HD30 Series Vector Control Inverter User Manual - Hpmont - V1.1 PDF
HD30 Series Vector Control Inverter User Manual - Hpmont - V1.1 PDF
Thank you for purchasing HD30 series vector control inverter manufactured by
Shenzhen Hpmont Technology Co., Ltd.
This User Manual describes how to use HD30 series inverters and their
installation wiring, parameter setting, troubleshooting and daily maintenance etc.
Before using the product, please read through this User Manual carefully. In
addition, please do not use this product until you have fully understood safety
precautions.
Note:
Preserve this Manual for future.
Due to product upgrade or specification change, and for the purpose of improving
convenience and accuracy of this manual, this manual’s contents may be modified.
If you need the User Manual due to damage, loss or other reasons, please contact
the regional distributor of our company or directly contact our company Technical
Service Center.
For the first time using, the user should carefully read this manual.
If you still have some problems during use, please contact our company Technical
Service Center.
Telephone: 4008-858-959 or 189 4871 3800
The product warranty is on the last page of this Manual, please preserve it for future.
Connection with peripheral devices
MCCB
Contactor
AC input reactor
EMI filter
Braking resistor
(optional)
Ground connection
EMI filter
AC output reactor
Motor
Ground connection
QUICK START for USER MENU of GROUP U
After finish setting, modifying the setting value of map (U00.01 and U00.03) can change value of
F00.13 and F03.01 automatically.
Factory setting
The user menu Group U can set up to 16 parameters, of which there are 14 parameters have
been set.
Note:
Some parameters have been set (factory setting) so that you could not set for the initial use.
Control the start/stop and set the running frequency via using the display panel
1. Power on. Using the display panel can set motor parameters (see the motor nameplate
parameter), running frequency and acceleration/deceleration time. See the following table.
2. Pressing panel’s RUN key can start the inverter, and pressing STOP key can stop the
inverter outputting.
Control the start/stop via terminals and set the running frequency via display panel
1. The terminal DI1 is forward running signal input, and DI2 is reverse running signal input, their
wirings are as following figure.
2. After power on, set the functional parameters in accordance with wirings, as following table.
No. Parameter name Setting value Meaning
F00.11 Command setting source selection 1 Terminal running command source
Forward running function (terminal
F15.00 DI1 terminal function selection 2 (factory setting)
forward signal input)
Rervese running function (terminal
F15.01 DI2 terminal function selection 3 (factory setting)
rervese signal input)
3. Set motor parameters (see motor nameplate parameters), running frequency and
acceleration/deceleration time via the display panel, as following table.
No. Parameter name No. Parameter name
F08.00 Rated power of motor 1 F00.13 Starting frequency digital setting
F08.01 Rated voltage of motor 1
F08.02 Rated current of motor 1 F03.01 Acceleration time 1
F08.03 Rated frequency of motor 1 F03.02 Deceleration time 1
F08.04 Rated RPM of motor 1
4. Close the K1 of the wiring diagram, the motor will run forward; close K2, run reverse;
simultaneously close or disconnect, the motor will stop.
Control the start/stop via terminals and set the running frequency via analogue
1. The terminal DI1 is forward running signal input, and DI2 is reverse running signal input, their
wirings are as following figure.
Forward terminal K1
DI1 DO1
K2 Output indicating signal at running
Reverse terminal
DI2
R1C
COM Common terminal
+10 R1B
Analogue input 1 Fault indication normally closed contact
AI1
GND R1A
Fault indication normally open contact
2. After power on, set the functional parameters in accordance with wirings, as following table.
No. Parameter name Setting value Meaning
F00.10 Frequency setting source selection 3 Analogue setting
F00.11 Command setting source selection 1 Terminal running command source
Forward running function (terminal
F15.00 DI1 terminal function selection 2 (factory setting)
forward signal input)
Rervese running function (terminal
F15.01 DI2 terminal function selection 3 (factory setting)
rervese signal input)
Frequency setting source (set by
F16.01 Analogue input AI1 function selection 2 (factory setting)
AI1)
3. Set motor parameters (see motor nameplate parameters), and acceleration/deceleration time
via the display panel, as following table.
R1B
Fault indication normally closed contact
12345678
RJ45
MODBUS R1A
SCI communication Fault indication normally open contact
communication terminal
2. After power on, set the functional parameters in accordance with wirings, as following table.
No. Parameter name Setting value Meaning
F00.10 Frequency setting source selection 2 SCI communication setting
F00.11 Command setting source selection 1 Terminal running command source
Forward running function (terminal
F15.00 DI1 terminal function selection 2 (factory setting)
forward signal input)
Rervese running function (terminal
F15.01 DI2 terminal function selection 3 (factory setting)
rervese signal input)
F15.18 DO1 terminal function selection 2 (factory setting) Inverter is running
F17.00 Data format 0 (factory setting) 1-8-2 format, no parity, RTU
F17.01 Baud rate 3 (factory setting) 9600bps
F17.02 Local address 2 (factory setting)
3. Set motor parameters (see motor nameplate parameters) and acceleration/deceleration time
via the display panel, as following table.
No. Parameter name No. Parameter name
F08.00 Rated power of motor 1 F08.04 Rated RPM of motor 1
F08.01 Rated voltage of motor 1
F08.02 Rated current of motor 1 F03.01 Acceleration time 1
F08.03 Rated frequency of motor 1 F03.02 Deceleration time 1
4. Close the K1 of the wiring diagram, the motor will run forward; close K2, run reverse;
simultaneously close or disconnect, the motor will stop.
5. Modify the running frequency via SCI communication function code 0X06 writing register
0x3201. Such as: modify the local address two of slave with running frequency of 45.00Hz, as
following table.
R1C
Common terminal
12345678
RJ45
MODBUS
R1B
SCI communication Fault indication normally closed contact
communication terminal
R1A
Fault indication normally open contact
2. After power on, set the functional parameters in accordance with wirings, as following table.
No. Parameter name Setting value Meaning
F00.10 Frequency setting source selection 2 SCI communication setting
Command setting source selection SCI communication running
F00.11 2
command source
F17.00 Data format 0 (factory setting) 1-8-2 format, no parity, RTU
F17.01 Baud rate 3 (factory setting) 9600bps
F17.02 Local address 2 (factory setting)
3. Set the motor parameters (see motor nameplate parameters) and acceleration/deceleration
time via the display panel, as following table.
No. Parameter name No. Parameter name
F08.00 Rated power of motor 1 F08.04 Rated RPM of motor 1
F08.01 Rated voltage of motor 1
F08.02 Rated current of motor 1 F03.01 Acceleration time 1
F08.03 Rated frequency of motor 1 F03.02 Deceleration time 1
4. Start and stop the local address 2 of inverter via SCI communication function code 0x06 writing
register 0x3200, such as forward start command, as following table.
Product Information 2
Mechanical Installation 3
Electrical Installation 4
Operation Instructions 5
Function Introduction 6
Troubleshooting 7
Maintenance 8
Options 9
Parameters A
Communication Protocol C
Shenzhen Hpmont Technology Co., Ltd Chapter 1 Safety Information and Precautions
80% Altitude(m)
1000 4000
Figure 1-1 Derating curve of inverter rated current and altitude
2.2 Nameplate
HZ A V RPM %
2.3 Specifications
Item Specification
Rated voltage and Single/three-phase: 200-240V, 50/60Hz
frequency Three-phase: 380-460V, 50/60Hz
Electrical
Speed setting mode Digital setting, analogue setting, SCI communication setting
Digital setting: 0.01Hz
Speed setting resulotion
Analogue setting: 0.1% × max-frequency
Speed control accuracy Sensorless vector control: ± 0.5%
Speed control range Sensorless vector control: 1:100
Torque control response Sensorless vector control: < 200ms
Start torque Sensorless vector control: 180% rated-torque /0.5Hz
Torque control accuracy ±5%
User-definable menu Total 16 user-definable maps, user can edit
Multi-group parameter
To achive 2 group parameters uploading to display panel of backup
upload and download
function
function
Programmable I/O Input interface programmable is up to 53 functions
interface Output interface pragrammable is up to 38 functions
Characteristic
Item Specification
Stall overvoltage Bus voltage can auto-control against overvoltage fault
Auto-limited current
Output current can auto-limit against overcurrent fault
protection
Overload pre-alarm and
Overload early pre-alarm and protect
alarm
Load loss protection Load loss alarm function
I/O phase loss
Protection
DI1-DI6
Digital input Remark: DI6 can be selectable for high-frequency input
(it can be extended to 9 inputs with HD30-EIO)
DO1, DO2
Digital output
Remark: DO2 can be selectable for high-frequency output
Item Specification
Five LEDs display
Setting frequency, output frequency, output voltage, output current,
Display panel
LED display
motor speed, output torque, switching value terminal, status
parameter, programm menu parameter and fault code etc.
LCD display Optional (HD-LCD), display operation contents in Chinese or English
Parameter copy Both LED and LCD display panel can achive quick parameter copy
Indicator 5 unit indicators, 5 status indicators
-10-+40℃, air temperature fluctuation is less than 0.5℃/min
The derating value of the output current of the inverter shall be 2% for
Operation temperature
each degree centigrade above 40℃. Max. allowed temperature is
50℃
Environment
2.4 Ratings
Rated capacity Rated input Rated output Motor power
Model
(kVA) current(A) current(A) (kW)
Single/three-phase power supply: 200-240V, 50/60Hz
HD30-2D0P4G 1.0 5.8 2.5 0.4
HD30-2D0P7G 1.5 10.5 4.0 0.75
HD30-2D1P5G 2.8 18.5 7.5 1.5
HD30-2D2P2G 3.8 24.1 10 2.2
Three-phase power supply: 200-240V, 50/60Hz
2
HD30-2T3P7G 5.9 19 17 3.7
HD30-2T5P5G 8.5 28 25 5.5
HD30-2T7P5G 11 35 32 7.5
HD30-2T011G 16 47 45 11
HD30-2T015G 21 62 55 15
HD30-2T018G 24 77 70 18.5
HD30-2T022G 30 92 80 22
HD30-2T030G 39 113 110 30
HD30-2T037G 49 156 130 37
HD30-2T045G 59 180 160 45
HD30-2T055G 72 214 200 55
HD30-2T075G 100 256 253 75
Three-phase power supply: 380-460V, 50/60Hz
HD30-4T0P7G 1.5 3.4 2.3 0.75
HD30-4T1P5G 2.5 5.2 3.8 1.5
HD30-4T2P2G 3.4 7.3 5.1 2.2
HD30-4T3P7G/5P5P 5.9/8.5 11.9/15 9.0/13 3.7/5.5
HD30-4T5P5G/7P5P 8.5/11 15/19 13/17 5.5/7.5
HD30-4T7P5G/011P 11/16 19/28 17/25 7.5/11
HD30-4T011G/015P 16/21 28/35 25/32 11/15
HD30-4T015G/018P 21/24 35/39 32/37 15/18.5
HD30-4T018G/022P 24/30 39/47 37/45 18.5/22
HD30-4T022G/030P 30/39 47/62 45/60 22/30
HD30-4T030G/037P 39/49 62/77 60/75 30/37
HD30-4T037G/045P 49/59 77/92 75/90 37/45
HD30-4T045G/055P 59/72 92/113 90/110 45/55
HD30-4T055G/075P 72/100 113/156 110/152 55/75
HD30-4T075G/090P 100/116 156/180 152/176 75/90
HD30-4T090G/110P 116/138 180/214 176/210 90/110
HD30-4T110G/132P 138/167 214/256 210/253 110/132
HD30-4T132G/160P 167/200 256/307 253/304 132/160
HD30-4T160G/200P 200/250 307/385 304/380 160/200
Nameplate
HZ A V RPM %
Display panel
Certification
Lower cover
Middle enclosure
Power terminal
connection hole
Plastic structure Metal structure
Danger
• Do not install if the inverter is imcomplete or impaired.
• Make sure that the inverter is far from the explosive and flammability things.
• Do not operate the inverter until the power is cut-off 10 minutes later.
3
Warning
• It is required not only carry the display panel and the cover but also the inverter bottom enclosure.
• Do not play metal into the inverter when installing.
HZ A V RPM %
A A
When one inverter is mounted on the top of the other, an air flow diverting plate should be fixed in
between. Just as shown in Figure 3-2.
HZ A V RPM %
HZ A V RPM %
HZ A V RPM %
H1
H
H2
Figure1
W 3
W1 D
4-Ød
H A V RPM %
H2
H1
H
Figure2
W D
W1
4-Ød
H2
H1
H
Figure3
HD30 series cabinet appearance is shown as Figure 3-3 and the dimension is as Table 3-3.
W
W1 4-Ød
D1
D
3
(a)
(b)
(c)
Figure 3-6 Dismantle of the plastic cover
Danger
• Only qualified electrical engineer can perform wiring job.
• Only when the power supply switch is completely off can you do the wiring job.
• You can’t open the inverter cover to do wiring operation until the power is cut-off 10 minutes later.
Do not wire or detach the inverter internal devices at power-on situation.
• Do not do wiring operation until the internal charge indicator of the inverter is off and the voltage
between (+) and (-) of the main circuit terminals is below 36V.
• Check the wiring carefully before connecting emergency stop or safety circuit.
• The earth terminal PE of the inverters must be reliable earthing. It must use two separate earth wire
due to the leakage current from the inverter to ground.
• It must use Type B mode when utilize earth leakage protection devices(ELCB/RCD). 4
• Do not touch the wire terminals of the inverter when it is live. The main circuit terminals is neither
allowed connecting to the enclosure nor short-circuiting.
Warning
• Do not do dielectric strength test on the inverter.
• Do wiring connection of the braking resistor or the braking unit according to the wiring figure.
• Make sure the terminals are fixed tightly.
• Do not connect the AC supply cable to the output terminals U, V, W of the inverter.
• Do not connect the phase-shifting capacitors to the output circuit.
• Be sure the inverter has ceased output before switching motor or change-over switches.
• The inverter DC bus terminals must not be short-circuited.
Danger
• The bare portions of the power cables must be bound with insulation tapes.
Warning
• Ensure that AC supply voltage is the same as inverter’s rated input voltage.
L1 L2 L3 U V W
(+) (-) BR PE
POWER MOTOR
L1 L2 L3 U V W
P1 (+) (-) BR PE
POWER MOTOR
L1 L2 L3
PE POWER
P1 (+) (-)
U V W
PE MOTOR
PE L1 L2 L3 (+) (-)
POWER
PE U V W
MOTOR
L1 L2 L3 (+) (-) BR U V W PE
Braking resistor
Optional AC reactor
Supply ground
4
Fuses
Mains supply
Figure 4-5 Main circuit connection of 5.5KW or below model
L1 L2 L3 P1 (+) (-) BR U V W PE
Mains supply
Figure 4-6 Main circuit connection of 7.5-55KW model
PE L1 L2 L3 P1 (+) (-) PE U V W
External
braking resistor
Supply ground
DC reactor
(optional)
External braking unit ground
Fuses
Mains supply
Figure 4-7 Main circuit connection of 75-280KW model
PE L1 L2 L3 (+) (-) PE U V W
External
braking resistor
Supply ground
Danger
• The control circuit is designed as ELV (Extra Low Voltage) circuit and basically isolated with the
power circuit. Do not touch the control circuit when the inverter is on power.
Warning
• If the control circuit is connected to the external devices with live touchable port (SELV circuit), it
should increase an additional isolating barrier to ensure that SELV classification of external devices
not be changed.
• If connect the communication terminal of the control circuit to the PC, you should choose the
RS485/232 isolating converter which meets the safety requirement.
In order to efficiently suppress the interference to control signals, the length of signal cables
4
should be less than 50m and keep a distance of at least 0.3m from the power lines. Please use
twisted-pair shielded cables for analogue input and output signals.
The positions of control terminal, wire jumper and SCI communication port in the control PCB are
shown in Figure 4-9.
Wire jumper Wire jumper
CN9 CN6
Figure 4-9 Positions of control terminal, wire jumper and SCI communication port in the control PCB
1
When pin 1 and pin 2 of the CN6 are short-circuited, AI2 channel
CN6
CN6 inputs voltage signal;
When pin 2 and pin 3 of the CN6 are short-circuited, AI2 channel
3
inputs current signal.
AO1 analogue output channel can select voltage or current signal.
1
When pin 1 and pin 2 of the CN7 are short-circuited, AO1 channel
CN7
CN7 outputs voltage signal;
When pin 2 and pin 3 of the CN7 are short-circuited, AO1 channel
3
outputs current signal.
AO2 analogue output channel can select voltage or current signal.
1
When pin 1 and pin 2 of the CN8 are short-circuited, AO2 channel
CN8
CN8 outputs voltage signal;
4
When pin 2 and pin 3 of the CN8 are short-circuited, AO2 channel
3
outputs current signal.
SCI communication can select proper resistance.
1
When pin 2 and pin 3 of the CN9 are short-circuited, no resistance;
CN9
CN9
When pin 1 and pin 2 of the CN9 are short-circuited, select the proper
3
resistance.
Pin 1 2 3 4 5 6 7 8
1 8
RJ45 terminal Signal +5V 485+ +5V GND GND GND 485- Reserved
1
1
AI2
CN7
CN8
CN9
Analogue ground
3
GND
GND Analogue ground
PE
Figure 4-12 HD30 control circuit connection diagram
SEL + 3.3V
+
Current
K R
-
DI1...DI6
COM
Figure 4-13 Dry contact connection when using internal 24V power
4
2.If the external power supply is used, the connection is as shown in Figure 4-14. (Note that the
SEL and the P24 are not short-circuited)
+ 24V
Dry contact connection
P24 using external power
SEL + 3.3V
+ +
DC - Current
12-30V
K R
-
DI1...DI6
COM
Figure 4-14 Dry contact connection when using external power
+ +
-
DC
12-30V
1 R
-
DI1
+ 3.3V
6 R
-
DI6
COM
Figure 4-15 Source input signal connection when using external power
2. If the external power supply is used, the drain connection is as shown in Figure 4-16. (Note
that the SEL and the P24 are not short-circuited)
SEL + 3.3V
COM +
1 R
-
DI1
+ 3.3V
6 R
-
External DI6
controller
Figure 4-16 Drain input signal connection when using external power
1 R
-
DI1
+ 3.3V
6 R
- 4
DI6
COM
Figure 4-17 NPN signal input connection when using internal 24V power
4. If the inverter’s internal +24V power supply is used, the common emitter output connection of
the PNP transistor in the external controller is as shown in Figure 4-18. (Note that the SEL and
the P24 are not short-circuited)
+ 24V
PNP connection
P24 using internal power
SEL + 3.3V
COM +
1 R
-
DI1
+ 3.3V
6 R
-
External DI6
controller
Figure 4-18 PNP signal input connection when using internal 24V power
Potentiometer
AI1
Control Filter capacitor
AI1 Control 0.022uF
Board
Board 50V
GND GND
PE Ferrite core
Figure 4-19 AI1 input terminal connection and disposal
Less than 50 m
Signal line winding on the
+10 ferrite core about 2 or 3 turns
Control
AI2
Potentiometer
+ 24V + 24V
Using internal power
P24 P24
R
R
DO2 DO2
+
f f - DC
12-30V
COM COM
> 30cm
> 50cm 4
Power or motor cables
Power cables
Signal/control cables
Figure 4-24 System wiring
Shielded/armoured cable: High frequency low impedance shielded cable should be used. For
example: copper net, aluminum net or iron net.
Normally, the control cables must use the shielded cables and the shielding metal net must be
connected to the metal enclosure of the inverter by cable clamps as shown in Figure 4-25.
PE PE
Enclosure Enclosure
Figure 4-25 Correct connection of the shielded cable
The inverter should be derated if the motor cables are too long or their cross sectional area (CSA)
is too large. The inverter’s cables should be the cables with specified CSA (see Table 4-1)
because the capacitance of the cable to ground is in proportional to the cable’s CSA. If the cable
with big CSA is used, its current should be reduced. The current should be decreased by 5%
when per level of CSA is increased.
4.5.4 Ground Connections
The earth terminals PE must be connected to earth properly. The earthing cable should be as
short as possible (the earthing point should be as close to the inverter as possible) and the
earthing area should be as large as possible.
The grounding resistance should be less than 10Ω for 380V Class inverters.
Do not share the earth wire with other devices such as welding machines or power tools. It could
share the earthing pole, but the motor and the inverter each have their own earthing pole, then
the earthing effect is better. The recommended and avoided earthing methods are respectively
shown in Figure 4-26 and Figure 4-27.
PE PE PE PE
Danger
• Only when the inverter terminal cover has been fitted can you switch on AC power source. Do not
remove the cover after power is switched on.
• Ensure the motor and the mechnical device are in the use application before the inverter starts.
• Keep away from the inverter if the auto-restart function is enabled at power outage.
• If changed the PCBA, you should correctly set the parameters before operating.
Warning
• Do not check or detect the signal during the inverter operation.
• Do not randomly change the inverter parameter setting.
• Please thoroughly complete all control debugging and testing, make all adjustments and conduct a
full safety assessment before switching the run command source of the inverter.
• Do not touch the energy-depletion braking resistor due to the high temperature.
5
5.1 Function Description
Note:
In the following sections, you may encounter control, running and status of the inverter
description many times.
Please read this section carefully. It will help you to correctly understand and use the functions to
be discussed.
Hz A V RPM %
PRG JOG
SHF ENT
RUN STOP
JOG Jog key In the mode of display panel control, jog start the inverter
ENT enter/confirm
Enter lower menu or confirm saving the data
key
Remote/local status Lighting: Indicate the inverter isn’t in display panel control mode
LO/RE
indicator Lightless: Indicate the inverter is in display panel control mode
Password locked Lighting: Indicate the user password lock of the inverter is avail
LOCK
status indicator Lightless: Indicate there is no user password or unlocked
Lighting: The unit of the present function parameter or status
display parameter is Hz
Frequency unit Flashing: Output frequency status display at the stop or run
Hz 5
indicator situation
Lightless: The unit of the present function parameter or status
display parameter is not Hz
Lighting: The unit of the present function parameter or status
display parameter is A
A Current unit indicator
Lightless: The unit of the present function parameter or status
display parameter is not A
Lighting: The unit of the current function parameter or status
display parameter is V
V Voltage unit indicator
Lightless: The unit of the current function parameter or status
display parameter is not V
Lighting: The unit of the present function parameter or status is
rpm
Rotary speed unit Flashing: Running rotatry speed status display at the stop or run
RPM
indicator situation
Lightless: The unit of the present function parameter or status
display parameter is not rpm
Lighting: The unit of the present function parameter or status
display parameter is %
% % unit indicator
Lightless: The unit of the present function parameter or status
display parameter is not %
The indicator has three statuses: Lightless, lighting, flashing statuses are shown as following:
It means lightless indicator; It means lighting indicator; It means flashing indicator.
LED display Meaning LED display Meaning LED display Meaning LED display Meaning
0 A J U
1 b L u
2 C n y
3 c o -
4 d P Point
5 E q Full display
6 F r No display
Flash
7 H S
modifiable
8 h T
9 i t
Hz A V RPM %
Hz A V RPM %
PRG
Hz A V RPM % Hz A V RPM %
Hz A V RPM % Hz A V RPM %
Hz A V RPM %
5
Hz A V RPM % Hz A V RPM % Hz A V RPM %
Hz A V RPM % Hz A V RPM %
PRG
Hz A V RPM % Hz A V RPM %
PRG PRG
Hz A V RPM % Hz A V RPM %
Hz A V RPM % Hz A V RPM %
1.5 s
FWD REV ALM LO/RE LOCK FWD REV ALM LO/RE LOCK FWD REV ALM LO/RE LOCK
later
Hz A V RPM % Hz A V RPM %
PRG JOG
FWD REV ALM LO/RE LOCK FWD REV ALM LO/RE LOCK FWD REV ALM LO/RE LOCK
FWD REV ALM LO/RE LOCK FWD REV ALM LO/RE LOCK FWD REV ALM LO/RE LOCK
RUN STOP
Hz A V RPM %
Uploading parameters
Figure 5-15 Display uploading parameter
Download:
When set the function parameter F01.02 = 2/3(download the display panel EEPROM storage
parameter 1/2 to the setting value of current function code) or F01.02=5/6 (downloaded functional
parameter includes the motor parameter), the display panel will display “dnLd”. When the
download is finished, the display panel will jump to display next function code F01.03.
FWD REV ALM LO/RE LOCK FWD REV ALM LO/RE LOCK
Hz A V RPM % Hz A V RPM %
Note:
1.When downloading parameters, it displays “dFAiL” which represents that the EEPROM
storage parameters of display panel and the function parameters of current inverter do not match.
First, you need upload the setting value of the correct function code to the EEPROM of display
panel, and then you can download.
2.When upload or download parameters, the display panel is flashing to display “E0022” which
represents that the EEPROM of display panel is fault. It will jump to next function code for 10
seconds later. The troubleshooting is in Chapter 7 (Page 123).
0: Display panel running source. Start and stop the inveter by pressing the key RUN , STOP , JOG .
1: Terminal running source. Start and stop by using the corresponding external terminals.
• External terminal FWD (multi-function terminal is set to 2), REV (multi-function terminal is set to
3), JOGF1 (multi-function terminal is set to 20), JOGR1 (multi-function terminal is set to 21),
JOGF2 (multi-function terminal is set to 22), JOGR2 (multi-function terminal is set to 23). For
more information please see Group F15.
2: SCI communication running source. Start and stop by SCI communication port according to
communication protocol.
F00.12 Function selection of the multi-function key 0-2【2】
0: Switch the display panel running direction. Switch the display panel running direction by key.
• When F00.11 = 0, it is valid. Do not save when power is off.
1: Switch local and remote control. Switch the local and remote control by key.
• When F00.11 = 0 or 1, it is valid.
2: The multi-function key is invalid.
F00.13 Starting frequency digital setting 0.00-upper limit【50.00Hz】
When F00.10 = 0 or 1, F00.13 start to set the initial frequency value.
Time
Tens:
0: Does not lock the parameter mapping relationship of Group U and Group F.
1: Lock the parameter mapping relationship of Group U and Group F.
F01.02 Function code parameter initialization (download) 0-6【0】
0: No operation. The inverter is in regular parameter read/write status. Display panel
• Whether can change the parameter it depends on the user’s Download
password status and the actual operating conditions. Display panel stored 6
function parameter
1: Restore to factory settings.
F01.02=2/3/5/6
• Except F01.00, F01.02, F01.03, Group F08, F13.01-F13.15,
HD30
F19.15, F19.19, F19.24, F20.08, F20.09, F20.21-F20.37,
F23.00 and Group y.
• Operation steps: If set F01.02 = 1, press to ensure and the parameters are restored to
factory settings. The display panel dispalys “rESEt”. Then the display panel will display
parameters in stop status after finish restoring to factory setting.
2: Download the display panel EEPROM parameter 1 to the current function code settings.
3: Download the display panel EEPROM parameter 2 to the current function code settings.
4: Clear fault information. The fault history of F20.21-F20.37 will be clear.
5: Download the display panel EEPROM parameter 1 to the current function code settings (including
the motor parameters).
6: Download the display panel EEPROM parameter 2 to the current function code settings (including
the motor parameters).
F01.03 Display panel EEPROM parameter initialization (upload) 0-2【0】
0: No operation. The inverter is in regular parameter read/write status. Display panel
1: Upload the current function code settings to the display panel Upload
EEPROM parameter 1. HD30 present setting
2: Upload the current function code settings to the display panel function parameter
EEPROM parameter 2. F01.03=1/2
Note: F01.00, F01.02, F01.03, F20.21-F20.37 and Group y do not HD30
upload or download.
Frequency
F02.02
F02.01 Forward F00.19 F02.03 Time
0
F02.03
F02.02 Reverse
F00.19: dead time of direction switch
1: Brake first and then start from DWELL frequency.
• Refer to F02.04 and F02.05 parameters for the DC braking.
• Starting DC braking is enabled only in the process from the stop status to running status. But it
is disabled in the process of direction switch, as shown in the figure. There is no F02.05 (DC
braking time) when reverse.
Frequency
F02.02
F02.01 F02.05 Forward F00.19 F02.03 Time
0
F02.03
F02.02 Reverse
F00.19: dead time of direction switch
Time
F02.05 = 0.0s, there is no DC braking F02.05
process at start. Run command
• Only when F02.00 = 1 will F02.05 be
enabled.
F02.06 Speed tracking mode selection 0,1【0】
0: Searching based on residual voltage.
• The inverter injects certain frequency’s voltage to the motor and starts speed searching
according to F02.08 setting.
1: Searching based on current.
• The inverter injects current to the motor according to F02.08 setting and starts speed searching
according to F02.07 setting.
F02.14
• Only when F02.13 = 0 will it be enabled. Time
• Set F02.14 or F02.15 as 0, DWELL frequency
at stop is disabled.
Frequency
0: Linear acceleration or deceleration. Output
frequency increases or decreases according F00.06
to the constant slope, as shown in figure.
0
Acc. time Dec. time Time
Frequency
1: S-curve acceleration or deceleration. F00.06
Output frequency increases or decelerases T1:F03.11
according to the S-curve. T2:F03.12
• Refer to F03.11-F03.14 about the T3:F03.13
corresponding parameters of S-curve. T4:F03.14
In the figure:
0
• T5 is the setting acceleration time.
T1 T2 T3 T4 Time
• T6 is the setting deceleration time. T5 T6
• T7 is the actual acceleration time. T7 T8
• T8 is the actual deceleration time.
F03.01 Acceleration time 1 0.1-6000.0
F03.02 Deceleration time 1 【15kW and below
F03.03 Acceleration time 2 inverter: 10.0s】
F03.04 Deceleration time 2 【18.5-55kW
F03.05 Acceleration time 3 interter :30.0s】
F03.06 Deceleration time 3 【75kW and above
F03.07 Acceleration time 4 inverter: 60.0s】
Time
F05.02 F05.04
F05.06 F05.08
F05.01 F05.03 P/A(reference) F05.01 F05.03 P/A(reference)
F05.05 F05.07 F05.05 F05.07
Inflection point 1
F05.16 F05.10
F05.15 F05.13 F05.11 F05.09 P/A(reference) F05.15 F05.13 F05.11 F05.09 P/A(reference)
In the figure:
• P/A is terminal pulse/ analogue reference.
• Pulse frequency P is 100% corresponding to F16.17 maximum input pulse frequency.
• Analogue input value (A) is 100% corresponding to 10V or 20mA.
F05.17 Skip frequency 1 F00.09-upper limit
F05.18 Skip frequency 2 【0.00Hz】
F05.19 Skip frequency 3
F05.20 Range of skip frequency 0.00-30.00【0.00Hz】
The setting of skip frequency is for
the inverter’s output frequency to Setting frequency after adjusted
avoid resonance with the load.
F05.19
• The inverter will skip the above
frequencies as shown in figure.
Up to 3 skip frequency ranges F05.18 6
can be set. Skip range
F05.17
Setting frequency
• During the process of acceleration/ deceleration, the inverter will run with countinous frequency
output, ignoring the skip frequency ranges. But the inverter will not run at constant speed in the
skip frequency ranges.
• Frequency setting is uncontinuous, while frequency output is continuous.
F05.21 Jog operation frequency digital setting 2 0.00-upper limit【5.00Hz】
When select jog operation 2 through terminal, set the jog frequency operation according to F05.21.
Units: PLC operation mode selection (taking 15-step PLC for example)
• 0: Stop after single cycle operation. The inverter stops automatically after one operating cycle. It
will start only after receiving the run command next time.
f3 f13
f2 f12
f4 f11 f14
f1 f15
f5 f10 Stop
f9
f6
f8
f7
T1 T2 T3 T4 T5 T6 T7 T8 T9 T10 T11 T12 T13 T14 T15
Run command
• 1: Maintain the final value after single cycle of PLC operation. The inverter will maintain the run
frequency and direction of the last step after completing one operating cycle.
f3 f13
f2 f12
f4 f11 f14
f1
f5 f15 Maintaining
f10
f9
f6
f8
f7 6
T1 T2 T3 T4 T5 T6 T7 T8 T9 T10 T11 T12 T13 T14 T15
Run command
• 2: Cycle operation. The inverter will operate with a new cycle from Step 1 automatically after
completing one operating cycle until receiving the stop command.
Operating with a new cycle
f3 f13 automatically
f2 f12
f4 f11 f14
f1 f1
f5 f15
f10
f9
f6 Stop
f8
f7
T1 T2 T3 T4 T5 T6 T7 T8 T9 T10 T11 T12 T13 T14 T15 T1
Run command
Stop command
Running frequency
Amplitude Fw = Fset x F07.04
FH = Fset + Fw
Upper limit of frequency FH
F07.02
Jump freq. = Fw x F07.05
Stop command
I1 I2
1-S
R2
S
U1
Io
Lm
The idling exciting current (F08.11) can be calculated by the motor’s rated current (F08.02) and
motor’s power factor (F08.05) or detected by motor auto-tuning (F08.06 = 2).
The relationship between rated torque current, idling exciting current and motor’s rated current is
below:
Rated torque current = F08.05 × F08.02
F08.01
• If F09.00 = 4 (user-definable curve), F09.06 is
F09.02 V3,F3
enabled.
V2,F2
• The V/f curve can be defined by connecting 3 F09.04
points of (V1, F1), (V2, F2) and (V3, F3), to
adapt to special load. F09.06 V1,F1
• According to the actual operation, set proper
curve to meet the requirements of load 0
characteristics. F09.05 F09.03 F09.01 F08.03 Frequency
• The inverter can accept that run command source switch changes while running, but only at
stop status all switches can be enabled.
11: Switch to terminal control mode.
• When this terminal function is enabled, the run command source will be forcibly switched to the
terminal control mode.
• The priority of frequency selection is below:
Terminal control mode to be the run command source > Display panel’s M key achieves local
and remote switching function (F00.12 = 1) > Run command source selection terminal 1and 2
(multi-function terminal is No. 9,10 function) > Run command source defined by F00.11.
• The modification of run command source is enabled only at stop.
12: External stop command input.
• When enabled, the inverter stops according to F02.13 (stop mode selection). It is valid for all
command source.
K4 K3 K2 K1 Frequency setting
0 0 0 0 Setting frequency
0 0 0 1 Multi-step frequency 1 (F06.00)
0 0 1 0 Multi-step frequency 2 (F06.01)
0 0 1 1 Multi-step frequency 3 (F06.02)
0 1 0 0 Multi-step frequency 4 (F06.03)
0 1 0 1 Multi-step frequency 5 (F06.04)
0 1 1 0 Multi-step frequency 6 (F06.05)
0 1 1 1 Multi-step frequency 7 (F06.06)
1 0 0 0 Multi-step frequency 8 (F06.07)
1 0 0 1 Multi-step frequency 9 (F06.08)
1 0 1 0 Multi-step frequency 10 (F06.09) 6
1 0 1 1 Multi-step frequency 11 (F06.10)
1 1 0 0 Multi-step frequency 12 (F06.11)
1 1 0 1 Multi-step frequency 13 (F06.12)
1 1 1 0 Multi-step frequency 14 (F06.13)
1 1 1 1 Multi-step frequency 15 (F06.14)
Output frequency
f1-f15 corresponds to multi-step frequency 1-15
f3 f13
f2 f12
f4 f11 f14
f1 f15
f5 f10
f6 f9
f8
f7
K1
K2
K3
K4
• Note: When select 20 and 21, the functions 24 and 25 are invalid.
26,27: Acceleration/deceleration time selection terminals 1 and 2.
• Acceleration/deceleration time 1-4 can be selected through logic combination of the terminals
1 and 2, as shown in table.
• The inverter can realise 4 groups Acc./Dec. time selection through the function of 2 Acc./Dec.
terminals.
• The inverter can realise 2 groups Acc./Dec. time selection through the function of 1 Acc./Dec.
terminals.
Acc./Dec. terminal 2 Acc./Dec. terminal 1 Acc./Dec. selection
0 0 Acc./Dec. time 1
0 1 Acc./Dec. time 2
1 0 Acc./Dec. time 3
1 1 Acc./Dec. time 4
123
Run command
K2 K1
P24 Mode 1 Mode 2
SEL 0 0 Stop Stop
K1 FWD 1 0 Reverse Stop
K2 REV 0 1 Forward Forward
COM
1 1 Stop Reverse
P24 P24
SEL SEL
SB2 FWD SB2 FWD
SB1 DIi SB1 DIi
SB3 REV K REV
COM COM
SB1:Normally-closed stop button (effective at the falling edge) K:Direction selection button (level on)
K = 0 (forward) K = 1 (reverse)
SB2:Normally-open forward button (effective at the risling edge)
SB1:Normally-closed stop button (effective at the falling edge)
SB3:Normally-open reverse button (effective at the rising edge) SB2:Normally-open run button (effective at the risling edge)
Time
Output signal
Limitation of upper/lower limits of wobble frequency
6
15: Simple PLC operating status indication. The indicating signal will be output when the inverter is at
simple PLC operating.
16: Simple PLC pausing indication. The indicating signal will be output if the simple PLC operation is
suspended by external terminals.
17: Simple PLC cycle completion indication. The indicating signal will be output if one cycle of PLC
operation is finished.
18: Completion of simple PLC operation stages. The indicating signal will be output if the current step
of PLC operation is finished.
19: Completion of simple PLC operation. The indicating signal will be output if the PLC operation is
finished.
20: Output data from SCI communication. Output indicating signal of open collector or relay is
controlled by the SCI communication directly.
21: Preset operating time out.
• The indicating signal will be output if the inverter’s operating time reaches the preset operating
time (F15.36)
Note: The No. 17, 18, 19 and 21 functions output indicating signal which is single pulse signal,
500ms.
Output
The pulse signal will be output if the inverter’s
output frequency is within the FAR range. As
shown in the right figure. Preset
frequency Detecting range
Time
DO 6
Time
F15.28 Zero-frequency operation threshold 0.00-upper limit【0.00Hz】
F15.29 Zero-frequency hysteresis
Running frequency
F15.28 and F15.29 are used to set the
F15.28
zero-frequency operation output control function, F15.29
please see the right figure.
Time
Running status
Zero-frequency
operation output
Time
Zero-frequency output
Time
Output frequency
The indicating signal can be output if the setting
frequency F15.30 is higher than certain frequency F15.31
(F15.31), and becomes disabled when the setting F15.32
frequency is lower than certain frequency of FDT1 FL
level (F15.31 - F15.32). Please refer to FL of the
right figure.
Time
DO
1 2 3 4 5 6 7 8
DI1
DO1
DO2
F15.39 Reserved
6
F15.40 Reserved
F15.41 Reserved
F15.42 Reserved
F15.43 Terminal output delay 0.0-100.0【0.0s】
1
Thermistor V V
Note: Only when using HD30-EIO will F16.03
and F16.04 (analogue inputs AI3 and AI4) be I R
AI4-
3
enabled.
F16.05 Analogue input AI1 bias -100.0-100.0【0.0%】
F16.08 Analogue input AI2 bias
F16.11 Analogue input AI3 bias
F16.14 Analogue input AI4 bias
F16.06 Analogue input AI1 gain -10.00-10.00【1.00】
F16.09 Analogue input AI2 gain
F16.12 Analogue input AI3 gain
F16.15 Analogue input AI4 gain
F16.07 Analogue input AI1 filtering time 0.01-10.00【0.05s】
F16.10 Analogue input AI2 filtering time 6
F16.13 Analogue input AI3 filtering time
F16.16 Analogue input AI4 filtering time
When select AI1-AI4 inputs as open-loop frequency setting source, the relationship between the
analogue input and the setting frequency is shown as figure:
The analogue voltage reasults from setting frequency signal disposed by analogue input filtering, bias
and gain. The relationship between the analogue voltage and the setting frequency is set by
parameters of Group F05.
• Analogue input gain and bias are involved in analogue calculation is as following formula: Y=kX+b
• Here: Y is the calculated analogue, X is the value before adjusting, k is the analogue input gain
(F16.06, F16.09, F16.12, F16.15), and b is the analogue input bias (F16.05, F16.08, F16.11,
F16.14).
• F16.07, F16.10, F16.13, F16.16 define the filtering time. It is used to filter the analogue signal.The
longer the filter time is, the higher the immunity level is, but the response time is prolonged. That
is, the shorter the filter time is, the quicker the response time is, but the lower the immunity level.
Note: Only when using HD30-EIO will F16.11-F16.16 (analogue inputs AI3 and AI4) be
enabled.
F16.17 Maximum input pulse frequency 0.0-50.0【10.0kHz】
When set the DI6 terminal as pulse input, F16.17 defines the maximum input pulse frequency.
F16.18 Input pulse filtering time 0-500【10ms】
It is used to filter the input pulse frequency and filter out the small fluctuations in the pulse frequency.
F16.22=50%
F16.22=0
50%
F16.23=200%
F16.23=100%
6
Preprocessing
Display panel
Initial value Save function at power off
Digital
Terminal UP/DN F19.03 and stop control F19.04
Auxiliary
SCI communication Digital frequency
setting Auxiliary
AI Analogue source setting
Gain process External reference
selection frequency 6
Pulse F19.02 curve selection F05.00
Pulse F19.00
Process PID
YES
NO YES
Fstart>Fmin fstart=Fmin Flow=0 H=Fcmd
Hz
YES Fcmd
Fmin
fstart=Fstart Fstart
Time
Voltage
F19.14
0: This function is disabled.
1: This function is enabled. And low-voltage Bus voltage
compensation is activated. F19.15
• If the bus voltage is lower than F19.15, the Output freq. Time
inverter will decrease the operating frequency
according to F19.13. Setting freq.
• If the bus voltage is higher than F19.15 and Acceleration
maintains the voltage rise diagnosis time
F19.13 time
(F19.14), the inverter will reset the setting
frequency to run. Otherwise, the inverter will Time
continue to decrease the running frequency.
• The carrier frequency will affect the operating noise of the motor. The higher the carrier frequency,
the lower the noise made by the motor. Please properly set the carrier frequency.
• When the value is higher than the factory setting, the inverter should be derated by 5% when per
1kHz is increased compared to the factory setting.
F23.01 Reserved
F23.02 PWM overshoot enable 0,1【1】
0: Disabled.
1: Enabled.
F23.03 PWM modulation mode 0-2【0】
0: Two-phase modulation or three-phase modulation.
1: Three-phase modulation.
2: Two-phase modulation.
Chapter 7 Troubleshooting
HD30 series inverter has inbuilt protective and warning self-diagnostic functions. If a fault occurs,
the fault code will be displayed on the display panel. At the same time, fault relay acts,
accordingly the inverter stops output and the motor coasts to stop.
When fault or alarm occurs, please record the fault details and take proper actions according to
the below Table 7-1. If you need some technical help, please contact to the suppliers or directly
call Shenzhen Hpmont Technology Co., Ltd.
After the fault is eliminated, please reset the inverter by any of the following methods:
1. Display panel.
2. External reset terminal (multi-function terminal set as No. 46 function).
3. Communication.
4. Switching on the inverter after switching off.
Table 7-1 Fault alarm description and counter-measures
Fault code Fault name Possible reasons of fault Counter-measures
• It is normal status of powering on
• At the begining of powering on
and powering off
and at the end of powering off
DC bus • Please check input power
-Lu- • Input voltage is too low
undervoltage voltage
• Improper wiring leads to
• Please check wiring and wire the
undervoltage of hardware
inverter properly
Inverter output
• Connect the inverter and motor
overcurrent (in
E0001 • Improper connection between properly
acceleration
inverter and motor • Please set correct motor
process)
Inverter output
• Improper motor parameters parameters (F08.00-F08.04、 7
• The rating of the used inverter F13.01-F13.05)
overcurrent (in
E0002 is too small • Select inverter with higher rating
deceleration
• Acceleration/deceleration time • Please set proper acceleration
process)
is too short time and deceleration time
Inverter output (F03.01-F03.08)
• Instant stop occurs, the
overcurrent (in
E0003 running motor is restarted • Please set start mode to be
constant speed
speed tracking (F02.00=2)
process)
DC bus over
• Please check power input
voltage
E0004 • Please set a proper value for
(in acceleration • Input voltage is too high
process) deceleration time (F03.02、
• Deceleartion time is too short
F03.04、F03.06、F03.08)
DC bus over • Improper wiring leads to
• Please check wiring and wire the
voltage overvoltage of hardware
E0005 inverter properly
(in deceleration • Instant stop occurs, the
• Please set start mode to be
process) running motor is restarted
speed tracking (F02.00=2)
DC bus over • Improper selection of the
• Select according to the
voltage braking devices
E0006 recommended braking devices of
(in constant
user manual
speed process)
Chapter 8 Maintenance
Many factors such as ambient temperature, humidity, dust, oscillation, internal component aging,
wear and tear will give rise to the occurrence of potential faults. Therefore, it is necessary to
conduct daily maintenance to the inverter.
• If the inverter has been transported for a long distance, please check whether the components
of the inverter are complete and the screws are well tightened.
• Please periodically clean the dust inside the inverter and check whether the screws are loose.
Danger
• Only a trained and qualified professional person can maintain the inverter.
• Maintenance personnel should take off all metal jewellery before carrying out maintenance or
internal measurements in the inverter. Suitable clothes and tools must be used.
• High voltage exists when the inverter is powered up or running.
• Checking and maintaining can only be done after the inverter’s AC power is cut off and wait for at
least 10 minutes. The cover maintenance can only be done after ensured that the charge indicator
inside the inverter and the indicators on the display panel are off and the voltage between main
circuit power terminals (+) and (-) is below 36V.
Warning
• For the inverter stored for more than 2 years, please use voltage regulator to increase the input
voltage gradually.
• Do not leave metal parts like screws or pads inside the inverter.
• Do not make modification on the inside of inverter without instruction from the supplier.
• There are IC components inside the inverter, which are sensitive to static electricity. Directly touch
the components on the PCB board is forbidden.
Chapter 9 Options
9.1 Extension I/O Card (HD30-EIO)
HD30 series inverters using with extension I/O card (HD30-EIO) can achieve the extension of
analogue input, digital input and relay contact output, shown as Figure 9-1.
CN4
CN4 external thermistor as motor overheat detection signal input;
When pin 2 and pin 3 of CN4 are short-circuited, AI4 channel R
1
inputs reference analogue.
GND
PE
Figure 9-3 Wiring of AI4 selected analogue input terminal
Thermistor
CN3
I/O card 3 3
V V
AI4-
CN4
GND I 1 R 1
PE
Figure 9-4 Wiring of AI4 as over-heated signal detection input terminal
Wiring of digital input terminal
Extension I/O card digital input terminals (DI7—DI9) have the same connection with control
board digital input terminals (DI1—DI6), please refer to section 4.4.4 digital input terminal wiring
of Control Terminal Connection.
CN2
CN2 inputs voltage;
When pin 2 and pin 3 of the CN2 are short-circuited, channel 1 I
3
inputs current.
Analogue input channel 2:
1
When pin 1 and pin 2 of the CN3 are short-circuited, channel 2 V
CN3
CN3 inputs voltage;
When pin2 and pin 3 of the CN3 are short-circuited, channel 2 I
3
inputs current.
76 ± 0.2
Mounting base
134.5 +0.1
134 ± 0.2
0
142
Mounting size
86 76.5 +0.1
0
Appendix A Parameters
Attributes are changed:
”*”: It denotes that the value of this parameter is the actual value which cannot be modified.
“×”: It denotes that the setting of this parameter cannot be modified when the inverter is in run
status.
”○”: It denotes that the setting of this parameter can be modified when the inverter is in run
status.
“―”: The same as the mapping functional parameter.
: It denotes that this parameter is enabled when using corresponding extension option.
Factory Modified
No. Name Range Unit Setting
Default attributes
Group d00 Status Display Parameters (refer to pages 54-59)
d00.00 Series of the inverter 0x10-0x50 *
Software version of the
d00.01 00.00-99.99 *
control board
d00.02 Reserved
Special software
d00.03 version of the control 00.00-99.99 *
board
d00.04 Reserved
Software version of the
d00.05 00.00-99.99 *
display panel
d00.06 Custom series No. 0-9999 *
Units: Display the current
driving motor
0: Motor 1
Motor and control 1: Motor 2
d00.07 *
mode Tens: Control mode
0: V/f control without PG
1: Reserved
2: Vector control without PG
Rated current of the 5.5kW or below type: 0.01A
d00.08 *
inverter 7.5kW or above type: 0.1A
Extension function of
d00.09 0: Standard inverter *
the inverter
Units:
Bit0: Inverter fault
Bit1: Run/stop
Bit2: Forward/reverse
Bit3: Zero speed running
Tens:
Bit1&Bit0: Acceleration/
deceleration/ constant
Bit2: Reserved
d00.10 Inverter status Bit3: DC braking (including *
start and stop DC braking)
Hundreds:
Bit0: Parameter auto-tuning
Bit1: Reserved
Bit2: Speed limiting value
Bit3: Reserved
Thousands:
Bit0: Stall overvoltage
Factory Modified
No. Name Range Unit Setting
Default attributes
Bit1: Current limiting
Bit2: Reserved
Bit3: Reserved
Master setting
d00.11 0-4 *
frequency source
Master setting
d00.12 0.01-400.00Hz *
frequency
Auxiliary setting
d00.13 0.01-400.00Hz *
frequency
d00.14 Setting frequency 0.01-400.00Hz *
Reference frequency
d00.15 (after acceleration/ 0.01-400.00Hz *
deceleration)
d00.16 Output frequency 0.01-400.00Hz *
d00.17 Setting speed 0-60000rpm *
d00.18 Running speed 0-60000rpm *
0: Positive sequence, L1(R)
preceding L2(S) preceding
Three-phase power
L3(T)
d00.19 supply input sequence *
1: Negative sequence, L1(R)
phase
preceding L3(T) preceding
L2(S)
d00.20 Output voltage 0-999V *
d00.21 Output current Actual value, unit is 0.1A *
d00.22 Reserved
0-300.0% (motor rated
d00.23 Output torque *
torque)
d00.24 Output power Actual value, unit is 0.1kW *
d00.25 DC bus voltage 0-999V *
Potentiometer input
d00.26 voltage of the display 0.00-5.00V *
panel
d00.27 AI1 input voltage 0.00-10.00V *
AI1 input voltage (after
d00.28 0.00-10.00V *
disposal)
d00.29 AI2 input voltage -10.00-10.00V * A
AI2 input voltage (after
d00.30 -10.00-10.00V *
disposal)
d00.31 AI3 input voltage -10.00-10.00V *
AI3 input voltage (after
d00.32 -10.00-10.00V *
disposal)
d00.33 AI4 input voltage -10.00-10.00V *
AI4 input voltage (after
d00.34 -10.00-10.00V *
disposal)
Factory Modified
No. Name Range Unit Setting
Default attributes
DI6 terminal pulse
d00.35 0-50000Hz *
input frequency
d00.36 AO1 output 0.00-10.00V *
d00.37 AO2 output 0.00-10.00V *
High-speed output
d00.38 0-50000Hz *
pulse frequency
d00.39 Heatsink temperature 0.0-999.9℃ *
d00.40 Setting line speed 0-max output line speed *
d00.41 Reference line speed 0-max output line speed *
d00.42 Reserved
d00.43 Reserved
d00.44 Process PID reference -100.0-100.0% *
d00.45 Process PID feedback -100.0-100.0% *
d00.46 Process PID tolerance -100.0-100.0% *
Process PID integral
d00.47 -100.0-100.0% *
item
d00.48 Process PID output -100.0-100.0% *
d00.49 External counting value 0-9999 *
Bit0-Bit8 corresponding to
DI1-DI9
0: Input terminal disconnect
with common terminal
d00.50 Input terminal status 1: Input terminal connect with *
common terminal
Factory Modified
No. Name Range Unit Setting
Default attributes
content
d00.53 Actual length 0-65535m *
d00.54 Total length 0-65535km *
d00.55 Total time at power-on 0-65535h *
d00.56 Total time at operation 0-65535h *
High bit of motor total
d00.57 0-65535k kW.h *
energy consumption
Low bit of motor total
d00.58 0.0-999.9kW.h *
energy consumption
High bit of energy con.
d00.59 0-65535k kW.h *
at this time running
Low bit of energy con.
d00.60 0.0-999.9kW.h *
at this time running
1-100
d00.61 Present fault *
100: means undervoltage
Group F00 Basic Parameter (refer to pages 59-62)
F00.00 Reserved
0: V/f control without PG
F00.01 Control mode selection 1: Reserved 0 1 ×
2: Vector control without PG
0: G type
F00.02 Inverter type setting 0 1 ×
1: P type
0: Motor 1
F00.03 Motor selection 0 1 ×
1: Motor 2
0: Option is invalid
HD30 general
1: HD30-EIO is valid
F00.04 extension option 0 1 ×
2: Reserved
selection
3: HD30-PIO is valid
HD30 extension
F00.05 0: No extension application 0 1 ×
application function
Inverter max. output
F00.06 50.00-400.00Hz 50.00Hz 0.01Hz ×
frequency
Upper limit of operation 0: Digital setting (F00.08)
F00.07 frequency setting 1: Analogue input AI setting 0 1 ×
source 2: Terminal pulse setting
A
Upper limit of operation
F00.08 0.00-F00.06 50.00Hz 0.01Hz ×
frequency
Lower limit of operation
F00.09 0.00-upper limit 0.00Hz 0.01Hz ×
frequency
0: Display panel digital
Frequency setting setting
F00.10 0 1 ×
sources selection 1: Terminal digital setting
2: SCI communication setting
Factory Modified
No. Name Range Unit Setting
Default attributes
3: AI analogue setting
4: Terminal pulse setting
Factory Modified
No. Name Range Unit Setting
Default attributes
F00.16 Interval of jog operation 0.0-100.0s 0.0s 0.1s ×
0: The same as run
Operation direction
F00.17 command 0 1 ×
selection
1: Opposite to run command
0: Reverse operation is
permitted
F00.18 Anti-reverse operation 0 1 ×
1: Reverse operation is
prohibitted
Dead time of direction
F00.19 0.0-3600.0s 0.0s 0.1s ×
switch
Key enable of optional 0: Enabled
F00.20 0 1 ○
display panel 1: Disabled
Dormant function 0: Disabled
F00.21 0 1 ×
selection 1: Enabled
Dormancy wake up
F00.22 0.0-360.0s 0.0s 0.1s ○
time
Group F01 Protection of Parameters ( refer to pages 62-64)
F01.00 User’s password 00000-65535 0 1 ○
Units:
0: Full menu mode
1: Checking menu mode
(Only different from factory
setting parameters can be
displayed)
Factory Modified
No. Name Range Unit Setting
Default attributes
settings (including the motor
parameters).
6: Download the display
panel EEPROM parameter 2
to the current function code
settings (including the motor
parameters).
0: No operation
1: Upload the current
function code settings to the
Display panel display panel EEPROM
F01.03 EEPROM parameter parameter 1 0 1 ○
initialization 2: Upload the current
function code settings to the
display panel EEPROM
parameter 2
Group F02 Run/Stop Control Parameters (refer to pages 64-68)
0: From the DWELL
frequency to start
1: Brake first and then start
from DWELL frequency
F02.00 Start mode selection 2: Start after speed tracking. 0 1 ×
If the result of speed tracking
is smaller than F02.02, it will
start from the starting
DWELL frequency
F02.01 Starting delay time 0.00-10.00s 0.00s 0.01s ×
Start DWELL
F02.02 0.00-upper limit 0.00Hz 0.01Hz ×
frequency setting
Retention time of
F02.03 starting DWELL 0.00-10.00s 0.00s 0.01s ×
frequency
DC braking current 0-100% (inverter’s rated
F02.04 50% 1% ×
setting current)
DC braking time at
F02.05 0.00-60.00s 0.50s 0.01s ×
start
0: Searching based on
Speed tracking mode residual voltage
F02.06 0 1 ×
selection 1: Searching based on
current
0: From the max. output
frequency to start speed
Speed search mode searching
F02.07 1 1 ×
based on current 1: From the stopping
frequency to start speed
searching
F02.08 Setting reference 0-100% (motor’s rated 50% 1% ×
Factory Modified
No. Name Range Unit Setting
Default attributes
current for speed current)
search
Acc./Dec. time of the
F02.09 1.0-50.0s 5.0s 0.1s ×
speed search
Waiting time of speed
F02.10 0.1-5.0s 1.0s 0.1s ×
search
V/f ratio of speed
F02.11 0.0-100.0% 100.0% 0.1% ×
search
Disposal time after
F02.12 0.01-5.00s 1.00s 0.01s ×
speed search
0: Decelerate to stop
(decreases to DWELL
frequency setting and holds
on retention time of DWELL
F02.13 Stop mode selection 0 1 ×
frequency, then it will stop)
1: Coast to stop
2: Decelerate to stop with DC
braking
DWELL frequency
F02.14 0.00-upper limit 0.00Hz 0.01Hz ×
setting at stop
Retention time of
F02.15 DWELL frequency at 0.00-10.00s 0.00s 0.01s ×
stop
DC braking initial
F02.16 0.00-50.00Hz 0.50Hz 0.01Hz ×
frequency at stop
DC braking waiting
F02.17 0.00-10.00s 0.00s 0.01s ×
time at stop
F02.18 DC braking time at stop 0.00-10.00s 0.50s 0.01s ×
0: The jog functions of start
and stop mode etc are
invalid.
F02.19 Jog control mode 0 1 ×
1: The jog functions of start
and stop mode etc are
enabled.
Group F03 Acceleration/Deceleration Parameters (refer to pages 68-70)
Acc./Dec. mode 0: Linear Acc. or Dec.
F03.00 0 1 ○
selection 1: S-curve Acc. or Dec.
F03.01 Acceleration time 1 0.1-6000.0s 0.1s ○
A
15kW or
F03.02 Deceleration time 1 0.1-6000.0s below 0.1s ○
F03.03 Acceleration time 2 0.1-6000.0s models: 0.1s ○
10.0s
F03.04 Deceleration time 2 0.1-6000.0s 0.1s ○
F03.05 Acceleration time 3 0.1-6000.0s 0.1s ○
18.5-55
F03.06 Deceleration time 3 0.1-6000.0s kW: 30.0s 0.1s ○
F03.07 Acceleration time 4 0.1-6000.0s 0.1s ○
F03.08 Deceleration time 4 0.1-6000.0s other 0.1s ○
Factory Modified
No. Name Range Unit Setting
Default attributes
models:
60.0s
Switching frequency of
F03.09 acceleration time 2 and 0.00-upper limit 0.00Hz 0.01Hz ×
time 1
Switching frequency of
F03.10 deceleration time 2 and 0.00-upper limit 0.00Hz 0.01Hz ×
time 1
S-curve characteristic
F03.11 time at starting 0.00-2.50s 0.20s 0.01s ○
acceleration
S-curve characteristic
F03.12 time at ending 0.00-2.50s 0.20s 0.01s ○
acceleration
S-curve characteristic
F03.13 time at starting 0.00-2.50s 0.20s 0.01s ○
deceleration
S-curve characteristic
F03.14 time at ending 0.00-2.50s 0.20s 0.01s ○
deceleration
Acceleration time of jog
F03.15 0.1-6000.0s 6.0s 0.1s ○
operation
Deceleration time of
F03.16 0.1-6000.0s 6.0s 0.1s ○
jog operation
Deceleration time of
F03.17 0.1-6000.0s 10.0s 0.1s ○
emergency stop
Group F04 Process PID Control (refer to pages 70-72)
Process PID control 0: PID control is disabled
F04.00 0 1 ×
selection 1: PID control is enabled
0: Digital reference
Reference source
F04.01 1: AI analogue reference 0 1 ×
selection
2: Terminal pulse reference
Feedback source 0: AI analogue feedback
F04.02 0 1 ×
selection 1: Terminal pulse feedback
Setting digital
F04.03 -10.00-10.00V 0.00V 0.01V ○
reference
F04.04 Proportional gain (P) 0.00-10.00 2.00 0.01 ○
F04.05 Integral time (I) 0.00-10.00s 1.00s 0.01s ○
F04.06 Integral upper limit 0.00-upper limit 50.00Hz 0.01Hz ○
0.00-10.00s
F04.07 Differential time (D) The differential is disabled 0.00s 0.01s ○
when F04.07 is set to 0
Differential amplitude
F04.08 0.00-upper limit 20.00Hz 0.01Hz ○
limit value
F04.09 Sampling cycle (T) 0.01-50.00s 0.10s 0.01s ○
Factory Modified
No. Name Range Unit Setting
Default attributes
F04.10 Bias limit 0.0-20.0% (reference) 2.0% 0.1% ○
0: Set by F04.13
PID regulator upper
F04.11 1: Set by AI analogue value 0 1 ×
limit source selection
2: Set by terminal pulse input
0: Set by F04.14
PID regulator lower
F04.12 1: Set by AI analogue value 0 1 ×
limit source selection
2: Set by terminal pulse input
PID regulator upper
F04.13 0.00-upper limit 50.00Hz 0.01Hz ×
limit value
PID regulator lower
F04.14 0.00-upper limit 0.00Hz 0.01Hz ×
limit value
PID regulator 0: Positive
F04.15 0 1 ×
characteristic 1: Negative
0: Stop integral regulation
when the frequency reaches
the upper or lower limit
Integral regulation
F04.16 1: Continue the integral 1 1 ×
selection
regulation when the
frequency reaches the upper
or lower limit
F04.17 PID output filter time 0.01-10.00s 0.05s 0.01s ○
0: PID regulation disable
reverse (When PID output is
PID output reverse negative, 0 is the limit)
F04.18 0 ×
selection 1: PID regulation enable
reverse (When F00.18 = 1
disable reverse, 0 is the limit)
PID output reverse
F04.19 0.00Hz-upper limit 50.00Hz 0.01Hz ×
frequency’s upper limit
Group F05 External Reference Curve Parameters (refer to pages 72-74)
Units: AI1 characteristic
curve selection
Tens: AI2 characteristic
curve selection
Hundreds: AI3 characteristic
curve selection
Thousands: AI4
External reference characteristic curve selection
A
F05.00 00000 1 ×
curve selection Ten thousands: Pulse input
characteristic curve selection
0: Line 1
1: Line 2
2: Polyline
Only when using HD30-EIO
can hundreds and thousands
be enabled.
Factory Modified
No. Name Range Unit Setting
Default attributes
Minimum reference of
F05.01 0.0-F05.03 0.0% 0.1% ○
line 1
Minimum reference
F05.02 corresponding value of 0.0-100.0% 0.0% 0.1% ○
line 1
Maximum reference of
F05.03 F05.01-100.0% 100.0% 0.1% ○
line 1
Maximum reference
F05.04 corresponding value of 0.0-100.0% 100.0% 0.1% ○
line 1
Minimum reference of
F05.05 0.0-F05.07 0.0% 0.1% ○
line 2
Minimum reference
F05.06 corresponding value of 0.0-100.0% 0.0% 0.1% ○
line 2
Maximum reference of
F05.07 F05.05-100.0% 100.0% 0.1% ○
line 2
Maximum reference
F05.08 corresponding value of 0.0-100.0% 100.0% 0.1% ○
line 2
Maximum reference of
F05.09 F05.11-100.0% 100.0% 0.1% ○
polyline
Maximum reference
F05.10 corresponding value of 0.0-100.0% 100.0% 0.1% ○
polyline
Inflection point 2
F05.11 F05.13-F05.09 100.0% 0.1% ○
reference of polyline
Inflection point 2
F05.12 0.0-100.0% 100.0% 0.1% ○
corresponding value
Inflection point 1
F05.13 F05.15-F05.11 0.0% 0.1% ○
reference of polyline
Inflection point 1
F05.14 0.0-100.0% 0.0% 0.1% ○
corresponding value
Minimum reference of
F05.15 0.0-F05.13 0.0% 0.1% ○
polyline
Minimum reference
F05.16 corresponding value of 0.0-100.0% 0.0% 0.1% ○
polyline
F05.17 Skip frequency 1 F00.09-upper limit 0.00Hz 0.01Hz ×
F05.18 Skip frequency 2 F00.09-upper limit 0.00Hz 0.01Hz ×
F05.19 Skip frequency 3 F00.09-upper limit 0.00Hz 0.01Hz ×
Range of skip
F05.20 0.00-30.00Hz 0.00Hz 0.01Hz ×
frequency
Jog operation
F05.21 0.00-upper limit 5.00Hz 0.01Hz ○
frequency digital
Factory Modified
No. Name Range Unit Setting
Default attributes
setting 2
Group F06 MS SPEED and Simple PLC (refer to pages 74-78)
Multi-step frequency
F06.00 F00.09-upper limit 3.00Hz 0.01Hz ○
command 1
Multi-step frequency
F06.01 F00.09-upper limit 6.00Hz 0.01Hz ○
command 2
Multi-step frequency
F06.02 F00.09-upper limit 9.00Hz 0.01Hz ○
command 3
Multi-step frequency
F06.03 F00.09-upper limit 12.00Hz 0.01Hz ○
command 4
Multi-step frequency
F06.04 F00.09-upper limit 15.00Hz 0.01Hz ○
command 5
Multi-step frequency
F06.05 F00.09-upper limit 18.00Hz 0.01Hz ○
command 6
Multi-step frequency
F06.06 F00.09-upper limit 21.00Hz 0.01Hz ○
command 7
Multi-step frequency
F06.07 F00.09-upper limit 24.00Hz 0.01Hz ○
command 8
Multi-step frequency
F06.08 F00.09-upper limit 27.00Hz 0.01Hz ○
command 9
Multi-step frequency
F06.09 F00.09-upper limit 30.00Hz 0.01Hz ○
command 10
Multi-step frequency
F06.10 F00.09-upper limit 33.00Hz 0.01Hz ○
command 11
Multi-step frequency
F06.11 F00.09-upper limit 36.00Hz 0.01Hz ○
command 12
Multi-step frequency
F06.12 F00.09-upper limit 39.00Hz 0.01Hz ○
command 13
Multi-step frequency
F06.13 F00.09-upper limit 42.00Hz 0.01Hz ○
command 14
Multi-step frequency
F06.14 F00.09-upper limit 45.00Hz 0.01Hz ○
command 15
Simple PLC control 0: No PLC operation
F06.15 0 1 ×
selection 1: Enabling PLC operation
Units: PLC operation mode
selection
0: Stop after single cycle A
operation
1: Maintain the final value
Simple PLC operation
F06.16 after single cycle of PLC 0000 1 ×
mode selection
operation
2: Cycle operation
Factory Modified
No. Name Range Unit Setting
Default attributes
0: Start from step 1
1: Continue to operate from
the step where the inverter
pauses
2: Continue to operate at the
frequency when the inverter
pauses
Factory Modified
No. Name Range Unit Setting
Default attributes
10
F06.38 Running time of step 11 0.0-3276.7 0.0 0.1 ○
Running time of step 0.0-3276.7
F06.40 0.0 0.1 ○
12
Running time of step 0.0-3276.7
F06.42 0.0 0.1 ○
13
Running time of step 0.0-3276.7
F06.44 0.0 0.1 ○
14
Running time of step 0.0-3276.7
F06.46 0.0 0.1 ○
15
Group F07 Wobble Operation Parameters (refer to pages 78-80)
Wobble operation 0: Disabled
F07.00 0 1 ×
selection 1: Enabled
Units: Start mode of wobble
operation
0: Auto start (according to
F07.03)
1: Manual start
Factory Modified
No. Name Range Unit Setting
Default attributes
F07.05 Jump frequency 0.0-F07.04 0.0% 0.1% ×
F07.06 Wobble operation cycle 0.0-999.9s 10.0s 0.1s ×
Rising time of triangle
F07.07 0.0-100.0% (F07.06) 50.0% 0.1% ×
wave
Group F08 Asynchronous Motor 1 Parameters (refer to pages 80-82)
F08.00 Rated power of motor 1 0.2-500.0kW 0.1kW ×
Rated voltage of motor
F08.01 0-inverter’s rated voltage Dependent 1V ×
1
on inverter
5.5kW above: 0.0-999.9A 0.1A
Rated current of motor model
F08.02 5.5kW or below: 0.00- ×
1 0.01A
99.99A
Rated frequency of
F08.03 1.0-400.0Hz 50.0Hz 0.1Hz ×
motor 1
F08.04 Rated speed of motor 1 1-24000rpm 1500rpm 1rpm ×
Dependent
F08.05 Power factor of motor 1 0.001-1.000 on inverter 0.001 ×
model
0: Auto-tuning is disabled
Parameter auto-tuning
F08.06 1: Stationary auto-tuning 0 1 ×
of motor 1
2: Rotary auto-tuning
5.5kW above: 0.000-
0.001Ω
Stator resistance of 9.999Ω
F08.07 ×
motor 1 5.5kW or below: 0.00-
0.01Ω
99.99Ω
5.5kW above: 0.000-
0.001Ω
Rotor resistance of 9.999Ω
F08.08 ×
motor 1 5.5kW or below: 0.00-
0.01Ω
99.99Ω
5.5kW above: 0.00- Dependent 0.01m
Leakage inductance of 500.00mH on inverter H
F08.09 ×
motor 1 5.5kW or below: 0.0- model
0.1mH
5000.0mH
5.5kW above: 0.00- 0.01m
Mutual inductance of 500.00mH H
F08.10 ×
motor 1 5.5kW or below: 0.0-
0.1mH
5000.0mH
5.5kW above: 0.0-999.9A 0.1A
Idling exciting current
F08.11 5.5kW or below: 0.00- ×
of motor 1 0.01A
99.99A
F08.12 Reserved
F08.13 Reserved
F08.14 Reserved
Group F09 V/f Control Parameters (refer to pages 82-85)
Factory Modified
No. Name Range Unit Setting
Default attributes
0: Line
1: Square curve
V/f curve selection of
F09.00 2: 1.2 exponential curve 0 1 ×
motor 1
3: 1.7 exponential curve
4: User-defined curve
V/f frequency value F3
F09.01 F09.03-F08.03 0.00Hz 0.01Hz ×
of motor 1
V/f voltage value V3 of
F09.02 F09.04-F08.01 0V 1V ×
motor 1
V/f frequency value F2
F09.03 F09.05-F09.01 0.00Hz 0.01Hz ×
of motor 1
V/f voltage value V2 of
F09.04 F09.06-F09.02 0V 1V ×
motor 1
V/f frequency value F1
F09.05 0.00-F09.03 0.00Hz 0.01Hz ×
of motor 1
V/f voltage value V1 of
F09.06 0-F09.04 0V 1V ×
motor 1
45kW and
below: 2.0%
55-132kW
Torque boost of motor 0.0-30.0% inverter:
F09.07 0.1% ×
1 0.0: Auto torque boost 1.0%
160kW and
above:
0.5%
Cut-off point used for
F09.08 manual torque boost of 0.0-50.0% (F08.03) 30.0% 0.1% ○
motor 1
Slip compensation gain
F09.09 0.0-300.0% 100.0% 0.1% ○
of motor 1
Slip compensation filter
F09.10 0.01-10.00s 0.10s 0.01s ○
time of motor 1
Slip compensation
F09.11 0.0-250.0% 200.0% 0.1% ×
limitation of motor 1
Compensation
F09.12
constant of motor 1
0.1-25.0s 2.0s 0.1s ○ A
F09.13 Reserved
0: Disabled
AVR function of motor 1: Enabled all the time
F09.14 1 1 ○
1 2: Disabled in deceleration
process
0: Oscillation suppression is
Oscillation-suppression
F09.15 dependent on the motor’s 1 1 ○
mode of motor 1
exciting current component
Factory Modified
No. Name Range Unit Setting
Default attributes
1: Oscillation suppression is
dependent on the motor’s
torque current component
Oscillation-suppression
F09.16 0-200 50 1 ○
coefficient of motor 1
F09.17 Reserved
F09.18 Reserved
Group F10 Motor 1 Vector Control Speed-loop Parameters (refer to pages 85-86)
Speed control
F10.00 proportional gain 1 of 0.1-200.0 20.0 0.1 ○
motor 1
Speed control integral
F10.01 0.00-10.00s 0.20s 0.01s ○
time 1 of motor 1
Speed control
F10.02 proportional gain 2 of 0.1-200.0 20.0 0.1 ○
motor 1
Speed control integral
F10.03 0.00-10.00s 0.20s 0.01s ○
time 2 of motor 1
Speed-loop PI
F10.04 switching frequency 1 0.00-50.00Hz 10.00Hz 0.01Hz ○
of motor 1
Speed-loop PI
F10.05 switching frequency 2 0.00-50.00Hz 15.00Hz 0.01Hz ○
of motor 1
Speed-loop integral 0.0-200.0% (motor rated
F10.06 180.0% 0.1% ○
limitation of motor 1 current)
0.00-1.00s
Speed-loop differential
F10.07 There is not the speed-loop 0.00s 0.01s ○
time of motor 1
differential when F10.07 = 0
0.000-1.000s
Speed-loop output filter
F10.08 When F10.08 = 0, the 0.020s 0.001s ○
time of motor 1
speed-loop filter is disabled
F10.09 Reserved
F10.10 Reserved
Motor torque limitation
0.0-200.0% (motor rated
F10.11 when motor 1 is 180.0% 0.1% ×
current)
forward
Motor torque limitation
0.0-200.0% (motor rated
F10.12 when motor 1 is 180.0% 0.1% ×
current)
reverse
Recreated torque
0.0-200.0% (motor rated
F10.13 limitation when motor 1 180.0% 0.1% ×
current)
is forward
Recreated torque
0.0-200.0% (motor rated
F10.14 limitation when motor 1 180.0% 0.1% ×
current)
is reverse
Factory Modified
No. Name Range Unit Setting
Default attributes
Group F11 Reserved
Group F12 Reserved
Group F13 Asynchronous Motor 2 Parameters (refer to pages 86-88)
0: V/f control without PG
Control mode selection
F13.00 1: Reserved 0 1 ×
of motor 2
2: Vector control without PG
F13.01 Rated power of motor 2 0.2-500.0kW 0.1kW ×
Rated voltage of motor
F13.02 0-inverter rated voltage Dependent 1V ×
2
on inverter
5.5kW above: 0.0-999.9A 0.1A
Rated current of motor model
F13.03 5.5kW or below: 0.00- ×
2 0.01A
99.99A
Rated frequency of
F13.04 1.0-400.0Hz 50.0Hz 0.1Hz ×
motor 2
F13.05 Rated speed of motor 2 1-24000rpm 1500rpm 1rpm ×
Dependent
F13.06 Power factor of motor 2 0.001-1.000 on inverter 0.001 ×
model
0: Auto-tuning is disabled
Parameter auto-tuning
F13.07 1: Stationary auto-tuning 0 1 ×
of motor 2
2: Rotary auto-tuning
5.5kW above: 0.000-
0.001Ω
Stator resistance of 9.999Ω
F13.08 ×
motor 2 5.5kW or below: 0.00-
0.01Ω
99.99Ω
5.5kW above: 0.000-
0.001Ω
Rotor resistance of 9.999Ω
F13.09 ×
motor 2 5.5kW or below: 0.00-
0.01Ω
99.99Ω
5.5kW or below: 0.00- Dependent 0.01m
Leakage inductance of 500.00mH on inverter H
F13.10 ×
motor 2 5.5kW or below: 0.0- model
0.1mH
5000.0mH
5.5kW above: 0.00- 0.01m
Mutual inductance of 500.00mH H
F13.11 ×
motor 2 5.5kW or below: 0.0-
0.1mH
A
5000.0mH
5.5kW above: 0.0-999.9A 0.1A
Idling exciting current
F13.12 5.5kW or below: 0.00- ×
of motor 2 0.01A
99.99A
F13.13 Reserved
F13.14 Reserved
F13.15 Reserved
F13.16 V/f curve selection of 0: Line 0 1 ×
Factory Modified
No. Name Range Unit Setting
Default attributes
motor 2 1: Square curve
2: 1.2 exponential curve
3: 1.7 exponential curve
4: User-defined curve
V/f frequency value F3
F13.17 F13.19-F13.04 0.00Hz 0.01Hz ×
of motor 2
V/f voltage value V3 of
F13.18 F13.20-F13.02 0V 1V ×
motor 2
V/f frequency value F2
F13.19 F13.21-F13.17 0.00Hz 0.01Hz ×
of motor 2
V/f voltage value V2 of
F13.20 F13.22-F13.18 0V 1V ×
motor 2
V/f frequency value F1
F13.21 0.00-F13.19 0.00Hz 0.01Hz ×
of motor 2
V/f voltage value V1 of
F13.22 0-F13.20 0V 1V ×
motor 2
45kW and
below: 2.0%
55-132 kW
Torque boost of motor 0.0-30.0% inverter:
F13.23 0.1% ×
2 0.0: Auto torque boost 1.0%
160kW and
above:
0.5%
Cut-off point used for
F13.24 manual torque boost of 0.0-50.0% (F13.04) 30.0% 0.1% ○
motor 2
Slip compensation gain
F13.25 0.0-300.0% 100.0% 0.1% ○
of motor 2
Slip compensation filter
F13.26 0.01-10.00s 0.10s 0.01s ○
time of motor 2
Slip compensation
F13.27 0.0%-250.0% 200.0% 0.1% ×
limitation of motor 2
Compensation
F13.28 0.1-25.0s 2.0s 0.1s ○
constant of motor 2
F13.29 Reserved
0: Disabled
AVR function of motor 1: Enabled all the time
F13.30 1 1 ○
2 2: Disabled in deceleration
process
0: Oscillation suppression is
Oscillation-suppression dependent on the motor’s
F13.31 1 1 ○
mode of motor 2 exciting current component
1: Oscillation suppression is
Factory Modified
No. Name Range Unit Setting
Default attributes
dependent on the motor’s
torque current component
Oscillation-suppression
F13.32 0-200 50 1 ○
coefficient of motor 2
F13.33 Reserved
F13.34 Reserved
Speed control
F13.35 proportional gain 1 of 0.1-200.0 20.0 0.1 ○
motor 2
Speed control integral
F13.36 0.00-10.00s 0.20s 0.01s ○
time 1 of motor 2
Speed control
F13.37 proportional gain 2 of 0.1-200.0 20.0 0.1 ○
motor 2
Speed control integral
F13.38 0.00-10.00s 0.20s 0.01s ○
time 2 of motor 2
Speed-loop PI
F13.39 switching frequency 1 0.00-50.00Hz 10.00Hz 0.01Hz ○
of motor 2
Speed-loop PI
F13.40 switching frequency 2 0.00-50.00Hz 15.00Hz 0.01Hz ○
of motor 2
Speed-loop integral 0.0-200.0% (motor rated
F13.41 180.0% 0.1% ○
limitation of motor 2 current)
0.00-1.00s
Speed-loop differential
F13.42 There is not the speed-loop 0.00s 0.01s ○
time of motor 2
differential when F13.42 = 0
0.000-1.000s
Speed-loop output filter
F13.43 When F13.43 = 0, the 0.020s 0.001s ○
time of motor 2
speed-loop filter is disabled
F13.44 Reserved
F13.45 Reserved
Motor torque limitation
0.0-200.0% (motor rated
F13.46 when motor 2 is 180.0% 0.1% ×
current)
forward
Motor torque limitation
0.0-200.0% (motor rated
F13.47 when motor 2 is 180.0% 0.1% × A
current)
reverse
Recreated torque
0.0-200.0% (motor rated
F13.48 limitation when motor 2 180.0% 0.1% ×
current)
is forward
Recreated torque
0.0-200.0% (motor rated
F13.49 limitation when motor 2 180.0% 0.1% ×
current)
is reverse
F13.50 Reserved
Factory Modified
No. Name Range Unit Setting
Default attributes
F13.51 Reserved
F13.52 Reserved
Group F14 Reserved (refer to pages 88-89)
Group F15 Digital I/O Terminal Parameters (refer to pages 89-102)
0: Reserved
1: Inverter enabled
2: FWD function
DI1 terminal function 3: REV function
F15.00 2 1 ×
selection 4: Three-wire operation
mode
5,6,7: Frequency source
selection 1, 2, 3
8: AI to be the frequency
source
9,10: Run command source
selection 1,2
11: Terminal control mode to
DI2 terminal function
F15.01 be the run command source 3 1 ×
selection
12: External stop command
input
13-16: Multi-step frequency
terminal 1-4
17: Frequency ramp (UP)
18: Frequency ramp (DN)
19: Clearing auxiliary
frequency setting
DI3 terminal function 20,21: Forward and reverse
F15.02 0 1 ×
selection jog 1 command control input
(JOGF1/ JOGR1)
22,23: Forward and reverse
jog 2 command control input
(JOGF2/ JOGR2)
24: Jog 1 command control
input
25: Jog 1 direction control
input (Remark: When select
DI4 terminal function 20 and 21, the functions 24
F15.03 0 1 ×
selection and 25 are invalid)
26: Acc./Dec. time selection
terminals 1
27: Acc./Dec. time selection
Factory Modified
No. Name Range Unit Setting
Default attributes
terminals 2
28: Acc./Dec. mode selection
29: Acc./Dec. prohibition
30: Switch to ordinary
DI5 terminal function running mode
F15.04 0 1 ×
selection
31: Reset the stop status of
PLC operation
32: Pausing the process PID
33: Disabling the process
PID
34: Holding PID integral
35: Clearing PID integral
36: Switch to wobble
DI6 terminal function operation
F15.05 0 1 ×
selection 37: Reset the wobble
operating status
38: DC braking start while
stopping
39: External pause signal
(normally-open input)
40: External pause signal
(normally-closed input)
DI7 terminal (option 41: Coast to stop
F15.06 terminal) function (normally-open input) 0 1 ×
selection 42: Coast to stop
(normally-closed input)
43: Emergency stop
44: External fault signal
(normally-open input)
45: External fault signal
(normally-closed input)
46: External reset (RST)
DI8 terminal (option
input
F15.07 terminal) function 0 1 ×
47: Switch between motor 1
selection
and motor 2
48: Timing function input
49: Clearing the length
50: Clearing the counter to
zero A
51: Counter’s triggering
signal input
52: Length counting input
DI9 terminal (option
(only DI6 terminal is enabled)
F15.08 terminal) function 0 1 ×
53: Pulse frequency input
selection
(only DI6 terminal is enabled)
54-84: Reserved
85: Pausing PLC operation
86: Terminal stop DC braking
Factory Modified
No. Name Range Unit Setting
Default attributes
F15.09 Reserved
F15.10 Reserved
F15.11 Reserved
Acc./Dec. rate of 0.01Hz
F15.12 0.00-99.99Hz/s 1.00Hz/s ×
UP/DN terminal /s
0: 2ms
Terminal detecting
F15.13 1: 4ms 0 1 ○
interval
2: 8ms
Terminal detecting filter
F15.14 0-10000 2 1 ○
number
Bit0-Bit8 is corresponding
to DI1-DI9
Bitx: DIy terminal input
positive and negative logic
Terminal input positive
0: Positive logic
F15.15 and negative logic 000 1 ○
1: Negative logic
setting
0: Reserved
1: Inverter ready
2: Inverter is running (RUN)
DO1 terminal function 3: Inverter is forward running
F15.18 2 1 ×
selection 4: Inverter is reverse running
5: Inverter is DC braking
6: Inverter is in
zero-frequency status
Factory Modified
No. Name Range Unit Setting
Default attributes
7: Inverter is in
zero-frequency running
8: Reserved
9,10: Frequency detection
DO2 terminal function
F15.19 threshold (FDT1,FDT2) 0 1 ×
selection
11: Frequency arriving signal
(FAR)
12: Limitation of upper limit of
frequency
13: Limitation of lower limit of
frequency
14: Limitation of upper/lower
limits of wobble frequency
RLY1 relay function 15: Simple PLC operating
F15.20 31 1 ×
selection status indication
16: Simple PLC pausing
indication
17: Simple PLC cycle
completion indication
18: Completion of simple
PLC operation stages
19: Completion of simple
RLY2 relay (extension
PLC operation
F15.21 relay) function 0 1 ×
selection 20: Output data from SCI
communication
21: Preset operating time out
22: Timing function output
23: Preset counting value
reach
24: Indicating counting value
reach
RLY3 relay (extension
25: Setting length arrive
F15.22 relay) function 0 1 ×
selection 26: Indication of motor 1 and
motor 2
27,28: Reserved
29: Undervoltage lock-up
signal (LU)
30: Overload signal (OL)
31: Inverter fault
A
32: External fault
RLY4 relay (extension 33: Inverter auto-reset fault
F15.23 relay) function 0 1 ×
34: Three-phase power
selection
supply forward input
35-37:Reserved
38: High-frequency output
(only DO2)
Output terminal Bit0-Bit2 is corresponding
F15.24 000 1 ○
positive and negative to DO1-DO2
Factory Modified
No. Name Range Unit Setting
Default attributes
logic selection Bit2-Bit5 is corresponding
to RLY1-RLY4
Bitx: DOy and RLYy
terminals output positive and
negative logic
0 means positive logic
1 means negative logic
Factory Modified
No. Name Range Unit Setting
Default attributes
Display panel with
0: Reserved
F16.00 potentiometer function 0 1 ×
selection 1: Upper limit frequency
setting source
Analogue input AI1 2: Frequency setting source
F16.01 2 1 ×
function selection 3: Auxiliary frequency
reference
Analogue input AI2 4: Process PID reference
F16.02 5 1 ×
function selection 5: Process PID feedback
6: Process PID regulating
Analogue input AI3 upper limit
F16.03 0 1 ×
function selection 7: Process PID regulating
lower limit
Analogue input AI4 8: Motor overheating signal
F16.04 0 1 ×
function selection input
Factory Modified
No. Name Range Unit Setting
Default attributes
0: Reserved
1: Output frequency (0-
max. output frequency)
2: Reference frquency (0-
max. output frequency)
AO1 terminal output 3: Motor speed (0-
F16.19 1 1 ○
function selection maximum output frequency
corresponding to speed)
4: Output current (0-twice
motor’s rated current)
5: Output current (0-twice
motor’s rated current)
6-9: Reserved
10: Output torque (0-3
times motor’s rated torque)
11: Output voltage (0-1.2
times inverter’s rated
AO2 terminal output voltage)
F16.20 0 1 ○
function selection 12: Bus voltage (0-2.2
times inverter’s rated
voltage)
13: Output power (0-twice
motor’s rated power)
14: AI1 input (0-10V)
15: AI2 input (-10-10V / 0-
20mA)
16: AI3 input (-10-10V / 0-
20mA)
17: AI4 input (-10-10V / 0-
High-speed pulse
20mA)
F16.21 output function 0 1 ○
18: Output frequency (- 1
selection
times-1 times maximum
output frequency)
19: Reference frequency (- 1
times-1 times maximum
output frequency)
Analogue output AO1
F16.22 -100.0-100.0% 0.0% 0.1% ○
bias
Analogue output AO1
F16.23 0.0-200.0% 100.0% 0.1% ○
gain
Analogue output AO2
F16.24 -100.0-100.0% 0.0% 0.1% ○
bias
Analogue output AO2
F16.25 0.0-200.0% 100.0% 0.1% ○
gain
DO2 maximum output
F16.26 0.1-50.0kHz 10.0kHz 0.1kHz ○
pulse frequency
Group F17 SCI Communication Parameters (refer to pages 106-107)
Factory Modified
No. Name Range Unit Setting
Default attributes
0: 1-8-2 format, no parity,
RTU
1: 1-8-1 format, even
parity,RTU
2: 1-8-1 format, odd parity,
RTU
F17.00 Data format 0 1 ×
3: 1-7-2 format, no parity,
ASCII
4: 1-7-1 format, even parity,
ASCII
5: 1-7-1 format, odd parity,
ASCII
0: 1200bps
1: 2400bps
2: 4800bps
3: 9600bps
F17.01 Baud rate selection 4: 19200bps 3 1 ×
5: 38400bps
6:57600bps
7:76800bps
8:115200bps
F17.02 Local address 0-247 2 1 ×
F17.03 Host PC response time 0-1000ms 0ms 1ms ×
0.0-1000.0s
Time threshold for
When F17.04 = 0, it will not
F17.04 detecting 0.0s 0.1s ×
detect communication time
communication status
out.
0.0-1000.0s
Detecting time at When F17.05 = 0, it will not
F17.05 0.0s 0.1s ×
communication error detect the communication
error.
Action selection at
F17.06 communication time 3 1 ×
out 0: Coast to stop
Action selection at 1: Emergency stop
F17.07 3 1 ×
communication fault 2: Decelerate to stop
Action selection at 3: Continue to run
F17.08 communication 1 1 × A
peripheral device fault
0: Communication write
Communication write function parameter without
function parameter of storage EEPROM.
F17.09 1 1 ×
storage EEPROM 1: Communication write
method selection function parameter with
storage EEPROM.
Group F18 Display Control Parameters (refer to pages 107-109)
Factory Modified
No. Name Range Unit Setting
Default attributes
0: Chinese
F18.00 Language selection 0 1 ○
1: English
Displaying contrast of
F18.01 1-10 5 1 ○
the LCD display panel
0: Reserved
Set the display 1: Inverter’s rated current
F18.02 parameter 1 during 2: Inverter’s extension 8 1 ○
operation function
3: Inverter status
4: Master setting frequency
Set the display source
F18.03 parameter 2 during 5: Master setting frequency 7 1 ○
operation 6: Auxiliary setting frequency
7: Setting frequency
8: Reference frequency (after
acceleration/ deceleration)
Set the display
9: Output frequency
F18.04 parameter 3 during 9 1 ○
10: Setting speed
operation
11: Running speed
12: Three-phase power
supply input phase sequence
Set the display 13: Output voltage
F18.05 parameter 4 during 14: Output current 13 1 ○
operation 15: Reserved
16: Output torque
17: Output power
Set the display 18: DC bus voltage
F18.06 parameter 5 during 19: Potentiometer input 14 1 ○
operation voltage
20: AI1 input voltage
21: AI1 input voltage (after
disposal)
Set the display
22: AI2 input voltage
F18.07 parameter 6 during 18 1 ○
23: AI2 input voltage (after
operation
disposal)
24: AI3 input voltage
25: AI3 input voltage (after
disposal)
Set the display
F18.08 26: AI4 input voltage 7 1 ○
parameter 1 at stop
27: AI4 input voltage (after
disposal)
28: DI6 terminal pulse input
frequency
Set the display 29: AO1 output
F18.09 18 1 ○
parameter 2 at stop
30: AO2 output
31: High-speed output pulse
Factory Modified
No. Name Range Unit Setting
Default attributes
frequency
32: Heatsink temperature
Set the display 33: Set the line speed
F18.10 20 1 ○
parameter 3 at stop
34: Reference line speed
35-36: Reserved
37: Process PID reference
38: Process PID feedback
Set the display 39: Process PID error
F18.11 22 1 ○
parameter 4 at stop 40: Process PID integral
value
41: Process PID output
42: External couting value
Set the display 43: Input terminal status
F18.12 44: Output terminal status 43 1 ○
parameter 5 at stop
45: MODBUS
communication status
46: Actual length
47: Total length
Set the display 48: Total time at power on
F18.13 44 1 ○
parameter 6 at stop (hour)
49: Total time at running
(hour)
F18.14 Reserved
Factory Modified
No. Name Range Unit Setting
Default attributes
0: Master setting + auxiliary
setting
1: Master setting – auxiliary
setting
2: MAX (master setting,
auxiliary setting)
Master/Auxiliary setting 3: MIN (master setting,
F19.01 0 1 ○
calculation auxiliary setting)
4: Master setting + auxiliary
setting × master setting /
max. value of master setting
5: Master setting – auxiliary
setting × master setting /
max. value of master setting
Analogue auxiliary
F19.02 0.00-9.99 1.00 0.01 ○
setting coefficient
Initial value of digital
F19.03 0.00-F00.06 0.00Hz 0.01Hz ○
auxiliary frequency
Units: Save selection at
power outage (Only when
F19.00 = 1 or 2 will F19.04
be enabled)
0: Not save auxiliary
frequency at power outage
1: The auxiliary frequency
will be saved to F19.03 at
power outage
Control selection of
F19.04 digital auxiliary 00 1 ○
Tens: Frequency disposal
frequency
when the inverter stops (Only
when F19.00 = 1 or 2 will
F19.04 be enabled)
0: Maintain the auxiliary
frequency when the inverter
stops
1: The auxiliary frequency
clears to zero when the
inverter stops
0: No adjustment
1: To adjust as per the max.
Adjustment selection of
F19.05 output frequency 1 1 ○
setting frequency
2: To adjust as per the
current frequency
Adjustment coefficient
F19.06 0.0-200.0% 100.0% 0.1% ○
of setting frequency
0: Auto stop mode
Control selection of
F19.07 1: Immediate stop mode 0 1 ○
cooling fan
2: The fan runs continuously
Factory Modified
No. Name Range Unit Setting
Default attributes
when power on
Factory Modified
No. Name Range Unit Setting
Default attributes
and in constant speed
running proces
Auto current limiting G:150.0%
F19.21 20.0-200.0% 0.1% ×
threshold P:110.0%
15kW and
below:
10.0s
0.0-6000.0s 18.5-55
Deceleration time at
F19.22 0.00: Limit current without kW inverter: 0.1s ×
auto current limiting
deceleration. 30.0s
75kW and
above:
60.0s
Enabled mode of 0: Rise edge enabled mode
F19.23 0 1 ○
terminal run command 1: Level enabled mode
220V inverter: 330-400V 380V
Action voltage of
F19.24 380V inverter: 630-750V 720V 1V ×
braking unit
660V inverter: 850-1200 1130V
F19.25 Reserved
F19.26 Preset length 0-65535m 0m 1m ×
F19.27 Actual length 0-65535m 0m 1m *
F19.28 Length ratio 0.001-30.000 1.000 0.001 ×
Length checking
F19.29 0.001-1.000 1.000 0.001 ×
coefficient
Measuring shaft
F19.30 1.00-100.00cm 10.00cm 0.01cm ×
diameter
Number of pulses per
F19.31 1-9999 1 1 ×
revolution
Length arrive and
0: Output level signal
F19.32 output function 0 1 ○
1: Output 500ms pulse
selection
Record of length
0: Auto-clear
F19.33 disposal after length 0 1 ○
1: No change
arrive
Record of length 0: Auto-clear
F19.34 0 1 ○
disposal at stop 1: No change
F19.35 Reserved
F19.36 Reserved
F19.37 Reserved
F19.38 Reserved
Group F20 Protection of Fault Parameters (refer to pages 116-119)
Units: Overload pre-alarm
Overload pre-alarm
F20.00 detection 00000 1 ×
detection
0: It is active all the time in
Factory Modified
No. Name Range Unit Setting
Default attributes
running status
1: It is active only at constant
speed
Hundreds: Overload
threshold selection
0: Ratio of load current to the
motor’s rated current (alarm:
motor overload)
1: Ratio of load current to the
inverter’s rated current
(alarm: inverter overload)
Factory Modified
No. Name Range Unit Setting
Default attributes
3: It is detecting all the time
in running process, and then
cut off the output after
detecting (fault)
4: It is detectes only at the
same speed, and then cut off
the output after detecting
(fault)
Inverter output
F20.04 load-loss detection 0-100% 30% 1% ×
threshold
Inverter output
F20.05 load-loss detection 0.00-20.00s 1.00s 0.01s ×
time
0: Does not detect the motor
overheating.
Motor overheating 1: Positive charateristic
F20.06 0 1 ×
signal input type (PTC)
2: Negative charateristic
(NTC)
Thermistor value at
F20.07 0.0-10.0kΩ 5.0kΩ 0.1kΩ ×
motor overheating
Input phase loss
F20.08 0-50% 30% 1% ×
detection reference
Input phase loss
F20.09 1.00-5.00s 1.00s 0.01s ×
detection time
Output phase loss
F20.10 0-50% 20% 1% ×
detection reference
Output phase loss
F20.11 0.00-20.00s 3.00s 0.01s ×
detection time
0-100%
PID reference lose
F20.12 0: Does not detect PID 0% 1% ×
detected value
reference lose
0.00-10.00s
PID reference loss
F20.13 When set to 0, does not 0.20s 0.01s ×
detection time
detect PID reference loss
0-100%
PID feedback loss
F20.14 0: Does not detect PID 0% 1% ×
detected value
feedback loss
0.00-10.00s
PID feedback loss
F20.15 When set to 0, does not 0.20s 0.01s ×
detection time
detect PID feedback loss
Detection value at PID 0-100%
F20.16 feedback out of the 100%: Does not detect PID 100% 1% ×
limit feedback out of the limit
F20.17 Detection time at PID 0.00-10.00s 0.20s 0.01s ×
Factory Modified
No. Name Range Unit Setting
Default attributes
feedback out of the When set to 0, does not
limit detect PID feedback out of
the limit
0-100
F20.18 Auto reset times 0 1 ×
0: No auto reset function
0.1s/
F20.19 Auto reset interval 2.0-20.0s/times 5.0s/ times ×
times
Units: In auto reset process
0: Faulted relay doesn’t act
1: Faulted relay acts
Faulted relay action
F20.20 00 1 ○
selection Tens: In the undervoltage
process
0: Faulted relay doesn’t act
1: Faulted relay acts
0: No fault history
E0001: Acc. overcurrent
E0002: Dec. overcurrent
E0003: Costant overcurrent
E0004: Acc. overvoltage
E0005: Dec. overvoltage
E0006: Constant overvoltage
E0007: Stall overvoltage
E0008: Fault of power
module
E0009: Heatsink overheat
E0010: Fault of braking unit
E0011: CPUfault
E0012: Parameters
auto-tuning fault
Type of fifth latest (the E0013: Contactor is not
F20.21 0 1 *
last) fault actuated
E0014: Fault of current
detection circuit
E0015: Fault of input phase
E0016: Fault of output phase
E0017: Inverter overload
E0018: Inverter output is A
unloaded
E0019: Motor overload
E0020: Motor overheat
E0021: Access fault of
Control board EEPROM
E0022: Access fault of
display panel EEPROM (only
displaying without any
protection)
Factory Modified
No. Name Range Unit Setting
Default attributes
E0023: Fault setting of
parameters
E0024: Fault of external
equipment
E0025: PID reference loss
E0026: PID feedback loss
E0027: PID feedback out of
limiting
E0028: SCI communication
time-out
E0029: SCI communication
error
Setting frequency at
F20.22 0.00-400.00Hz 0Hz 0.01Hz *
the last fault
Running frequency at
F20.23 0.00-400.00Hz 0Hz 0.1Hz *
the last fault
Bus voltage at the last
F20.24 0-999V 0V 1V *
fault
Output voltage at the
F20.25 0-999V 0V 1V *
last fault
Output current at the 7.5kW or above: actual value 0.0A 0.1A
F20.26 *
last fault 5.5kW or below: actual value 0.00A 0.01A
Input terminal status at
F20.27 0-0x1FF 0 1 *
the last fault
Output terminal status
F20.28 0-0x7FF 0 1 *
at the last fault
Interval of fifth latest
F20.29 0-6553.5 hours 0.0 0.1h *
fault
Type of fourth latest
F20.30 0-99 0 1 *
fault
Interval of fourth latest
F20.31 0-6553.5 hours 0.0 0.1h *
fault
F20.32 Type of third latest fault 0-99 0 1 *
Interval of third latest
F20.33 0-6553.5 hours 0.0 0.1h *
fault
Type of second latest
F20.34 0-99 0 1 *
fault
Interval of second
F20.35 0-6553.5 hours 0.0 0.1h *
latest fault
F20.36 Type of first latest fault 0-99 0 1 *
Interval of first latest
F20.37 0-6553.5 hours 0.0 0.1h *
fault
Group F21 Reserved
Group F22 Reserved
Group F23 PWM Control Parameters (refer to pages 120-120)
Factory Modified
No. Name Range Unit Setting
Default attributes
Dependent
Set the carrier
F23.00 1-16kHz on inverter 1kHz ×
frequency
model
F23.01 Reserved
0: Disabled
F23.02 PWM overshoot enable 1 1 ×
1: Enabled
0: Two-phase modulation or
three-phase modulation
F23.03 PWM modulation mode 0 1 ×
1: Three-phase modulation
2: Two-phase modulation
Group U User Menu Mode Display Parameters (refer to parameters 120-122)
User menu map of
U00.00 00.01 0.01 ○
setting 1
User menu map of
U00.02 00.06 0.01 ○
setting 2
User menu map of
U00.04 00.08 0.01 ○
setting 3
User menu map of
U00.06 00.13 0.01 ○
setting 4
User menu map of
U00.08 00.10 0.01 ○
setting 5
User menu map of
U00.10 00.11 0.01 ○
setting 6
User menu map of
U00.12 02.13 0.01 ○
setting 7
User menu map of
U00.14 00.00-23.02,99.99 03.01 0.01 ○
setting 8
99.99 is corresponding to no
User menu map of
U00.16 parameter mapping function 03.02 0.01 ○
setting 9
User menu map of
U00.18 08.00 0.01 ○
setting 10
User menu map of
U00.20 08.01 0.01 ○
setting 11
User menu map of
U00.22 08.02 0.01 ○
setting 12
User menu map of
U00.24 08.03 0.01 ○ A
setting 13
User menu map of
U00.26 08.04 0.01 ○
setting 14
User menu map of
U00.28 ― 0.01 ○
setting 15
User menu map of
U00.30 ― 0.01 ○
setting 16
The setting value of
U00.01 ― ― ―
map 1
Factory Modified
No. Name Range Unit Setting
Default attributes
The setting value of
U00.03 ― ―
map 2
The setting value of
U00.05 ― ―
map 3
The setting value of
U00.07 ― ―
map 4
The setting value of
U00.09 ― ―
map 5
The setting value of
U00.11 ― ―
map 6
The setting value of
U00.13 ― ―
map 7
The setting value of
U00.15 ― ―
map 8
The setting value of
U00.17 ― ―
map 9
The setting value of
U00.19 ― ―
map 10
The setting value of
U00.21 ― ―
map 11
The setting value of
U00.23 ― ―
map 12
The setting value of
U00.25 ― ―
map 13
The setting value of
U00.27 ― ―
map 14
The setting value of
U00.29 ― ―
map 15
The setting value of
U00.31 ― ―
map 16
2. Interfaces
1) Interface mode and pin definition
Pin 1 2 3 4 5 6 7 8
1 8
RJ45 terminal Signal +5V 485+ +5V GND GND GND 485- Reserved
3. Network Mode
Frame head (at least Slave Function Frame tail (at least
3.5 character spacing) address parameter Data Checking 3.5 character spacing)
ASCII mode
Modbus data frame
MODBUS adopts “Big Endian” encoding mode, higher byte prior to lower byte at sending.
1) RTU mode
In the RTU mode, the idle time of frame head and frame tail passing bus should be not less than
3.5 bytes, and data checking relies on CRC-16. The whole information need be checked. The
concrete CRC checking is referred to the page 194.
Take RTU data for example: To read internal register F00.08 of No. 1 inverter:
The command frame:
2) ASCII mode
In ASCII mode, the frame head is “0x3A”, while the frame tail default is “0x0D”“0x0A” and the
frame tail can be set by the users. In ASCII mode, all the data bytes will be sent via ASCII code
except frame head and frame tail, higher 4-byte prior to lower 4-byte at sending. In ASCII mode,
data is 7-byte and for the “A”-“F” will adopt their uppercase of the ASCII code. The data adopts
LRC checking, covering the slave address and data. Checksum is the character of data that is
involved in checking and the complement code of carry bit.
Take ASCII data for example: To write 4000 (0x0FA0) to the internal register F00.08 of Slave 1.
LRC checking = the complement code of (0x01+0x41+0x00+0x08+0x0F+0xA0) =0x07
6. Protocol Function
1) Supported function
MODBUS protocol supports the below parameter operation:
Function code Instructions
0x03 To read the inverter’s function parameters and parameters in operating status
To rewrite function parameter (whether can be saved by F17.09 at power off) or control
0x06
parameter of single inverter
0x08 Circuit diagnosis
To rewrite function parameter (cannot be saved at power off) or control parameter of
0x41
single inverter
0x42 Function parameters management
To rewrite function parameter (whether can be saved by F17.09 at power off) or control
0x10
parameter of certain inverters
To rewrite function parameter (can be saved at power off) or control parameter of
0x43
certain inverters
If the operation command fails, the response is fault code. For instance, continuously read 13
function codes from F00.00 then the return frame will be as follows:
Address Parameter Error code Checksum
0x01 0x83 0x03 0x01 0x31
The fault code is the same as (function parameter+0x80), and its instruction is as follows:
2) The command and response frame of MODBUS protocol parameter (in RTU mode)
① To read inverter parameters (function code 0x03)
Protocol data unit Length of data (byte) Range
Address 1 0-247, 0 is broadcast address
Function code 1 0x03
Command frame Starting register address 2 0x0000-0xFFFF
No. of register 2 0x0001-0x000C
CRC/LRC checking 2/1
Address 1 1-247
Function code 1 0x03
Response frame Read byte no. 1 2* no. of registers
Register content 2* no. of registers
CRC/LRC checking 2/1
② To rewrite function parameter (whether can be saved by F17.09 at power off) or control
parameter (function code 0x06) of single inverter (function code 0x06)
③ To rewrite function parameter (cannot be saved at power off) or control parameter of single
inverter (function code 0x41)
Protocol data unit Length of data (byte) Range
Address 1 0-247, 0 is broadcast address
Function code 1 0x06. 0x41
Command frame Register address 2 0x0000-0xFFFF
Register content 2 0x0000-0xFFFF
CRC/LRC checking 2/1
Address 1 1-247
Function code 1 0x06. 0x41
Response frame Register address 1 0x0000-0xFFFF
Register content 2 0x0000-0xFFFF
CRC/LRC checking 2/1
⑤ To rewrite function parameter (whether can be saved by F17.09 at power off) or control
parameter of certain inverters (function code 0x10)
This command rewrites the contents of continuous data unit from starting register address where
is mapped as inverter’s function parameter and control parameter etc. The inverter will start to
save from low address to high address of the register when it continuously saves many register
parameters. The saving operation will return from the first faulty address if it isn’t completely
success.
⑥ Function parameters management (function code 0x42)
The inverter function parameters management includes reading the upper/lower limit of
parameters, to read parameter characteristics, to read the biggest intergroup index of function
parameters, to read the previous and next function parameter group number, to read index of the
parameter being displayed and to display next status parameter. The parameter characteristics
include read-write ability, parameter units and scaling. These commands are used to adjust
remotely inverter parameters.
The command and response frames of the function parameters management are as follows:
Protocol data unit Length of data (byte) Range
0-247, 0 is broadcast
Address 1
address
Function code 1 0x42
Command frame
Subfunction code 2 0x0000-0x0008
Data 2 Depends on inverter model
CRC /LRC checking 2/1
Address 1 1-247
Function code 1 0x42
Response frame Subfunction code 2 0x0000-0x0008
Data 2 0x0000-0xFFFF
CRC /LRC checking 2/1
Their intergroup indexes are mapped as the lower bytes. Please refer to the instruction manual
for more details on function parameters F00-F23, P00-P05 and U00.
The users can realize the inverter’s starting, stopping and running speed setting through the
control parameter, and obtain the inverter’s running frequency, output current, etc. through
indexing the inverter’s status parameters.
1) Control parameters
The inverter’s control parameter intergroup indexes are as follows:
Register address Parameter name Retained or not at power loss
0x3200 Control command character No
0x3201 Running frequency setting No
0x3202 Auxiliary running frequency setting No
0x3203 Reserved
0x3204 Virtual terminal control setting No
2) Status parameter
Inverter status parameter intergroup index is as following table:
For instance: The register address of function parameter F03.02 is 0x0302, and that of function
parameter F16.01 is 0x1001.
It takes a comparatively long time to online calculate the CRC checksum of each byte, but it will
save program space. Code of online calculating CRC is shown below:
unsigned int crc_check(unsigned char *data,unsigned char length)
{
int i;
unsigned crc_result=0xffff;
while(length--)
{
crc_result^=*data++;
for(i=0;i<8;i++)
{
if(crc_result&0x01)
crc_result=(crc_result>>1)^0xa001;
else
crc_result=crc_result>>1;
}
}
return (crc_result=((crc_result&0xff)<<8)|(crc_result>>8));
}
4. When the frequency setting source F00.10 = 2, set the frequency value to 45.00Hz by writing
the register address 0x3201.
11. Functional parameter management and read the lower limit of F02.03
Address Code Subfunction code Data Checksum
0x02 0x42 0x00 0x01 0x02 0x03 0x69 0x57
Unit:
Clinet info
Add. Of unit:
Tel.: Fax:
Product info
Power: Model:
Service unit:
Maintenance date:
1. The warranty period of the product is 18 months (refer to the barcode on the product
body). During the warranty period, if the product fails or it is damaged under condition
of normal use by following the user’s manual, our company will be responsible for free
maintenance.
2. The starting time of the warranty period is manufacturing date (see the barcode on the
product body), but we could negotiate settlement under special condition.
3. Within warranty period, maintenance will be charged for damages caused by the
following reasons:
A. The damage is caused by improper use or repair/modification without prior
permission;
B. The damage is caused by abnormal voltage, fire, flood, other disasters and
second disasters;
C. The damage is caused by dropped or transportation after purchase;
D. The damage is caused by the operation not following this user’s manual;
E. The damage or failure is caused by the trouble out of the equipment (e.g. external
device).
4. If there is any failure or damage to the product, please correctly fill out the Product
Warranty Card in detail.
5. The maintenance fees are charged according to the newly adjusted Maintenance Price
List by our company.
6. In general, the warranty card will not be reissued. Please keep the card and present it
to the maintenance personnel when asking for maintenance.
7. If there is any problem during the service, please contact the agent of our company or
our company directly.
8. This agreement should be interpreted by Shenzhen Hpmont Technology Co., Ltd.