Hey, in this article we are going to see the Connection Diagram of a single-phase analog ammeter with a
Selector Switch and CTs(Current Transformer) for three-phase current measurement. This type of connection
you will see in different types of electrical panels such as power control panels, motor control panels, etc.
Ammeter is basically a measuring device that is used to measure the electrical current. A single-phase two-
terminal ammeter can be used to measure current flow in a single-phase power system. But by connecting
some additional equipment such as a selector switch and CTs we can measure current flow in three phase
system also. So, here we will see the whole wiring diagram for current measurement in a three-phase system.
Ammeter Connection Diagram with Selector Switch and CT POPULAR ARTICLES
Residual Current Circuit Break
Working, Function, Use
Here, you can see the connection diagram between Ammeter, Selector Switch, and Current Transformers(CTs)
for current measurement in a three-phase system. Fog Light Wiring and Connecti
Diagram with Relay and Switch
How Auto ON/OFF sensor light
Electrical Wiring Diagram and
Circuit Diagram Difference
Open Circuit VS Closed Circuit
Characteristics
Can a step-up transformer be u
amplifier?
Bulb Wiring in Series and Para
Connection
Light Switch Wiring Procedure
Connection, Diagram, Control
Half Adder and Full Adder Circ
Diagram, Truth Table
What is Transition or Contact
Resistance? Example
How to do Wiring Lights in Par
Connection? Procedure, Diagra
Electrical Power Socket Conne
Diagram and Wiring Procedure
In this arrangement, you can see the current flow in each phase by rotating the selector switch. When you
kept the selector switch in the 'O' position the ammeter will not show any current flow as it is in off condition.
When you rotate the switch in the 'R' position the ammeter will show the value of the current flow through
the R phase. When you rotate the switch in the 'Y' position the ammeter will show the value of current flow
through the B phase. Similarly, when you rotate the switch in the 'B' position the ammeter will show the value
of current flow through the B phase.
Connection Procedure
1. First of all, you have to take all the equipment with proper rating. Especially, the current ratio of the CTs
and Ammeter must be the same.
2. Now place all the CTs with phase wires between the power circuit and the load circuit and mark the CTs
as 1,2, and 3 for R, Y, and B phases respectively.
3. Now connect the phase or positive(anything identified) terminal of the CT1 to the 'R' or 'L1" terminal of
the Selector Switch.
4. Connect the phase or positive(anything identified) terminal of the CT2 to the 'Y' or 'L2" terminal of the
Selector Switch.
5. Similarly, connect the phase or positive(anything identified) terminal of the CT3 to the 'B' or 'L3"
terminal of the Selector Switch.
6. Now connect the neutral terminal of all the CTs together and connect to the 'C' or 'N' terminal of the
Selector Switch.
7. Now connect the output terminals of the selector switch(here A1, A2) to the two terminals of the
ammeter.
8. After completing all the connections you can turn on the power and operate the selector switch to
measure the current.
Understanding CT and Ammeter Current Ratio
For example, if the current ratio of the CT is 100:5. The current flow in the secondary winding(or output
terminals) of the CT will be 5A when the actual current flow in the system is 100A. Now, your ammeter should
have a current ratio of 5:100. So when the ammeter senses the current 5A it will show 100A on the display. If
you take different current ratio for CT and Ammeter, then you have to do more complex calculations for
measuring the proper current flow.
Read Also:
Wattmeter Connection Diagram and Wiring Explained
Do Easily 3 Phase Energy Meter Connection.
Digital Voltmeter Wiring Diagram and Connection Procedure
Digital Ammeter Wiring Diagram and Connection with CT
Voltmeter and Selector Switch Connection for Three (3) Phase Supply
Thank you for visiting the Website. Keep visiting for more Updates.
Remember that Electrical is very Dangerous. And all information provided in this blog is for general knowledge
only. So before executing or doing any electrical related work please verify and gather authorization.
Share this Article: Whatsapp Facebook Twitter Pinterest Linkedin
Previous Next
Digital Voltmeter Wiring Diagram and Connection Digital Wattmeter Connection Diagram and Wiring
Procedure Procedure
RESOURCES POPULAR CATEGORIES CONNECT WITH US
Electrical Engineering Interesting Question and Electrical Connection Wiring Diagram Find Us on Google News
Answers
About Us
Electronics Engineering Interesting Question and Electrical Protection Generators & Motors
Contact Us
Answers
Block Diagram Digital Electronics Facebook Page
Engineering Image, photos, illustration for
Commercial Use Follow Us on Instagram
Computer Pin Diagram Symbols
ETechnoG Photo Gallary & Image Use policy Report Violation
Download our EBook Now Circuit Diagram ICs Power Electronics Disclaimer
Learn Everything with Diagram Advertise with Us
Electrical Installation Difference
Online Electrical & Electronic Calculators
Telecommunication Battery Power Factor
Download Free PDFs
Electrical Faults Logic Gates Power Supply
Sensor CarElectrical Sound System
HVAC System Industrial Knowledge Safety
Appliances Automation Electronics Project
Formula Fire Alarm System BoatElectrical
Full Form Robotics
© 2018-2023 ETechnoG