Determine by the sinking-fund
method the amount of money to be saved annually for replacement if
the yearly rate of compound interest is 5%.

26 (A)
A power plant supplies the loads having maximum demands of 40,
50 and 30 MW respectively. The load factor of the plant on the
basis of annual load curve is 60 percent and the diversity factor of
the load is 1.2. Determine (a) the maximum load on the power
plant, (b) the capacity of the power plant required to take the loads
and (c) annual energy supplied by the power plant.

(B)The following loads are connected to a power plant:


Type of load Max. demand Diversity factor Demand factor
(MW)
Domestic 15 1.5 0.75
Commercial 25 1.25 0.85
Industrial 50 1.35 0.9

If the overall diversity factor is 1.5, determine (a) the maximum load, and
(b) the connected load of each type.

27(A)The annual peak load on a 35 MW power station is 30 MW.


The power station supplies load having maximum demands of
9MW, 12 MW, 5 MW and 5.5 MW. The annual load factor is 0.55
Find:
(i) Average load
(ii) Energy supplied per year
(iii) Diversity factor
(iv) Demand factor

(B)The input-output curve of a 150 MW station is expressed by the


formula,
I = 106 (300 + 6L + 0.035L3) + L4
where I is in kcal per hour and L is in mega-watts. Find the load at
which minimum heat rate occurs and check with the plot.
28(A)
A load duration curve for an industrial load is served by
hydro-thermal plants follows a straight line. The maximum and
minimum loads are 30 and 10 MW, respectively. The hydel-plant is
available at the time of minimum regulating flow which is just
enough to take a peak load of 75 MWh per day. On investigation, it
was found economical to pump water from lower reservoir to
higher reservoir using the excess power from steam plant during
peak period allowing steam plant to run at 100 per cent load all the
times. Determine the capacities of hydel and steam plants required
for the purpose. Assume efficiency of steam to electric conversion
= 45%

(B)In a steam power plant the capital cost of power generation


equipment is Rs. 30 × 10 . The useful life of the plant is 27 years and
salvage value of the plant to Rs. 1 × 10 5 . Determine by sinking fund
method the amount to be saved annually for replacement if the rate of
annual compound interest is 5%.

29(A)
The yearly duration curve for a certain plant can be considered as
a straight line from 20 to 5 MW , WHERE power IS supplied BY
one generator rated at 5 MW and two GENERATING units of 10
MW capacity each. Determine
(a) Installed capacity
(b) Plant factor
(c) Maximum demand
(d) Load factor
(e) Utilization factor

(B)A central power station has annual load factor, capacity factor and
use factor as 60%, 40% and 45%, respectively. The maximum demand
is 15 MW. Estimate (a) the annual energy produc tion and revenue
earned if the cost of energy is Re 1/UNIT, (b) the reserve capacity over
and above the peak load, and (c) the hours per year the station is not in
service.
30 (A)
A power plant has the following annual factors: Load factor = 70
per cent; capacity factor = 50 per cent. Use factor = 60 per cent.
Maximum demand is 20 MW. Find out the following:
(a) Annual energy production
(b) Reserve capacity over and above peak load
(c) Hours during which the plant is not in service per year

(B)he incremental fuel costs for two generating units A and B of a power
plant are given by the following relations:
dFA /dPA = 0.07 PA + 10
dFB /dPB = 0.08 PB + 12
where P is the power in MW and F is the fuel cost in rupees per
hour.
(a) Find the economic loading of the two units when the total
load to be supplied by the power station is 120 MW.
Find the net increase in fuel cost per hour if the load is equally shared
by the two units.

31 (A)
A base load power station and a standby power station share a
common load as follows:
Base load station annual output = 150 × 10 6 kWh
Base load station capacity = 25 MW
Maximum demand on base load station = 30 MW
Stand by station capacity = 18 MW
Maximum demand on standby station = 15 MW
Stand-by-station annual output = 14 × 10 6 kWh
Maximum demand on standby station = 15 MW
Determine the following for both power stations: (a) load factor and
(b) capacity factor

(B)The capital cost of a power generating equipment in a steam power


plant is Rs 90 *10 6 . The useful life of the plant is 25 years and its
salvage value is 10% of the capital cost. Determine by the sinking-fund
method the amount of money to be saved annually for replacement if
the yearly rate of compound interest is 3%.
32(A)
The peak load on a power station is 40 MW. The loads having
maximum demands of 18, 12, 8 and 9 MW are connected to the
power station. The capacity of the power station is 50 MW, annual
load factor is 62 per cent find,
(i) Average load on the power station
(ii) Energy supplied per year
(iii) Demand factor
(iv) Diversity factor

(B)A power plant has the following annual factors: Load factor = 70%;
Capacity factor = 50%; Use factor = 60%; Maximum demand = 20 MW.
Estimate (a) annual energy production, (b) reserve capacity over and
above the peak load, and (c) the hours per year during which the plant is
not in service.

33 (A)

(The annual peak load on a 30 MW power station is 25 MW. The


power station supplies load having maximum demands of 10 MW,
8.5 MW, 5 MW and 4.5 MW. The annual load factor is 0.5. Find:
(i) Average load
(ii) Energy supplied per year
(iii) Diversity factor
(iv) Demand factor

(B)The input-output curve of a 150 MW station is expressed by the


formula,
I = 106 (250 + 5L + 0.03L3) + L4
where I is in kcal per hour and L is in mega-watts. Find the load at
which minimum heat rate occurs and check with the plot.

34 (A)
The maximum demand of a power station is 26,000 kW and daily
load curve is described as follows:
Time (h) 0-4 4-8 8-12 12-16 16-20 22-24
Load 8 15 28 15 42 8
(MW)
(i) Determine the load factor
(ii) What is the load factor of stand by equipment rated at 8 MW
that takes up all load in excess of 15 MW. Calculate use factor
also.

(B)The capital cost of a power generating equipment in a steam


power plant is Rs 80 *10 6 . The useful life of the plant is 30 years
and its salvage value is 5% of the capital cost. Determine by the
sinking-fund method the amount of money to be saved annually for
replacement if the yearly rate of compound interest is 6%.

35 (A)

Draw load curve and the load duration curve from the following
data. Find the load factor and utilization factor of the plant serving
this load if its capacity is 90 MW.
Time 12 2 AM 6 AM 8 AM 12 12.30 1 PM 5 PM 6 PM 12
PM AM PM PM
Load 18 8 8 48 48 38 48 48 68 18
(MW)

(B)
The connected loads of a consumer consist of 10 electric bulbs
of 60 W each and 2 electric heaters of 1000 W each. His
maximum demand is 1500 W. On an average, he uses 8 bulbs
for 5 hours a day and one heater for 3 hours a day. Estimate his
average load, monthly energy consumption and load factor.

36 (A)

A power station has a maximum demand of 80 × 10 3 kW and daily


load curve is defined as follows:
Time 0-6 6-8 8-12 12-14 14-18 18-22 22-24
(h)
Load 40 50 60 50 70 80 40
(MW)
(a) Draw load curve and the load duration curve .Determine the
load factor of power station.
(b) What is the load factor of standby equipment raid at 25 MW
that takes up all load in excess of 60 MW? Also calculate its use
factor.

(B)An yearly load duration curve of a gas turbine power plant is a


straight line from 50,000 to 5,000 kW. The load is taken by a power plant
that consists of two units of 30,000 kW each and one unit of 20,000 kW.
Determine (a) load factor and (b) capacity factor of the plant.

37 (a)
A power station has two 60 MW unit each running for 7,000 hr a
year and an 30 MW unit running for 1,500 hr a year. The energy
produced per year is 700 × 10 6 kWh, calculate the following:
(a) Plant load factor
(b) Plant use factor

(b)The original value of an equipment is Rs2,50,000 and its


salvage value at the end of its useful life of 20 years is Rs25,000.
Find the value of the equipment at the end of 10 years of its use by
the following methods: (a) straight line depreciation and (b) sinking
fund depreciation, when it is compounded annually at 8%.

38 (A)

The loads on a power plant with respect to time for 24 hr are listed
below:
Time 0-6 6-8 8-12 12-14 14-18 18-22 22-24
(h)
Load 40 40 60 50 70 80 40
(MW)
Draw the load curve,LOAD DURATION CURVE and find cut the
load factor of the power station. If the loads above 60 MW are
taken by stand by unit of 20 MW capacity, find out the load factor of
the stand by unit.

(B)A power station has two 60 MW unit each running for 7,000 hr a year
and an 30 MW unit running for 1,500 hr a year. The energy produced
per year is 700 × 10 6 kWh, calculate the following:
(a) Plant load factor
(b) Plant use factor

39 (A)
The daily load of a power station is given below:
Time 12 12 6 AM 8 AM 12 12:30 1 PM 5 PM 6 PM 12
night AM noon PM night
Load 20 10 10 40 40 30 40 40 60 20
(MW)
(a) Plot load and load duration curve for the system
(b) Find out the load factor

(B)The incremental fuel costs of two generating units A and B of a


power station are given by the following expressions:
dFA/dPA=0.025 PA+2.5
dFB/dPB = 0.02PB+1.75
where F is in rupees per hour and P it is MW. Determine incremental
fuel cost and loading schedule for minimum cost if the total load to be
supplied is to be 50 MW 175 MW and 200MW. Both units operate at all
times and maximum and minimum load on each unit is to be 100 MW
and 15 MW respectively.

40(A)

The input output curve of a 10MW power station is expressed as


follows:
i=106(8+L+0.4L2)
where i is in kcal per hour and L is in MW.
Determine the average heat rate of the power station for a day if it
operates at its full capacity for 12 hours and is kept running at zero
load for remaining 12 hours. Also calculate the saving per kWh of
energy produced if the energy is generated at a constant 24 hours
load (100% load factor).
(B)
The following data are collected from a daily load curve of a power
plant.
Load 15000 12000 10000 8000 6000 4000 2000
(kW)
No of 875 876 1750 2630 4380 7000 8740
hours at
load
(a) Find out the load factor of the system.
(b) If the load is supplied by two plants one is acting as base load
plant of 10,000 kW capacity and other as peak load plant of 7,500
kW capacity, find out the annual load factor, annual capacity factor
and annual use factor for both plants.

41(A)
A power station has a maximum demand of 80 x 10 k W and daily
load curve is defined as follows:
Time 0-6 6-8 8-12 12-14 14-18 18-26 22-24
(h)
Load 40 50 60 50 70 80 40
(MW)
(a) Draw the load CURVE AND load duration curve and find out
the load factor of the power station.
(b) What is the load factor of standby equipment rated at 25 MW
that takes up all load in excess of 60 MW ? Also calculate its use
factor.

(B)A chimney is 28 metres high and the temperature of hot gases inside
the chimney is 320oC. The ternperaiuie of outside air is 27oC and
furnace as supplied with 15 kg of air per kg of coal burnt. Calculate
(a) Draught in mm of water.
(b) Draught height in metres of hot gases.

42 (A)
Find the diversity factor of power station which supplies the
following loads:
Load A: Motor load of 100 kW working between 10AM. and 6P.M.
Load B: Lighting load of 60 kW between 6 P.M. and 10A.M.
Load C: Pumping load of 40 kW between 4 P.M. and 10AM.

(B)
In a steam power plant the capital cost of power generation equipment
is Rs. 30 × 10 . The useful life of the plant is 24 years and salvage value
of the plant to Rs. 1.5 × 10 5 . Determine by sinking fund method the
amount to be saved annually for replacement if the rate of annual
compound interest is 7%.

44 (A)
The annual peak load on a 30 MW power station is 25 MW. The
power station supplies loads having maximum demands of 10MW,
8.5 MW, 5 MW and 4.5 MW. The annual load factor is 45%.
Find:
(a) Average load,
(b) Energy supplied per year,
(c) Diversity factor,
(d) Demand factor.

(B)Determine the height of chimney to gel net draught of 12 mm if the


total draft losses are 4mm. The temperature of air is 25oC and the
temperature of chimney gases is 300oC. The mass of air used per kg of
fuel used is 18 kg. One kg of air occupies a volume of 0. 7734 m3 at
N.T.P.

45(A)
For a power station the yearly load duration curve is a straight line
from 30,000 to 4,000 kW. To meet the load three turbo-generators
are installed. The capacity of two generators is 15,000 kW each
and the third is rated at 5,000 kW. Determine the following:
(a) Load factor,
(b) Capacity factor or plant factor,
(c) Maximum demand.

(B)The daily load of a power station is given below:


Time 12 12 6 AM 8 AM 12 12:30 1 PM 5 PM 6 PM 12
night AM noon PM night
Load 20 10 10 40 40 30 40 40 60 20
(MW)
(a) Plot load and load duration curve for the system
(b) Find out the load factor

46(A)
The maximum (peak) load on a thermal power plant of 60 MW
capacity is 50 MW at an annual load factor of 50%. The loads
having maximum demands of25 MW, 20 MW, 8 MW and 5 M are
connected to the power station. Determine : (a) Average load on
power station (b) Energy generated per year (c) Demand factor (d)
Diversity factor.

(B)The capital cost of a power generating equipment in a steam


power plant is Rs 80 *10 6 . The useful life of the plant is 30 years
and its salvage value is 5% of the capital cost. Determine by the
sinking-fund method the amount of money to be saved annually for
replacement if the yearly rate of compound interest is 6%.

47 (A)
A power station is to supply three region of load hose peak loads
are 20 MW, 15 MW and 25 MW. The annual load factor is 50% and
the diversity factor of the load at the station is 1.5. Determine the
following:
(a) Maximum demand on the station,
(b) Installed capacity suggesting number of unit.
(c) Annual energy supplied.

(B)Determine the height of chimney to gel net draught of 14 mm if


the total draft losses are 5 mm. The temperature of air is 30oC and
the temperature of chimney gases is 20oC. The mass of air used
per kg of fuel used is 18 kg. One kg of air occupies a volume of 0.
7734 m3 at N.T.P.

48 (A)
The load of a residential consumer for a day was found to be as
follows:

From 12.00 midnight to 6A.M. No load


From 6A.M. to 8A.M. 120W
From 6A.M. to 9.30A.M. 540 W
From 9.30A.M. to 11.30A.M. No load
From 11.30A.M. to 2P.M. 480W
From 2 P.M. to 3.30 P.M. No load
From 3.30 P.M. to 5P.M. 120 W
From 5 P.M. to 6.30 P.M. 360 W
From 6.30 A.M. to 9A.M. 480 W
From 9P.M. to 12 midnight 120 W
Calculate
(a) Energy consumed
(b) Load factor.

(B)A plant costing Rs 175,000 has a useful life of 120years. Find the
amount which should be saved annually to replace the equipment at the
end of that time (a) by the straight-line method, and (b) by the
sinking-fund method if the annual rate of compound interest is 5%.
Assume that the salvage value of the equipment is Rs 50000.

49 (A)
An input-output curve of a 10 MW station is expressed as follows:
I = 106(I6+8L+0.4L2)
where I is in kcal per hour and L is in mega watts.
(i) Without plotting any curve find the load at which the maximum
efficiency occurs.
(ii) Find the increase in input required to increase station output
from 3 to 5 MW by means of the input-output curve and also by
incremental rate curve.

(B)The capital cost of a power generating equipment in a steam


power plant is Rs 80 *10 6 . The useful life of the plant is 30 years
and its salvage value is 5% of the capital cost. Determine by the
sinking-fund method the amount of money to be saved annually for
replacement if the yearly rate of compound interest is 6%.

50(A)
The incremental fuel costs of two generating units A and B of a
power station are given by the following expressions:
dFA/dPA=0.01 PA+2.25
dFB/dPB = 0.015PB+1.5
where F is in rupees per hour and P it is MW. Determine
incremental fuel cost and loading schedule for minimum cost if the
total load to be supplied is to be 50 MW 175 MW and 200MW.
Both units operate at all times and maximum and minimum load on
each unit is to be 100 MW and 15 MW respectively.

(B)The incremental fuel costs for two generating units A and B of a


power plant are given by the following relations:
dFA /dPA = 0.05 PA + 11.5
dFB /dPB = 0.075 PB + 10.5
where P is the power in MW and F is the fuel cost in rupees per
hour.
Find the net increase in fuel cost per hour if the load is equally shared
by the two units.

51(a)
In a power distribution system a certain feeder supplies three
distribution transformers each one supplying a group of
transformers whose connected loads are as follows:
Transformer I Transformer 2 Transformer 3
Store lighting and Power Residence Lighting General Power service and
Commercial lighting
(j)10 RW, 5 H.P. (i)0.5kW (i)10 H.P., 5 kW
(ii)4 kW (ii)20kW (ii)15 H.P.
Assuming motor efficiency 70% and suitable demand factor and
diversity factors, Calculate maximum feeder load.

(b)The maximum demand of a power station is 26,000 kW and daily


load curve is described as follows:
Time (h) 0-4 4-8 8-12 12-16 16-20 22-24
Load 8 15 28 15 42 8
(MW)
(i) Determine the load factor
(ii) What is the load factor of stand by equipment rated at 8 MW that
takes up all load in excess of 15 MW. Calculate use factor also.

52(a)
A power station has to supply loud as follows:
Time (h) 0-6 6-12 12-14 14-18 18-24
Load (MW) 30 90 60 100 50
(a) Draw the load curve.
(b) Draw load-duration curve.
(c) Choose suitable generating units to supply the load.
(d) Calculate load factor.
(e) Calculate plant capacity.

(b)Determine the height of chimney to gel net draught of 15 mm if the


total draft losses are 5mm. The temperature of air is 27oC and the
temperature of chimney gases is 310oC. The mass of air used per kg of
fuel used is 19 kg. One kg of air occupies a volume of 0. 7734 m3 at
N.T.P.

53
(A)
The input output curve of 100 MWpower station is expressed as
follows:
I = 106 (100+2L +0.0004L3)
where I is in kcal/hr and L is in MW.
Determine (i) Input, heat rate and efficiency when load is 40 MW
(ii) Load at which e ff iciency is maximum.

(B)
The peak load on a power station is 40 MW. The loads having
maximum demands of 18, 12, 8 and 9 MW are connected to the
power station. The capacity of the power station is 50 MW, annual
load factor is 62 per cent find,
(i) Average load on the power station
(ii) Energy supplied per year
(iii) Demand factor
(iv) Diversity factor

54 (a)
The peak load on a power plant is 60 MW. The loads having
maximum demands of 30 MW, 20 MW, 10 MW and 14 MW are
connected to the power plant. The capacity of the power plant is
80MW and the annual load factor is 0.50. Estimate (a) the average
load on the power plant, (b) the energy supplied per year, (c) the
demand factor, (d) the diversity factor.

(b)Determine the height of chimney to produce a static draught of


25 mm of water if the mean flue gas temperature in a chimney is
310oC and ambient temperature in boiler house is 20oC. Assume
barometer reading as 760 mm of mercury.
(a) Annual load factor
(b) Plant use factor
(c) Capacity factor.

55(a)
The maximum (peak) load on a thermal power plant of 60 MW
capacity is 50 MW at an annual load factor of 50%. The loads
having maximum demands of25 MW, 20 MW, 8 MW and 5 M are
connected to the power station. Determine : (a) Average load on
power station (b) Energy generated per year (c) Demand factor (d)
Diversity factor.

(b)The capital cost of a power generating equipment in a steam


power plant is Rs 80 *10 6 . The useful life of the plant is 30 years
and its salvage value is 5% of the capital cost. Determine by the
sinking-fund method the amount of money to be saved annually for
replacement if the yearly rate of compound interest is 6%.

You might also like