Switchgear Lab Manual
Switchgear Lab Manual
Switchgear Lab Manual
Lab No. 01
To study different types of switchgear equipment used in electrical
power system
S.No Apparatus
1 SWITCHES
2 FUSES
3 CIRCUIT BREAKERS
4 Relays
5 control panels
6 current transformers
7 potential transformers
Theory
SWITCHES:
A switch is a device which is used to open or close an electrical circuit in a
convenient way. It can be used under full-load or no-load conditions but it cannot
interrupt the fault currents.
The switches may be classified into:
Air-break switch. It is an air switch and is designed to open a circuit under load.
Air-break switches are generally used outdoor for circuits of medium capacity.
Isolator or disconnecting switch. It is designed to open a circuit under no load. Its
main purpose is to isolate one portion of the circuit from the other and is not
intended to be opened while current is flowing in the line.
FUSES:
A fuse is a short piece of wire or thin strip which melts when excessive current
flows through it for sufficient time. It is worthwhile to note that a fuse performs
both detection and interruption functions.
Relays:
A relay is a device which detects the fault and supplies information to the breaker
for circuit interruption.
________________________________________________________________
________________________________________________________________
________________________________________________________________
________________________________________________________________
Objective
Equipment
1. MCB circuit breaker
Theory
Circuit Breaker:
A circuit breaker is equipment which can break of the circuit.
(i) Make or break a circuit either manually or by remote control under normal
conditions
(ii) Break a circuit automatically under abnormal conditions (fault) i.e. Overload
short circuit
(iii) Make a circuit either manually or by remote control under fault conditions.
Operating Principle:
A circuit breaker essentially consists of fixed and moving contacts, called
electrodes.
Under normal operating conditions, these contacts remain closed and will not open
automatically until and unless the system becomes faulty. Of course, the contacts
can be opened manually or by remote control whenever desired. When a fault
occurs on any part of the system, the trip coils of the circuit breaker get energized
and the moving contacts are pulled apart by some mechanism, thus opening the
circuit.
The failure of the bushing can occur in two ways. Firstly, the breakdown may be
caused by puncture i.e., dielectric failure of the insulating material of the bushing.
Secondly, the breakdown may occur in the form of a flash-over between the
exposed conductor at either end of the bushing and the earthed metal.
(ii) Circuit breaker contacts. The circuit breaker contacts are required to carry
normal as well as short-circuit current. In carrying the normal current, it is desirable
that the temperature should not rise above the specified limits and that there should
be low voltage drop at the point of contact.
(iii) Instrument transformers. In a modern power system, the circuits operate at
very high voltages and carry current of thousands of amperes. The measuring
instruments and protective devices cannot work satisfactorily if mounted directly on
the power lines. This difficulty is overcome by installing instrument transformers
on the power lines.
Conclusion
In an over current relay the actuating quantity is only current. There is only
one current operated element in the relay. Under fault condition. When the
relay current exceed from pick up current relay activate automatically and
operate the circuit breaker.
CONCLUTIONS:
________________________________________________________________
________________________________________________________________
________________________________________________________________
________________________________________________________________
Objective
Turn ratio and transformation ratio of transformer of V.T
Performance test of V.T
Define line voltage ,phase voltage
Uses of V.T
Equipment
S.No Name OF Equipment Quantity
01 voltage Transformer 01
02 Auto transformer(variable AC supply) 01
03 Volt meter 02
04 Loads 01
Theory
Voltage Transformer:
The Voltage Transformer can be thought of as an electrical component rather than an
electronic component. A transformer basically is very simple static (or stationary)
electro-magnetic passive electrical device that works on the principle of Faraday’s
law of induction by converting electrical energy from one value to another. A
transformer operates on the principals of “electromagnetic induction”, in the form
of Mutual Induction.
Voltage transformer also called potential transformer(PT). It is essentially a step
down transformer and steps down the voltage to a known ratio. The primary of this
transformer consists of a large number of turns of fine wire connected across the
line. The secondary winding consists of a few turns and provides for measuring
instruments and relays a voltage which is a known fraction of the line voltage.
i.e A voltage transformer has 1500 turns of wire on its primary coil and 500 turns
of wire for its secondary coil. What will be the turns ratio (TR) of the transformer.
This ratio of 3:1 (3-to-1) simply means that there are three primary turns for every
one secondary turn.
Transformation ratio
The invers of turn ratio ,its define the ratio between secondary turns or voltage to
the primary turns or voltage of transformer.
Ns Vs Ip
.transformation ratio K= = =
Np Vp Is
1. They reduce voltage signal for the purpose of measurement, control and protection.
2. P.T isolate the relay and instruments circuit from high input voltage.
3. Suitable for operation of relay and instrument connected to their secondary.
Observation Table
S.No Primary Secondary Turn ratio Transformation N × Vs−Vp
Ratio error¿ ×100
Voltage Vp voltage Vs N=Vp/Vs ratio k=Vs/Vp Vp
01
02
03
Lab No. 05
To study the operation of over current relay and plot the
performance characteristics
Objective
Equipment
Theory
Working : Over current relay are fed from current transformer whenever the current
through the relay exceeds the preset value the relay operate and activates the trip coil
of the circuit breaker ,isolating the faulty section from healthy section of electrical
system.
Application of over current protection
Overcurrent protection is used almost in all electrical equipment such as HT lines,
Transformer, Generators, Motors etc.
Pick-up current. It is the minimum current in the relay coil at which the relay starts
to operate. So long as the current in the relay is less than the pick-up value, the relay
does not operate and the breaker controlled by it remains in the closed position.
CONCLUTIONS:
Lab No. 06
To determine the transformation ratio of the current
transformer.
Objective
To study the transformation Ratio of the CT transformer
Apparatus:
S.No Apparatus Quantity
01 Standard cable 01
02 Transformer turn ratio(TTR) meter 01
03 Current transformer 01
04 Multi meter 01
Theory:
Transformer Ratio: In general, the transformation ratio can be defined as the ration
of the voltage present at the secondary windings of the transformer to the voltage
present at the primary windings of the same transformer. In simple words, it can
also be said that the transformation ratio is the ratio of secondary voltage to the
primary voltage. As we all know that the voltage is represented by the symbol “V”.
The secondary voltage is represented by “VS”. Similarly, the primary voltage is
Transformer Ratio=Vs/Vp
Turns Ratio:As it is cleared from its name, the turn ratio can be defined as the ratio
between the number of turns of secondary winding to the number of turns in the
primary winding. The turns are usually represented in theoretical knowledge by
“N”. The turns in primary winding can be represented by “NP” whereas the turns in
the secondary winding can be represented by “NS”.
The expression to represent the turns ration can be given as:
Turns Ratio=secondary Turn/ primary Turns
Transformer Ratio=Ns/Np
Current Ratio:-The current ratio can be defined as the ratio of the current flowing
through the primary winding of a transformer to the current flowing through the
secondary winding of the same transformer. In simple words, we can say that the
ratio of the primary current to the secondary current is known as the current ratio. In
theoretical expression, current is normally represented by the symbol “I”. The
secondary current is represented by “IS” and the primary current is represented
by “IP”. The transformer ratio can be represented by the expression shown below.
Current Ratio= Primary Current/ secondary Current
Transformer Ratio=Ip/Is
Procedure:
The current transformer basically consists of an iron core upon which primary and
secondary windings are wound. The primary winding of the transformer is
connected in series with the load and carries the actual current flowing to the load,
while the secondary winding is connected to a measuring device or a relay. The
number of secondary turns is proportional to the current flowing through the
primary; i.e., the larger the magnitude of current flowing through the primary, more
the number of secondary turns.
The ratio of primary current to the secondary current is known as the current
transformation ratio of the CT. Usually the current transformation ratio of the CT is
Diagram:
01
02
Observation Table:
CONCLUTIONS:
________________________________________________________________
________________________________________________________________
________________________________________________________________
________________________________________________________________
Lab No. 07
To study the time delay relay and connection
Objective
To study Time delay Relay.
Apparatuses
Timer Relay.
Theory
Time delay relay:
The type of time delay relay used will depend on the system setup. On- and off-
delay timers represent the most typical time delay relay timers in use. Other types
include interval-on-operate, flasher, and repeat cycle timers.
On-delay timers:
Normally open, on-delay timers start timing when the input voltage (power) is
applied. The output is energized at the end of the delay. Input voltage has to be
removed to de-energize the output and reset the time delay relay.
Also referred to as delay-on-operate timers, they are often used for blower motors
to delay the operation for a specific time period after a gas, electric, or oil heater has
been turned on. On-delay timers are also used to stagger starting times for multiple
compressors or motors that are activated by the main switch. This avoids excessive
Off-delay timers can be used in air-conditioning systems to hold the blower motor
in operation for a specific time period after the thermostat has turned the cooling
compressor off. They may also be used to operate electrical devices and motors for
a specified time, such as coin-operated dryers in commercial laundries. Other
applications include gas valve controls, telephone circuit control, and elevator
door control.
CONCLUTIONS:
________________________________________________________________
________________________________________________________________
________________________________________________________________
Electrical Engineering Technology Page 21
________________________________________________________________
Lab No.08
To study over voltage relay and their connection
Objective
Overvoltage Relay.
Equipment
S.No Equipment Quantity
1 Relay 1
2 circuit breaker 1
3 Connector wire --
Theory
Overvoltage Relay:
It uses a normally closed contact (N.C.). As long as the monitored voltage remains
below the maximum voltage the equipment can withstand (Pick-Up Setting), the
relay remains de-energized and the N.C. contact remains closed, keeping the load
energized.
If the operating voltage increases beyond the maximum rating of the equipment, the
relay energizes and the N.C. contact opens, turning off the load. When the voltage
CONCLUTIONS:
________________________________________________________________
________________________________________________________________
________________________________________________________________
Lab No. 09
To study the operation of directional over current relay
Objective
Equipment
S.No Apparatus Rating Quantity
01 Single phase Transformer 2MVA 02
02 Power grid 100MVAsc 01
03 Directional Over current relay SPAS 348C 02
04 Current Transformer(CT) 20:5 Ratio 02
05 Lamp 0.5MVA 03
06 Circuit Breaker 4.76 kv,1200A,2cycle 03
07 Bus Bar 4kv 06
Working :
Directional Over Current Relay This is also a special type of over current relay with
a directional features. This directional over current relay employs the principle of
actuation of the relay, when the fault current flows into the relay in a particular
direction. If the power flow is in the opposite direction, the relay will not operate.
Normally, the conventional over current relay (non-direction) will act for fault
current in any direction. The directional over current relay recognizes the direction
in which fault occurs, relative to the location of the relay
ETAP Simulation of directional over current relay
Equipment
S.N Apparatus Rating Quantity
o
1 Grade 60MVAsec, 11KV 1
2 Transforms 2MV , 33KV 2
2MV , 11KV
3 Circuit breakers 1200 Amp 3
4 Current transformers 20:5 3
5 Over current relay - 1
6 Deferential relay - 1
7 Buses - 3
8 Lamp load 1 MVA 1
Theory
Differential protection scheme in a power transformer
This type of relay is applicable for unit protection. There are two number of CTs
with respect to primary and secondary. During the normal condition the both
primary and secondary currents are balanced.
Principle of Differential Protection scheme is one simple conceptual technique. The
differential relay actually compares between primary current and secondary current
of power transformer, if any unbalance found in between primary and secondary
currents the relay will actuate and inter trip both the primary and secondary circuit
breaker of the transformer.
Lab No. 12
Primary and back up protection
Objective
The backup relaying often provides primary protection when the primary
relays are out of service for repairs.
Equipment
S.No Name OF Equipment Rating Quantity
1 Grid 50 MVAsec,11kv 01
2 100MVA, 11kv to 500kv
Theory:
Primary Protection
The main protection or primary protection is the first line protection which provides
quick-acting and selective clearing of a fault within the boundary of the circuit
section or element it protects. The main protection is provided in each section of an
electrical installation.
Backup Protection
The backup protection provides the back up to the main protection whenever it fails
in operation or its cut out for repairs. The backup protection is essential for the
proper working of the electrical system. The backup protection is the second line of
defense which isolates the faulty section of the system in case the main protection
fails to function properly. The failure of the primary protection occurs because of
the failure of the DC supply circuit, current or voltage supply to relay circuit, relay
protective circuit or because of the circuit breaker.
The backup protection may be provided either on the same circuit breaker which
would be normally opened by the main protection or in the different circuit breaker.
The backup protection is mainly used where the main protection of the adjacent
circuit is unable to back up the main protection of the given circuit. Sometimes for
simplification, the backup protection has a low sensitivity and operated over a
limited backup zone.
Circuit Diagram
Lab No. 13
To study star to star and delta to delta connection
Objective
Equipment
S.No Apparatus Quantity
01 three phase Transformer 01
02 Single phase generators 03
03 Scope 02
04 Voltage and current measuring meter 02
05 Loads (100K,) 03
Theory
Three-phase transformer connections
The three phase transformer consists three transformers either separate or
combined with one core. The primary and secondary of the transformer can be
independently connected either in star or delta. There are four possible connections
for a 3-phase transformer bank.
The choice of connection of three phase transformer depends on the various factors
likes the availability of a neutral connection for grounding protection or load
connections, insulation to ground and voltage stress, availability of a path for the
flow of third harmonics, etc. The various types of connections are explained below.
The only disadvantage of the delta-delta connection is that there is no neutral. This
connection is useful when neither primary nor secondary requires a neutral and the
voltage are low and moderate.
Observation Table
S.No Input Output Input Out Put Efficiency Voltage
Voltage voltage Power Power Regulation
01
02
03